Thank youfor purchasing our products!
Please read this manual before using the product.
nJoy is a brand of power and backup protecon products that
create soluons for mulple levels of environment complexity,
This UPS will protect your electronic equipment from physical
damage and will provide emergency baery backup power to
prevent data loss in the event of power problems.
The following models belong to the Balder Series:
1000 VA
residenal to industrial.
Balder 1000
1500 VA
Balder 1500
2000 VA
3000 VA
1
Package contents
UPS unit
Power cord
USB cable
Rack mounng holders
Tower mounng stand
Screws
02
Balder 2000
Balder 3000
User manual
Warranty card
USB cable (only for models
with HID USB communicaon
port).
Page 3
USB
EPO
OUT
RS232
IN
NETWORK/FAX/MODEM
INTELLIGENT SLOT
PROGRAMMABLE
OUTLETS (P1)
OUTPUT
INPUT
10A max.
USB
EPO
OUT
RS232
IN
NETWORK/FAX/MODEM
INTELLIGENTSLOT
PROGRAMMABLE OUTLETS (P1)
OUTPUT
INPUT
2
Product overview
Front View 1000/1500/2000/3000
LCD panel
H
M
S
Vac
Vac
Vdc
Vdc
Hz
Hz
888
888
INPUT
OUTPUT
P1
ON/MUTE
SELECT
OFF/ENTER
Funcon buons
LCD Panel
345
1
8
H
M
S
888
INPUT
Vdc
Hz
Vac
888
OUTPUT
Vdc
Hz
2
Vac
9
English
Română
P1
1. Baery info
2. Load info
3. Backup me info
4. Conguraon and fault info
5. Mute operaon
NOTE!
The HID USB communicaon port port is only available for Balder 1000,
Balder 1500, Balder 2000 and Balder 3000.
76
6. Mode operaon info
7. Programmable outlet info
8. Input and baery voltage info
9. Output info
03
Page 4
NOTE!
Before installaon, please inspect the unit. Be sure that nothing inside the
package is damaged. Keep the original package in a safe place for future use.
Back View
5
7
4
8
1
3
OUT
IN
NETWORK/FAX/MODEM
Balder 1000&1500
4
OUT
IN
NETWORK/FAX/MODEM
Balder 2000
Balder 3000
04
USB
RS232
6
5
USB
RS232
6
EPO
INTELLIGENT SLOT
8
7
8
EPO
INTELLIGENT SLOT
8
7
4
INTELLIGENT
SLOT
OUT
NETWORK/FAX/MODEM
IN
EPO
826 9
10A max.
PROGRAMMABLE
OUTLETS (P1)
9
2
1
10A max.
PROGRAMMABLE
OUTLETS (P1)
9
2
INPUT
OUTPUT
3
INPUT
OUTPUT
3
5
PROGRAMMABLE
OUTLETS (P1)
USB
RS232
1
INPUT
OUTPUT
OUTPUT
Page 5
1. Programable Output
receptacles: connect to non-
crical mission loads (max 10A)
2. General Output receptacles:
connect to crical mission
loads (max 10A)
3. AC input
4. Network/Fax/Modem surge
3
Important Safety Warnings
Please comply with all warnings and operang instrucons in this manual
strictly. Save this manual properly and carefully read the following
instrucons before installing the unit. Do not operate this unit before
reading through all safety informaon and operang instrucons carefully:
Transportaon
protecon
5. USB communicaon port
6. RS-232 communicaon port
7. SNMP intelligent slot
8. Emergency power o funcon
connector (EPO)
9. Connector for baery pack
• Please transport the UPS system only in the original package to
protect against shock and impact.
Preparaon
• Condensaon may occur if the UPS system is moved directly from
cold to warm environment. The UPS system must be absolutely dry
before being installed. Please allow at least two hours for the UPS
system to acclimate to the environment.
• Do not install the UPS system near water or in moist environments.
• Do not install the UPS system where it would be exposed to direct
sunlight or near heat sources.
• Do not block venlaon holes in the UPS housing.
Installaon
• Do not connect appliances or devices which would overload the UPS
system (e.g. laser printers) to the UPS output sockets.
• Place cables in such a way that no one can step on or trip over them.
• Do not connect domesc appliances such as hair dryers to UPS
output sockets.
English
Română
05
Page 6
• The UPS can be operated by any individuals with no previous
experience.
• Connect the UPS system only to an earthed shockproof outlet which
must be easily accessible and close to the UPS system.
• Please use only VDE-tested, CE-marked mains cable (e.g. the mains
cable of your computer) to connect the UPS system to the building
wiring outlet (shockproof outlet).
• Please use only VDE-tested, CE-marked power cables to connect the
loads to the UPS system.
• When installing the equipment, it should ensure that the sum of
the leakage current of the UPS and the connected devices does not
exceed 3.5mA.
Operaon
• Do not disconnect the mains cable on the UPS system or the
building wiring outlet (shockproof socket outlet) during operaons
since this would cancel the protecve earthing of the UPS system
and of all connected loads.
• The UPS system features its own, internal current source (baeries).
The UPS output sockets or output terminals block may be electrically
live even if the UPS system is not connected to the building wiring
outlet.
• In order to fully disconnect the UPS system, rst press the OFF/
Enter buon to disconnect the mains.
• Prevent uids or other foreign objects from entering the inside of the
UPS system.
Maintenance, service and faults
• The UPS system operates with hazardous voltages. Repairs may be
carried out only by qualied maintenance personnel.
• Cauon - risk of electric shock. Even aer the unit is disconnected
from the mains (building wiring outlet), components inside the UPS
system are sll connected to the baery and electrically live and
dangerous.
• Before carrying out any kind of service and/or maintenance,
disconnect the baeries and verify that no current is present and no
06
Page 7
hazardous voltage exists in the terminals of high capability capacitor
such as BUS-capacitors.
• Only persons are adequately familiar with baeries and with the
required precauonary measures may replace baeries and supervise
operaons. Unauthorized persons must be kept well away from the
baeries.
• Cauon - risk of electric shock. The baery circuit is not isolated
from the input voltage. Hazardous voltages may occur between the
baery terminals and the ground. Before touching, please verify that
no voltage is present!
• Baeries may cause electric shock and have a high short-circuit
current. Please take the precauonary measures specied in this
manual and any other measures necessary when working with
baeries: remove wristwatches, rings and other metal objects, use
only tools with insulated grips and handles.
• When changing baeries, install the same number and same type of
baeries.
• Do not aempt to dispose of baeries by burning them. This could
cause baery explosion.
• Do not open or destroy baeries. Escaping electrolyte can cause
injury to the skin and eyes. It may be toxic.
• Please replace the fuse only with the same type and amperage in
order to avoid re hazards.
• Do not dismantle the UPS system.
• WARNING: This is a category C2 UPS product. In a residenal
environment, this product may cause radio interference, in which
case the user may be required to take addional measures. (only for
220/230/240 VAC system).
English
Română
07
Page 8
4
Installaon
4.1 Operang principle
The operang principle of the UPS is shown below:
Input
Dynamic
EMI/RFI
Filters
The UPS is composed of mains input, EMI/RFI lters, recer/PFC,
inverter, baery charger, DC-to-DC converter, baery, dynamic bypass
and UPS output.
The UPS can protect your equipment from all power problems such as
surges, spikes, blackouts, brownouts and line noise. When AC power is
present and the ON/ Mute switch is turned ON, the UPS will provide
pure and stable AC power to the output. The UPS will also charge the
baery in the on-line mode.
Recer
/PFC
Baery
Charger
Bypass
DC-to-DC
converter
Baery
Output
Inverter
08
Page 9
4.2 Connecng your equipment and rst usage
The UPS is simple to install and operate. Please read the following steps
before connecng any equipments to this UPS:
Step 1.Connecng the baeries: For safety consideraon, the UPS is
shipped out from factory without connecng the baery wires. To reconnect baery wires please follow below steps:
I. Remove front panel
II. Connect the AC input and reconnect baery wires.
III. Put the front panel back to
the unit.
English
Română
09
Page 10
Step 2.Connect to External Baery Cabinet: When connecng external
baery cabinet, please be sure to connect polarity correctly. Connect
posive pole of baery cabinet to posive pole of external baery
connector in UPS and negave pole of baery cabinet to negave pole
of external baery connector in UPS. Polarity mis-connecon will cause
UPS internal fault.
Connect only compable Balder baery cabinet provided by nJoy. Please
read the manual of the UPS and baery cabinet and set the UPS baery
total capacity in Ah and the charging current accordingly. The use of
another baery cabinet may damage the UPS and void the warranty.
OUT
IN
NETWORK/FAX/MODEM
Max, 50A
BATETRY BREAKER
USB
EPO
RS232
INTELLIGENT SLOT
10A max.
PROGRAMMABLE
OUTLETS (P1)
NOTE!
