NORD BU0050 User Manual

Page 1
SK TU1-DEV SK TU2-DEV SK TU3-DEV
GB
BU 0050
Page 2
NORD USS and Modbus RTU Manual Safety information
N O R D Frequency inverters
Safety and operating instructions for
drive power converters
(as per: Low Voltage Directive 2006/95/EEC )
1. General During operation, drive power converters may, depending on their
protection class, have live, bare, moving or rotating parts or hot surfaces.
Unauthorised removal of covers, improper use, incorrect installation or operation causes a risk of serious personal injury or material damage.
Further information can be found in this documentation. All transportation, installation, initialisation and maintenance work
must be carried out by qualified personnel (compliant with IEC 364, CENELEC HD 384, DIN VDE 0100, IEC 664 or DIN VDE 0110, and national accident prevention regulations).
For the purposes of these basic safety instructions, qualified personnel are persons who are familiar with the assembly, installation, commissioning and operation of this product and who have the relevant qualifications for their work.
2. Proper use in Europe
Drive power converters are components intended for installation in electrical systems or machines.
When installed in machines, the drive power converter cannot be commissioned (i.e. commencement of the proper use) until it has been ensured that the machine meets the provisions of the EC Directive 2006/42/EEC (Machine Directive); EN 60204 must also be complied with.
Commissioning (i.e. implementation of the proper use) is only permitted if the EMC Directive (2004/108/EEC) is complied with.
Drive power converters with the CE mark meet the requirements of the Low Voltage Directive 2006/95/EEC. The harmonized standards stated in the Declaration of Conformity are used for the drive power converters.
Technical data and information for connection conditions can be found on the name plate and in the documentation, and must be complied with.
The drive power converters may only be used for the safety functions which are described and for which they have been explicitly approved.
3. Transport, storage
Information regarding transport, storage and correct handling must be complied with.
4. Installation
The installation and cooling of the equipment must be implemented according to the regulations in the corresponding documentation.
The drive power converters must be protected against impermissible loads. Especially during transport and handling, components must not be deformed and/or insulation distances must not be changed. Touching of electronic components and contacts must be avoided.
Drive power converters have electrostatically sensitive components, which can be easily damaged by incorrect handling. Electrical components must not be mechanically damaged or destroyed (this may cause a health hazard!).
5. Electrical connections
When working on live drive power converters, the applicable national accident prevention regulations must be complied with (e.g. VBG A3, formerly VBG 4).
The electrical installation must be implemented according to the applicable regulations (e.g. cable cross-section, fuses, ground lead connections). Further information is contained in the documentation.
Information about EMC-compliant installation – such as shielding, earthing, location of filters and installation of cables can be found in the drive power converter documentation. These instructions must be complied with even with CE marked drive power converters. Compliance with the limiting values specified in the EMC regulations is the responsibility of the manufacturer of the system or machine.
6. Operation
Where necessary, systems where drive power converters are installed must be equipped with additional monitoring and protective equipment according to the applicable safety requirements, e.g. legislation concerning technical equipment, accident prevention regulations, etc.
The parameterisation and configuration of the drive power converter must be selected so that no hazards can occur.
All covers must be kept closed during operation.
7. Maintenance and repairs
After the drive power converter is disconnected from the power supply, live equipment components and power connections should not be touched immediately, because of possible charged capacitors. Observe the relevant information signs located on the drive power converter.
Further information can be found in this documentation.
These safety instructions must be kept in a safe place!
2 Subject to technical amendments BU 0050 GB-3111
Page 3
NORD USS and Modbus RTU Manual Concerning this document
Designation of previous issues
Software Version
Comments
BU 0500 GB, December 2004 Part No. 607 0502 / 5204
Latest version
BU 0050 GB, August 2011 Part No. 607 0502 / 3111
Deletion of option "DevicenNet mc" for FI series
"vector mc"
Inclusion of SK 500E series frequency inverters  Implementation of Modbus RTU (for SK 500E)
NOTE
This supplementary operating manual is only valid in conjunction with the operating manual supplied for the respective frequency inverter.
Documentation
Designation: BU 0050 GB Part No.: 607 05 01 Device series: USS for SK 300E, SK 500E (entire series), SK 700E, SK 750E Modbus RTU for SK 540E and SK 545E
Version list
Publisher
Getriebebau NORD GmbH & Co. KG
Rudolf-Diesel-Str. 1 D-22941 Bargteheide http://www.nord.com/ Tel.: +49 (0) 45 32 / 401-0 Fax +49 (0) 45 32 / 401-555
BU 0050 GB-3111 Subject to technical amendments 3
Page 4
NORD DeviceNet Manual Concerning this document
Intended use of the frequency inverter
Compliance with the operating instructions is necessary for fault-free operation and the
acceptance of any warranty claims. These operating instructions must be read before working with the device!
These operating instructions contain important information about servicing. They must therefore be kept close to the device.
The described optional modules can only be used for the specifically defined frequency inverter series, use across series is only possible with the SK TU2-… module with SK 300E and SK 750E. The use of these modules with other devices is not permitted and can lead to their destruction.
The described optional modules and the corresponding frequency inverters are devices for stationary installation in control cabinets or decentralised structures. All details regarding technical data and permissible conditions at the installation site must be complied with.
Commissioning (commencement of the intended use) is not permitted until it has been ensured that the machine complies with the EMC Directive 204/108/EEC and that the conformity of the end product meets the Machinery Directive 2006/42/EEC (observe EN 60204).
Getriebebau NORD GmbH & Co. KG, 2011
4 Subject to technical amendments BU 0050 GB-3111
Page 5
Contents
FOREWORD ................................................................................................................................ 7
1 USS ........................................................................................................................................... 7
1.1 General information .............................................................................................. 7
1.1.1 The USS Protocol ..................................................................................................... 7
1.1.2 Features .................................................................................................................... 7
1.1.3 Delivery ..................................................................................................................... 7
1.1.4 Scope of supply ......................................................................................................... 8
1.1.5 Certifications ............................................................................................................. 8
1.1.6 Identification System ................................................................................................. 8
1.2 Modules ................................................................................................................ 9
1.2.1 SK 500E .................................................................................................................... 9
1.2.2 SK 700E .................................................................................................................. 12
1.2.3 SK 300E .................................................................................................................. 18
1.3 USS Protocol Specification ................................................................................ 19
1.3.1 General information................................................................................................. 19
1.3.2 Telegram Structure ................................................................................................. 19
1.3.3 Data Coding ............................................................................................................ 20
1.3.4 Character Frame ..................................................................................................... 20
1.3.5 Transfer Procedure ................................................................................................. 21
1.3.6 Start Pause Time .................................................................................................... 21
1.3.7 Response Delay Time ............................................................................................. 22
1.4 Bus Configuration ............................................................................................... 23
1.4.1 General information................................................................................................. 23
1.4.2 Topology ................................................................................................................. 23
1.4.3 Transfer Method ...................................................................................................... 23
1.4.4 Installation of the Bus System ................................................................................. 24
1.5 Data transmission ............................................................................................... 26
1.5.1 Structure of reference data ..................................................................................... 26
1.5.2 PPO types ................................................................................................ ............... 27
1.5.3 Process data (PZD)................................................................................................. 29
1.5.4 Parameter range (PKW) .......................................................................................... 39
1.6 Telegram examples ............................................................................................ 43
1.6.1 The Macro Generator .............................................................................................. 43
1.6.2 Switch-on block Standby .................................................................................... 44
1.6.3 Enable with 50% setpoint ........................................................................................ 46
1.6.4 Writing a parameter................................................................................................. 47
1.6.5 Reading the acceleration time parameter ............................................................... 48
1.7 Master Telegram Times ..................................................................................... 49
1.8 Frequency Inverter Settings ............................................................................... 50
1.8.1 Frequency inverter bus parameters ........................................................................ 50
2 MODBUS RTU ........................................................................................................................ 61
2.1 The bus system .................................................................................................. 61
2.2 Features ............................................................................................................. 61
2.3 Telegram Structure ............................................................................................. 62
2.4 RTU Frames ....................................................................................................... 62
2.5 Function Codes .................................................................................................. 62
2.5.1 01h Read Coil ......................................................................................................... 63
2.5.2 05h Write Single Coils ............................................................................................. 63
2.5.3 0Fh Write Multiple Coils .......................................................................................... 64
2.5.4 03h Read Holding Register ..................................................................................... 65
2.5.5 06h Write Single Register ....................................................................................... 66
2.5.6 10h Write Multiple Register ..................................................................................... 66
2.6 Exception Responses ......................................................................................... 68
2.7 Watchdog ........................................................................................................... 68
2.8 Description of parameters .................................................................................. 69
BU 0050 GB-3111 Subject to technical amendments 5
Page 6
NORD USS and Modbus RTU Manual
3 FAULTS .................................................................................................................................. 71
3.1 Troubleshooting ................................................................................................. 71
3.1.1 Error display............................................................................................................ 71
3.1.2 Error memory .......................................................................................................... 71
3.2 Error messages ................................................................................................. 72
4 ADDITIONAL INFORMATION ............................................................................................... 73
4.1 Maintenance and servicing information ............................................................. 73
4.2 Abbreviations in this manual .............................................................................. 73
5 KEYWORD INDEX ................................................................................................................. 74
6 Subject to technical amendments BU 0050 GB-3111
Page 7
1.1 USS - General information
Foreword
This supplementary documentation is valid for the SK 300E, SK 500E, SK 700E series and for the SK 750E. It describes the setup of communication via RS485.
For this, the main emphasis is on communication according to the USS protocol. Corresponding optional modules are available for the SK 700E and SK 750E series. The SK 300E and SK 500E series have an appropriate interface integrated as standard.
In addition, the requirements of Modbus communication (SK 540E and higher) will be considered.
1 USS
1.1 General information
1.1.1 The USS Protocol
With the aid of the USS protocol, a user can set up a serial bus coupling between a higher level Master and several slave systems. Master systems can for example be memory programmable control units (SPS) or PCs.
The USS protocol allows the user to implement automation tasks with conveying according to time-cycled telegram traffic (fixed telegram length required), as well as visualisation tasks.
The USS protocol is a simple, serial transfer protocol defined by Siemens, which if fully tailored to the needs of drive technology.
1.1.2 Features
Support of a multiple point coupling, e.g. EIA RS 485 hardware or a point-to-point coupling, e.g. EIA RS 232.
Master / Slave access procedure  Single Master System  Maximum 32 participants (maximum 31 slaves)  Simple, secure telegram framework  Same physical bus design as PROFIBUS (DIN 19245 Part 1)  The data interface to the basic device is according to the PROFILE for variable speed drives.
This means that with USS, the information to the drive unit is transferred in the same way as with the PROFIBUS-DP.
Can be used for commissioning, service and automation  Service tools on PC (NORD CON)  Simple to implement in customer-specific systems-
1.1.3 Delivery
Check the equipment immediately after delivery/unpacking for transport damage such as deformation or loose parts.
If there is any damage, contact the carrier immediately and carry out a thorough assessment.
Important! This also applies even if the packaging is undamaged.
BU 0050 GB-3111 Subject to technical amendments 7
Page 8
NORD USS and Modbus RTU Manual
SK TU1-RS2
Bus system: AS1 = AS-Interface, CAN = CAN, CAO = CANopen, RS2 = RS232, USS = USS, etc. Device series: SK TU1 / SK TU2 / SK TU3
1.1.4 Scope of supply
SK TU1-RS232* for frequency inverter SK 700E IP20 or SK CU1-STD for frequency inverter SK 700E, SK 750E IP20 or SK CU1-USS for frequency inverter SK 700E, SK 750E IP20 or
*incl. screw for optional fixing to the FI
1.1.5 Certifications
1.1.5.1 European EMC Directive
If NORD frequency inverters or their options are installed according to the recommendations in this instruction manual, it meets all EMC directive requirements, as per the EMC product standard for motor-operated systems EN 61800-3.
1.1.5.2 RoHS compliance
The bus options described here are designed to be RoHS compliant according to Directive 2002/95/EEC
1.1.6 Identification System
8 Subject to technical amendments BU 0050 GB-3111
Page 9
1.2 USS - Modules
WARNING
NOTE
Modules should not be inserted or removed unless the device is free of voltage. The slots may only be used for the intended modules.
Installation of a technology unit separate from the frequency inverter is not possible. It must be connected directly to the frequency inverter.
LED
red/green
1.2 Modules
1.2.1 SK 500E
1.2.1.1 General
By the use of various modules for display, control and parameterisation, the SK 5xxE can be easily adapted to various requirements.
Alphanumerical display and operating modules can be used for simple commissioning. For more complex tasks, various connections to a PC or an automation system can be selected.
The technology unit (Technology Unit, SK TU3-…) is connected externally to the frequency inverter and is therefore easy to access and replace at any time.
As delivered, without the technology unit, 2 LEDs (green/red) are visible externally. These indicate the actual device status.
The green LED indicates that the mains voltage is present and operational, while a flashing code that increases in speed shows the degree of overload at the frequency inverter output.
The red LED signals actual error by flashing with a frequency which corresponds to the number code of the error (Manual BU 0500 Section 6).
BU 0050 GB-3111 Subject to technical amendments 9
Page 10
NORD USS and Modbus RTU Manual
X7: additional terminal
block with RS485 interface (terminals 73/74)
SK 520Eor higher
X11: 1x RJ12 socket to
connect the RS232 or RS485 interface
X11
1.2.1.2 RS 485 interface
As standard, all devices in the SK 500E series have an integrated interface for USS bus communication. According the version of the Fi, the following interfces are available: X11 RJ12 socket (available for the entire series) X7:73/74 RS485 + / - terminal connection (available for SK 520E or higher)
10 Subject to technical amendments BU 0050 GB-3111
Page 11
1.2 USS - Modules
Contact
Function
Data
Description / wiring suggestion
DIP switch 1/2 (top side of frequency inverter)
DIP-1
Termination resistor for RS485 interface (RJ12); ON = switched in [Default = "OFF"] For RS232 communication DIP1 to "OFF"
X11 X10 X9
RS4 85 _ A
RS4 85 _B
G N D
TXD
RXD
+ 5V
1 2
ON
CAN _H
CAN _L
CAN _GN DncCAN _SHLD
CAN _GN DncCAN _24 V
CAN _H
CAN _L
CAN _GN DncCAN _SHLD
CAN _GN DncCAN _24 V
RS48 5_A
RS48 5_B
GN D
TXD
RXD
+ 5 V
SK 511E and above
RS232/485 DIP CAN/CANopen
DIP-2 Termination resistor for CAN/CANopen
interface (RJ12); ON = switched in [Default = "OFF"]
Terminal
Function
Data
Description / wiring suggestion
X7:73
Data cable RS485
Baud rate 9600…38400Baud
Termination resistor R=120
BUS connection parallel to RS485 on RJ12 plug NOTE: The termination resistance of DIP switch 1 (see
RJ12/RJ45) can also be used for contacts 73/74.
X7:74
NOTE
To ensure reliable communication, a termination resistor (DIP switch DIP1) must be set at both ends of the bus.
RJ 12 socket (X11) In addition to the RS485 interface, the RJ12 socket also provides an interface for communication via RS 232.
However, the RS232 interface is only intended for connecting a PC. If a network is to be set up with several participants which communicate via USS (frequency inverters), it
must be noted that communication must be via RS 485. The RS232 interface (contacts X11:TXD and X11:RXD) cannot be deactivated on the frequency inverter. In
order to prevent a short circuit of these data cables and therefore the destruction of the RS232 driver, the contacts TXD, RXD and +5V must not have a common connection to several frequency inverters.
Terminal connection (X7:73/74) Above configuration level SK520E the frequency inverters are equipped with an additional terminal block
(X7). This provides the possibility of setting up the RS485 bus communication via contacts 73 and 74.
BU 0050 GB-3111 Subject to technical amendments 11
Page 12
NORD USS and Modbus RTU Manual
Technology units (Technology Units) are modules which can be inserted from above for display, parameterisation and control of the inverter.
WARNING
NOTE
Modules must not be inserted or removed unless the device is free of voltage. The slots may
only be used for the intended modules. The slots are coded to prevent them from being incorrectly connected.
