Nokia Solutions and Networks T6FE1 User Manual

Chapter 4: Acceptance Test Procedures
Table of Contents
Automated Acceptance Test Procedure 4-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Introduction 4-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Reduced ATP 4-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ATP Test Options 4-2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ATP Prerequisites 4-2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
TX/RX Antenna Connections 4-3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Acceptance Tests – Test Set–up 4-4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Required Test Equipment 4-4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Abbreviated (All–inclusive) Acceptance Tests 4-6 . . . . . . . . . . . . . . . . . . . . . . . . . .
All–inclusive Tests 4-6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
All TX/RX ATP Test 4-6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
All TX ATP Test 4-8 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
All RX ATP Test 4-9 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4
Individual Acceptance Tests 4-11 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
RX and TX Testing 4-11 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Individual Tests 4-11 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
TX Spectral Purity Transmit Mask Acceptance Test 4-13 . . . . . . . . . . . . . . . . . . . . .
Background 4-13 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Spectral Purity TX Mask Acceptance Test 4-14 . . . . . . . . . . . . . . . . . . . . . .
TX Waveform Quality (Rho) Acceptance Test 4-16 . . . . . . . . . . . . . . . . . . . . . . . . . .
Background 4-16 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Waveform Quality (Rho) Acceptance Test 4-16 . . . . . . . . . . . . . . . . . . . . . .
TX Pilot Time Offset Acceptance Test 4-18 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Background 4-18 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
TX Code Domain Power/Noise Floor Acceptance Test 4-20 . . . . . . . . . . . . . . . . . . .
Background 4-20 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
RX FER Acceptance Test 4-23 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Background 4-23 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
FER Acceptance Test 4-23 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Generating an ATP Report 4-25 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Background 4-25 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ATP Report 4-25 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
FEB 2005 1X SC 4812T Lite BTS Optimization/ATP
PRELIMINARY
Table of Contents – continued
Updating Calibration Data Files 4-26 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Software Release Caveats 4-26 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4
1X SC 4812T Lite BTS Optimization/ATP FEB 2005
PRELIMINARY
Automated Acceptance Test Procedure
Introduction
The Acceptance Test Procedures (ATP) allow Cellular Field Engineers (CFEs) to run automated Acceptance Tests on all BTS Subsystem Devices equipped in the CDF using the LMF and the Test Equipment it supports.
The CFE can choose to save the results of ATP Tests to a report file from which ATP Reports are generated for later printing. See the Generating an ATP Report section in this chapter.
Because Test Equipment Functions during Acceptance Testing are controlled by the LMF through the GPIB, only the Test Equipment Models supported by the LMF can be used.
NOTE
– Before using the LMF, read the Release Notes
“Caveats” section in the WinLMF On-Line Help SR2.16.x for any applicable information.
– The ATP Test is to be performed on out-of-service
sectors only.
– DO NOT substitute Test Equipment with other
models not supported by the LMF.
4
Reduced A TP
Refer to Chapter 3 for detailed interconnection information needed for calibrating equipment, cables, and other Test Equipment Set components.
NOTE
Equipment has been factory–tested for FCC Compliance. If license–governing bodies require documentation
supporting BTS Site Compliance with regulations, a full ATP may be necessary.
Perform the Reduced ATP only if reports for the specific BTS Site are NOT required.
After downloading the proper operational software to the BTS, the CFE must perform these procedures (minimum recommendation):
1. Verify that the TX/RX Paths by performing TX Calibration, TX Audit, and FER Tests.
2. Retrieve Calibration Data required for normal site operation.
Should failures occur while performing the specified tests, refer to the Basic Troubleshooting section of this manual for help in determining the failure point. Once the point of failure has been identified and corrected, refer to the BTS Optimization and ATP Test Matrix (Table C-1) to determine the applicable test that must be performed.
FEB 2005 1X SC 4812T Lite BTS Optimization/ATP 4-1
PRELIMINARY
Automated Acceptance Test Procedure – continued
In the unlikely event that the BTS passes these tests but has a Forward Link problem during normal operation, the CFE should then perform the additional TX Tests for troubleshooting: TX Spectral Mask, TX Rho, and TX Code Domain.
ATP Test Options
ATP Tests can be run individually or as one of the following groups:
S All TX: TX Tests verify that the performance of the BTS Transmit
Elements. These include the GLI, MCC, BBX, Trunking Modules, the LPA Modules, and passive components including Splitters, Combiners, Bandpass Filter(s), and RF Cables.
S All RX: The RX Test verifies the performance of the BTS Receive
4
Elements. These include the MPC, EMPC (for Companion Frames), BBX, MCC, GLI Cards, and the passive components including RX Filters and RF Cables.
S All TX/RX: Executes all TX and RX Tests.
ATP Prerequisites
S Full Optimization: Executes the TX Calibration, downloads BLO,
and executes the TX Audit before running all TX and RX Tests.
Before attempting to run any ATP Tests, ensure that the following have been completed:
S BTS has been optimized (BBX Cards calibrated and BLOs
downloaded) (Chapter 3)
S The carrier(s) and/or sector(s) to be tested have been taken out of
service at the CBSC.
S LMF is logged into the BTS. S CSM Cards, GLI Cards, BBX Cards, MCC Cards and TSU (if the
RFDS is installed) have correct code and Data Loads.
S Primary CSM and GLI are INS_ACTIVE (bright green). S MCC Cards are INS_ACTIVE (bright green). S No BBX Cards are keyed (transmitting). S BBX Cards are OOS_RAM (yellow). S Test Cables are calibrated. S Test Equipment has been selected, warmed–up 60 minutes, and
calibrated.
S GPIB is on. S BTS Transmit Connectors are properly terminated for the test(s) to be
performed.
4-2 1X SC 4812T Lite BTS Optimization/ATP FEB 2005
PRELIMINARY
Automated Acceptance Test Procedure – continued
WARNING
1. All Transmit Connectors must be properly terminated for all ATP Tests.
2. Before the FER is run, make sure that one of the following is done:
– All transmitter Connectors are properly terminate
OR
– All LPA Modules are turned OFF (circuit breakers
pulled)
Failure to observe these warnings may result in bodily injury or equipment damage.
TX/RX Antenna Connections
Figure 4-1 identifies the Frame Transmit and Receive Antenna Connections where measurements are to be taken.
Figure 4-1: TX and RX Antenna Connections on I/O Panel
RX DIV RX MAIN on TRF
REAR
Not Used on DRF
4
TX on TRF or TX/RX MAIN on DRF
FRONT
FEB 2005 1X SC 4812T Lite BTS Optimization/ATP 4-3
ti-CDMA-WP-00214-v01-ildoc-ftw REF
PRELIMINARY
Acceptance Tests – Test Set–up
Required T est Equipment
The following Test Equipment is required:
S LMF S Power Meter (used with HP 8921A/600 and Advantest R3465) S Communications System Analyzer S Signal Generator for FER Testing (required for all Communications
System Analyzers for 1X FER)
WARNING
Before installing any Test Equipment directly to any
BTS TX OUT Connector, verify that there are no
4
CDMA Channels keyed.
– At active sites, have the OMC–R/CBSC place the
carrier assigned to the LPA Modules under test OOS. Failure to do so can result in serious personal injury and/or equipment damage.
Acceptance T est Equipment Set–up
NOTE
The Test Equipment must be re–calibrated before using it to perform the TX Acceptance Tests.
All ATP Testing
Perform the procedure in Table 4-1 to Set–up Test Equipment for all tests..
4-4 1X SC 4812T Lite BTS Optimization/ATP FEB 2005
PRELIMINARY
Acceptance Tests – Test Set–up – continued
Table 4-1: Set–up Test Equipment – TX Output Verify/Control Tests Procedure
n Step Action
1 If it has not already been done, interface the LMF Computer to the BTS.
– Refer to Table 3-6 and Figure 3-3.
2 If it has not already been done, start a GUI LMF Session and log into the BTS.
– Refer to Table 3-10.
3 If it has not already been done, connect Test Equipment for Acceptance Testing.
– Refer to Figure 3-20, Figure 3-21, Figure 3-22, Figure 3-23, Figure 3-24, or Figure 3-25, as
applicable, for the Test Equipment and Antenna Duplexing being used.
* IMPORTANT
LMF–based Measurements factor into TX Test Test Cable Insertion Loss between the RF Modem Frame and Test Equipment.
If additional attenuation, such as external TX Combiners, is inserted in the path, it must be identified to the LMF by including it in the TX Test Cable Calibration.
– If this is not possible, include the attenuation in the TX Path by editing Test Cable Insertion
Loss Values (refer to Table 3-35).
– Failure to do this will result in test inaccuracies and potential for erroneous ATP failures
because the additional losses would not be compensated for in the test measurements.
4
FEB 2005 1X SC 4812T Lite BTS Optimization/ATP 4-5
PRELIMINARY
Abbreviated (All–inclusive) Acceptance Tests
All–inclusive Tests
General
The all–inclusive Acceptance Tests are performed from the LMF GUI Environment. These all–inclusive tests are called abbreviated ATPs because they execute various combinations of individual Acceptance Tests with a single command. This allows verification of multiple aspects of BTS performance while minimizing time needed for individual Test Set–up and initiation.
Abbreviated ATP Options
There are three abbreviated Acceptance Tests that evaluate different performance aspects of the BTS. This allows the CFE to select testing to
4
meet the specific requirements for individual Maintenance and Performance Verification situations. The following items summarize the coverage of each Abbreviated Test.:
S All TX/RX: Performs all transmit and receive ATPs on the selected
MCC Cards and BBX Cards.
S All TX: Performs complete set of transmit ATPs on the selected MCC
Cards and BBX Cards. Testing is the equivalent of performing all of the following individual tests:
TX Mask Test – Rho Test – Pilot Time Offset TestCode Domain Power Test
S All RX: Performs complete Receive ATP on the selected MCC Cards
and BBX Cards. Testing is the equivalent of performing the FER Test.
Abbreviated Acceptance Test Procedures
Procedures to accomplish each type of Abbreviated ATP are included in the following subsections..
All TX/RX A TP Test
Perform the procedure in Table 4-2 to perform the Abbreviated, All–inclusive Transmit And Receive Test.
Table 4-2: All TX/RX Acceptance Test Procedure
n Step Action
1 Set–up the Test Equipment initially for Abbreviated Tests as described in Table 4-1.
NOTE
If the LMF has been logged into the BTS with a different Multi–Channel Preselector setting than the one to be used for this test, the LMF must be logged out of the BTS and logged in again with the new Multi–Channel Preselector setting.
– Using the wrong MPC Setting can cause a false test failure.
table continued on next page
4-6 1X SC 4812T Lite BTS Optimization/ATP FEB 2005
PRELIMINARY
Abbreviated (All–inclusive) Acceptance Tests – continued
Table 4-2: All TX/RX Acceptance Test Procedure
n ActionStep
2 Select the BBX Cards and MCC Cards to be tested. 3 Click on Tests in the BTS Menu Bar, and select All TX/RX ATP... from the Pull–down Menu. 4 Select the appropriate carrier(s) and sector(s) (carrier-bts#-sector#-carrier#) from those displayed
in the Channels/Carrier Pick List.
NOTE
To select multiple items, hold down the Shift or Ctrl Key while clicking on Pick List Items to select multiple carrier(s)–sector(s).
5 Verify that the correct Channel Number for the selected carrier is shown in the Carrier #
Channels Box.
– If it is not, obtain the latest bts–#.cdf (or bts–#.necf) and cbsc–#.CDF Files from the CBSC.
NOTE
If necessary, the correct Channel Number may be manually entered into the Carrier # Channels Box.
4
6 Select the appropriate RX Branch (BOTH, MAIN, or DIVersity) in the Pull–down Menu.
* IMPORTANT
The RX Main and Diversity Paths must be tested separately for this configuration because each requires a different Multi–Coupler Preselector type to provide the proper Test Signal Gain.
NOTE
If a Companion Frame with the Inter–frame Diversity RX Cabling disconnected is being tested do not select BOTH in this step.
7 In the Rate Set Box, select the appropriate Data Rate (1=9600 3=9600 1X) from the Pull–down
Menu.
NOTE
The Rate Set selection of 3 is only available if 1X Cards are selected for the test.
8 Enter the Channel Elements to be tested for the RX ATP in the Channel Element(s) Box.
– By default, all Channel Elements are specified. – The Channel Element Numbers are 0.based; therefore, the first Channel Element is 0.
NOTE
Use one of the following methods to enter more than one Channel Element:
– Enter non–sequential Channel Elements separated by a comma and no spaces (for example;
0,5,15).
– Enter a range of sequential Channel Elements by typing the first and last Channel Elements
separated by two periods (for example; 0..15).
table continued on next page
FEB 2005 1X SC 4812T Lite BTS Optimization/ATP 4-7
PRELIMINARY
Abbreviated (All–inclusive) Acceptance Tests – continued
Table 4-2: All TX/RX Acceptance Test Procedure
n ActionStep
9 In the Test Pattern Box, select the Test Pattern to use for the Acceptance Tests from the
Pull–down Menu.
– Refer to “Test Pattern Drop–down Pick List” under “TX Calibration and the LMF” in the Bay
Level Offset Calibration section of Chapter 3.
10 Click OK to display a Status Bar followed by a Directions Pop–up Window. 11 Execute the Cable Connection Directions as they are displayed, and click the Continue Button to
begin testing.
– As the ATP Process is completed, results will be displayed in the Status Report Window.
12 Click either the Save Results Button or the Dismiss Button.
4
* IMPORTANT
If Dismiss is used, the test results will not be saved in the Test Report File.
All TX ATP Test
Perform the procedures in Table 4-3 to perform the Abbreviated, All–inclusive Transmit Test.
Table 4-3: All TX Acceptance Test Procedure
n Step Action
1 Set–up the Test Equipment for Abbreviated Tests per Table 4-1. 2 Select the BBX Cards and MCC Cards to be tested. 3 Click on Tests in the BTS Menu Bar, and select All TX ATP... from the Pull–down Menu. 4 Select the appropriate carrier(s) and sector(s) (carrier-bts#-sector#-carrier#) from those displayed
in the Channels/Carrier Pick List.
NOTE
To select multiple items, hold down the Shift or Ctrl Key while clicking on Pick List Items to select multiple carrier(s)–sector(s).
5 Verify that the correct Channel Number for the selected carrier is shown in the Carrier #
Channels Box.
– If it is not, obtain the latest bts–#.cdf (or bts–#.necf) and cbsc–#.CDF Files from the CBSC.
NOTE
If necessary, the correct Channel Number may be manually entered into the Carrier # Channels Box.
table continued on next page
4-8 1X SC 4812T Lite BTS Optimization/ATP FEB 2005
PRELIMINARY
Abbreviated (All–inclusive) Acceptance Tests – continued
Table 4-3: All TX Acceptance Test Procedure
n ActionStep
6 In the Rate Set Box, select the appropriate Transfer Rate (1 = 9600, 3 = 9600 1X) from the
Pull–down Menu.
NOTE
The Rate Set Selection of 3 is only available if 1X Cards are selected for the test.
7 In the Test Pattern Box, select the Test Pattern to use for the Acceptance Test from the Pull–down
Menu.
– Refer to “Test Pattern Drop–down Pick List” under “TX Calibration and the LMF” in the Bay
Level Offset Calibration section of Chapter 3.
8 Click OK to display a Status Bar followed by a Directions Pop–up Window. 9 Execute the Cable Connection Directions as they are displayed, and click the Continue Button to
begin testing.
– As the ATP Process is completed, results will be displayed in the Status Report Window.
10 Click either the Save Results Button or the Dismiss Button.
4
* IMPORTANT
If Dismiss is used, the test results will not be saved in the Test Report File.
All RX A TP Test
Perform the procedure in Table 4-4 to perform the Abbreviated, All–inclusive Receive Test.
Table 4-4: All RX Acceptance Test Procedure
n Step Action
1 Set–up the Test Equipment for Abbreviated Tests per Table 4-1.
NOTE
If the LMF has been logged into the BTS with a different Multi–Channel Preselector setting than the one to be used for this test, the LMF must be logged out of the BTS and logged in again with the new Multi–Channel Preselector setting.
– Using the wrong MPC Setting can cause a false test failure.
2 Select the BBX Cards and MCC Cards to be tested. 3 Click on Tests in the BTS Menu Bar, and select All RX ATP... from the Pull–down Menu. 4 Select the appropriate carrier(s) and sector(s) (carrier-bts#-sector#-carrier#) from those displayed
in the Channels/Carrier Pick List.
NOTE
To select multiple items, hold down the Shift or Ctrl Key while clicking on Pick List Items to select multiple carrier(s)–sector(s).
table continued on next page
FEB 2005 1X SC 4812T Lite BTS Optimization/ATP 4-9
PRELIMINARY
Abbreviated (All–inclusive) Acceptance Tests – continued
Table 4-4: All RX Acceptance Test Procedure
n ActionStep
5 Verify that the correct Channel Number for the selected carrier is shown in the Carrier #
Channels Box.
– If it is not, obtain the latest bts–#.cdf (or bts–#.necf) and cbsc–#.CDF Files from the CBSC.
NOTE
If necessary, the correct Channel Number may be manually entered into the Carrier # Channels Box.
6 Select the appropriate RX Branch (BOTH, MAIN, or DIVersity) in the Pull–down Menu. 7 In the Rate Set Box, select the appropriate Data Rate (1=9600, 2=14400, 3=9600 1X) from the
Pull–down Menu.
4
NOTE
The Rate Set Selection of 1 is only available if non–1X Cards are selected for the test. The Rate Set Selection of 3 is only available if 1X Cards are selected for the test.
8 Enter the Channel Elements to be tested for the RX ATP in the Channel Element(s) Box.
– By default, all Channel Elements are specified. – The Channel Element Numbers are 0.based; that is the first Channel Element is 0.
NOTE
Use one of the following methods to enter more than one Channel Element:
– Enter non–sequential Channel Elements separated by a comma and no spaces (for example;
0,5,15).
– Enter a range of sequential Channel Elements by typing the first and last Channel Elements
separated by two periods (for example; 0..15).
