Nokeval 201, 202 User Manual

Page 1
No 050101
Nokeval
User's Manual
Models 201 & 202
1
Page 2
Contents
User's Manual Models 201 & 202 ..................................................................1
Autopowered LED-displays ............................................................................3
T ypical application ................................................................................................................ 3
Front panel buttons and indicators ..................................................................5
Configuration mode.................................................................................. 5
Resetting configuration parameters .......................................................... 5
Alarm level setting..................................................................................... 5
Alarm functions ........................................................................................ 5
Disable alarms.......................................................................................... 5
Manual reset............................................................................................. 5
Configuration...................................................................................................6
Enter into configuration mode .................................................................. 6
Access code for configuration ................................................................. 6
Description............................................................................................................................ 7
Input terminals.......................................................................................... 7
Alarm connections, only with model 202................................................... 7
Measuring mode ................................................................................................................... 7
Configuration mode..............................................................................................................7
Alarms off................................................................................................. 7
Nokeval Oy
Yrittäjäkatu 12 37100 NOKIA, FINLAND Tel. +358 3-342 4800 Fax. +358 3-342 2066
email [email protected] http:// www.nokeval.com
2
Page 3
Autopowered LED-displays
201 and 202
Space for unit of measure. Commonly used unit collection is delvered with the unit.
Transmitter
4-20 mA
• For process input 4-20 mA
• Without external power supply
• Loop resistance 240 ohm only
• 4-digit processor based display
• Scaling on front panel
• 2 settable alarms
• Pass words for alarms and configuration
• Front panel rating IP 65
Nokeval
20.1
4-20 mA
4..20 mA Polarity
protected
m³/h
(+)
( - )
Alarm 1 (low level)
Alarm 2 (High level)
Semiconductor fuse
Uz=4,8 V
3240
General description
Autopowered bright red LED-display needs no external power supply. Current signal 4-20 mA provides the necessary energy. Therefore, it is possible to install the meter in places having no auxiliary power available. You can now replace the autopowered LCD-displays, having very poor visibility, by bright red LED-displays. There are two models: 201 without alarms and model 202 with two alarm contacts. Display scaling and configuration by front panel buttons. Unit has digital filter for stabilizing the 4-digit display.
10 ohm
This feature is usefull in cases where large numerical value is needed. In model 202 You may configure two optional alarms, high and low. Alarm value setting is designed for applications where it can stay as it is once adjusted. More versatile alarm settings and alternative alarm modes offer our powered models 2011 and 2021. Pass word is settable for entering configuration and alarm stages. Front panel protection IP65.
3
Page 4
T echnical specifications:
Input 4..20 mA
Display scaling -999....+9999
Accuracy 0.05% of span Input voltage drop 201 continuous 4,8 V = 4-20 mA (comparable 240 Ω, non resistive)
20 2 continuous 7,3 V = 4-20 mA (comparable 340 Ω, non resistive) with alarms Alarm relays (option) 2 solid state relays (SSR), max. 250 VAC, 150 mA Alarm reset automatic or manual (hold) via front panel key Alarm mode High and low level Hysteresis Selectable 0..100 % Display 4-digit red LED, 14.5 mm, adjustable brightness Front plate protection IP65 with gasket, without gasket IP54 Push buttons Switches under front panel surface Ambient temperature 0...+60 °C T erminals Detachable 2,5 mm² Weight 150 g
Order codes:
Model 201-4/20 mA 4-digit 4-20 mA loop powered indicator Model 202-4/20 mA With optional 2 alarms
Connections:
Relays max. 250 VAC, 150 mA
Low level alarm
High level alarm
Case dimensions (mm):
ø2,5
48
A1 A2
654 321
7
96
-
+
Input 4-20 mA
Alarm only in model 202
Nc
T erminal 3 is not used
65
Cut out
43.7 x 90,7 mm ± 0.7 mm
4
6
Gasket (IP65)
10
Page 5
Front panel buttons and indicators
Alarm indicators LED's A1..A2.
5620
▲▼-arrow-buttons are used to change numerical value and for moving on configuration menu.