Installation of a technology unit separate from the frequency inverter is not possible. It must be
connected directly to the frequency inverter.
Customer interfaces (Customer Units) are modules which are inserted into the upper slot inside the inverter. They are used for control and communication using digital/analog signals or bus interfaces.
Special extensions (EXtension Units) are inserted into the lower slot of the inverter. Such an extension unit is required if the speed is to be controlled or positioning is to be carried out by an incremental (absolute) encoder.
1.2.2 SK 700E
1.2.2.1 General
With the combination of modules for display, technology units and modules with digital and analog inputs and interfaces, customer interfaces or special extensions, the SK 700E can be easily extended to cater for the requirements of a wide range of applications.
12 Subject to technical amendments BU 0050 GB-3111
Page 13
WARNING
NOTE
Modules must not be inserted or removed unless the device is free of voltage. The slots may only be used for the intended modules.
Installation of a technology unit separate from the frequency inverter is not possible. It must be connected directly to the frequency inverter.
RXD
0V
TXD
6 1 5
9
5V
700E
N O RD A C
700E
N O RD A C
1.2.2.2 Technology Box RS232
(SK TU1-RS2, Option)
The Technology Box (Technology Unit) is clipped to the outside of the inverter. The RS232 interface enables simple connection of an SK 700E to a PC with a
serial interface. Communication between PC and frequency inverter can be set up using the
NORD CON Software (Windows). This is used for the control, parameterisation and display of operating values of the frequency inverter.
This allows a simple functional test of the inverter to be carried out and, following successful parameterisation, the data set can be saved as a file.
1.2.2.3 Installation of the SK TU1 technology unit
1.2 USS - Modules
Installation of the technology units must be carried out as follows:
1. Switch off the mains voltage, observe the waiting period.
2. Remove the dummy cover by actuating the unlocking device on the top and bottom edge.
3. Allow the technology unit to engage audibly by pressing lightly on the mounting surface.
BU 0050 GB-3111 Subject to technical amendments 13
Page 14
NORD USS and Modbus RTU Manual
Connector
Functions
Maximum cross-section
Parameter
X1.1
Output relay
1,5 mm2
P434 ... P443
X1.2
Analog signals IN / OUT
1,0 mm2
P400 ... P419
X1.3
Digital inputs
1,0 mm2
P420 ... P423
X1.4
Bus signals / power supply
1,0 mm2
P503 ... P548
74 RS485 -
X1.1
X1.2
X1.3
X1.4
11 VREF 10V 12 AGND /0V 13 AIN1 ­14 AIN1 + 17 AOUT1
21 DIG IN 1 22 DIG IN 2 23 DIG IN 3 24 DIG IN 4 42 VO +15V
41 VO +5V 40 GND /0V 73 RS485 +
01 REL1.1 02 REL1.2 03 REL2.1 04 REL2.2
NOTE: All control voltages are based on a common reference potential!
Potentials AGND /0V and GND /0V are internally linked in the device.
The maximum total current 5/15V is 300mA!
Potentialfreier Kontakt oder Ausgang einer SPS: 7,5...33V
(low = 0...3,5Volt)
Differenzeingang 0...10V
0...20mA
Voltage supply: 5V RS 485 (USS protocol)
5V supply for ParameterBox, p-box or motor thermistor
Data cables USS protocol
Digitale Eingänge: DIG IN 1 = Ein rechts DIG IN 2 = Ein links DIG IN 3 = Parametersatz bit 0 DIG IN 4 = Festfrequenz 1
Ausgangsrelais: max. 2,0A 28V DC /230V AC
U
REF
= 10V / I
max
= 10 mA
Analogausgang SPS: 0...10V oder Potentiometer: 2...10k
Spannungsversorgung: 15V
Termination resistor for RS 485 interface (120)
Zuschaltbarer Bürdenwiderstand für 0/4...20mA Analogeingang (250)
U/I switching
Analog input,
250
ON = Current,
OFF = Voltage
Termination
resistor
RS 485
120
O F F
O F F
1.2.2.4 Customer unit Standard I/O
(SK CU1-STD, Option)
The standard I/O of the customer interface(Customer Unit) provides sufficient control terminals for most applications and it is fully terminal-compatible with NORDAC vector mc..
1 analog differential input, 4 digital inputs and 1 analog output are available for control of the frequency inverter.
Readiness for operation is shown via the 2 relay contacts and a mechanical motor brake is activated at the correct time.
The connected frequency inverter can be accessed via the RS485 interface. In addition to the entire range of control functions, parameterisation is also possible.
TheNORD CON software can be used to carry out a simple function test of the serial interface and the parameterisation of the inverter. For this, an interface converter (e.g. SK IC1-232/485) must be used between the PC and the inverter. Following successful parameterisation, the complete data set can be stored as a file by means of NORD CON.
14 Subject to technical amendments BU 0050 GB-3111
Page 15
1.2 USS - Modules
Connector
Functions
Maximum cross-section
Parameter
X4.1
Output relay
1,5 mm2
P434 ... P436
X4.2
Digital input
1,5 mm2
P420
X4.3
Data cables
1,5 mm2
P503 ... P548
NOTE: All control voltages are based on a common reference potential!
Potentials AGND /0V and GND /0V are internally linked in the device.
The maximum total current 5/15V is 300mA!
X4.1
X4.2
X4.3
01 REL1.1 02 REL1.2
41 VO +5V 40 GND /0V 73 RS485+ 74 RS485-
21 DIG IN 1
42 VO +15V
Data cables: RS485
(terminal 73-74, RS485 +/-)
Control signal: 2.5 ... 33V
Output relay: Max. 2.0A 28V DC /230 V AC
Digital input 1 (P420)
Voltage supply: 15V
USS
USS termination resistor
not connected
connected
ON
1.2.2.5 USS Customer Interface
(SK CU1-USS, Option)
In addition to data connections, the USS customer units are also equipped with conventional digital inputs and outputs.
Via the existing relay contacts, a mechanical motor brake can be controlled or readiness for operation can be communicated to a higher level system.
The digital input has a 2.5V switching threshold for the evaluation of the temperature sensor. The input can, however, also be used for an emergency stop function.
BU 0050 GB-3111 Subject to technical amendments 15
Page 16
NORD USS and Modbus RTU Manual
WARNING
NOTE
Installation must be carried out by qualified personnel only, paying particular attention to safety and warning instructions.
A customer interface must not be replaced while it is carrying voltage.
Kundenschnittstelle
Sondererweiterung
Technologiebox
Verrieglungsstift
CLOSED
OPEN
Verriegelung geschlossen Verriegelung gffnet
Locking pin
Technology unit
Customer interface
Special extension unit
Locking device closed
Locking device open
1.2.2.6 Installation of customer units
1. Switch off the mains voltage, observe the waiting period.
2. Remove the cover grid from the connection area by loosening the 2 screws and levering out the device cover (slot) or simply pull it out.
3. Locking lever in the "open" position.
4. Using light pressure push the customer unit into the upper guide rail until it engages.
5. Move the locking lever to the "closed" position.
6. Remove the connector by pressing the releases then make the necessary connections. Then insert the connectors until they engage.
7. Replace all covers.
16 Subject to technical amendments BU 0050 GB-3111
Page 17
1.2 USS - Modules
Motor PTC
Supply voltage +5V
Digital input
Removing customer units:
1. Switch off the mains voltage, observe the waiting period.
2. Remove the cover grid from the connection area by loosening the 2 screws and levering out the device cover (slot) or simply pull it out.
3. Locking lever in the "open" position.
4. Using a screwdriver (as shown), lever the customer unit out of its engaged position and then remove it by hand.
5. Move the locking lever to the "closed" position.
6. Replace all covers.
Motor temperature protection applies for all customer units!
For secure protection against motor overheating, a temperature sensor (thermistor, PTC) can be connected to any digital input.
The appropriate parameters (P420 ... P425, depending on option) must be set to a value of 13 (PTC thermistor input) for this purpose.
The supply voltage varies dependent upon the customer unit. The lowest voltage possible should be chosen.
Internal switching in the inverter prevents excessive PTC voltage.
The cable routing should always be separate from the motor cable and with shielded cables.
BU 0050 GB-3111 Subject to technical amendments 17
Page 18
NORD USS and Modbus RTU Manual
M12 connector (Detail 1)
Terminal (Detail 2)
Functions
Maximum cross-section
4 (black)
73
RS485 +
1,5 mm2
3 (blue)
74
RS485 -
1,5 mm2
2 (white)
41
+5V
1,5 mm
2
1 (brown)
40
0V, GND
1,5 mm2
3,0 m
1
2
1.2.3 SK 300E
Technology units and customer interfaces
Through the combination of modules for the display, (technology units) and modules with digital and analog inputs, as well as interfaces, (customer units) or bus interfaces, the SK 300E can be easily adapted to the requirements of a wide range of applications.
The NORD CON software can be used to carry out a simple function test of the serial interface and parameterisation of the inverter. For this, an interface converter (e.g. SK IC1-232/485) must be used between the PC and the inverter. Following successful parameterisation, the complete data set can be stored as a file by means of NORD CON.
Further details can be found in Manual BU 0300.
USS interface (RS485)
With the SK 300E, an RS485 interface is lead out to a 4-pin M12 round connector (Detail 1) as standard. In addition to being used for external control (ParameterBox) it can also be used as a bus interface.
If required an M12 SUB D9 (Part No.. 278910060) connecting cable is available.
Parallel to the external M12 connection, in the connection unit (trio interface, removed from FI) terminals 73/74 are also available for connection.
The RS485 termination resistor (Detail 2) can be switched in or out using the DIP switch in the connection unit.
18 Subject to technical amendments BU 0050 GB-3111
Page 19
1.3 USS - Protocol speciication
STX
LGE
ADR
N1
N2
..
Nn
BCC
1.3 USS Protocol Specification
1.3.1 General information
The USS protocol defines an access procedure according to the Master/Slave principle for communication via a serial bus. A sub-set of this also includes point-to-point connection. A master and a maximum of 31 slaves can be connected to a bus. The individual slaves are accessed by the master via an address character in the telegram. Direct exchange of messages between the individual slaves is not possible. Communication is carried out in semi-duplex mode. The master function cannot be transferred (single master system).
Data transfer via the two-cable bus is carried out by individual characters in the format: 1 start bit, 8 data bits 1 even parity bit and 1 stop bit (8E1) - This results in a character frame of 11 bits.
The direction of the data on the bus (transmit or receive) is specified by the master.
1.3.2 Telegram Structure
Each telegram starts with the start character STX (= 02 Hex), followed by the length (LGE) and the address byte (ADR). This is followed by the information characters. The telegram
is concluded by the data saving character BCC (Block Check Character).
For word information (16 Bit) in the information data block (= information character block) the High Byte (first character) is always transmitted first, followed by the Low Byte (second character). The same applies for double-word information:
First the High Word is transmitted, followed by the Low Word.
BU 0050 GB-3111 Subject to technical amendments 19
Page 20
NORD USS and Modbus RTU Manual
STX
(Start of Text): ASCII character: 02 Hex The start character forms the first character in the telegram and together with the start pause it is used
for reliable detection of the start of the telegram.
LGE
(Telegram length): 1 Byte, contains the length of the telegram. The telegram length is located in the 2nd byte of the telegram and indicates the length of the telegram
from the 3rd byte onwards. Specification of the length enables differentiation between the various types of telegram. The data recipient can use the length byte to check the number of characters to be received.
ADR
(Address byte): 1 byte, also contains the slave address.
Bit7 Bit6 Bit5 Bit4 Bit3 Bit2 Bit1 Bit0
0 M BC | Address (0..30) |
The USS address is located in the 3rd byte (data bits 0 to 4) of the telegram. The slave device which is to transmit or receive data is identified via the USS address. Therefore, a maximum of one slave device can be represented by each of the 31 possible addresses For this, the appropriate address must be set in the slave device. Bit 5 and Bit 6 have a special meaning.
Bit 5 Broadcast: A so-called broadcast telegram can be triggered by setting this bit. In a broadcast telegram, address bits 0 to 4 are ignored by the connected slaves, i.e. the transmitted telegram is processed by all of the slaves. However, in contrast to standard addressing, the slaves do not transmit a response telegram as this would result in bus conflicts.
Bit 6 Echo: By setting the 6th bit, the inverter returns a telegram which is identical to the one which it has received (for commissioning).
N1... Nn
Information characters: each one byte, content depending on task
BCC
1 byte, data saving character (Block Check Character) The check-sum BCC is formed byte-wise over the entire telegram as an Exclusive OR link. The result
after the last net character is then the BCC.
BCC = STX XOR LGE XOR ADR XOR N1 XOR....N
N
1.3.3 Data Coding
1.3.4 Character Frame
Each transmitted character begins with a start bit (logical 0) and end with a stop bit (logical 1). 8 bits (1 byte) are transmitted. Saving is performed by a parity bit (even parity). Therefore 11 bits are transmitted for each character.
20 Subject to technical amendments BU 0050 GB-3111
Page 21
1.3 USS - Protocol speciication
Time
Size
Meaning
t
SP
Minimum 2 character durations*
Start pause time
t
AVZ
Maximum 20 ms
Response Delay Time
t
TLZ
1.5 x consecutive telegram duration
= 1,5 x (n+4) x character duration
Max. residual telegram duration
t
ZVZ
Smallest start pause time
Character delay time
*Character duration = 11 x (1/Baud rate)
Master
BCC
LGE
ADR
1. n BCC
STX
STX
LGE
ADR
1. n BCC
t
SP
t
AVZ
STX
t
SP
t
TLZ
Slave
x
x+1
t
ZVZ
1.3.5 Transfer Procedure
The USS protocol functions according to the master/slave principle, whereby the master is the control device (PC, SPS etc) and the slaves are the frequency inverters
Only one slave can be addressed with each telegram (exception: broadcast telegram without response by the slaves).
In order to ensure reliable detection of the start of the telegram by the slave, the master must observe a so­called start pause between the receipt of the slave telegram and transmission of the next telegram. The master starts to transmit a telegram. After the data package has been sent, the master switches the bus data direction from transmission to reception. The slave addressed in the telegram must respond within a specified response time.
The lengths of the master and slave telegrams are the same, i.e. the master telegram determines the length of the response by the slave.
Telegram traffic can be cyclical a acyclical.
The following time definitions must be observed:
1.3.6 Start Pause Time
The start character STX (= 02 Hex) on its own is not sufficient to enable the slaves to uniquely identify the start of a telegram, because the bit combination 02/Hex may also occur in the information characters. Therefore, in advance of the STX a start pause time tSP where no characters are sent for at least the duration of 2 characters is specified for the master. The start pause time is a component of the order telegram. A valid telegram is only identified by an STX with a preceding start pause.
The exchange of data is always performed according to the pattern described above (semi-duplex operation):
The minimum start pause time which is to be observed for the various baud rates can be found in the Master Telegram Time table in the Additional Information section.
BU 0050 GB-3111 Subject to technical amendments 21
Page 22
NORD USS and Modbus RTU Manual
1.3.7 Response Delay Time
The time interval between the last character of the order telegram (BCC) and the start of the response telegram (STX) is called the response delay time t 20ms, however, it must not be smaller than the start pause. If the addressed participant does not respond within the maximum permissible response delay time, an error message is saved in the master. The master then sends the telegram which is intended for the next slave.
The minimum response delay time which is to be observed for the various baud rates can be found in the Master Telegram Time table in the Additional Information section.
. The maximum permissible response delay time is
AVZ
22 Subject to technical amendments BU 0050 GB-3111
Page 23
1.4 USS - Bus structure
1.4 Bus Configuration
1.4.1 General information
The basis for the physical interface of the USS protocol is the 'Recommended Standard RS-485' For point-to-point connections, a sub-set of EIA RS-232 (CCITT V.24), TTY (20mA current loop) or optic fibre
cable can be used as the physical interface. SK 300E and SK 500E series inverters are always configured with an RS485 interface on the terminal
connection bar or connector. For SK 700E series devices, the customer interface standard or USS must be selected.