9 Click OK to display a Status Bar followed by a Directions Pop–up Window.
10 Follow Cable Connection Directions as they are displayed, and click the Continue Button to
begin testing.
– When the ATP Process is completed, results will be displayed in the Status Report Window.
11 Click either the Save Results Button or the Dismiss Button.
* IMPORTANT
If Dismiss is used, the test results will not be saved in the Test Report File.
4-10 1X SC 4812T Lite BTS Optimization/ATP FEB 2005
PRELIMINARY
Individual Acceptance Tests
RX and TX Testing
The following individual ATP Tests can be used to evaluate specific aspects of BTS Operation against individual performance requirements. All testing is performed using the LMF GUI Environment.
TX Testing
TX Tests verify any given Transmit Antenna Path and Output Power Control. All tests are performed using the external, calibrated Test Equipment. All measurements are made at the appropriate BTS TX OUT Connector(s).
TX Tests verify TX Operation of the entire CDMA Forward Link using selected BBX Cards assigned to respective Sector Antennas. Each BBX is keyed–up to generate a CDMA Carrier (using both bbxlevel and BLO) at the CDF File–specified Carrier Output Power Level.
RX Testing
RX Testing verifies Receive Antenna Paths for BBX Cards selected for the test. All tests are performed using the external, calibrated Test Equipment to inject a CDMA RF Carrier with all zero Longcode at the specified RX Frequency at the appropriate BTS RX IN Connector(s).
RX Tests verify RX Operation of the entire CDMA Reverse Link using all equipped MCC Cards assigned to all respective sector/antennas.
4
Individual Tests
Spectral Purity TX Mask
This test verifies that the transmitted CDMA Carrier Waveform generated on each sector meets the transmit Spectral Mask Specification (as defined in IS–97) with respect to the assigned CDF File Values.
Waveform Quality (Rho)
This test verifies that the transmitted Pilot Channel Element Digital Waveform Quality (Rho) exceeds the minimum specified value in IS–97. Rho represents the correlation between the actual and perfect CDMA Modulation Spectrums. 1.0000 represents 100% (or perfect correlation).
Pilot Time Offset
The Pilot Time Offset is the difference between the Communications System Test Set Measurement Interval (based on the BTS System Time Reference) and the incoming block of transmitted data from the BTS (Pilot only, Walsh Code 0).
Code Domain Power/Noise Floor
This test verifies the Code Domain Power Levels, that have been set for all ODD numbered Walsh Channels, using the OCNS Command. This is done by verifying that the ratio of PILOT divided by OCNS is equal to
2 dB, and, that the Noise Floor of all EVEN–numbered “OFF”
10.2 +
Walsh Channels measures < –27 dB for IS–95A/B and CDMA2000 1X with respect to total CDMA Channel Power.
FEB 2005 1X SC 4812T Lite BTS Optimization/ATP 4-11
PRELIMINARY
Individual Acceptance Tests – continued
BTS FER
This test verifies the BTS Receive FER on all Traffic Channel Elements currently configured on all equipped MCC Cards (full rate at one percent FER) at an RF Input Level of –119 dBm on the Main RX Antenna Paths using operator–selected, CDF–equipped MCC Cards and BBX Cards at the site. Diversity RX Antenna Paths are also tested using the lowest equipped MCC Channel Element ONLY.
NOTE
There are no pass/fail criteria associated with FER Readings taken at levels below –119 dBm, other than to verify that the FER Measurement reflects changes in the RX Iinput Signal Level.
4
4-12 1X SC 4812T Lite BTS Optimization/ATP FEB 2005
PRELIMINARY
TX Spectral Purity Transmit Mask Acceptance Test
Background
Overview
This test verifies the Spectral Purity of each operator–selected BBX Carrier keyed–up at a specific frequency specified in the current CDF. All tests are performed using the external, calibrated Test Equipment controlled by the same command. All measurements are made at the appropriate BTS TX Antenna Connector..
Test Patterns
There are four operator–selectable Test Patterns with which this Acceptance Test can be performed. The patterns, along with the channels tested and Gain Setting for each, are listed in Table 3-40. Refer to “TX Calibration and the LMF” in the Bay Level Offset Calibration section of Chapter 3 for more information on the Test Patterns..
Equipment Operation During Testing
At least one MCC must be selected to perform the Standard, CDF Pilot, and CDF Test Patterns. For these Test Patterns, Forward Links are enabled for Synch Channel (SCH), Paging Channel (PCH), and Traffic Channel (TCH) Elements from the selected MCC(s), as shown in Table 3-40.
Gain is set for the applicable channels on each antenna as shown in the table. The operator–selected BBX Cards will be keyed using a BLO–corrected bbxlvl Value to generate a CDMA Carrier. RF Output Power, as measured at the appropriate Frame TX Antenna Connector, will be set to one of the following depending on the Operating Frequency Spectrum.:
S 800 MHz: 33.5 dBm S 1.9 GHz: 31.0 dBm
4
Test Measurements
The Test Equipment will measure and return the attenuation level in dB of all spurious and IM products with respect to the Mean Power of the CDMA Channel measured in a 1.23 MHz bandwidth, verifying that results meet system tolerances at the following test points. Refer to also Figure 4-2):
S For 800 MHz:
– At least –45 dB @ + 750 kHz from Center Frequency – At least –45 dB @ – 750 kHz from Center Frequency – At least –60 dB @ – 1980 kHz from Center Frequency – At least –60 dB @ + 1980 kHz from Center Frequency
S For 1.9 GHz:
– At least –45 dB @ + 885 kHz from Center Frequency – At least –45 dB @ – 885 kHz from Center Frequency – At least –55 dB @ – 1980 kHz from Center Frequency – At least –55 dB @ + 1980 kHz from Center Frequency
FEB 2005 1X SC 4812T Lite BTS Optimization/ATP 4-13
PRELIMINARY
TX Spectral Purity Transmit Mask Acceptance Test – continued
Redundant BBX Testing
The BBX will then de–key, and if selected, the Redundant BBX will be assigned to the current TX Antenna Path under test. The test will then be repeated..
Spectral Purity TX Mask Acceptance T est
Perform the procedure in Table 4-5 to verify that the Transmit Spectral Mask Specification on the TX Antenna Paths for the selected BBX Cards.
Table 4-5: Spectral Purity Transmit Mask Test Procedure
4
n Step Action
1 Set–up the Test Equipment for TX Acceptance Tests per Table 4-1. 2 Select the BBX Cards to be tested. 3 If the Test Pattern to be used is Standard, CDFPilot, or CDF; select at least one MCC.
– Refer to the “Test Pattern Drop–down Pick List” in the “BayLevel Offset Calibration” section
of Chapter 3.
4 Click on Tests in the BTS Menu Bar, and select TX > TX Mask... from the Pull–down Menus. 5 Select the appropriate carrier(s) and sector(s) (carrier-bts#-sector#-carrier#) from those displayed
in the Channels/Carrier Pick List.
NOTE
To select multiple items, hold down the Shift or Ctrl Key while clicking on Pick List Items to select multiple carrier(s)–sector(s).
6 Verify that the correct Channel Number for the selected carrier is shown in the Carrier #
Channels Box.
– If it is not, obtain the latest bts–#.cdf (or bts–#.necf) and cbsc–#.CDF Files from the CBSC.
NOTE
If necessary, the correct Channel Number may be manually entered into the Carrier # Channels Box.
7 If at least one MCC was selected in Step 3, select the appropriate Transfer Rate (1 = 9600, 3 =
9600 1X) from the Pull–down Menu in the Rate Set Box.
NOTE
The Rate Set Selection of 3 is only available if 1X Cards are selected for the test.
8 In the Test Pattern Box, select the Test Pattern to use for the Calibration from the Pull–down
Menu.
– Refer to the “Test Pattern Drop–down Pick List” under “TX Calibration and the LMF” in the
Bay Level Offset Calibration section of Chapter 3.
9 Click OK to display a Status Bar followed by a Directions Pop–up Window.
table continued on next page
4-14 1X SC 4812T Lite BTS Optimization/ATP FEB 2005
PRELIMINARY
TX Spectral Purity Transmit Mask Acceptance Test – continued
Table 4-5: Spectral Purity Transmit Mask Test Procedure
n ActionStep
10 Follow the Cable Connection Directions as they are displayed, and click the Continue Button to
begin testing.
– As the ATP Process is completed, results will be displayed in a Status Report Window.
11 Click either the Save Results Button or the Dismiss Button.
* IMPORTANT
If Dismiss is used, the test results will not be saved in the Test Report File.
Figure 4-2: TX Mask Verification Spectrum Analyzer Display
.5 MHz Span/Div Ampl 10 dB/Div
Mean CDMA Bandwidth
Power Reference
Center Frequency Reference
4
– 1980 kHz
– 885 kHz + 885 kHz
– 750 kHz
Attenuation level of all
spurious and IM products
with respect to the Mean
Power of the CDMA Channel
+ 1980 kHz
+750 kHz
FEB 2005 1X SC 4812T Lite BTS Optimization/ATP 4-15
PRELIMINARY
TX Waveform Quality (Rho) Acceptance Test
Background
Overview
This test verifies the transmitted Pilot Channel Element Digital Waveform Quality of each operator–selected BBX Carrier keyed–up at a specific frequency specified in the current CDF. All tests are performed using the external, calibrated Test Equipment controlled by the same command. All measurements are made at the appropriate TX Antenna Connector..
Equipment Operation During Testing
Pilot Gain will be set to 262 for each antenna, and all TCH Elements from the MCC Cards will be forward–link disabled. The selected BBX Cards will be keyed–up using both bbxlvl and BLO to generate a
4
CDMA Carrier (with Pilot Channel Element only, Walsh Code 0). RF Output Power is set at 40 dBm as measured at the appropriate BTS TX Antenna Connector..
Test Measurements
The Test Equipment will measure and return the Pilot Channel Element Digital Waveform Quality (Rho) Percentage, verifying that the result meets the following specification.:
Waveform Quality (Rho) should be > 0.912.
Redundant BBX Testing.
The BBX will then de–key, and if selected, the Redundant BBX will be assigned to the current TX Antenna Path under test. The test will then be repeated for the Redundant BBX..
Waveform Quality (Rho) Acceptance T est
Perform the procedure in Table 4-6 to verify that the Pilot Channel Element Waveform Quality (Rho) on the TX Antenna Paths for the selected BBX Cards.
Table 4-6: Waveform Quality (Rho) Test Procedure
n Step Action
1 Set–up the Test Equipment for TX Acceptance Tests per Table 4-1. 2 Select the BBX Cards to be tested. 3 Click on Tests in the BTS Menu Bar, and select TX > Rho... from the Pull–down Menus. 4 Select the appropriate carrier(s) and sector(s) (carrier-bts#-sector#-carrier#) from those displayed
in the Channels/Carrier Pick List.
NOTE
To select multiple items, hold down the Shift or Ctrl Key while clicking on Pick List Items to select multiple carrier(s)–sector(s).
table continued on next page
4-16 1X SC 4812T Lite BTS Optimization/ATP FEB 2005
PRELIMINARY
TX Waveform Quality (Rho) Acceptance Test – continued
Table 4-6: Waveform Quality (Rho) Test Procedure
n ActionStep
5 Verify that the correct Channel Number for the selected carrier is shown in the Carrier #
Channels Box.
– If it is not, obtain the latest bts–#.cdf (or bts–#.necf) and cbsc–#.CDF Files from the CBSC.
NOTE
If necessary, the correct Channel Number may be manually entered into the Carrier # Channels Box.
6 Click OK to display a Status Bar followed by a Directions Pop–up Window. 7 Follow the Cable Connection Directions as they are displayed, and click the Continue Button to
begin testing.
– As the ATP Process is completed, results will be displayed in a Status Report Window.
8 Click either the Save Results Button or the Dismiss Button.
* IMPORTANT
If Dismiss is used, the test results will not be saved in the Test Report File.
4
FEB 2005 1X SC 4812T Lite BTS Optimization/ATP 4-17
PRELIMINARY
TX Pilot Time Offset Acceptance Test
Background
Overview
This test verifies the transmitted Pilot Channel Element Pilot Time Offset of each operator–selected BBX Carrier keyed–up at a specific frequency specified in the current CDF. All tests will be performed using the external, calibrated Test Equipment controlled by the same command. All measurements will be made at the BTS TX Antenna Connector..
Equipment Operation During Testing
The Pilot Gain will be set to 262 for each antenna and all TCH Elements from the MCC Cards will be forward–link disabled. The
4
selected BBX Cards will be keyed using both bbxlvl and BLO to generate a CDMA Carrier (with Pilot Channel Element only, Walsh Code 0). TX Power Output is set at 40 dBm as measured at the TX Output..
Test Measurements
Pilot Time Offset Acceptance Test
The Test Equipment will measure and return the Pilot Time Offset in ms, verifying that results meet the following specification.:
Pilot Time Offset should be within 3 ms of the target PT Offset (zeroms).
.Redundant BBX Testing –
The BBX will then de–key, and if selected, the Redundant BBX will be assigned to the current TX Antenna Path under test. The test will then be repeated for the Redundant BBX..
NOTE
This test also executes and returns the TX Frequency and TX Waveform Quality (Rho) ATP Tests, however, only Pilot Time Offset results are written to the ATP Test Report.
Perform the procedure in Table 4-7 to verify that the Pilot Time Offset on the TX Antenna Paths for the selected BBX Cards.
Table 4-7: Test Pilot Time Offset
n Step Action
1 Set–up the Test Equipment for TX Acceptance Tests per Table 4-1. 2 Select the BBX Cards to be tested.
table continued on next page
4-18 1X SC 4812T Lite BTS Optimization/ATP FEB 2005
PRELIMINARY
TX Pilot Time Offset Acceptance Test – continued
Table 4-7: Test Pilot Time Offset
n ActionStep
3 Click on Tests in the BTS Menu Bar, and select TX > Pilot Time Offset... from the Pull–down
Menus.
4 Select the appropriate carrier(s) and sector(s) (carrier-bts#-sector#-carrier#) from those displayed
in the Channels/Carrier Pick List.
NOTE
To select multiple items, hold down the Shift or Ctrl Key while clicking on Pick List Items to select multiple carrier(s)–sector(s).
5 Verify that the correct Channel Number for the selected carrier is shown in the Carrier #
Channels Box.
– If it is not, obtain the latest bts–#.cdf (or bts–#.necf) and cbsc–#.CDF Files from the CBSC.
NOTE
If necessary, the correct Channel Number may be manually entered into the Carrier # Channels Box.
4
6 Click OK to display a Status Bar followed by a Directions Pop–up Window. 7 Follow the Cable Connection Directions as they are displayed, and click the Continue Button to
begin testing.
– As the ATP Process is completed, results will be displayed in a Status Report Window.
8 Click either the Save Results Button or the Dismiss Button.
* IMPORTANT
If Dismiss is used, the test results will not be saved in the Test Report File.
FEB 2005 1X SC 4812T Lite BTS Optimization/ATP 4-19
PRELIMINARY
TX Code Domain Power/Noise Floor Acceptance Test
Background
Overview
This test verifies the Code Domain Power and Noise Floor of each operator–selected BBX Carrier keyed at a specific frequency specified in the current CDF. All tests are performed using the external, calibrated Test Equipment controlled by the same command. All measurements are made at the appropriate BTS TX Antenna Connector..
CDMA Channel Test Set–up
Pilot Gain should be set to 262 for each antenna and the selected MCC Cards should be configured to supply all odd–numbered Walsh Code
4
Traffic Channel Elements by enabling Orthogonal Channel Noise Source (OCNS) on all odd MCC Channel Elements (maximum 32 Full Rate Channels with an OCNS Gain of 81).
– All even–numbered Walsh Code Traffic Channel Elements should
have OCNS disabled, and are considered “OFF”.
– Selected MCC Cards should be Forward–Link Enabled for the
antenna (sector) under test..
Equipment Operation During Testing
The BBX should be keyed–up using a BLO–corrected generate a CDMA Carrier consisting of Pilot and OCNS Channels. RF Output Power, as measured at the appropriate Frame TX Antenna Connector, is set at one of the following values depending on the Operating Frequency Spectrum.:
– 800 MHz: 33.5 dBm – 1.9 GHz: 31.0 dBm
Test Measurements
The Test Equipment will measure and return the Channel Element Power in dB of all specified Walsh Channels within the CDMA spectrum. Additional calculations will be performed to verify that the following parameters are met.
– Refer to Figure 4-3 for graphic representations.:
bbxlvl Value to
S Traffic Channel Element Power Level will be verified by calculating
the ratio of Pilot Power to OCNS Gain of all Traffic Channels [Root Sum of the Square (RSS) of each OCNS Gain divided by the Pilot Power].
– This value should be 10.2 dB + 2.0 dB.
S Noise Floor (unassigned “OFF” even–numbered Walsh Channels) is
verified to be < –27 dB for IS–95A/B and CDMA2000 1X with respect to total CDMA Channel Power
4-20 1X SC 4812T Lite BTS Optimization/ATP FEB 2005
.
PRELIMINARY
TX Code Domain Power/Noise Floor Acceptance Test – continued
NOTE
When performing this test using the LMF and the MCC is an MCC8E or MCC24E, the Redundant BBX may fail or show marginal performance. This is due to a Timing Mismatch that the LMF does not address. Performing this test from the CBSC will not have this timing problem.
Redundant BBX Testing
The BBX will then de–key, and if selected, the Redundant BBX will be assigned to the current TX Antenna Path under test. The test will then be repeated for the Redundant BBX. Upon completion of the test, OCNS Channels will be disabled on the specified MCC Channel Elements..
Code Domain Power/Noise Floor T est
Perform the procedure in Table 4-8 to verify the Code Domain Power/Noise Floor of each selected BBX Carrier keyed–up at a specific frequency.
Table 4-8: Code Domain Power/Noise Floor Test Procedure
n Step Action
1 Set–up the Test Equipment for TX Acceptance Tests per Table 4-1. 2 Select the BBX Cards and MCC Cards to be tested. 3 Click on Tests in the BTS Menu Bar, and select TX > Code Domain Power... from the
Pull–down Menus.
4 Select the appropriate carrier(s) and sector(s) (carrier-bts#-sector#-carrier#) from those displayed
in the Channels/Carrier Pick List.
