Noirot 7358-3T, 7358-5T, 7358-7T, 7358-8T Installation Manual

Noirot
Spot Plus
Digital Timer
Electric Convection Panel Heater
In Order To Qualify For Your
Lifetime Warranty
Please Visit our Website and complete the Online Registration
Operating & Installation
Instructions
2 www.noirot.com.au
RECOMMENDATION FOR WALL INSTALLATION
This heater is sold ready for DIY installation, with Wall bracket and flexible cord supplied. To remove the wall bracket from the heater you need to push down on the spring loaded clips located at the top of the bracket. This can be done by using your fingers or, if preferred, a screwdriver (No: 1 Fig.1). Fit the wall bracket to the wall with suitable fixing method according to the surface you mount the heater on (not included). Place the heater on to the bracket and clip into position.
Note: To centre your appliancelaterally on the wall, use the holemarked 2.
Model Height A B C
7358-3T 440 420 208 106 7358-5T 440 580 178 201 7358-7T 440 745 320 210 7358-8T 440 900 405 248
The heater must not be located immediately below a socket outlet (as per requirement of Clause 7.12 of AS/NZS 60335.2.30).
Fig. 1
www.noirot.com.au 3
For maximum efficiency, this heater is to be wall mounted between a minimum height of 100mm and a maximum height of 150mm off the floor. This is to allow the necessary volume of air to flow freely through the vents. It is also important to allow a minimum of 100mm clearance at the top and sides of the heater and 500mm from the front (Fig. 2) so as not to force the air back into the heater and activate the Over Temperature Safety Thermal Cut-Out Switch.
WARNING: IN ORDER TO AVOID
OVERHEATING, DO NOT COVER THE HEATER
If the “Over Temperature Safety Thermal Cut-Out Switch” is activated, the heater will automatically switch off to limit the temperature to a safe value. To reset the thermal cut-out, simply switch the heater off, unplug it from the power point and remove the obstruction(s). Plug the heater back in and switch it on. The thermal cut-out switch will reset after a few minutes and the heater will function normally.
PANEL LOCATIONS
This heater is suitable for use in all rooms including Zone 2 in Bathrooms (Fig.3) in accordance with AS/NZS 3000: 2000 (Wiring Rules). Although this heater is double insulated and does not require earthing, for use in the bathroom it must be located so that the controls cannot be
touched by a person in the bath or shower.
Fig. 3
Fig. 2