For the SK 700E series, RS 232 technology modules can be used for communication (only point-to-point communication possible)
1.4.2 Topology
The USS bus is based on a linear topology without spur cables. Both ends of the lines end at a participant and must be terminated there with bus termination networks.
The maximum cable length and the maximum distance between the master and the last slave is restricted by the properties of the cable, the ambient conditions and the transfer rate. With a transfer rate < 100kbit/s, a maximum length of 1200m is possible.
[EIA Standard RS-422-A December 1978, Appendix, Page 14] The number of participants is restricted to 32 (1 master, 31 slaves).
1.4.3 Transfer Method
Transfer is by the half-duplex method, i.e. alternation between transmission and reception, and must be controlled by the software. The half-duplex method allows the use of the same cables for both transfer directions.
This enables simple and low-cost bus wiring, operation in environments where there is interference as well as a high data transfer rate.
BU 0050 GB-3111 Subject to technical amendments 23
Page 24
NORD USS and Modbus RTU Manual
1.4.4 Installation of the Bus System
In an industrial environment the correct installation of the bus system is particularly important in order to reduce potential interference. The following points are designed to help prevent interference and problems right from the start.
The installation guidelines are not complete and applicable safety and accident prevention guidelines must be complied with.
1.4.4.1 Cable material
The frequency inverter is usually connected to the USS bus system by a twisted, shielded two-wire cable.
The guaranteed transfer speeds or transfer distances can only be achieved without errors if the specified cable parameters are complied with.
Structural Details:
2
Cable diameter : 2 0,5 mm Flexible strand: 16 0,2 mm Twisting: 20 twists / m Total shielding: Mesh, tinned copper wire,
1.1 mm2,
85 % visual covering Total diameter: 5 mm External sheath: according to requirements for
flammability, combustion residues,
etc.
Thermal / Electrical Properties:
Conductor resistance (20°C): 40 W/km Insulation resistance (20°C): 200 W/km Operating voltage (20°C): 300 V Test voltage (20°C): 1500 V Temperature range: -40 °C T 80 °C Load capacity: 5 A Capacitance: 120 pF/m
24 Subject to technical amendments BU 0050 GB-3111
Page 25
1.4 USS - Bus structure
1.4.4.2 Cable runs / Shielding (EMC)
If EMC measures are not in place, high-frequency interference which is principally brought about by switch procedures or lightning often causes electronic components in the Bus participants to become faulty and error­free operation can no longer be ensured.
Proper shielding of the bus cable reduces the electrical interference which can arise in an industrial environment. Best shielding characteristics can be achieved with the following measures
Connect the Bus participants with the shortest amount of cable possible. The shielding of the Bus cable must be applied completely and to a wide area on both sides. * Avoid using spur lines to connect field devices to the Bus. Avoid extending the Bus lines using plug connectors.
Bus lines should be laid with a minimum spacing of 20cm to other lines which carry a voltage higher than 60V. This applies to lines laid inside and outside of control cabinets.
*)Note: If earthing potential values are different, transient currents may flow through shielding which
is connected on both sides. This may be a danger to electronic components. Differences in potential must be reduced using adequate potential equalisation.
1.4.4.3 Bus termination
The bus lines be terminated at both ends. For this, a resistance of 120 must be connected between the data signal lines RS485 + and RS485 - on the
first and last participant. With some modules, the termination resistor can be switched in with DIP switches. As delivered, the bus
termination resistor is not activated. If the bus termination resistor is not integrated into the module, it must be installed in the module or the
connector housing.
BU 0050 GB-3111 Subject to technical amendments 25
Page 26
NORD USS and Modbus RTU Manual
MASTER
SLAVE
Parameter order
Control word + Setpoint
Parameter response
Status word + Actual value
PKW section
PZD section
Order telegram
Response telegram
Processing
1.5 Data transmission
1.5.1 Structure of reference data
This section describes the cyclic data traffic between the master and the frequency inverter. The reference data is divided into two sections:
PKW section (Parameterisation; Parameter Identification- Value) PZD section (Processdata)
Parameter values can be read and written via the PKW section of the reference data. All tasks which are carried out via the PKW interface are essentially tasks for configuration, monitoring or diagnosis.
The PZD section serves to control the frequency inverter. The control word or status word as well as the setpoint and actual values are transferred in the process data.
Access always consists of an order and a response telegram. In the order telegram, the reference data is transferred to the slave. In the response telegram, the reference data is transferred from the slave to the master. The structure of both telegrams is identical.
Telegram traffic / structure of reference data area
Processing of the process data is carried out immediately in the FI (high priority), in order to ensure a rapid reaction to control commands or a change in status can be transmitted to the master without delay.
On the other hand, the processing speed of the PKW data has a lower priority, so that processing may take considerably longer.
26 Subject to technical amendments BU 0050 GB-3111
Page 27
1.5 USS - Data transfer
Type
Task
PPO1
extended parameter data telegram with 32 bit parameter values and process data
PPO2
Telegram with extended process data (main and two auxiliary setpoint values) and 32 bit parameter value
PPO3
Process data telegram with main setpoint value without parameter data
PPO4
extended process data telegram with main and auxiliary setpoint values without parameter data
PPO
Parameter Process data Object
STW
Control word
PKW
Parameter identifier Value
ZSW
Status word
PZD
Process data
SW1..3
Setpoints 1-3
PKE
Parameter identifier
IW1..3
Actual values 1-3
IND
Index
PWE
Parameter Value
NOTE
Because of the protocol specification, for PPO types 2 and 4 6 words must be reserved for
the address area of the process data (PZD). The two last words are not used for the process data telegrams and are therefore merely reserve areas.
1.5.2 PPO types
For cyclic data traffic, the Parameter- Process data Object (PPO) with which the process data (PZD) and parameters (PKW) are transferred from the master to the frequency inverter is defined. The frequency inverter can process PPO types 1, 2, 3 or 4.
PPO3 and PPO4 are purely process data objects for applications which do not require parameter processing.
Abbreviations used:
Note:: An SPS can normally only consistently transfer double words by means of I/O memory access.
For longer data formats (PKW channel always / PZD data with PPO2 or PPO4) system functions (e.g. SFC 14, consistent data reading / SFC15, consistent data writing) must be used.
BU 0050 GB-3111 Subject to technical amendments 27
Page 28
NORD USS and Modbus RTU Manual
PKW
PZD
PKE
IND
PWE
PWE
PZD1
PZD2
PZD3
PZD4
STW
SW1
SW3
SW2
ZSW
IW1
IW3
IW2
1st word
2nd word
3rd word
4th word
5th word
6th word
7th word
8th word
PPO 1
PPO 2 1st word
2nd word
3rd word
4th word
PPO3
PPO4
PKW
PZD
PKE
IND
PWE
PWE
PZD1
PZD2
PZD3
PZD4
STW
SW1
SW2
SW3
ZSW
IW1
IW2
IW3
1st word
2nd word
3rd word
4th word
5th word
6th word
7th word
8th word
PPO 1
PPO 2 1st word
2nd word
3rd word
4th word
PPO3
PPO4
1.5.2.1 PPO types SK 300E/700E/750E
The following diagram shows an overview of the supported PPO types.
1.5.2.2 PPO types for SK 500E series
The following diagram shows an overview of the supported PPO types. Please not the arrangement of SW2/SW3 and IW2/IW3
28 Subject to technical amendments BU 0050 GB-3111
Page 29
1.5 USS - Data transfer
1st word
2nd word
3rd word
4th word
PZD area with  1x16 bit setpoint
STW ZSW
SW1
IW1
PZD area with up to 3 16 bit setpoints
STW ZSW
SW1
IW1
SW3
IW3
SW2
IW2
PZD area with 1x 32-Bit setpoint and 1x 16-Bit
STW ZSW
SW1
IW1
SW2
IW2
1st word
2nd word
3rd word
4th word
PZD area with 1x16 bit setpoint
STW ZSW
SW1
IW1
PZD area with up to 3 16 bit setpoints
STW ZSW
SW1
IW1
SW2
IW2
SW3
IW3
Note: 32-Bit setpoints consist of High and Low words (16-Bit each).
1.5.3 Process data (PZD)
In the process data area PZD, control words and setpoints are transferred from the master to the slave (frequency inverter) and in return, status words and actual values are sent from the slave to the master. The structure of the PZD area is always the same in terms of the sequence of its elements (words), however, dependent upon direction of data Master Slave / Slave Master, it is designated differently
The process data area of the reference data has the following structure:
- STW: Controlword; length 16 Bit, order telegram contains control bits (e.g. enable, quick stop, error acknowledgement)
- ZSW: Statusword; length 16 Bit, response telegram contains status bits (e.g. FI running, error)
- SW1..3: Setpointvalues; maximum of 3 possible, 16 or 32Bit, order telegram e.g. frequency setpoint value, position setpoint value, torque setpoint value
- IW1..3: Actualvalues; maximum of 3 possible, 16 or 32Bit, response telegram e.g. actual frequency value, actual position value, actual torque value
1.5.3.1 Process data for SK 300E/700E/750E
1.5.3.2 Process data for SK 500E (entire series)
BU 0050 GB-3111 Subject to technical amendments 29
Page 30
NORD USS and Modbus RTU Manual
PZD1
PZD2
PZD3
PZD4
STW
SW1
SW2/3
SW2/3
15
14
13
12
11
10 9 8 7 6 5 4 3 2 1 0
Bit
Value
Meaning
Comments
0 0 OFF 1
Reverse with the brake ramp, with disconnection from supply at f=0Hz
1 ON
Ready for operation
1 0 OFF 2
Cut off voltage; the inverter output voltage is switched off; the FI enters a state where switching on is disabled.
1 Operating condition
OFF 2 is cancelled
2 0 OFF 3
Quick stop with programmed quick stop time; with disconnection from supply at f=0Hz; the FI switches to starting disabled condition.
1 Operating condition
OFF 3 is cancelled
3 0 Disable operation
Cut off voltage; the inverter output voltage is switched off; the FI enters a state where switching on is enabled.
1 Enable operation
The output voltage is enabled; ramp to the existing setpoint
4 0 Lock ramp generator
Ramp generator is set to zero; no disconnection from supply at f=0Hz; FI remains in the operation enabled state.
1 Operating condition
Enable ramp generator
5 0 Stop ramp generator
The setpoint currently provided by the ramp generator is "frozen" (frequency is maintained).
1 Enable ramp generator
Enable setpoint on ramp generator
6 0 Disable setpoint
Selected setpoint value is set to zero on the ramp generator.
1 Enable setpoint
Selected ramp generator setpoint is activated.
7 0 No acknowledgement
With the switch from 0 to 1, errors which are no longer active are acknowledged.
1 Acknowledge
Note: When a digital input has been programmed for the "ack.fault" function, this bit must not permanently be set to 1 via the bus (otherwise, edge evaluation would be prevented).
8 0
1 Bit 8 active
Bus bit 8 from the control word is set. (Only for SK 200E and SK 500E) For further details of the function please refer to parameter (P480).
9 0
1 Bit 9 active
Bus bit 9 from the control word is set. (Only for SK 200E and SK 500E) For further details of the function please refer to parameter (P480).
10 0 PZD invalid
The transmitted process data is invalid.
1 PZD valid
Valid process data is transferred from the master. Note:If setpoints only are transferred via the bus, this bit must be set so that the
transferred setpoint is valid.
11 0
1 Rotational direction:
right
Rotational direction right (priority) ON*
12 0
1 Rotational direction:
left
Rotational direction left ON*
13
0/1 Reserved
14
0/1
Bit 0 to switch parameter set
00 = Parameter set 1 01 = Parameter set 2
10 = Parameter set 3 11 = Parameter set 4
15
0/1
Bit 1 to switch parameter set
Table 14
1.5.3.3 Control word (STW)
The control word (STW) is the first word transferred to the frequency inverter in the process data area in an order telegram. For example, a control word "Ready for switch-on" corresponds to 047E
(hex)
.
* If Bit 12=0, then "Direction of rotation right ON" applies
30 Subject to technical amendments BU 0050 GB-3111
Page 31
1.5 USS - Data transfer
PZD1
PZD2
PZD3
PZD4
ZSW
IW1
IW2/3
IW2/3
15
14
13
12
11
10 9 8 7 6 5 4 3 2 1 0
Bit
Value
Meaning
Comments
0 0 Not ready to start
1
Ready to start
Initialisation completed, charging relay ON, output voltage disabled
1 0 Not ready for operation
Causes: No command has been activated, fault is signaled, OFF2 or OFF3 activated, starting disabled state activated
1 Ready for operation
ON command activated, no faults present. The inverter can be started with the command ENABLE OPERATION
2 0 Operation disabled
1
Operation enabled
The output voltage is enabled; ramp to the existing setpoint
3 0 No fault
1 Fault
Drive fault resulting in stoppage; this state is changed to starting disabled after the fault has been successfully acknowledged
4 0 OFF 2
OFF2 command applied
1 No OFF 2
5 0
OFF 3
OFF3 command applied
1 No OFF 3
6 0 Starting not disabled
1 Starting disabled
Switches first to OFF1, then to ready-to-start status
7 0 No warning
1
Warning
Drive operation continues, no acknowledgement necessary
8 0 Actual value not O.K.
Actual value does not match the setpoint (with POSICON: failure to reach setpoint position)
1 Actual value O.K.
Actual value matches required setpoint (setpoint has been reached) (with POSICON: setpoint has been reached)
9 0 Local guidance
Guidance on local device has been activated
1 Guidance requested
The master has been requested to assume guidance.
10 0
1 Bit 10 active
Bus bit 10 from the status word is set. For further details of function, please refer to parameter P481.
11 0
1 Rotational direction:
right
Inverter output voltage is turning right
12 0
1 Rotational direction:
left
Inverter output voltage is turning left
13 0
1 Bit 13 active
Bus bit 13 from the status word is set. For further details of function, please refer to parameter P481.
14
0/1
Currently active parameter set 0
00 = Parameter set 1 01 = Parameter set 2
10 = Parameter set 3 11 = Parameter set 4
15
0/1
Currently active parameter set 1
1.5.3.4 Status word (ZSW)
In the inverter response telegram, in the area of the process data the status word (ZSW) is transferred as the first word. For example, the status word "Ready for switch-on" corresponds to 0B31
(hex)
.
BU 0050 GB-3111 Subject to technical amendments 31
Page 32
NORD USS and Modbus RTU Manual
Bit
Value
Meaning
Comments
10 0 MFR 1 reference value
undershot
Programmed function of the MFR 1 not met or actual value < programmed reference value
1 MFR 1 reference value
reached
Programmed function of the MFR 1 is fulfilled, or Actual value > programmed reference value
13 0 MFR 4 reference value
undershot
Only for SK 700E/750E with POSICON extension: Status MFR 4 = 0
1 MFR 4 reference value
reached
Only for SK 700E/750E with POSICON extension: Status MFR 4 = 1
PZD1
PZD2
PZD3
PZD4
STW
SW1
SW2/3
SW3/2
15
14
13
12
11
10 9 8 7 6 5 4 3 2 1 0
Deviations in the status word (ZSW) for SK 300E and SK 700/750E series devices
With the above device types, the meanings of the two bits 10 and 13 in the status word deviate from the status word of the SK 500 E.
Meaning of the two individual bits:
1.5.3.5 Setpoint 1 (SW1)
The function of the 1st setpoint is set in parameter P546. The following options are available:
Setpoint frequency The setpoint frequency in setpoint 1 is transferred as a 16 Bit value as standard. Setpoint 1 is transferred to
the inverter as the second word in the process data area in the order telegram.
The setpoint is transferred as a whole number with a value range of -32768 to 32767 (8000 hex to 7FFF hex). The value 16384 (4000 hex) is equal to 100%. The value C000 HEX corresponds to -100%. A setpoint of 100% corresponds to the parameter maximum frequency (parameter P105) set in the same parameter set.