These baery cabinets care compable with the following UPS:
• CA0312GX-AZ (36Vdc): UPS Balder 1000 / 1500
• CA0712GX-AZ (72Vdc): UPS Balder 2000 / 3000
10
INPUT
OUTPUT
Page 11
Step 3. Mounng the UPS: Balder series UPS can be either displayed on
the desk or mounted in the 19” rack chassis. Please choose your favourite
way to posion this UPS.
A. Rack - mount installaon
First x the holders of the rack on the UPS.
Then x the UPS on the rack through the holders
B. Tower installaon
English
Română
First x the holders to t
the UPS.
Then put the UPS in place.
11
Page 12
Step 4. UPS input connecon: Plug the UPS into a two-pole, three-wire,
grounded receptacle only. Avoid using extension cords.
Step 5. UPS output connecon:
of output: programmable outlets and general outlets. Please connect noncrical devices to the programmable outlets and crical devices to the
general outlets. During power failure, you may extend the backup me
to crical devices by seng shorter backup me for non crical devices.
For socket-type outputs there two kinds
CAUTION
Do NOT plug LASER
PRINTERS into any of
the outlets.
Step 6. Communicaon connecon: To allow for unaended UPS
shutdown/start-up and status monitoring, connect the communicaon
cable one end to the USB/RS-232 port and the other to the communicaon
port of your PC. With the monitoring soware installed, you can schedule
UPS shutdown/start-up and monitor UPS status through PC. The UPS is
equipped with a slot for either SNMP or AS400 card. When installing either
SNMP or AS400 card in the UPS, it will provide advanced communicaon
and monitoring opons.
Communication port:
USB PortRS-232 PortIntelligent slot
Do NOT plug any SURGE STRIPS into any of the
outlets.
NOTE!
USB port and RS-232 port can’t work at the same me.
12
Page 13
Step 7. Network connecon: Connect a single modem/phone/fax line
into surge-protected “IN” outlet on the back panel of the UPS unit.
Connect from “OUT” outlet to the equipment with another modem/fax/
phone line cable.
Network/Fax/Phone surge port:
Step 8. Disable and enable EPO funcon: Keep the pin 1 and pin 2 closed
for UPS normal operaon.
It’s in closed status for UPS
normal operaon.
Step 9. Turn on the UPS:
for two seconds to power on the UPS.
Press the ON/Mute buon on the front panel
To acvate EPO
funcon, remove
these two screws.
NOTE!
The baery charges fully during the rst ve hours of normal operaon. Do
not expect full baery run capability during this inial charge period.
Step 10. Install soware: For opmal computer system protecon, install
UPS monitoring soware to fully congure UPS shutdown. Use supplied
RS-232 or USB communicaon cable to connect RS-232/USB port of
UPS and RS-232/USB port of PC. Install the UPS monitoring soware
from hps://www.power-soware-download.com/viewpower.html to fully
congure UPS shutdown.
13
English
Română
Page 14
5
Operaons
5.1 Buon operaons
ON/MUTE
ON/Mute Buon
• Turn on the UPS: Press and hold ON/Mute buon for at least 2 sec-
onds to turn on the UPS.
• Mute the alarm: Aer the UPS is turned on in baery mode, press
and hold this buon for at least 5 seconds to disable or enable the
alarm system. But it’s not applied to the situaons when warnings or
errors occur.
• Up key: Press this buon to display previous selecon in UPS seng
mode.
• Switch to UPS self-test mode: Press ON/Mute buons simultane-
ously for 5 seconds to enter UPS self-tesng while in AC mode, ECO
mode, or converter mode.
OFF/Enter Buon
• Turn o the UPS: Press and hold this buon for at least 2 seconds
to turn o the UPS. The UPS will be in standby mode under normal
power or transfer to Bypass mode if the Bypass seng is enabled.
• Conrm selecon key: Press this buon to conrm selecon in UPS
sengs mode.
Select Buon
• Switch LCD message: Press this buon to change the LCD message
for input voltage, input frequency, baery voltage, output voltage
and output frequency.
• Sengs mode: Press and hold this buon for 5 seconds to enter
UPS sengs mode when the UPS is in standby mode or bypass
mode.
• Down key: Press this buon to display next selecon in UPS sengs
mode.
SELECT
OFF/ENTER
14
Page 15
ON/Mute + Select Buon
• Switch to bypass mode: When the main power is normal, press ON/
Mute and Select buons simultaneously for 5 seconds. Then the
UPS will enter to bypass mode. This acon will be ineecve when
the input voltage is out of acceptable range.
5.2 LCD Panel Indicators
H
M
S
888
INPUT
Vac
Vdc
Hz
888
OUTPUT
Vac
Vdc
Hz
P1
DisplayFuncon
Backup me informaon
H
M
S
Indicates the esmated backup me.
H: hours, M: minute, S: second.
Conguraon and fault informaon
Indicates the conguraon items, and the conguraon
items are listed in details in secon 5.5.
Indicates the warning and fault codes, and the codes are
listed in details in secon 5.7 and 5.8.
Mute operaon
English
Română
Indicates that the UPS alarm is disabled.
15
Page 16
Output & Load informaon
Vac
Indicates the output voltage and output frequency.
Vdc
P1
Hz
Vac: AC voltage, Vdc: DC voltage, Hz: frequency
Indicates the load level by 0-24%, 25-49%, 50-74% and
75-100%.
Indicates overload.
Indicates the load or the UPS output is short circuit.
Indicates that programmable management outlets are
working.
Indicates the UPS connects to the mains.
Indicates the baery is working.
Indicates the bypass circuit is working.
888
OUTPUT
Load informaon
Programmable outlets informaon
Mode operaon informaon
16
Indicates the ECO mode is enabled.
Indicates the AC to DC circuit is working.
Page 17
Baery informaon
Indicates the inverter circuit is working.
Indicates the output is working.
Indicates the baery level by 0-24%, 25-49%, 50-74%,
and 75-100%.
Indicates the baery is fault.
Indicates low baery level and low baery voltage.
Input & baery informaon
Indicate the input voltage, input frequency and baery
voltage.
Vac: AC voltage, Vdc: DC voltage, Hz: frequency
5.3 Audible Alarm Indicators
ModeAlarm
Baery Mode Sounding every 5 seconds
Low BaerySounding every 2 seconds
OverloadSounding every second
FaultConnuously sounding
Bypass ModeSounding every 10 seconds
English
Română
17
Page 18
5.4 LCD display wordings index
AbbreviaonDisplay contentMeaning
ENA
DIS
ESC
HLS
LLS
BAT
BAH
CHA
CBV
CFV
EPO
AO
AC
OIT
EAT
RAT
CF
ENA
d15
ESC
HLS
LLS
bAT
bAH
CHA
Cbu
CFu
EPO
AO
AC
OIt
EAt
rAt
CF
Enable
Disable
Escape
High loss
Low loss
Baery
Baery AH
Charger current
Charger boost voltage
Charger oat voltage
EPO
Acve open
Acve close
Output isolaon
transformer
Esmated autonomy me
Running autonomy me
Converter
18
Page 19
ON
SD
OI
TP
CH
FU
BR
EE
OK
BL
OL
NC
OC
SF
BF
BV
ON
Sd
OI
TP
CH
FU
br
EE
0K
bL
OL
NC
OC
SF
bF
bv
ON
Shutdown
Over input current
Temperature
Charger
Bypass frequency
unstable
Baery
Replacement
EEPROM error
OK
Baery Low
Over Load
Baery No Connect
Over Charge
Site wiring fault
Baery Fault
Bypass Out Range
English
Română
19
Page 20
888 888
5.5 UPS sengs
1
2
3
NOTE!
Most parameters can be set only in bypass/standby mode; please set the UPS
to bypass/standby mode (see secon 5.1) and then change parameters.
There are two parameters to set up the UPS.
• Parameter 1: For program alternaves. Refer to the table below.
• Parameter 2&3: The sengs opons or values for each program.
InterfaceSengs
01: Output voltage sengs
Parameter 2: Output voltage:
200: presents output voltage is 200Vac
208: present output voltage is 208Vac
Vac
230
OUTPUT
220: present output voltage is 220Vac
230: present output voltage is 230Vac
240: present output voltage is 240Vac
voltage point and low voltage point for ECO
mode by pressing Down key or Up key.
HLS: High loss voltage in ECO mode in
parameter 2.
The seng range in parameter 3 is from +7V
230
Vac
to +24V of the nominal voltage. (Default:
+12V)
LLS: Low loss voltage in ECO mode in
parameter 2.
The seng range in parameter 3 is from -7V
to -24V of the nominal voltage.
(Default: -12V)
HLS
INPUT
06: Bypass enable/disable when UPS is o
Parameter 2: Enable or disable Bypass
ENA
funcon. You may choose the following two
opons:
ENA: Bypass enable
DIS: Bypass disable (Default)
English
Română
21
Page 22
07: Bypass voltage range seng
Parameter 2: Set the acceptable high voltage
point and acceptable low voltage point for
Bypass mode by pressing the Down key or
Up key.
