Balder Series User Manual
UPCMCOP110HBAAZ01B UPCMCOP120HBAAZ01B PWUP-OL150BA-AZ01B PWUP-OL300BA-AZ01B UPCMCOP130HBAAZ01B
Manual de ulizare
Before using this product, carefully read all product documentaon and retain it for future reference.
141.33.23.0
Page 2
Thank you for purchasing our products!
Please read this manual before using the product.
nJoy is a brand of power and backup protecon products that create soluons for mulple levels of environment complexity,
This UPS will protect your electronic equipment from physical
damage and will provide emergency baery backup power to
prevent data loss in the event of power problems.
The following models belong to the Balder Series:
1000 VA
residenal to industrial.
Balder 1000
1500 VA
Balder 1500
2000 VA
3000 VA
Package contents
UPS unit Power cord USB cable
Rack mounng holders Tower mounng stand
Screws
02
Balder 2000
Balder 3000
User manual Warranty card USB cable (only for models
with HID USB communicaon port).
Page 3
USB
EPO
OUT
RS232
IN
NETWORK/FAX/MODEM
INTELLIGENT SLOT
PROGRAMMABLE
OUTLETS (P1)
OUTPUT
INPUT
10A max.
USB
EPO
OUT
RS232
IN
NETWORK/FAX/MODEM
INTELLIGENT SLOT
PROGRAMMABLE OUTLETS (P1)
OUTPUT
INPUT
2
Product overview
Front View 1000/1500/2000/3000
LCD panel
H M S
Vac
Vac
Vdc
Vdc
Hz
Hz
888
888
INPUT
OUTPUT
P1
ON/MUTE
SELECT
OFF/ENTER
Funcon buons
LCD Panel
3 4 5
8
H M S
888
INPUT
Vdc Hz
Vac
888
OUTPUT
Vdc Hz
2
Vac
9
English
Română
P1
1. Baery info
2. Load info
3. Backup me info
4. Conguraon and fault info
5. Mute operaon
NOTE!
The HID USB communicaon port port is only available for Balder 1000, Balder 1500, Balder 2000 and Balder 3000.
76
6. Mode operaon info
7. Programmable outlet info
8. Input and baery voltage info
9. Output info
03
Page 4
NOTE!
Before installaon, please inspect the unit. Be sure that nothing inside the package is damaged. Keep the original package in a safe place for future use.
Back View
5
7
4
8
3
OUT
IN
NETWORK/FAX/MODEM
Balder 1000&1500
4
OUT
IN
NETWORK/FAX/MODEM
Balder 2000
Balder 3000
04
USB
RS232
6
5
USB
RS232
6
EPO
INTELLIGENT SLOT
8
7
8
EPO
INTELLIGENT SLOT
8
7
4
INTELLIGENT SLOT
OUT
NETWORK/FAX/MODEM
IN
EPO
8 26 9
10A max.
PROGRAMMABLE
OUTLETS (P1)
9
2
10A max.
PROGRAMMABLE
OUTLETS (P1)
9
2
INPUT
OUTPUT
3
INPUT
OUTPUT
3
5
PROGRAMMABLE OUTLETS (P1)
USB
RS232
INPUT
OUTPUT
OUTPUT
Page 5
1. Programable Output
receptacles: connect to non-
crical mission loads (max 10A)
2. General Output receptacles:
connect to crical mission loads (max 10A)
3. AC input
4. Network/Fax/Modem surge
3
Important Safety Warnings
Please comply with all warnings and operang instrucons in this manual strictly. Save this manual properly and carefully read the following instrucons before installing the unit. Do not operate this unit before reading through all safety informaon and operang instrucons carefully:
Transportaon
protecon
5. USB communicaon port
6. RS-232 communicaon port
7. SNMP intelligent slot
8. Emergency power o funcon
connector (EPO)
9. Connector for baery pack
• Please transport the UPS system only in the original package to
protect against shock and impact.
Preparaon
• Condensaon may occur if the UPS system is moved directly from
cold to warm environment. The UPS system must be absolutely dry before being installed. Please allow at least two hours for the UPS system to acclimate to the environment.
• Do not install the UPS system near water or in moist environments.
• Do not install the UPS system where it would be exposed to direct
sunlight or near heat sources.
• Do not block venlaon holes in the UPS housing.
Installaon
• Do not connect appliances or devices which would overload the UPS
system (e.g. laser printers) to the UPS output sockets.
• Place cables in such a way that no one can step on or trip over them.
• Do not connect domesc appliances such as hair dryers to UPS
output sockets.
English
Română
05
Page 6
• The UPS can be operated by any individuals with no previous
experience.
• Connect the UPS system only to an earthed shockproof outlet which
must be easily accessible and close to the UPS system.
• Please use only VDE-tested, CE-marked mains cable (e.g. the mains
cable of your computer) to connect the UPS system to the building
wiring outlet (shockproof outlet).
• Please use only VDE-tested, CE-marked power cables to connect the
loads to the UPS system.
• When installing the equipment, it should ensure that the sum of
the leakage current of the UPS and the connected devices does not exceed 3.5mA.
Operaon
• Do not disconnect the mains cable on the UPS system or the
building wiring outlet (shockproof socket outlet) during operaons since this would cancel the protecve earthing of the UPS system and of all connected loads.
• The UPS system features its own, internal current source (baeries).
The UPS output sockets or output terminals block may be electrically
live even if the UPS system is not connected to the building wiring outlet.
• In order to fully disconnect the UPS system, rst press the OFF/
Enter buon to disconnect the mains.
• Prevent uids or other foreign objects from entering the inside of the
UPS system.
Maintenance, service and faults
• The UPS system operates with hazardous voltages. Repairs may be
carried out only by qualied maintenance personnel.
• Cauon - risk of electric shock. Even aer the unit is disconnected
from the mains (building wiring outlet), components inside the UPS
system are sll connected to the baery and electrically live and dangerous.
• Before carrying out any kind of service and/or maintenance,
disconnect the baeries and verify that no current is present and no
06
Page 7
hazardous voltage exists in the terminals of high capability capacitor such as BUS-capacitors.
• Only persons are adequately familiar with baeries and with the
required precauonary measures may replace baeries and supervise operaons. Unauthorized persons must be kept well away from the baeries.
• Cauon - risk of electric shock. The baery circuit is not isolated
from the input voltage. Hazardous voltages may occur between the baery terminals and the ground. Before touching, please verify that no voltage is present!
• Baeries may cause electric shock and have a high short-circuit
current. Please take the precauonary measures specied in this
manual and any other measures necessary when working with
baeries: remove wristwatches, rings and other metal objects, use only tools with insulated grips and handles.
• When changing baeries, install the same number and same type of
baeries.
• Do not aempt to dispose of baeries by burning them. This could
cause baery explosion.
• Do not open or destroy baeries. Escaping electrolyte can cause
injury to the skin and eyes. It may be toxic.
• Please replace the fuse only with the same type and amperage in
order to avoid re hazards.
• Do not dismantle the UPS system.
• WARNING: This is a category C2 UPS product. In a residenal
environment, this product may cause radio interference, in which case the user may be required to take addional measures. (only for 220/230/240 VAC system).
English
Română
07
Page 8
4
Installaon
4.1 Operang principle
The operang principle of the UPS is shown below:
Input
Dynamic
EMI/RFI
Filters
The UPS is composed of mains input, EMI/RFI lters, recer/PFC, inverter, baery charger, DC-to-DC converter, baery, dynamic bypass and UPS output.
The UPS can protect your equipment from all power problems such as
surges, spikes, blackouts, brownouts and line noise. When AC power is present and the ON/ Mute switch is turned ON, the UPS will provide pure and stable AC power to the output. The UPS will also charge the baery in the on-line mode.
Recer
/PFC
Baery
Charger
Bypass
DC-to-DC
converter
Baery
Output
Inverter
08
Page 9
4.2 Connecng your equipment and rst usage
The UPS is simple to install and operate. Please read the following steps before connecng any equipments to this UPS:
Step 1. Connecng the baeries: For safety consideraon, the UPS is shipped out from factory without connecng the baery wires. To re­connect baery wires please follow below steps:
I. Remove front panel
II. Connect the AC input and re­connect baery wires.
III. Put the front panel back to the unit.
English
Română
09
Page 10
Step 2. Connect to External Baery Cabinet: When connecng external baery cabinet, please be sure to connect polarity correctly. Connect posive pole of baery cabinet to posive pole of external baery connector in UPS and negave pole of baery cabinet to negave pole of external baery connector in UPS. Polarity mis-connecon will cause UPS internal fault.
Connect only compable Balder baery cabinet provided by nJoy. Please read the manual of the UPS and baery cabinet and set the UPS baery total capacity in Ah and the charging current accordingly. The use of another baery cabinet may damage the UPS and void the warranty.
OUT
IN
NETWORK/FAX/MODEM
Max, 50A
BATETRY BREAKER
USB
EPO
RS232
INTELLIGENT SLOT
10A max.
PROGRAMMABLE
OUTLETS (P1)
NOTE!
These baery cabinets care compable with the following UPS:
• CA0312GX-AZ (36Vdc): UPS Balder 1000 / 1500
• CA0712GX-AZ (72Vdc): UPS Balder 2000 / 3000
10
INPUT
OUTPUT
Page 11
Step 3. Mounng the UPS: Balder series UPS can be either displayed on
the desk or mounted in the 19” rack chassis. Please choose your favourite way to posion this UPS.