32 Subject to technical amendments BU 0050 GB-3111
Page 33
1.5 USS - Data transfer
PZD1
PZD2
PZD3
PZD4
STW
SW1, 32 Bit
SW2
SK 700E/750E
POSICON
P546=3, 32bit setpoint position
SW1, 16 Bit
SW2, 16 Bit
SW3
SK 53xE
P546=21 (23)
Low word
P547=22 (24)
High word
P546[-01]=21
(23)
Low word
P546[-02]=22
(24)
High word
SK 54xE
SK 700E + SK TU1-POS
Bit
Function
Bits 0-5
Position array/position increment
Bit 6
Reference point run
Bit 7
Reference point
Bit 8
Teach-in
Bit 9
Quit teach-in
Bit 10
Reset position
SK 500E
Bit
Function
Bits 0-3
Position array/position increment
Bits 4-7
Vacant
Bits 8-15
no significance
Setpoint position (16 or 32 Bit)
With the special extension Posicon (SK XU1-POS) of the SK 700E the absolute setpoint position can be transferred as a 16 or 32 Bit value in Setpoint 1, whereby the resolution is 1=0.001 rotation. In addition, the control terminals (setting of POSICON control bits) can be transferred in binary.
The SK 53xE / SK54xE version of the SK 500E series is also able to transfer positions, however here, the 32 Bit position is divided into two 16 Bit components (Low word and High word). The assignment of the two 16 Bit components is then carried out via appropriate parameterisation on 2 arbitrary setpoints (e.g.: SW1 and SW2).
16-Bit setpoint position setting:
As a 16 Bit value, a range of +32767 (= 32,767 revolutions) to -32768 (= -32,768 revolutions) is possible. The 16 Bit setpoint position is transferred as the second word in the process data area (as with the setpoint frequency)
32-Bit setpoint position setting:
As a 32 Bit value, the full position range of +/- 50000,000 revolutions is available. With the SK 700E/750E, the 32 Bit setpoint position is transferred in the area of the process data as the second and third word (with the SK 500E in any two of the three words PZD2, PZD3, PZD4).
Control Bit settings POSICON (SK 700E/750E/53xE):
A 16 Bit value is transferred in which the control terminals of the POSICON special extension unit are mapped. The setpoint position is based on the position array or position increment as per (P610).
The transferred Bits have the following meaning (see Manual BU 710 / BU 0510):
BU 0050 GB-3111 Subject to technical amendments 33
Page 34
NORD USS and Modbus RTU Manual
PZD1
PZD2
PZD3
PZD4
STW
SW1
SW3
SW2
PZD1
PZD2
PZD3
PZD4
STW
SW1
SW2
Setting
100% is equal to
Off
Setpoint frequency, actual frequency PID, actual frequency PID limited, actual frequency PID monitored, frequency addition, frequency subtraction, maximum frequency
Maximum frequency (P105)
Torque current limit
Torque current limit (P112)
Current limit
Inverter rated current
Servo mode torque
Nominal torque (P112)
Lead torque
Lead torque (P214)
1.5.3.6 Second and third setpoint (SW2/3)
With the SK 500E, the assignment of setpoints 2 and 3 to the process data words PZD3 and PZD4 is carried out in the opposite manner to the SK 300E/700E/750E series.
Second and third setpoint SK 300E/SK 700E/SK 750E(SW2/3)
If the PPO type 2 or 4 is used, in addition to setpoint 1, a 2nd setpoint can be transferred in word PZD4 and a 3rd setpoint in PZD3.
A third setpoint value can only be transferred if a 32 Bit setpoint value is not transferred in the first setpoint.
The second and third setpoints are always 16 Bit. The function of the second and third setpoints can be set in the inverter with parameter P547 „'Setpoint function 2‟ and P548 „'Setpoint function 3‟ respectively.
Both setpoints are transferred as whole numbers in the range (-32768 to 32767). The value 16384 (4000 HEX) corresponds to 100%. The value C000 HEX is equal to –100%, so that setpoints in the range –200% to +200% can be transferred. A setpoint of 100% corresponds to the respective nominal value:
In addition, POSICON control bits can be transferred here (see setpoint 1)
34 Subject to technical amendments BU 0050 GB-3111
Page 35
1.5 USS - Data transfer
PZD1
PZD2
PZD3
PZD4
STW
SW1
SW2
SW3
Setting
100% is equal to
Off
Setpoint frequency, actual frequency PID, actual frequency PID limited, actual frequency PID monitored, frequency addition, frequency subtraction, maximum frequency
Maximum frequency (P105)
Torque current limit
Torque current limit (P112)
Current limit
Inverter rated current
Servo mode torque
Nominal torque (P112)
Lead torque
Lead torque (P214)
Second and third setpoint SK 500E (SW2/3)
In addition to setpoint 1, a second setpoint can be transferred in word PZD3 and a third setpoint in PZD4.
The second and third setpoints are always 16 Bit. The function of the second and third setpoints can be set in the inverter with parameter P547 „Setpoint 2 function‟ and P548 „Setpoint 3 function‟ respectively.
Both setpoints are transferred as whole numbers in the range -32768 to 32767. The value 16384 (4000 HEX) corresponds to 100%. The value C000 HEX is equal to –100%, so that setpoints in the range –200% to +200% can be transferred. A setpoint of 100% corresponds to the respective nominal value:
BU 0050 GB-3111 Subject to technical amendments 35
Page 36
NORD USS and Modbus RTU Manual
PZD1
PZD2
PZD3
PZD4
ZSW
IW1
IW2/3
IW3/2
15
14
13
12
11
10 9 8 7 6 5 4 3 2 1 0
SK 700E/750E
Bit
Status
Bits 0-5
Digital input 1-6
Bits 6-11 for POSICON special extension unit
Digital input 7-12
Bit 6 for encoder special extension unit
Digital input 7
Bits 12-15
Multifunctional relay 1-4
SK 500E
Bit
Status
Bits 0-4
Digital input 1-5
Bits 5-6 (above SK 520E)
Digital input 6-7
Bits 12-15
Relay and digital outputs 1 - 4
PZD1
PZD2
PZD3
PZD4
ZSW
IW1
IW2
1.5.3.7 Actual value 1 (IW1)
The actual value 1, i.e. the actual output frequency of the inverter, is transferred as a 16 Bit value as standard in the actual value 1. The actual value 1 is transferred to the master in the inverter response telegram as the second word in the process data area.
The actual value 1 is transferred as a whole number in the range (-32768 to 32767). In addition to the actual frequency, other actual inverter values can be transferred. The setting is made in P543 'Actual value 1 function'.
The settings „Actual frequency‟, „Actual speed‟, „Current‟ and „Torque current‟ are transferred as percentages
of the respective nominal values. The value 16384 (4000 HEX) corresponds to 100%. The value C000 HEX corresponds to -100%. Actual values in the range –200% to +200% can be transferred.
With the setting „Digital I/O status‟, the states of the control terminals and the relay (MFR) /digital outputs can be transferred:
With the setting 'Actual position' and 'Setpoint position' the actual absolute position is transferred. The resolution is 1 = 0.001 revolutions.
If with SK 700E/750E the value 'Setpoint position 32 Bit' is set in parameter P546 (Setpoint function 1), then the actual value (setpoint or actual position) is also transferred as a 32 Bit value in PZD2 and PZD3:
1.5.3.8 Actual value 2 and actual value 3 (IW2/3)
It is possible to forward two more actual values to the controller if PPO type 2 or 4 is used for transfer. The assignment of the actual values 2 and 3 to the process data words PZD3 and PZD4 is carried out in the
same way as the assignment of setpoints 2 and 3. These also differ in sequence between the SK 500E and other inverter series.
36 Subject to technical amendments BU 0050 GB-3111
Page 37
1.5 USS - Data transfer
Status
Bit 6
Switch-on
disable
Bit 5
Emergency
stop
Bit 4
Disable
voltage
Bit 3
Fault
Bit 2
Operation
enabled
Bit 1
Standby
Bit 0
Ready for
switch-on
Not ready to start
0 X X 0 0 0 0
Starting disabled
1 X X 0 0 0 0
Ready to start
0 1 1 0 0 0 1
Activated
0 1 1 0 0 1 1
Operation enabled
0 1 1 0 1 1 1
Fault
0 X X 1 0 0 0
Error active
0 X X 1 1 1 1
Emergency stop active
0 0 1 0 1 1 1
Second and third actual value SK 300E/SK 700E/SK 750E(SW2/3)
The actual value 2 (IW2) is transmitted in PZD4. The value to be transferred can be selected in P544 (actual bus value 2). Actual value 3 (IW3) can be transmitted in PDZ3 if actual value 1 is not a 32 Bit value. The value to be transferred can be selected in P545 (actual bus value 3).
Second and third setpoint SK 500E (SW2/3)
The actual value 2 (IW2) is transmitted in PZD3. The value to be transferred can be selected in P544 (actual bus value 2). The actual value 3 (IW3) is transmitted in PZD4. The value to be transferred can be selected in P545 (actual bus value 3).
1.5.3.9 The status machine
The frequency inverter passes through a status machine. The changes between various states are triggered by the respective control commands in the process data control word. The actual status is returned in the process data status word.
After switching on, the inverter is in switch-on disabled status. This status can only be ended by transmitting the “Shut down (Off 1)” command.
The answer to a Master telegram normally does not yet contain a reaction to the control command. The controller must check the answers from the slaves as to whether the control command has been carried out.
The following Bits indicate the status of the frequency inverter:
BU 0050 GB-3111 Subject to technical amendments 37
Page 38
NORD USS and Modbus RTU Manual
Switch-on
disabled
Ready for sw itch-on
Activated
Operation
enabled
Emergency stop
active
Error reaction
active
Error
From any device status
3 4 5 6 8
4 5
5
Not on standby
Switching on theinverter
Loading relay applied
Error
Error reaction complete
Bit0 = 0: Shut down & Bit1 = 1: Enable voltage & Bit2 = 1: Enable pulses (xxxx x1xx xxxx x110)
Bit 3 = 0: Disable operation Bit0 = 1: Switch on
Bit3 = 1: Enable operation
Bit2 = 0: Emergency stop
Bit1 = 0: Disable voltage
v Bit2 = 0:Emergency stop
Priority of control commands:
1. Disable / enable voltage
2. Emergency stop
3. Shut down
4. Enable operation
5. Switch on
6. Disable operation
7. Reset error
Coding of status:
1: Bit 0 = 0 2: Bit 6 = 1 3: Bit 0 = 1 4: Bit 1 = 1 5: Bit 2 = 1 6: Bit 5 = 0 7: Bit 2 & Bit 3 = 1 8: Bit 3 = 1
3
5
2 3
3 64
2
2
1
2
3
7
8
f = 0 reached (emergency stop complete)
Bit701
Error acknowledgement
Control bits
0. Standby / Shut dow n
1. Disable / enable voltage
2. Enable pulses / emergency stop
3. Disable / enable operation
4. Betriebsbedingung / HLGsperren
5. Enable / stop RUE
6. Enable / disable setpoint
7. Error acknowledgement (01)
10. Control data valid / invalid
11. Direction of rotation clockwise
12. Direction of rotation anticlockwise
14. Parameter set Bit 0
15. Parameter set Bit 1
4
5
6
Bit4 = 0: Move dow n emergency stop ramp and
remain in'Operation enabled'
Bit5 = 0: Hold frequency Bit6 = 0: Setpoint = 0%
Bit0 = 0: Shut down
5
Bit3 = 1: Enable operation
& Bit0 = 1: Switch on
2
Internal status machine
2
38 Subject to technical amendments BU 0050 GB-3111
Page 39
1.5 USS - Data transfer
NOTE
If parameter changes are made i.e. parameter identifier values (PKW), care must be taken that
the maximum number of permissible writing cycles to the frequency inverter EEPROM (100,000 cycles) is not exceeded. I.e. continuous cyclical writing must be prevented. For certain applications it is sufficient if the values are only saved in the RAM memory of the frequency inverter. For further details se Saving in the EEPROM under Parameter P560 in the frequency inverter manual.
1 2 3 4
PKE
IND
PWE1
PWE2
15
14
13
12
11
10 9 8 7 6 5 4 3 2 1 0
SPM
AK
PNU
1.5.4 Parameter range (PKW)
Using the PKW mechanism, parameter processing can be carried out in the cyclical data traffic. For this the master formulates an order and the inverter formulates the response to this. The parameter area is only used for transfer with PPO type 1 and PPO type 2.
In principle, the parameter range consists of a parameter identification, in which the type of order (Write, Read etc.) and the relevant parameters are specified. Individual parameter sets or array elements can be addressed with the aid of the Index. The parameter value contains the value to be written or read.
Note: A parameter order must be repeated until the inverter responds with the corresponding response
telegram.
1.5.4.1 Parameter label (PKE)
The order or response and the associated parameters are encrypted in the parameter label (PKE).
The parameter label (PKE) is always a 16 bit value. PNU: The bits 0 to 10 contain the number of the required parameter (PNU),or the number of the current
parameter in the response parameter from the inverter.
Note: For the inverter parameter numbers (PNU) of the particular inverter series please refer to the
relevant operating instructions for the inverter.
SPM: Bit 11 is the toggle-bit for spontaneous messages. This function is not supported! AK: Bits 12 to 15 contain the order or response label.
BU 0050 GB-3111 Subject to technical amendments 39
Page 40
NORD USS and Modbus RTU Manual
AK
Function
Response label positive
0
No order
0 1 Order parameter value
1 / 2
2
Change parameter value (word)
1
3
Change parameter value (double word)
2 4 Reserved
- 5 Reserved
-
6
Order parameter value (array)
4 / 5
7
Change parameter value (array word)
4
8
Change parameter value (array double word)
5
9
Order the number of array elements
6
10
Reserved
-
11
Change parameter value (array double word) without writing into EEPROM
5
12
Change parameter value (array word) without writing into EEPROM
4
13
Change parameter value (double word) without writing into EEPROM
2
14
Change parameter value (word) without writing into EEPROM
1
AK
Function
0
No response
1
Transfer parameter value (word)
2
Transfer parameter value (double word)*
4
Transfer parameter value (array word)
5
Transfer parameter value (array double word)*
7
Order cannot be executed (with error number in PWE2)
The following table lists all the orders which can be transferred from the master to the inverter. The right­hand column contains the response, which is normally sent (response label positive). Only certain response labels are possible, depending on the order label. In case of error (response label negative) the inverter will always supply the value 7 in the response label (AK) to the master.
Meaning of the values sent in the response label:
* Only for PPO type 2 and PPO type 4
As long as an order has not yet been executed, the inverter provides the response to the last order. Therefore the master must always check whether the received response matches the order sent. For the plausibility check, the value in the response label (AK), the received parameter number (PNU) with the corresponding Index (IND) as well as the current parameter value (PWE) can be used for the description of parameters.
40 Subject to technical amendments BU 0050 GB-3111
Page 41
1.5 USS - Data transfer
No.
Meaning
0
Invalid parameter number
1
Parameter value cannot be changed
2
Lower or upper value limit exceeded
3
Incorrect sub-index
4
No array
5
Invalid data type
6
Only resettable (only 0 may be written)
7
Description element cannot be changed
9
Description data not present
201
Invalid order element in the last order received
202
Internal response label cannot be depicted
1 2 3 4
PKE
IND
PWE1
PWE2
15
14
13
12
11
10 9 8 7 6 5 4 3 2 1 0
No information / all 0
P1-P4 Array 1-64
P1-P4
Sub-index
Array 1-256
Array element
Parameter set
Index
5 (000101
BIN
)
2 (01
BIN
)
15
HEX
= 0001 0101
BIN
21 (010101
BIN
)
4 (11
BIN
)
57
HEX
= 0101 0111
BIN
Error messages if the order cannot be executed If the response label is "Order cannot be executed" (AK = 7), then an error message is added to the
parameter value (PWE2) of the inverter response. For the meanings of the transferred values , please refer to the following table.
1.5.4.2 Sub-index (IND)
The structure and function of the parameter index (IND) depends on the type of parameter to be transferred. For values which depend on the parameter set, the parameter set can be selected via Bits 0 and 1 of the
Index (IND) (0 = parameter set 1, 1 = parameter set 2,...). If the parameter to be processed is also an array parameter (e.g. position array for the POSICON option),
then the sub-index of the required parameter can additionally be accessed via Bit 2 to Bit 7 of the sub-index (0 = array element 1, 1 = array element 2,…):
If a parameter is not dependent on the parameter set, then Bits 0 -7 are used for the sub-index. Please refer to the operating instructions for details of the structure of the individual parameters and which
values may be called up.