NOTE
To select multiple items, hold down the Shift or Ctrl Key while clicking on Pick List Items to select multiple carrier(s)–sector(s).
5 Verify that the correct Channel Number for the selected carrier is shown in the Carrier #
Channels Box.
– If it is not, obtain the latest bts–#.cdf (or bts–#.necf) and cbsc–#.CDF Files from the CBSC.
4
NOTE
If necessary, the correct Channel Number may be manually entered into the Carrier # Channels Box.
6 If at least one MCC was selected in Step 3, select the appropriate Transfer Rate (1 = 9600, 3 =
9600 1X) from the Pull–down Menu in the Rate Set Box.
NOTE
The Rate Set selection of 3 is only available if 1X Cards are selected for the test.
table continued on next page
FEB 2005 1X SC 4812T Lite BTS Optimization/ATP 4-21
PRELIMINARY
TX Code Domain Power/Noise Floor Acceptance Test – continued
Table 4-8: Code Domain Power/Noise Floor Test Procedure
n ActionStep
7 Click OK to display a Status Bar followed by a Directions Pop–up Window. 8 Follow the Cable Connection Directions as they are displayed, and click the Continue Button to
begin testing.
– As the ATP Process is completed, results will be displayed in a Status Report Window.
9 Click either the Save Results Button or the Dismiss Button.
* IMPORTANT
If Dismiss is used, the test results will not be saved in the Test Report File.
4
Figure 4-3: Code Domain Analyzer CD Power/Noise Floor Display Examples
Pilot Channel
MAX OCNS
CHANNEL
Active channels
MIN OCNS
CHANNEL
MAX NOISE
FLOOR
Walsh 0 1 2 3 4 5 6 7 ... 63
8.2 dB 12.2 dB
Inactive channels
Code Domain Power/Noise Floor (OCNS Pass) Example
Pilot Channel
FAILURE – EXCEEDS
MAX OCNS SPEC.
Active channels
8.2 dB 12.2 dB
PILOT LEVEL
MAX OCNS SPEC. MIN OCNS SPEC.
MAXIMUM NOISE FLOOR: < –27 dB FOR IS–95A/B AND CDMA2000 1X
PILOT LEVEL
MAX OCNS SPEC. MIN OCNS SPEC.
FAILURE – DOES NOT
MEET MIN OCNS SPEC.
Walsh 0 1 2 3 4 5 6 7 ... 63
FAILURE – EXCEEDS MAX
NOISE FLOOR SPEC.
MAXIMUM NOISE FLOOR: < –27 dB FOR IS–95A/B AND CDMA2000 1X
Inactive channels
Code Domain Power/Noise Floor (OCNS Failure) Example
4-22 1X SC 4812T Lite BTS Optimization/ATP FEB 2005
PRELIMINARY
RX FER Acceptance Test
Background
Overview
This test verifies the BTS Frame Erasure Rate (FER) on all TCHs currently configured on operator–selected MCC Cards (full rate at 1% FER) at –119 dBm. All tests are performed using the external, calibrated Test Equipment as the Signal Source controlled by the same command. Measurements are made at the specified BTS RX Antenna Connection..
Equipment Operation During Testing
The Pilot Gain on each MCC will be set to 262 for each TX Antenna, and the Forward Link for all TCH Elements from the MCC Cards will be enabled. Appropriate BBX(s) must be keyed in order to enable the RX Receive Circuitry. Operator–selected BBX Cards will be keyed using only bbxlvl, to generate a CDMA Carrier with Pilot Channel Element only.
4
Transmit Power Output is set at –40 dBm. Test Equipment Output Power is set so that the received power at the BBX is –119 dBm. The Final Output Power Setting of the Test Equipment takes into account the MPC type, BTS RF Path Losses, and test Test Cable Insertion Losses. If selected, the Redundant BBX will be assigned to the current RX Antenna Paths under test..
Test Measurements
The LMF will prompt the MCC Channel Element under test to measure all–zero Longcode and provide the FER report on the selected active MCC on the Reverse Link for the Main and, if selected, Diversity RX Antenna Paths. Results are evaluated to ensure they meet the following specification.:
FER returned less than 1% and Total Frames measured is 1500
Redundant BBX Testing
After the test, the BBX and the Test Equipment will be de–keyed to shut down the Pilot Signal and the active Channel Element, respectively. If the Redundant BBX was tested, BBXR assignment to an active sector will also be reset..
FER Acceptance T est
Perform the procedure in Table 4-9 to verify the FER on RX Antenna Paths using selected MCC Cards and BBX Cards.
FEB 2005 1X SC 4812T Lite BTS Optimization/ATP 4-23
PRELIMINARY
RX FER Acceptance Test – continued
Table 4-9: FER Test Procedure
n Step Action
1 Set–up the Test Equipment for RX Acceptance Tests per Table 4-1. 2 If the LMF has been logged into the BTS with a different Multi–Channel Preselector setting than
the one to be used for this test, the LMF must be logged out of the BTS and logged in again with the new Multi–Channel Preselector Setting.
* IMPORTANT
Using the wrong MPC Setting can cause a false test failure.
3 Select the BBX Cards and MCC Cards to be tested. 4 Click on Tests in the BTS Menu Bar, and select RX > FER... from the Pull–down Menu.
4
5 Select the appropriate carrier(s) and sector(s) (carrier-bts#-sector#-carrier#) from those displayed
in the Channels/Carrier Pick List.
NOTE
To select multiple items, hold down the Shift or Ctrl Key while clicking on Pick List Items to select multiple carrier(s)–sector(s).
6 Verify that the correct Channel Number for the selected carrier is shown in the Carrier #
Channels Box.
– If it is not, obtain the latest bts–#.cdf (or bts–#.necf) and cbsc–#.CDF Files from the CBSC.
NOTE
If necessary, the correct Channel Number may be manually entered into the Carrier # Channels Box.
7 Select the appropriate RX Branch (Both, Main, or Diversity) in the Pull–down Menu. 8 In the Rate Set Box, select the appropriate Data Rate (1=9600, 2=14400, 3=9600 1X) from the
Pull–down Menu.
NOTE
The Rate Set selection of 2 is only available if non–1X Cards are selected for the test. The Rate Set selection of 3 is only available if 1X Cards are selected for the test.
9 Click OK to display a Status Bar followed by a Directions Pop–up Window.
10 Follow Cable Connection Directions as they are displayed, and click the Continue Button to
begin testing.
– As the ATP Process is completed, results will be displayed in the Status Report Window.
11 Click either the Save Results Button or the Dismiss Button.
* IMPORTANT
If Dismiss is used, the test results will not be saved in the Test Report File.
4-24 1X SC 4812T Lite BTS Optimization/ATP FEB 2005
PRELIMINARY
Generating an ATP Report
Background
ATP Report
Each time an ATP Test is run, ATP Data is updated and must be saved to an ATP Report File using the Save Results Button to close the Status Report Window. The ATP Report File will not be updated if the Status Report Window is closed using the Dismiss Button.
A separate report is created for each BTS and includes the following for each test:
S Test Name S PASS or FAIL S Description Information (if applicable) S BBX Number S Channel Number S Carrier Number S Sector Number S Upper Test Limit S Lower Test Limit S Test Result S Time Stamp S Details/Warning Information (if applicable)
Perform the procedures in the Table 4-10 to view and create a printable file for the ATP Report.
Table 4-10: ATP Report Generation Procedure
n Step Action
1 Click on the Login Tab (if not in the forefront).
4
2 Click on the desired BTS in the Available Base Stations Pick List to select it. 3 Click on the Report Button. 4 If a printable file is not needed, click on the Dismiss Button. 5 If a printable file is required, perform the following actions.
5a Select the desired file type (text, comma–delimited, HTML) for the report file from the Pull–down
Menu at the bottom of the screen.
5b Click the Save Button to save the file.
– The file will be saved in the selected format in the bts–# folder for the BTS selected.
FEB 2005 1X SC 4812T Lite BTS Optimization/ATP 4-25
PRELIMINARY
Updating Calibration Data Files
Software Release Caveats
Software Release R2.16.5.x allows the user to load the Calibration File from the LMF directly onto the MGLI. The MGLI will then FTP the new Calibration File to the OMC–R, thereby eliminating the need for the user to place the Calibration File at the OMC–R.
Copy and Load Cal File to the CBSC
After completing the TX Calibration and audit, updated CAL File information must be moved from the LMF Windows environment back to the CBSC, a UNIX environment. The following procedures detail moving files from one environment to the other.
Copying CAL Files from LMF to a Diskette
4
Table 4-11: Copy CAL Files to a Diskette Procedure
Perform the procedures in Table 4-11 to copy the CAL Files from an LMF Computer to a 3.5 diskette.
n Step Action
1 With Windows running on the LMF Computer, insert a disk into Drive A:\. 2 Launch the Windows Explorer Application Program from the Start > Programs Menu List. 3 Select the applicable <x>:\<lmf home directory/cdma/bts–# Folder. 4 Drag the bts–#.cal file to Drive A. 5 Repeat Steps 3 and 4, as required, for other bts–# Folders.
Copying CAL Files from Diskette to the CBSC
Perform the procedures in Table 4-12 to copy CAL Files from a diskette to the CBSC.
Table 4-12: Copy CAL Files from Diskette to the CBSC Procedure
n Step Action
1 Log into the CBSC on the OMC–R UNIX Workstation using your Account Name and Password. 2 Place the diskette containing the Calibration File(s) into the Workstation Diskette Drive. 3 Enter EJECT –q and press the Enter Key. 4 Enter mount and press the Enter Key.
NOTE
S Verify that the message “floppy/no_name” is displayed on the last line.
– If the EJECT Command was previously entered, floppy/no_name will be appended with a
number.
– Use the explicit floppy/no_name reference displayed.
table continued on next page
4-26 1X SC 4812T Lite BTS Optimization/ATP FEB 2005
PRELIMINARY
Updating Calibration Data Files – continued
Table 4-12: Copy CAL Files from Diskette to the CBSC Procedure
n ActionStep
5 Enter cd /floppy/no_name and press the Enter Key. 6 Enter ls –lia and press the Enter Key.
– Verify that the bts–#.cal file filename appears in the displayed Directory Listing.
7 Enter cd and press the Enter Key. 8 Enter pwd and press the Enter Key.
– Verify that the displayed response shows the correct Home Directory (/home/<user’s name>).
9 With Solaris versions of UNIX, create a UNIX–formatted version of the bts–#.cal file in the Home
Directory by performing the following actions.
9a Type the following command:
dos2unix /floppy/no_name/bts–#.cal bts–#.cal
Where: # = BTS Number for which the CAL File was created
9b Press the Enter Key.
NOTE
Other versions of UNIX do not support the dos2unix Command. In these cases, use the UNIX cp (Copy) Command.
– The copied files contain DOS Line Feed Characters that must be edited out with a UNIX Text
Editor.
10 Enter ls –l *.cal and press the Enter Key. Verify that the CAL Files have been copied.
– Verify that all CAL Files to be transferred appear in the displayed listing.
11 Type EJECT, and press the Enter Key. 12 Remove the diskette from the workstation.
4
FEB 2005 1X SC 4812T Lite BTS Optimization/ATP 4-27
PRELIMINARY
Updating Calibration Data Files – continued
Notes
4
4-28 1X SC 4812T Lite BTS Optimization/ATP FEB 2005
PRELIMINARY
Chapter 5: Prepare to Leave the Site
Table of Contents
Prepare to Leave the Site 5-3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Bringing Modules into Service with the LMF 5-3 . . . . . . . . . . . . . . . . . . .
LMF Removal 5-4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Re–connect BTS T1/E1 Spans 5-5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Reset All Devices and Initialize Site Remotely 5-6 . . . . . . . . . . . . . . . . . . .
5
FEB 2005 1X SC 4812T Lite BTS Optimization/ATP
PRELIMINARY
Table of Contents – continued
Notes
5
1X SC 4812T Lite BTS Optimization/ATP FEB 2005
PRELIMINARY
Prepare to Leave the Site
External T est Equipment Removal
Perform the procedure in Table 5-1 to disconnect the Test Equipment and configure the BTS for active service.
Table 5-1: External Test Equipment Removal Procedure
n Step Action
n W ARNING
Make sure that no BBX Cards are keyed before performing this procedure.
– Failure to do so can result in personal injury and damage to BTS LPA Modules. 1 At the rear of the frame, disconnect all external Test Equipment from all TX and RX Connectors. 2 Reconnect and visually inspect all TX and RX Antenna Feed Lines at the Frame RF Interface
Panel.
* IMPORTANT
Verify that all Sector Antenna Feed Lines are connected to the correct Antenna Connectors on the frame. Crossed Antenna Cables will degrade Call Processing.
5
Bringing Modules into Service with the LMF
NOTE
Whenever possible, have the CBSC/MM bring up the site and enable all devices on the BTS.
If a Reason Code is present and/or data should/could not be loaded remotely from the CBSC, follow the steps outlined in Table 5-2 as required to bring BTS Processor Modules from an OOS State to an INS State.
Table 5-2: Bring Modules into Service Procedure
n Step Action
1 In the LMF GUI Environment, select the device(s) to be enabled by clicking on each one.
* IMPORTANT
S The MGLI and CSM must be INS_ACTIVE (bright green) before an MCC can be enabled.
2 Enable the Processor Cards in the following order.
1. MGLI
2. CSM Cards
3. MCC Cards table continued on next page
FEB 2005 1X SC 4812T Lite BTS Optimization/ATP 5-3
PRELIMINARY
Prepare to Leave the Site – continued
Table 5-2: Bring Modules into Service Procedure
n ActionStep
3 Click on Device in the BTS Menu Bar, and select Enable from the Pull–down Menu.
– A Status Report Window is displayed.
* IMPORTANT
If a BBX is selected, a Transceiver Parameters Window is displayed to collect Keying
Information. Do not enable the BBX. 4 Click Cancel to close the Transceiver Parameters Window, if applicable. 5 Click OK to close the Status Report Window.
– Bright Green is the color of devices that successfully change to INS.
LMF Removal
Perform the procedure in Table 5-3 as required to terminate the LMF GUI Session and remove the LMF Computer.
5
Table 5-3: Terminate the LMF Session and Remove the LMF Procedure
n Step Action
! CAUTION
Do not power down the LMF Computer without performing the procedure below; corrupted
and/or lost Data Files may result. 1 Log out of all BTS Sessions and exit the LMF by clicking on File in the LMF Window Menu Bar
and selecting Logout and Exit from the Pull–down Menu. 2 In the Windows Task Bar, click Start and select Shutdown. 3 Click Yes when the Shut Down Windows Message appears. 4 Wait for the system to shut down and the screen to go blank. 5 Disconnect the LMF Computer Ethernet Port from the BTS Frame. 6 Disconnect the LMF Computer Serial Port, the RS–232–to–GPIB Interface Box, and the GPIB
Cables as required for equipment transport.
5-4 1X SC 4812T Lite BTS Optimization/ATP FEB 2005
PRELIMINARY
Prepare to Leave the Site – continued
Re–connect BTS T1/E1 Spans
Before leaving the site, connect any T1 or E1 Span Connectors removed previously to allow the LMF to control the BTS. Refer to Table 5-4 and Figure 3-2.
Table 5-4: T1 or E1 Spans Re–connection Procedure
n Step Action
1 Re–connect any disconnected Span Connectors to the Span I/O A and B Boards. 2 If equipped, ensure that the CSU is powered ON. 3 Verify Span Status, ensuring that the OMC–R/CBSC can communicate with the BTS.
Final Checks Before Leaving Site
Make sure all requirements listed in Table 5-5 are completed before leaving the site.
Table 5-5: Check Before Leaving the Site Procedure
5
n Step Action
1 For AC Frame only:
Validate the Vtrim Signal Cabling. 2 Ensure that the Battery Voltage is 27 Volts at 25C.
– If external batteries are provided by the Customer, ensure that the Customer Circuit Breaker is
closed.
NOTE
A Low Voltage Disconnect must be in series with the external batteries. 3 Verify that no Alarm Conditions are being reported to the CBSC after all Cabinet Doors are
closed.
FEB 2005 1X SC 4812T Lite BTS Optimization/ATP 5-5
PRELIMINARY
Prepare to Leave the Site – continued
Reset All Devices and Initialize Site Remotely
Devices in the BTS should not be left with Data and Code Loaded from the LMF. The Configuration Data and Code Loads used for normal operation could be different from those stored in the LMF Files.
The following two procedure, one for Circuit Backhaul and the other for Packet Backhaul, are provided to remotely reset the BTS Devices and then initialize the BTS.
Circuit Backhaul Remote Reset and Initialization
Perform the procedure in Table 5-6 to remotely reset the BTS Devices in a Circuit Backhaul BTS, and then remotely initialize the same BTS.
Table 5-6: Circuit Backhaul Remote Reset and Initialization Procedure
n Step Action
1 Terminate the LMF Session by performing the procedure in Table 5-3. 2 Reconnect the Spans by performing the procedure in Table 5-4.
5
3 From the BTS Site, contact the OMC–R and request the operator to perform a BTS Reset.
OR
At the BTS Site, perform the actions in Step 4 through Step 6. 4 Unseat one GLI Card and wait for 30 seconds. 5 Re–seat the GLI and wait for it to complete its Initialization Process (this takes about one minute). 6 Repeat Step 4 and Step 5 for the second GLI. 7 Depending on the number and configuration of installed operational GLI Cards, perform the
following actions.
S BTS with Redundant GLI Cards, proceed to Step 8.
S BTS with a non–Redundant GLI or a non–operational Redundant GLI, proceed to Step 9.
8 From the OMC–R, run the ACTIVATE Command on the BTS.
– After the ACTIVATE Command has been executed, proceed to Step 10.
9 From the OMC–R, perform the following actions.
9a ACTIVATE the GLI.
– This action sets the NextLoad Att ribute for the GLI to work wi th the current BSS Software
Version. 9b Disable the GLI. 9c Enable the GLI.
– This action allows the MM to load the software version specified by the NextLoad Attribute.