A. Rack - mount installaon
First x the holders of the rack on the UPS.
Then x the UPS on the rack through the holders
B. Tower installaon
English
Română
First x the holders to t
the UPS.
Then put the UPS in place.
11
Page 12
Step 4. UPS input connecon: Plug the UPS into a two-pole, three-wire,
grounded receptacle only. Avoid using extension cords.
Step 5. UPS output connecon:
of output: programmable outlets and general outlets. Please connect non­crical devices to the programmable outlets and crical devices to the general outlets. During power failure, you may extend the backup me to crical devices by seng shorter backup me for non crical devices.
For socket-type outputs there two kinds
CAUTION
Do NOT plug LASER PRINTERS into any of
the outlets.
Step 6. Communicaon connecon: To allow for unaended UPS shutdown/start-up and status monitoring, connect the communicaon cable one end to the USB/RS-232 port and the other to the communicaon port of your PC. With the monitoring soware installed, you can schedule UPS shutdown/start-up and monitor UPS status through PC. The UPS is equipped with a slot for either SNMP or AS400 card. When installing either SNMP or AS400 card in the UPS, it will provide advanced communicaon and monitoring opons.
Communication port:
USB Port RS-232 Port Intelligent slot
Do NOT plug any SURGE STRIPS into any of the outlets.
NOTE!
USB port and RS-232 port can’t work at the same me.
12
Page 13
Step 7. Network connecon: Connect a single modem/phone/fax line into surge-protected “IN” outlet on the back panel of the UPS unit. Connect from “OUT” outlet to the equipment with another modem/fax/ phone line cable.
Network/Fax/Phone surge port:
Step 8. Disable and enable EPO funcon: Keep the pin 1 and pin 2 closed
for UPS normal operaon.
It’s in closed status for UPS
normal operaon.
Step 9. Turn on the UPS:
for two seconds to power on the UPS.
Press the ON/Mute buon on the front panel
To acvate EPO funcon, remove these two screws.
NOTE!
The baery charges fully during the rst ve hours of normal operaon. Do not expect full baery run capability during this inial charge period.
Step 10. Install soware: For opmal computer system protecon, install UPS monitoring soware to fully congure UPS shutdown. Use supplied RS-232 or USB communicaon cable to connect RS-232/USB port of UPS and RS-232/USB port of PC. Install the UPS monitoring soware
from hps://www.power-soware-download.com/viewpower.html to fully
congure UPS shutdown.
13
English
Română
Page 14
5
Operaons
5.1 Buon operaons
ON/MUTE
ON/Mute Buon
• Turn on the UPS: Press and hold ON/Mute buon for at least 2 sec-
onds to turn on the UPS.
• Mute the alarm: Aer the UPS is turned on in baery mode, press
and hold this buon for at least 5 seconds to disable or enable the alarm system. But it’s not applied to the situaons when warnings or errors occur.
• Up key: Press this buon to display previous selecon in UPS seng
mode.
• Switch to UPS self-test mode: Press ON/Mute buons simultane-
ously for 5 seconds to enter UPS self-tesng while in AC mode, ECO mode, or converter mode.
OFF/Enter Buon
• Turn o the UPS: Press and hold this buon for at least 2 seconds
to turn o the UPS. The UPS will be in standby mode under normal power or transfer to Bypass mode if the Bypass seng is enabled.
• Conrm selecon key: Press this buon to conrm selecon in UPS
sengs mode.
Select Buon
• Switch LCD message: Press this buon to change the LCD message
for input voltage, input frequency, baery voltage, output voltage and output frequency.
• Sengs mode: Press and hold this buon for 5 seconds to enter
UPS sengs mode when the UPS is in standby mode or bypass mode.
• Down key: Press this buon to display next selecon in UPS sengs
mode.
SELECT
OFF/ENTER
14
Page 15
ON/Mute + Select Buon
• Switch to bypass mode: When the main power is normal, press ON/
Mute and Select buons simultaneously for 5 seconds. Then the UPS will enter to bypass mode. This acon will be ineecve when the input voltage is out of acceptable range.
5.2 LCD Panel Indicators
H
M
S
888
INPUT
Vac Vdc Hz
888
OUTPUT
Vac Vdc Hz
P1
Display Funcon
Backup me informaon
H
M
S
Indicates the esmated backup me.
H: hours, M: minute, S: second.
Conguraon and fault informaon
Indicates the conguraon items, and the conguraon items are listed in details in secon 5.5.
Indicates the warning and fault codes, and the codes are
listed in details in secon 5.7 and 5.8.
Mute operaon
English
Română
Indicates that the UPS alarm is disabled.
15
Page 16
Output & Load informaon
Vac
Indicates the output voltage and output frequency.
Vdc
P1
Hz
Vac: AC voltage, Vdc: DC voltage, Hz: frequency
Indicates the load level by 0-24%, 25-49%, 50-74% and 75-100%.
Indicates overload.
Indicates the load or the UPS output is short circuit.
Indicates that programmable management outlets are
working.
Indicates the UPS connects to the mains.
Indicates the baery is working.
Indicates the bypass circuit is working.
888
OUTPUT
Load informaon
Programmable outlets informaon
Mode operaon informaon
16
Indicates the ECO mode is enabled.
Indicates the AC to DC circuit is working.
Page 17
Baery informaon
Indicates the inverter circuit is working.
Indicates the output is working.
Indicates the baery level by 0-24%, 25-49%, 50-74%, and 75-100%.
Indicates the baery is fault.
Indicates low baery level and low baery voltage.
Input & baery informaon
Indicate the input voltage, input frequency and baery voltage.
Vac: AC voltage, Vdc: DC voltage, Hz: frequency
5.3 Audible Alarm Indicators
Mode Alarm
Baery Mode Sounding every 5 seconds
Low Baery Sounding every 2 seconds
Overload Sounding every second
Fault Connuously sounding
Bypass Mode Sounding every 10 seconds
English
Română
17
Page 18
5.4 LCD display wordings index
Abbreviaon Display content Meaning
ENA
DIS
ESC
HLS
LLS
BAT
BAH
CHA
CBV
CFV
EPO
AO
AC
OIT
EAT
RAT
CF
ENA d15 ESC HLS LLS bAT bAH CHA Cbu CFu EPO AO AC OIt
EAt rAt CF
Enable
Disable
Escape
High loss
Low loss
Baery
Baery AH
Charger current
Charger boost voltage
Charger oat voltage
EPO
Acve open
Acve close
Output isolaon
transformer
Esmated autonomy me
Running autonomy me
Converter
18
Page 19
ON
SD
OI
TP
CH
FU
BR
EE
OK
BL
OL
NC
OC
SF
BF
BV
ON Sd OI TP CH FU
br EE 0K bL OL NC OC SF bF bv
ON
Shutdown
Over input current
Temperature
Charger
Bypass frequency unstable
Baery Replacement
EEPROM error
OK
Baery Low
Over Load
Baery No Connect
Over Charge
Site wiring fault
Baery Fault
Bypass Out Range
English
Română
19
Page 20
888 888
5.5 UPS sengs
2
3
NOTE!
Most parameters can be set only in bypass/standby mode; please set the UPS to bypass/standby mode (see secon 5.1) and then change parameters.
There are two parameters to set up the UPS.
• Parameter 1: For program alternaves. Refer to the table below.
• Parameter 2&3: The sengs opons or values for each program.
Interface Sengs
01: Output voltage sengs
Parameter 2: Output voltage: 200: presents output voltage is 200Vac 208: present output voltage is 208Vac
Vac
230
OUTPUT
220: present output voltage is 220Vac 230: present output voltage is 230Vac 240: present output voltage is 240Vac
NOTE: Derate capacity to 80% when the output
voltage is adjusted to 200VAC/208VAC.
02: Frequency Converter enable/disable
Parameter 2: Enable or disable converter mode.
CF ENA
You may choose the following two opons:
CF ENA: converter mode enable CF DIS: converter mode disable (Default)
NOTE: Derate capacity to 80% when Frequency
Converter mode is enabled.
20
Page 21
03: Output frequency sengs
Parameter 2: You may set the inial frequency on baery mode:
BAT 50: presents output frequency of 50Hz BAT 60: presents output frequency of 60Hz
CF 500
Hz
OUTPUT
If converter mode is enabled, you may choose
the following output frequency:
CF 50: present output frequency is 50Hz CF 60: present output frequency is 60Hz
04: ECO enable/disable
Parameter 2: Enable or disable ECO funcon.
ENA
You may choose the following two opons:
ENA: ECO mode enable DIS: ECO mode disable (Default)
05: ECO voltage range seng
Parameter 2: Set the acceptable high
voltage point and low voltage point for ECO mode by pressing Down key or Up key. HLS: High loss voltage in ECO mode in parameter 2. The seng range in parameter 3 is from +7V
230
Vac
to +24V of the nominal voltage. (Default: +12V) LLS: Low loss voltage in ECO mode in parameter 2. The seng range in parameter 3 is from -7V to -24V of the nominal voltage.