BU 0050 GB-3111 Subject to technical amendments 41
Page 42
NORD USS and Modbus RTU Manual
Baud rate
Interval
4800 Baud
100 ms
9600 Baud
50 ms
19200 Baud
25 ms
38400 Baud
15 ms
1.5.4.3 Parameter value (PWE)
According to the type of the PPO or parameter, transfer of the parameter value (PWE) is always as a word (16 Bit) or double word (32 Bit) Only one parameter value can be transferred in a telegram.
A 32 bit parameter value comprises PWE1 (high value word) and PWE2 (low value word, 4th word). A 16 Bit parameter value for PPO1 and PPO2 is transferred in PWE2. For negative values the High word
must be set to FFFF hex. Note: 32-Bit parameter values are only used with the POSICON option. All the relevant parameters are
described in the POSICON supplementary manual.
The parameter value is transferred as an integer value. For parameters with resolutions 0.1 or 0.01 the parameter value must be multiplied by the inverse of the resolution.
Example: A start-up time of 99.99 seconds is to be set:
99.99s 99,99 * 1/0.01 = 99.99 * 100 = 9999. Therefore the value 9999
= 270F
dec
must be transferred.
hex
1.5.4.4 Master Function Output
With a setting in parameter P503, the inverter control signals (digital and/or analog) which are to be output as a bradcast telegram (type PPO3/PPO4) in USS protocol format via the RS 485 interface can be selected. The control source is still selected in P509. The transfer intervals depend on the USS baud rate which is set:
42 Subject to technical amendments BU 0050 GB-3111
Page 43
1.6 USS – Telegram examples
1.6 Telegram examples
Various example telegrams are shown below to clarify the control and parameterisation of the frequency inverter with the USS protocol.
Note: When transferring parameter orders, it must be taken into account that the slave does not
immediately respond to orders in the parameter channel of the master telegram, but a positive response can be delayed by one or more communication cycles. The master must therefore repeat the required order until the corresponding slave response is received.
The macro generator of the NORD CON control and parameterisation software is used as a programming aid. The macro generator is started directly from the NORD CON program via the menu bar.
1.6.1 The Macro Generator
Simple process sequences can be simulated with the aid of the macro generator. This can used for instance, for testing during commissioning. Parameterisation of the devices is also possible. The individual telegrams of a macro are shown in hexadecimal format. This information can be used to create control programs based on the USS protocol.
A macro can consist of several steps. The telegram wich is transferred to the inverter can be observed in the Hex view in the overview. A sub-menu provides help for creating the individual steps.
USS address Control word Setpoint Parameter number Parameter index Parameter value Order
Together, all of these steps comprise a step in the macro The telegram structure in the Hex view of each individual step is shown in the Macro window.
BU 0050 GB-3111 Subject to technical amendments 43
Page 44
NORD USS and Modbus RTU Manual
Byte No.
0 1 2 3 4 5 6 7 8
9
10
11
12
13
Meaning
STX
LGE
ADR
PKE
PKE
IND
IND
PWE
PWE
ZSW
ZSW
IW1
IW1
BCC
Hexadecimal
02
0C
00
00
00
00
00
00
00
0B
70
00
00
75
Bit
Value
Value
HEX
Meaning
15
0 0 Parameter set Bit 1 off
14 0 Parameter set Bit 0 off
13 0 Reserved
12 0 Rotation left is off
11
1 B Rotation right is on
10 0 Reference value undershot
9 1 Bus controller
8 1 Setpoint = actual value
7
0 7 No warning
6 1 Starting disabled
5 1 No emergency stop
4 1 Disable voltage
3
0 0 No fault
2 0 Operation disabled
1 0 Not ready for operation
0 0 Not on standby
0 1 2 3 4 5 6 7 8
9
10
11
12
13
STX
LGE
ADR
PKE
PKE
IND
IND
PWE
PWE
STW
STW
SW1
SW1
BCC
02
0C
00
00
00
00
00
00
00
04
7E
00
00
74
Abbreviations used:
PKW Parameter identifier Value PZD Process data PKE Parameter identifier IND Index PWE Parameter Value STW Control word 1 ZSW Status word 1 SW1..3 Setpoint IW1..3 Actual value
1.6.2 Switch-on block Standby
A frequency inverter with the USS address 0 is to be switched from the status "Switch-on disabled" (STW Bit 0 – 0), which is active when the device is switched on, to the "Standby" status (STW Bit 0 = 1). Parameter set 1 is valid and no parameter data is transfered.
Procedure:
Check last status word (ZSW 0A 70) Set address (Address 00) Generate control word (STW 04 7E) Send telegram Check response telegram (ZSW 0B 31)
Details:
The status word of frequency inverter is in switch-on block status
To switch the frequency inverter to the standby status, the following telegram must be sent:
44 Subject to technical amendments BU 0050 GB-3111
Page 45
1.6 USS – Telegram examples
0 1 2 3 4 5 6 7 8
9
10
11
12
13
STX
LGE
ADR
PKE
PKE
IND
IND
PWE
PWE
ZSW
ZSW
IW1
IW1
BCC
02
0C
00
00
00
00
00
00
00
0B
31
00
00
34
Bit
Value
Value
HEX
Meaning
15
0 0 Parameter set Bit 1 off
14 0 Parameter set Bit 0 off
13 0 Reserved
12 0 Rotation left is off
11
1 B Rotation right is on
10 0 Reference value undershot
9 1 Bus controller
8 1 Setpoint = actual value
7
0 3 No warning
6 0 Starting not disabled
5 1 No emergency stop
4 1 Enable voltage
3
0 1 No fault
2 0 Operation disabled
1 0 Not ready for operation
0 1 Ready to start
When the frequency inverter switches to standby status, it sends the following response telegram:
Note: The control telegram must be sent cyclically as the frequency inverter may not switch to the
required status within the response time of a telegram.
BU 0050 GB-3111 Subject to technical amendments 45
Page 46
NORD USS and Modbus RTU Manual
0
1 2 3 4 5 6 7
8
9
10
11
12
13
STX
LGE
ADR
PKE
PKE
IND
IND
PWE
PWE
ZSW
ZSW
IW1
IW1
BCC
02
0C
0A
00
00
00
00
00
00
0B
31
00
00
37
0
1 2 3 4 5 6 7
8
9
10
11
12
13
STX
LGE
ADR
PKE
PKE
IND
IND
PWE
PWE
STW
STW
SW1
SW1
BCC
02
0C
0A
00
00
00
00
00
00
04
7F
20
00
5F
0
1 2 3 4 5 6 7
8
9
10
11
12
13
STX
LGE
ADR
PKE
PKE
IND
IND
PWE
PWE
ZSW
ZSW
IW1
IW1
BCC
02
0C
0A
00
00
00
00
00
00
0F
37
20
00
1C
1.6.3 Enable with 50% setpoint
A frequency inverter with the USS address 10, which is in "Standby" status (Section 1.6.2) is to be enabled for clockwise rotation with 50% setpoint. The last response telegram was received as follows in the controller.
Procedure:
Check last status word (ZSW 0A 31) Set address (Address 0A) Generate control word (STW 04 7F) Generate setpoint (2000 hex) Send telegram Check response telegram (ZSW 0F 37)
Details:
Starting requirement (status word of frequency inverter)
The following telegram must be sent to the inverter
The frequency inverter accelerates the motor in the ramp. When the inverter has reached the 50% setpoint, it responds with the following telegram.
Note: The status of MFR 1 is indicated in Bit 10 of the response telegram. Depending on the
programmed function and status, the status word may differ.
46 Subject to technical amendments BU 0050 GB-3111
Page 47
1.6 USS – Telegram examples
0
1
2 3 4 5 6 7 8 9 10
11
12
13
14
15
STX
LGE
ADR
PKE
PKE
IND
IND
PWE
PWE
PWE
PWE
STW
STW
SW1
SW1
BCC
02
0E
03
20
66
00
01
00
00
03
E8
00
00
00
00
80
0
1
2 3 4 5 6 7 8 9 10
11
12
13
14
15
STX
LGE
ADR
PKE
PKE
IND
IND
PWE
PWE
PWE
PWE
ZSW
ZSW
IW1
IW1
BCC
02
0E
03
10
66
00
01
00
00
03
E8
09
31
00
00
88
1.6.4 Writing a parameter
When transferring parameter orders, it must be taken into account that the slave does not immediately respond to orders in the parameter channel of the master telegram, but a positive response can be delayed by one or more communication cycles. The master must therefore repeat the required order until the corresponding slave response is received.
The acceleration time parameter (USS No. = 102 to be set to the value 10sec in parameter set 2. No process data is transferred.
As the acceleration time has an internal inverter resolution of 0.01sec, a parameter value of 10 / 0.01 = 1000 (3E8
) must be transferred. PPO1 was selected as the PPO type.
hex
Procedure:
Set address (Address 03) Select parameter (P 102
dec
/ P 66
hex
)
Select order label (2 = change parameter value (word)) Select parameter set 2 (IND = 01) Set parameter word (1000
dec
/ 3E8
HEX
)
Send telegram Check response telegram
The telegram is composed as follows in hexadecimal notation:
dec
/ 66
) of a frequency inverter with the USS address 3, is
hex
When the order has been fully implemented by the inverter, it responds with
BU 0050 GB-3111 Subject to technical amendments 47
Page 48
NORD USS and Modbus RTU Manual
0
1
2 3 4 5 6
7 8 9
10
11
12
13
STX
LGE
ADR
PKE
PKE
IND
IND
PWE
PWE
STW
STW
SW1
SW1
BCC
02
0C
03
10
66
00
01
00
00
00
00
00
00
7A
0
1
2 3 4 5 6 7 8
9
10
11
12
13
STX
LGE
ADR
PKE
PKE
IND
IND
PWE
PWE
ZSW
ZSW
IW1
IW1
BCC
02
0C
03
10
66
00
01
03
E8
0B
31
20
00
A8
1.6.5 Reading the acceleration time parameter
The acceleration time parameter (USS No. = 102
dec
/ 66
) in parameter set 2 of a frequency inverter with the
hex
USS address 3, is to be read out. No process data is transferred.
Procedure:
Set address (Address 03) Generate parameter label (PKE 10 66) Select parameter set 2 (IND = 01) Send telegram Check response telegram (PWE = 3E8)
Details:
The response telegram of the slave contains the required parameter value in internal standardisation and could be as follows:
The value sent in PWE2 is C8
corresponding to 1000
HEX
corresponds to an acceleration time of 1000 * 0.01 = 10 seconds
10 / 0.01 = 1000 (3E8
, with a resolution of 0.01 seconds, this
DEC
)
hex
48 Subject to technical amendments BU 0050 GB-3111
Page 49
1.7 USS - Master- Telegram times
Baud
rate
PPO type
Telegram
Bytes
Start pause
time
[msec]
Minimum total
run time
[msec]
Maximum run
time
[msec]
Response delay
time
[msec]
4800
PPO0
14
4,583
32,083
48,1
4,583
4800
PPO1
16
4,583
36,667
55
4,583
4800
PPO2
20
4,583
45,833
68,8
4,583
4800
PPO3 8 4,583
18,333
27,5
4,583
4800
PPO4
12
4,583
27,5
41,3
4,583
9600
PPO0
14
2,292
16,042
24,1
2,292
9600
PPO1
16
2,292
18,333
27,5
2,292
9600
PPO2
20
2,292
22,917
34,4
2,292
9600
PPO3 8 2,292
9,167
13,8
2,292
9600
PPO4
12
2,292
13,75
20,6
2,292
19200
PPO0
14
1,146
8,021
12
1,146
19200
PPO1
16
1,146
9,167
13,8
1,146
19200
PPO2
20
1,146
11,458
17,2
1,146
19200
PPO3 8 1,146
4,583
6,9
1,146
19200
PPO4
12
1,146
6,875
10,3
1,146
38400
PPO0
14
0,573
4,01 6 0,573
38400
PPO1
16
0,573
4,583
6,9
0,573
38400
PPO2
20
0,573
5,729
8,6
0,573
38400
PPO3 8 0,573
2,292
3,4
0,573
38400
PPO4
12
0,573
3,438
5,2
0,573
1.7 Master Telegram Times
The telegram times to be monitored depend on the currently valid baud rate and the telegram length. For the data format: 8E1, the following running times apply:
The start pause time and the typical response delay time are determined by the transfer time for two bytes of data. The maximum response time provided by the telegram is 20msec.
The total run time in the table is the consecutive telegram run time, i.e. the stop bit of the last character immediately follows the start character of the next character. However, in practice there are time delays between the bytes of a telegram. Therefore the factor 1.5 is used for the maximum telegram run time.
Maximum total run time = 1-5 * consecutive telegram run time
The interface driver software must check or maintain compliance with the following telegram parameters and trigger an error if they are repeatedly overshot:
Telegram length details of the received telegram (LGE) Telegram format (start character / STX, check-sum / BCC) Character format (parity, start and stop bit) Total run time of the slave response
Response delay time (typical transfer duration for 2 bytes, max 20 msec)
BU 0050 GB-3111 Subject to technical amendments 49
Page 50
NORD USS and Modbus RTU Manual
Parameter
Setting value / Description / Note
Comments
P480 ..[-01] ... .. [-12]
Function BusIO In Bits
(Function of Bus I/O In Bits)
0 ... 72 { 0 }
The Bus I/O In Bits are perceived as digital inputs. They can be set to the same functions as the digital inputs (See P420…of the respective FI manual).
[-01]= Bus I/O In Bit 0 [-02]= Bus I/O In Bit 1 [-03]= Bus I/O In Bit 2 [-04]= Bus I/O In Bit 3 [-05]= Bus I/O In Bit 4 [-06]= Bus I/O In Bit 5
[-07]= Bus I/O In Bit 6 [-08]= Bus I/O In Bit 7 [-09]= Flag 1 (only SK 500E) [-10]= Flag 2 (only SK 500E) [-11]= Bit 8 BUS control word (only for SK 500E) [-12]= Bit 9 BUS control word (only for SK 500E)
P481 .. [-01] ... .. [-10]
Function BusIO Out Bits
(Function of Bus I/O Out Bits)
0 ... 39 { 0 }
The bus I/O Out bits are perceived as multi-function relay outputs. They can be set to the same functions as the digital inputs (See P434…of the respective FI manual).
[-01]= Bus I/O Out Bit 0 [-02]= Bus I/O Out Bit 1 [-03]= Bus I/O Out Bit 2 [-04]= Bus I/O Out Bit 3 [-05]= Bus I/O Out Bit 4 [-06]= Bus I/O Out Bit 5
[-07]= Bus I/O Out Bit 6 / Flag 1 [-08]= Bus I/O Out Bit 7 / Flag 2 [-09]= Bit 10 BUS status word (only for SK 500E) [-10]= Bit 13 BUS status word (only for SK 500E)
P482 .. [-01] ... .. [-10]
Stand. BusIO Out Bits
(Standardisation of Bus I/O Out Bits)
-400 … 400 % { 100 }
Adjustment of the limit values of the relay functions/Bus Out Bits. For a negative value, the output function will be output negative.
When the limit value is reached and the setting values are positive, the relay contact closes, with negative setting values the relay contact opens.
P483 .. [-01] ... .. [-10]
Hyst. BusIO Out Bits
(Hysteresis of Bus I/O Out Bits)
1 … 100 % { 10 }
Difference between switch-on and switch-off point to prevent oscillation of the output signal.
1.8 Frequency Inverter Settings
1.8.1 Frequency inverter bus parameters
To operate the inverter with the USS protocol, the bus must be connected to the master and some settings must be made on the frequency inverter.
The frequency inverter can always be parameterised. Control of the inverter via USS can be activated by setting parameter P509 to value 2, 3 or 4 (for SK 500E to 2) (see below). In order to access the inverter via the control unit, only the baud rate in P511 and the inverter address P512 need to be set.
The telegram down time P513 can be selected depending on the USS system.