HLS: Bypass high voltage point
260
Vac
230-264: seng the high voltage point in
parameter 3 from 230Vac to 264Vac. (Default:
264Vac)
LLS: Bypass low voltage point
170-220: seng the low voltage point in
parameter 3 from 170Vac to 220Vac. (Default:
170Vac)
HLS
INPUT
08: Bypass frequency range seng
Parameter 2: Set the acceptable high frequency point and acceptable low frequency
point for Bypass mode by pressing the
Down key or Up key.
530
Hz
HLS: Bypass high frequency point
51-55Hz: seng the frequency high loss
point from 51Hz to 55HZ(Default: 53.0Hz).
LLS: Bypass low Frequency point
45-49Hz: seng the frequency low loss point
from 45Hz to 49HZ(Default: 47.0Hz)
HLS
INPUT
09: Programmable outlets enable/disable
Parameter 2: Enable or disable the program-
dIS
P1
mable outlets funcon.
You may choose the following two opons:
Parameter 2: Set up backup me limits for
programmable outlets.
0-999: seng the backup me limits in
minutes from 0-999 for programmable
outlets which connect to non-crical
devices on baery mode. (Default: 999).
11: Autonomy limitaon seng
Parameter 2: Set up backup me on baery
mode for general outlets.
M
999
0-999: seng the backup me in minutes from
0-999 for general outlets on ba. mode.
DIS: Disable the autonomy limitaon and
the backup me will depend on baery
capacity. (Default)
NOTE: When seng as “0”, the backup me
will be only 10 seconds.
12: Baery total AH seng
Parameter 2: Set up the baery total AH of
the UPS.
7-999: seng the baery total capacity
from 7-999 in AH. Please set the correct
baery total capacity if external baery
bAH 7
bank is connected.
EXAMPLE:
with one baery cabinet with 6 pcs of
HR09122F baeries (two strings of 3
baeries), total baery AH seng will
be: 9AH (UPS baery string capacity) +
2xHR09122F (2 strings of HR09122F
baeries inside baery cabinet) = 23AH
13: Maximum charger current seng
English
Română
if you use Balder 1500 together
CHA
If you use external baery pack please set
the appropriate charging current based
on baery capacity used. Please use the
following table as reference:
23
Page 24
Battery capacity(AH)
NOTE: If you connect Baery Pack 2U for
Balder 1500 to Balder 1500 you should set
maximum charger current to 4A.
If you connect Baery Pack 2U for Balder
3000 to Balder 3000 you should set maximum
charger current to 4A.
14: Charger Boost voltage seng
Parameter 2: Set up the charger boost
voltage.
Cbu 23 6
Vdc
2.25-2.40: seng the charger boost voltage
from 2.25 V/cell to 2.40V/cell. (Default:
2.36V/cell)
15: Charger Float voltage seng
Parameter 2: Set up the charger oat
voltage.
2.20-2.33: seng the charger oat voltage
CFu 22 8
Vdc
from 2.20 V/cell to 2.33V/cell. (Default:
2.28V/cell)
NOTE: Parameters 14 and 15 should be set
based on baeries specicaons.
16: EPO logic seng
Parameter 2: Set up the EPO funcon
control logic.
AO: Acve Open (Default). When AO is
EPO AO
selected as EPO logic, it will acvate EPO
funcon with Pin 1 and Pin 2 in open status.
AC: Acve Close. When AC is selected as
EPO logic, it will acvate EPO funcon with
Pin 1 and Pin 2 in close status.
Parameter 2: Allow or disallow external
output isolaon transformer connecon.
dI S
ENA: If selected, it’s allowed to connect to
an external output isolaon transformer.
DIS: If selected, it’s not allowed to connect
to external output isolaon transformer.
(Default)
18: Display seng for autonomy me
Parameter 2: Set up the display seng for
autonomy me
Vac
EAT: If EAT is selected, it will display the
remaining autonomy me. (Default)
RAT: If RAT is selected, it will show
accumulated autonomy me so far.
19: Acceptable input voltage range seng
Parameter 2: Set the acceptable high
voltage point and acceptable low voltage
point for input voltage range by pressing the
Down key or Up key.
HLS: Input high voltage point
300
Vac
280/290/300: seng the high voltage point
in parameter 2. (Default: 300Vac)
LLS: Bypass low voltage point
110/120/130/140/150/160: seng the
low voltage point in parameter 2. (Default:
110Vac)
HLS
INPUT
00: Exit seng
English
Română
ESC
Exit the seng mode.
25
Page 26
5.6 Operang mode descripon
Operang mode DescriponLCD display
When the input voltage is
within acceptable range,
Online mode
ECO mode
Frequency
Converter mode
Baery mode
Bypass mode
UPS will provide pure
and stable AC power to
output. The UPS will also
charge the baery in
online mode.
Energy saving mode:
When the input voltage is
within voltage regulaon
range, UPS will bypass
voltage to output for
energy saving. The UPS
will also charge the
baery at ECO mode.
When input frequency is
within 40 Hz to 70 Hz,
the UPS can be set at a
constant output frequency,
50 Hz or 60 Hz. The UPS
will sll charge baery
under this mode. The
capacity of the UPS should
be derated to 80% when
Frequency Converter
mode is enabled.
When the input voltage
is beyond the acceptable
range or power failure, the
UPS will backup power
from baery and alarm is
sounding every 5 seconds.
When input voltage is
within acceptable range
but UPS is overload, UPS
will enter bypass mode
or bypass mode can be
set by front panel. Alarm
is sounding every 10
seconds.
230
INPUT
230
INPUT
230
INPUT
720
INPUT
230
INPUT
Vac
Vac
Vac
Vdc
Vac
230
OUTPUT
230
OUTPUT
230
OUTPUT
230
OUTPUT
230
OUTPUT
Vac
P1
Vac
P1
Vac
P1
Vac
P1
Vac
P1
26
Page 27
Standby mode
UPS is powered o and
there is no output supply
power, but the UPS sll
can charge baeries.
230
INPUT
Vac
Vac
0
OUTPUT
Fault mode
When a fault has
occurred, the ERROR icon
and the fault code will be
displayed.
Vac
INPUT
5.7 Faults Reference Code
Fault eventFault codeIcon
Bus start fail01-
Bus over02-
Bus under03-
Inverter so start fail11-
Inverter voltage high12-
Inverter voltage Low13-
Inverter output short14
Baery voltage too high27
Baery voltage too low28
Charger output short2A-
Over temperature41-
Overload43
Charger failure45-
Over input current49-
Vac
0
OUTPUT
English
Română
27
Page 28
5.8 Warning indicator
Warning
Low Baery
Overload
Over input current
Baery is not
connected
Over Charge
Site wiring fault
EPO enable
Over temperature
Charger failure
Baery fault
Out of bypass voltage
range
Bypass frequency
unstable
Baery replacement
EEPROM error
NOTE!
“Site Wiring Fault” funcon can be enabled/disabled via soware. Please
check soware manual for the details.
Icon
(ashing)
BYPASS
CodeAlarm
Sounding every 2
seconds
Sounding every
second
Sounding 2 beep
OI
every 10 seconds
Sounding every 2
seconds
Sounding every 2
seconds
Sounding every 2
seconds
Sounding every 2
EP
seconds
Sounding every 2
TP
seconds
Sounding every 2
CH
seconds
Sounding every 2
seconds
Sounding every 2
seconds
Sounding every 2
FU
seconds
Sounding every 2
br
seconds
Sounding every 2
EE
seconds
28
Page 29
6
Replacing the baery
NOTE!
This UPS is equipped with internal baeries. When your baery lifeme is
over you can replace them without shung down the UPS or connected loads
thanks to the hot-swappable baery design. Replacement is a safe procedure,
isolated from electrical hazards.
CAUTION
Consider all warnings, cautions, and notes before replacing the
batteries.
Step 1. Remove front panel.
Step 3. Pull out the baery box
by removing the two screws on
the front panel.
Step 2. Disconnect baery wires.
English
Română
Step 4. Remove the top cover of
baery box and replace the
inside baeries following the
baery kit assembly procedure.
29
Page 30
Step 5. Aer replacing the
baeries, put the baery box
back to original locaon and
screw it ghtly.
Step 6. Re-connect the baery
wires and put the front panel
back to the unit.
30
Page 31
6.1 Baery kit assemly procedure
Balder 1000 / 1500
Step 1. Remove adhesive tapes.
Tapes
Tapes
Step 3. Put assembled baery
packs on one side of plasc
shells.
Step 2. Connect all baery
terminals by following below
chart.
English
Step 4. Cover the other side of
plasc shell as in the below
picture.