(Default: -12V)
HLS
INPUT
06: Bypass enable/disable when UPS is o
Parameter 2: Enable or disable Bypass
ENA
funcon. You may choose the following two opons:
ENA: Bypass enable DIS: Bypass disable (Default)
English
Română
21
Page 22
07: Bypass voltage range seng
Parameter 2: Set the acceptable high voltage point and acceptable low voltage point for
Bypass mode by pressing the Down key or
Up key.
HLS: Bypass high voltage point
260
Vac
230-264: seng the high voltage point in parameter 3 from 230Vac to 264Vac. (Default:
264Vac)
LLS: Bypass low voltage point 170-220: seng the low voltage point in parameter 3 from 170Vac to 220Vac. (Default:
170Vac)
HLS
INPUT
08: Bypass frequency range seng
Parameter 2: Set the acceptable high fre­quency point and acceptable low frequency point for Bypass mode by pressing the
Down key or Up key.
530
Hz
HLS: Bypass high frequency point
51-55Hz: seng the frequency high loss point from 51Hz to 55HZ(Default: 53.0Hz).
LLS: Bypass low Frequency point
45-49Hz: seng the frequency low loss point from 45Hz to 49HZ(Default: 47.0Hz)
HLS
INPUT
09: Programmable outlets enable/disable
Parameter 2: Enable or disable the program-
dIS
P1
mable outlets funcon. You may choose the following two opons:
ENA: Programmable outlets enable DIS: Programmable outlets disable (Default)
22
Page 23
10: Programmable outlets seng
M
999
P1
Parameter 2: Set up backup me limits for programmable outlets. 0-999: seng the backup me limits in
minutes from 0-999 for programmable
outlets which connect to non-crical devices on baery mode. (Default: 999).
11: Autonomy limitaon seng
Parameter 2: Set up backup me on baery mode for general outlets.
M
999
0-999: seng the backup me in minutes from 0-999 for general outlets on ba. mode. DIS: Disable the autonomy limitaon and the backup me will depend on baery capacity. (Default)
NOTE: When seng as “0”, the backup me
will be only 10 seconds.
12: Baery total AH seng
Parameter 2: Set up the baery total AH of the UPS. 7-999: seng the baery total capacity from 7-999 in AH. Please set the correct baery total capacity if external baery
bAH 7
bank is connected.
EXAMPLE:
with one baery cabinet with 6 pcs of HR09122F baeries (two strings of 3 baeries), total baery AH seng will be: 9AH (UPS baery string capacity) + 2xHR09122F (2 strings of HR09122F baeries inside baery cabinet) = 23AH
13: Maximum charger current seng
English
Română
if you use Balder 1500 together
CHA
If you use external baery pack please set
the appropriate charging current based
on baery capacity used. Please use the
following table as reference:
23
Page 24
Battery capacity(AH)
NOTE: If you connect Baery Pack 2U for
Balder 1500 to Balder 1500 you should set maximum charger current to 4A. If you connect Baery Pack 2U for Balder 3000 to Balder 3000 you should set maximum charger current to 4A.
14: Charger Boost voltage seng
Parameter 2: Set up the charger boost
voltage.
Cbu 23 6
Vdc
2.25-2.40: seng the charger boost voltage from 2.25 V/cell to 2.40V/cell. (Default:
2.36V/cell)
15: Charger Float voltage seng
Parameter 2: Set up the charger oat voltage.
2.20-2.33: seng the charger oat voltage
CFu 22 8
Vdc
from 2.20 V/cell to 2.33V/cell. (Default:
2.28V/cell)
NOTE: Parameters 14 and 15 should be set
based on baeries specicaons.
16: EPO logic seng
Parameter 2: Set up the EPO funcon control logic. AO: Acve Open (Default). When AO is
EPO AO
selected as EPO logic, it will acvate EPO funcon with Pin 1 and Pin 2 in open status. AC: Acve Close. When AC is selected as EPO logic, it will acvate EPO funcon with Pin 1 and Pin 2 in close status.
Total charging
7~20 2 20~40 4 40~60 6 60~80 8
80~100 10
100~150 12
current (A)
24
Page 25
17: External output isolaon transformer connecon
Parameter 2: Allow or disallow external output isolaon transformer connecon.
dI S
ENA: If selected, it’s allowed to connect to
an external output isolaon transformer.
DIS: If selected, it’s not allowed to connect
to external output isolaon transformer.
(Default)
18: Display seng for autonomy me
Parameter 2: Set up the display seng for autonomy me
Vac
EAT: If EAT is selected, it will display the
remaining autonomy me. (Default)
RAT: If RAT is selected, it will show
accumulated autonomy me so far.
19: Acceptable input voltage range seng
Parameter 2: Set the acceptable high
voltage point and acceptable low voltage point for input voltage range by pressing the Down key or Up key. HLS: Input high voltage point
300
Vac
280/290/300: seng the high voltage point in parameter 2. (Default: 300Vac) LLS: Bypass low voltage point 110/120/130/140/150/160: seng the low voltage point in parameter 2. (Default:
110Vac)
HLS
INPUT
00: Exit seng
English
Română
ESC
Exit the seng mode.
25
Page 26
5.6 Operang mode descripon
Operang mode Descripon LCD display
When the input voltage is
within acceptable range,
Online mode
ECO mode
Frequency
Converter mode
Baery mode
Bypass mode
UPS will provide pure
and stable AC power to
output. The UPS will also charge the baery in online mode.
Energy saving mode: When the input voltage is within voltage regulaon
range, UPS will bypass
voltage to output for energy saving. The UPS
will also charge the
baery at ECO mode.
When input frequency is
within 40 Hz to 70 Hz,
the UPS can be set at a constant output frequency,
50 Hz or 60 Hz. The UPS will sll charge baery under this mode. The
capacity of the UPS should
be derated to 80% when Frequency Converter mode is enabled.
When the input voltage
is beyond the acceptable range or power failure, the UPS will backup power
from baery and alarm is sounding every 5 seconds.
When input voltage is
within acceptable range
but UPS is overload, UPS
will enter bypass mode or bypass mode can be
set by front panel. Alarm is sounding every 10 seconds.
230
INPUT
230
INPUT
230
INPUT
720
INPUT
230
INPUT
Vac
Vac
Vac
Vdc
Vac
230
OUTPUT
230
OUTPUT
230
OUTPUT
230
OUTPUT
230
OUTPUT
Vac
P1
Vac
P1
Vac
P1
Vac
P1
Vac
P1
26
Page 27
Standby mode
UPS is powered o and
there is no output supply
power, but the UPS sll can charge baeries.
230
INPUT
Vac
Vac
0
OUTPUT
Fault mode
When a fault has occurred, the ERROR icon and the fault code will be
displayed.
Vac
INPUT
5.7 Faults Reference Code
Fault event Fault code Icon
Bus start fail 01 -
Bus over 02 -
Bus under 03 -
Inverter so start fail 11 -
Inverter voltage high 12 -
Inverter voltage Low 13 -
Inverter output short 14
Baery voltage too high 27
Baery voltage too low 28
Charger output short 2A -
Over temperature 41 -
Overload 43
Charger failure 45 -
Over input current 49 -
Vac
0
OUTPUT
English
Română
27
Page 28
5.8 Warning indicator
Warning
Low Baery
Overload
Over input current
Baery is not
connected
Over Charge
Site wiring fault
EPO enable
Over temperature
Charger failure
Baery fault
Out of bypass voltage
range
Bypass frequency unstable
Baery replacement
EEPROM error
NOTE!
“Site Wiring Fault” funcon can be enabled/disabled via soware. Please check soware manual for the details.
Icon
(ashing)
BYPASS
Code Alarm
Sounding every 2
seconds
Sounding every
second
Sounding 2 beep
OI
every 10 seconds
Sounding every 2
seconds
Sounding every 2
seconds
Sounding every 2
seconds
Sounding every 2
EP
seconds
Sounding every 2
TP
seconds
Sounding every 2
CH
seconds
Sounding every 2
seconds
Sounding every 2
seconds
Sounding every 2
FU
seconds
Sounding every 2
br
seconds
Sounding every 2
EE
seconds
28
Page 29
6
Replacing the baery
NOTE!
This UPS is equipped with internal baeries. When your baery lifeme is over you can replace them without shung down the UPS or connected loads thanks to the hot-swappable baery design. Replacement is a safe procedure, isolated from electrical hazards.
CAUTION
Consider all warnings, cautions, and notes before replacing the batteries.
Step 1. Remove front panel.
Step 3. Pull out the baery box
by removing the two screws on the front panel.
Step 2. Disconnect baery wires.
English
Română
Step 4. Remove the top cover of baery box and replace the inside baeries following the baery kit assembly procedure.
29
Page 30
Step 5. Aer replacing the baeries, put the baery box back to original locaon and screw it ghtly.
Step 6. Re-connect the baery
wires and put the front panel
back to the unit.
30
Page 31
6.1 Baery kit assemly procedure
Balder 1000 / 1500
Step 1. Remove adhesive tapes.
Tapes
Tapes
Step 3. Put assembled baery packs on one side of plasc shells.
Step 2. Connect all baery
terminals by following below
chart.
English
Step 4. Cover the other side of plasc shell as in the below picture.
Română
31
Page 32
Balder 2000 / 3000
Step 1. Remove adhesive tapes.
Step 3. Put assembled baery
packs on one side of plasc shells.
Step 2. Connect all baery terminals by following below chart.