1.8.1.1 Control clamp parameters
50 Subject to technical amendments BU 0050 GB-3111
Page 51
1.8.1.2 Extra functions
Parameter
Setting value / Description / Note
Comments
P502 ... [-01]
... [-05]
Master function value
(Master function value)
SK 5xxE
1 ... 24 { 0 }
Selection of master values (up to SK 535E: max. 3 master values, SK 540 and above: max. 5 master values:
[-01] = Master value 1
[-02] = Master value 2
[-03] = Master value 3
SK 540E and above:
[-04] = Master value 4
[-05] = Master value 5
Selection of possible setting values for master values:
0 = Off 1 = Actual frequency 2 = Actual speed 3 = Current 4 = Torque current 5 = State of digital inputs
and outputs
6 = Reserved 7 = Reserved 8 = Setpoint frequency
9 = Error message 10 = Reserved 11 = Reserved 12 = Digital Out Bit 0…7 13 = Reserved 14 = Reserved 15 = Reserved 16 = Reserved 17 = Value analog input 1 18 = Value analog input 2
19 = Setpoint frequency
master value
20 = Setpoint frequency after
master value ramp
21 = Actual frequency without
master value slip
22 = Speed encoder 23 = Actual freq. with slip
(from SW V2.0)
24 = Master value, act. freq.
with slip
(from SW V2.0)
P503
Master function output
(Master function output)
SK 300E, SK 700E, SK 750E
1 ... 6 { 0 }
To use the master function output, the inverter controller source must be selected in P509. Only the master frequency (setpoint 1 and control word) is transferred with Mode 1, while the actual values selected in P543, P544 and P545 are transferred in Mode 2.
In Mode 3 a 32Bit actual position and a 16Bit setpoint speed (after ramp) is output. Mode 3 is required for synchronous control with the POSICON option.
0 = Off 1 = USS mode 1 2 = CAN Mode 1
up to 250kBaud
3 = USS mode 2 4 = CAN Mode 2
up to 250kBaud
5 = USS mode 3 6 = CAN Mode 3
P503
Master function output
(Master function output)
SK 5xxE
1 ... 5 { 0 }
To use the Master function output, the inverter controller source must be selected in P509. The master value to be transmitted is determined via the BUS interface in parameter P502.
0 = Off
1 = USS
2 = CAN (up to 250kBaud)
3 = CANopen
4 = System bus active
5 = CANopen+Sys.bus act.
P507
PPO Type
(PPO Type)
1 ... 4 { 1 }
Type of PPO used (see Section 1.5.2 6)
1.8 USS – Frequency inverter settings
BU 0050 GB-3111 Subject to technical amendments 51
Page 52
NORD USS and Modbus RTU Manual
Parameter
Setting value / Description / Note
Comments
P509
Interface
(interface)
SK 300E, SK 700E, SK 750E
0 ... 21 { 0 }
Selection of the interface from which the inverter is controlled.
0 = Control terminal or keyboard control with the Control Box (option) ,the ParameterBox
(option) or the Potentiometer option
1 = Control terminals only, the inverter can only be controlled via the 4 digital inputs and the
analog input.
2 = USS setpoint, the frequency setpoint is transferred via the USS protocol. Control via the
digital inputs is still active.
3 = USS control word, the control signals (enable, direction of rotation, ...) are transferred via
USS, the setpoint via the analog input or the fixed frequencies.
4 = USS, all control data is transferred via the USS protocol. The analog input and the digital
inputs have no function (except safety functions, see below)
5 =
P509
Control word source
(Control word source)
SK 5xxE
0 ... 10 { 0 }
Selection of the interface via which the FI is controlled.
0 = Control terminal or keyboard control with the Control Box (if P510=0), the
ParameterBox (not extension parameter box) or via BUS I/O Bits.
1 = Only control terminals , the FI can only be controlled via the digital and analog inputs or
via the bus I/O Bits.
2 = USS control word: the control signals (enable, direction of rotation, ...) are transferred via
the RS485 interface. The setpoint is transferred via the analog input or the fixed frequencies. Above SK 540E this setting should also be selected if communication via Modbus RTU is intended. The frequency inverter automatically detects whether this is a USS protocol or a Modbus protocol.
3 =
P510
Aux. setpoint interface
(Auxiliary setpoints interface)
SK 700E, SK 750E
0 ... 8 { 0 }
Selection of the interface from which the inverter is controlled.
0 = Auto: The auxiliary setpoint value is automatically
taken from the interface of the main setpoint value P509 >interface<
1 = USS 2 = CANbus 3 = Profibus
4 = InterBus 5 = CANopen 6 = DeviceNet 7 = Reserved 8 = CAN Broadcast
P510 ... [-01] ... [-02]
Setpoints source
(Setpoints source)
SK 5xxE
0 ... 10 { 0 }
Selection of the setpoint source to be parameterised.
[-01] = Main setpoint source
[-02] = Auxiliary setpoint source
Selection of the interface via which the FI receives the setpoint.
0 = Auto: the source of the auxiliary
setpoint is automatically derived from the setting in the parameter P509 >Interface<
1 = Control terminals, digital and analog
inputs control the frequency, including fixed frequencies
2 = USS (or Modbus RTU above SK 540E)
3 = CAN
4 = Profibus
5 = InterBus
6 = CANopen
7 = DeviceNet
8 = EtherCAT
9 = CAN Broadcast 10 = CANopen Broadcast
52 Subject to technical amendments BU 0050 GB-3111
Page 53
1.8 USS – Frequency inverter settings
Parameter
Setting value / Description / Note
Comments
P511
USS baud rate
(USS baud rate)
0 ... 7 { 3 }
Setting of the transfer rate (transfer speed) via the RS485 interface. All bus participants must have the same baud rate setting.
0 = 4800 Baud
1 = 9600 Baud
2 = 19200 Baud
3 = 38400 Baud
4 = 57600 Baud (SK 54xE)
5 = 115200 Baud (SK 54xE)
6 = 230400 Baud (SK 54xE)
7 = 460800 Baud (SK 54xE)
NOTE: For communication via Modbus (available for SK 540E and above) a transfer rate of
maximum 38400 Baud must be set.
P512
USS Address
(USS Address)
0 ... 30 { 0 }
Setting of the FI bus address for USS (or SK 540E and above: also Modbus) communication.
P513
Telegram downtime
(Telegram downtime)
-0.1 / 0.0 /
0.1 ... 100.0 s { 0.0 }
Monitoring function of the active bus interface. Following receipt of a valid telegram, the next one must arrive within the set period. Otherwise the FI reports an error and switches off with the error message E010 >Bus Time Out<.
0.0 = Off: Monitoring is switched off.
-0.1 = No error: Even if communication between BusBox and FI is interrupted (e.g. 24V error,
Box removed, etc.), the FI will continue to operate unchanged.
BU 0050 GB-3111 Subject to technical amendments 53
Page 54
NORD USS and Modbus RTU Manual
Parameter
Setting value / Description / Note
Comments
P543 (P)
Bus – Actual value 1
(Bus – Actual value 1)
0 ... 12 (24) { 1 }
The return value 1 (IW1) can be set for bus control in this parameter.
SK 300E, SK 700E SK 750E
0 = Off 1 = Actual frequency
2 = Actual speed 3 = Current 4 = Torque current 5 = Status of digital inputs and relay 6 = Actual position (only POSICON,
SK700/750E)
7 = Setpoint position (only POSICON,
SK700/750E)
8 = Setpoint frequency 9 = Error number 10 = Actual position increment 1 (only
POSICON, SK700/750E)
11 = Setpoint position increment 1 (only
POSICON, SK700/750E)
12 = BUS I/O Out Bits 0-7
SK 500E
0 = Off 1 = Actual frequency 2 = Actual speed 3 = Current 4 = Torque current (100% = P112) 5 = State of digital inputs and outputs2 6 = Actual position Low word 7 = Setpoint position Low word 8 = Setpoint frequency
9 = Error number 10 = Actual position increment Low word 11 = Setpoint position increment Low word 12 = Bus I/O Out Bits 0...7 13 = Actual position High word 14 = Setpoint position High word 15 = Actual position increment High word 16 = Setpoint position increment High word 17 = Value analog input 1 (P400) 18 = Value analog input 2 (P405) 19 = Setpoint frequency master value (P503) 20 = Setpoint frequency after master value ramp 21 = Actual frequency without master value slip 22 = Speed from encoder
(only possible with SK 52x/53xE and encoder feedback)
23 = Actual frequency with slip, "Actual frequency
with slip"
24 = Master value, actual freq. with slip, "Master
value, actual freq. with slip"
NOTE: For SK 540 and SK545E 5 actual values are available. These are all set in
parameter P543, which is divided into 5 array elements for this purpose. Parameters P544 and P545 are not required for this inverter version.
[-01] = Actual bus value 1
[-02] = Actual bus value 2
[-03] = Actual bus value 3
[-04] = Actual bus value 4
[-05] = Actual bus value 5
P544 (P)
Actual bus value 2
(Actual bus value 2)
except SK 54xE
0 ... 12 (24) { 0 }
The return value 2 (IW2) can be set for bus control in this parameter. For setting values, see parameter (P543)
P545 (P)
Actual bus value 3
(Actual bus value 3)
except SK 54xE
0 ... 12 (24) { 0 }
In this parameter, the return value 3 (IW3) can be set for bus control. This is only available if P546 3 (only applies for SK 700E / SK 750E).
For setting values, see parameter (P543)
1
2
An indicated revolution of the motor results from 8192 encoder increments.
The assignment of the digital inputs in P543/ 544/ 545 = 5
Bit 0 = DigIn 1 Bit 1 = DigIn 2 Bit 2 = DigIn 3 Bit 3 = DigIn 4 Bit 4 = DigIn 5 Bit 5 = DigIn 6 Bit 6 = DigIn 7 Bit 7 = Reserved Bit 8 = Reserved Bit 9 = Reserved Bit 10 = Reserved Bit 11 = Reserved Bit 12 = Out 1 Bit 13 = Out 2 Bit 14 = Out 3 Bit 15 = Out 4
54 Subject to technical amendments BU 0050 GB-3111
Page 55
1.8 USS – Frequency inverter settings
Parameter
Setting value / Description / Note
Comments
P546 (P)
Function Bus setpoint 1
(Function of bus setpoint 1)
0 ... 7 (47) { 1 }
In this parameter, a function is assigned to the delivered setpoint 1 (SW1) for bus control.
NOTE: Further details can be found in the respective FI manual or in the description of P400.
SK 300E, SK 700E SK 750E
0 = Off 1 = Setpoint frequency (16 bit) 2 = 16 Bit setpoint position
(only POSICON SK700/750E)
3 = 32 Bit setpoint position
(only POSICON, SK700/750E and if PPO- type 2 or 4 are selected)
4 = Control terminals POSICON (only
POSICON, SK700/750E, 16Bit)
5 = Setpoint position (16 Bit) increment 1
(onlyPOSICON, SK700/750E)
6 = Setpoint position (32 Bit) increment 1
(onlyPOSICON, SK700/750E)
7 = Bus IO In Bits 0-7
SK 500E
0 = Off 1 = Setpoint frequency (16 bit) 2 = Torque current limit (P112) 3 = Actual frequency PID 4 = Frequency addition 5 = Frequency subtraction 6 = Current limit (P536) 7 = Maximum frequency (P105) 8 = Actual PID frequency limited 9 = Actual PID frequency monitored
(SK 530E and above) (SK 530E and above) (SK 530E and above) (SK 530E and above)
NOTE: For SK 540 and SK545E 5 setpoints are available. These are all set in parameter
P546, which is divided into 5 array elements for this purpose. Parameters P547 and P548 are not required for this inverter version.
[-01] = Bus setpoint 1
[-02] = Bus setpoint 2
[-03] = Bus setpoint 3
[-04] = Bus setpoint 4
[-05] = Bus setpoint 5
P547 (P)
Function Bus setpoint 2
(Function of bus setpoint 2)
except SK 54xE
0 ... 46 (47) { 0 }
In this parameter, a function is assigned to the delivered setpoint 2 (SW2) for bus control.
0 = Off 1 = Setpoint frequency 2 = Torque current limit (P112) 3 = Actual frequency PID 4 = Frequency addition 5 = Frequency subtraction 6 = Current limit (not SK 300E) 7 = Maximum frequency (not SK 300E) 8 = Actual PID frequency limited 9 = Actual PID frequency monitored 10 = Torque (not SK 300E) 11 = Torque lead (not SK 300E) 12 = Control terminals POSICON (not
SK 300E)
13 = Multiplication (not SK 300E) 14 = PI process controller actual value
15 = PI process controller setpoint 16 = PI process controller lead 17 = Digital In bits 0...7 18 = Curve travel calculator (not SK 300E) 19 = Set relay 20 = Set analog output 21 = Setpoint position Low word
(SK 530E and above)
22 = Setpoint position High word
(SK 530E and above)
23 = Setpoint position increment Low word
(SK 530E and above)
24 = Setpoint position increment High word
(SK 530E and above)
25 = ... 45 reserved
46 = Setpoint, torque process controller
(not SK 300E)
47 = Gearing transfer factor (only SK 500E)
BU 0050 GB-3111 Subject to technical amendments 55
Page 56
NORD USS and Modbus RTU Manual
Parameter
Setting value / Description / Note
Comments
P548 (P)
Function Bus setpoint 3
(Function of bus setpoint 3)
except SK 54xE
0 ... 46 (47) { 0 }
In this parameter, a function is assigned to the delivered setpoint 3 (SW3) for bus control. This is only available if P546 3 (only applies for SK 700E / SK 750E).
For setting values, see parameter (P547)
NOTE
As of firmware version V1.9 R0 for the SK 500E series, not only current error messages but also warnings and information messages can be displayed via the parameter. In this context, the parameter (P700) has been converted into an array parameter. I.e. error messages are displayed in (P700 [-01]), warnings in (P700[-02]), and information in (P700 [-03]).
For all other series (SK 300E, SK 700E, SK 750E), parameter (P700) still only indicates error messages.
Parameter
Setting value / Description / Note
Comments
P740 ... [-01] ... [-06]
Process data Bus In
(Process data Bus In)
SK 300E, SK 700E, SK 750E
0000 ... FFFF (hex)
Displays the actual control word and the setpoints.
[-01] = Control word [-02] = Setpoint 1 (P546) [-03] = Setpoint 1 High byte [-04] = Setpoint 2 (P547) [-05] = Setpoint 3 (P548) [-06] = Bus I/O In Bits (P480)
P740 ... [-01] ... [-13]
Process data Bus In
(Process data Bus In)
SK 500E to SK 535E
0000 ... FFFF (hex)
This parameter informs about the actual control word and the setpoints that are transferred via the bus systems.
[-01 ] = Control word
Control word, source from P509.
[-02] = Setpoint 1 [-03] = Setpoint 2 [-04] = Setpoint 3
Setpoint data from main setpoint P510 - 01.
[-05] = Bus I/O In Bits (P480)
The displayed value depicts all Bus In bit sources linked with OR.
[-06] = Parameter data In 1 [-07] = Parameter data In 2 [-08] = Parameter data In 3 [-09] = Parameter data In 4 [-10] = Parameter data In 5
Data during parameter transfer.
[-11] = Setpoint 1 [-12] = Setpoint 2 [-13] = Setpoint 3
Setpoint data from auxiliary setpoint P510 - 02.
1.8.1.3 Information parameters
56 Subject to technical amendments BU 0050 GB-3111
Page 57
1.8 USS – Frequency inverter settings
Parameter
Setting value / Description / Note
Comments
P740 ... [-01] ... [-23]
Process data Bus In
(Process data Bus In)
SK 540E / SK 545E
0000 ... FFFF (hex)
This parameter informs about the actual control word and the setpoints that are transferred via the bus systems.
For display, a BUS system must be selected in P509
[-01 ] = Control word
Control word, source from P509.
[-02] = Setpoint 1 [-03] = Setpoint 2 [-04] = Setpoint 3 [-05] = Setpoint 4 [-06] = Setpoint 5
Setpoint data from main setpoint (P510 [-01]).
[-07] = Bus I/O In Bits (P480)
The displayed value depicts all Bus In bit sources linked with OR.