9d Once the GLI is INS_ACT, contact the OMC–R to again run the ACTIVATE Command on the
BTS.
table continued on next page
5-6 1X SC 4812T Lite BTS Optimization/ATP FEB 2005
PRELIMINARY
Prepare to Leave the Site – continued
Table 5-6: Circuit Backhaul Remote Reset and Initialization Procedure
n ActionStep
10 Once the GLI Cards are loaded with the specified Code Version, the active GLI will verify and
update, as required, its RAM.
– Also , i f necess ary, ROM Cod e Loads for the ins tal led CSM, M CC , a nd B BX Cards us in g th e
DLM. 11 After all activities at the site have been completed, contact the OMC–R to confirm that the BTS is
under OMC–R control.
Packet Backhaul Remote Reset and Initialization
Perform the procedure in Table 5-7 to remotely reset the BTS Devices in a Packet Backhaul BTS, and then remotely initialize the same BTS.
Table 5-7: Packet Backhaul Remote Reset and Initialization Procedure
n Step Action
1 Terminate the LMF Session by performing the procedure in Table 5-3. 2 Reconnect the Spans by performing the procedure in Table 5-4. 3 Determine which of the two types of PREACTIVATE Load Processes is applicable to your
situation. Rolling Upgrade: This Load Process is only available when the BTS Cards are populated for Full
Redundancy as applicable. Quick Reboot: This Load Process is used when Redundancy for the BTS Cards is not available.
– The GLI3 disables and reboots to the new Load. This will cause all the other cards to go out
of service.
– Once it is rebooted, the GLI3 determines which cards require a new Load and then downloads
the cards in the order that they establish communication with the GLI3 following their reboot.
– The GLI3 can reload up to 16 devices simultaneously.
4 From the BTS Site, contact the OMC–R and request the operator to PREACTIVATE the BTS to
the required software version for the BSS.
5 After all activities at the site have been completed, contact the OMC–R to confirm that the BTS is
under OMC–R control.
5
FEB 2005 1X SC 4812T Lite BTS Optimization/ATP 5-7
PRELIMINARY
Prepare to Leave the Site – continued
Notes
5
5-8 1X SC 4812T Lite BTS Optimization/ATP FEB 2005
PRELIMINARY
Chapter 6: Troubleshooting
Table of Contents
Basic Troubleshooting: Overview 6-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Overview 6-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Troubleshooting: Installation 6-2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Cannot Log into Cell-Site 6-2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Force LAN A Active
(LMF Connection at I/O Panel LAN Connector) 6-3 . . . . . . . . . . . . . . . .
Force LAN A Active
(LMF Connection at Service Shelf LAN Connector) 6-4 . . . . . . . . . . . . .
Set the GLI IP Address 6-5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Cannot Communicate with Power Meter 6-7 . . . . . . . . . . . . . . . . . . . . . . .
Cannot Communicate with Communications System Analyzer 6-7 . . . . . .
Cannot Communicate with Signal Generator 6-8 . . . . . . . . . . . . . . . . . . . .
Troubleshooting: Download 6-9 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Troubleshooting: Download 6-9 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Cannot Download DATA to Any Device (Card) 6-10 . . . . . . . . . . . . . . . . . .
Cannot ENABLE Device 6-10 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
LPA Errors 6-11 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Troubleshooting: Calibration 6-12 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Calibration Audit Failure 6-13 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6
Basic Troubleshooting: RF Path Fault Isolation 6-14 . . . . . . . . . . . . . . . . . . . . . . . . .
Overview 6-14 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
If Every Test Fails 6-14 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Verify BLO Check Box 6-15 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Single–Sided BLO Check Box 6-15 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
If Faults Are Isolated 6-15 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Fault Isolation Flowchart 6-15 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Flowchart Prerequisites 6-16 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
TX Power Output Fault Isolation Flowchart 6-17 . . . . . . . . . . . . . . . . . . . . .
Troubleshooting: Transmit ATP 6-18 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
BTS Passed Reduced ATP Tests but Has Forward Link Problem in
Normal Operation 6-18 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Cannot Perform TX Mask Measurement 6-18 . . . . . . . . . . . . . . . . . . . . . . . .
Cannot Perform Rho or Pilot Time Offset Measurement 6-18 . . . . . . . . . . .
Cannot Perform Code Domain Power and Noise Floor Measurement 6-19 .
Troubleshooting: Receive ATP 6-20 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Multi–FER Test Failure 6-20 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
FEB 2005 1X SC 4812T Lite BTS Optimization/ATP
PRELIMINARY
Table of Contents – continued
Troubleshooting: CSM Checklist 6-21 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Problem Description 6-21 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Intermittent 19.6608 MHz Reference Clock / GPS Receiver Operation 6-21
No GPS Reference Source 6-21 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Checksum Failure 6-21 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
GPS Bad RX Message Type 6-21 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CSM Reference Source Configuration Error 6-22 . . . . . . . . . . . . . . . . . . . . .
Takes Too Long for CSM to Come INS 6-22 . . . . . . . . . . . . . . . . . . . . . . . .
Troubleshooting: SCCP Backplane 6-23 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Introduction 6-23 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Connector Functionality 6-23 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SCCP Backplane Troubleshooting Procedure 6-24 . . . . . . . . . . . . . . . . . . . .
Digital Control Problems 6-25 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
DC Power Problems 6-27 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Troubleshooting: RFDS 6-29 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Introduction 6-29 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
All Tests Fail 6-29 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
All RX and TX Paths Fail 6-29 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Module Front Panel LED Indicators and Connectors 6-31 . . . . . . . . . . . . . . . . . . . . .
Module Status Indicators 6-31 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Module LED Status (except GLI3, CSM, BBX, MCC) 6-31 . . . . . . . . . . . .
6
Troubleshooting: Span Control Link 6-42 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Power Supply Module LED Status Combinations 6-31 . . . . . . . . . . . . . . . .
1X SC 4812T Lite BTS Optimization/ATP FEB 2005
PRELIMINARY
Basic Troubleshooting: Overview
Overview
The information in this chapter addresses some of the scenarios likely to be encountered by Customer Field Engineering (CFE) Team Members while performing BTS Optimization and Acceptance Testing. This Troubleshooting Guide was created as an interim reference document for use in the field. It provides “what to do if” basic troubleshooting suggestions when the BTS Equipment does not perform according to the procedures documented in the manual.
Comments are consolidated from inputs provided by CFEs and information gained from experience in Motorola Labs and Classrooms.
6
FEB 2005 1X SC 4812T Lite BTS Optimization/ATP 6-1
PRELIMINARY
Troubleshooting: Installation
Cannot Log into Cell-Site
Table 6-1: Login Failure Troubleshooting Procedures
n Step Action
1 If the LED on either GLI is solid RED, it implies a hardware failure.
Reset the GLI by re-seating it.
– If re–seating the MGLI does not fix the problem, proceed to Step 2.
2 Install a GLI Card in the Redundant GLI Slot and retry.
NOTE
A Red LED may also indicate no termination on an External LAN Connector (I/O Panel at the top of the frame or at the top of a Logical BTS Frame).
3 Circuit BTS:
Verify that the Span Line is disconnected at the Span I/O Card.
Circuit or Packet BTS:
Verify that the OMC–R has disabled the BTS.
4 “Ping” the INS_ACTIVE GLI.
– Refer to Table 3-15.
5 Verify that the LMF is connected to the Primary LAN (LAN A) at one of the following locations.
6
6 If LAN A is not the active LAN, force a LAN Switch to LAN A by performing the procedure in
7 Verify that the LMF was configured properly. 8 If a Xircom Parallel BNC LAN Interface is being used, verify that the BTS-LMF Cable is RG-58
9 Verify that the External LAN Connectors are properly terminated at either of the following two
10 If the LMF is connected to the Primary LAN at the Service Shelf, verify that a T-Adapter is not
11 If the LMF is connected to the Primary LAN at the Service Shelf, try connecting to the Ethernet
– The Service Shelf below the SCCP Cage. – The BTS I/O Panel at the top of the frame.
Table 6-2.
(flexible black cable, less than 2.5 feet in length).
locations.
– Service Shelf – BTS I/O Panel at the top of the frame.
used on the LMF Computer or on the Ethernet Hub/Adapter Connector.
Out Port on the I/O Panel (top of frame) using the procedure in Table 3-7. 12 Re-boot the LMF and retry. 13 Re-seat the INS_ACTIVE GLI and retry.
table continued on next page
6-2 1X SC 4812T Lite BTS Optimization/ATP FEB 2005
PRELIMINARY
Troubleshooting: Installation – continued
Table 6-1: Login Failure Troubleshooting Procedures
n ActionStep
14 Re-seat the INS_ACT GLI and retry. 15 Verify that the GLI IP Addresses are configured properly by performing the procedure in
Table 6-4.
Force LAN A Active (LMF Connection at I/O Panel LAN Connector)
Table 6-2: Procedure to Force Ethernet LAN A to Active State as Primary LAN
(LMF Connection at I/O Panel LAN Connector)
n Step Action
1 If LAN A is not the active LAN, make certain all External LAN Connectors are either terminated
with 50 Loads or cabled to another frame.
2 If it has not already been done, connect the LMF Computer to the Stand–alone or Starter Frame,
as applicable (Table 3-6).
3 If it has not already been done, start a GUI LMF Session and log into the BTS on the active LAN
(Table 3-10).
4 Remove the 50 Terminator from the LAN B IN Connector on the I/O Panel of the Stand–alone
or Starter Frame.
– The LMF Session will become inactive.
5 Log into the BTS with the LMF (Table 3-10).
– Forcing LAN A to the INS_ACTIVE State was successful if the LMF can log into the BTS
and status any card in the cage.
S If LAN A was successfully forced to an active state, skip to Step 12.
6 With the 50 Terminator still removed from the LAN B IN Connector, remove the 50
Terminator from LAN B OUT Connector.
– If more than one frame is connected to the LAN, remove the Terminator from the last frame in
the chain. 7 Again attempt to log the LMF into the BTS Frame on LAN A. 8 If the LAN was successfully forced to an active state, proceed to Step 12.
– Forcing the LAN to the INS_ACTIVE State was successful if the LMF can log into the BTS
and status any card in the cage.
6
9 With the 50 Terminators still removed from LAN B, unseat each GLI Gard in each frame
connected to the LAN, until all are disconnected from the SCCP Backplanes.
10 Reseat each GLI Card until all are reconnected.
. . . continued on next page
FEB 2005 1X SC 4812T Lite BTS Optimization/ATP 6-3
PRELIMINARY
Troubleshooting: Installation – continued
Table 6-2: Procedure to Force Ethernet LAN A to Active State as Primary LAN
(LMF Connection at I/O Panel LAN Connector)
n ActionStep
11 Allow the GLI Cards to power up, then attempt to select and status cards in the SCCP Cages.
S If LAN A is active, proceed toStep 12. S If LAN A is still not active, troubleshoot or continue troubleshooting following the procedures
in Table 6-1.
Replace the 50 Terminators removed from the LAN B IN and OUT connectors.
12
NOTE
To ensure the INS_ACT GLI Card does not swap LANs after LMF login, the 50 Terminator may be left off of the LAN B OUT connector until LMF operations are completed.
Force LAN A Active (LMF Connection at Service Shelf LAN Connector)
Table 6-3: Force Ethernet LAN A to Active State as Primary LAN,
LMF Connection at Service Shelf LAN Connector
n Step Action
6
1 If LAN A is not the active LAN, make certain all external LAN Connectors are either terminated
with 50 Loads or cabled to another frame.
2 If it has not already been done, connect the LMF Computer to LAN B on the Stand–alone or
Starter Frame, as applicable (Table 3-6). 3 If it has not already been done, start a GUI LMF Session and log into the BTS (Table 3-10). 4 Remove the 50 Terminator from the LAN B IN Connector on the I/O Panel at the top of the
Stand–alone or Starter Frame.
– The LMF session will become inactive. 5 Log the LMF out of the BTS. 6 Disconnect the LMF Computer from the Service Shelf LAN B Connector and connect it to the
LAN A Connector.
7 Determine if LAN A is active and capable of accepting an LMF log–in by using the LMF Ping
Utility to query the INS_ACT GLI (Table 3-15). 8 If the INS_ACT GLI responds to the ping, log into the BTS on LAN A. 9 Attempt to select and status a card in the BTS.
– Forcing LAN A to active state was successful if the LMF can log in, select, and status any
card in the cage.
S If LAN A was successfully forced to an active state, skip to Step 16.
. . . continued on next page
6-4 1X SC 4812T Lite BTS Optimization/ATP FEB 2005
PRELIMINARY
Troubleshooting: Installation – continued
Table 6-3: Force Ethernet LAN A to Active State as Primary LAN,
LMF Connection at Service Shelf LAN Connector
n ActionStep
10 With the 50 Terminator still removed from the LAN B IN Connector, remove the 50
Terminator from LAN B OUT connector.
– If more than one frame is connected to the LAN, remove the Terminator from the last frame in
the chain.
11 If LAN A was successfully forced to an active state, skip to Step 16.
– Forcing LAN A to active state was successful if the LMF can log in, select, and status any
card in the cage.
12 With the 50 Terminators still removed from LAN B, unseat each GLI Card in each frame
connected to the LAN, until all are disconnected from the SCCP Backplanes.
13 Reseat each GLI Card until all are reconnected. 14 Allow the GLI Cards to power up, then attempt to select and status cards in the SCCP Cages.
S If LAN A is active, proceed to Step 16.
15 If LAN A is still not active, troubleshoot or continue troubleshooting following the procedures in
Table 6-1.
Replace the 50 Terminators removed from the LAN B IN and OUT Connectors.
16
NOTE
To ensure the INS_ACT GLI Card does not swap LANs after LMF Login, the 50 Terminator
may be left off of the LAN B OUT Connector until LMF Operations are completed.
Set the GLI IP Address
Table 6-4: Procedure to set GLI IP Address
n Step Action
1 If it has not previously been done, establish an MMI Communication Session with the GLI Card
as described in Table 3-14. 2 Enter the following Command to display the IP Address and Subnet Mask Settings for the card:
config lg0 current
A response similar to the following will be displayed:
6
GLI3>config lg0 current
lg0: IP Address is set to
DEFAULT (configured based on Card location)
lg0: netmask is set to
DEFAULT (255.255.255.128)
table continued on next page
FEB 2005 1X SC 4812T Lite BTS Optimization/ATP 6-5
PRELIMINARY
Troubleshooting: Installation – continued
Table 6-4: Procedure to set GLI IP Address
n ActionStep
3 If the IP Address setting response shows an IP Address rather than “Default (configured
based on Card location)
config lg0 ip default
A response similar to the following will be displayed:
GLI3>config lg0 ip default
_param_config_lg0_ip(): param_delete(): 0x00050001
lg0: ip address set to DEFAULT
4 If the GLI Subnet Mask Setting does not display as “DEFAULT (255.255.255.128),” set it to
default by entering the following command:
config lg0 netmask default
A response similar to the following will be displayed:
GLI3>config lg0 netmask default
,” enter the following:
_param_config_lg0_netmask(): param_delete(): 0x00050001
lg0: netmask set to DEFAULT
5 Set the GLI Route Default to default by entering the following command:
config route default default
A response similar to the following will be displayed:
6
GLI3>config route default default
_esh_config_route_default(): param_delete(): 0x00050001
route: default gateway set to DEFAULT
6 When changes are completed, close the MMI Session, and reset the GLI Card.
NOTE
Changes to the settings will not take effect unless the GLI is reset. 7 Once the GLI is reset, re–establish MMI Communication with it and issue the following command
to confirm its IP Address and Subnet Mask Settings:
config lg0 current
A response similar to the following will be displayed:
GLI3>config lg0 current
lg0: IP Address is set to
DEFAULT (configured based on Card location)
lg0: netmask is set to
DEFAULT (255.255.255.128)
8 Repeat Steps 1 through 7 for all remaining GLI Cards, including those in any additional
inter–connected frames.
6-6 1X SC 4812T Lite BTS Optimization/ATP FEB 2005
PRELIMINARY
Troubleshooting: Installation – continued
Cannot Communicate with Power Meter
Table 6-5: Power Meter Communication Failure Troubleshooting Procedure
n Step Action
1 Verify Power Meter is connected to LMF with GPIB Adapter. 2 Verify Cable Connections as specified in Chapter 3. 3 Verify that the GPIB Address of the Power Meter is set to the same value displayed in the
applicable GPIB Address Box of the LMF Options Window Test Equipment Tab.
– Refer to Table 3-29 or Table 3-30 and the Setting GPIB Addresses section of Appendix F for
details.
4 Verify that the GPIB Adapter DIP Backplane Configuration Switch Settings are correct.
– Refer to Test Equipment Preparation section of Appendix F for details.
5 Verify that the GPIB Adapter is not locked up.
– Under normal conditions, only two green LEDs are ‘ON’ (Power and Ready). – If any other LED is continuously ‘ON’, then cycle GPIB Box Power and retry.
6 Verify that the LMF Computer COM1 Port is not used by another application.
– For example, if a HyperTerminal Window is open for MMI, close it.
7 Reset all Test Equipment by clicking Util in the BTS Menu Bar and selecting Test Equipment >
Reset from the Pull–down Menus.
Cannot Communicate with Communications System Analyzer
Table 6-6: Communications System Analyzer Communication Failure Troubleshooting Procedure
n Step Action
1 Verify that the analyzer is connected to LMF with GPIB Adapter. 2 Verify that the Cable Connections are as specified in Chapter 3. 3 Verify that the Analyzer GPIB Address is set to the same value displayed in the applicable GPIB
Address Box of the LMF Options Window Test Equipment Tab.
– Refer to Table 3-29 or Table 3-30 and the Setting GPIB Addresses section of Appendix F for
details.
4 Verify that the GPIB Adapter DIP Backplane Configuration Switch Settings are correct.
– Refer to Test Equipment Preparation section of Appendix F for details.
6
5 Verify that the GPIB Adapter is not locked up.
– Under normal conditions, only two green LEDs are ‘ON’ (Power and Ready). – If any other LED is continuously ‘ON’, then cycle GPIB Box Power and retry.