Step 4. Cover the other side of plasc shell as in the below picture.
32
Page 33
7
Troubleshoong
Problem Possible cause Soluons
Check if input power cord is
rmly connected to the mains.
Plug the AC input power cord to the
AC input correctly.
Set the circuit in
closed posion
to disable EPO
funcon.
Rotate mains power socket by
180˚ and then
connect to UPS
system.
Check if all
baeries are connected well.
Contact service unit.
No indicaon and alarm even though the main is normal.
The icon
code EP are ashing on LCD
display and alarm is sounding
every second.
The icon
warning code SF are ashing on LCD display. Alarm is sounding every 2 seconds.
The icon
warning code NC are ashing on LCD display. Alarm is sounding every 2 seconds.
Fault code is shown as 27 and the icon on LCD display and alarm is
connuously sounding.
and the warning
and the
and and
is lighng
The AC input power is not
connected well.
The AC input is connected to the
UPS output.
EPO funcon is acvated.
Line and neutral conductors of UPS
input are reversed.
The external or internal baery
is incorrectly
connected.
Baery voltage
is too high or the
charger is fault.
English
Română
Fault code is shown as 28 and the icon on LCD display and alarm is
connuously sounding.
is lighng
Baery voltage
is too low or the
charger is fault.
Contact service unit.
33
Page 34
UPS is overloaded.
The icon and
are ashing on LCD display. Alarm is sounding every second.
Fault code is shown as 49 on LCD display and alarm is
connuously sounding.
Fault code is shown as 43 and the icon
on LCD display. Alarm is connuously sounding.
Fault code is shown as 14 and the icon on LCD display and alarm is
connuously sounding.
is lighng
is lighng
UPS is overloaded. Devices connected
to the UPS are fed directly by the electrical network
via the Bypass.
Aer repeve overloads, the
UPS is locked in
the Bypass mode. Connected devices
are fed directly by
the mains.
UPS is over input current.
The UPS shut down
automacally
because of
overload at the UPS output.
The UPS shut down
automacally
because short circuit occurs on
the UPS output.
Remove excess
loads from UPS
output.
Remove excess
loads from UPS
output rst. Then
shut down the
UPS and restart it.
Remove excess
loads from UPS
output.
Remove excess
loads from UPS output and restart
it.
Check output wiring and if
connected devices
are in short circuit
status.
34
Page 35
Fault code is shown as 01, 02, 03, 11, 12, 13 and 41 on LCD display and alarm is
connuously sounding.
Baery backup me is shorter than nominal value.
Fault code is shown as 2A on LCD display and alarm is
connuously sounding.
A UPS internal
fault has occurred.
There are two possible results:
1. The load is sll supplied, but
directly from AC
power via bypass.
2. The load is no
longer supplied by
power.
Baeries are not fully charged.
Baeries defect.
The short circuit occurs on the
charger output.
Contact service unit.
Charge the
baeries for at
least 5 hours and then check
capacity. If the problem sll
persists, consult
your dealer.
Contact your dealer to replace
the baery or
replace them by
yourself.
Check if
baery wiring
of connected
external pack is
in short circuit
status.
English
Română
Fault code is shown as 45
on LCD display. At the same me, alarm is connuously sounding.
The charger does
not have output and baery voltage is less than 10V/PC.
Contact service unit.
35
Page 36
Disposal of Old Electrical & Electronic Equipment
(Applicable in the European Union and other European countries with separate collecon systems)
This symbol on the product or on its packaging indicates that this product shall not be
treated as household waste.
Instead it shall be handed over to the applicable collecon point for the recycling of electrical and electronic equipment.
By ensuring this product is disposed of correctly, you will help prevent potenal negave consequences for the environment and human health, which could otherwise be caused by inappropriate waste handling of this product.
The recycling of materials will help to conserve natural resources.
36
Page 37
Multumim pentru ca a ales produsele noastre!
Va rugam ci cu atene manualul de ulizare inainte de a pune in
nJoy este un brand de solui UPS dedicate protecei si rezervei de energie din diferite medii de ulizare, de la rezidenal la industrial
UPS-ul va protejeaza echipamentele electronice de daune zice
si ofera o baterie de rezerva pentru a preveni pierderile de date in
cazul intreruperilor accidentale ale energiei electrice.
funcune acest produs.
Din seria Balder fac parte urmatoarele modele:
1000 VA
1500 VA
2000 VA
3000 VA
Connutul pachetului
UPS Cablu de alimentare Cablu USB
Supor pentru montarea
in rack
Balder 1000
Balder 1500
Balder 2000
Balder 3000
Suport pentru montarea
Suruburi
Cablu USB (doar pentru modelele cu port de comunicare HID USB)
English
Română
pe vercala
37
Page 38
USB
EPO
OUT
RS232
IN
NETWORK/FAX/MODEM
INTELLIGENT SLOT
PROGRAMMABLE
OUTLETS (P1)
OUTPUT
INPUT
10A max.
USB
EPO
OUT
RS232
IN
NETWORK/FAX/MODEM
INTELLIGENT SLOT
PROGRAMMABLE OUTLETS (P1)
OUTPUT
INPUT
2
Prezentarea produsului
Vedere din fata 1000/1500/2000/3000
Ecran LCD
Ecran LCD
3 4 5
Butoane
H M S
Vac
Vac
Vdc
Vdc
Hz
Hz
888
888
INPUT
OUTPUT
P1
ON/MUTE
SELECT
OFF/ENTER
8
H
M
S
888
INPUT
Vdc Hz
Vac
888
OUTPUT
Vdc Hz
2
Vac
9
P1
1. Informai si nivel baterie
2. Informai si nivel incarcare
3. Informai mp de backup
4. Erori si congurai
5. Modul "Mute"
NOTA!
Inainte de instalare inspecta unitatea. Fi siguri ca nimic din interiorul pachetului nu este stricat. Tine pachetul original intr-un loc sigur pentru o
76
6. Informai mod operare
7. Informai prize programabile
8. Informai tensiune de intrare
si stare baterie
9. Informai tensiune de iesire
ulizare ulterioara.
38
Page 39
NOTA!
Portul HID USB este disponibil doar pentru modelele Balder 1000, Balder 1500, Balder 2000 and Balder 3000.
Vedere din spate
5
7
4
8
3
OUT
IN
NETWORK/FAX/MODEM
Balder 1000&1500
4
OUT
IN
NETWORK/FAX/MODEM
Balder 2000
Balder 3000
USB
RS232
6
5
USB
RS232
6
EPO
INTELLIGENT SLOT
8
7
8
EPO
INTELLIGENT SLOT
8
7
4
INTELLIGENT SLOT
OUT
NETWORK/FAX/MODEM
IN
EPO
8 26 9
10A max.
PROGRAMMABLE
OUTLETS (P1)
9
2
INPUT
OUTPUT
English
10A max.
PROGRAMMABLE
OUTLETS (P1)
3
INPUT
OUTPUT
Română
9
5
PROGRAMMABLE OUTLETS (P1)
USB
RS232
2
3
INPUT
OUTPUT
OUTPUT
39
Page 40
1. Prize de iesire programabile
desnate echipamentelor non­crice (max 10A)
2. Prize de iesire programabile
desnate echipamentelor crice (max 10A)
3. Alimentare AC
4. Priza protece supratensiune
3
Averzari de siguranta
Va rugam sa respecta toate aversmentele si instrucunile de ulizare din acest manual. Pastra acest manual in mod corespunzator si ci cu atene urmatoarele instrucuni inainte de instalarea aparatului. Nu folosi aceasta unitate inainte de a ci toate instrucunile de siguranta si de ulizare cu atene:
Transport
• Va rugam sa transporta sistemul UPS numai in ambalajul original
pentru a-l proteja impotriva socurilor.
Pregare
• Condensul poate aparea daca sistemul UPS este mutat dintr-un
mediu rece in unul cald. Sistemul UPS trebuie sa e uscat inainte de a  instalat. Va rugam sa aloca cel pun doua ore pentru ca sistemul UPS sa se aclimazeze cu mediul unde dori sa il instala.
• Nu instala sistemul UPS langa apa sau in medii umede.
• Nu instala sistemul UPS acolo unde ar  expus la lumina directa a
soarelui sau in apropierea surselor de incalzire.
• Nu bloca oriciile de venlae ale carcasei UPS-ului.
Instalare
• Nu conecta aparate sau dispozive care ar suprasolicita sistemul
UPS (de exemplu: imprimantele laser) la mufele de iesire UPS.
• Instala cablurile in asa fel incat nimeni sa nu calce pe ele.
• Nu conecta aparate de uz casnic, cum ar  uscatoare de par la
prizele de iesire UPS.
pentru Retea / Fax / Modem
5. Port comunicare USB
6. Port comunicare RS-232
7. Slot pentru cardul SNMP
8. Conector pentru funca EPO
(oprire de urgenta)
9. Conector pentru cabinetul de
baterii
40
Page 41
• UPS-ul poate  folosit de orice persoana, fara a necesita nicio
experienta anterioara.
• Conecta sistemul UPS numai la o priza cu impamantare, care
trebuie sa e usor accesibila si aproape de sistemul UPS.
• Va rugam sa folosi numai cabluri de alimentare testate VDE si cu
marcaj CE (de exemplu: cablul de alimentare de la computer) pentru a conecta sistemul UPS la reteaua electrica a cladirii.