*
Conf-led indicates configuration mode
Exit from selected configuration stage
Configuration mode
Configuration can be started by pressing and holding ★- and ▲-keys simultaneously for 2 seconds. Configuration stage is for selecting input, display scaling and alarm function. Specified instructions on pages 6-7 section Configuration.
Resetting configuration parameters
Some times it is necessary to return indicator parameters to factory defaults, e.g. if secret access code is missed. Resetting can be done by pressing and holding ★- and ➤-keys simultaneously for 2 seconds when connecting input signal 4..20 mA. Prosedure will reset all settings to factory defaults.
Alarm level setting
Enter selections in configuration stage
Alarm functions
Alarms can be viewed in configuration mode. Special instructions on pages 6-7, section configuration.
Disable alarms
Negative hysteresis value disables alarm function.
Manual reset
Auto reset is a standard function. Manual reset with front panel ▼-key can be selected by choosing wider hysteresis than full span (Hi -Lo). For example: Input scaling is 0..100,0 i.e. full span is 100. Select hysteresis larger than 100 (9999) and You will have manual reset.
Alarm levels are selected with ▲▼-buttons one number at a time.
Changing begins from the most signifigant digit on the left, desimal point
is selected first. Next digit to right is selected with ➤-button.
Accept and exit with ★ -button.
Value selection
400.00
Numbers
0...9
Selecting next digit
400.00
Desimal point selection with -keys before number selection
5
Page 6
Configuration
Configuration can be started by pressing and holding ★- and ▲-keys simultaneously for 2 seconds. Arrow keys ▲▼ moves up and down in main menu. Desired function is selected with ➤-key. Save mode can be selected directly by pushing ★-key in main menu.
Enter into configuration mode
Configuration can be started by pressing and holding ★- and ▲-keys simultaneously for 2 seconds. Arrow keys ▲▼ moves up and down in main menu.
UnDo
SAVE
Undo changes and exit
Save and Exit
AL L
Old value
State of
change
Alarm values and hysteresis are selected in configuration mode. Changes can be restored by selecting text UnDO into display and pressing ➤-key. Note! Detailed configuration stage description on next page.
Access code for configuration
Configuration mode can be secured with pass word. If function is selected unit asks CODE. Enter required key combination as shown on page 8 section CFCo.
Return (★)
*
New value
Low level alarm setting.
AL H
ALHy
DEC
Lo
Hi
FiLt
Inte
High alarm setting, same routine as low level setting.
Hysteresis 0..50%. Negative value disables alarm function. Manual reset with front panel keys can be selected by choosing wider hysteresis than full span (Hi -Lo).
Decimals 0-3 (▲▼)
Return (★)
*
Old value
Display scaling for 20 mA, maximum value. e.g. 20 mA=1000, decimals are selected in section DEC. Same routine as section Lo.
Digital filter, factory default 0,2. Value 1 means no filter
Display intensity 1-15. 15 = brightest
State of
change
New value
LO and HI
Display scaling for 4 mA. Point selects number of digits (not decimals) (▲▼) and then select minmum scale value with arrow keys (➤) (▲▼). Number of decimals is selcted in section DEC. When exiting with ★-key, display show selected value with decimals.
TrF
CFCO
CAL
Square root function: LIN = linear display
Sqrt = square root display
Pass word for configuration mode
CODE
Input calibration. Detailed instructions on page 8.
6
Page 7
Description
Input terminals 1 (+) signal loop (4…20mA) 2 (-) signal loop 3 Not used, can be used as a spare terminal
Voltage drop in 4..20 mA input loop is max 4.8 V. This corresponds 240 ohm loop resistance. When alarms are used (optional) voltage drop is max 7.3 V. Input is secured for reversed polarity and over current tolerance is 100 mA.
Alarm connections, only with model 202 4, 5 Low level alarm, display is lower than alarm level 6, 7 High level alarm, display is higher than alarm level
An example of Manual reset / hold function:
High level alarm is 100 °C and low level -5 °C. When input is over 100 °C, LED A2 lits (relay A2 energized) and it don't go off even if the input goes below 100 °C. It must be resetted manually with front panel key ▼. Alarm will be resetted also if input goes below selected low level (-5°C). That is because both relays cannot be energized at the same time. If You do not want to use this bossibility given by the other alarm, select it's value larger that the scaled range (not in use).
