Nor-Cal IQ+ Adaptive Pressure Controller User Manual

Adaptive Pressure Controller
Tel: 800-824-4166
or 530-842-4457
Fax: 530-842-9130
www.n-c.com
1967 So. Oregon
Nor-Cal Products, Inc.
IQ+ OP-LIT 9/08
IntellIsys AdAptIve pressure Controllers
Table of Contents
1.0
............Introduction ..............................................................................................................................................
2.0
............Device Specification ..................................................................................................................................
............Unpacking and Installation ........................................................................................................................
3.0
3.1
....... Master Buried Box Controllers ...................................................................................................................
3.2
....... Slave Buried Box Controllers ......................................................................................................................8
3.3
....... Master On-Board Controllers ....................................................................................................................9
3.4
....... Slave On-Board Controller ......................................................................................................................
4.0
...........Theory of Operation ................................................................................................................................
5.0
............IQ+ Controller Module Interfaces ............................................................................................................
6.0 ..............
6.1
7.0
............DeviceNet Interface .................................................................................................................................
7.1
7.2
8.0
............DeviceNet Device Profile ..........................................................................................................................
8.1
8.2
8.3
8.4
8.5
8.6
8.7
8.8
8.9
8.10
8.11
8.12
8.13
9.0
............Battery Back-Up ......................................................................................................................................
10.0 Appendix I Appendix II - Warranty and Intellectual Property Coverage
RS-232 Serial Interface and Commands ..................................................................................................
....... How to Configure IQ+ for Your System ...................................................................................................
....... Overview and Setup ................................................................................................................................
....... DeviceNet Communications ...................................................................................................................
....... Identity Object ........................................................................................................................................
....... Message Router Object ...........................................................................................................................
....... DeviceNet Object ....................................................................................................................................
....... Assembly Object .....................................................................................................................................
....... I/O Assembly Instances ............................................................................................................................
....... Connection Object..................................................................................................................................
....... Discrete Input Point Object ......................................................................................................................
....... S-Device Supervisor Object ......................................................................................................................
....... S-Analog Sensor Object ..........................................................................................................................
...... S-Analog Actuator Object .......................................................................................................................
...... S-Single Stage Controller Object .............................................................................................................
...... Selection Object ......................................................................................................................................
...... Master / Slave Object ..............................................................................................................................
..........Product Support......................................................................................................................................
- Spare Parts and Ordering Information ..................................................................................................
.............................................................................................
4 5 6 7
10 11 12 13 16 18 18 20 22 23 23 23 23 24 25 25 25 27 28 28 30 31 32 33 35 36
IQ+ OP-LIT 9/08
22
Visit our Web Site www.n-c.com
IntellIsys AdAptIve pressure Controllers
List of Tables
2.1
......IQ+ Controller General Equipment Specification .............
2.2
.....IQ+ Controller Analog TTL I/O .........................................
2.3
......IQ+ Controller RS-232 Serial I/O ......................................
2.4
......IQ+ Controller Performance ............................................
2.5
......IQ+ Controller Reliability .................................................
3.1
......Buried Box Controllers (Master) .......................................7
3.2
......Buried Box Controllers (Slave) ..........................................8
3.3
......Master On-Board Controllers ..........................................9
3.4
......Slave On-Board Controllers .......................................... 10
5.1
......Dip Switch Configuration ............................................. 12
6.1
.....RS-232 Serial ICommands .............................................
......RS-232 Serial Requests and Responses ..........................
6.2
6.3
......Values for xx for use with Dual Range Mode ..................
..... DeviceNet Commands ............................................................17
6.4 .
6.5 ...... RS-232 Serial Commands .......................................................17
6.6 .....RS-232 Serial Requests and Responses ......................... 17
7.1
......DeviceNet Module LED Status .......................................
7.2
......DeviceNet Network LED Status ......................................
7.3
......DeviceNet Explicit Messaging ........................................
7.4
......Output Assembly Formats .............................................
7.5
......Input Assembly Formats ................................................
8.1.1
... Identity Object Attributes and services ...........................
8.1.2 ..Identity Object Status Bit Map .......................................
8.3.1
... DeviceNet Object Attributes and Services ......................
8.4.1
... Assembly Object Attributes ...........................................
8.5.1
... Output Assembly Instances ...........................................
8.5.2
... Input Assembly Instances ..............................................
8.6.1
... Connection Object Attributes .......................................
8.7.1
... Discrete Input Point Object Attribute; Instance ID 1........
8.7.2
... Discrete Input Point Object Attribute; Instance ID 2....... 25
8.8.1
... S-Device Supervisor Object Attributes and Services ........
8.8.2
... S-Device Supervisor Object Device Status Value ............
8.8.3
... S-Device Supervisor Object Exception Status Bit Map.... 25
8.8.4
..S-Device Supervisor Opject Exception Detail ................. 26
8.9.0
... S-Analog Sensor Object Class Attributes: Instance 0 ..... 27
8.9.1
... S-Analog Sensor Object Attributes; Instance 1,2 .......... 27
8.9.2
... S-Analog Sensor Object Attributes; Instance 3.............. 27
8.9.3
... S-Analog Sensor Object Status Bit Map .........................
13 13 15
18 18 20 21 21 23 23 23 23 24 24 25 25
25 25
27
8.10.1
5 5 5 5 5
.S-Analog Actuator Object Attibutes ..............................
8.10.2
.S-Analog Actuator Exception Status Bit Map .................
.S-Analog Actuator Object Override Value ......................
8.10.3
8.10.4
.S-Analog Actuator Object Safe State Value ...................
8.11.1
.S-Single Stage Controller Object Attributes; Instance 1 ..
8.11.2
.S-Single Stage Controller Object Attributes; Instance 2 ..
8.11.3 . S-Stage Controller Object Control Mode Value .
8.11.4 . S-Single Stage Controller Object Status Bit Map ......................29
8.11.5 . S-Single Stage Controller Object Safe State Value....................29
8.12.1 . Selection Object Attributes; Instance 1 ....................................29
8.12.2 . Selection Object Attributes; Instance 2 ....................................30
8.13.1 . Master/Slave Object Attributes ...............................................31
8.13.2 . Master/Slave Object Individual Valve Control (Action) Valve .....31
8.13.3 . Master/Slave Object Device Status Value .................................31
8.13.4 . Master/Slave Object Cluster Information Bit Map ....................31
8.13.5 . Slave Network LED Status .......................................................32
10.1 .... Possible Failure Modes and Recommended Actions ................33
10.2 .... Valid Status LED Combinations ...............................................34
......................29
List of Figures
3.1
......Buried Box Controller (Master) ........................................7
3.2
......Buried Box Controller (Slave) ...........................................
3.3 ...... On-Board Controller (Master) ...................................................9
3.4
......On-Board Controller (Slave) ...........................................
4.1 ...... Typical Installation and Configuration of a Buried Box IQ+ ..........
............ Pressure Control System .........................................................11
4.2 .....Typical Installation and Configuration of an IQ+ Pressure ..
...........Control Valve ............................................................... 11
6.1 .....Volume Too Low Slow Oscillations at set point .............. 16
6.2 .....Volume Too High Undershoot ...................................... 16
6.2.1 ..Volume Too High Slow Valve Movement, Slow ............ 16
6.3 .....Delay Too Low Overshoot and Pressure Oscillation........ 16
6.4 .....Speed Too High Low Speed Oscillations ........................ 17
6.5 .....Speed Too Low Undershoot, slow valve movement ...... 17
7.1 .....DeviceNet Connector Pin Assignment .......................... 18
7.2 .....DeviceNet Baud Rate Selection Switch ..........................
7.4
......Typical DeviceNet Hardware Installation ........................
8.1
......Object Model for the Process Control Valve Device ........
8.2
......Object State Transition Diagram ....................................
28 28 28 28 28 29
8
10
18 19 22 27
Information in this manual is subject to change without notice.
Call toll free 800-824-4166 or 530-842-4457 FAX 530-842-9130
Contact Nor-Cal Products
Intellisys Customer Support
at 800-824-4166 ext. 186
or visit our website
at www.n-c.com
IQ+ OP-LIT 9/08
3
IntellIsys AdAptIve pressure Controllers
1.0 - Introduction
Thank you for purchasing the new Intellisys™ IQ+ downstream adaptive pressure controller from Nor-Cal Products. Before installing and operating the product, please read this manual thoroughly as it contains critical correction, interface and operating tips. If you encounter any problems, or if you have any questions, please contact our Intellisys Customer Service Support at 800-824-4166, ext. 186 or visit our web site at www.n-c.com.
Nor-Cal Products’ IQ+ pressure controllers are designed for downstream pressure control over a wide range of vacuum control applications. The IQ+ controller is a self-contained unit that incorporates all control electronics and associated pressure control software. IQ+ controllers are available in Analog, DeviceNet and Ethernet communication protocols. Buried box versions connect to the valve via a valve cable, while QPA, QPD and QPE controllers are mounted directly on the valve. Any IQ+ controller, regardless of type, accepts the inputs from one or two pressure gauges as well as communications to the host controller, thus making it the heart of a pressure control loop.
All models have local open/close switches, LED status lights and RS232 communication.
Important Personnel Safety and Product Protection Information
Throughout this manual, information that is of particular importance to the installation, the safety of oper­ating personnel and the protection of equipment are highlighted by the following three symbols. The WARNING symbol is also used on the equipment wherever necessary.
NOTE: Calls attention to helpful tips about proper
installation, maintenance or use of the controller.
CAUTION: Highlights areas of concern that, if overlooked, could
result in damage to the controller or surrounding equipment.
WARNING : Alerts the installation, operating or maintenance
personnel of hazardous aspects of the controller, which, if ignored could result in serious personal injury or death.
IQ+ OP-LIT 9/08
44
Visit our Web Site www.n-c.com
IntellIsys AdAptIve pressure Controllers
2.0 - Device Specification
The following tables summarize specifications essential to the installation and hook-up of the IQ+ product. Please note that the information herein is limited to the IQ+ controller. For valve installation instructions and guidelines, please refer to the appropriate Valve Operating Manual.
TABLE 2.1 – IQ+ CONTROLLER GENERAL EQUIPMENT SPECIFICATIONS
FEATURE SPECIFICATION
Dimensions Please refer to the diagram specific to sections 3.1 to 3.5 Weight, in lbs (kg) 1.1 lb (0.5 kg) Rated Input Voltage 24 VDC ±10% Rated Current 5.0 A @ 24 VDC max, 1.5 A @ 24 VDC average Rated Input
Protection Gauge Power Supply
(Optional) Protection Class I Degree of Protection
(IP) Laser Class 1 (LED’s) Certifications/EU
Directives Maximum Altitude 6562 ft (2000 m) Allowable Ambient
Operating Temperature
Allowable Ambient Humidity
Installation Clearance
FEATURE SPECIFICATION
Analog (Gauge) Input 0 to 10V differential Analog Output 0 to 10V unipolar @ 35 mA, short circuit protected
TTL Input
TTL Output Open collector, optically isolated, 25V @ 10 mA max
29 Volts max, reverse and current limited
± 15 VDC @ 1400 mA
X0
CE Standard for Process Equipment including EMC Directive 89/336/EC for D/C powered models..
32ºF to 113ºF (0ºC to 45ºC)
0 to 95% non-condensing
3” (75 mm) on all perforated sides. A minimum of 3½” (90 mm) is needed to allow for connectors. If access and line of sight is required for LED’s and switches a minimum of 6” (150mm) is required on those sides.
TABLE 2.2 – IQ+ CONTROLLER ANALOG TTL I/O
Diode protected at –0.4 VDC, compatible with open collector relay closure or standard logic signals, 25V max. Maximum low input voltage is 0.6V and minimum sink current is 1 mA. Minimum high input voltage is 2.5V, or open.
TABLE 2.3 –IQ+ CONTROLLER RS-232 SERIAL I/O
FEATURE SPECIFICATION
Communications Settings
Connections
Communications Protocol See Section 6.0 in this manual
End of line delimiter
TABLE 2.4 – IQ+ CONTROLLER PERFORMANCE
FEATURE
Valve speed (open to closed)
Control range
Accuracy
Repeatability 0.12% of reading 0.12% of reading
FEATURE BUTTERFLY VALVES PENDULUM VALVE
Electronics MTBF >10,000 hours >10,000 hours Warranty 1 year 1 year
BUTTERFLY VALVES
125 to 250 msec, depending on valve size
0.5% to 100% of gauge
0.25% of reading (5mV min)
TABLE 2.5 – IQ+ CONTROLLER RELIABILITY
Factory configured at 9600 baud, 1 stop bit, no parity, 8-bit character
Rxd Data, Txd data and Common. No handshake connections.
Carriage return (ASCII 0x0D) or Line Feed (ASCII 0x0A) or carriage return then line feed in that order
GATE & PENDULUM VALVES
2 to 5 sec, depending on valve size
0.5% to 100% of gauge
0.25% of reading (5mV min)
Call toll free 800-824-4166 or 530-842-4457 FAX 530-842-9130
IQ+ OP-LIT 9/08
5
IntellIsys AdAptIve pressure Controllers
3.0 - Unpacking and Installation
Inspect the shipping box before unpacking. Any damage should be reported to Nor-Cal Products or directly to the transportation carrier. Carefully remove the product from the box and visually inspect it for damage. If return of the product to Nor-Cal Products should become necessary, please contact Intellisys Customer Service to obtain a Return Materials Authorization (RMA) Number.
NOTE: Do not discard the packing materials until the product has been inspected to your satisfaction.