• Va rugam sa folosi numai cabluri de alimentare testate VDE si cu
marcaj CE pentru a conecta sarcinile la sistemul UPS.
• La instalarea echipamentului, trebuie sa va asigura ca totalul
curentului de scurgere al UPS si al dispozivelor conectate nu depaseste 3,5 mA.
Operare
• Nu deconecta cablul de alimentare de la sistemul UPS sau de
la priza cladirii in mpul ulizarii, deoarece acest lucru ar anula impamantarea de protece a sistemului UPS si a tuturor sarcinilor conectate.
• Sistemul UPS are propria sursa de curent intern (baterii). Prizele de
iesire sau terminale de iesire pe categorii pot  incarcate electric,
chiar daca sistemul UPS nu este conectat la sistemul electric al
cladirii.
• Pentru a deconecta complet sistemul UPS, apasa intai butonul
OFF/Enter pentru a deconecta sursa de alimentare.
• Nu lasa sa ajunga in interiorul unitai UPS niciun obiect strain sau
lichide.
Intrenere, Service si Defecte
• Sistemul UPS funconeaza cu tensiuni periculoase. Reparaile pot 
efectuate numai de catre personalul de intrenere calicat.
• Atene - risc de soc electric. Chiar si dupa ce aparatul este
deconectat de la reteaua electrica, componentele din interiorul sistemului UPS sunt inca conectate la baterie si sunt incarcate
electric si periculoase.
• Inainte de a efectua orice fel de service si / sau intrenere,
deconecta bateriile si verica sa nu existe curent sau tensiune
periculoasa in terminalele condensatorului de mare capacitate, cum
English
Română
41
Page 42
ar  condensatorul BUS.
• Numai persoanele care sunt familiarizate in mod adecvat cu baterii si
cu masurile de precaue necesare pot inlocui bateriile si supraveghea operaunile. Persoane neautorizate trebuie sa e nute departe de baterii sistemului UPS.
• Atene - risc de soc electric. Circuitul bateriei nu este izolat de
tensiunea de intrare. Tensiuni periculoase pot aparea intre bornele bateriei si pamant. Inainte de a ange, va rugam sa verica ca nu exista tensiune!
• Bateriile pot provoca soc electric. Va rugam sa lua masurile de
precaue specicate mai jos, precum si orice alte masuri necesare atunci cand se lucreaza cu bateriile sistemului: da-va jos ceasurile de mana, inelele si alte obiecte metalice si folosi doar instrumente cu manere izolate.
• La schimbarea bateriilor, instala acelasi numar si acelasi p de
baterii.
• Nu incerca sa distruge bateriile prin arderea lor. Acest lucru poate
cauza explozia bateriilor.
• Nu deschide sau distruge bateriile. Scurgerea de electrolit poate
provoca leziuni la nivelul pielii si ochilor, totodata acesta este foarte toxic.
• Va rugam sa inlocui siguranta numai cu acelasi p de siguranta si
amperaj pentru a evita pericolele de incendiu.
• Nu dezasambla sistemul UPS.
• ATENTIE: Acesta este un produs din categoria C2. Intr-un mediu
rezidenal, poate cauza interferente radio, caz in care ulizatorul este rugat sa ia masuri suplimentare!
42
Page 43
4
Instalare
4.1 Principiu de funconare
Principiul de funconare a acestui UPS este urmatorul:
Input
Dynamic
EMI/RFI
Filters
Sursa neintrerupbila de tensiune are in componenta sa: intrarea de la retea, ltrele pentru EMI / RFI (interferente electromagnece / interferente radio-frecventa), redresorul si PFC (coreca factorului de putere), incarcatorul bateriilor, bateriile, convertorul DC-DC (tensiune connua la tensiune connua), invertorul, bypassul dinamic si iesirea sursei neintrerupbile de tensiune.
UPS-ul va poate proteja echipamentul de toate problemele legate de tensiunea electrica cum ar : suprasarcini, uctuai de tensiune, caderi de tensiune si zgomotul de pe retea. Cand curentul este prezent la reteaua
de alimentare si comutatorul (ON/Mute) este pornit (ON) UPS-ul isi
incarca bateria si asigura echipamentului energia necesara funconarii direct de la retea.
Recer
/PFC
Baery
Charger
Bypass
DC-to-DC
converter
Baery
Output
Inverter
43
English
Română
Page 44
4.2 Conectarea echipamentelor si prima folosire
UPS-ul este simplu de folosit si de instalat. Urma pasii de mai jos inainte
de a conecta echipamentul la UPS:
Pasul 1. Conecta bateriile: Pentru masuri de siguranta, UPS-ul este livrat fara sa aiba conectate cablurile bateriei. Pentru a reconecta aceste cabluri va rugam sa urma pasi de mai jos:
I. Detasa panoul frontal.
II. Conecta alimentarea si reconecta cablurile bateriei.
III. Pune panoul frontal la loc.
44
Page 45
Pasul 2. Conectare cabinet de baterii extern: Atunci cand conecta UPS­ul la un cabinet de baterii extern asigura-va ca polaritatea este corecta (polul poziv al cabinetului de baterii la polul poziv al conectarii la UPS si polul negav al cabinetului de baterii la polul negav al conectarii la UPS). Polaritatea inversata va aduce daune UPS-ului.
Folosi doar cabinete de baterii nJoy compabile cu seria Balder. Va rugam sa ci manualul de ulizare al UPS-ului si al cabinetelor de baterii si sa seta valoarea capacitai totale a bateriilor in Ah si curentul de incarcare in consecinta. Folosirea altor cabinete de baterii poate duce
OUT
IN
NETWORK/FAX/MODEM
Max, 50A
BATETRY BREAKER
USB
EPO
RS232
INTELLIGENT SLOT
10A max.
PROGRAMMABLE
OUTLETS (P1)
NOTA!
Cabinetele de baterii sunt compabile cu urmatoarele modele:
• CA0312GX-AZ (36Vdc): UPS Balder 1000 / 1500
• CA0712GX-AZ (72Vdc): UPS Balder 2000 / 3000
OUTPUT
INPUT
English
Română
45
Page 46
la deteriorarea UPS-ului si la pierderea garanei. Pasul 3. Montarea UPS-ului: Acest model de UPS poate sa e pozionat e vercal e orizontal - montat intr-o carcasa rack de 19”. Va rugam sa alege pozia in care dori sa poziona UPS.
A. Montarea in Rack:
Intai xa supori rack-ului pe UPS.
Apoi xa UPS-ul pe rack cu ajutorul suruburilor.
B. Montarea vercala
Fixa supori pentru a
susne UPS-ul.
46
Apoi xa UPS-ul.
Page 47
Pasul 4. Conexiune de intrare UPS: Conecta UPS-ul la priza tripolara, impamantata. Nu uliza prelungitoare.
Pasul 5. Conexiune de iesire UPS:
variante: prize programabile si prize generale. Conecta dispozivele non-crice la prizele programabile si dispozivele crice la prizele generale. In mpul unei caderi de curent, pute exnde mpul de backup la dispozivele crice, setand un mp mai scurt de backup pentru dispozivele non-crice.
Pentru iesirile de p priza exista doua
ATENTIE
NU conectati imprimante laser la
nici una din prizele UPS-ului.
NU conectati alte ACCESORII CU PROTECTIE la niciuna
din prize.
Pasul 6. Conexiunea de comunicare: Pentru a permite oprirea/pornirea
nesupravegheata a UPS-ului si monitorizarea starii acestuia, conecta un
capat al cablului de comunicare la portul USB/RS-232 si celalalt la portul
de comunicare al PC-ului. Cu soware-ul de monitorizare instalat, pute programa oprirea si pornirea UPS-ului si sa monitoriza starea UPS prin intermediul PC-ului. UPS-ul este echipat cu un slot inteligent, perfect pentru card SNMP sau AS400. Cand instala cardul SNMP sau AS400 in UPS, ve obne opuni de comunicare si monitorizare avansata.
Port de comunicare
Port USB Port RS-232 Slot inteligent
NOTA!
Porturile USB si RS-232 nu pot funcona in acelasi mp.
47
English
Română
Page 48
Pasul 7. Conexiunea in retea: Conecta o linie de modem/telefon/fax in priza protejata IN ce se aa in spatele UPS-ului. Conecta in priza OUT echipamentul cu o alta linie de modem/telefon/fax.
Port Retea/Fax/Telefon:
Pasul 8. Acva si dezacva funca EPO: Tine pin-ul 1 si 2 inchisi pentru modul de operare normal al UPS-ului. Pentru a acva funca EPO taia cablul dintre pin 1 si pin 2.
Pentru modul de operare normala conectorul este in
stare inchisa.
Pasul 9. Pornirea UPS-ului:
pentru cel pun 2 secunde pentru a porni UPS-ul.
Apasa si ne apasat butonul ON / Mute
Pentru a acva funca EPO inlatura cele doua suruburi.
NOTA!
Bateria se incarca complet in decursul primelor cinci ore de funconare normala. In aceasta perioada de incarcare iniala bateria nu va funcona la capacitatea maxima.