. . . continued on next page
FEB 2005 1X SC 4812T Lite BTS Optimization/ATP 6-7
PRELIMINARY
Troubleshooting: Installation – continued
Table 6-6: Communications System Analyzer Communication Failure Troubleshooting Procedure
n ActionStep
6 Verify that the LMF Computer COM1 Port is not used by another application.
– For example, if a HyperTerminal Window is open for MMI, close it.
7 Reset all Test Equipment by clicking Util in the BTS Menu Bar and selecting Test Equipment >
Reset from the Pull–down Menus.
Cannot Communicate with Signal Generator
Table 6-7: Signal Generator Communication Failure Troubleshooting Procedure
n Step Action
1 Verify that the Signal Generator is connected to the LMF containing a GPIB Adapter. 2 Verify that the Cable Connections are as specified in Chapter 3. 3 Verify that the Signal Generator GPIB Address is set to the same value displayed in the applicable
GPIB Address Box of the LMF Options Window Test Equipment Tab.
– Refer to Table 3-29 or Table 3-30 and the Setting GPIB Addresses section of Appendix F for
details.
4 Verify that the GPIB Adapter DIP Backplane Configuration Switch Settings are correct.
6
5 Verify that the GPIB Adapter is not locked up.
6 Verify that the LMF Computer COM1 Port is not used by another application.
7 Reset all Test Equipment by clicking Util in the BTS Menu Bar and selecting Test Equipment >
– Refer to Test Equipment Preparation section of Appendix F for details.
– Under normal conditions, only two green LEDs are ‘ON’ (Power and Ready). – If any other LED is continuously ‘ON’, then cycle GPIB Box Power and retry.
– For example, if a HyperTerminal Window is open for MMI, close it.
Reset from the Pull–down Menus.
6-8 1X SC 4812T Lite BTS Optimization/ATP FEB 2005
PRELIMINARY
Troubleshooting: Download
Troubleshooting: Download
Table 6-8: Code Download Failure Troubleshooting Procedure
n Step Action
1 Verify that the T1 or E1 Span is disconnected from the BTS at Site I/O Boards.
– Refer to Figure 3-2.
2 Verify that the LMF can communicate with the BTS Devices using the LMF Status Function. 3 Establish communications with the MGLI before trying to communicate with any other BTS
Device.
– The MGLI must be INS_ACTIVE (bright green).
4 Verify that the target card is physically present in the cage and powered-up.
S If the target card LED is solid red, it implies a hardware failure.
S If the target card LED is bright green, proceed to Step 9.
5 Reset the target card by re-seating it.
S If the LED Alarm is still being reported, proceed to Step 6.
S If the LED Alarm is no longer being reported, proceed to Step 9.
6 Replace with the same type of card from another slot and retry. 7 Re-seat the card and try again.
S If the Download Portion completes and the Reset Portion fails, proceed to Step 8.
S If a BBX or an MCC remains OOS_ROM (blue) after Code Download, proceed to Step 9.
S If a BBX reports a Failure Message and is OOS_RAM, the Code Load was OK.
– Use the LMF Status Function to verify the Load. 8 Reset the device by selecting the device and selecting Reset. 9 Use the LMF Device > Status Function to verify that the Code Load was accepted.
S If the Code Load was accepted, proceed to Step 10. S If the Code Load was not accepted, proceed to Table 6-9 to troubleshoot the Data Download
Failure.
10 Use LMF Device > Download > Flash to load RAM Code into Flash Memory.
6
FEB 2005 1X SC 4812T Lite BTS Optimization/ATP 6-9
PRELIMINARY
Troubleshooting: Download – continued
Cannot Download DA TA to Any Device (Card)
Table 6-9: Data Download Failure Troubleshooting Procedure
n Step Action
1 Re-seat the card and repeat the Code and Data Load Procedure. 2 Verify that the ROM and RAM Code Loads are of the same release by statusing the card.
– Refer to Download the BTS section of Chapter 3 for more information.
Cannot ENABLE Device
Before a device can be enabled (placed in service), it must be in the OOS_RAM State (yellow in LMF Display) with data downloaded to the device. The color of the device on the LMF changes to green once it is enabled.
The four Device States that can be displayed by the LMF are:
S ENABLED (bright green, INS_ACT) S STANDBY (olive green, INS_STANDBY – Mate CSM and GLI only) S DISABLED (yellow, OOS_RAM) S RESET (blue, OOS_ROM)
6
n Step Action
1 Re-seat the card and repeat the Code and Data Load Procedure. 2 If the CSM cannot be enabled, verify that the CDF has correct latitude and longitude data for the
Cell Site location and GPS Sync.
3 Verify that the Primary CSM is in the INS_ACTIVE (bright green) State.
Table 6-10: Device Enable (INS) Failure Troubleshooting Procedure
NOTE
MCC Cards will not enable without the CSM being INS.
4 Verify that the 19.6608 MHz CSM Clock is present; MCC Cards will not enable without it.
S If MCC Cards give “invalid or no System Time,” proceed to Step 5.
NOTE
BBX Cards should not be enabled for ATP Tests. 5 Verify that the CSM is enabled. 6 When all else fails, perform the following actions.
6a Log out of the BTS. 6b Exit the LMF.
table continued on next page
6-10 1X SC 4812T Lite BTS Optimization/ATP FEB 2005
PRELIMINARY
Troubleshooting: Download – continued
Table 6-10: Device Enable (INS) Failure Troubleshooting Procedure
n ActionStep
6c Restart the application. 6d Log into the BTS. 6e Re–attempt Device Enable Actions.
LPA Errors
Table 6-11: LPA Errors
n Step Action
1 If the LPA Modules continuously report alarms, cycle power by resetting the applicable DC PDA
Circuit Breakers. 2 Establish an MMI Session with the LPA (Table 3-14), connecting the cable to the applicable MMI
Port on the ETIB.
2a Type alarms at the HyperTerminal Window Prompt and press Enter.
– The resulting display may provide an indication of the problem.
2b Call Field Support for further assistance.
6
FEB 2005 1X SC 4812T Lite BTS Optimization/ATP 6-11
PRELIMINARY
Troubleshooting: Calibration
Bay Level Offset Calibration Failure
Table 6-12: BLO Calibration Failure Troubleshooting Procedure
n Step Action
1 Verify that the Power Meter or Communications System Analyzer is configured correctly.
– Refer to the Test Equipment Set–up section of Chapter 3, and is connected to the proper BTS
TX Antenna Connector.
2 If a Power Meter is being used, perform the following actions.
2a Re-calibrate the Power Meter and verify it is calibrated correctly with Cal Factors from the Power
Sensor.
– Refer to Appendix F.
2b Verify that the Power Sensor is functioning properly by checking it with the 1–mW (0 dBm)
Power Ref Signal.
2c Verify communication between the LMF and Power Meter is working by checking that the Meter
Display is showing RES : 3 Verify that the parameters in the bts–#.cdf File are set correctly for the BTS Operating Band as
follows:
For 1900 MHz:
Bandclass = 1; Freq_Band = 16
6
For 800 MHz:
Bandclass = 0; Freq_Band = 8 4 Verify that no LPA on the carrier is in Alarm State (rapidly flashing red LED).
– If any LPAs are in Alarm State, proceed to Step 5.
NOTE
Under normal conditions, only two green LEDs are ‘ON’ (Power and Ready). 5 Reset the LPA(s) by pulling the applicable circuit breaker on the DC PDA. 6 After 5 seconds, push the circuit breaker back in. 7 Verify that the GPIB Adapter is not locked up.
– If any other LED is continuously ‘ON’, proceed to Step 8.
8 Power-cycle (turn power off and on) the GPIB Box and retry the procedure.
6-12 1X SC 4812T Lite BTS Optimization/ATP FEB 2005
PRELIMINARY
Troubleshooting: Calibration – continued
Calibration Audit Failure
Table 6-13: Calibration Audit Failure Troubleshooting Procedure
n Step Action
1 Verify that the Power Meter or Communications System Analyzer is configured correctly.
– Refer to the Test Equipment Set–up section of Chapter 3), and is connected to the proper BTS
TX Antenna Connector.
2 If a Power Meter is being used, perform the following actions.
2a Re-calibrate the Power Meter and verify it is calibrated correctly with Cal Factors from the Power
Sensor.
– Refer to Appendix F.
2b Verify that the Power Sensor is functioning properly by checking it with the 1–mW (0 dBm)
Power Ref Signal.
2c Verify communication between the LMF and Power Meter is working by checking that the Meter
Display is showing RES :. 3 Verify that no LPAs on the carrier are in Alarm State (rapidly flashing red LED).
– If any LPAs are in Alarm State, proceed to Step 4.
4 Reset the LPA(s) by performing the following actions.
4a Pull the applicable circuit breaker on the DC PDA, and, 4b After 5 seconds, push the circuit breaker back in.
5 After Calibration, the BLO Data must be re-loaded to the BBX Cards before auditing.
– Click on the BBX(s), and in the BTS Menu Bar select Device > Download >BLO. – Re-try the audit.
6 Verify that the GPIB Adapter is not locked up.
– Under normal conditions, only two green LEDs are ‘ON’ (Power and Ready). – If any other LED is continuously ‘ON’, proceed to Step 7.
7 Power Cycle (turn power off and on) the GPIB Box and re–try. 8 If Calibration is being performed for the Redundant BBX, ensure that the Single–Sided BLO
Check Box is not checked in the CDMA Test Parameters Test Set–up Window. 9 If additional items, such as Directional Couplers or Combiners, have been installed in the TX
Path, make sure that one of the following has been done:
S Verify BLO Check Box in the CDMA Test Parameters Test Set–up window is unchecked.
6
S The additional Path Losses have been added into each applicable sector using the Util > Edit >
TX Coupler Loss... Function.
FEB 2005 1X SC 4812T Lite BTS Optimization/ATP 6-13
PRELIMINARY
Basic Troubleshooting: RF Path Fault Isolation
Overview
The Optimization (RF Path Characterization or Calibration) and Post-Calibration (Audit) Procedures measure and limit-check the BTS reported Transmit and Receive Levels of the path from each BBX to the back of the frame. When a fault is detected, it is specific to a Receive or Transmit Path. The Troubleshooting Process in this section determines the most probable cause of the fault.
As the Calibration and Audit Tests are performed, results are displayed in the LMF Test Status Report Window. When faults are encountered, the Test Procedure in progress continues running and displaying any further faults. If it appears that there are major faults, the test can be aborted.
The test results can be saved to a directory \cdma\bts–# Folder. To do this, close the Test Status Report Window using the Save Results Button.
NOTE
Closing the Test Status Report Window with the Dismiss Button will delete the test results without saving them.
If a test is re–run or a new calibration, audit, or test is run and the results are saved, the previous test results in the bts–#.rpt File are overwritten. To prevent losing previous test results in the bts–#.rpt
6
If Every Test Fails
File, refer to the procedure in Table 4-10 before performing further testing with the LMF.
If there are major faults, recheck the Test Equipment Attachments for errors. If none are found, close the Test Status Report Window using the Save Results Button, and save the contents of the resulting bts–#.rpt file as described in Table 4-10. Also, note other specifics about the failure, and proceed with the Fault Isolation Procedure.
If all tests fail, perform the procedure in Table 6-14.
bts–#.rpt File in the<x>:\<lmf home
Table 6-14: All Tests Fail Troubleshooting Procedure
n Step Action
1 Check the Calibration Equipment for proper operation by manually setting the Signal Generator
Output Attenuator to the lowest Output Power Setting. 2 Connect the Output Port to the Spectrum Analyzer RF Input Port. 3 Set the Signal Generator Output Attenuator to –90 dBm, and switch on the RF Output. 4 Verify that the Spectrum Analyzer can receive the signal, indicate the correct Signal Strength
(accounting for the Cable Insertion Loss), and indicate the approximate frequency.
6-14 1X SC 4812T Lite BTS Optimization/ATP FEB 2005
PRELIMINARY
Basic Troubleshooting: RF Path Fault Isolation – continued
Verify BLO Check Box
When performing a Calibration with the TX Calibration... or All Cal/Audit... Functions, the Verify BLO Check Box should normally be
checked. When a Calibration fails, determine if any items such as Directional Couplers or Combiners have been added to the TX Path.
If additional items have been installed in the path, try re–running the Calibration with Verify BLO unchecked. If Calibration still does not pass, refer to the following paragraphs and use the TX Output Fault Isolation Flowchart to identify the most probable cause of the failure.
Single–Sided BLO Check Box
When performing a Calibration with the TX Calibration... or All Cal/Audit... Functions, the Single–Sided BLO Check Box should not
be checked when the Redundant BBX is being calibrated. When a Calibration fails with the Redundant BBX selected, try re–running the Calibration with the Single–Sided BLO Check Box unchecked.
– If the Calibration still fails, refer to the following paragraphs and
use the TX Output Fault Isolation Flowchart to identify the most probable cause of the failure.
If Faults Are Isolated
Fault Isolation Flowchart
If the Fault Reports are isolated between successful Path Checks, the root cause of the faults most likely lies with one or more of the Field Replaceable Unit (FRU) cards/modules.
– If more than one failure was reported, look for a common
denominator in the data. For example, if any TX Test fails on one sector only, the BBX assigned to that sector (Table 1-5) is a likely cause. Also, look at the Severity of the failure.
– If the Path Loss is just marginally out of the relaxed specification
limit during the Post-Calibration TX Audit, suspect excessive Test Cable Insertion Loss.
– If limits are missed by a wide margin, suspect incorrectly wired
cables or total device failure.
Use the TX Output Fault Isolation Flowchart in Figure 6-1 to identify the strongest possible cause for a failed TX Test.
The flowchart covers the Transmit Path.
– Transmit Paths usually fail the lower Test Limit, indicating
excessive Loss in some component in the BTS Site or incorrect wiring.
– A failure of an upper Test Limit usually indicates a problem with
the Test Set–up or external equipment.
Before replacing a suspected FRU, always repeat and verify that the test results to rule out a transient condition. If a BBX fails an Upper Limit in the Post–Calibration Audit Procedure, re–calibrate and verify that the out–of–tolerance condition for that BBX and/or sector before replacement.
6
FEB 2005 1X SC 4812T Lite BTS Optimization/ATP 6-15
PRELIMINARY
Basic Troubleshooting: RF Path Fault Isolation – continued
Flowchart Prerequisites
Before entering the Fault Isolation Sequence shown in the flowchart, ensure that the following items have been completed:
S GLI Cards, MCC Cards, and BBX Cards have been downloaded with
the correct ROM Code, RAM Code, and data (Table 3-16, Table 3-17, and Table 3-18).
S MGLI, CSM Cards, and MCC Cards are enabled (Table 3-17,
Table 3-20, and Table 3-21, respectively).
S Ensure that the LED on the correct CCD Card is solid green. S Ensure no alarms are being reported by opening an LMF Alarm
Window as outlined in WinLMF On-Line Help SR2.16.x .
6
6-16 1X SC 4812T Lite BTS Optimization/ATP FEB 2005
PRELIMINARY
Basic Troubleshooting: RF Path Fault Isolation – continued
TX Power Output Fault Isolation Flowchart
Figure 6-1: TX Output Fault Isolation Flowchart
Start
TX Power
Out of Limits
Did TX Output
fail the High or
Low limit?
Low limit
failure.
If equipped, does a
BBX on the same
carrier but for a
different sector
pass?
No, next BBX on same carrier
fails on different sector .
High limit
failure.
Yes, it passes.
Does
Redundant BBX
have the same problem on the
same sector?
Yes
Does any other sector have the same problem?
No
No
Yes
Likely Cause: BBX Card
Attempt re–Calibration before replacement.
Likely Cause: External Power Measurement
Equipment and/or Set–up.
Also check: Switch Card
External Attenuators & Pads, Check Site Documentation.
Likely Cause: CIO Card
Carrier Trunking Module
Also check: CIO–Trunking Module cabling
TX Filter/Combiner cabling TX DRDC/TRDC cabling
Likely Cause: BBX Card
Loose connections on CIO–Trunking Module cabling, TX Filter/Combiner cabling, or TX DRDC/TRDC cabling
Also check: CIO Card
Carrier Trunking Module
6
If equipped, does a
BBX on a different
carrier but for the
same sector
pass?
No, everything fails
Likely Cause: Crossed TX cabling to include:
Yes, it passes.
Module–Filter/Combiner,
Also check: Carrier Trunking Module
Likely Cause: CIO Card not fully seated
Module–Filter/Combiner,
– CIO–Trunking Module, – Trunking
– Filter/Combiner–DRDC/TRDC Carrier LPA Modules
CIO Card.
External Power Measurement Equipment and/or Set–up Crossed TX cabling to include: – CIO–Trunking Module, – Trunking
– Filter/Combiner–DRDC/TRDC
FEB 2005 1X SC 4812T Lite BTS Optimization/ATP 6-17
PRELIMINARY
Troubleshooting: Transmit ATP
BTS Passed Reduced A TP Tests but Has Forward Link Problem in Normal Operation
Perform the procedure in Table 6-15 to troubleshoot a Forward Link problem during normal operation after passing a reduced ATP.
Table 6-15: Forward Link Failure (BTS Passed Reduced ATP) Troubleshooting Procedure
n Step Action
1 Perform the following additional tests to troubleshoot a Forward Link problem:
1a – TX Mask 1b – TX Rho 1c – TX Code Domain
Cannot Perform TX Mask Measurement
Table 6-16: TX Mask Measurement Failure Troubleshooting Procedure
n Step Action
6
Cannot Perform Rho or Pilot Time Offset Measurement
1 Verify that the TX Audit passes for the BBX(s). 2 If performing manual measurement, verify that the analyzer is set–up correctly. 3 Verify that no LPA in the sector is in Alarm State (flashing red LED). 4 Re-set the LPA by pulling the circuit breaker, and, after 5 seconds, pushing it back in.