Pre-Installation Functionality Check
Nor-Cal Products carefully ensures that every product shipped is in perfect working condition. However, it is still a good idea to quickly check the functionality of the unit prior to installation into the vacuum system. To do so, for buried box IQ+ controllers, connect the controller to the valve and then to an appropriate +24DC, 4A power source. For all valve IQ+ controllers simply apply the +24DC, 4A power source. The butterfly valves will complete a 30 second valve initialization sequence ... the valve will stop in the open positoin. For soft shut (TSS) valves and pendulum (TPV) valves press the open and close buttons at the same time. The valves will begin the valve initialization sequence like the butterfly valve. The length of time to complete this sequence will vary from 40-60 seconds depending upon the type and size of valve. The valve will complete a 30-second initialization sequence during which the valve plate will cycle back-and-forth a few times while the OPEN/CLOSE LEDs blink in an alternat­ing pattern. The valve will eventually stop in the open position. Further verification of the system can be done by toggling the “OPEN / CLOSE” switch (if available) on the controller front panel. If the valve does not operate as described please contact Nor­Cal Technical Support.
avoid putting bodily parts in or near the valve gate mechanism or other moving parts. These may move
WARNING : When working with or troubleshooting Nor-Cal APC products extreme care must be taken to
suddenly and unexpectedly, and many of them are driven with sufficient force so as to cause significant harm and possibly even dismemberment. Nor-Cal Products recommends that a lock-out and tag-out procedure be strictly followed whenever human physical intervention is required on all of its control valves.
Installation
To allow for proper ventilation, make sure that at least 3 inches of unobstructed space is available adjacent to all perforated sides of the IQ+ controller. Then, complete all cable connections as required referring to the figures and pin assignment tables in Sections 3.1 – 3.3 of this manual. A list of pre-manufactured cable assemblies available from Nor-Cal Products can be found in Appendix I.
CAUTION: The optional +15V and –15V power supply pins of the IQ+ gauge connector are power sources
that are intended to power the optional system pressure gauge(s). It can supply a maximum of 1500 mA. Do not use for any other purpose and do not connect to the tool main 15V supply as the two supplies would
interfere with each other.
NOTE: Low voltage controller models do not have a power on/off switch. Consider installing an external
power on/off switch between the DC power supply and the controller to allow for de-energizing the unit
without having to disconnect the cable.
IQ+ OP-LIT 9/08
66
Visit our Web Site www.n-c.com
IntellIsys AdAptIve pressure Controllers
Net Ctrl
Fault
0
2
4
6
8
0
2
4
6
8
VALVE
GAUGE
P O W ER
POWER
SVC
PORT
2
5
P
1
RATE
SW1
C LOS E
O P EN
IQ+ SERIES
ADAPTIVE PRESSURE CONTROLLER
Mod
3.1 - Master Buried Box Controllers
TABLE 3.1 – BURIED BOX CONTROLLERS (MASTER)
POWER (XLR) SERVICE PORT VALVE AUXILIARY DEVICENET GAUGE
PIN FUNCTION PIN FUNCTION PIN SIGNAL
ASSIGNMENT
1 +24VDC
Power Input
2 Power Return 2 Authorized
3 Drain
4 N-C Net Hi
5 NC- Net Low
1
2
2
1 Authorized
Technicians Only
Technicians Only
3 Authorized
Technicians Only
1 Drive A + 1 Reserved 1 Drain 1 CDG1 +
2 Drive A- 2 RS232 TX 2 DNET Power
3 Drive B- 3 RS232 RX 3 DNET Power
4 Drive B + 4 Digital
5 Sense B - 5 Reserved 5 CAN L 5 CDG2 +
6 Sense B + 6 RS485 A 6 CDG2 -
7 Sense A - 7 Reserved 7 Reserved
8 Sense A + 8 RS485 B 8 CDG1 -
9 Reserved 9 TTL IN 0 9 CDG Power Ground
10 Reserved 10 TTL IN 1
11 Reserved 11 Digital
12 Reserved 12 TTL Com
13 Reserved 13 TTL Out 0
14 Reserved 14 TL Out 1
15 Reserved 15 Chassis
PIN FUNCTION PIN FUNCTION PIN FUNCTION
2 + 15VDC CDG Power
3 - 15VDC CDG Power
Ground
Ground
Ground
in +
in -
4 CAN H 4 Reserved
(Optional)
(Optional)
FIGURE 3.1 – BURIED BOX
CONTROLLER (MASTER)
1
Connect to Earth Ground at power supply
2
N-C Net is a proprietary communication protocol. Do not connect these pins to anything other than approved Nor-Cal items.
Call toll free 800-824-4166 or 530-842-4457 FAX 530-842-9130
IQ+ OP-LIT 9/08
7
IntellIsys AdAptIve pressure Controllers
O P EN
C L OSE
Ctrl
Fault
1
3
5
7
9
SLAVE ID
POWER
Net
SVC
PORT
IQ+ SERIES
AADDAAPPTTIIVVEE PPRREESSSSUURREE CCOONNTTRROOLLLLEERR
P O W E R
VALVE
3.2 - Slave Buried Box Controllers
POWER (XLR) SERVICE PORT VALVE
PIN FUNCTION PIN FUNCTION PIN SIGNAL ASSIGNMENT
1 +240VDC Power Input 1 Authorized Technicians
2 Power Return 2 Authorized Technicians
3 Drain
4 N-C Net Hi
5 NC- Net Low
1
2
2
TABLE 3.2 – BURIED BOX CONTROLLERS (SLAVE)
Only
Only
3 Authorized Technicians
Only
1 Drive A +
2 Drive A -
3 Drive B -
4 Drive B +
5 Sense B -
6 Sense B +
7 Sense A -
8 Sense A +
9 Reserved
10 Reserved
11 Reserved
12 Reserved
13 Reserved
14 Reserved
15 Reserved
FIGURE 3.2 – BURIED BOX CONTROLLER (SLAVE)
1
Connect to Earth Ground at power supply
2
N-C Net is a proprietary communication protocol. Do not connect these pins to anything other than approved Nor-Cal items.
IQ+ OP-LIT 9/08
88
Visit our Web Site www.n-c.com
IntellIsys AdAptIve pressure Controllers
RATE
Net
Mod
Ctrl
Fault
0
2
4
6
8
0
2
4
6
8
MSD
LSD
AUXILIARY
GAUGE
POWER
SVC
PORT
IQ + SERIES
A DAP TIVE P R ES SU RE C ON TR OLL ER
C L O SE
O P E N
2
5
P
1
3.3 - Master On-Board Controllers
TABLE 3.3 – ON-BOARD CONTROLLER S(MASTER)
POWER (XLR) SERVICE PORT AUXILIARY DEVICENET GAUGE
PIN FUNCTION PIN FUNCTION PIN FUNCTION PIN FUNCTION PIN FUNCTION
1 +24VDC Power
Input
2 Power Return 2 Authorized
3 Drain
4 N-C Net Hi
5 NC- Net Low
1
2
2
1 Authorized
Technicians Only
Technicians Only
3 Authorized
Technicians Only
1 Reserved 1 Drain 1 CDG1 +
2 RS232 TX 2 DNET Power
3 RS232 RX 3 DNET Power
4 Digital Ground 4 CAN H 4 Reserved
5 Reserved 5 CAN L 5 CDG2 +
6 RS485 A 6 CDG2 -
7 Reserved 7 Reserved
8 RS485 B 8 CDG1 -
9 TTL IN 0 9 CDG Power Return
10 TTL IN 1
11 Digital Ground
12 TTL COM
13 TTL OUT 0
14 TL OUT 1
15 Chassis Ground
in +
In -
2 + 15VDC CDG Power
(Optional)
3 - 15VDC CDG Power
(Optional)
(Optional)
FIGURE 3.3 – ON-BOARD CONTROLLER (MASTER)
IQ+ OP-LIT 9/08
1
Connect to Earth Ground at power supply
2
N-C Net is a proprietary communication protocol. Do not connect these pins to anything other than approved Nor-Cal items.
Call toll free 800-824-4166 or 530-842-4457 FAX 530-842-9130
9
IntellIsys AdAptIve pressure Controllers
O P EN
C LO S E
Ctrl
Fault
POWER
Net
1
3
5
7
9
SVC
PORT
IQ+ SERIES
AADDAAPPTTIIVVEE PPRREESSSSUURREE CCOONNTTRROOLLLLEERR
SLAVE ID
P O W ER
3.4 - Slave On-Board Controllers
POWER (XLR) SERVICE PORT
PIN FUNCTION PIN FUNCTION
1 +24VDC Power Input 1 Authorized Technicians Only
2 Power Return 2 Authorized Technicians Only
3 Drain
4 N-C Net Hi
5 NC- Net Low
TABLE 3.4 - ON-BOARD CONTROLLERS (SLAVE)
1
2
2
3 Authorized Technicians Only
FIGURE 3.4 – ON-BOARD CONTROLLER (SLAVE)
1
Connect to Earth Ground at power supply
2
N-C Net is a proprietary communication protocol. Do not connect these pins to anything other than approved Nor-Cal items.
1010
IQ+ OP-LIT 9/08
Visit our Web Site www.n-c.com
IntellIsys AdAptIve pressure Controllers
Vacuum Chamber
Pump
DC power supply
Host system with
RS232/485 or DeviceNet
communications
Nor-Cal IQ+ Valve
Vacuum gauge(s)
Vacuum Chamber
Pump
DC power supply
Host system with
RS232/485 or DeviceNet
communications
IQ+ Controller
Nor-Cal throttle valve
Vacuum gauge(s)
4.0 - Theory of Operation
All IQ+ controllers are designed for downstream pressure control (see Fig 4.1 and 4.2). As such, it is one of several important components in a pressure control system. Other essential components include a host system computer, a throttle valve and one or two vacuum gauges, such as a Capacitance Diaphragm Gauge (CDG), and a pump system. Most manufacturers’ vacuum gauges can be used to provide the vacuum measurement signal, provided they have a voltage output proportional to pressure. The IQ+ controller requires a pressure gauge signal output that is 0-10V linear and proportional to pressure.
FIGURE 4.1 – TYPICAL INSTALLATION AND CONFIGURATION OF A BURIED BOX IQ+ PRESSURE CONTROL SYSTEM
Initialization Sequence
When first powered up, butterfly valves with the IQ+ controller will run the valve through an initialization sequence that lasts for approximately 30 seconds. The primary purpose for this operation is for the controller to determine the fully open and closed points, as well as for certain motor and position calibration steps to occur. While the initialization sequence is active, the amber FAULT light will be illuminated and the OPEN/CLOSE LEDs both will be extinguished. Once the initialization sequence is complete, the valve will move to the fully open position and the green OPEN LED will illuminate.
NOTE: The controllers for TPV pendulum valves and TSS
gate valves contain a valve initialization safety lock function.
This safety lock will prevent valve initialization to occur until given a “clear-to-proceed” command. The RS-232 serial command for this is T4.
CAUTION: Never attempt to initialize a throttle valve with
differential pressure across the sealing gate. Make sure the
pressure on both sides is equalized to ±20 Torr. Damage to pumps and other equipment can occur otherwise.
FIGURE 4.2 – TYPICAL INSTALLATION AND CONFIGURATION OF AN IQ+ PRESSURE CONTROL VALVE
Normal Operation
After the initialization sequence is complete normal operation of the valve is possible. There are two primary modes of operation, a) position control mode and b) pressure control mode.
In position control mode, the valve will move to any position in its range based on a position set-point command from the host. The valve will remain in that position until instructed to do otherwise. Position control mode can be useful in certain cases where pre-determined amount of throttling is necessary.
Pressure control mode, is used whenever control to a specific process
pressure level is desired. The host provides the set-point value to the controller which, in turn, moves the valve to achieve that set point as quickly as possible. During pressure control mode, external perturbations such as flow changes and plasma events will automatically be compensated for by the controller so that the pressure set-point is maintained. The value can be changed by the host at any time.
Tuning
The IQ+ controller contains an Adaptive Pressure Control Algorithm that has been designed to work over a wide range of flow and pressure combina­tions. In some cases 3 system parameters may have to be adjusted. These include system volume, system delay and speed. See Section 6.1: How to
configure IQ+ for your system.
Call toll free 800-824-4166 or 530-842-4457 FAX 530-842-9130
IQ+ OP-LIT 9/08
11
IntellIsys AdAptIve pressure Controllers
5.0 - IQ+ Controller Module Interfaces
IQ+ controllers have several interfaces available for communications and connectivity to peripheral devices, depending on model. These are described by func­tion below. Please also refer to Figures 3.1 – 3.4 and their associated Tables for the specific connectors and their pin assignments.
Vacuum Gauge Interface
The pressure signal from one or two vacuum gauges can be interfaced to the IQ+ controller module through the connector labeled GAUGE. In addition, ±15 VDC is available as an option to power such gauges from these ports.
NOTE: If the power requirement of the gauge(s) used
exceeds the rated power output, then a separate power
source must be used. ±15V@1500mA.
When only one gauge is used, then the pressure signal must be connected to the CDG1+ and CDG1- signal pins. Use of two gauges requires adhering to the following:
The full scale range of the two gauges used must be set prior to use. See sec­tion 6.0.
Serial interface
An RS-232 serial interface is available on all controller models. Please refer to the Section 6.0 for a full description of the communications protocol and a listing of all active serial commands. A three-wire connection completes the communications consisting of Rxd (data from the IQ+), Txd (data to the IQ+) and digital ground.
are neither needed nor available.
settings are 9600 Baud, 1 stop bit and no parity. These settings
Every serial input command sent by the HOST has an end-of-line delimiter, car­riage return ASCII 0x0D [hex], or the line feed character ASCII 0x0A [hex], or the carriage return and line feed character in that order. The IQ+ device end­of-line delimiter is the carriage return and line feed characters.