Pasul 10. Instaleaza programul soware: Instala programul de management: pentru o congurare completa a UPS-ului este
recomandata instalarea programului de management de la urmatorul link
hps://www.power-soware-download.com/viewpower.html
48
Page 49
5
Operai
5.1 Butoane
Butonul ON/Mute
• Pornirea UPS-ului: Apasa si ne apasat butonul ON / Mute pent-
ru cel pun 2 secunde pentru a porni UPS-ul.
• Oprirea alarmei: Cand UPS-ul este in modul de baterie, ne
apasat acest buton mp de cel pun 5 secunde pentru a acva sau dezacva sistemul de alarma. Nu se aplica la situaile in care apar aversmente sau erori.
• Tasta sus: Apasa acest buton pentru a asa seleca anterioara in
modul de setare UPS.
• Comutarea la modul UPS de auto-testare: Apasa si ne apasat
butonul ON / Mute mp de 5 secunde pentru a accesa modul UPS de auto-testare in mp ce sunte in modul AC, ECO sau convertor.
Butonul OFF/Enter
• Oprirea UPS-ului: Apasa si ne apasat acest buton mp de cel
pun doua secunde pentru a opri UPS-ul. UPS-ul va  in modul de asteptare (standby) in caz de prezenta normala a tensiunii sau va  transferat in modul bypass in cazul in care acest modul este acvat.
• Tasta de conrmare a selecei: Apasa acest buton pentru a conr-
ma seleca in modul de setare UPS.
Butonul de Selectare
• Comutare mesaj LCD: Apasa acest buton pentru a schimba
mesajul de pe LCD in informai pentru tensiune de intrare, frecventa intrare, tensiunea bateriei, tensiunea de iesire si frecventa de iesire. Acesta va reveni la asajul implicit dupa o pauza de 10 secunde.
• Modul de setare: Apasa si ne apasat acest buton mp de 5
secunde pentru a intra in modul de setare al UPS-ului atunci cand
UPS-ul este in modul de bypass sau standby.
• Tasta jos: Apasa acest buton pentru a asa seleca urmatoare in
modul de setare al UPS-ului.
ON/MUTE
SELECT
OFF/ENTER
English
Română
49
Page 50
ON/Mute + Butonul de Selectare
• Comutarea la modul de bypass: Atunci cand tensiunea la retea este
normala, apasa butoanele ON / Mute si Select simultan pentru 5 secunde. In acest fel, UPS-ul va intra in modul de bypass. Aceasta acune va  inecienta atunci cand tensiunea de intrare este in afara intervalului acceptabil.
5.2 Indicatori ecran LCD
H
M
S
888
INPUT
Vac Vdc Hz
888
OUTPUT
Vac Vdc Hz
P1
Asaj Funce
Informai despre mpul de back-up
H
M
S
Indica esmav mpul de back-up ramas. H: ore, M: minute, S: secunde.
Informai despre congurare si erori
Indica metodele de congurare detaliate in secunea 5.5.
Indica codurile de eroare detaliate in secunea
5.7 si 5.8.
Funconare in modul Mute
50
Indica alarma oprita.
Page 51
Informai despre tensiunea de iesire, nivel baterie si nivel incarcare
Indica voltajul la intrare, frecventa la intrare, curentul electric la intrare, voltajul bateriei, curentul electric al
Vac
bateriei, nivel baterie, temperatura ambientala, voltajul la
Vdc
888
OUTPUT
Informai incarcare
Hz
iesire, frecventa la iesire, incarcare curent electric si nivel de incarcare in procente.
Vac: AC voltage, Vdc: DC voltage, Hz: frecventa
Indica nivelul de incarcare asel: 0-24%, 25-49%, 50­74% si 75-100%.
Indica supraincarcare.
Indica scurt-circuit.
Informai despre prizele programabile
P1
Stare de funconare UPS
Indica faptul ca prizele programabile funconeaza.
Indica UPS conectat la retea.
Indica baterie funconala.
Indica faptul ca circuitul bypass funconeaza.
Indica faptul ca Modul ECO e acvat.
Indica faptul ca circuitul AC-DC funconeaza.
English
Română
51
Page 52
Indica faptul ca circuitul invertorului funconeaza.
Indica faptul ca este tensiune la iesire.
Baery informaon
Indica nivelul de incarcare asel: 0-24%, 25-49%, 50­74%, si 75-100%.
Indica eroare baterie.
Indica baterie slaba.
Informai despre tensiunea de intrare, nivel baterie si nivel incarcare
Indica tensiunea la intrare, frecventa si tensiunea bateriei.
Vac: AC voltage, Vdc: DC voltage, Hz: frecventa
5.3 Indicatori sonori alarma
Mod Alarma
Modul Baterie Suna la ecare 5 secunde
Baterie Slaba Suna la ecare 2 secunde
Supraincarcare Suna la ecare secunda
Eroare Suna neintrerupt
Mod Bypass Suna la ecare 10 secunde
52
Page 53
5.4 Index Asaj LCD
Abreviere Cod ecran Semnicae
ENA
DIS
ESC
HLS
LLS
BAT
BAH
CHA
CBV
CFV
EPO
AO
AC
OIT
EAT
RAT
CF
ENA d15 ESC HLS LLS bAT bAH CHA Cbu CFu
EPO AO AC OIT EAT RAT CF
Acvat
Dezacvat
Renunta
Prag superior
Prag inferior
Baterie
Amperaj baterie
Curent de incarcare
Incarcare rapida
Tensiunea de mennere a
bateriilor
EPO
Deschidere acva
Inchidere acva
Transformator de izolare extern
Autonomie esmata
Autonomie acumulata
Convertor
English
Română
53
Page 54
ON
SD
OI
TP
CH
FU
BR
EE
OK
BL
OL
NC
OC
SF
BF
BV
ON Sd OI TP CH FU br EE 0K bL OL NC OC SF bF bv
Pornit
Inchidere
Supra-curent la intrare
Temperatura
Incarcator
Frecventa de bypass
instabila
Inlocuieste bateriile
Eroare EEPROM
OK
Baterie slaba
Supra-incarcare
Bateriile nu se
conecteaza
Supra-incarcare
Eroare la cablurile de conectare
Eroare baterie
Bypass in afara ariei acceptate
54
Page 55
888 888
5.5 Setari UPS
1
2
3
NOTA!
Majoritatea paremetrilor pot  seta doar in mod standby sau bypass. Seta prima oara UPS-ul in mod standby sau bypass (vezi secunea 5.1) si apoi seta parametrii.
Exista doi parametrii de setari.
• Parametrul 1: Pentru alternave de program. Consulta tabelul de mai jos.
• Parametrele 2 si 3: Pentru setarea informailor de asaj.
Interfata Setari
01: Setari tensiune la iesire
Parametrul 2: Tensiune la iesire 200: tensiunea de iesire este 200Vac 208: tensiunea de iesire este 208Vac 220: tensiunea de iesire este 220Vac
Vac
230
OUTPUT
230: tensiunea de iesire este 230Vac 240: tensiunea de iesire este 240Vac
NOTA: Capacitatea UPS-ului scade la 80%
atunci cand tensiunea la iesire este ajustata la 200VAC/208VAC.
02: Convertor de tensiune Acvat/Dezacvat
Parametrul 2: Acva sau dezacva modul convertor. Pute alege urmatoarele opuni:
CF ENA
CF ENA: Mod de conversie acvat CF DIS: Mod de conversie dezacvat
(Setare implicita)
NOTA: Capacitatea UPS-ului scade la 80% cand
Modul convertor de tensiune este acvat.
English
Română
55
Page 56
03: Setarea frecventei la iesire
Parametrul 2: Setare frecventa iesire. Pute seta frecventa iniala in modul baterie:
BAT 50: frecventa de iesire este 50Hz BAT 60: frecventa de iesire esteHz
CF 500
Hz
OUTPUT
Daca modul de conversie este acvat, atunci pute selecta urmatoarele frecvente de iesire:
CF 50: frecventa de iesire este 50Hz CF 60: frecventa de iesire este 60Hz
04: ECO Acvat/Dezacvat
Parametrul 2: Acva sau dezacva funca
ENA
ECO. Pute alege urmatoarele opuni:
ENA: mod ECO acvat DIS: mod ECO dezacvat (Setare implicita)
05: Setarea plajei de tensiune ECO
Parametrul 2: Stabili valoarea maxima, respecv minima acceptata a tensiunii
pentru modul ECO prin apasarea butoanelor
Down si Up.
HLS: Pragul superior de tensiune in Modul ECO
Vac
HLS
INPUT
230
- parametrul 2. Plaja de setari ale parametrului 3 este de la +7V la +24V fata de tensiunea nominala (implicit: +12V).
LLS: Pragul inferior de tensiune in Modul ECO -
parametrul 2. Plaja de setari ale parametrului 3 este de la -7V la
-24V fata de tensiunea nominala (implicit: -12V).
06: Acvare/dezacvare bypass cand UPS-ul este oprit
Parametrul 2: Acveaza sau deacveaza
ENA
funca de bypass. Pute alege una din urmatoarele opuni:
ENA: Acvare bypass DIS: Dezacvare bypass (implicit)
56
Page 57
07: Setarile plajei tensiunii de bypass
Parametrul 2: Stabili valoarea maxima, respecv minima acceptata a tensiunii pentru
modurile Bypass prin apasarea butoanelor
Down si Up.
HLS: Pragul superior de tensiune pentru Bypass.