Alarms off
Negative hysteresis value disables alarm function.
➤➤
Dec
➤
➤➤
Decimal selection 0..3, i.e. 0.9, 0.99 or 0.999
Solid state realays,SSR: max. 250 V ±DC/AC, 150 mA, 12 ohm. Isolation between input loop 4 kV.
Alarms can be taken into use by removing jumper inside the case. Voltage drop will increase to 7,3 V.
Measuring mode
This is normal operating mode. Scaled input signal is in display. LED indicators functions are: A1 = Low level indicator A2 = High level indicator Conf = Unit in configuration or calibration mode
Measuring mode can be changed to Configuration mode by pressing simutaneously ▲★-keys. If Access code is used it must be entered when display shows
Code, enter selected button combination.
Configuration mode
Undo, Save
Exit from configuration mode. SAVE saves new configuration and Undo exits without saving.
➤➤
➤
➤➤
➤➤
➤
➤➤
➤➤
➤
➤➤
➤➤
➤
➤➤
1.000 = no filter
0.200 = normal filter
Lo, Hi
Lo and Hi scales display to input signal 4..20 mA. Lo
value is selected for input 4 mA and correspondingly Hi value is for 20 mA input. e.g. 4..20 mA = display Lo -100.. Hi +200
Filt
Display Filter. This fucntion stabiles display value when wide measuring range is used. Filter value can be set between 1 (min) ..0.010 (max).
e.g. 0.2 =(1/5) one new measurement and 4 old values or
0.1 = (1/10) one new + 9 old values (slower) Alarms are controlled with the filtered value (filter affects to alarms reaction time).
Inte
Display intesity (brightness). You can change the intensity with ▲▼-buttons. Hold ▼-key to decrease intensity and vice versa. In measuring mode intensity decreases automatically when input is under 6 mA.
➤➤
➤
➤➤
➤➤
➤
➤➤
AL L, AL H
Alarm levels (L=low, H=high). Both alarms cannot be energized at the same time. Therefore low level cannot have higher value than high alarm and vice versa. If input signal is under 3 mA relays will be de-energized. (Normal open 'NO' relays needs energy to be closed).
ALHy
Alarm hysteresis is number of digits below and above selected alarm level (both sides have same value). Normally alarm relays are enegized when display value goes to alarm level and de-energized when it goes over
hysteresis value. Alarms can also have manual reset when hysteresis value is set larger than measuring range (full span). Manual reset is done with ▼-key from front panel.
➤➤
TrF
➤
➤➤
Transfer function selection. Lin = normal fnction Sqrt = square root function Square root function enables even negative input. This is usefull in cases where e.g. flow goes backwards.
CFCo
Access code for configuration mode. Access code is formed with ▲▼★➤-keys. Code is formed with six pushes of front panel buttons. Not in use when code is set to (★★★★★★) (factory default). If configuration access code is forgotten, all the settings can be returned to factory defaults (not calibration) by holding down buttons ★ and ➤ while connecting input signal 4..20 mA.
7
➤➤
➤
➤➤
Page 8
Calibration
When calibrating, accurate 4 and 20 mA signals are needed. The device is factory supplied calibrated, and it is scaled to display 0-100.0 unless ordered differently.
CAL >
If the device displays incorrect readings (more than
0.05% of range), it should be recalibrated. Before doing that, ensure that the input signal is correct (using a separate mA meter) and that the scaling (Lo, Hi) is appropriate.
Enter configuration menu, select CAL and press ➤ key. Enter calibration password 112213, ▲▲▼▼▲★. “4_20” is displayed.
Feed a precise 4.000 mA signal to the device and press ▼ key. Wait until the display reappears. Then feed 20.000 mA and press ▲ key. Calibration values are stored immediately and cannot be undone.
Finally exit to the configuration menu with ★ key.
Nokeval Oy
Yrittäjäkatu 12 37100 NOKIA, FINLAND Tel. +358 3-342 4800 Fax. +358 3-342 2066
email [email protected] http:// www.nokeval.com
8
Loading...