NOTE: CTS, RTS and DSR connections
NOTE: The default factory RS-232 communications parameter
can only be changed on models with DIP switches, and changing the setting requires cycling IQ+ input power off then back on.
DeviceNet Interface (not available on all models)
The five-pin circular DeviceNet port allows for complete remote control, monitoring and power supply of the IQ+ controller in a cost effective and reli­able way. In addition to the connector are two status LEDs labeled Mod and Net, as well as three rotary switches labeled MSD, LSD and RATE. A complete explanation of the DeviceNet physical and software interfaces can be found in Sections 8 and 9.
Service Port
The Service Port is reserved for factory authorized service technicians
Indicating LEDs
There are a host of indicating LEDs on the IQ+ controller, depending on model. In general, the green Power LED is illuminated whenever power is applied to the device. The green Ctrl LED is illuminated whenever the IQ+ is in set point control (pressure or position). The amber Fault LED is illuminated briefly during the initialization sequence after power-up but primarily if the IQ+ device enters a fault state. Two LEDs are located adjacent to the OPEN and CLOSE switches, and are illuminated whenever the valve position is within 2% of either limit.
Switches
Some controller models have a bank of four DIP switches labeled SW1. These switches are used to define valve size. Relative to the printed text on the over­lay, switch 1 is on the left
switch in the “up’ position is OFF or “0”
A
A switch in the “down” position is ON or “1”
Refer to table 5.1 below for a complete listing of valid DIP switch settings.
Primarily intended for operation during installation or troubleshooting, the IQ+ also features two push button switches on the face of the controller that can be used to drive the valve fully open or closed. To prevent inadvertent valve operation, these switches cannot be used if the IQ+ valve is in Control Mode (green Ctrl LED on).
TABLE 5.1 – DIP SWITCH CONFIGURATION
SW1 SW2 SW3 SW4 VALVE SIZE
0 0 0 0 1 inch
0 0 0 1 1.5 inch
0 0 1 0 2 inch
0 0 1 1 2.5 inch
0 1 0 0 3 inch
0 1 0 1 4 inch
0 1 1 0 6 inch
0 1 1 1 8 inch
1 0 0 0 10 inch
1 0 0 1 12 inch
1 0 1 0 14 inch
1 0 1 1 16 inch
1 1 0 0 TBD
1 1 0 1 TBD
1 1 1 0 TBD
1 1 1 1 TBD
1212
IQ+ OP-LIT 9/08
Visit our Web Site www.n-c.com
IntellIsys AdAptIve pressure Controllers
6.0 - RS-232 Serial Interface and Commands
Interface basics
All IQ+ controllers support RS-232 serial communications available though auxiliary port. A full description of the communications protocol and a listing of all active serial commands follows in this section. A three-wire connection needs to be completed to provide the communications lines, with Rxd (data from the IQ+), Txd (data to the IQ+) as well as signal common on. See Section 3.0 for details.
NOTE: Hardware handshaking is not available.
NOTE: The default factory RS-232 communications parameter settings are 9600 Baud, 1 stop bit, no parity and 8-bit character.
These settings can only be changed using a serial command.
Every serial input command sent by the HOST has an end-of-line delimiter, carriage return ASCII 0x0D [hex], or the line feed character ASCII 0x0A [hex], or the carriage return and line feed character in that order. The IQ+ -device end-of-line delimiter is the carriage return and line feed characters.
Serial Commands Summary
Table 6.1 and 6.2 summarize the serial commands and responses available with the IQ+ controller. Additional commands
may be included to enable customer specific functions. Please contact Nor-Cal Products Intellisys Customer Support for more details.
TABLE 6.1 – RS-232 SERIAL COMMANDS
SERIAL
COMMAND DESCRIPTION
C Close the valve Same function as pressing the CLOSE button
O Open the valve Same function as pressing the OPEN button
H Hold the valve in the current position Stops active pressure control, if device is in that mode
T1x
S1xx.xx
D1 Activates set-point #1. Put the device in control mode, effectively making the setpoint active.
Vxx.xx Go to valve position xx.xx is 0 to 100% of full open
L0 Auto select CDG1 or CDG2 for best resolution Default two gauge configuration. L1 Control to and report CDG1 values only Selects Gauge 1 for manitenance function.
L2 Control to and report CDG2 values only Selects Gauge 2 for manitenance function. N1xx Sets the full scale range of CDG1 Values for xx can be found in Table 6.3 N2xx Sets the full scale range of CDG2 Values for xx can be found in Table 6.3
J4
Sets the type of set point #1. When x=0, the set-point type is position. When x=1, the set-point type is pressure.
Used to program a value for set point xx.xx is any number between 0.00 and
100.00, representing the % of gauge full scale
Clears the “initialization safety lock feature” included on some TPV and TSS controllers
RS-232 Commands Examples
The following section provides examples of the most commonly used commands and responses. The serial command protocol is not case sensitive, though all the command examples in this section are listed in capital letters. Furthermore, whenever necessary the character Ø has been used to designate the number zero, so as to not confuse it with the letter O.
TABLE 6.2 – RS-232 SERIAL REQUESTS AND RESPONSES
SERIAL
REQUEST DESCRIPTION
R1
R5
R6
R38
R26
GSN RN1 RN2
RESET
Requests the set point value S1+xxxx, where xxxx is a number from 0.00 to 100.00 Requests the current pressure P+xxxx, where xxxx is a number from 0.00 to 100.00 Requests the current valve position V+xxxx, where xxxx is a number from 0.00 to 100.00 Requests the software version IQ+3-[version #] [version date] (text)
Report set point type
Get the serial number of the device SN: xxxxxxxx Requests full scale range of CDG1 N1xx.xx, where xx.xx is the full scale range of CDG1 in Torr Requests full scale range of CDG2 N2xx.xx, where xx.xx is the full scale range of CDG2 in Torr Resets the device Same as cycling power
NOTES / EXAMPLES
S150, for example, programs the value of 50% for the setpoint. When using a 1 Torr gauge, this corresponds to 500 mTorr..
Initializes Valve
RESPONSE
T1x, When x=0, the set-point type is position. When x=1, the set-point type is pressure.
Call toll free 800-824-4166 or 530-842-4457 FAX 530-842-9130
IQ+ OP-LIT 9/08
13
IntellIsys AdAptIve pressure Controllers
6.0 - RS-232 Serial Interface and Commands (continued)
Modifying the Setpoint
The IQ+ controller normally has five programmable set point selectable to be either pressure control or valve position control. Before using the set point to control either pressure or valve position, the set point value must be programmed. This is done by the following command:
S1xx.xx where xx.xx is a number from 0.00 to 100.00.
One or no decimal places may also be used i.e. x.x or x.
Reading the Setpoint
The set point can be read back to the Host controller only through the serial port.
o verify the set point
R1 T
The IQ controller will respond with
S1+xx.xx where xx.xx is the set point value.
Selecting Valve Position Control or Pressure Control
The set point input value is common for both valve position and pressure control. Therefore, it is necessary to program the IQ+ so that it controls to the correct type. The factory default setting is pressure control.
Set set point type
T1x where X=0 g position control T1x where X=1 g Pressure control (default)
Verifying the Control Mode
Before starting either pressure control or position control operations it might be necessary to verify the setting of the set point type. This can only be accomplished through the serial port with the command
R26
The IQ controller responds with:
here x is Ø for position control or 1 for pressure control (default).
T1x w
How to Control Valve Position
One of the two main functions of the IQ+ controller is Valve Position Control. In this mode the IQ+ controller will simply move the throttle valve plate to a prescribed position according to a set point. The set point is a value between 0% and 100%, where 0% is closed and 100% is open.
OPEN: The serial command is O.
The controller will only respond by opening the valve.
CLOSE: The serial command is C.
The controller will only respond by closing the valve.
HOLD: The serial command is H. The controller will
only respond by stopping the valve at the current position.
lve Position: Vxx.xx where xx.xx is a number from
Any Va
0.00 to 100.00% of full open. One or no decimal places may also be used i.e. x.x or x.
Similarly use the T1Ø command to set the set point type to position control. Then follow the information outlined in the How To Modify the Setpoint and How To Control System Pressure sections.
Reading the Valve Position
The valve position may also be obtained through the serial port.
The valve position is reported as a % of full open using the command:
R6
The Controller responds with the valve position using the format:
xxx.xx where xx.xx is a number from 0.00 to 100%
V+
of valve open position.
How to Control System Pressure
The principal function of the IQ+ controller is to control system pressure. To accomplish this, the controller needs to be put in “pressure control mode” while being supplied a pressure set point. The pressure set point is propor­tional to the vacuum gauge’s full scale range.
Controlling pressure using the serial port provides additional flexibility.
To activate a set point issue the command: D1
The active set point must be set to the correct value before activating the pressure control set point. The set point can be modified any time before, dur­ing, or after pressure control. Also a different set point can be activated at any time.
Note: For pressure control mode, the setpoint type must = 1, i.e. T11
Reading System Pressure
Pressure, as output by the system gauge(s) to the IQ+ Controller, can be read directly from the controller. Both the signals from CDG1 and CDG2 can be read independently.
The IQ+ controller will report the pressure via the serial port with the following command:
R5
The controller will respond with:
P+xx.xx where + indicates the polarity of
the value and xx.xx is the valuein % relative to CDG1 full scale.
The range of xx.xx is from 0.00 to 100.00 and represents the pressure as a percentage of the full scale of the CDG1 pressure gauge. The value can be less than 0 if the vacuum gauge electronics have drifted or greater than 100 but limited to 110%. For example, it the system uses a 100 Torr gauge and the pressure is actually 10 Torr, the controller response will be P+10.00. On the other hand, if the pressure is 10 Torr but the system has a 20 Torr gauge, the controller response will be P+50.00.
When two CDG’s are used, the IQ+ will always report the pressure as a percentage of the high range gauge. For example, if the system has a 100 Torr gauge attached to CDG1 and a 1 Torr gauge attached to CDG2 and the actual system pressure is 0.1 Torr the response to the R5 command will be P+0.100.
IQ+ OP-LIT 9/08
1414
Visit our Web Site www.n-c.com
IntellIsys AdAptIve pressure Controllers
6.0 - RS-232 Serial Interface and Commands (continued)
Activating Dual Pressure Sensor Configuration
When two pressure gauges are attached to the IQ+ controller, the controller can operate in three distinct modes of operation.
Dedicated to the first gauge:
(This is the power-on default mode) In that mode the controller only considers CDG1 for pressure control as well as reporting. This mode is initiated by the L1 command
Dedicated to the second gauge:
In that mode the controller only considers CDG2 for pressure control. as well as reporting. This mode is initiated by the L2 command. Pressure is still reported as a % of full scale of CDG1.
The L1 and L2 commands particularly relevant to dual chamber systems venting to one single downstream exhaust valve. In that situation there are two distinct pressure gauges corresponding to each individual vacuum chamber. The IQ+ controller is then used alternatively control pressure in each chamber.
Dual range mode: (Default) LØ activates this mode, in which the controller utilizes the two gauges to
optimize the pressure measurement. Two gauges are intended to be comple­mentary in covering the dynamic pressure range. The high gauge is referred to as the primary gauge. The low gauge is designed to be the secondary gauge covering the low range measurements. In dual range mode gauges can be switched. The gauge range needs to be predefined as illustrated in the next section. The IQ+ controller will use the range information to determine the pressure at which the controller will switch from reading one CDG to another. The automatic switch over is at 90% of the full scale value of the lower range gauge when the pressure is decreasing and greater than 99% of the full scale value of the lower range gauge when the pressure is increasing. Please note that in Dual Range Mode, all set point commands are with respect to the pri­mary gauge range (CDG1).
L1 and L2 are normally used for maintenance purposes only. Restore the IQ+
to dual range made upon conpletion of maintenance usign the LØ serial com- mand
TABLE 6.3 – VALUES TYPICAL OF
XX FOR USE WITH
DU
AL RANGE MODE
CDG1 OR
CDG2
FULL SCALE
(IN TORR)
0.1 0.1
0.2 0.2
0.5 0.5 1 1 2 2
5 5
10 10 (CDG1 default)
50 50 100 100 500 500
1000 1000
0
VALUE
OF XX
Not connected
(CDG2 default)
NOTE: Any number can
be used for a gauge full scale.
How to Configure Pressure Sensor Parameters
When two pressure gauges are used it is necessary to program the IQ+ with sufficient information so that it knows the full scale of each gauge and, hence, the ratio of the full scale pressure ranges. The factory default full-scale range for CDG1 is 10 Torr, and that for CDG2 is 0 Torr ( not con­nected).
NOTE: Programming the gauge full scale range is not necessary
when only one gauge is installed. First, program the full scale
range of CDG1 using:
N1xx where xx is the number found in Table 6.3 describing the
full scale range of CDG1. For example, enter N1100 if CDG 1 is a 100 Torr gauge or N10.25 if it is a 250 milltorr gauge.
Then, program the CDG2 full scale range with:
N2xx where the value for xx can
also be found in Table 6.3,
epresenting the CDG2 full scale.
r
he full scale of CDG1 must always
T
e greater than that of CDG2.
b
x N210 is a 10 Toor gauge 2.
E
Reading the Pressure Sensor Configuration
The full scale setting of the CDG’s can only be accessed through the serial port. Once the full scale ranges for CDG1 and CDG2 have been entered, the IQ+ controller will automatically calculate their ratio. A ratio of 1000:1 is the limit between the two pressure gauges.
Verify the CDG entries by querying the IQ+ controller for a CDG range report with the following commands:
RN1
The controller will respond with:
N1xx.xx where xx.xx is the full scale range of CDG1.