Română
31
Page 32
Balder 2000 / 3000
Step 1. Remove adhesive tapes.
Step 3. Put assembled baery
packs on one side of plasc
shells.
Step 2. Connect all baery terminals
by following below chart.
Step 4. Cover the other side of plasc
shell as in the below picture.
32
Page 33
7
Troubleshoong
ProblemPossible causeSoluons
Check if input
power cord is
rmly connected
to the mains.
Plug the AC input
power cord to the
AC input correctly.
Set the circuit in
closed posion
to disable EPO
funcon.
Rotate mains
power socket by
180˚ and then
connect to UPS
system.
Check if all
baeries are
connected well.
Contact service
unit.
No indicaon and alarm even
though the main is normal.
The icon
code EP are ashing on LCD
display and alarm is sounding
every second.
The icon
warning code SF are ashing
on LCD display. Alarm is
sounding every 2 seconds.
The icon
warning code NC are ashing
on LCD display. Alarm is
sounding every 2 seconds.
Fault code is shown as 27
and the icon
on LCD display and alarm is
connuously sounding.
and the warning
and the
and and
is lighng
The AC input
power is not
connected well.
The AC input is
connected to the
UPS output.
EPO funcon is
acvated.
Line and neutral
conductors of UPS
input are reversed.
The external or
internal baery
is incorrectly
connected.
Baery voltage
is too high or the
charger is fault.
English
Română
Fault code is shown as 28
and the icon
on LCD display and alarm is
connuously sounding.
is lighng
Baery voltage
is too low or the
charger is fault.
Contact service
unit.
33
Page 34
UPS is overloaded.
The icon and
are ashing on LCD display.
Alarm is sounding every
second.
Fault code is shown as 49
on LCD display and alarm is
connuously sounding.
Fault code is shown as 43
and the icon
on LCD display. Alarm is
connuously sounding.
Fault code is shown as 14 and
the icon
on LCD display and alarm is
connuously sounding.
is lighng
is lighng
UPS is overloaded.
Devices connected
to the UPS are
fed directly by the
electrical network
via the Bypass.
Aer repeve
overloads, the
UPS is locked in
the Bypass mode.
Connected devices
are fed directly by
the mains.
UPS is over input
current.
The UPS
shut down
automacally
because of
overload at the
UPS output.
The UPS
shut down
automacally
because short
circuit occurs on
the UPS output.
Remove excess
loads from UPS
output.
Remove excess
loads from UPS
output rst. Then
shut down the
UPS and restart it.
Remove excess
loads from UPS
output.
Remove excess
loads from UPS
output and restart
it.
Check output
wiring and if
connected devices
are in short circuit
status.
34
Page 35
Fault code is shown as 01,
02, 03, 11, 12, 13 and 41
on LCD display and alarm is
connuously sounding.
Baery backup me is shorter
than nominal value.
Fault code is shown as 2A
on LCD display and alarm is
connuously sounding.
A UPS internal
fault has occurred.
There are two
possible results:
1. The load is
sll supplied, but
directly from AC
power via bypass.
2. The load is no
longer supplied by
power.
Baeries are not
fully charged.
Baeries defect.
The short circuit
occurs on the
charger output.
Contact service
unit.
Charge the
baeries for at
least 5 hours
and then check
capacity. If the
problem sll
persists, consult
your dealer.
Contact your
dealer to replace
the baery or
replace them by
yourself.
Check if
baery wiring
of connected
external pack is
in short circuit
status.
English
Română
Fault code is shown as 45
on LCD display. At the same
me, alarm is connuously
sounding.
The charger does
not have output
and baery
voltage is less than
10V/PC.
Contact service
unit.
35
Page 36
Disposal of Old Electrical & Electronic Equipment
(Applicable in the European Union and other European countries with
separate collecon systems)
This symbol on the product or on its packaging indicates that this product shall not be
treated as household waste.
Instead it shall be handed over to the applicable collecon point for the recycling of
electrical and electronic equipment.
By ensuring this product is disposed of correctly, you will help prevent potenal
negave consequences for the environment and human health, which could otherwise
be caused by inappropriate waste handling of this product.
The recycling of materials will help to conserve natural resources.
36
Page 37
Multumim pentru ca a ales produsele noastre!
Va rugam ci cu atene manualul de ulizare inainte de a pune in
nJoy este un brand de solui UPS dedicate protecei si rezervei de
energie din diferite medii de ulizare, de la rezidenal la industrial
UPS-ul va protejeaza echipamentele electronice de daune zice
si ofera o baterie de rezerva pentru a preveni pierderile de date in
cazul intreruperilor accidentale ale energiei electrice.
funcune acest produs.
Din seria Balder fac parte urmatoarele modele:
1000 VA
1500 VA
2000 VA
3000 VA
1
Connutul pachetului
UPS
Cablu de alimentare
Cablu USB
Supor pentru montarea
in rack
Balder 1000
Balder 1500
Balder 2000
Balder 3000
Suport pentru montarea
Suruburi
Cablu USB (doar
pentru modelele cu port de
comunicare HID USB)
English
Română
pe vercala
37
Page 38
USB
EPO
OUT
RS232
IN
NETWORK/FAX/MODEM
INTELLIGENT SLOT
PROGRAMMABLE
OUTLETS (P1)
OUTPUT
INPUT
10A max.
USB
EPO
OUT
RS232
IN
NETWORK/FAX/MODEM
INTELLIGENTSLOT
PROGRAMMABLE OUTLETS (P1)
OUTPUT
INPUT
2
Prezentarea produsului
Vedere din fata 1000/1500/2000/3000
Ecran LCD
Ecran LCD
345
Butoane
H
M
S
Vac
Vac
Vdc
Vdc
Hz
Hz
888
888
INPUT
OUTPUT
P1
ON/MUTE
SELECT
OFF/ENTER
1
8
H
M
S
888
INPUT
Vdc
Hz
Vac
888
OUTPUT
Vdc
Hz
2
Vac
9
P1
1. Informai si nivel baterie
2. Informai si nivel incarcare
3. Informai mp de backup
4. Erori si congurai
5. Modul "Mute"
NOTA!
Inainte de instalare inspecta unitatea. Fi siguri ca nimic din interiorul
pachetului nu este stricat. Tine pachetul original intr-un loc sigur pentru o
76
6. Informai mod operare
7. Informai prize programabile
8. Informai tensiune de intrare
si stare baterie
9. Informai tensiune de iesire
ulizare ulterioara.
38
Page 39
NOTA!
Portul HID USB este disponibil doar pentru modelele Balder 1000, Balder
1500, Balder 2000 and Balder 3000.
Vedere din spate
5
7
4
8
1
3
OUT
IN
NETWORK/FAX/MODEM
Balder 1000&1500
4
OUT
IN
NETWORK/FAX/MODEM
Balder 2000
Balder 3000
USB
RS232
6
5
USB
RS232
6
EPO
INTELLIGENT SLOT
8
7
8
EPO
INTELLIGENT SLOT
8
7
4
INTELLIGENT
SLOT
OUT
NETWORK/FAX/MODEM
IN
EPO
826 9
10A max.
PROGRAMMABLE
OUTLETS (P1)
9
2
INPUT
OUTPUT
English
10A max.
PROGRAMMABLE
OUTLETS (P1)
1
3
INPUT
OUTPUT
Română
9
5
PROGRAMMABLE
OUTLETS (P1)
USB
RS232
2
3
1
INPUT
OUTPUT
OUTPUT
39
Page 40
1. Prize de iesire programabile
desnate echipamentelor noncrice (max 10A)
2. Prize de iesire programabile
desnate echipamentelor
crice (max 10A)
3. Alimentare AC
4. Priza protece supratensiune
3
Averzari de siguranta
Va rugam sa respecta toate aversmentele si instrucunile de ulizare
din acest manual. Pastra acest manual in mod corespunzator si ci
cu atene urmatoarele instrucuni inainte de instalarea aparatului. Nu
folosi aceasta unitate inainte de a ci toate instrucunile de siguranta si
de ulizare cu atene:
Transport
• Va rugam sa transporta sistemul UPS numai in ambalajul original
pentru a-l proteja impotriva socurilor.
Pregare
• Condensul poate aparea daca sistemul UPS este mutat dintr-un
mediu rece in unul cald. Sistemul UPS trebuie sa e uscat inainte de
a instalat. Va rugam sa aloca cel pun doua ore pentru ca sistemul
UPS sa se aclimazeze cu mediul unde dori sa il instala.
• Nu instala sistemul UPS langa apa sau in medii umede.
• Nu instala sistemul UPS acolo unde ar expus la lumina directa a
soarelui sau in apropierea surselor de incalzire.
• Nu bloca oriciile de venlae ale carcasei UPS-ului.
Instalare
• Nu conecta aparate sau dispozive care ar suprasolicita sistemul
UPS (de exemplu: imprimantele laser) la mufele de iesire UPS.