Table 6-17: Rho and Pilot Time Offset Measurement Failure Troubleshooting Procedure
n Step Action
1 Verify the presence of the RF Signal by switching to the Spectrum Analyzer Screen. 2 Verify that the PN Offsets displayed on the analyzer is the same as the PN Offset in the CDF File. 3 Re–load MGLI Code and Data, and repeat the test. 4 If performing manual measurement, verify that the analyzer is set–up correctly. 5 Verify that no LPA in the sector is in Alarm State (flashing red LED). 6 Reset the LPA by pulling the circuit breaker, and, after 5 seconds, pushing back in.
table continued on next page
6-18 1X SC 4812T Lite BTS Optimization/ATP FEB 2005
PRELIMINARY
T roubleshooting: Transmit ATP – continued
Table 6-17: Rho and Pilot Time Offset Measurement Failure Troubleshooting Procedure
n ActionStep
7 If the Rho Value is unstable and varies considerably (e.g. .95,.92,.93), it may indicate that the
GPS is still Phasing (trying to reach and maintain 0 Frequency Error).
7a Go to the Frequency Bar in the upper right corner of the Rho Meter and select Hz. 7b Press <Shift–avg> and enter 10, to obtain an average Rho Value.
– This is an indication the GPS has not stabilized before going INS and may need to be
re-initialized.
Cannot Perform Code Domain Power and Noise Floor Measurement
Table 6-18: Code Domain Power and Noise Floor Measurement Failure Troubleshooting Procedure
n Step Action
1 Verify the presence of the RF Signal by switching to the Spectrum Analyzer Screen on the
Communications System Analyzer. 2 Verify that the PN Offset displayed on analyzer is the same as the PN Offset being used in the
CDF File. 3 Disable and re-enable the MCC (one or more MCC Cards based on the extent of the failure).
6
FEB 2005 1X SC 4812T Lite BTS Optimization/ATP 6-19
PRELIMINARY
Troubleshooting: Receive ATP
Multi–FER T est Failure
Table 6-19: Multi-FER Failure Troubleshooting Procedure
n Step Action
1 Verify that the Test Equipment is configured correctly for an FER Test. 2 Verify that the Test Equipment is locked to the 19.6608 MHz and Even Second Clocks.
– On the HP 8921 Analyzer, the yellow LED (REF UNLOCK) must be OFF.
3 Verify MCC Cards have been loaded with data and are INS_ACTIVE. 4 Disable and re-enable the MCC (one or more based on the extent of the failure). 5 Disable, re-load code and data, and re-enable the MCC (one or more MCC Cards based on extent
of failure). 6 Verify that the Antenna Connections to the frame are correct based on the LMF Directions
Messages.
6
6-20 1X SC 4812T Lite BTS Optimization/ATP FEB 2005
PRELIMINARY
Troubleshooting: CSM Checklist
Problem Description
Many Clock Synchronization Manager (CSM) Card problems may be resolved in the field before sending the boards to the factory for repair. This section describes known CSM problems identified in Field Returns, some of which are field-repairable. Check these problems before returning suspect CSM Cards.
Intermittent 19.6608 MHz Reference Clock / GPS Receiver Operation
If problems are occurring with CSM Card Kit Numbers, SGLN1145 or SGLN4132, check the Suffix with the Kit Number. If the Kit Number has version “AB,” then replace it with version ‘‘BC’’ or higher, and return the Model AB CSM Card to the Repair Center.
No GPS Reference Source
Checksum Failure
Correct Hardware
Check the CSM Cards for proper hardware configuration for the type of GPS in use and the SCCP Cage Slot where they are installed.
RF–GPS (Local GPS) – CSM Kit Number SGLN1145, which should be installed in Slot l, has an on-board GPS Receiver; while Kit Number SGLN4132, in Slot 2, does not have a GPS Receiver..
Remote GPS (RGPS) – Kit Number SGLN4132ED or later, which should be installed in both Slot 1 and Slot 2, does not have a GPS Receiver..
Any incorrectly configured board must be returned to the Repair Center.
Do not attempt to change hardware configuration in the field.
– Also, verify that the GPS Antenna is not damaged and is installed
per recommended guidelines.
The CSM could have corrupted data in its firmware resulting in a non-executable code. The problem is usually caused by either electrical disturbance, or interruption of data during a download. Attempt another download with no interruptions in the data transfer. Return the CSM Card back to the Repair Center if the attempt to reload fails.
6
GPS Bad RX Message T ype
This problem is believed to be caused by a later version of CSM Software (3.5 or higher) being downloaded, via LMF, followed by an earlier version of CSM Software (3.4 or lower), being downloaded from the CBSC. Download again with CSM Software Code 3.5 or higher. Return the CSM Card back to the Repair Center if the attempt to reload fails.
FEB 2005 1X SC 4812T Lite BTS Optimization/ATP 6-21
PRELIMINARY
Troubleshooting: CSM Checklist – continued
RF GPS
REMOTE
SGLN4132ED
Without GPS
CSM Reference Source Configuration Error
This problem is caused by an incorrect Reference (Clock) Source Configuration performed in the field by software download. CSM Kit Numbers SGLN1145 and SGLN4132 must have the proper Reference Sources configured, as shown in Table 6-20, to function correctly.
Table 6-20: CSM Reference (Clock) Sources by GPS Type and Kit Number
GPS Type CSM Kit No.
SGLN1145 With GPS Receiver 1
SGLN4132
REMOTE SGLN4132ED Without GPS GPS
Takes Too Long for CSM to Come INS
or later
6
Hardware
Configuration
Without GPS Receiver
Receiver
This problem may be caused by a delay in GPS Acquisition. Check the Accuracy Flag Status and/or current position. Refer to the CSM System Time/GPS and HSO Verification section of Chapter 3.
At least one satellite should be visible and tracked for the “surveyed” Mode, and four satellites should be visible and tracked for the “estimated” Mode. Also, verify that the correct Base Site Position Data is being used in “surveyed” Mode.
CSM
Slot No.
2
1
2
Reference Source Configuration
Primary = Local GPS Backup = HSO
Primary = Mate GPS Backup = HSO
Primary = Remote GPS Backup = HSO
Primary = Remote GPS Backup = HSO
6-22 1X SC 4812T Lite BTS Optimization/ATP FEB 2005
PRELIMINARY
Troubleshooting: SCCP Backplane
Introduction
The SCCP Backplane is a multi–layer printed circuit board that interconnects all of the SCCP Cards and Modules. The complexity of this board lends itself to possible improper diagnoses when problems occur.
Connector Functionality
The following Connector Overview describes the major types of Backplane Connectors along with the functionality of each. This will assist the CFE to:
S Determine which connector(s) is associated with a specific problem
type.
S Isolate problems to a specific cable or connector.
Span Line Connector
The 50–pin Span Line Connector provides a primary and secondary (if used) Span Line Interface to each GLI in the SCCP Cage. The Span Line is used for MM/EMX Switch Control of the Master GLI and also all of the BBX Traffic.
Power Input (Return A and B Connectors)
Provides 27 Volt Input for use by the Power Supply Modules.
Power Supply Module Interface
Each Power Supply Module has a series of three different connectors to provide the needed inputs/outputs to the SCCP Backplane. These are:
– VCC/Ground Input Connector – Harting–style Multiple Pin Interface – +15V Analog Ground Output Connector
The Transceiver Power Module converts 27 Volts to a regulated +15, +6.5, +5.0 Volts to be used by the SCCP Cage Cards.
GLI Connector
This connector consists of a Harting 4SU Digital Connector and a 6–conductor COAXial Connector for RDM Distribution. The connectors provide inputs/outputs for the GLI Cards in the SCCP Backplane.
GLI Ethernet “A” and “B” Connections
These SMB Connectors are located on the SCCP Backplane and connect to the GLI Card. This interface provides all the Control and Data Communications over the Ethernet LAN between the Master GLI, the Redundant GLI, and the LMF.
6
BBX Connector
Each BBX Connector consists of a Harting 2SU/1SU Digital Connector and two 6–conductor COAXial Connectors. These connectors provide DC, Digital, and RF Inputs/Outputs for the BBX Cards in the SCCP Backplane.
FEB 2005 1X SC 4812T Lite BTS Optimization/ATP 6-23
PRELIMINARY
Troubleshooting: SCCP Backplane – continued
CIO Connectors
S RF RX Antenna Path Signal Inputs are routed through RX Paths of
the DRDCs or TRDCs at the RF Interface Panel (rear of the frame), and through COAXial Cables to the two MPC Cards.
The three “A” (Main) Signals go to one MPC; the three “B” (Diversity) Signals to the other. The MPC outputs the low–noise–amplified signals through the SCCP Backplane to the CIO where the signals are split and sent to the appropriate BBX.
S A Digital Bus then routes the Baseband Signal through the BBX, to
the SCCP Backplane, and then on to the MCC Slots.
S Digital TX Antenna Path Signals originate at the MCC Cards. Each
output is routed from the MCC Slot through the SCCP Backplane to the appropriate BBX.
S TX RF Path Signal originates from the BBX, travels through the
SCCP Backplane to the CIO, through the CIO, and then through multi-conductor COAXial Cabling to the Trunking Module and LPA Modules in the LPA Shelf.
SCCP Backplane Troubleshooting Procedure
The following tables provide standard procedures for troubleshooting problems that appear to be related to a defective SCCP Backplane. The tables are broken down into possible problems and steps that should be taken in an attempt to find the root cause.
6
NOTE
All steps in all tables should be followed before any attempt to replace the SCCP Backplane.
6-24 1X SC 4812T Lite BTS Optimization/ATP FEB 2005
PRELIMINARY
Troubleshooting: SCCP Backplane – continued
Digital Control Problems
No GLI Control via LMF (all GLI Cards)
Table 6-21: No GLI Control Through LMF (All GLI Cards)
n Step Action
1 Check the Ethernet LAN for proper connection, damage, shorts, or opens. 2 Ensure that the LAN IN and OUT Connectors in the Power Entry Compartment are properly
terminated. 3 Ensure that the proper IP Address is entered in the Network Login Tab of the LMF Login Screen. 4 Logout and exit from the LMF. 5 Restart the LMF. 6 Login to the BTS again. 7 Verify SCCP Backplane Shelf ID DIP Switch is set correctly. 8 Visually check the Master GLI Connectors (both card and backplane) for damage. 9 Replace the Master GLI with a known good GLI.
No GLI Control through Span Line Connection (All GLI Cards)
Table 6-22: No GLI Control Through Span Line Connection (Both GLI Cards)
n Step Action
1 Verify that the SCCP Backplane Shelf ID DIP Switch is set correctly. 2 Verify that the BTS and GLI Cards are correctly configured in the OMC–R/CBSC Database. 3 Verify that the Span Configurations set in the GLI Cards match those in the OMC–R/CBSC
Database.
– Refer to Table 6-47. 4 Visually check the Master GLI Connectors (both card and backplane) for damage. 5 Replace the Master GLI with a known good GLI. 6 Check the Span Line Cabling from the Punchblock to the Master GLI for proper connection and
damage.
Table 6-23: MGLI Control Good – No Control Over Co–located GLI
6
n Step Action
1 Verify that the BTS and GLIs are correctly configured in the OMC–R/CBSC Database. 2 Check the Ethernet Connections for proper connection, damage, shorts, or opens. 3 Visually check all GLI Connectors (both card and backplane) for damage. 4 Replace the remaining GLI with a known good GLI.
FEB 2005 1X SC 4812T Lite BTS Optimization/ATP 6-25
PRELIMINARY
Troubleshooting: SCCP Backplane – continued
No AMR Control (MGLI good)
Table 6-24: MGLI Control Good – No Control Over AMR
n Step Action
1 Visually check the Master GLI Connectors (both card and backplane) for damage. 2 Replace the Master GLI with a known good GLI. 3 Replace the AMR with a known good AMR.
No BBX Control in the Shelf
Table 6-25: MGLI Control Good – No Control over Co–located BBX Cards
n Step Action
1 Visually check all GLI Connectors (both card and backplane) for damage. 2 Replace the remaining GLI with a known good GLI. 3 Visually check BBX Connectors (both card and backplane) for damage. 4 Replace the BBX with a known good BBX.
No (or Missing) Span Line Traffic
6
Table 6-26: BBX Control Good – No (or Missing) Span Line Traffic
n Step Action
1 Visually check all GLI Connectors (both card and backplane) for damage. 2 Replace the remaining GLI with a known good GLI. 3 Visually check all Span Line Distribution (both connectors and cables) for damage. 4 If the problem seems to be limited to one BBX, replace the BBX with a known good BBX.
No (or Missing) MCC24E/MCC8E Channel Elements
Table 6-27: No MCC–1X/MCC24E/MCC8E Channel Elements
n Step Action
1 Verify Channel Elements on a co–located MCC of the same type.
(CDF MccType Codes: MCC8E = 0; MCC24E = 2; MCC–1X = 3) 2 Check MCC Connectors (both card and backplane) for damage. 3 If the problem seems to be limited to one MCC, replace it with a known good MCC of the same
type. 4 If no Channel Elements are active on any MCC, verify the Clock Reference to the CIO.
6-26 1X SC 4812T Lite BTS Optimization/ATP FEB 2005
PRELIMINARY
Troubleshooting: SCCP Backplane – continued
DC Power Problems
WARNING
Potentially lethal voltage and current levels are routed to the BTS Equipment.
This test must be carried out with a second person present, acting in a safety role.
Remove all rings, jewelry, and wrist watches prior to beginning this test.
No DC Input Voltage to SCCP Cage Power Supply Modules
Table 6-28: No DC Input Voltage to Power Supply Module Troubleshooting Procedure
n Step Action
1 Verify the DC Power is applied to the BTS Frame. 2 Determine if any circuit breakers have tripped.
S If a breaker has tripped, proceed to Step 3.
S If breaker does not trip, there is probably a defective module or subassembly within the SCCP
Cage.
– Perform the tests in Table 2-2 to attempt to isolate the module. 3 Remove all cards and modules from the SCCP Cage. 4 Reset the circuit breaker.
S If it does reset, proceed to Step 5. S If it does not reset or trips again, there is probably a cable or breaker problem within the frame
or DC PDA. 5 Verify that the PS1 and PS2 Circuit Breakers on the DC PDA are functional. 6 Remove the BTS Frame Rear Access Panel (Figure 2-2), and use a voltmeter to determine if the
Input Voltage is being routed to the SCCP Backplane. Measure the DC Voltage Levels between:
S The PWR_IN_A and PWR_RTN_A Contacts on the extreme right side at the rear of the
backplane.
S The PWR_IN_B and PWR_RTN_B Contacts on the extreme right side at the rear of the
backplane.
6
NOTE
If the voltage is not present, there is probably a cable or circuit breaker problem within the frame or DC PDA.
7 If everything appears to be correct, visually inspect the PS1 and PS2 Power Supply Module
Connectors.
table continued on next page
FEB 2005 1X SC 4812T Lite BTS Optimization/ATP 6-27
PRELIMINARY
Troubleshooting: SCCP Backplane – continued
Table 6-28: No DC Input Voltage to Power Supply Module Troubleshooting Procedure
n ActionStep
8 Replace the Power Supply Modules with known good modules. 9 If Steps 1 through 7 fail to indicate a problem, an SCCP Backplane failure has occurred (possibly
an open trace).
No DC Voltage (+5, +6.5, or +15 Volts) to a Specific GLI, BBX, or Switch Module
Table 6-29: No DC Input Voltage to any SCCP Cage Module Troubleshooting Procedure
n Step Action
1 If it has not been done, perform the procedure in Table 6-28. 2 Inspect the SCCP Cage Card Connectors (both card and backplane) for damage. 3 Replace suspect cards with known good cards.
TX and RX Signal Routing Problems
6
n Step Action
1 Inspect all Harting Cable Connectors and Backplane Connectors for damage in all the affected
2 Perform the steps outlined in the RF Path Troubleshooting Flowchart in Figure 6-1.
Table 6-30: TX and RX Signal Routing Problems Troubleshooting Procedure
card slots.
6-28 1X SC 4812T Lite BTS Optimization/ATP FEB 2005
PRELIMINARY
Troubleshooting: RFDS
Introduction
The RFDS is used to perform Pre–Calibration Verification and Post-Calibration Audits that limit-check the RFDS-generate and reported Receive Levels of every path from the RFDS through the Directional Coupler Coupled Paths. In the event of test failure, refer to the following tables.
All Tests Fail
Table 6-31: RFDS Fault Isolation – All Tests Fail Troubleshooting Procedure
Step Action
1 Check the TX Calibration Equipment for proper operation by performing the following actions. 1a Manually set the Signal Generator Output Attenuator to the lowest Output Power Setting. 1b Connect the Output Port to the Spectrum Analyzer RF Input Port.
2 Set the Signal Generator Output Attenuator to –90 dBm, and switch on the RF Output.
3 Verify that the Spectrum Analyzer can do the following:
– Receive the signal. – Indicate the correct Signal Strength (accounting for the Cable Insertion Loss). – Indicate the approximate frequency.
4 Visually inspect the RF Cabling.
Make sure that the Directional Coupler Forward Port and Reflected Port are connected to the RFDS Antenna Select Unit on the RFDS.
5 Check the wiring against the Site Documentation Wiring Diagram or the 1X SC4812T Lite Hardware
Installation manual (68P09262A57) 6 Verify that all changes to the RFDS Parameter Settings have been downloaded. 7 Status the TSU to verify that the TSIC and SUA Software Versions are correct. 8 Check to see that all RFDS Cards show green on the Front Panel LEDs. 9 Visually check for external damage.
10 If any card LEDs do not show green, replace the RFDS with a known–good unit.
– Re–test after replacement.
6
All RX and TX Paths Fail
If every Receive or Transmit Path fails, the problem most likely lies with the RF Converter Card or the Transceiver Card. Replace the RFDS with a known–good unit and retest.
FEB 2005 1X SC 4812T Lite BTS Optimization/ATP 6-29
PRELIMINARY
Troubleshooting: RFDS – continued
All Tests Fail on a Single Antenna
If all path failures are on one Antenna Port (Forward or Reflected), perform the checks in Table 6-32.
Table 6-32: RFDS Fault Isolation – All Tests Fail on Single Antenna Path Troubleshooting Procedure
Step Action
1 Visually inspect the frame internal RFDS Cabling to the suspect TRDC or DRDC. 2 Verify that the Forward and Reflected Ports connect to the correct RFDS Antenna Select Unit
positions on the RFDS ASU Card.