To check the full scale range of CDG2 send the command:
RN2
The controller will respond with
N2xx.xx where xx.xx is the full scale range of CDG2.
Call toll free 800-824-4166 or 530-842-4457 FAX 530-842-9130
IQ+ OP-LIT 9/08
15
IntellIsys AdAptIve pressure Controllers
6.1 - How to Configure IQ+ for Your System
System Configuration Parameters
There are three parameters to adjust that will affect how the valve will react to changes in gas flow and pressure set points.
The parameters only need to be set once and will cover the full range of pro­cess pressure setpoints. The three parameters are:
lume
Vo
Delay
Speed
Volume
Volume is a Dependent phase multiplier and is based on the size of the pres­sure chamber and controls how fast the valve will react.
No specific relationship to physical chamber size (example: a setting of 50 does not equal a 50L chamber).
ume is 0. Range is 1-100.
The default setting for Vo
If the pressure signal over shoots the set point, increase the value of Vo
l
FIGURE 6.1 – VOLUME TOO LOW
ume.
l
FIGURE 6.2 .1– VOLUME TOO HIGH
Delay
Feedback delay compensates for the physical properties of the vacuum system that cause delays in the pressure gauge readings when a pressure change occurs.
Keep the Delay setting as low as possible.
The default value of Delay is 0. Range is 0-10.
If Delay is adjusted, it should be set as low as possible.
If the pressure signal oscillates at set point then increase Delay.
If the pressure signal under shoots the set point, decrease the value of
Volume.
FIGURE 6.2 – VOLUME TOO HIGH
FIGURE 6.3 – DELAY TOO LOW
Speed
The default setting for Speed is 100 (100%). Range is 1-100. Normally this parameter does not require adjustment.
Reducing speed will help reduce low frequency oscilations. Speed should be reduced only after any adjustments to Vo have failed. When reducing Speed, set Delay to 0..
Maximum valve speed during pressure control does not affect the Open-Close, or Close-Open valve speed. If Speed is set too high the pressure will oscillate at set point (See Fig. 6.4). If Speed is set too low the valve will move slowly (See Fig. 6.5).
lume and Delay
1616
IQ+ OP-LIT 9/08
Visit our Web Site www.n-c.com
IntellIsys AdAptIve pressure Controllers
6.1 - How to Configure IQ+ for Your System (continued)
FIGURE 6.4 – SPEED TOO HIGH
System Configuration Commands
DeviceNet Commands
Class ID 33 hex Instance ID 1 (Process Control)
Setting Volume, Delay and Speed
FIGURE 6.5 – SPEED TOO LOW
E 6.4 – DEVICENET COMMANDS
TABL
ATTRIBUTE ID HEX ACCESS CODE NAME FORMAT VALUE
64 OE (get) 10 (set) Volume INT 1-100, default = 0
65 OE (get) 10 (set) Delay INT 0-10, default = 0
66 OE (get) 10 (set) Speet INT 1-100, default = 100
TABLE 6.5 – RS-232 SERIAL COMMANDS
SERIAL COMMAND DESCRIPTION RESPONSE
SVxxx Set Volume where xxx is a number from 1 to 100 PID VOLUME: xxx
SDxxx Set Delay where xxx is a number from 1 to 10 PID DELAY: xxx
SSxxx Set Speed where xxx is a number from 1 to 100 PID SPEED: xxx
TABLE 6.6 – RS-232 SERIAL REQUESTS AND RESPONSES
SERIAL REQUEST DESCRIPTION RESPONSE
RV Requests Volume value PIC VOLUME: xxx
RD Requests Delay value PID DELAY: xxx
RS Requests Speed value PID SPEED: xxx
RPI Requests values of Volume, Delay and Speed SPEED: xxx
VOLUME: xxx DELAY: xxx
A Record the current Volume, Delay, and Speed parameters.
or serial interface set the serial port speed 100ms or less. For Devicenet
F
B
set to 50ms. Or less.
C Start pressure control at a process critical set point, or a set point halfway
between the system maximum and minimum process pressure set points. With the system GUI or a PC that can graph data observe the pressure and
valve movement.
D If the pressure parameters need adjusting stop pressure control and Open
the valve. Enter new value for pressure parameters.
Setting Volume, Delay and Speed (Example)
The system has a 1 Torr pressure gauge. The pressure control range is 20mTorr - 600 mTorr. The process critical range is 120mTorr.
A Record values of Volume, Delay, and Speed.
Start pressure control with a set point 120mTorr. Adjust the parameters if
B
necessary.
C Start pressure control with a set point of 20mTorr. Adjust parameters if
Call toll free 800-824-4166 or 530-842-4457 FAX 530-842-9130
necessary. If any changes are made then re-check the 120mTorr set point.
D Start pressure control at 600mTorr.. Adjust the parameters if neces-
sary. If any changes are made then re-check the 120mTorr and 20mTorr set points.
E Record new values of Volume, Delay, and Speed.
l
Parameters are adjusted in this order: Vo
ume Delay Speed
(not normally adjusted)
E If the pressure response is satisfactory, input a set point at the system
minimum pressure or another process critical set point. Make adjustments as necessary. If a change was made re-check pressure set point in step C.
F If the pressure response is satisfactory, input a set point at system maxi-
mum pressure. Adjust if necessary. If a change was made re-check set points in steps C and D.
G Record new parameters for Volume, Delay, and Speed.
IQ+ OP-LIT 9/08
17
IntellIsys AdAptIve pressure Controllers
250Kb
P
RATE
500Kb125Kb
1 Drain
4 CAN_H
3 V-
2 V+
5 CAN_L
MSD
LSD
4
6
2
8
2
4
6
P
ADDRESS
0
0
7.0 - DeviceNet Interface
7.1. Overview and setup
DeviceNet is a network communication protocol that provides a cost-effective solution to low-level device networking for semiconductor equipment tools. Process data and other information such as configuration parameters can be communicated for up to 64 nodes per network at data rate up to 500K baud. The DeviceNet pressure controller conforms to the ODVA & ControlNet International, Ltd. Process Control Valve (PCV) device profile. This device profile is available in the CIP Networks Library: Volume One, Edition 3.3 -- The Common Industrial Protocol (CIP Accordingly, the purpose of this manual is to provide an overview on the basic use of the DeviceNet communication interface as it relates to the IQ+ pressure controller, as well as report the different options supported by the controller soft­ware communication interface.
DeviceNet Connector:
The communication port is a sealed micro­style M12 male connector that conforms to the DeviceNet specification. The connector pin out is shown in Figure 7.1.
DeviceNet requires power input of 11-24 VDC provided through the DeviceNet connector. Separately, the controller unit requires a 24 VDC +/- 10% power source, which is provided through the power connector. See section 3.0.
TM
) of the official DeviceNet specification.
FIGURE 7.1 - DEVICENET
CONNECTOR PIN ASSIGNMENT
Mo
dule Status: A bicolor (red/green) Module status LED indicates the status
of the communication module according to the logic in Table 7.1.
TABLE 7.1 - DEVICENET MODULE LED STATUS
LED STATUS
Green Module OK
Red Fault condition
Flashing Red Lost DeviceNet power OFF No DC power
Network Status:
A bicolor (red/green) Network status LED indicates the status of the communi­cation link according to the logic in Table 7.2.
TABLE 7.2 - DEVICENET NETWORK LED STATUS
LED STATUS
Flashing Green Network OK device online Green Network OK connection established Flashing Red Recoverable fault Red Unrecoverable fault OFF No network detected
ud Rate Selection:
Ba
The baud rate selector as shown in Figure 7.2 is a 4 position rotary switch used to select the desired baud
FIGURE 7.2 -
DEVICENET BAUD RATE
SELECTION SWITCH
rate of the controller, respectively 125Kb, 250Kb, 500Kb and software programmable. The factory default setting is 125Kb. The software programmable baud rate is kept in non-volatile memory and settable through the DeviceNet object.
CID Selector:
MA
Two rotary switches are used to set the MACID of the device on the network between 0 and 63 and software programmable. Note that MACID 0 is com-
monly reserved for the DeviceNet network master and should not be used by any device. The factory default setting is MACID 63. Additionally, positions 64 to 99 correspond to the software programmable setting. The MACID programmed in non-volatile memory will then be used.
The software programmable MACID is
FIGURE 8.3 - DEVICENET
ADDRESS SWITCHES
configurable via DeviceNet. However, note
that a change to the baud rate and MACID switches only becomes effective once the device is reset. This happens automatically
hen setting the MACID in programmable
w
mode.
No network detected:
This is an indication from the software that multiple attempts to publish a message (typically a duplicate MACID check message) have been made but no acknowledgement of that message has been received. It is the normal mode of operation if the network connection is not used.
Network OK
device online:
If the device successfully detects a live bus it will transition to flashing green, that is the standby mode, the device is ready for the master node to establish a connection.
Network OK
connection established:
When the device has successfully been attributed a connection by the master the network LED will transition to solid green.
Recoverable fault:
If the master unexpectedly drops the DeviceNet connection (lets the slave time out) the LED will transition to flashing red, signaling the occurrence of a time out fault. If the network master re-establishes the connection the device will then recover to normal operating mode.
Unrecoverable fault:
A red Network LED signals the occurrence of a major network fault such as two devices having the same MACID, an incompatible baud rate setting or a short in the communication signal lines.
1818
Visit our Web Site www.n-c.com
IQ+ OP-LIT 9/08
IntellIsys AdAptIve pressure Controllers
SSTechnology
interface card SST 5136 DN
Tool
system
CAN_H
CAN_L
V+
V-
Drain
Interface
Card
Power Supply
+24v
GND
IQ+ based
Controller 1
Controller 2
Controller 3
Other Devices
Cordset
InterlinkBT RSC572-*M
Drop Junction
InterlinkBT VB2-FKM FKM FSM 57
BUS
IQ+ based
IQ+ based
7.1. Overview and setup (continued)
Required Hardware:
A DeviceNet network is composed of a host controller, a bus and one or more external devices such as IQ+. The master node or host controller is commonly composed of a computer equipped with a DeviceNet interface card. The bus is made of cable connectors and junctions generally arranged in trunkline­dropline configuration as shown in Figure 7.4.
Interface and bus system part numbers are given as indication only. The IQD Controllers come ready to plug into any qualified DeviceNet network.
Prior to power up, you must initially:
1. Select the appropriate baud rate.
All the devices on the network must operate
t the same baud rate.
a
2. Select an individual device MACID that is
not already in use by another device.
IQ+ controller devices can be plugged in and removed from the network live, however, if an inappropriate baud rate setting is selected it will bring the IQ+ controller to a network fault and possibly bring other installed devices on the bus to a fault. Upon connection the IQ+ controller will transmit a duplicate MACID check to verify the uniqueness of its address. If another device with the same MACID address is detected the IQ+ Controller transitions to a red network LED status.
Power Supply System and Typical Configuration:
It is essential for the controller to have dedicated access to the pressure gauge. Accordingly the preferred configuration is for the controller to host the gauge through the analog signal link while the controller takes charge of reporting the process parameter through the DeviceNet communication link.
The IQ+ controllers require external 24 VDC power for operation. This must be applied to the XLR power port. The DeviceNet interface requires separate power input via the DeviceNet cable connection. This DeviceNet link can be powered from 11 to 24 VDC.
General Considerations for Valve Operation Using DeviceNet
DeviceNet is an object oriented communications protocol. The Process Control Valve device type encompasses several objects from the Hierarchy of Semiconductor Equipment Device Objects (see figure 9.1). These objects are managed by the S-Device Supervisor Object, which tasks include reporting device status. The interaction with the device can be carried out in different ways. The Selection Object is a router object which directs setpoint data to the desired destination – pressure control or position control – via the S-Single Stage Controller Object. Instead of setting a setpoint through the Selection Object, it can be set directly in the S-Single Stage Controller Object. Process data is gathered from the S-Analog Sensor Object, which provides pressure data from up to two pressure gauges and valve position data. This document contains exam­ples of how to set and get parameters through DeviceNet.
To be able to perform pressure or position control, the controller must first be transitioned to the device Executing state. This can be done in one of two ways; explicitly by means of executing a Start service request or by sending valid polled I/O data to the controller. See the DeviceNet Communications section for a more detailed description on how this is done. See figure 9.2 for more details on device states.
Pressure control is performed based on the selected process variable source. By default, the selection will be automatic based on the pres­sure range that each pressure gauge covers. Setting a setpoint using automatic switching will be relative to the high gauge range, if multiple gauges are used. The source can be forced to either the low or the high range gauge. When the source used is set to “automatic”, the source actually reporting the pressure data can be retrieved through the S­Analog Sensor Object.
Some Nor-Cal valves require initialization before they are ready for opera­tion. Nor-Cal has an Initialize service designed solely for this purpose. See S-Device Supervisor Object section for more information on which valve models are affected.
FIGURE 7.4 - TYPICAL DEVICENET HARDWARE
INSTALLATION
Call toll free 800-824-4166 or 530-842-4457 FAX 530-842-9130
IQ+ OP-LIT 9/08
19
IntellIsys AdAptIve pressure Controllers
7.2 - DeviceNet Communications
This section describes how to communicate with and control the controller using the DeviceNet port. DeviceNet has two basic message types: Explicit and I/O messaging
Explicit Me Explicit messages are used to read or write an individual piece of information
in the device. They are mainly used for initial configuration. Explicit messages include the path to locate the data of interest, this consists of the class ID, attribute ID, and instance number. They also specify an action to be taken. The table below lists some of the key information available through explicit messaging. Please refer to Section 9 for the full device profile characteristic.