• Instala cablurile in asa fel incat nimeni sa nu calce pe ele.
• Nu conecta aparate de uz casnic, cum ar uscatoare de par la
prizele de iesire UPS.
pentru Retea / Fax / Modem
5. Port comunicare USB
6. Port comunicare RS-232
7. Slot pentru cardul SNMP
8. Conector pentru funca EPO
(oprire de urgenta)
9. Conector pentru cabinetul de
baterii
40
Page 41
• UPS-ul poate folosit de orice persoana, fara a necesita nicio
experienta anterioara.
• Conecta sistemul UPS numai la o priza cu impamantare, care
trebuie sa e usor accesibila si aproape de sistemul UPS.
• Va rugam sa folosi numai cabluri de alimentare testate VDE si cu
marcaj CE (de exemplu: cablul de alimentare de la computer) pentru a
conecta sistemul UPS la reteaua electrica a cladirii.
• Va rugam sa folosi numai cabluri de alimentare testate VDE si cu
marcaj CE pentru a conecta sarcinile la sistemul UPS.
• La instalarea echipamentului, trebuie sa va asigura ca totalul
curentului de scurgere al UPS si al dispozivelor conectate nu
depaseste 3,5 mA.
Operare
• Nu deconecta cablul de alimentare de la sistemul UPS sau de
la priza cladirii in mpul ulizarii, deoarece acest lucru ar anula
impamantarea de protece a sistemului UPS si a tuturor sarcinilor
conectate.
• Sistemul UPS are propria sursa de curent intern (baterii). Prizele de
iesire sau terminale de iesire pe categorii pot incarcate electric,
chiar daca sistemul UPS nu este conectat la sistemul electric al
cladirii.
• Pentru a deconecta complet sistemul UPS, apasa intai butonul
OFF/Enter pentru a deconecta sursa de alimentare.
• Nu lasa sa ajunga in interiorul unitai UPS niciun obiect strain sau
lichide.
Intrenere, Service si Defecte
• Sistemul UPS funconeaza cu tensiuni periculoase. Reparaile pot
efectuate numai de catre personalul de intrenere calicat.
• Atene - risc de soc electric. Chiar si dupa ce aparatul este
deconectat de la reteaua electrica, componentele din interiorul
sistemului UPS sunt inca conectate la baterie si sunt incarcate
electric si periculoase.
• Inainte de a efectua orice fel de service si / sau intrenere,
deconecta bateriile si verica sa nu existe curent sau tensiune
periculoasa in terminalele condensatorului de mare capacitate, cum
English
Română
41
Page 42
ar condensatorul BUS.
• Numai persoanele care sunt familiarizate in mod adecvat cu baterii si
cu masurile de precaue necesare pot inlocui bateriile si supraveghea
operaunile. Persoane neautorizate trebuie sa e nute departe de
baterii sistemului UPS.
• Atene - risc de soc electric. Circuitul bateriei nu este izolat de
tensiunea de intrare. Tensiuni periculoase pot aparea intre bornele
bateriei si pamant. Inainte de a ange, va rugam sa verica ca nu
exista tensiune!
• Bateriile pot provoca soc electric. Va rugam sa lua masurile de
precaue specicate mai jos, precum si orice alte masuri necesare
atunci cand se lucreaza cu bateriile sistemului: da-va jos ceasurile
de mana, inelele si alte obiecte metalice si folosi doar instrumente
cu manere izolate.
• La schimbarea bateriilor, instala acelasi numar si acelasi p de
baterii.
• Nu incerca sa distruge bateriile prin arderea lor. Acest lucru poate
cauza explozia bateriilor.
• Nu deschide sau distruge bateriile. Scurgerea de electrolit poate
provoca leziuni la nivelul pielii si ochilor, totodata acesta este foarte
toxic.
• Va rugam sa inlocui siguranta numai cu acelasi p de siguranta si
amperaj pentru a evita pericolele de incendiu.
• Nu dezasambla sistemul UPS.
• ATENTIE: Acesta este un produs din categoria C2. Intr-un mediu
rezidenal, poate cauza interferente radio, caz in care ulizatorul
este rugat sa ia masuri suplimentare!
42
Page 43
4
Instalare
4.1 Principiu de funconare
Principiul de funconare a acestui UPS este urmatorul:
Input
Dynamic
EMI/RFI
Filters
Sursa neintrerupbila de tensiune are in componenta sa: intrarea de
la retea, ltrele pentru EMI / RFI (interferente electromagnece /
interferente radio-frecventa), redresorul si PFC (coreca factorului de
putere), incarcatorul bateriilor, bateriile, convertorul DC-DC (tensiune
connua la tensiune connua), invertorul, bypassul dinamic si iesirea
sursei neintrerupbile de tensiune.
UPS-ul va poate proteja echipamentul de toate problemele legate de
tensiunea electrica cum ar : suprasarcini, uctuai de tensiune, caderi de
tensiune si zgomotul de pe retea. Cand curentul este prezent la reteaua
de alimentare si comutatorul (ON/Mute) este pornit (ON) UPS-ul isi
incarca bateria si asigura echipamentului energia necesara funconarii
direct de la retea.
Recer
/PFC
Baery
Charger
Bypass
DC-to-DC
converter
Baery
Output
Inverter
43
English
Română
Page 44
4.2 Conectarea echipamentelor si prima folosire
UPS-ul este simplu de folosit si de instalat. Urma pasii de mai jos inainte
de a conecta echipamentul la UPS:
Pasul 1.Conecta bateriile: Pentru masuri de siguranta, UPS-ul este livrat
fara sa aiba conectate cablurile bateriei. Pentru a reconecta aceste cabluri
va rugam sa urma pasi de mai jos:
I. Detasa panoul frontal.
II. Conecta alimentarea si
reconecta cablurile bateriei.
III. Pune panoul frontal la loc.
44
Page 45
Pasul 2.Conectare cabinet de baterii extern: Atunci cand conecta UPSul la un cabinet de baterii extern asigura-va ca polaritatea este corecta
(polul poziv al cabinetului de baterii la polul poziv al conectarii la UPS si
polul negav al cabinetului de baterii la polul negav al conectarii la UPS).
Polaritatea inversata va aduce daune UPS-ului.
Folosi doar cabinete de baterii nJoy compabile cu seria Balder.
Va rugam sa ci manualul de ulizare al UPS-ului si al cabinetelor de
baterii si sa seta valoarea capacitai totale a bateriilor in Ah si curentul
de incarcare in consecinta. Folosirea altor cabinete de baterii poate duce
OUT
IN
NETWORK/FAX/MODEM
Max, 50A
BATETRY BREAKER
USB
EPO
RS232
INTELLIGENT SLOT
10A max.
PROGRAMMABLE
OUTLETS (P1)
NOTA!
Cabinetele de baterii sunt compabile cu urmatoarele modele:
• CA0312GX-AZ (36Vdc): UPS Balder 1000 / 1500
• CA0712GX-AZ (72Vdc): UPS Balder 2000 / 3000
OUTPUT
INPUT
English
Română
45
Page 46
la deteriorarea UPS-ului si la pierderea garanei.
Pasul 3.Montarea UPS-ului: Acest model de UPS poate sa e pozionat
e vercal e orizontal - montat intr-o carcasa rack de 19”. Va rugam sa
alege pozia in care dori sa poziona UPS.
A. Montarea in Rack:
Intai xa supori rack-ului pe UPS.
Apoi xa UPS-ul pe rack cu ajutorul suruburilor.
B. Montarea vercala
Fixa supori pentru a
susne UPS-ul.
46
Apoi xa UPS-ul.
Page 47
Pasul 4. Conexiune de intrare UPS: Conecta UPS-ul la priza tripolara,
impamantata. Nu uliza prelungitoare.
Pasul 5. Conexiune de iesire UPS:
variante: prize programabile si prize generale. Conecta dispozivele
non-crice la prizele programabile si dispozivele crice la prizele
generale. In mpul unei caderi de curent, pute exnde mpul de backup
la dispozivele crice, setand un mp mai scurt de backup pentru
dispozivele non-crice.
Pentru iesirile de p priza exista doua
ATENTIE
NU conectati
imprimante laser la
nici una din prizele
UPS-ului.
NU conectati alte
ACCESORII CU
PROTECTIE la niciuna
din prize.
Pasul 6. Conexiunea de comunicare: Pentru a permite oprirea/pornirea
nesupravegheata a UPS-ului si monitorizarea starii acestuia, conecta un
capat al cablului de comunicare la portul USB/RS-232 si celalalt la portul
de comunicare al PC-ului. Cu soware-ul de monitorizare instalat, pute
programa oprirea si pornirea UPS-ului si sa monitoriza starea UPS prin
intermediul PC-ului. UPS-ul este echipat cu un slot inteligent, perfect
pentru card SNMP sau AS400. Cand instala cardul SNMP sau AS400 in
UPS, ve obne opuni de comunicare si monitorizare avansata.