[-08] = Parameter data In 1 [-09] = Parameter data In 2 [-10] = Parameter data In 3 [-11] = Parameter data In 4 [-12] = Parameter data In 5
Data during parameter transfer: Order label (AK),Parameter number (PNU),Index (IND), Parameter value (PWE 1/2)
[-13] = Setpoint 1 [-14] = Setpoint 2 [-15] = Setpoint 3 [-16] = Setpoint 4 [-17] = Setpoint 5
Setpoint data from the master function value (Broadcast), if P509 = 9/10 (P510 [-02])
[-18] = Control word PLC
Control word, source PLC
[-19] = Setpoint 1 [-20] = Setpoint 2 [-21] = Setpoint 3 [-22] = Setpoint 4 [-23] = Setpoint 5
Setpoint data from the PLC.
P741 ... [-01] ... [-06]
Process data Bus Out
(Process data Bus Out)
SK 300E, SK 700E, SK 750E
0000 ... FFFF (hex)
Displays the actual status word and actual values.
[-01] = Status word [-02] = Actual value 1 (P543) [-03] = Actual value 1 High byte [-04] = Actual value 2 (P544) [-05] = Actual value 3 (P545) [-06] = Bus I/O Out Bits (P481)
BU 0050 GB-3111 Subject to technical amendments 57
Page 58
NORD USS and Modbus RTU Manual
Parameter
Setting value / Description / Note
Comments
P741 ... [-01] ... [-13]
Process data Bus Out
(Process data Bus Out)
SK 500E to SK 535E
0000 ... FFFF (hex)
This parameter provides information about the actual status word and the actual values that are transferred via the bus systems.
[-01] = Status word
Status word, source from P509.
[-02] = Actual value 1 (P543) [-03] = Actual value 2 (P544) [-04] = Actual value 3 (P545)
[-05] = Bus I/O Out Bit (P481)
The displayed value depicts all Bus In bit sources linked with OR.
[-06] = Parameter data Out 1 [-07] = Parameter data Out 2 [-08] = Parameter data Out 3 [-09] = Parameter data Out 4 [-10] = Parameter data Out 5
Data during parameter transfer.
[-11] = Actual value 1 master function [-12] = Actual value 2 master function [-13] = Actual value 3 master function
Actual value of master function 502/P503.
P741 ... [-01] ... [-23]
Process data Bus Out
(Process data Bus Out)
SK 540E / SK 545E
0000 ... FFFF (hex)
This parameter provides information about the actual status word and the actual values that are transferred via the bus systems.
[-01] = Status word
Status word, source from P509.
[-02] = Actual value 1 (P543 [-01]) [-03] = Actual value 2 (P543 [-02]) [-04] = Actual value 3 (P543 [-03]) [-05] = Actual value 4 (P543 [-04]) [-06] = Actual value 5 (P543 [-05])
[-07] = Bus I/O Out Bit (P481)
The displayed value depicts all Bus In bit sources linked with OR.
[-08] = Parameter data Out 1 [-09] = Parameter data Out 2 [-10] = Parameter data Out 3 [-11] = Parameter data Out 4 [-12] = Parameter data Out 5
Data during parameter transfer.
[-13] = Actual value 1 master function [-14] = Actual value 2 master function [-15] = Actual value 3 master function [-16] = Actual value 4 master function [-17] = Actual value 5 master function
Actual value of master function 502/P503. [-18] = Status word PLC
Status word via PLC
[-19] = Actual value 1 PLC [-20] = Actual value 2 PLC [-21] = Actual value 3 PLC [-22] = Actual value 4 PLC [-23] = Actual value 5 PLC
Actual value data via PLC
58 Subject to technical amendments BU 0050 GB-3111
Page 59
1.8 USS – Frequency inverter settings
Parameter
Setting value / Description / Note
Comments
P742
Database version
(Database version)
0 ... 9999
Displays the internal database version of the FI.
P744
Configuration level
(Configuration level)
SK 300E, SK 700E, SK 750E
0 ... 9999
This parameter displays the option modules detected by the FI. The display with the ParameterBox is in plain text. The possible combinations are displayed in code in the ControlBox. Both right digits indicate the
customer unit used and the two left digits indicate the special extension unit. The options vary depending on the FI type.
Customer Unit SK CU1-
Special extension unit SK XU1-...
No IO XX00 Basic IO XX01 Standard IO XX02 Multi IO XX03 USS IO XX04 CAN IO XX05 Profibus IO XX06
Encoder 01XX POSICON 02XX
P744
Configuration level
(Configuration level)
SK 5xxE
0000 ... FFFF (hex)
This parameter displays the design status integrated in the FI. Display is in hexadecimal code (SimpleBox, ControlBox, Bus system).
The display is in plain text when the ParameterBox is used.
SK 500E … 515E = 0000 SK 520E = 0101
SK 530E … 535E = 0201 SK 540E … 545E = 0301
P745
Module version
(Module version)
SK 300E, SK 5xxE
0.0 ... 3276.7
Design status (software version) of the technology unit (SK TU2/3-xxx), but only when a separate processor is present, therefore not for SK TU2/3-CTR.
Have this data available if you have a technical query.
P745 ...[-01] ... [-03]
Module version
(Module version)
SK 700E, SK 750E
0.0 ... 3276.7
Software version of the installed module [-01] Technology unit [-02] Customer Unit [-03] Special Extension Unit
BU 0050 GB-3111 Subject to technical amendments 59
Page 60
NORD USS and Modbus RTU Manual
Parameter
Setting value / Description / Note
Comments
P746
Module status
(Module status)
SK 300E, SK 5xxE
0000 ... FFFF (hex)
Indicates the actual status (readiness, error, communication) of the technology unit (SK TU2/3-xxx), but only when own processor is present, therefore not for the SK TU2/3-CTR.
Code details can be found in the respective BUS module manual. Different contents are shown depending on the modules.
P746 ... [-01] ... [-03]
Module status
(Module status)
SK 700E, SK 750E
0000 ... FFFF (hex)
Status of integrated modules [-01] Technology unit [-02] Customer Unit [-03] Special Extension Unit
NOTE
When activated, the functions block current, quick stop, remote control and cancel error are available at the (local) control terminals. To operate the drive, a high signal must be present on the digital inputs being used before the drive can be enabled.
60 Subject to technical amendments BU 0050 GB-3111
Page 61
2.2 Modbus RTU - Features
2 Modbus RTU
(SK 540E and above)
2.1 The bus system
Modbus is an open communication protocol, which is based on a Master/Slave architecture. The bus system must be set up in a linear configuration, whose ends are terminated with terminating resistors. In principle, up to 256 participants are possible within a bus system. These communicate with each other via RS485.
2.2 Features
As standard, frequency inverters of version SK 540E and above provide the Modbus in version Modbus RTU <8, E, 1>. Installation is by means of a two-core cable with an additional GND connection.
Electrically isolated bus interface Modbus RTU <8, E, 1> up to 32 participants can be connected to a segment (communication via RS485) Point to point communication (between 2 participants) is possible via RS232 Connection via terminal bar X7:73/74 (SK 520E and above) or connection via RJ12 socket (X11)
Caution: with more than 2 participants, communication via RS232 is not possible, and for their protection, the RS232 contacts TXD and RXD must not be connected.
Termination resistors can be connected via DIP switch on the FI (DIP 1). Address range 0,1,3 … 30
Address 2 must not be used! Address 0 is reserved for the master (Broadcast Mode)
The baud rate is adjustable (4800Baud … 38400Baud)
With communication between only 2 participants, an RS232 connection can be set up. In this case, care must be taken that the communication speed may be lower, especially with long cable lengths.
For a network with more than 2 participants, the RS485 interface must always be used. Switchover between the Modbus and the USS protocol is automatic. The condition for this is that address 2 is
not set in parameter (P512).
The frequency inverter can process 2 versions of the Modbus protocol.
1. Communication via Bus IOs: If the frequency inverter is to be accessed via Bus IO Bits, the functions must be assigned in parameters (P480) and (P481). The source for the control word and the setpoints (P509/P510) must be set to "Control terminals". (For details: see "Coil list")
2. Process data communication: If process data is to be exchanged or parameters changed, the source for the control word and the setpoints (P509/P510) must be set to "USS". The definition of the parameters is made in the parameters (P543) to (P548). (For details: see "Process data")
BU 0050 GB-3111 Subject to technical amendments 61
Page 62
NORD USS and Modbus RTU Manual
Function Code
Function name
Description
01h
Read Coil
Reading access to all IN & OUT bits on the the bus
05h
Write Single Coils
Writing access to individual bus IN bits
0Fh
Write Multiple Coils
Simultaneous writing access to all bus IN bits
03h
Read Holding Register
Reading access to parameters
06h
Write Single Register
Writing access to an individual parameter (max 16Bit)
10h
Write Multiple Register
Writing access to 32Bit parameters or several PZD data
Address
8 bit
Function Codes
8 bit
Data
Variable = N x 8 bits
CRC
16 bit
2.3 Telegram Structure
The address field consists of eight Bits, which represent the address of the recipient. In its response, the Slave returns this address to the Master, so that the master can identify the response. The function field consists of 8 Bits. These encode how the content of the data field is to be interpreted. If the Slave has received the query from the Master correctly, it responds with the same function code. The structure of the data field is explained in detail in the section "Function Codes". Finally, a 16Bit CRC checksum is transmitted.
2.4 RTU Frames
In RTU mode the start of transmission is not marked by control codes, but rather via a break in transmission at least 3.5 characters long. The length of the transmission break therefore depends from the transfer speed. The end of the message is also marked by a break in transmission which is at least 3.5 characters long.
2.5 Function Codes
Function codes specify the required action associated with the transmission of the telegram. The following codes are supported:
62 Subject to technical amendments BU 0050 GB-3111
Page 63
2.5 Modbus RTU: Function codes
Master Slave
Slave Master
Function Code
1 Byte
0x01
Function Code
1 Byte
0x01
Start address
2 Byte
0x0000 to 0x000F
Number of bytes
1 Byte
1 to 2
Number of bits
2 Byte
1 to 16
Status of bits
n Byte
Query (Master Slave)
Response (Slave Master)
Address
0x08
Address
0x08
Function Code
0x01
Function Code
0x01
Start address High
0x00
Number of bytes
0x01
Start address Low
0x08
Status of Coils
0x03
Number of High Coils
0x00
CRC High
0x12
Number of Low Coils
0x04
CRC Low
0x15
CRC High
0xBC
CRC Low
0x92
Master Slave
Slave Master
Function Code
1 Byte
0x05
Function Code
1 Byte
0x05
Address
2 Byte
0x0000 to 0x0007
Address
2 Byte
0x0000 to 0x0007
Coil value
2 Byte
0x0000 or 0xFF00
Coil value
2 Byte
0x0000 or 0xFF00
Query (Master Slave)
Response (Slave Master)
Address
0x08
Address
0x08
Function Code
0x05
Function Code
0x05
Address High
0x00
Address High
0x00
Address Low
0x01
Address Low
0x01
Coil value High
0xFF
Coil value High
0xFF
Coil value Low
0x00
Coil value Low
0x00
CRC High
0xDD
CRC High
0xDD
CRC Low
0x63
CRC Low
0x63
2.5.1 01h Read Coil
This function enables the readout of inverter bits. The addresses of the bits are listed in the "Coil List".
Example:
4 bits are queries from the address 0x0008 (Bus OUT bits 1 to 4). The bus OUT bits 1 and 2 are High and the other two bits are Low.
2.5.2 05h Write Single Coils
Writes a single 1Bit value The addresses of the bits are listed in the Coil List. The value 0x0000 is written if a bit is to be deleted. 0xFF00 is written if the bit is to be set.
Example:
Bus IN Bit 2 is set to the address 0x0001.
BU 0050 GB-3111 Subject to technical amendments 63
Page 64
NORD USS and Modbus RTU Manual
Master Slave
Slave Master
Function Code
1 Byte
0x0F
Function Code
1 Byte
0x0F
Start address
2 Byte
0x0000 to 0x0007
Start address
2 Byte
0x0000 to 0x0007
Number of Coils
2 Byte
0x0001 to 0x0008
Number of Coils
2 Byte
0x0001 to 0x0008
Number of bytes
1 Byte
1
Query (Master Slave)
Response (Slave Master)
Address
0x08
Address
0x08
Function Code
0x0F
Function Code
0x0F
Start address High
0x00
Start address High
0x00
Start address Low
0x01
Start address Low
0x01
Number of High Coils
0x00
Number of High Coils
0x00
Number of Low Coils
0x04
Number of Low Coils
0x04
Number of bytes
0x01
CRC High
0x05
Coil value
0x0D
CRC Low
0x51
CRC High
0x02
CRC Low
0xF9
2.5.3 0Fh Write Multiple Coils
Via this access, all of the 8 writable coils can be switched simultaneously.
Example:
Bus IN Bits 2, 4 and 5 are set from start address 0x0001.
64 Subject to technical amendments BU 0050 GB-3111
Page 65
2.5 Modbus RTU: Function codes
NOTE
The parameter (P050) "Process data IN" and (P051) "Process data OUT" are executed in the background and are not visible to the user. From a structural point of view, these are array parameters ([-01 … -04]). Assignment of the setpoints in parameter (P050) is carried out via
the parameters (P546 (… P548)). The return of the actual values in parameter (P051) is
assigned in parameters (P543 (… P545)).
Master Slave
Slave Master
Function Code
1 Byte
0x03
Function Code
1 Byte
0x03
Start address
2 Byte
0x0000 to 0xFFFF
Number of bytes
2 Byte
0x01 to 0x08
Number of parameters
2 Byte
0x0001 to 0x0004
Parameter value
N*2Byte
Query (Master Slave)
Response (Slave Master)
Address
0x08
Address
0x08
Function Code
0x03
Function Code
0x03
Start address High
0x19
Number of bytes
0x02
Start address Low
0x80
Parameter value High
0x00
Number of parameters High
0x00
Parameter value Low
0xC8
Number of parameters Low
0x01
CRC High
0x65
CRC High
0x82
CRC Low
0xD3
CRC Low
0x27
Query (Master Slave)
Response (Slave Master)
Address
0x08
Address
0x08
Function Code
0x03
Function Code
0x03
Start address High
0x0C
Number of bytes
0x08
Start address Low
0xC0
Parameter value 1 High
0x2B
Number of parameters High
0x00
Parameter value 1 Low
0x37
Number of parameters Low
0x04
Parameter value 2 High
0x09
CRC High
0x47
Parameter value 2 Low
0xC4
CRC Low
0xFC
Parameter value 3 High
0x02
Parameter value 3 Low
0x03
Parameter value 4 High
0x09
Parameter value 4 Low
0xC4
CRC High
0x65
CRC Low
0xD3
2.5.4 03h Read Holding Register
This enables the readout of one or more parameters. However, usually only a single 16Bit format parameter can be read out. The function code 0x10 must be used for 32Bit parameters.
The only exception to this are the process parameters P050 and P051. Here, all the elements of the array assigned to the parameter can be read out simultaneously.
Example 1:
Parameter P102, parameter set 1 is read out (Content = 200 / 0x00C8).
Example 2:
The following 4 process data are read out: status word and actual values 1 to 3 (P051[-00] to P051[-03]) status word = 0x2B37 // IW1 = 0x09C4 // IW2 = 0x0203 // IW3 = 0x09C4.
BU 0050 GB-3111 Subject to technical amendments 65
Page 66
NORD USS and Modbus RTU Manual
Master Slave
Slave Master
Function Code
1 Byte
0x06
Function Code
1 Byte
0x06
Address
2 Byte
0x0000 to 0xFFFF
Address
2 Byte
0x0000 to 0xFFFF
Parameter Value
2 Byte
0x0000 to 0xFFFF
Parameter Value
2 Byte
0x0000 to 0xFFFF
Query (Master Slave)
Response (Slave Master)
Address
0x08
Address
0x08
Function Code
0x06
Function Code
0x06
Address High
0x19
Address High
0x19
Address Low
0x81
Address Low
0x81
Parameter value High
0x01
Parameter value High
0x01
Parameter value Low
0x23
Parameter value Low
0x23
CRC High
0x9E
CRC High
0x9E
CRC Low
0x6E
CRC Low
0x6E
NOTE
The parameter (P050) "Process data IN" and (P051) "Process data OUT" are executed in the background and are not visible to the user. From a structural point of view, these are array parameters ([-01 … -04]). Assignment of the setpoints in parameter (P050) is carried out via
the parameters (P546 (… P548)). The return of the actual values in parameter (P051) is assigned in parameters (P543 (… P545)).