Vac
HLS
INPUT
260
230-264: setarea valorii de sus a pragului de
tensiune este in parametrului 3 de la 230V la
246V (implicit: 264V).
LLS: Pragul inferior de tensiune pentru
Bypass.
170-220: setarea pragului inferior de tensi­une este in parametrul 3 de la 170V la 220V (implicit: 170V)
08: Setarea plajei de frecventa in modul Bypass
Parametrul 2: Stabili valoarea maxima, respecv, minima acceptata a frecventei
pentru modul Bypass prin apasarea bu-
toanelor Down si Up.
HLS: Valoarea superioara a frecventei.
530
Hz
51-55Hz: setarea valorii pragului superior al frecventei de la 51 Hz la 55Hz (implicit 53 Hz). LLS: Valoarea inferioara a frecventei. 45-49Hz: setarea valorii pragului inferior al frecventei de la 45Hz la 49Hz (implicit: 47 Hz)
HLS
INPUT
09: Acvare/dezacvare prize de iesire programabile
Parametru 2: Acveaza sau dezacveaza funca de prize de iesire
dIS
P1
programabile.
ENA: Acvarea prizelor programabile. DIS: Dezacvarea prizelor programabile
(implicit).
English
Română
57
Page 58
10: Setari pentru prizele programabile
M
999
P1
Parametrul 2: Seteaza limita mpului de backup al prizelor de iesire programabile. 0-999: pute seta limita mpului de backup de la 0-999 pentru prizele programabile care sunt conectate la dispozive necrice in mod baterie. (implicit: 999)
11: Setari privind limitele de autonomie
Parametrul 2: Stabileste mpul de backup pentru prizele generale in modul baterie.
M
999
0-999: stabilirea mpului de backup in minute de la 0 la 999 pentru prizele de iesire generale in modul baterie. DIS: Dezacvarea limitarii autonomiei asel ca mpul de backup va depinde de capacitatea bateriei (implicit).
NOTA: Pentru valoarea “0” a setarii, mpul de
backup va  de doar 10 secunde
12: Setarea valorii capacitai totale a bateriei in Ah
Parametrul 2: Stabileste capacitatea totala a
bateriei UPS-ului in Ah. 7-999: setarea capacitai totale a bateriei de la 7 la 999 Ah. Va rugam sa seta corect capacitatea totala a bateriilor daca conecta
bAH 7
cabinete externe de baterii. EXEMPLU: daca folosi UPS-ul Balder 1500
impreuna cu un cabinet cu 6 baterii de HR09122F (doua siruri de cate 3 baterii), capacitatea totala a
bateriei este: 9Ah (capacitatea bateriei din UPS) + 2 x HR09122F (2 siruri de baterii de HR09122F din cabinet) = 23Ah
13: Setari pentru valoarea maxima a curentului de incarcare
58
CHA
Daca folosi cabinete de baterii externe va rugam sa seta valoarea maxima a curentului de incarcare conform cu tabelul de mai jos:
Page 59
Capacitate baterie (AH)
7~20 2 20~40 4 40~60 6 60~80 8
80~100 10
100~150 12
NOTA: Daca la modelele Balder 1500 si 3000
este conectat cabinetul de baterii 2U atunci valoarea maxima a curentului de incarcare va  4A.
Curent de incarcare
total (A)
14: Setari tensiune de incarcare rapida a bateriei
Parametrul 2: Seteaza valoarea tensiunii de incarcare.
Cbu 23 6
Vdc
2.25-2.40: seteaza valoarea tensiunii de incarcare intre 2.25 V/cell si 2.40V/cell. (Implicit: 2.36V/cell).
15: Setari pentru valoarea voltajului de mennere a bateriei
Parametrul 2: Seteaza valoarea voltajului de mennere a bateriei.
2.20-2.33: seteaza valoarea de mennere
CFu 22 8
Vdc
intre 2.20 V/cell si 2.33V/cell. (Implicit:
2.28V/cell).
NOTA: Seta parametrii 14 si 15 in funce de
specicaile bateriilor ulizate.
16: Setari EPO
Parametrul 2: Setarea controlului logic al
funcei EPO. AO: Acv deschis (implicit). Cand AO este selectat ca si funce logica EPO, va acva
EPO AO
funca EPO aunci cand PIN1 si PIN2 sunt in status deschis. AC: Acv inchis. Cand AO este selectat ca si funce logica EPO, va acva funca
EPO aunci cand PIN1 si PIN2 sunt in status
inchis.
English
Română
59
Page 60
17: Conectarea unui transformator de izolare extern
Parametrul 2: Permite sau nu conectarea
unui transformator de izolare extern. ENA: Daca este selectata aceasta opune,
dI S
este permisa conectarea unui transformator
de izolare extern. DIS: Daca este selectata aceasta opune, nu
este permisa conectarea unui transformator
de izolare extern. (Implicit).
18: Setari ecran pentru autonomie
Parametrul 2: Seteaza ecranul pentru a arata autonomia ramasa sau acumulata. EAT: Daca EAT e selectat ecranul va arata
Vac
durata autonomiei ramase. (implicit) RAT: Daca RAT e selectat ecranul va arata
durata autonomiei acumulate pana in acel
moment.
19: Setari pentru plaja de tensiune de intrare acceptata
Parametrul 2: Seteaza valoarea maxima  minima a tensunii de intrare acceptate apasand butoanele Down si Up. HLS: valoare maxima de intrare.
Vac
HLS
INPUT
300
280/290/300: setare valoare maxima a voltajului - parametrul 2. (Implicit: 300Vac) LLS: valoare minima bypass. 110/120/130/140/150/160: setare valoare minima a voltajului - parametrul 2. (Implicit: 110Vac).
00: Iesire din setari
60
ESC
Iese din modul de setari.
Page 61
5.6 Descrierea modului de operare
Mod de operare Descriere Asaj ecran
Atunci cand tensiunea de
intrare este in intervalul
Mod Online
Mod ECO
Mod Convertor Frecventa
Mod Baterie
Mod Bypass
acceptabil, UPS-ul va
asigura curentul pur si
stabil catre iesire. UPS-ul va incarca in acelasi mp si bateria in modul online.
Mod economisire energie: Cand tensiunea de intrare este in parametrii
accepta, UPS-ul va face
bypass la tensiunea de iesire pentru a economisi
energie. UPS-ul va incarca bateria in acest mod.
Cand frecventa de intrare este intre 40Hz SI 70Hz, UPS-ul poate  setat la o frecventa de iesire constanta de 50-60Hz. Bateria va  incarcata in acest mod. Capacitatea UPS-ului va scadea la 80% cand acest mod este acvat.
Atunci cand tensiunea de intrare este inafara
intervalului acceptabil sau cand a cazut curentul
si alarma suna o data la
ecare 5 secunde, UPS-ul va funcona de pe baterie.
Cand tensiunea de intrare este in limitele acceptate, dar UPS-ul este
supraincarcat, va intra in Modul Bypass automat. Alarma va suna o data la ecare 10 secunde.
230
INPUT
230
INPUT
230
INPUT
720
INPUT
230
INPUT
Vac
Vac
Vac
Vdc
Vac
230
OUTPUT
230
OUTPUT
230
OUTPUT
230
OUTPUT
230
OUTPUT
Vac
P1
Vac
P1
English
Vac
P1
Română
Vac
P1
Vac
P1
61
Page 62
Mod Standby
UPS-ul este oprit si nu
exista tensiune de iesire,
dar acumulatorii se
incarca.
230
INPUT
Vac
Vac
0
OUTPUT
Mod Eroare
UPS-ul trece in mod
eroare, caz in care nu va furniza tensiune de iesire iar iconita de eroare va clipi pe ecran.
Vac
INPUT
5.7 Coduri de Eroare
Eroare Cod Icoana
Eroare pornire BUS 01 -
Supratensiune BUS 02 -
Subtensiune BUS 03 -
Eroare la pornirea invertorului 11 -
Supratensiune la invertor 12 -
Subtensiune la invertor 13 -
Scurt-circuit la iesire invertor 14
Tensiunea la baterii prea mare 27
Tensiunea la baterii prea mica 28
Scurtcircuit la iesirea bateriei 2A -
Supraincalzire 41 -
Suprasarcina 43
Eroare Baterie 45 -
Supra sarcina la iesire UPS 49 -
Vac
0
OUTPUT
62
Page 63
5.8 Indicatori de atenonare
Averzare
Baterie descarcata
Suprasarcina
Supra sarcina la iesire UPS
Bateria nu este conectata
Supraincarcare
Conectare gresita
Acvare EPO
Supraincalzire
Eroare de incarcare
Eroare la baterie
Iesire din intervalul de
bypass
Frecventa de bypass
instabila
Inlocuire baterie
Eroare EEPROM
NOTA!
Averzarea "Conectare gresita" poate  acvata sau dezacvata prin soware.
Icoana
(palpaie)
BYPASS
Cod Alarma
Suna la ecare 2
secunde
Suna la ecare
secunda
Suna de 2 ori la
OI
ecare 10 secunde
Suna la ecare 2
secunde
Suna la ecare 2
secunde
Suna la ecare 2
secunde
Suna la ecare 2
EP
secunde
Suna la ecare 2
TP
secunde
Suna la ecare 2
CH
secunde
Suna la ecare 2
secunde
Suna la ecare 2
secunde
Suna la ecare 2
FU
secunde
Suna la ecare 2
br
secunde
Suna la ecare 2
EE
secunde
English
Română
63
Page 64
6
Inlocuirea bateriei
NOTA!