Port de comunicare
Port USBPort RS-232Slot inteligent
NOTA!
Porturile USB si RS-232 nu pot funcona in acelasi mp.
47
English
Română
Page 48
Pasul 7. Conexiunea in retea: Conecta o linie de modem/telefon/fax in
priza protejata IN ce se aa in spatele UPS-ului. Conecta in priza OUT
echipamentul cu o alta linie de modem/telefon/fax.
Port Retea/Fax/Telefon:
Pasul 8. Acva si dezacva funca EPO: Tine pin-ul 1 si 2 inchisi
pentru modul de operare normal al UPS-ului. Pentru a acva
funca EPO taia cablul dintre pin 1 si pin 2.
Pentru modul de operare
normala conectorul este in
stare inchisa.
Pasul 9. Pornirea UPS-ului:
pentru cel pun 2 secunde pentru a porni UPS-ul.
Apasa si ne apasat butonul ON / Mute
Pentru a acva funca
EPO inlatura cele
doua suruburi.
NOTA!
Bateria se incarca complet in decursul primelor cinci ore de funconare
normala. In aceasta perioada de incarcare iniala bateria nu va funcona la
capacitatea maxima.
Pasul 10. Instaleaza programul soware: Instala programul de
management: pentru o congurare completa a UPS-ului este
recomandata instalarea programului de management de la urmatorul link
• Pornirea UPS-ului: Apasa si ne apasat butonul ON / Mute pent-
ru cel pun 2 secunde pentru a porni UPS-ul.
• Oprirea alarmei: Cand UPS-ul este in modul de baterie, ne
apasat acest buton mp de cel pun 5 secunde pentru a acva sau
dezacva sistemul de alarma. Nu se aplica la situaile in care apar
aversmente sau erori.
• Tasta sus: Apasa acest buton pentru a asa seleca anterioara in
modul de setare UPS.
• Comutarea la modul UPS de auto-testare: Apasa si ne apasat
butonul ON / Mute mp de 5 secunde pentru a accesa modul UPS
de auto-testare in mp ce sunte in modul AC, ECO sau convertor.
Butonul OFF/Enter
• Oprirea UPS-ului: Apasa si ne apasat acest buton mp de cel
pun doua secunde pentru a opri UPS-ul. UPS-ul va in modul de
asteptare (standby) in caz de prezenta normala a tensiunii sau va
transferat in modul bypass in cazul in care acest modul este acvat.
• Tasta de conrmare a selecei: Apasa acest buton pentru a conr-
ma seleca in modul de setare UPS.
Butonul de Selectare
• Comutare mesaj LCD: Apasa acest buton pentru a schimba
mesajul de pe LCD in informai pentru tensiune de intrare,
frecventa intrare, tensiunea bateriei, tensiunea de iesire si frecventa
de iesire. Acesta va reveni la asajul implicit dupa o pauza de 10
secunde.
• Modul de setare: Apasa si ne apasat acest buton mp de 5
secunde pentru a intra in modul de setare al UPS-ului atunci cand
UPS-ul este in modul de bypass sau standby.
• Tasta jos: Apasa acest buton pentru a asa seleca urmatoare in
modul de setare al UPS-ului.
ON/MUTE
SELECT
OFF/ENTER
English
Română
49
Page 50
ON/Mute + Butonul de Selectare
• Comutarea la modul de bypass: Atunci cand tensiunea la retea este
normala, apasa butoanele ON / Mute si Select simultan pentru 5
secunde. In acest fel, UPS-ul va intra in modul de bypass. Aceasta
acune va inecienta atunci cand tensiunea de intrare este in
afara intervalului acceptabil.
Indica metodele de congurare detaliate in
secunea 5.5.
Indica codurile de eroare detaliate in secunea
5.7 si 5.8.
Funconare in modul Mute
50
Indica alarma oprita.
Page 51
Informai despre tensiunea de iesire, nivel baterie si nivel incarcare
Indica voltajul la intrare, frecventa la intrare, curentul
electric la intrare, voltajul bateriei, curentul electric al
Vac
bateriei, nivel baterie, temperatura ambientala, voltajul la
Vdc
888
OUTPUT
Informai incarcare
Hz
iesire, frecventa la iesire, incarcare curent electric si nivel
de incarcare in procente.
Vac: AC voltage, Vdc: DC voltage, Hz: frecventa
Indica nivelul de incarcare asel: 0-24%, 25-49%, 5074% si 75-100%.
Indica supraincarcare.
Indica scurt-circuit.
Informai despre prizele programabile
P1
Stare de funconare UPS
Indica faptul ca prizele programabile funconeaza.
Indica UPS conectat la retea.
Indica baterie funconala.
Indica faptul ca circuitul bypass funconeaza.
Indica faptul ca Modul ECO e acvat.
Indica faptul ca circuitul AC-DC funconeaza.
English
Română
51
Page 52
Indica faptul ca circuitul invertorului funconeaza.
Indica faptul ca este tensiune la iesire.
Baery informaon
Indica nivelul de incarcare asel: 0-24%, 25-49%, 5074%, si 75-100%.
Indica eroare baterie.
Indica baterie slaba.
Informai despre tensiunea de intrare, nivel baterie si nivel incarcare
Indica tensiunea la intrare, frecventa si tensiunea bateriei.
Vac: AC voltage, Vdc: DC voltage, Hz: frecventa
5.3 Indicatori sonori alarma
ModAlarma
Modul BaterieSuna la ecare 5 secunde
Baterie SlabaSuna la ecare 2 secunde
SupraincarcareSuna la ecare secunda
EroareSuna neintrerupt
Mod BypassSuna la ecare 10 secunde
52
Page 53
5.4 Index Asaj LCD
AbreviereCod ecranSemnicae
ENA
DIS
ESC
HLS
LLS
BAT
BAH
CHA
CBV
CFV
EPO
AO
AC
OIT
EAT
RAT
CF
ENA
d15
ESC
HLS
LLS
bAT
bAH
CHA
Cbu
CFu
EPO
AO
AC
OIT
EAT
RAT
CF
Acvat
Dezacvat
Renunta
Prag superior
Prag inferior
Baterie
Amperaj baterie
Curent de incarcare
Incarcare rapida
Tensiunea de mennere a
bateriilor
EPO
Deschidere acva
Inchidere acva
Transformator de izolare extern
Autonomie esmata
Autonomie acumulata
Convertor
English
Română
53
Page 54
ON
SD
OI
TP
CH
FU
BR
EE
OK
BL
OL
NC
OC
SF
BF
BV
ON
Sd
OI
TP
CH
FU
br
EE
0K
bL
OL
NC
OC
SF
bF
bv
Pornit
Inchidere
Supra-curent la
intrare
Temperatura
Incarcator
Frecventa de bypass
instabila
Inlocuieste bateriile
Eroare EEPROM
OK
Baterie slaba
Supra-incarcare
Bateriile nu se
conecteaza
Supra-incarcare
Eroare la cablurile de
conectare
Eroare baterie
Bypass in afara ariei
acceptate
54
Page 55
888 888
5.5 Setari UPS
1
2
3
NOTA!
Majoritatea paremetrilor pot seta doar in mod standby sau bypass. Seta
prima oara UPS-ul in mod standby sau bypass (vezi secunea 5.1) si apoi
seta parametrii.
Exista doi parametrii de setari.
• Parametrul 1: Pentru alternave de program. Consulta tabelul de mai jos.
• Parametrele 2 si 3: Pentru setarea informailor de asaj.
InterfataSetari
01: Setari tensiune la iesire
Parametrul 2: Tensiune la iesire
200: tensiunea de iesire este 200Vac
208: tensiunea de iesire este 208Vac
220: tensiunea de iesire este 220Vac
Vac
230
OUTPUT
230: tensiunea de iesire este 230Vac
240: tensiunea de iesire este 240Vac
NOTA: Capacitatea UPS-ului scade la 80%
atunci cand tensiunea la iesire este ajustata la
200VAC/208VAC.
02: Convertor de tensiune Acvat/Dezacvat
Parametrul 2: Acva sau dezacva modul
convertor.
Pute alege urmatoarele opuni:
CF ENA
CF ENA: Mod de conversie acvat
CF DIS: Mod de conversie dezacvat
(Setare implicita)
NOTA: Capacitatea UPS-ului scade la 80% cand
Modul convertor de tensiune este acvat.