CLASS
ID
The most straightforward way of sending individual commands to the controller is to use a node-commissioning software utility. These utilities are part of the DeviceNet interface card package.
Explicit messaging connection examples:
P
L
T
Note that in DeviceNet communications, data to and from the device is always encoded least significant byte first as specified in the data management sec­tion of the DeviceNet protocol specification. For instance the value 12345678 hex is encoded as follow:
OCTET NUMBER
OU
How to get device identity information:
S
S
S
S
T
or 612 dec, which is the vendor ID that has been attributed to N
C
T
meaning 2B13A hex or 176442 dec, which is the serial number of the d (
ssaging:
TABLE 7.3 - DEVICENET EXPLICIT MESSAGING
INSTANCE
HEX
1 1 1 1 1 6 1 1 7 3 1 1 3 1 2
31 1 6
31 2 6
31 3 6
2E 1 5
2E 1 9
ID
HEX
ATTRIBUTE
ID
HEX
SERVICE ID
0E (get) Vendor ID 0E (get) Serial Number 0E (get) Product Name 0E (get) 10 (set) MACID 0E (get) 10 (set) Baud Rate
0E (get)
0E (get)
0E (get) Valve position
0E (get) 10 (set)
0E (get) 10 (set) Process setpoint
HEX
VARIABLE
NAME
Process input (low range)
Process input (high range)
Pressure control and position control
ower up the device, the network LED will transition to flashing green et the master open an explicit connection with the device he network LED will transition to solid green
1st 2nd 3rd 4th
TPUT DATA
78 56 34 12
elect the service code 0E (get attribute) elect class ID 1 (select the identity object) elect instance ID 1 (there is only instance supported) elect attribute ID 1 (vendor ID attribute) he device will respond with data bytes 64 02 meaning 264 hex
or-Cal Products Inc. hange the attribute ID for 6 (serial number attribute)
he device will respond with data bytes on the form, 3A B1 02 00
evice.
Nor-Cal device serial numbers are composed of at least 6 digits)
How initialize the valve (not required on all valve types):
elect the service code 32 (initialize service)
S
Select class ID 30 (select the s-device supervisor object) elect instance ID 1
S
How to transition the controller to the executing state:
To be able to perform pressure or position control by means of explicit messaging, the controller has to be transitioned to the device Executing state.
elect the service code 6 (start service)
S elect class ID 30 (select the s-device supervisor object)
S elect instance ID 1
S
How to control valve position:
elect the service code 10 (set attribute)
S
elect class ID 2E (select the selection object)
S
elect instance ID 1 (setpoint)
S
elect attribute ID 0E (destination used) followed by the data 02 (position
S
control)
hen
t
elect the service code 10 (set attribute)
S
elect class ID 2E (select the selection object)
S
elect instance ID 1 (setpoint)
S
elect attribute ID 0F (source data value) followed by the setpoint 00 40
S
he device will move the valve to 50% of its stroke
T
elect attribute ID 0F (source data value) followed by the
S
setpoint 00 00 The device will move the valve to 0% of its
troke or closed
s
How to control pressure:
Select the service code 10 (set attribute)
elect class ID 2E (select the selection object)
S elect instance ID 1 (setpoint)
S elect attribute ID 0E (destination used) followed by 01 (pressure control)
S
then
elect the service code 10 (set attribute)
S
Select class ID 2E (select the selection object) elect instance ID 1 (setpoint)
S elect attribute ID 0F (source data value) followed by the setpoint 00 20
S
pressure control)
(
he device will try to control pressure at 25% of full scale of the selected
T ressure source
p
elect attribute ID 0F (source data value) followed by the setpoint FF 7F
S he device will try to control pressure at 100% of full scale of the selected
T
ressure source
p
How to read the valve limit switch:
elect the service code 0E (get attribute)
S
elect class ID 8 (select the discrete input point object)
S
elect instance ID 1 (closed limit switch)
S
elect attribute ID 3
S
he device will respond with data bytes 01 meaning that
T
the close limit switch is activated and the valve is closed
elect instance ID 2 (open limit switch)
S
elect attribute ID 3
S
he device will respond with data bytes 00 meaning that
T
the open limit switch is not activated and the valve is not opened
Note: The examples above assume that default data
type (INT) and data units (Counts) is used.
IQ+ OP-LIT 9/08
2020
Visit our Web Site www.n-c.com
IntellIsys AdAptIve pressure Controllers
7.2 - DeviceNet Communications (continued)
How to read system pressure and valve position:
elect the service code 0E (get attribute)
S
Select class ID 31 (select the s-analog sensor object)
elect instance ID 1 (process input low range)
S
elect attribute ID 6 (value attribute)
S
he device will respond with data bytes 00 00
T
meaning that the measured pressure is 0
elect instance ID 3 (valve position)
S
elect attribute ID 6 (value attribute). The device will respond
S
with data bytes FF 7F meaning that the valve position is fully open.
OUTPUT ASSEMBLY FORMATS
INSTANCE HEX VARIABLES
7
(default)
17
97
(Master / Slave)
INSTANCE HEX VARIABLES
2
(default)
4
5
0B
12
1A
96
97
(Master / Slave)
TABLE 7.4
Control setpoint Control instance
FP-Control setpoint Control instance
Control mode Pressure setpoint Position setpoint Control instance Individual valve control (address) Individual valve control (action)
INPUT ASSEMBLY FORMATS
TABLE 7.5
Exception status Process variable
Exception status Process variable Control setpoint
Exception status Process variable Control setpoint Valve position
Exception status Process variable Valve
Discrete
Input 2
Exception status FP-Process variable
Exception status FP - Process variable FP - Valve
Discrete
Input 2
Exception status Process variable input 1 (low range) Process variable input 2 (high range) Valve Active process input instance
Discrete
Input 2
Control mode Pressure setpoint Position setpoint Control instance Individual valve control (address) Individual valve control (action)
Discrete
Input 1
Discrete
Input 1
Discrete
Input 1
Input/Output Messaging:
I/O messaging is used to read and write data to the device on a periodic basis. They are used for transmission of a continuous stream of data such as setpoint or process pressure. I/O messages have limited overhead and rely on a prearranged set of data called assemblies. The IQ+ controller handles input assemblies and output assemblies in a poll connection. In an I/O poll connection the tool DeviceNet controller periodically sends an output assembly and the IQ+ responds with an input assembly. The IQ+ supports 3 output and 8 input assembly formats. For polled I /O connections, the device will automatically transition to the device Executing state after the first valid I/O data has been received.
Example of I/O messaging transactions:
The following is an example format of a typical poll connection, using default settings.
After having opened the I/O connection the master sends the following data:
BYTE DESCRIPTION DATA RANGE
1 2
3
4
Setpoint (low byte) Setpoint (high byte)
Setpoint destination (low byte)
Setpoint destination (high byte)
0 to 7FFFh
00 for no operation 01 for pressure control 02 for position control
Note: The setpoint is a number from 0000 hex to 7FFF hex covering the
range 0 to 100%. In other words, in pressure control mode, 7FFF hex represent full scale of the selected pressure source. If the pressure gauge used is 1 Torr then a set point of 4000 hex will control pressure to 0.5 Torr.
In valve position control mode, 7FFF hex represents full open stroke. Respectively, 0000 hex setpoint corresponds to closing the valve and 7FFF hex corresponds to fully opening the valve.
The controller response is formatted accordingly:
BYTE DESCRIPTION DATA RANGE
1
exception status See table 8.8.2 on page 12
2
pressure (low byte)
3
pressure (high byte)
0 to 6000h
Note: Data types and data units may be changed in application objects
handling pressure and position related attributes. Data type can only be changed if no I/O connection has been established using a related attribute and the device is in idle state. Data units can only be changed when the device is in idle state. Changes to these attributes in application objects are non-volatile (recorded in NVRAM).
IQ+ OP-LIT 9/08
Call toll free 800-824-4166 or 530-842-4457 FAX 530-842-9130
21
IntellIsys AdAptIve pressure Controllers
Discrete
Input Class
Connection
Class
I/O
I/O
I/O
Explicit
Message
Explicit
Message
Explicit
Message
Message
Router
Assembly
Assembly
Assembly
S-Device
Supervisor
DeviceNet
Identity
Hierarchy of
Semiconductor Equipment
Device Objects
Selection Class
S-Analog Sensor
Class
Process 1
Process 2
S-Single Stage
Controller Class
Process
Position
Setpoint
Close
Limit
Open
Limit
S-Analog
Actuator
Position
Control
Variable
DeviceNet
(not a member of the Hierachy)
Master/Slave
8.0 - DeviceNet Device Profile
Figure 8.1 - Object Model for the Process Control Valve Device
2222
IQ+ OP-LIT 9/08
Visit our Web Site www.n-c.com
IntellIsys AdAptIve pressure Controllers
8.1 - Identity Object
Class ID 1 hex Instance ID 1
Vendor ID: Assigned number to
Nor-Cal Products Inc. is 612
Device type: The value of 1Dhex
is used for process control valve
(cf. specification One, Edition 3.3, page 6-182)
Product code: Nor-Cal Products
attributes a specific product code
as a function of the valve size or type.
8.2 - Message Router Object
TABLE 8.1.1 – IDENTITY OBJECT ATTRIBUTES AND SERVICES
ATTRIBUTE ID HEX SERVICE ID HEX NAME FORMAT VALUE
1 0E (get) 2 0E (get) 3 0E (get) 4 0E (get) 5 0E (get) 6 0E (get) 7 0E (get)
None 05 (reset)
Vendor ID UINT 612 (264 h) (ROM) Device Type UINT 00 1D (ROM) Product Code UINT 00 xx (NVRAM) Revision UINT(maj.)+UINT(min.) xx xx (ROM) Status WORD See table 8.1.2 Serial Number 32 bits (6 digits) xxxxxx (NVRAM) Product Name String <=32 “INTELLISYS” (ROM) Invokes reset service: 0 = DeviceNet reset (default reset)
1 = out of box reset (NVRAM reset + DeviceNet reset) 64h = device power cycle
TABLE 8.1.2 IDENTITY OBJECT STATUS BIT
BIT DEFINITION
0 1 2 3
4-7
8
9 10 11
12-15
MAP
Owned Reserved (=0) Configured Reserved (=0) Extended device status Minor recoverable fault Minor unrecoverable fault Major recoverable fault Major unrecoverable fault Reserved (=0)
Class ID 2 hex Instance ID 1
No class or instance attributes supported.
8.3 - DeviceNet Object
Class ID 3 hex Instance ID 1
ATTRIBUTE ID HEX SERVICE ID HEX NAME FORMAT VALUE
The values of attribute 1 and 2
are retrieved from NVRAM if
the front panel switches are set to program mode; otherwise, the value selected by the front panel switch is reported.
The set service of attribute 1 and 2
directly updates the value for these
attributes in NVRAM. When setting the MAC ID, the device will auto- matically reset. To update baud rate, a manual hardware or software reset has to be executed.
The value of attributes 2 and 9 are
decoded as follows: 0=125Kb, 1=250Kb, 2=500Kb
8.4 - Assembly Object
TABLE 8.3.1 – DEVICENET OBJECT ATTRIBUTES AND SERVICES
1 0E (get) 10 (set) 2 0E (get) 10 (set) 5 0E (get)
6 0E (get)
7 0E (get)
8 0E (get)
9 0E (get)
None 4B None 4C
MAC ID USINT 0-63 (from NVRAM in P mode) Baud Rate USINT 0-2 (from NVRAM in P mode) Allocation info Byte+Byte Allocation choice + master ID
MAC ID switch changed
Baud rate switch changed
MAC ID switch value
Baud rate switch value
Allocate master/slave connection Release master/slave connection
BOOL
BOOL
USINT 0-99
USINT 0-9
0 = No Change, 1 = Change since last reset or
power-up 0 = No Change,
1 = Change since last reset or power-up
Class ID 4 hex Instance ID (see static assembly Table 9.5.1 and 9.5.2)
Get or set service selectively supported as a function of the selected instance in the connection object.
ATTRIBUTE ID HEX SERVICE ID HEX NAME FORMAT VALUE
Call toll free 800-824-4166 or 530-842-4457 FAX 530-842-9130
TABLE 8.4.1 – ASSEMBLY OBJECT ATTRIBUTES
3
0E (get) 10 (set) Data ARRAY Static assembly
IQ+ OP-LIT 9/08
23
IntellIsys AdAptIve pressure Controllers
8.5 - I/O Assembly Instances
TABLE 8.5.1 – OUTPUT ASSEMBLY INSTANCES
INSTANCE HEX BYTE VARIABLES EPATH HEX
0-1
7 (default)
17
97
(Master Slave)
Control setpoint
2-3
Control instance
0-3
FP - Control setpoint
4-5
Control instance
0
Control mode
1-2
Pressure setpoint
3-4
Position setpoint
5
Control instance
6
Individual valve control (address)
7
Individual valve control (action)
INSTANCE HEX BYTE VARIABLES EPATH HEX
2
(default)
4 0
5 0
0B 0
12 0
1A 0
96 0
98
(Master/Slave)
0
Exception status
1-2
Process variable
Exception status Process variable
1-2
Control setpoint
3-4
Exception status Process variable
1-2
Control setpoint
3-4
Valve position
5-6
Exception status Process variable
1-2
Valve
3-4
5 Discrete
Exception status
1-4
FP - Process variable Exception status
FP - Process variable
1-4
FP - Valve
5-8
9 Discrete
Exception status Process variable input 1 (low range)
1-2
Process variable input 2 (high range)
3-4
Valve
5-6
Active process input instance
7 8 Discrete
0
Exception Status
1-2
Process variable input 1 (low range)
3-4
Process variable input 2 (high range)
5-6
Valve
7
Device Status
8
Cluster information (address 00 - Master)
...