– Refer to the RFDS Installation Manual for details. 3 Replace the RFDS with a known–good unit. 4 Replace the RF Cables between the affected TRDC or DRDC and the RFDS.
6
6-30 1X SC 4812T Lite BTS Optimization/ATP FEB 2005
PRELIMINARY
Module Front Panel LED Indicators and Connectors
Module Status Indicators
Each of the non-passive Plug-in Cards/Modules has a bi-color (green and red) Status Indicator LED located on the card/module Front Panel. The LED is labeled PWR/ALM. If both colors are turned on, the indicator appears yellow.
Each plug-in card/module, except for the Fan Module, has its own Alarm (Fault) Detection Circuitry that controls the state of the PWR/ALM LED.
The Fan TACH Signal of each Fan Module is monitored by the AMR Card. Based on the status of this signal, the AMR controls the state of the PWR/ALM LED on the Fan Module.
Module LED Status (except GLI3, CSM, BBX, MCC)
PWR/ALM LED
Table 6-33 describes the states of the Card/Module Status Indicator LEDs.
Power Supply Module LED Status Combinations
Table 6-33: Card/Module PWR/ALM LED States
LED State Device Status
Solid GREEN NORMAL (Fault–Free) Mode
– No alarm present.
Solid RED Alarm (Fault) Mode due to electrical or hardware
failure.
– An alarm is being reported.
Note that an Alarm (Fault) Indication may or may not be due to a complete card/module failure and normal service may or may not be reduced or interrupted.
The Power Supply Module (PWR CNVTR) has its own Alarm (Fault) Detection Circuitry that controls the state of the PWR/ALM LED.
PWR/ALM LED
Table 6-34 describes the states of the bi-color Status Indicator LED.
Table 6-34: Card/Module PWR/ALM LED States
6
LED State Device Status
Solid GREEN NORMAL (Fault–Free) Mode
– No alarm present.
Solid RED Alarm (Fault) Mode due to electrical or hardware
failure.
– An alarm is being reported.
FEB 2005 1X SC 4812T Lite BTS Optimization/ATP 6-31
PRELIMINARY
Module Front Panel LED Indicators and Connectors – continued
CSM LED Status Combinations
PWR/ALM LED
The CSM Cards contain on-board Alarm Detection. Hardware and Software/Firmware Alarms are indicated via the Front Panel LEDs. Refer to Table 6-35.
After the Memory Tests, the CSM loads OOS–RAM Code from the Flash EPROM, if available.
– If not available, the OOS–ROM Code is loaded from the Flash
EPROM.
Table 6-35: CSM Card PWR/ALM LED States
LED State Device Status
Solid GREEN Master CSM is locked on to the GPS or
LFR while operating in INS_ACTIVE or INS_STANDBY Mode.
– No alarm present.
Solid RED 1. Color during System Initialization.
2. Alarm (Fault) Mode – An alarm is being reported.
Fast Flashing GREEN Standby CSM is locked on to the GPS or
LFR while in INS_STANDBY Mode.
– No alarm present.
6
Alternating Slow Flashing RED/ Fast Flashing GREEN
Fast Flashing GREEN 1. OOS_RAM Mode
Alternating Fast Flashing RED/ Fast Flashing GREEN
Alternating Fast Flashing RED/ Slow Flashing GREEN
OOS_ROM Mode
– An alarm is being reported.
2. INS_ACTIVE Mode in DUMB
Configuration.
– No alarm present.
OOS_RAM Mode
– An alarm is being reported.
OOS_RAM Mode and attempting to lock on to the GPS Signal.
– An alarm is being reported.
table continued on next page
6-32 1X SC 4812T Lite BTS Optimization/ATP FEB 2005
PRELIMINARY
Module Front Panel LED Indicators and Connectors – continued
Table 6-35: CSM Card PWR/ALM LED States
LED State Device Status
Solid YELLOW After a reset, the CSMs begin to boot.
Color during the SRAM Test and the Flash EPROM Code Check Test.
– If SRAM or Flash EPROM Tests fail,
the LED changes to Steady RED and the CSM attempts to reboot.
OFF 1. No DC Power to the card.
2. The on-board fuse is open.
FREQ Monitor Connector
A Test Port provided on the CSM Front Panel via a BNC Receptacle allows monitoring of the 19.6608 MHz Clock Signal generated by the CSM. When both CSM 1 and CSM 2 are in an in-service (INS) condition, the CSM 2 Clock Signal Frequency is the same as that output by CSM 1.
The Clock Signal is a Sine Wave Signal with a Minimum Amplitude of +2 dBm (800 mVpp) into a 50 Load connected to this port.
SYNC Monitor Connector
A Test Port provided at the CSM Front Panel via a BNC Receptacle allows monitoring of the “Even Second Clock” Reference Signal generated by the CSM Cards.
At this port, the Reference Signal is a Transistor–Transistor Logic (TTL) Active–High Signal with a Pulse Width of 153 nanoseconds.
MMI Connector
Behind the Front Panel – only accessible when the card is partially extended from its SCCP Cage Slot. The RS–232 MMI Port Connector is intended to be used primarily in the development or factory environment, but may be used in the field for Debug/Maintenance purposes.
6
FEB 2005 1X SC 4812T Lite BTS Optimization/ATP 6-33
PRELIMINARY
Module Front Panel LED Indicators and Connectors – continued
Figure 6-2: CSM Front Panel LED and Monitor Ports
SYNC MONITOR
PWR/ALM Indicator
FREQ MONITOR
FW00303
6
GLI3 LED Status Combinations
The GLI3 Card Indicators, Controls, and Connectors are described below and shown in Figure 6-3.
The Front Panel Indicators and Controls consist of:
S Four LEDs S One Pushbutton
ACTIVE LED
Table 6-36: GLI Card ACTIVE LED States
LED State Device Status
Solid GREEN INS_ACTIVE Mode
– This indication means that the GLI has Shelf
Control and is providing control of the digital interfaces.
OFF Not Active (i.e., INS_STANDBY).
– The Mate GLI is INS_ACTIVE and
operating normally.
6-34 1X SC 4812T Lite BTS Optimization/ATP FEB 2005
PRELIMINARY
Module Front Panel LED Indicators and Connectors – continued
MASTER LED
Table 6-37: GLI Card MASTER LED States
LED State Device Status
Solid GREEN GLI is Master (also referred to as MGLI).
– The GLI Card located in the Top Shelf is
designated by hardware as the INS_ACTIVE GLI Card.
– The GLI Card located in the Bottom Shelf is
designated by hardware as the INS_STANDBY GLI Card.
OFF GLI is non-master (i.e., Slave).
ALARM LED
Table 6-38: GLI Card ALARM LED States
LED State Device Status
Slow Flashing GREEN
Solid GREEN Turns ON briefly during System Initialization
OFF GLI is operating normally.
STATUS LED
Table 6-39: GLI Card STATUS LED States
LED State Device Status
Slow Flashing GREEN
Solid GREEN Turns ON briefly during System Initialization
OFF GLI is operating normally.
SPANS LED
Table 6-40: GLI Card STATUS LED States
INS_ACTIVE or INS_STANDBY Mode.
when the STATUS LED turns OFF.
INS_ACTIVE or INS_STANDBY
when the ALARM LED turns OFF.
6
LED State Device Status
Solid GREEN GLI is operating normally. Solid YELLOW One or more of the equipped initialized Span
Lines is receiving a Remote Alarm Indication Signal from the Remote End of the Span Line.
table continued on next page
FEB 2005 1X SC 4812T Lite BTS Optimization/ATP 6-35
PRELIMINARY
Module Front Panel LED Indicators and Connectors – continued
Table 6-40: GLI Card STATUS LED States
LED State Device Status
Solid RED One or more of the equipped initialized Span
Lines is in Alarm Mode.
OFF GLI is powered down, in Initialization Mode, or
in INS_STANDBY Mode.
GLI3 Pushbutton and Connectors
Figure 6-3 shows the Front Panel of the GLI3 Card and includes a description of the components.
RESET Pushbutton
Depressing the RESET Pushbutton causes a partial reset of the CPU and a reset of all board devices. GLI3 will be placed in the OOS_ROM state (blue).
MMI Connector
The RS–232MMI Port Connector is intended primarily for development or factory use but may be used in the field for Debug/Maintenance purposes.
6
6-36 1X SC 4812T Lite BTS Optimization/ATP FEB 2005
PRELIMINARY
Module Front Panel LED Indicators and Connectors – continued
Figure 6-3: GLI3 Front Panel
LED OPERATING STATUS
BPR A
BPR B
Connects to either a BPR or Expansion Cage and is wired as an Ethernet hub.
Connects to either a BPR or Expansion Cage and is wired as an Ethernet hub.
AUX
Wired as an Ethernet hub for direct connection to a personal comput er with a standard Ethernet cable. It allows connection of an Ethernet sniffer" when the Ethernet switch is properly configured for port mon itoring. This port may also be connected to the optional Motorola MOSCAD−L Network Fault Management unit using a Crossover Ethernet cable.
GLI
Supports the cross−coupled Ethernet circuits to the Mate GLI using a standard Ethernet straight cable.
RESET
Pressing and releasing the switch resets al l functions on the GLI3.
ALARM OFF − operating normally.
ON − briefly during powerup when the Alarm LED turns OFF. SLOW GREEN − when the GLI3 is INS (inservice).
Span
OFF − card is powered down, in initialization, or in standby. GREEN − operating normally. YELLOW − one or more of the equipped initialized spans is receiving a remote alarm indication signal from the far end. RED − one or more of the equipped initialized spans is in an alarm state.
MMI
An RS232, serial, asynchronous communications link for use as an MMI port. This port supports 300 baud, up to a maximum of 115,200 baud communications.
STATUS OFF − operating normally.
ON − briefly during powerup when the Alarm LED turns OFF. SLOW GREEN − when the GLI3 is INS (inservice).
ACTIVE
Shows the operating status of the redundant cards. The redundant card toggles automatically if the active card is removed or fails.
ON − ac tive card operating normally. OFF − standby card operating normally.
BPR B AUX RESET
GLIBPR A
ALARM
MMI
STA
100BASE–T to BTS Packet Router or Expansion Port
100BASE–T Auxiliary Monitor Port
Dual 100BASE–T in a single RJ45 to Redundant (Mate) GLI3
SPAN
ACT
Reset Switch Span (LED)
Alarm (LED) MMI Port
Active (LED) Status (LED)
ti-CDMA-WP-00064-v01-ildoc-ftw
6
BBX LED Status Combinations
PWR/ALM LED
All Broadband Transceiver (BBX) Cards have their own Alarm (Fault) Detection Circuitry that controls the state of the PWR/ALM LED.
Table 6-41 describes the states of the bi-color PWR/ALM LED.
Table 6-41: BBX Card PWR/ALM LED States
Physical and Alarm State Off Red Green
Microprocessor in Reset ––– Continuous ––– OOS–ROM – No alarm 1.4s ––– 0.2s OOS–ROM – Alarm ––– 1.4s 0.2s OOS–RAM – No alarm 0.2s ––– 0.2s
FEB 2005 1X SC 4812T Lite BTS Optimization/ATP 6-37
PRELIMINARY
Module Front Panel LED Indicators and Connectors – continued
Table 6-41: BBX Card PWR/ALM LED States
Physical and Alarm State GreenRedOff
OOS–RAM – Alarm ––– 0.2s 0.2s In Service – No alarm ––– ––– Continuous In Service – Alarm ––– 0.2s 1.4s
ACTIVE LED
Table 6-42 describes the states of the ACTIVE LED:
Table 6-42: BBX Card ACTIVE LED States
Physical and Alarm State Off Red Green
Dekeyed Continuous ––– ––– Keyed ––– ––– Continuous
MCC LED Status Combinations
The Multi-Channel CDMA (MCC–24/MCC–8E/MCC–1X) Card has Status Indicator LEDs and Connectors as described below. Refer to Figure 6-4. Note that the figure does not show the connectors; they are concealed by the removable lens. The location of the LEDs are as follows:
S PWR/ALM LED is at the top of the card.
6
S ACTIVE LED is at the bottom of the card.
PWR/ALM LED
Table 6-43: MCC Card PWR/ALM LED States
LED State Device Status
Solid RED 1. Briefly lit during System Initialization.
2. Alarm (Fault) Mode. – An alarm is being reported.
OFF Operating normally.
ACTIVE LED
Table 6-44: MCC Card ACTIVE LED States
LED State Device Status
Solid GREEN Card is code–loaded, enabled, and operating
in INS_ACTIVE Mode, on-line, processing traffic.
– No alarm present.
Slow Flashing GREEN Card is not code–loaded.
– No alarm present.
6-38 1X SC 4812T Lite BTS Optimization/ATP FEB 2005
PRELIMINARY
Module Front Panel LED Indicators and Connectors – continued
Table 6-44: MCC Card ACTIVE LED States
LED State Device Status
Fast Flashing GREEN Card is code–loaded but not enabled.
– No alarm present.
Solid RED Alarm (Fault) Mode.
– An alarm is being reported.
Alternating Slow Flashing RED / Slow Flashing GREEN
OFF 1. Card is inactive.
Both PWR/ALM and ACTIVE LEDs
Table 6-45: MCC Card PWR/ALM and ACTIVE LED States
LED State Device Status
Solid RED 1. Card is in Reset Mode.
MMI Connectors
RS–232 Port Connector:
This Port Connector (four pin) is intended to be used primarily in Development and Factory environments, but may be used in the field for Debugging purposes.
– A Removable Lens covers this Port Connector.
The CHI Bus is inactive after System Initialization.
2. Card is off-line.
3. Card is not processing traffic.
2. The BCP is inactive.
6
The RJ–14 Ethernet Port Connector:
This Port Connector (eight pin) is intended to be used primarily in the Development environment, but may be used in the field for High Data Rate Debugging purposes.
– A Removable Lens covers this Port Connector.
FEB 2005 1X SC 4812T Lite BTS Optimization/ATP 6-39
PRELIMINARY
Module Front Panel LED Indicators and Connectors – continued
Figure 6-4: MCC24 and MCC–1X Front Panel LEDs and LED Indications
PWR/ALM ACTIVE
PWR/ALM L E D
LED OPERATING STATUSCOLOR
GREENACTIVE
RED
RED
ON – Briefly during Power–up and during failure conditions
RAPIDLY FLASHING – Card is Code Loaded but not enabled
SLOW FLASHING – Card is not Code Loaded ON – Card is Code Loaded and enabled (INS_ACT)
ON – 1) Briefly during Power–up
2) Continuously during fault conditions
SLOW FLASHING (alternately with green) – Concentration Highway Interface (CHI) Bus inactive on Power–up
4812ETL0030–1
ACTIVE LED
LENS (REMOVABLE)
PWR/ALM OFF – Operating normally
An alarm is generated in the event of a failure
6
CLPA LED Status Combinations
ETIB Board LED for the LPA Module
In the SC 4812T Lite Platform, the CLPA Module does not contain an LEDs. The LED on the CLPA Fan Module provides visual operational information for the CLPA Module. Refer to Figure 6-5.
Each LPA Module is provided with a bi–color LED on the ETIB Module next to the MMI Connector. Refer to Table 6-46.
6-40 1X SC 4812T Lite BTS Optimization/ATP FEB 2005
PRELIMINARY
Module Front Panel LED Indicators and Connectors – continued
Table 6-46: LPA ETIB Module LED
LED State Device Status
Solid GREEN INS_ACTIVE Mode
– No alarm present.
Figure 6-5: CLPA Module
Alternating Flashing GREEN/ RED
INS_ACTIVE Mode
S If a BBX is keyed, a Low Power
Alarm is present.
S If a BBX is not keyed, no alarm is
present.
Flashing RED Alarm (Fault) Mode
– An LPA Alarm is being reported.
TOP
CLPA
MODULE
6
BOTTOM
CLPA
MODULE
FAN
MODULE
FEB 2005 1X SC 4812T Lite BTS Optimization/ATP 6-41
PRELIMINARY
Troubleshooting: Span Control Link
Span Problems (No Control Link)
Table 6-47: Control Link Failure Troubleshooting Procedure
n Step Action
1 Connect the LMF Computer to the MMI Port on the applicable MGLI3/GLI3 as shown in
Figure 6-6.
2 Start an MMI Communication Session with the applicable MGLI3/GLI3 by using the Windows
Desktop Shortcut Icon.
– Refer to Table 3-14.
3 Once the connection window opens, press the LMF Computer Enter Key until the GLI3>
Prompt is obtained. At the GLI3> Prompt, enter:
4
config ni current <cr> (equivalent of Span view command)
The system will respond with a display similar to the following:
The frame format in flash is set to use T1_2. Equalization: Span A – Default (0–131 feet for T1/J1, 120 Ohm for E1) Span B – Default (0–131 feet for T1/J1, 120 Ohm for E1) Span C – Default (0–131 feet for T1/J1, 120 Ohm for E1) Span D – Default (0–131 feet for T1/J1, 120 Ohm for E1) Span E – Default (0–131 feet for T1/J1, 120 Ohm for E1) Span F – Default (0–131 feet for T1/J1, 120 Ohm for E1)
6
Linkspeed: Default (56K for T1 D4 AMI, 64K otherwise) Currently, the link is running at the default rate The actual rate is 0
NOTE
Defaults for Span Equalization are 0–131 feet for T1/J1 Spans and 120 Ohm for E1. Default Link Speed is 56K for T1 D4 AMI Spans and 64K for all other types. There is no need to change from defaults unless the OMC–R/C BS C Span Configuration requires it.
5 The Span Configurations loaded in the GLI must match those in the OMC–R/CBSC Database for
the BTS.
S If they do, proceed to Step 6. S If they do not, proceed to Table 6-48.
6 Repeat Steps 1 through 5 for all remaining GLI Cards. 7 If the Span Settings are correct, verify the EDLC Parameters using the show Command.
– Check for any Alarm Conditions that indicate the Span is not operating correctly.
S Try looping back the Span Line from the DSX Panel to the MM, and verify that the looped
signal is good.