English
Română
55
Page 56
03: Setarea frecventei la iesire
Parametrul 2: Setare frecventa iesire. Pute seta
frecventa iniala in modul baterie:
BAT 50: frecventa de iesire este 50Hz
BAT 60: frecventa de iesire esteHz
CF 500
Hz
OUTPUT
Daca modul de conversie este acvat, atunci
pute selecta urmatoarele frecvente de iesire:
CF 50: frecventa de iesire este 50Hz
CF 60: frecventa de iesire este 60Hz
04: ECO Acvat/Dezacvat
Parametrul 2: Acva sau dezacva funca
ENA
ECO. Pute alege urmatoarele opuni:
ENA: mod ECO acvat
DIS: mod ECO dezacvat (Setare implicita)
05: Setarea plajei de tensiune ECO
Parametrul 2: Stabili valoarea maxima,
respecv minima acceptata a tensiunii
pentru modul ECO prin apasarea butoanelor
Down si Up.
HLS: Pragul superior de tensiune in Modul ECO
Vac
HLS
INPUT
230
- parametrul 2.
Plaja de setari ale parametrului 3 este de la +7V la
+24V fata de tensiunea nominala (implicit: +12V).
LLS: Pragul inferior de tensiune in Modul ECO -
parametrul 2.
Plaja de setari ale parametrului 3 este de la -7V la
-24V fata de tensiunea nominala (implicit: -12V).
06: Acvare/dezacvare bypass cand UPS-ul este oprit
Parametrul 2: Acveaza sau deacveaza
ENA
funca de bypass. Pute alege una din
urmatoarele opuni:
Parametrul 2: Stabili valoarea maxima,
respecv minima acceptata a tensiunii pentru
modurile Bypass prin apasarea butoanelor
Down si Up.
HLS: Pragul superior de tensiune pentru Bypass.
Vac
HLS
INPUT
260
230-264: setarea valorii de sus a pragului de
tensiune este in parametrului 3 de la 230V la
246V (implicit: 264V).
LLS: Pragul inferior de tensiune pentru
Bypass.
170-220: setarea pragului inferior de tensiune este in parametrul 3 de la 170V la 220V
(implicit: 170V)
08: Setarea plajei de frecventa in modul Bypass
Parametrul 2: Stabili valoarea maxima,
respecv, minima acceptata a frecventei
pentru modul Bypass prin apasarea bu-
toanelor Down si Up.
HLS: Valoarea superioara a frecventei.
530
Hz
51-55Hz: setarea valorii pragului superior al
frecventei de la 51 Hz la 55Hz
(implicit 53 Hz).
LLS: Valoarea inferioara a frecventei.
45-49Hz: setarea valorii pragului inferior al
frecventei de la 45Hz la 49Hz (implicit: 47
Hz)
HLS
INPUT
09: Acvare/dezacvare prize de iesire programabile
Parametru 2: Acveaza sau
dezacveaza funca de prize de iesire
Parametrul 2: Seteaza limita mpului de
backup al prizelor de iesire programabile.
0-999: pute seta limita mpului de backup
de la 0-999 pentru prizele programabile care
sunt conectate la dispozive necrice in
mod baterie. (implicit: 999)
11: Setari privind limitele de autonomie
Parametrul 2: Stabileste mpul de backup
pentru prizele generale in modul baterie.
M
999
0-999: stabilirea mpului de backup in
minute de la 0 la 999 pentru prizele de iesire
generale in modul baterie.
DIS: Dezacvarea limitarii autonomiei
asel ca mpul de backup va depinde de
capacitatea bateriei (implicit).
NOTA: Pentru valoarea “0” a setarii, mpul de
backup va de doar 10 secunde
12: Setarea valorii capacitai totale a bateriei in Ah
Parametrul 2: Stabileste capacitatea totala a
bateriei UPS-ului in Ah.
7-999: setarea capacitai totale a bateriei
de la 7 la 999 Ah. Va rugam sa seta corect
capacitatea totala a bateriilor daca conecta
bAH 7
cabinete externe de baterii.
EXEMPLU: daca folosi UPS-ul Balder 1500
impreuna cu un cabinet cu 6 baterii de HR09122F
(doua siruri de cate 3 baterii), capacitatea totala a
bateriei este: 9Ah (capacitatea bateriei din UPS) +
2 x HR09122F (2 siruri de baterii de HR09122F
din cabinet) = 23Ah
13: Setari pentru valoarea maxima a curentului de incarcare
58
CHA
Daca folosi cabinete de baterii externe va
rugam sa seta valoarea maxima a curentului
de incarcare conform cu tabelul de mai jos:
Page 59
Capacitate baterie (AH)
7~202
20~404
40~606
60~808
80~10010
100~15012
NOTA: Daca la modelele Balder 1500 si 3000
este conectat cabinetul de baterii 2U atunci
valoarea maxima a curentului de incarcare va
4A.
Curent de incarcare
total (A)
14: Setari tensiune de incarcare rapida a bateriei
Parametrul 2: Seteaza valoarea tensiunii de
incarcare.
Cbu 23 6
Vdc
2.25-2.40: seteaza valoarea tensiunii de
incarcare intre 2.25 V/cell si 2.40V/cell.
(Implicit: 2.36V/cell).
15: Setari pentru valoarea voltajului de mennere a bateriei
Parametrul 2: Seteaza valoarea voltajului de
mennere a bateriei.
2.20-2.33: seteaza valoarea de mennere
CFu 22 8
Vdc
intre 2.20 V/cell si 2.33V/cell. (Implicit:
2.28V/cell).
NOTA: Seta parametrii 14 si 15 in funce de
specicaile bateriilor ulizate.
16: Setari EPO
Parametrul 2: Setarea controlului logic al
funcei EPO.
AO: Acv deschis (implicit). Cand AO este
selectat ca si funce logica EPO, va acva
EPO AO
funca EPO aunci cand PIN1 si PIN2 sunt in
status deschis.
AC: Acv inchis. Cand AO este selectat
ca si funce logica EPO, va acva funca
EPO aunci cand PIN1 si PIN2 sunt in status
inchis.
English
Română
59
Page 60
17: Conectarea unui transformator de izolare extern
Parametrul 2: Permite sau nu conectarea
unui transformator de izolare extern.
ENA: Daca este selectata aceasta opune,
dI S
este permisa conectarea unui transformator
de izolare extern.
DIS: Daca este selectata aceasta opune, nu
este permisa conectarea unui transformator
de izolare extern. (Implicit).
18: Setari ecran pentru autonomie
Parametrul 2: Seteaza ecranul pentru a
arata autonomia ramasa sau acumulata.
EAT: Daca EAT e selectat ecranul va arata
Vac
durata autonomiei ramase. (implicit)
RAT: Daca RAT e selectat ecranul va arata
durata autonomiei acumulate pana in acel
moment.
19: Setari pentru plaja de tensiune de intrare acceptata
Parametrul 2: Seteaza valoarea maxima
minima a tensunii de intrare acceptate
apasand butoanele Down si Up.
HLS: valoare maxima de intrare.
Vac
HLS
INPUT
300
280/290/300: setare valoare maxima a
voltajului - parametrul 2. (Implicit: 300Vac)
LLS: valoare minima bypass.
110/120/130/140/150/160: setare valoare
minima a voltajului - parametrul 2.
(Implicit: 110Vac).
00: Iesire din setari
60
ESC
Iese din modul de setari.
Page 61
5.6 Descrierea modului de operare
Mod de operare DescriereAsaj ecran
Atunci cand tensiunea de
intrare este in intervalul
Mod Online
Mod ECO
Mod Convertor
Frecventa
Mod Baterie
Mod Bypass
acceptabil, UPS-ul va
asigura curentul pur si
stabil catre iesire. UPS-ul
va incarca in acelasi mp si
bateria in modul online.
Mod economisire energie:
Cand tensiunea de
intrare este in parametrii
accepta, UPS-ul va face
bypass la tensiunea de
iesire pentru a economisi
energie. UPS-ul va incarca
bateria in acest mod.
Cand frecventa de intrare
este intre 40Hz SI 70Hz,
UPS-ul poate setat
la o frecventa de iesire
constanta de 50-60Hz.
Bateria va incarcata in
acest mod. Capacitatea
UPS-ului va scadea la
80% cand acest mod este
acvat.
Atunci cand tensiunea
de intrare este inafara
intervalului acceptabil
sau cand a cazut curentul
si alarma suna o data la
ecare 5 secunde, UPS-ul
va funcona de pe baterie.
Cand tensiunea de
intrare este in limitele
acceptate, dar UPS-ul este
supraincarcat, va intra in
Modul Bypass automat.
Alarma va suna o data la
ecare 10 secunde.
230
INPUT
230
INPUT
230
INPUT
720
INPUT
230
INPUT
Vac
Vac
Vac
Vdc
Vac
230
OUTPUT
230
OUTPUT
230
OUTPUT
230
OUTPUT
230
OUTPUT
Vac
P1
Vac
P1
English
Vac
P1
Română
Vac
P1
Vac
P1
61
Page 62
Mod Standby
UPS-ul este oprit si nu
exista tensiune de iesire,
dar acumulatorii se
incarca.