8 +
...
nn
Cluster information (address
20 04 24 07 30 03
20 04 24 17 30 03
20 04 24 97 30 03
TABLE 8.5.2 – INPUT ASSEMBLY INSTANCES
The control instance indicates the significance of the control
setpoint: 1 = pressure control 2 = position control.
20 04 24 07 30 03
20 04 24 04 30 03
20 04 24 05 30 03
20 04 24 0B 30 03
input 2
input 2
input 2
nn – Slave nn)
Discrete
Input 1
20 04 24 12 30 03
20 04 24 1A 30 03
Discrete
Input 1
20 04 24 96 30 03
Discrete
Input 1
20 04 24 98 30 03
2424
Note: The process variable will be based on the full scale
range of the active sensor except for instance 96 hex and instance 98 hex, where it is based on the full scale range of each individual sensor. The active sensor can be determined from attribute 5F hex, Active instance number, of the
S-Analog Sensor Object, class instance 0.
Note: Assembly instances 97 hex and 98 hex are
described in detail in the Master/Slave Object section.
Note: After establishing an I/O connection, data types of appli-
cation objects related to attributes included in the I/O assem­blies will self-adjust to give consistency in data type between pressure related and position related attributes. This applies to attributes of the S-Analog Sensor Object, the S-Analog Actuator Object and the S-Single Stage Controller Object
IQ+ OP-LIT 9/08
Visit our Web Site www.n-c.com
IntellIsys AdAptIve pressure Controllers
TABLE 8.6.1 – CONNECTION OBJECT ATTRIBUTES
ATTRIBUTE ID HEX SERVICE ID HEX NAME FORMAT VALUE
1 0E (get)
State
UINT
0-5, 0=no cxn, 3=cxnted
2 0E (get)
Instance type
UINT
0=explicit, 1=IO
3 0E (get)
Transport class trigger
BYTE
80,82,83
4 0E (get)
Produced connection ID
UINT
FBh 05h (EC), FFh 03h (IO)
5 0E (get)
Consumed connection ID
UINT
FCh 05h (EC), FDh 05h (IO)
6 0E (get)
Initial com. char.
BYTE
21 for EC, 01 for IO
7 0E (get)
Produced connection size
UINT
12h (EC), 7h (IO)
8 0E (get)
Consumed connection size
UINT
12h (EC), 3h (IO)
9 0E (get) 10 (set)
Expected packet rate
UINT
Connection timing
0C 0E (get)
Watchdog time out action
UINT
1 for EC, 0 for IO
0D 0E (get)
Produced connection length
UINT
0 in EC, 6 in IO
0E 0E (get) 10 (set)
Produced connection path
EPATH
IO input assembly path
0F 0E (get)
Consumed connection length
UINT
0 in EC, 6 in IO
10 0E (get) 10 (set)
Consumed connection path
EPATH
IO output assembly path
11 0E (get)
Production inhibit time
UINT
00
8.6 - Connection Object
Class ID 5 hex Instance ID 1, 2 (1=EC, 2=IO)
Attribute 0E &10: Setting of this
attribute is allowed only when in configure I/O state.
EPATH returns an “invalid
The current assembly path is
Watch dog timeout action:
0 = transition to timeout, (IO only) 1= auto delete 2= auto reset (IO only) 3= deferred delete (EC only)
Attribute 7 and 8: report 12 for
explicit connection or the actual
8.7 - Discrete Input Point Object
Class ID 8 hex Instance ID 1 1 = closed 0 = not closed
Instance ID 2 1 = open 0 = not open
8.8 - S - Device Supervisor Object
Attempt to set unsupported
attribute value” error.
stored in the device’s NVRAM and restored on power up.
static assembly length in IO.
Note: EC = Explicit Messaging Connection, IO = I/O Connection
TABLE 8.7.1 - DISCRETE INPUT POINT OBJECT ATTRIBUTE; INSTANCE ID 1
ATTRIBUTE ID HEX SERVICE ID HEX NAME FORMAT VALUE
1
ATTRIBUTE ID HEX SERVICE ID HEX NAME FORMAT VALUE
3
0E (get) Open limit switch BOOL 0-1
TABLE 8.7.2 - DISCRETE INPUT POINT OBJECT ATTRIBUTE; INSTANCE ID 2
0E (get) Open limit switch BOOL 0-1
Class ID 30 hex
Instance ID 1
TABLE 8.8.1 – S-DEVICE SUPERVISOR OBJECT ATTRIBUTES AND SERVICES
ATTRIBUTE ID HEX SERVICE ID HEX NAME FORMAT VALUE
3 4 5 6 7 8
9 0B 0C
OD
OE
None None None
None
None
None
None
Call toll free 800-824-4166 or 530-842-4457 FAX 530-842-9130
0E (get) Device Type Short string “PCV” (ROM) 0E (get) SEMI rev. Level Short string “E54-0997” (ROM) 0E (get) Manufacturer name Short string “NOR-CAL” (ROM) 0E (get) Model number Short string (ROM) 0E (get) Software revision level Short string (ROM) 0E (get) Hardware revision level Short string (ROM) 0E (get) Manufacturer’s serial number Short string (ROM) 0E (get) Device status USINT See table 8.8.4 0E (get) Exception status BYTE See table 8.8.4 OE (get) Exception detail alarm STRUCT See table 8.11.3 OE (get) Exception detail warning STRUCT See table 8.11.3 05 (reset) Resets device to self-testing state 06 (start) Move the device to executing state 07 (stop) Moves device to Idle state
32 (initialize valve)
4B (abort) Moves device to Abort state
4C (recover Resets device to self-testing state
4D (perform diagnostics)
Initializes valve and transitions device from self-testing state to Idle state (not needed for all valve types)
Perform diagnostic routines (will return device to self-testing state if not in Abort state); parameters TBD
detail bits determines the exception bits
NOTE: A logical ‘OR’ of the related
TABLE 8.8.2 - S-DEVICE SUPERVISOR OBJECT
DEVICE STATUS VALUE
ATTRIBUTE
VALUE
STATE
0 Undefined 1 Self testing 2 Idle 3 Self test exception 4 Executing 5 Abort 6 Critical fault
7-50 Reserved
51-99 Devicenet specific
NOTE: At power on, butterfly valves proceed
directly to idle state. Pendulum valves will rest
at self-testing state until explicitly transitioned
to idle state for safety purposes. (Access
code 32 (initialize)
TABLE 8.8.3 – S-DEVICE SUPERVISOR OBJECT
EXCEPTION STATUS BIT MAP
BIT FUNCTION
Alarm device common
0 1
Alarm device specific
2
Alarm manufacturer specific
3
0 (reserved)
4
Warning device common
5
Warning device specific
6
Warning manufacturer specific
7
1= expanded method
IQ+ OP-LIT 9/08
25
IntellIsys AdAptIve pressure Controllers
8.8 - Device Supervisor Object (continued)
TABLE 8.8.4 - S-DEVICE SUPERVISOR OBJECT EXCEPTION DETAIL
DATA COMPONENT BIT 7 BIT 6 BIT 5 BIT 4 BIT 3 BIT 2 BIT 1 BIT 0
Comon exception
detail size
Comon exception
detail Byte #0
Comon exception
detail Byte #1
PCV Device exception
detail size
PCV Device exception
detail Byte #0
PVC Device exception
detain Byte #1
PCV Device exception
detail Blllyte #2
PVC Device exception
detail Byte #3
PVC Device exception
detail Byte #4
Manufacturer
exception detail size
Manufacturer
exception detail Byte
#0
0 0 0 0 0 0 1 0
Reserved Real-time fault Reserved Data memory Non-volatile
Reserved Reset
0 0 0 0 0 1 0 1
Process variable high † S-Analog Sensor (2)
0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0
0 0 0 0 0 0 Status Discrete
0 0 0 0 0 0 0 1
0 0 0 0 0 0 0 0
exception
Process variable high † S-Analog Sensor (2)
Mondify vendor Scheduled
Process variable high † S-Analog Sensor (2)
maintenance
due
Process variable high † S-Analog Sensor (2)
memory
PS input
voltage
Process variable high † S-Analog Sensor (2)
Code
memory
PS output
voltage
Process variable high † S-Analog Sensor (2)
Microprocessor Diagnostic
Reserved PS over
Process variable high † S-Analog Sensor (2)
Input Point (2)
PProcess variable high † S-Analog Sensor (2)
Discrete Input
current
Status
Point (1)
* Only used in the warning exception detail. This bit is always = 0 in the Alarm exception detail † Warning and alarm levels for S-Analog Sensor Object are the full scale and zero sensor readings †† Warning and alarm bits are set for S-Single Stage Controller when setpoint cannot be reached
NOTE: The bitmap for Warning exception detail and Alarm exception detail is the same.
IQ+ OP-LIT 9/08
2626
Visit our Web Site www.n-c.com
IntellIsys AdAptIve pressure Controllers
Self-Testing
Self-Test Exception
Idle
Abort
Executing
Critical Fault
Self test failed
Condition cleared
Power on Reset Diagnostic request
Self-test passed
Stop request
Time out
Connection deleted
Start request
Or first valid IO data
Abort request
Recover request
Abort request
Abort request
Critical Fault
from any state
FIGURE 8.2 - OBJECT STATE TRANSITION DIAGRAM
8.9 - S-Analog Sensor Object
Class ID 31 hex Instance ID 0 (class-level)
NOTE: This class subclass only apply to
instances 1 and 2.
Identifies the gauge providing the
pressure value for input Assemblies and S-Single Stage Controller Object, Instance 1
Instance ID 1, 2 (process input)
ATTRIBUTE ID HEX SERVICE ID HEX NAME FORMAT VALUE
ATTRIBUTE ID HEX SERVICE ID HEX NAME FORMAT VALUE
TABLE 8.9.0 - S-ANALOG SENSOR OBJECT CLASS ATTRIBUTES; INSTANCE 0
5F
63
0E (get) Active instance number UINT
OE (get) Subclass UINT I = Instance Selector
TABLE 8.9.1 – S-ANALOG SENSOR OBJECT ATTRIBUTES; INSTANCE 1, 2
3
0E (get) 10 (set) Data type USINT
If two pressure sensors are used,
instance 1 corresponds to the low range pressure sensor and instance 2
4
0E (get) 10 (set) Data units UINT
corresponds to the high range pressure sensor
The process input value is a signed 16-bit integer encoded with least significant byte first and scaled
according to
5
6
7
0E (get) Reading valid BOOL
0E (get) Value
0E (get) Status BYTE See table 8.9.3
6000 hex = 100% of full scale sensor reading
0A
0E (get) Full Scale REAL
0000 hex = 0
The process input signal acquisition
range is currently limited to -5% to
C7
0E (get) 10 (set) Full Scale REAL
110%
Attribute C7 is used to set the full scale value of the sensor in Torr
60
63
0E (get) 10 (set)
0E (get) Subclass UINT 6 = Transfer function
Instance 3 (valve position)
NOTE: There is no subclass for instance 3.
The Valve position value is a signed
16-bit integer encoded with least
ATTRIBUTE ID HEX SERVICE ID HEX NAME FORMAT VALUE
3
TABLE 8.9.2 – S-ANALOG SENSOR OBJECT ATTRIBUTES; INSTANCE 3
0E (get) 10 (set) Data type USINT
significant byte first and scaled to 7FFF hex = open 0000 hex = closed
Call toll free 800-824-4166 or 530-842-4457 FAX 530-842-9130
TABLE 8.9.3 –S-ANALOG
SENSOR OBJECT STATUS BIT MAP
BIT DEFINITION
0 1 2 3
4-7
High Alarm Low Alarm High Warning Low Warning Reserved
4
5
6
7
0A
0E (get) 10 (set) Data units UINT
0E (get) Reading valid BOOL
0E (get) Value
0E (get) Status BYTE See table 9.9.3
0E (get) Full Scale
NOTE: High alarm and warning levels are 6000 hex for instance 1 and 7FFF hex for instance 2.
Low alarm and warning levels are 0000 hex for both instances.