S Listen for a Control Tone on the appropriate Timeslot from the Base Site and MM.
table continued on next page
6-42 1X SC 4812T Lite BTS Optimization/ATP FEB 2005
PRELIMINARY
Troubleshooting: Span Control Link – continued
Table 6-47: Control Link Failure Troubleshooting Procedure
n ActionStep
8 Exit the GLI MMI Session and HyperTerminal Connection by performing the following actions.
8a Select File from the Connection Window Menu Bar. 8b Select Exit from the Pull–down Menu.
Figure 6-6: MGLI/GLI Board MMI Connection Detail
To MMI Port
8–PIN
8–PIN TO 10–PIN RS–232 CABLE (P/N 30–09786R01)
STATUS RESET ALARM SPANS MASTER MMI ACTIVE
STATUS LED
RESET Pushbutton
ALARM LED
SPANS LED
MASTER LED
MMI Port Connector
ACTIVE LED
NULL MODEM
BOARD
(TRN9666A)
6
LMF COMPUTER
COM1
OR
COM2
RS–232 CABLE
DB9–TO–DB25 ADAPTER
FEB 2005 1X SC 4812T Lite BTS Optimization/ATP 6-43
PRELIMINARY
Troubleshooting: Span Control Link – continued
Set BTS Site Span Configuration
NOTE
Perform the following procedure ONLY if Span Configurations loaded in the MGLI3/GLI3s do not match those in the OMC–R/CBSC database, AND ONLY when the exact Configuration Data is available.
Loading incorrect Span Configuration Data will render the site inoperable.
Table 6-48: Set BTS Span Parameter Configuration Procedure
n Step Action
1 If not previously done, connect the LMF Computer to the MMI Port on the applicable
MGLI3/GLI3 as shown in Figure 6-6.
2 If there is no MMI Communication Session in progress with the applicable MGLI3/GLI3, initiate
one by using the Windows Desktop Shortcut Icon.
– Refer to Table 3-14.
3 At the GLI3> Prompt, enter the following command
GLI3>config ni format <option> <cr>
– The terminal will display a response similar to the following:
6
COMMAND SYNTAX: config ni format option Next available options: LIST – option : Span Option E1_1 : E1_1 – E1 HDB3 CRC4 no TS16 E1_2 : E1_2 – E1 HDB3 no CRC4 no TS16 E1_3 : E1_3 – E1 HDB3 CRC4 TS16 E1_4 : E1_4 – E1 HDB3 no CRC4 TS16 T1_1 : T1_1 – D4, AMI, No ZCS T1_2 : T1_2 – ESF, B8ZS J1_1 : J1_1 – ESF, B8ZS (Japan) – Default J1_2 : J1_2 – ESF, B8ZS T1_3 : T1_3 – D4, AMI, ZCS>
NOTE
With this command, all active (in–use) Spans will be set to the same format.
table continued on next page
6-44 1X SC 4812T Lite BTS Optimization/ATP FEB 2005
PRELIMINARY
Troubleshooting: Span Control Link – continued
Table 6-48: Set BTS Span Parameter Configuration Procedure
n ActionStep
4 To set or change the Span Type, enter the correct option from the list at the Entry Prompt (>), as
shown in the following example.
> T1_2 <cr>
– An acknowledgement similar to the following will be displayed:
The value has been programmed. It will take effect after the next reset. GLI3>
NOTE
The entry is case–sensitive and must be typed exactly as it appears in the list.
– If the entry is typed incorrectly, a response similar to the following will be displayed:
CP: Invalid command GLI3>
5 If the current MGLI/GLI Span Rate must be changed, enter the following MMI Command:
config ni Link Speed
– The terminal will display a response similar to the following:
<cr>
Next available options: LIST – Link Speed : Span Linkspeed 56K : 56K (default for T1_1 and T1_3 systems)
64K : 64K (default for all other Span Configurations) >
NOTE
With this command, all active (in–use) Spans will be set to the same Link Speed. To set or change the Span Link Speed, enter the required option from the list at the Entry Prompt
6
(>), as shown in the following example:
> 64K <cr>
– An acknowledgement similar to the following will be displayed:
The value has been programmed. It will take effect after the next reset. GLI3>
NOTE
The entry is case–sensitive and must be typed exactly as it appears in the list.
– If the entry is typed incorrectly, a response similar to the following will be displayed:
CP: Invalid command GLI3>
table continued on next page
6
FEB 2005 1X SC 4812T Lite BTS Optimization/ATP 6-45
PRELIMINARY
Troubleshooting: Span Control Link – continued
Table 6-48: Set BTS Span Parameter Configuration Procedure
n ActionStep
7 If the Span Equalization must be changed, enter the following MMI Command:
config ni equal <cr>
– The terminal will display a response similar to the following:
COMMAND SYNTAX: config ni equal Span equal Next available options: LIST – Span : Span a : Span A b : Span B c : Span C d : Span D e : Span E f : Span F >
8 At the Entry Prompt (>), enter the designator from the list for the Span to be changed as shown in
the following example:
> a <cr>
– The terminal will display a response similar to the following:
COMMAND SYNTAX: config ni equal a equal Next available options: LIST – equal : Span Equalization 0 : 0–131 feet (default for T1/J1) 1 : 132–262 feet
6
2 : 263–393 feet 3 : 394–524 feet 4 : 525–655 feet 5 : LONG HAUL 6 : 75 OHM 7 : 120 OHM (default for E1) >
9 At the Entry Prompt (>), enter the code for the required equalization from the list as shown in the
following example:
> 0 <cr>
– The terminal will display a response similar to the following:
> 0 The value has been programmed. It will take effect after the next reset. GLI3>
10 Repeat Step 7 through Step 9 for each in–use Span.
table continued on next page
6-46 1X SC 4812T Lite BTS Optimization/ATP FEB 2005
PRELIMINARY
Troubleshooting: Span Control Link – continued
Table 6-48: Set BTS Span Parameter Configuration Procedure
n ActionStep
11 Press the RESET Button on the MGLI3/GLI3 for changes to take effect.
* IMPORTANT
After executing the config ni format, config ni Link Speed, and/or config ni equal commands, the affected MGLI/GLI Card MUST be reset and reloaded for changes to take effect.
Although defaults are shown, always consult the Site Documentation for Span Type and Link Speed used at the site.
12 Once the MGLI/GLI has reset, execute the following command to verify Span Settings are as
required:
config ni current <cr> (equivalent of Span view command)
– The system will respond with a display similar to the following:
The frame format in flash is set to use T1_2. Equalization: Span A – 0–131 feet Span B – 0–131 feet Span C – Default (0–131 feet for T1/J1, 120 Ohm for E1) Span D – Default (0–131 feet for T1/J1, 120 Ohm for E1) Span E – Default (0–131 feet for T1/J1, 120 Ohm for E1) Span F – Default (0–131 feet for T1/J1, 120 Ohm for E1)
Linkspeed: 64K Currently, the link is running at 64K The actual rate is 0
S If the Span Configuration is correct, return to Step 6 of Table 6-47. S If the Span Configuration is not correct, proceed to Step 13.
13 Perform the applicable step from this table to change it. 14 Repeat Step 11 and Step 12 to verify required changes have been programmed.
6
FEB 2005 1X SC 4812T Lite BTS Optimization/ATP 6-47
PRELIMINARY
Troubleshooting: Span Control Link – continued
Notes
6
6-48 1X SC 4812T Lite BTS Optimization/ATP FEB 2005
PRELIMINARY
Appendix A: Data Sheets
Appendix Content
Optimization (Pre–ATP) Data Sheets A-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Site Checklist A-2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Preliminary Operations A-2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
GPS Receiver Operation A-5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
LPA IM Reduction A-6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
TX Bay Level Offset / Power Output Verification for 3–Sector
Configurations A-7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
TX Antenna VSWR A-9 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
RX Antenna VSWR A-9 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Alarm Verification A-10 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
A
Site Serial Number Check List A-11 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SCCP Cage A-11 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
LPA Modules A-12 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
FEB 2005 1X SC 4812T Lite BTS Optimization/ATP
PRELIMINARY
A
Table of Contents – continued
Notes
1X SC 4812T Lite BTS Optimization/ATP FEB 2005
PRELIMINARY
Optimization (Pre–ATP) Data Sheets
Verification of Test Equipment Used
T able A-1: Verification of Test Equipment Used
Manufacturer Model Serial Number
A
Comments:________________________________________________________ __________________________________________________________________
FEB 2005 1X SC 4812T Lite BTS Optimization/ATP A-1
PRELIMINARY
A
Optimization (Pre–ATP) Data Sheets – continued
Site Checklist
T able A-2: Site Checklist
OK Parameter Specification Comments
Deliveries Per established procedures
Floor Plan Verified
Inter Frame Cables:
Ethernet Frame Ground Power
Factory Data:
BBX Test Panel RFDS
Per procedure Per procedure Per procedure
Per procedure Per procedure Per procedure
Site Temperature
Dress Covers/Brackets
Preliminary Operations
T able A-3: Preliminary Operations
OK Parameter Specification Comments
Frame ID DIP Switches Per Site Equipage
Ethernet LAN
Verification
Comments:_________________________________________________________
Verified per procedure
A-2 1X SC 4812T Lite BTS Optimization/ATP FEB 2005
PRELIMINARY
Optimization (Pre–ATP) Data Sheets – continued
Pre–Power and Initial Power Tests
T able A-4: Pre–power Checklist
OK Parameter Specification Comments
Pre–Power–up Tests Table 2-2 Internal Cables:
Span CSM Power
Ethernet Connectors:
LAN A Ohms LAN B Ohms LAN A Shield LAN B Shield LAN A IN & OUT
Terminators
LAN B IN & OUT
Terminators
Ethernet Boots
Verified Verified Verified
Verified Verified Installed Installed Isolated Isolated Installed
A
Air Impedance Cage (single cage) Installed
Initial Power–up Tests Table 2-5
Comments:_________________________________________________________
Frame Fans LEDs
Operational Illuminated
FEB 2005 1X SC 4812T Lite BTS Optimization/ATP A-3
PRELIMINARY
A
Optimization (Pre–ATP) Data Sheets – continued
General Optimization Checklist
T able A-5: General Optimization Checklist
OK Parameter Specification Comments
Preparing the LMF
LMF–to–BTS Connection
Verify GLI2 Ethernet Address Settings
Ping LAN A
Ping LAN B
Verify ROM Code Loads for Software Release
Download/Enable MGLI2
Download/Enable GLI2
Set Site Span Configuration
Set CSM Clock Source
Enable CSM Cards
Download/Enable MCC Cards (24/8E/1X)
Download BBX Cards (2 or 1X)
Program TSU NAM
Load LMF Software Create site–specific BTS directory Create HyperTerminal Connection
Table 3-2 Table 3-3 Table 3-4
Table 3-6
Table 6-4 Table 3-15 Table 3-15
Table 3-16 Table 3-17 Table 3-17 Table 6-47 Table 3-19 Table 3-20 Table 3-18 Table 3-18 Table 3-52
Test Set Calibration
Test Cable Calibration
Comments:_________________________________________________________
Table 3-36 Table 3-32
A-4 1X SC 4812T Lite BTS Optimization/ATP FEB 2005
PRELIMINARY
Optimization (Pre–ATP) Data Sheets – continued
GPS Receiver Operation
T able A-6: GPS Receiver Operation
OK Parameter Specification Comments
A
GPS Receiver Control Task State:
tracking satellites
Initial Position Accuracy: Verify:
Current Position:
lat lon height
Current Position: satellites tracked Estimated:
(>4) satellites tracked,(>4) satellites visible
Surveyed:
1) satellite tracked,(>4) satellites visible
(>
GPS Receiver Status:Current Dilution of Precision (PDOP or HDOP): (<30)
Current Reference Source:
Number: 0; Status: Good; Valid: Yes
Verify parameter
Estimated or
Surveyed
RECORD in
msec and cm.
Also convert to
deg min sec.
Verify parameter
as appropriate
Verify parameter
Verify parameter
Comments:_________________________________________________________
FEB 2005 1X SC 4812T Lite BTS Optimization/ATP A-5
PRELIMINARY
A
Optimization (Pre–ATP) Data Sheets – continued
LPA IM Reduction
T able A-7: LPA IM Reduction
Parameter
Carrier
OK
LPA
#
2:1
3–SectorBP3–Sector
Specification
Comments
1A C1 C1 No Alarms
1B C1 C1 No Alarms
1C C1 C1 No Alarms
1D C1 C1 No Alarms
3A C2 C2 No Alarms
3B C2 C2 No Alarms
3C C2 C2 No Alarms
3D C2 C2 No Alarms
Comments:_________________________________________________________
A-6 1X SC 4812T Lite BTS Optimization/ATP FEB 2005
PRELIMINARY
Optimization (Pre–ATP) Data Sheets – continued
TX Bay Level Offset / Power Output Verification for 3–Sector Configurations
One Carrier and Two Carrier Non–adjacent Channels
T able A-8: TX BLO Calibration (Three Sector: One Carrier and Two Carrier Non–adjacent Channels)
OK Parameter Specification Comments
A
Calibrate Carrier 1
Calibrate Carrier 2
Calibration Audit
Carrier 1
TX Bay Level Offset = 45 dB
dB) prior to Calibration
(+5
TX Bay Level Offset = 45 dB
dB) prior to Calibration
(+5
0 dB (+0.5 dB) for Gain Set
Resolution Post–Calibration
BBX2–1, ANT–1A = ______dB
BBX2–r, ANT–1A = ______dB
BBX2–2, ANT–2A = ______dB
BBX2–r, ANT–2A = ______dB
BBX2–3, ANT–3A = ______dB
BBX2–r, ANT–3A = ______dB
BBX2–4, ANT–1B = ______dB
BBX2–r, ANT–1B = ______dB
BBX2–5, ANT–2B = ______dB
BBX2–r, ANT–2B = ______dB
BBX2–6, ANT–3B = ______dB
BBX2–r, ANT–3B = ______dB
BBX2–1, ANT–1A = ______dB
BBX2–r, ANT–1A = ______dB
BBX2–2, ANT–2A = ______dB
BBX2–r, ANT–2A = ______dB
Comments:________________________________________________________
__________________________________________________________________
FEB 2005 1X SC 4812T Lite BTS Optimization/ATP A-7
Calibration Audit
Carrier 2
0 dB (+0.5 dB) for Gain Set
Resolution Post–Calibration
BBX2–3, ANT–3A = ______dB
BBX2–r, ANT–3A = ______dB
BBX2–4, ANT–1B = ______dB
BBX2–r, ANT–1B = ______dB
BBX2–5, ANT–2B = ______dB
BBX2–r, ANT–2B = ______dB
BBX2–6, ANT–3B = ______dB
BBX2–r, ANT–3B = ______dB
PRELIMINARY
A
Optimization (Pre–ATP) Data Sheets – continued
Two Carrier Adjacent Channel
T able A-9: TX Bay Level Offset Calibration (Three Sector: Two Carrier Adjacent Channels)
OK Parameter Specification Comments
Calibrate Carrier 1
Calibrate Carrier 2
Calibration Audit
Carrier 1
TX Bay Level Offset = 45 dB (typical),
38 dB (minimum) prior to Calibration
TX Bay Level Offset = 45 dB (typical),
38 dB (minimum) prior to Calibration
0 dB (+0.5 dB) for Gain Set Resolution
Post–Calibration
BBX2–1, ANT–1A = ______dB
BBX2–r, ANT–1A = ______dB
BBX2–2, ANT–2A = ______dB
BBX2–r, ANT–2A = ______dB
BBX2–3, ANT–3A = ______dB
BBX2–r, ANT–3A = ______dB
BBX2–4, ANT–1B = ______dB
BBX2–r, ANT–1B = ______dB
BBX2–5, ANT–2B = ______dB
BBX2–r, ANT–2B = ______dB
BBX2–6, ANT–3B = ______dB
BBX2–r, ANT–3B = ______dB
BBX2–1, ANT–1A = ______dB
BBX2–r, ANT–1A = ______dB
BBX2–2, ANT–2A = ______dB
BBX2–r, ANT–2A = ______dB
Comments:________________________________________________________
__________________________________________________________________
A-8 1X SC 4812T Lite BTS Optimization/ATP FEB 2005
Calibration Audit
Carrier 2
0 dB (+0.5 dB) for Gain Set Resolution
Post–Calibration
BBX2–3, ANT–3A = ______dB
BBX2–r, ANT–3A = ______dB
BBX2–4, ANT–1B = ______dB
BBX2–r, ANT–1B = ______dB
BBX2–5, ANT–2B = ______dB
BBX2–r, ANT–2B = ______dB
BBX2–6, ANT–3B = ______dB
BBX2–r, ANT–3B = ______dB
PRELIMINARY
Optimization (Pre–ATP) Data Sheets – continued
TX Antenna VSWR
T able A-10: TX Antenna VSWR
OK Parameter Specification Data
A
Comments:________________________________________________________
__________________________________________________________________
RX Antenna VSWR
VSWR –
Antenna 1A
VSWR –
Antenna 2A
VSWR –
Antenna 3A
VSWR –
Antenna 1B
VSWR –
Antenna 2B
VSWR –
Antenna 3B
< (1.5 : 1)
< (1.5 : 1)
< (1.5 : 1)
< (1.5 : 1)
< (1.5 : 1)
< (1.5 : 1)
T able A-11: RX Antenna VSWR
OK Parameter Specification Data
Comments:_________________________________________________________
__________________________________________________________________
VSWR –
Antenna 1A
VSWR –
Antenna 2A
VSWR –
Antenna 3A
VSWR –
Antenna 1B
VSWR –
Antenna 2B
VSWR –
Antenna 3B
< (1.5 : 1)
< (1.5 : 1)
< (1.5 : 1)
< (1.5 : 1)
< (1.5 : 1)
< (1.5 : 1)
FEB 2005 1X SC 4812T Lite BTS Optimization/ATP A-9
PRELIMINARY
A
Optimization (Pre–ATP) Data Sheets – continued
Alarm Verification
T able A-12: CDI Alarm Input Verification
OK Parameter Specification Data
Comments:_________________________________________________________
Verify CDI Alarm
Input Operation.
BTS Relay #XX –
Contact Alarm Sets/Clears
A-10 1X SC 4812T Lite BTS Optimization/ATP FEB 2005
PRELIMINARY
Loading...