Acest UPS este echipat cu baterii interne si ulizatorul poate sa inlocuiasca bateriile fara sa opreasca UPSul sau sarcinile conectate. Inlocuirea bateriei este o procedura sigura, lipsita de pericole electrice.
ATENTIE
Luati in considerare toate avertismentele, atentionarile si notele inainte de inlocuirea bateriilor.
Pasul 1. Inlatura panoul frontal.
Pasul 3. Scoate cua bateriei
prin eliminarea celor 2 suruburi
de pe panoul frontal.
64
Pasul 2. Deconecta cablurile bateriei.
Pasul 4. Inlatura capacul superior al cuei bateriei si inlocui bateriile din interior
urmand procedura de asamblare
a kit-ului de baterii.
Page 65
Pasul 5. Dupa ce a inlocuit bateriile, pune cua bateriei inapoi in locaa originala si insuruba strans.
Pasul 6. Reconecta cablurile bateriei si pune panoul frontal inapoi.
English
Română
65
Page 66
6.1 Procedura de asamblare a kit-ului de baterii
Balder 1000 / 1500
Pasul 1. Indeparta benzile
adezive.
Tapes
Tapes
Pasul 3. Pune acumulatorii pe o parte a capacului de plasc.
Pasul 2. Conecta toate bornele bateriei urmarind gracul de mai jos.
Pasul 4. Acoperi cealalta parte a carcasei de plasc conform gracii de mai jos.
66
Page 67
Balder 2000 / 3000
Pasul 1. Indeparta benzile
adezive.
Pasul 3. Pune acumulatorii pe o parte a capacului de plasc.
Pasul 2. Conecta toate bornele bateriei urmarind graca de mai jos.
English
Pasul 4. Acoperi cealalta parte a carcasei de plasc conform gracii de mai jos.
Română
67
Page 68
7
Probleme si Solui
Problema Cauza posibila Solue
Verica daca
cablul de curent este conectat la
reteaua electrica.
Conecta
cablul de curent
corespunzator, la reteaua electrica.
Seta circuitul in pozie inchisa pentru a dezacva funca EPO.
Ro stecherul in priza de la retea
cu 180 de grade
iar apoi conecta UPS-ul.
Verica daca
toate bateriile sunt
conectate corect.
Contacta
unitatea de
service.
Indicatoarele nu se aprind si
alarma nu funconeaza, chiar daca curentul este normal.
Icoana
eroarea EP apar pe ecran. Alarma suna la ecare 2 secunde.
Icoanele
cu eroarea SF apar pe ecran. Alarma suna la ecare 2 secunde.
Icoanele
cu eroarea NC apar pe ecran. Alarma suna la ecare 2 secunde.
Codul de eroare 27 si icoana
si alarma suna connuu.
impreuna cu
si impreuna
si impreuna
palpaie pe ecranul LCD
Cablul de curent nu este conectat
corespunzator.
Reteaua electrica este conectata la
iesirea UPS-ului.
Funca EPO este acvata.
Plusul si minusul conductorilor UPS-ului sunt
inversa.
Bateria este
incorect conectata.
Tensiunea bateriei este prea mare sau incarcatorul este
defect.
Codul de eroare 28 si icoana
ipalpaie pe ecranul
LCD si alarma suna connuu.
68
Tensiunea bateriei este prea mica sau incarcatorul este
defect.
Contacta
unitatea de
service.
Page 69
Icoanele si palpaie
pe ecranul LCD. Alarma suna la ecare secunda.
Codul de eroare 49 palpaie pe ecranul LCD si alarma suna
connuu.
Codul de eroare este 43 iar icoana este impreuna cu alarma care suna
inconnuu.
UPS-ul se aa in suprasarcina.
UPS-ul se aa in suprasarcina. Dispozivele
conectate la UPS sunt alimentate direct din reteaua electrica prin
Bypass.
Dupa suprasarcini repetate, UPS-ul s-a blocat in modul
Bypass. Dispozivele
conectate la UPS sunt alimentate direct din reteaua
electrica.
UPS-ul s-a oprit in mod automat din
cauza suprasarcinii
de la iesirea UPS-
ului.
UPS-ul se snge
automat datorita supraincarcarii de
la iesire.
Inlatura sarcinile in exces din iesirile UPS-ului.
Inlatura sarcinile in exces din iesirile UPS-ului intai. Apoi opri UPS-ul si reporni-l.
Inlatura sarcinile in exces din iesirile UPS-ului.
Inlatura sarcinile in exces din
iesirile UPS-ului si
reporni-l.
English
Română
Codul de eroare 14 si icoana
palpaie pe ecranul
LCD si alarma suna connuu.
UPS-ul s-a oprit in mod automat
din cauza
scurtcircuitului aparut la iesirea
UPS-ului.
Verica cablarea
iesirilor si daca
dispozivele
conectate se
aa in stare de scurtcircuit.
69
Page 70
Codul de eroare este asat ca
01, 02, 03, 04, 11, 12, 13 sau 41 pe panoul LCD si alarma
suna connuu.
Timpul de backup al bateriei
este mai scurt decat valoarea nominala.
O eroare interna
a avut loc. Exista
doua posible
rezultate:
1. Sarcina este inca furnizata, dar
direct de la sursa de curent prin
bypass.
2. Sarcina nu mai este furnizata.
Bateriile nu sunt
complet incarcate.
Baterie defecta. Schimba bateria.
Contacta
unitatea de
service.
Incarca bateriile
pentru cel
pun 5 ore si apoi verica capacitatea. Daca
problema persista,
contacta unitatea de service.
Codul de eroare 2A apare pe ecran iar alarma suna
inconnuu.
Codul de eroare 45 apare pe ecran iar alarma suna
inconnuu.
70
Scurtcircuitul apare la iesirea
bateriei.
Bateria nu
funconeaza iar
tensiunea este mai
mica de 10V/PC.
Verica daca
si statusul cabinetului de
baterii semnaleaza un scurtcircuit.
Contacta
unitatea de
service.
Page 71
Dezafectarea echipamentelor electrice si electronice vechi
(Se aplica pentru ţarile membre ale Uniunii Europene si pentru alte tari europene cu sisteme de colectare separata).
Acest simbol aplicat pe produs sau pe ambalajul acestuia indica faptul ca acest produs nu trebuie tratat ca pe un deseu menajer.
El trebuie predat punctelor de reciclare a echipamentelor electrice si electronice.
Asigurandu-va ca acest produs este dezafectat in mod corect, veţi ajuta la prevenirea posibilelor consecinte negave asupra mediului si a sanatai umane, care ar  putut surveni daca produsul ar  fost dezafectat in mod necorespunzator.
Reciclarea materialelor va ajuta la conservarea resurselor naturale.
Page 72
Memo73Memo
72
Page 73
Page 74
EU Declaration of Conformity
We, manufacturer / importer
DAI-TECH SA
Str. Berlin, Nr 6, C.P. 307160,
Dumbrăvița, Timiș, România
declare that the products
UPS BALDER SERIES: UPCMCOP110HBAAZ01B UPCMCOP120HBAAZ01B
PWUP-OL150BA-AZ01B PWUP-OL300BA-AZ01B
UPCMCOP130HBAAZ01B
are in conformity with
(EC conformity marking)
Tested with the listed standards, the above mentioned products were found
in compliance with 2004/108/EC EMC Directive and with 2006/95/EC LVD
EN 62040 – 2: 2006
IEC 61000 – 4 – 2: 2001
IEC 61000 – 4 – 3: 2002
IEC 6100 – 4 – 4: 2004
(RoHS conformity marking) in accordance with European Directive 2011/65/EU.
Directive.
IEC 6100 – 4 – 5: 2005 IEC 6100 – 2 – 2: 2002
EN 62040 – 1 - 1: 2003
IEC 60950 – 1: 2001
and in conformity with
Stamp
Mar. 25, 2023
Timisoara
Date and location Signature and name
Tommy Lee
Page 75
Declaratie UE de conformitate
Noi, in calitate de producator / importator
DAI-TECH SA
Str. Berlin, Nr 6, C.P. 307160,
Dumbrăvița, Timiș, România
declaram ca urmatoarele produse
UPS BALDER SERIES: UPCMCOP110HBAAZ01B UPCMCOP120HBAAZ01B
PWUP-OL150BA-AZ01B PWUP-OL300BA-AZ01B
UPCMCOP130HBAAZ01B
sunt conforme cu
(simbolul de conformitate europeana)
Testate in standardele acceptate, produsele mentionate sunt conforme cu
directiva 2004/108/EC EMC si cu directiva 2006/95/EC LVD .
EN 62040 – 2: 2006 IEC 61000 – 4 – 2: 2001 IEC 61000 – 4 – 3: 2002
IEC 6100 – 4 – 4: 2004
IEC 6100 – 4 – 5: 2005 IEC 6100 – 2 – 2: 2002 EN 62040 – 1 - 1: 2003
IEC 60950 – 1: 2001
si in conformitate cu
(simbolul de conformitate RoHS ) in acord cu directiva europeana 2011/65/EU.