Pressure variable
mapping function
1 = Low range CDG 2 = High range CDG
C3h = INT (default) CAh = REAL
1001h = Counts (default) 1007h = Percent 1301h = Torr
0 = invalid reading 1 = valid reading
Specified by
Data type
Analog input value
The Value of full scale of the sensor
The Value of full scale of the sensor
Default 0.0 Torr (instance 1) Default 10.0 Torr (instance 2)
USINT 0 = None (linear)
C3h = INT (default) CAh = REAL
1001h = Counts (default) 1007h = Percent 1703h = Degrees
0 = invalid reading 1 = valid reading
Specified by
Data type
Specified by
data type
Analog input value
The Value of full scale of the sensor
IQ+ OP-LIT 9/08
27
IntellIsys AdAptIve pressure Controllers
8.10 - S-Analog Actuator Object
Class ID 32 hex
Instance ID 1
ATTRIBUTE ID HEX SERVICE ID HEX NAME FORMAT VALUE
TABLE 8.10.1 – S-ANALOG ACTUATOR OBJECT ATTRIBUTES
3 0E (get) 10 (set) Data type USINT
4 0E (get) 10 (set) Data units UINT
5 0E (get) 10 (set) Override USINT
6 0E (get) Value
7 0E (get) Status BYTE Alarm & Warning, Default = 0
15 OE (get) 10 (set) Safe State USINT See table 8.10.4
TABLE 8.10.2 –S-ANALOG
ACTUATOR EXCEPTION
ST
ATUS BITMAP
BIT DEFINITION
0
High Alarm
1
NA
2
High Warning
3
NA
4-7
reserved
TABLE 8.10.3 – S-ANALOG ACTUATOR OBJECT
ATTRIBUTE
VALUE
0 1 2 3 4
5-63
8.11 - S-Single Stage Controller Object
Class ID 33 hex
Instance ID 1 (process control)
NOTE: This device uses an adaptive
Gain and Phase adjustment
mechanism and can not be changed
C
hanges to sensor crossover
attributes are non-volatile
(recorded in NVRAM)
C
ontrol optimization is done in
real time and there is no learning
calibration sequence
ATTRIBUTE ID HEX SERVICE ID HEX NAME FORMAT VALUE
3 0E (get) 10 (set) Data type USINT
4 0E (get) 10 (set) Data units UINT
5 0E (get) 10 (set) Control Mode USINT See table 8.11.3
6 10 (set) Setpoint UINT
7 0E (get)
9 OE (get) 10 (set) Control Variable
0A 0E (get) Status BYTE See table 8.11.4 11 OE (get) 10 (set) Safe State USINT See table 8.11.5
59 0E (get) 10 (set)
5A 0E (get) 10 (set) Sensor crossover low Specified by data type 100% of low range gauge full scale (default) 5C OE (get) Phase REAL Derivative gain 5C OE (get) Kap REAL Second derivative gain
5E OE (get) Gain REAL Proportional gain
60 0E (get) 10 (set)
63 0E (get) Subclass UINT 1 = PID & source select
64 OE (get) 10 (set) Volume INT
65 OE (get) 10 (set) Delay INT Feedback delay Kap multiplier 0-10, default = 0
66 OE (get) 10 (set) Speet INT
C3h = INT (default) CAh = REAL
1001h = Counts (default) 1007h = Percent 1703h = Degrees
Specifies the operational mode of the controller, see table 8.10.3
Specified by
data type
OVERRIDE VALUE
ST
ATE
Normal Zero (closed) Maximum value (open) Hold Safe State (See Table 8.10.4) Reserved
TABLE 8.11.1 – S-SINGLE STAGE CONTROLLER OBJECT ATTRIBUTES; INSTANCE 1
Process variable
Sensor crossover
Process variable
Analog output value
(Pressure)
high
source
TABLE 8.10.4 – S-ANALOG ACTUATOR
OBJECT SAFE STATE VALUE
ATTRIBUTE
VALUE
0 1 2 3
4-63
Specified by data type
Specified by S-Analog
Actuator Object data
type
Specified by data type 0.9% of high range gauge full scale (default)
BYTE
Override attribute to
verride the Value
o
ttribute when in the
a device Executing state. For all other states, the Safe state will be used.
his attribute has the
T
ame effect as Control
s
ode of the S-Single
M
tage Controller Object
S
ST
ATE
Closed Open Hold (Default) Safe Value - Closed Reserved
C3h = INT (default) CAh = REAL
1001h = Counts (default 1007h = Percent 1301h = Torr
0 to 7FFFh for 0 to 100%
Analog output value Linked to S-Analog Sensor Object, instance 1 and 2
Drive signal output Linked to S-Analog Actuator Object, instance 1 0000h - 7FFFh
1 = Low range CDG 2 = High range CDG 3 = automatic
Chamber volume-dependent phase multiplier 1-100, default = 0
Max speed of valve during pressure control 1-100, default = 100
NOTE: Use the
IQ+ OP-LIT 9/08
2828
Visit our Web Site www.n-c.com
IntellIsys AdAptIve pressure Controllers
8.11 - S-Single Stage Controller Object (continued)
TABLE 8.11.2 – S-SINGLE STAGE CONTROLLER OBJECT ATTRIBUTES; INSTANCE 2
Instance ID 2 (position control)
NOTE: There is no subclass
for instance 2
ATTRIBUTE ID HEX SERVICE ID HEX NAME FORMAT VALUE
3 0E (get) 10 (set) Data type USINT
4 0E (get) 10 (set) Data units UINT
5 0E (get) 10 (set) Control Mode USINT See table 8.11.3 6 10 (set) Setpoint UINT Specified by data type
7 0E (get)
9 OE (get) 10 (set)
0A 0E (get) Status BYTE See table 8.11.4 11 OE (get) 10 (set) Safe State USINT See table 8.11.5
Process
variable
(Position)
Control variable
Specified by
data type
Specified by S­Analog Actuator Object data type
C3h = INT (default) CAh = Real
1001h = Counts (default 1007h = Percent 1703h = Degrees
Analog output value Linked to S-Analog Sensor Object, instance 3
Drive signal output Linked to S-Analog Actuator Object, instance 1 0000h - 7FFFh
TABLE 8.11.3 – S-STAGE CONTROLLER
OBJECT CONTROL MODE VALUE
ATTRIBUTE
VALUE
0 1 2 3 4
5-63
ST
ATE
Normal Closed Open Hold Safe State (Closed) Reserved
TABLE 8.11.4 – S-SINGLE
STAGE CONTROLLER OBJECT
STATUS BITMAP
BIT DEFINITION
Alarm exception
0
0 = cleared, 1 = set
1
Warning exception 0 = cleared, 1 = set
2-7
Reserved
TABLE 8.11.5 – S-SINGLE STAGE
CONTROLLER OBJECT SAFE STATE VALUE
ATTRIBUTE
VALUE
0 1 2 3
4-63
ST
ATE
Closed Open Hold (Default) Safe Value - Closed Reserved
Call toll free 800-824-4166 or 530-842-4457 FAX 530-842-9130
IQ+ OP-LIT 9/08
29
IntellIsys AdAptIve pressure Controllers
8.12 - Selection Object
Class ID 2E hex
Instance ID 1 (setpoint)
A
ttribute 0E determines
the selection between
pressure control or valve control (1 for pressure control, 2 for position control), default is 1 after reset.
A
change on attribute 0E
only becomes effective
once a new setpoint is sent (attribute 0F)
W
hen in pressure
control (destination used =1)
writing a new setpoint is immediately tasking the controller to regulate to the designated pressure
W
hen in position control
(destination used=2) writing a
new setpoint will directly affect the valve position
TABLE 8.12.1 – SELECTION OBJECT ATTRIBUTES; INSTANCE 1
ATTRIBUTE ID HEX SERVICE ID HEX NAME FORMAT VALUE
0 = Non-existent
1 0E (get)
2 0E (get)
3 0E (get)
4 0E (get)
5 0E (get)
6 0E (get)
8 0E (get)
0A 0E (get)
0D 0E (get)
0E 0E (get) 10 (set)
0F 0E (get) 10 (set)
State
Max destinations
Number of destinations
Destination List
Max sources
Number of sources
Source used UINT 00
Algorithm type
Object source list
Destination used
Input data value
USINT
UINT
UINT
Array of
STRUCT of
{Path length
(USINT)
Destination
path (EPATH)}
UINT
UINT
USINT
Array of
STRUCT of
{Path length
(USINT)
Destination
path (EPATH)}
UINT
UINT
1 = Idle 2 = Running
02
02
06 20 33 24 01 30 06 - S-Single Stage Controller, Instance 1, setpoint
06 20 33 24 02 30 06 - S-Single Stage Controller, Instance 2, setpoint
00
00
04 = Programmable data flow
00
Range = 0-2
Data type determined by destination used
TABLE 8.12.2 – SELECTION OBJECT ATTRIBUTES; INSTANCE 2
ATTRIBUTE ID HEX SERVICE ID HEX NAME FORMAT VALUE
0 = Non existent
1 0E (get)
2 0E (get)
3 0E (get)
4 0E (get)
5 0E (get)
6 0E (get)
8 0E (get)
0A 0E (get)
0D 0E (get)
0E 0E (get) 10 (set)
0F 0E (get) 10 (set)
State
Max destinations
Number of destinations
Destination list
Max Sources
Number of sources
Source used
Algorithm type
Object source list
Destination used
Input data value
USINT
UINT
UINT
Array of
STRUCT of
{Path length
(USINT)
Destination
path (EPATH)}
UINT
UINT
UINT
USINT
Array of
STRUCT of
{Path length
(USINT)
Destination
path (EPATH)}
UINT
UINT
1= Idle 2 = Running
01
01
06 20 32 24 01 30 06 - S-Analog Actuator Object, Instance 1, Value
02
02
00
04 = Programmable data flow
06 20 33 24 01 30 09 - S-Single Stage Controller Instance 1, Control Variable 06 20 33 24 02 30 09 - S-Single Stage Controller, Instance 2, Control Variable
01
Data type determined by S-Analog Actuator data type
IQ+ OP-LIT 9/08
3030
Visit our Web Site www.n-c.com
IntellIsys AdAptIve pressure Controllers
8.13 - Master/Slave Object
Class ID 64 he
Instance ID 1 (master)
ATTRIBUTE ID HEX SERVICE ID HEX NAME FORMAT VALUE
• When setting attribute 70,
Number of slaves, to a number greater than 0, the controller will automati- cally transition to Master mode. This attribute is only settable when no I/O connection using assembly instance 98 has been established.
TABLE 8.13.2 MASTER/SLAVE OBJECT INDIVIDUAL
VALVE CONTROL (ACTION) VALUE
ATTRIBUTE
VALUE
0, 3-254 No individual control
1 Freeze and close
2 Freeze and open
255 Unfreeze
I
NDIVIDUAL VALUE
ACTION
TABLE 8.13.1 – MASTER/SLAVE OBJECT ATTRIBUTES
70 0E (get) 10 (set)
73 0E (get) 10 (set)
74 0E (get) 10 (set)
75 0E (get)
76 0E (get)
None 05 (reset)
None 32 (initialize valve)
None 33 (reset faulted valve)
TABLE 8.13.3MASTER/SLAVE OBJECT DEVICE
STATUS VALUE
ATTRIBUTE
VALUE
0 Unknown
2 Position control
3 Closed
4 Open
5 Pressure control
6 Hold
12 Power failure
13 Safety mode
14 Fatal error
Number of
Slaves
Individual
valve control
(address)
Individual
valve control
(action)
Device status
information
Cluster
information
Invokes power reset service: 0 255=reset all valves
Initializes valve and transitions device from self-testing state to Idle state (not needed for all valve types) 0-nn=initialize valve number nn 255= initialize all valves
Invokes power reset service on faulted valves: 0-nn=reset faulted valve number nn 255= reset all faulted valves
STATE
USINT Range 0-10
Range 0 - nn = total number
USINT
USINT See table 8.13.2
BYTE See table 8.13.3
Array of BYTE See table 8.13.4
TABLE 8.13.4MASTER/SLAVE OBJECT
of Slaves (invalid value = no individual control)
-
nn=reset valve number nn
CLUSTER INFORMATION BITMAP
BIT DEFINITION
None set Normal operation
0 Closed
1 Open
2 Closed and frozen
3 Open and frozen
4 Fatal error
5 Power fail not ready
6 Reserved
7 Offline
warning
Master/Slave Operation:
If not previously set in the factory, set the number of Slaves through attribute 70 hex. After updating the attribute, the device will require a DeviceNet reset for all Master/Slave functions to work properly. Setting the ‘Number of Slaves’ attribute to a non-zero number will automatically configure the DeviceNet controller to act as a Master controller. After the DeviceNet controller has been set up as a Master, all connected Slaves will follow the Master’s movements unless instructed differently by the Master.
The Master/Slave system is best controlled using assembly output instance 97 hex and assembly input instance 98 hex. Using these assemblies, the slave valves will follow the Master movements. The Master and slaves can be individually operated by setting the individual valve control attributes to desired values.
For system safety reasons, should any valve have a problem (valve fault, communication problem, loss of power), all other valves will stop at their current position. Should there be a problem with DeviceNet, all valves will close. This could happen if DeviceNet power is lost or if a DeviceNet connection times out.
NOTE: Slave device addresses have to be set up sequentially,
i.e. for a system with three Slaves, the Slave addresses should be set to 01, 02, and 03 respectively. The Master controller will automatically have address 00.
Call toll free 800-824-4166 or 530-842-4457 FAX 530-842-9130
IQ+ OP-LIT 9/08
31
IntellIsys AdAptIve pressure Controllers
IntellIsys AdAptIve pressure Controllers
8.13 - Master/Slave Object
E
8.13.5 SLAVE NETWORK LED STATUS
TABL
LED STATUS
Flashing Green Network OK device online
Green Network OK connection
Flashing Red Connection timed out
NOTE: If a Slave valve has a problem of any kind, the Master
will indicate this by flashing the fault LED. For all other conditions, the Master LEDs operate the same as a standard IQ+ controller.
(continued)
established
9.0 - Battery Back-Up
Some APC models, including the IQ+ controller, are available with a power safe battery back-up option. When installed, this feature will drive the valve closed in the event of a power interruption to the APC controller. This is more commonly of interest when throttling gate- or pendulum valves are used, because these valves typically also serve as the vacuum line isolation valve. The following describes the general functionality and specifications of the battery back-up feature.
Battery Pack Information
Specially packaged 15-cell, 18V 500 mA·H Ni-Cd battery assembly.
Battery Life
Depends on various factors including temperature, number of discharge cycles, battery age, starting charge and valve type. Generally, however, a new freshly charged battery should close a typical gate- or pendulum valve ten times, or more, without being depleted to the point where full actuation is no longer possible.
Recharge Time
Depends on various factors including battery age, state of discharge and to a lesser degree temperature. Under normal conditions, a fully depleted battery should charge completely in approximately 5 hours. Recharging occurs auto­matically provided that the battery is still capable of being charged.
Battery Status
The battery voltage can be read by issuing the RS232 serial command GV. The controller will respond with the internal Power Supply voltage and the battery voltage as measured on the main PCB.