230
INPUT
Vac
Vac
0
OUTPUT
Mod Eroare
UPS-ul trece in mod
eroare, caz in care nu va
furniza tensiune de iesire
iar iconita de eroare va
clipi pe ecran.
Vac
INPUT
5.7 Coduri de Eroare
EroareCodIcoana
Eroare pornire BUS01-
Supratensiune BUS02-
Subtensiune BUS03-
Eroare la pornirea invertorului11-
Supratensiune la invertor12-
Subtensiune la invertor13-
Scurt-circuit la iesire invertor14
Tensiunea la baterii prea mare27
Tensiunea la baterii prea mica28
Scurtcircuit la iesirea bateriei2A-
Supraincalzire41-
Suprasarcina43
Eroare Baterie45-
Supra sarcina la iesire UPS49-
Vac
0
OUTPUT
62
Page 63
5.8 Indicatori de atenonare
Averzare
Baterie descarcata
Suprasarcina
Supra sarcina la iesire
UPS
Bateria nu este
conectata
Supraincarcare
Conectare gresita
Acvare EPO
Supraincalzire
Eroare de incarcare
Eroare la baterie
Iesire din intervalul de
bypass
Frecventa de bypass
instabila
Inlocuire baterie
Eroare EEPROM
NOTA!
Averzarea "Conectare gresita" poate acvata sau dezacvata prin
soware.
Icoana
(palpaie)
BYPASS
CodAlarma
Suna la ecare 2
secunde
Suna la ecare
secunda
Suna de 2 ori la
OI
ecare 10 secunde
Suna la ecare 2
secunde
Suna la ecare 2
secunde
Suna la ecare 2
secunde
Suna la ecare 2
EP
secunde
Suna la ecare 2
TP
secunde
Suna la ecare 2
CH
secunde
Suna la ecare 2
secunde
Suna la ecare 2
secunde
Suna la ecare 2
FU
secunde
Suna la ecare 2
br
secunde
Suna la ecare 2
EE
secunde
English
Română
63
Page 64
6
Inlocuirea bateriei
NOTA!
Acest UPS este echipat cu baterii interne si ulizatorul poate sa inlocuiasca
bateriile fara sa opreasca UPSul sau sarcinile conectate. Inlocuirea bateriei
este o procedura sigura, lipsita de pericole electrice.
ATENTIE
Luati in considerare toate avertismentele, atentionarile si notele
inainte de inlocuirea bateriilor.
Pasul 1. Inlatura panoul frontal.
Pasul 3. Scoate cua bateriei
prin eliminarea celor 2 suruburi
de pe panoul frontal.
64
Pasul 2. Deconecta cablurile
bateriei.
Pasul 4. Inlatura capacul
superior al cuei bateriei si
inlocui bateriile din interior
urmand procedura de asamblare
a kit-ului de baterii.
Page 65
Pasul 5. Dupa ce a inlocuit
bateriile, pune cua bateriei
inapoi in locaa originala si
insuruba strans.
Pasul 6. Reconecta cablurile
bateriei si pune panoul frontal
inapoi.
English
Română
65
Page 66
6.1 Procedura de asamblare a kit-ului de baterii
Balder 1000 / 1500
Pasul 1. Indeparta benzile
adezive.
Tapes
Tapes
Pasul 3. Pune acumulatorii pe
o parte a capacului de plasc.
Pasul 2. Conecta toate bornele
bateriei urmarind gracul de mai
jos.
Pasul 4. Acoperi cealalta parte
a carcasei de plasc conform
gracii de mai jos.
66
Page 67
Balder 2000 / 3000
Pasul 1. Indeparta benzile
adezive.
Pasul 3. Pune acumulatorii pe o
parte a capacului de plasc.
Pasul 2. Conecta toate bornele
bateriei urmarind graca de mai
jos.
English
Pasul 4. Acoperi cealalta parte
a carcasei de plasc conform
gracii de mai jos.
Română
67
Page 68
7
Probleme si Solui
ProblemaCauza posibilaSolue
Verica daca
cablul de curent
este conectat la
reteaua electrica.
Conecta
cablul de curent
corespunzator, la
reteaua electrica.
Seta circuitul
in pozie inchisa
pentru a dezacva
funca EPO.
Ro stecherul in
priza de la retea
cu 180 de grade
iar apoi conecta
UPS-ul.
Verica daca
toate bateriile sunt
conectate corect.
Contacta
unitatea de
service.
Indicatoarele nu se aprind si
alarma nu funconeaza, chiar
daca curentul este normal.
Icoana
eroarea EP apar pe ecran.
Alarma suna la ecare 2
secunde.
Icoanele
cu eroarea SF apar pe ecran.
Alarma suna la ecare 2
secunde.
Icoanele
cu eroarea NC apar pe ecran.
Alarma suna la ecare 2
secunde.
Codul de eroare 27 si icoana
si alarma suna connuu.
impreuna cu
si impreuna
si impreuna
palpaie pe ecranul LCD
Cablul de curent
nu este conectat
corespunzator.
Reteaua electrica
este conectata la
iesirea UPS-ului.
Funca EPO este
acvata.
Plusul si minusul
conductorilor
UPS-ului sunt
inversa.
Bateria este
incorect conectata.
Tensiunea bateriei
este prea mare sau
incarcatorul este
defect.
Codul de eroare 28 si icoana
ipalpaie pe ecranul
LCD si alarma suna connuu.
68
Tensiunea bateriei
este prea mica sau
incarcatorul este
defect.
Contacta
unitatea de
service.
Page 69
Icoanele si palpaie
pe ecranul LCD.
Alarma suna la ecare
secunda.
Codul de eroare 49 palpaie
pe ecranul LCD si alarma suna
connuu.
Codul de eroare este 43
iar icoana este
impreuna cu alarma care suna
inconnuu.
UPS-ul se aa in
suprasarcina.
UPS-ul se aa in
suprasarcina.
Dispozivele
conectate la UPS
sunt alimentate
direct din reteaua
electrica prin
Bypass.
Dupa suprasarcini
repetate, UPS-ul
s-a blocat in modul
Bypass.
Dispozivele
conectate la UPS
sunt alimentate
direct din reteaua
electrica.
UPS-ul s-a oprit in
mod automat din
cauza suprasarcinii
de la iesirea UPS-
ului.
UPS-ul se snge
automat datorita
supraincarcarii de
la iesire.
Inlatura sarcinile
in exces din iesirile
UPS-ului.
Inlatura sarcinile
in exces din iesirile
UPS-ului intai.
Apoi opri UPS-ul
si reporni-l.
Inlatura sarcinile
in exces din iesirile
UPS-ului.
Inlatura sarcinile
in exces din
iesirile UPS-ului si
reporni-l.
English
Română
Codul de eroare 14 si icoana
palpaie pe ecranul
LCD si alarma suna connuu.
UPS-ul s-a oprit
in mod automat
din cauza
scurtcircuitului
aparut la iesirea
UPS-ului.
Verica cablarea
iesirilor si daca
dispozivele
conectate se
aa in stare de
scurtcircuit.
69
Page 70
Codul de eroare este asat ca
01, 02, 03, 04, 11, 12, 13 sau
41 pe panoul LCD si alarma
suna connuu.
Timpul de backup al bateriei
este mai scurt decat valoarea
nominala.
O eroare interna
a avut loc. Exista
doua posible
rezultate:
1. Sarcina este
inca furnizata, dar
direct de la sursa
de curent prin
bypass.
2. Sarcina nu mai
este furnizata.
Bateriile nu sunt
complet incarcate.
Baterie defecta.Schimba bateria.
Contacta
unitatea de
service.
Incarca bateriile
pentru cel
pun 5 ore si
apoi verica
capacitatea. Daca
problema persista,
contacta unitatea
de service.
Codul de eroare 2A apare
pe ecran iar alarma suna
inconnuu.
Codul de eroare 45 apare
pe ecran iar alarma suna
inconnuu.
70
Scurtcircuitul
apare la iesirea
bateriei.
Bateria nu
funconeaza iar
tensiunea este mai
mica de 10V/PC.
Verica daca
si statusul
cabinetului de
baterii semnaleaza
un scurtcircuit.
Contacta
unitatea de
service.
Page 71
Dezafectarea echipamentelor electrice si electronice vechi
(Se aplica pentru ţarile membre ale Uniunii Europene si pentru alte tari
europene cu sisteme de colectare separata).
Acest simbol aplicat pe produs sau pe ambalajul acestuia indica faptul ca acest produs
nu trebuie tratat ca pe un deseu menajer.
El trebuie predat punctelor de reciclare a echipamentelor electrice si electronice.
Asigurandu-va ca acest produs este dezafectat in mod corect, veţi ajuta la prevenirea
posibilelor consecinte negave asupra mediului si a sanatai umane, care ar putut
surveni daca produsul ar fost dezafectat in mod necorespunzator.
Reciclarea materialelor va ajuta la conservarea resurselor naturale.