Master Slave
Slave Master
Function Code
1 Byte
0x10
Function Code
1 Byte
0x10
Start address
2 Byte
0x0000 to 0xFFFF
Start address
2 Byte
0x0000 to 0xFFFF
Number of parameters
2 Byte
0x0001 to 0x0004
Number of parameters
2 Byte
0x0001 to 0x0004 Number of bytes
1 Byte
0x01 to 0x08
Parameter Value
N*2 Byte
2.5.5 06h Write Single Register
Enables writing of a single 16Bit parameter.
Example:
Parameter P102, parameter set 2 is written with the value 0x0123 (see also the item "Parameter access" in Section 2.8 Description of parameters).
2.5.6 10h Write Multiple Register
This command enables several parameters to be written consecutively, and for parameters with a data length of 32Bit.
In the process data area, all process data of the P050 parameter array can be written simultaneously. If parameters are written with this access, only a single parameter can be written with a telegram. This access
is used to write 32Bit parameters.
66 Subject to technical amendments BU 0050 GB-3111
Page 67
Example 1:
Query (Master Slave)
Response (Slave Master)
Address
0x08
Address
0x08
Function Code
0x10
Function Code
0x10
Start address High
0x99
Start address High
0x99
Start address Low
0x40
Start address Low
0x40
Number of parameters High
0x00
Number of parameters High
0x00
Number of parameters Low
0x02
Number of parameters Low
0x02
Number of bytes
0x04
CRC High
0x6E
Parameter value 1 High
0x00
CRC Low
0x19
Parameter value 1 Low
0x12
Parameter value 2 High
0x34
Parameter value 2 Low
0x56
CRC High
0x29
CRC Low
0xAE
Query (Master Slave)
Response (Slave Master)
Address
0x08
Address
0x08
Function Code
0x10
Function Code
0x10
Start address High
0x0C
Start address High
0x0C
Start address Low
0x81
Start address Low
0x81
Number of parameters High
0x00
Number of parameters High
0x00
Number of parameters Low
0x03
Number of parameters Low
0x03
Number of bytes
0x06
CRC High
0xD3
Parameter value 1 High
0x03
CRC Low
0xE9
Parameter value 1 Low
0xE8
Parameter value 2 High
0x07
Parameter value 2 Low
0xD0
Parameter value 3 High
0x0B
Parameter value 3 Low
0xB8
CRC High
0xF5
CRC Low
0xDF
Parameter P613 [0] is written with the value 0x00123456.
Example 2:
Parameters P050[1] to P050[3], i.e. setpoint values 1 to 3 are written. Control word1 = 1000 // SW2 = 2000 // SW3 = 3000.
2.5 Modbus RTU: Function codes
BU 0050 GB-3111 Subject to technical amendments 67
Page 68
NORD USS and Modbus RTU Manual
Slave Master
Function Code
1 Byte
0x80 + Function code of the Master query
Exception Code
1 Byte
0x01 to 0x06
Exception Code
Description
01h
A function code has been sent, which is not supported by the FI.
02h
The telegram which has been sent is too long.  For read queries, the data range to be read out is too large.  The queried parameter is not known.  The parameter sub-index is not known.
03h
An incorrect data content has been transmitted in the function "Write Single Coil".  The number of parameters is above the limit set by Modbus.
04h
Error in access to the parameter database of the FI.  The number of coils to be written in the function "Write Single Coil" has been
exceeded
06h
The Slave is still occupied with current query and cannot receive a new order.
Query (Master Slave)
Response (Slave Master)
Address
0x08
Address
0x08
Function Code
0x06
Function Code
0x06
Address High
0x19
Address High
0x19
Address Low
0x81
Address Low
0x81
Parameter value High
0x01
Parameter value High
0x01
Parameter value Low
0x23
Parameter value Low
0x23
CRC High
0x9E
CRC High
0x9E
CRC Low
0x6E
CRC Low
0x6E
2.6 Exception Responses
If a query by the Modbus Master cannot be answered correctly, an error message is sent instead of the normal response. The error message is structured as follows:
Example:
Parameter P102, parameter set 2 is written with the value 0x0123.
2.7 Watchdog
Modbus communication can be monitored via the parameter P513. Monitoring is started with the first valid telegram. If the FI does not receive a new telegram within the time set in P513, error 10.0 is triggered in the FI.
68 Subject to technical amendments BU 0050 GB-3111
Page 69
2.8 Description of parameters
Bus IO In Bits
Bus IO Out Bits
Coil number
Name
R/W
Coil number
Name
R/W
0000h
Bus IO In 1
R/W
0008h
Bus IO OUT 1
R
0001h
Bus IO In 2
R/W
0009h
Bus IO OUT 2
R
0002h
Bus IO In 3
R/W
000Ah
Bus IO OUT 3
R
0003h
Bus IO In 4
R/W
000Bh
Bus IO OUT 4
R
0004h
Bus IO In 5
R/W
000Ch
Bus IO OUT 5
R
0005h
Bus IO In 6
R/W
000Dh
Bus IO OUT 6
R
0006h
Bus IO In 7
R/W
000Eh
Bus IO OUT 7
R
0007h
Bus IO In 8
R/W
000Fh
Bus IO OUT 8
R
NOTE
The parameter (P050) "Process data IN" and (P051) "Process data OUT" are executed in the background and are not visible to the user. From a structural point of view, these are array parameters ([-01 … -04]). Assignment of the setpoints in parameter (P050) is carried out via
the parameters (P546 (… P548)). The return of the actual values in parameter (P051) is
assigned in parameters (P543 (… P545)).
Parameter {factory setting}
Setting value / Description / Note
P050 [-01]
... [-04]
Process data IN
(Process data In)
0000 ... FFFF (hex) { all 0 }
This parameter is an internal parameter, which can neither be edited nor displayed.. The assignment of the setpoints is carried out via parameters (P546) … (P548) (SK540E and above: (P546[-01]) … (P546[-03])).
[-01 ] = Control word
Control word, source from P509.
[-02] = Setpoint 1 [-03] = Setpoint 2 [-04] = Setpoint 3
(P546) or (P546[-01]) (P547) or (P546[-02]) (P548) or (P546[-03])
Setpoint data from main setpoint (P510 [-01]).
P051 [-01]
... [-04]
Process data OUT
(Process data OUT)
0000 ... FFFF (hex) { all 0 }
This parameter is an internal parameter, which can neither be edited nor displayed.. The assignment of the actual values is carried out via parameters (P543) … (P545) (SK540E and above: (P543[-01]) … (P543[-03])).
[-01] = Status word
Status word, source from P509.
[-02] = Actual value 1 [-03] = Actual value 2 [-04] = Actual value 3
(P543) or (P543[-01]) (P544) or (P543[-02]) (P545) or (P543[-03])
2.8 Description of parameters
Coil List
Via the Coil List it is possible to obtain direct access to the Bus IN/OUT bits. In order for these bits to function, they must be parameterised in parameter P480 and P481 and the control word and setpoint must be parameterised to the setting "Control terminals" via P509/P510.
Process data
The process data is sent to the FI by means of parameter access. In order for this process data to function, the setpoint source P509/P510 must be set to "USS".
BU 0050 GB-3111 Subject to technical amendments 69
Page 70
NORD USS and Modbus RTU Manual
Start address
Bit 15 – Bit 6
Bit 5 – Bit 0
Parameter number
Array Index
NOTE
The description of the inverter parameters can be found in the main manual for the frequency inverter (BU0500). However, parameters related to bus communication can also be found in Section 1.8 .
Parameter access
The FI parameters cannot be directly accessed via the functions 03h, 06h or 10h, as many FI parameters have array elements. Therefore, the addresses for NORD parameters are according to the following model:
The lower 5 bits are available for the array elements, so that the maximum array size is 63. The parameter values are shifted by 6 places.
Examples
P102 Parameter set 1 = 0x1980 P102 Parameter set 2 = 0x1981 P510 Array element 2 = 0x7F81
70 Subject to technical amendments BU 0050 GB-3111
Page 71
3 Faults
NOTE
As of firmware version V1.9 R0 for the SK 500E series, not only current error messages but also warnings and information messages can be displayed via the parameter. In this context, the parameter (P700) has been converted into an array parameter. I.e. error messages are displayed in (P700 [-01]), warnings in (P700[-02]), and information in (P700 [-03]).
For all other series (SK 300E, SK 700E, SK 750E), parameter (P700) still only indicates error messages.
3.1 Troubleshooting
The majority of frequency inverter functions and operating data are continuously monitored and simultaneously compared with limiting values. If a deviation is detected, the inverter reacts with a warning or an error message.
Basic information on this topic is contained in the manual for the basic equipment. Errors cause the frequency inverters to switch off, in order to prevent a device fault. The following options are available to reset a fault (acknowledge):
1. Switching the mains off and on again,
2. By an appropriately programmed digital input (P420 ... P425 = Function 12),
3. By switching of the “Enable” on the frequency inverter (if no digital input is programmed for
acknowledgement),
4. By Bus acknowledgement or
5. By P506, the automatic error acknowledgement.
Device LEDs: As delivered, with SK 300E series devices (except ATEX versions) and SK 500E (without
technology unit), 2 LEDs (green/red) are externally visible. These indicate the actual device status.
The green LED indicates that the mains voltage is present and operational, while a flashing
code that increases in speed shows the degree of overload at the frequency inverter output.
Thered LED signals actual error by flashing with a frequency which corresponds to the
number code of the fault.
3 Faults
The following table shows all the faults which are attributable to bus operation. In the operating display of the optional "ControlBox" only error E010 is displayed. A finer categorisation of errors can be obtained from the information parameters P700 "Actual Faults" or P701 "Last Fault 1...5".
3.1.1 Error display
ControlBox / SimpleBox:The 4-digit, 7 segment display of these boxes indicates a fault with its number and
the prefix "E". If the cause of the error is no longer present, the error display flashes and the error can be acknowledged with the OK key.
ParameterBox: The error messages are shown in plain text.
3.1.2 Error memory
The current error is saved in parameter P700 and the last five error messages are saved in parameter P701 [­01]…[-05]. Further information on inverter status at the time the error occurred are stored in parameters P702 to P706 / P799. More detailed information can be found in the main manual for the frequency inverter.
BU 0050 GB-3111 Subject to technical amendments 71
Page 72
NORD USS and Modbus RTU Manual
Display in the ControlBox
Fault Text in the ParameterBox
Cause
Remedy
Group
Details in P700 / P701
E010
10.0
(Bus Timeout)
Telegram timeout, data transfer is faulty. Check P513.
Check external Bus connection.  Check bus protocol program process.  Check Bus Master.
10.2
Bus Timeout Option
Telegram timeout for external bus module, telegram communication is faulty.
Check external connection.  Check bus protocol program process.  Check Bus Master.
10.4
Init error Option
External bus module initialisation failure
Check P746.  Bus module not correctly plugged in.  Check Bus module current supply.
10.1
System error option
External Bus module system failure
10.3
10.5
10.6
10.7
10.8
Error option
Communication error in external module connection error/fault in external module
3.2 Error messages
Table of possible bus-specific error messages
72 Subject to technical amendments BU 0050 GB-3111
Page 73
4 Additional information
NOTE
If possible, the reason for returning the component/device should be stated. If necessary, at least one contact for queries should be stated.
This is important in order to keep repair times as short and efficient as possible. On request you can obtain a suitable goods return voucher from Getriebebau NORD
GmbH.
4 Additional information
4.1 Maintenance and servicing information
In normal use, NORD frequency inverters and their accessories are maintenance-free. If air intake filters have been built into the control cabinet, then these should also be regularly cleaned or
replaced. If you contact our technical support, please have the precise device type (name plate/display), accessories
and/or options, the software version used (P707) and the series number (name plate) at hand.
Repairs
The device must be sent to the following address if it needs repairing:
NORD Electronic DRIVESYSTEMS GmbH
Tjüchkampstr. 37
26605 Aurich, Germany
For queries about repairs, please contact:
Getriebebau NORD GmbH & Co. KG
Tel.: 04532 / 401-515 Fax: 04532 / 401-555
If a frequency inverter or accessories are sent in for repair, no liability can be accepted for any added components, e.g. such as line cables, potentiometer, external displays, etc.!
Please remove all non-original parts from the frequency inverter.
Internet information
You can also find the comprehensive manual in German and in English on our Internet site.
www.nord.com
4.2 Abbreviations in this manual
CU ....... Customer Unit (customer interface (internal)
DI, DIN . Digital input
EMC ..... Electromagnetic compatibility
FI ......... Frequency inverter
HW ....... Hardware
IND ....... Index
BU 0050 GB-3111 Subject to technical amendments 73
IW ..........Actual value
STW ......Control word
SW .......Software version, setpoint
TU .........Technology Unit (external)
ZSW ......Status word
Page 74
NORD USS and Modbus RTU Manual
5 Keyword index
A
Actual bus value 1 (P543) ........... 56
Actual bus value 2 (P544) ........... 56
Actual bus value 3 (P545) ........... 56
Actual value ................................ 37
Assembly .................... 9, 13, 16, 18
Auxiliary bus setpoint (P510) ...... 53
B
Bus parameters ........................... 51
C
CE ................................................. 8
Configuration level (P744) .......... 63
Control word................................ 30
Control word source (P509) ........ 53
Customer Units ..................... 12, 18
D
Data transmission ....................... 26
Database version (P742) ........... 63
Displays and control .................... 75
E
EMC Directive ............................... 8
Error memory .............................. 75
F
H
Hyst. Bus IO Out Bits (P483)...... 51
I
Interface (P509) ......................... 53
L
Low Voltage Directive .................. 2
M
Master function output (P503) .... 52
Master function value (P502) ..... 52
Modbus RTU .............................. 65
01h Read Coil ................... 67
03h Read Holding Register 69
05h Write Single Coils ....... 67
06h Write Single Register .. 70
0Fh Write Multiple Coils ..... 68
10h Write Multiple Register 70
Coil List ............................ 73
Exception Code ................. 72
Features ........................... 65
Function codes.................. 66
Parameter access .............. 74
Process data ..................... 73
Telegram Structure ........... 66
PPO type (P507) ........................ 52
PPO types .................................. 27
Process Bus Out (P741) ....... 61, 62
Process data .............................. 29
Process data Bus In (P740) .. 59, 61
PZD ................................ ...... 26, 29
R
Repairs ....................................... 77
RoHS compliance ......................... 8
S
Safety information ........................ 2
Setpoint ...................................... 33
Setpoints source (P510) ............. 54
Settings ...................................... 51
SK 300E ..................................... 18
SK 500E ....................................... 9
SK 700E ..................................... 12
SK CU1-STD .............................. 14
SK CU1-USS .............................. 15
SK TU1-RS2 ............................... 13
Special extension units ............... 12
Stand. Bus IO Out Bits (P482) .... 51
Status machine ........................... 38
Status word ................................ 32
Structure of reference data ......... 26
Faults .......................................... 75
Function Bus IO In Bits (P480).... 51
Function Bus IO Out Bits (P481) . 51 Function Bus setpoint 1 (P546) ... 58 Function Bus setpoint 2 (P547) ... 58 Function Bus setpoint 3 (P548) ... 59
Function Bus setpoints (P546) .... 58
Module status(P746) .................. 64
Module version (P745) ............... 63
P
Parameter area .......................... 40
PKW ..................................... 26, 40
Posicon ...................................... 34
T
Technology Units ........................ 12
Telegram downtime (P513) ........ 55
U
USS address (P512) .................. 55
USS baud rate (P511) ................ 55
74 Subject to technical amendments BU 0050 GB-3111
Page 75
5 Keyword index
BU 0050 GB 75
Page 76
NORD USS and Modbus RTU Manual
Part. No. 607 0502 / 3111
76 Subject to technical amendments BU 0050 GB-3111
Loading...