Battery Back-up Activation and Operation
The controller software continuously monitors the operating voltage delivered to it by the internal Power Supply. If that voltage drops below a certain thresh­old level for more than 50 msec, then the IQ+ disconnects all external power outputs (such as ±15 VDC), exits its present operational state and drives the valve closed using battery power. Once the valve is closed, the IQ+ disconnects itself altogether and shuts down.
Valve Close Speed
The speed at which the valve closes under battery power is the same as during normal operation.
Resuming Normal Operation
Once normal power is back on, the IQ+ controller will reinitialize the butterfly valve and be ready for operation after about 30 seconds. However, if the IQ+ controller is configured with the valve initialization safety lock function, then the J4 serial command needs to be issued before valve initialization can occur.
NOTE: The battery voltage reported may not be a true
indication of the battery’s condition, because the voltage is read
while the battery is in an unloaded state. Nor-Cal recommends replacing the battery approximately every 24 months, irrespective of apparent condition or usage history. Please refer to Appendix I for ordering information. Always obtain replacement battery packs from Nor-Cal Products.
3232
Visit our Web Site www.n-c.com
IQ+ OP-LIT 9/08
IQ+ OP-LIT 9/08
IntellIsys AdAptIve pressure Controllers
10.0 - Product Support
WARNING: When working with or troubleshooting Nor-Cal APC products extreme care must be taken to avoid putting bodily parts
in or near the valve gate mechanism or other moving parts. These may move suddenly and unexpectedly, and many of them are driven with sufficient force so as to cause significant harm and possibly even dismemberment. Nor-Cal Products recommends that a lock-out and tag-out procedure be strictly followed whenever human physical intervention is required on any of its control valves.
CAUTION: DO NOT open the enclosure. Damage to equipment may occur, and unauthorized access to internal parts will void the warranty.
Troubleshooting
Some basic troubleshooting can be done by the user referring to the instructions and suggestions in the table below which describes common symptoms and recommended actions. The Nor-Cal Products’ IQ+ controller module is designed for years of maintenance free operation. Electronics MTBF has been determined to be in excess of 10,000 hours continuous operation. There are no user serviceable parts or components inside the enclosure. If a problem does occur with the IQ+ control electronics or software, please refer to the basic troubleshooting instructions below or contact Nor-Cal Products Intellisys Customer Support to obtain additional instructions or a Return Materials Authorization number.
TABLE 10.1 – POSSIBLE FAILURE MODES AND RECOMMENDED ACTIONS
SYMPTOM POSSIBLE CAUSES RECOMMENDED ACTION
IQ+ does not appear to turn on. No LEDs are illuminated
The IQ+ is on (one or more LEDs illuminated) but it will not respond to commands
The IQ+ does not operate and only the amber FAULT LED is on.
Pressure control performance is unsatisfactory
The controller / valve will not respond to a new set-point value
The LEDs are illuminated in an unknown fashion
The IQ+ is not receiving power properly
The initialization safety lock function is active. The amber FAULT LED should be on and the OPEN/CLOSE LEDs should be blinking
The RS-232 serial connections are not properly made.
Communication settings disagree between the IQ+ and the host
A communications timeout has occurred Call for Intellisys Technical Support
The valve plate and/or actuator is jammed
There is something wrong with the motor drive circuitry or the internal power supply circutry
The IQ+ is not receiving the gauge pressure signal, or the signal is very noisy
The IQ+ is in valve position control mode Put the IQ+ in the correct mode by issuing the proper RS-232 or DeviceNet command System design or operating range may be
outside the capabilities of the Adaptive Pressure Control Algorithm
The new set-point value is too close to the old set-point vlaue
There is too much noise on the Gauge signal Change the Gauge Cable
Check external power supply, cabling and pin assignments. Try to restart the IQ+ by reconnecting power supply. Operate OPEN/CLOSE switches.
Execute an initialization sequence. Issue a DeviceNet initialization command or send the J4 command via the RS-232 serial port.
Check cabling and pin assignments. Make sure CTS, RTS and DSR connections are not made.
If RS-232 is used, make sure host is set for 9600 Baud, 1 stop bit and no parity. Cycle power to the IQ+ to refresh dip switch setting.
Cycle power to attempt re-initialization of the valve. For Butterfly Valves, turn power OFF and try to move the valve plate by hand. If the valve plate is stuck, call of Intellisys Technical Support
Call to obtain an RMA#
Check the gauge cabling and signal stability. Also, check for electrical noise or system vibrations, especially if a 100 m Torr (or similar) gauge is used.
Adjust System Parameters: Volume, Delay, Speed
When using serial communications, the difference between two set-point values should be more than 0.01%
Please refer to Table 12.2 describing valid LED combinations.
Call toll free 800-824-4166 or 530-842-4457 FAX 530-842-9130
IQ+ OP-LIT 9/08
33
IntellIsys AdAptIve pressure Controllers
IntellIsys AdAptIve pressure Controllers
10.0 - Product Support (continued)
TABLE 12.2 KEY
O = LED Off
= Green
G
= Flashing Green
FG
= Red
R FR = Flashing Red A = Amber
MOD NET CTRL FAULT
O O O O O / O
G G G A G / G
G O O O O / O
R O O O O / O
G FG O O O / O
G FR O O O / O
G G O O O / O
G R O O O / O
G G G O O / O
O O O A O / O
G G G O G or G
G O G O O / O
G O G O G or G
O O O A FG / FG
TABLE 10.2 – VALID STATUS LED COMBINATIONS
OPE
N/
CLOSE CO
MMENTS
All LEDs off. IQ+ is not receiving power, or internal software is corrupt. All LEDs on. This is valid for about 1 second after
power-up for initial check-up sequence. Mod, only, is illuminated (green) during initialization sequence. Mod, only, is illuminated (red) when the DeviceNet module is
in a non-recoverable fault mode Mod on (green), Net blinking (green) means
DeviceNet module OK but waiting for a connection Mod on (green), Net blinking (red) means DeviceNet
module OK but connection has timed out (a recoverable fault) Mod and Net on (both green) means DeviceNet module OK and device is online Mod (green) and Net (red) on means DeviceNet
module OK but network has experienced an unrecoverable fault (Mod, Net and Ctrl are green) IQ+ is in DeviceNet communications mode and it is
acting on a set point with the valve somewhere between open and closed positions Mod (green) and Fault (amber) are on indicates that IQ+ has either failed part of the
initialization sequence, or the valve plate has jammed (Mod, Net, Ctrl and OPEN or CLOSE are green) IQ+ is in DeviceNet communications
mode and it is acting on a set point with the valve either in open or closed positions (Mod and Ctrl are green) IQ+ is in RS-232 communications mode and it is acting on a
set point with the valve somewhere between open and closed positions (Mod, Ctrl and OPEN or CLOSE are green) IQ+ is in DeviceNet communications mode
and it is acting on a set point with the valve either in open or closed positions Fault (amber) is on and OPEN / CLOSE are flashing.
This is an indication that the “initialization safety lock function” is active.
3434
Global Sales and Service
Nor-Cal Products maintains sales and service
centers in over 30 countries worldwide.
Please visit our website at www.n-c.com
to find the center nearest you.
Visit our Web Site www.n-c.com
IQ+ OP-LIT 9/08
IQ+ OP-LIT 9/08
IntellIsys AdAptIve pressure Controllers
Diagram 1
Diagram 2
IntellIsys AdAptIve pressure Controllers
APPENDIX I – Spare Parts and Ordering Information
To make the completion of an Intellisys downstream pressure control system easy, Nor-Cal Products offers a comprehensive selection of cables and related accessories. These include signal and communications cables, power cords, power supplies as well as spare parts.
Model Number Matrix for Adaptive Pressure Controllers IQ+
Use the model number tree at right with the matrix below to define a valid Nor-Cal Products adaptive pressure controller model number.
Choose one option from each column.
VALVE TYPE USER INTERFACE INPUT VOLTAGE COMMUNICATIONS OPTIONS
1 = Geared Throttling Buterfly Valve or
Universal Valve Drive (TBV or UVD)
2 = Direct Drive Throttling Buterfly Valve
(TBV)
3 = Geared Drive Sealing Throttling
Buterfly Valves (TBVS)
7 = Throttling Soft-Shut Valve (TSS) E = Ethernet
8 = Throttling Pendulum Valve (TPV)
00 = Standard. Buried Box
(limited switches & LEDs)
BQC
Valve Type User Interface Input Voltage Battery
A = RS-232 + Analog/TTL Blank = None
L = 24 VDC differential R = RS-485 + Analog/TTL B = Battery backup
D = RS-232 + DeviceNet
Comm. Type
2
Backup
G = Gauge Power Supply
Sxx = Customer specific
model, xx = 01, 02, etc.y
Gauge Power
Supply
Controller Cables and Accessories
Most cable and cord part numbers listed below end with the number 10 as a suffix, which represents the cable length, measured in feet. Thus, Nor-Cal’s standard cable length is 10’ (3m). However, any length between 1’ (0.3m) and 30’ (9.1m) can be supplied as a special request. Please contact Nor-Cal Products for price and availability information.
VALVE CABLE LENGTH DESCRIPTION
TBV-CRD-10 10’ APC-to-Valve cable
GAUGE CABLES LENGTH DESCRIPTION
CDG-IQ-CRD-10 10’ DC powered APC-to-gauge cable, where gauge has 5-pole terminal block
CDG-IQ-CRD-DB9-10 10’ DC powered APC-to-gauge cable, where gauge has DB-9 plug connector
CDG-IQ-CRD-DB15-10 10’ DC powered APC-to-gauge cable, where gauge has DB-15 plug connector
CDG-IQ-CRD-Y 1’
Y-cable to be used with DC powered APCs when two-gauge connection is required. Use of this Y-cable also requires the use of CDG-CRD-10, CDG-CRD­DB9-10 or CDG-CRD-DB15-10 cables.
SERIAL CABLES LENGTH DESCRIPTION
IQ-CRD-RS232-10 10’ Connects any DC powered IQ+ to a standard PC or laptop DB-9 serial port
POWER CORDS DIAGRAM # LENGTH DESCRIPTION
AC Power Cord Plug Configurations
APC -PSM -DB15 Power Supply
CRD-PWR-US1 CRD-PWR-US2
CRD-PWR-UK
CRD-PWR-EU
POWER SUPPLY PART NUMBER
IQ+ Power Supply Part number pending, call representative for information
BATTERY BACK-UP SPARE PART NUMBER
IQ+ replacement battery Part number pending, call representative for information
GAUGE POWER SUPPLY PART NUMBER
1 7’ 2 7’ 3 7’ 4 7’
TBD Part number pending, call representative for information
Call toll free 800-824-4166 or 530-842-4457 FAX 530-842-9130
10A-125V rated appliance cable. 10A-250V rated appliance cable. 10A-250V rated appliance cable. For use in the UK 10A-250V rated appliance cable. For use in Continental Europe
IQ+ OP-LIT 9/08
IQ+ OP-LIT 9/08
35
35
IntellIsys AdAptIve pressure Controllers
IntellIsys AdAptIve pressure Controllers
Appendix II - Limited Warranty and Intellectual Property Coverage
Products manufactured by Nor-Cal Products, Inc. (hereinafter referred to as “Nor-Cal”) are warranted against defects in material and workmanship for a period of twelve (12) months from the date of shipment from Nor-Cal to the buyer. Any modification to the product by the buyer or their agent voids this war­ranty. Liability under this warranty is expressly, limited to replacement or repair (at Nor-Cal ’s option) of defective parts. Nor-Cal may at any time discharge its warranty as to any of it products by refunding the purchase price and taking back the products. This warranty applies only to parts manufactured, and labor provided, by Nor-Cal under valid warranty claims received by Nor-Cal within the applicable warranty period and shall be subject to the terms and conditions hereof. Expendable items such as tubes, heaters, sources, bellows, etc., by their nature may not function for one year; if such items fail to give reasonable service for a reasonable period of time, as determined solely by Nor-Cal, they will be repaired or replaced by Nor-Cal at its election. All warranty replacement or repair of parts shall be limited to equipment malfunctions which, in the sole opinion of Nor-Cal, are due or traceable to defects in original materials or workmanship. Malfunctions caused by abuse or neglect of the equipment are expressly not covered by this warranty. Nor-Cal expressly disclaims responsibility for any loss or damage caused by the use of its products other than in accordance with proper operating and safety procedures. Reasonable care must be taken by the user to avoid hazards. In-warranty repaired or replacement parts are warranted only for the remaining unexpired portion of the original warranty period applicable to the parts that have been repaired or replaced. After expiration of the applicable warranty period, the buyer shall be charged at Nor-Cal’s then current prices for parts and labor plus transportation. Except as stated herein, Nor-Cal makes no warranty, expressed or implied (either in fact or by operation of law), statutory or otherwise: and, except as stated herein, Nor-Cal shall have no liability for special or consequential damages of any kind or from any cause arising out of the sale, installation, or use of any of its products. Statements made by any person, including representatives of Nor-Cal, which are inconsistent or in conflict with the terms of this warranty shall not be binding upon Nor-Cal unless reduced to writing and approved by an officer of Nor-Cal. Merchandise may be returned at the sole discretion of Nor-Cal Products, but not more than 60 days after shipment. A fee may be charged for restocking the item. An RMA number must be obtained from Nor-Cal before returning any merchandise.
Intellectual Property Coverage
The products described in this manual are covered under U.S. Patent numbers 5,134,349; 5,202,613; 5,321,342; and 6,612,331. Additional patents are pending.
3636
Visit our Web Site www.n-c.com
IQ+ OP-LIT 9/08
IQ+ OP-LIT 9/08
Loading...