If the device is sold to a country in the European Economic Area (EEA)
this instruction handbook must be translated into the language of the
country in which the device is to be used.
Should the translated text be unclear, the original instruction handbook
(German) must be consulted or the manufacturer contacted for clarification.
Copyright
No part of this publication may be reproduced, transmitted, sold or disclosed without prior permission. Damages will be claimed for violations.
All rights reserved.
Names
The use of general descriptive names, trade names, trademarks and the
like in this handbook does not entitle the reader to assume they may be
used freely by everyone. They are often protected registered trademarks
even if not marked as such.
17 Table of Pictures................................................................97
18 Index .................................................................................100
19 Certificates and Approvals .............................................101
Instruction Manual
Page 6 OCM F - Rev. 04 as of 18.02.2014
®
2 General
OCM F
Important
READ CAREFULLY BEFORE USE
KEEP IN A SAFE PLACE FOR LATER REFERENCE
This Instruction manual for the measurement transmitter OCM F is intended for
the initial start-up of the unit depicted on the title page.
Read the instructions carefully prior to use.
This Instruction manual is part of the OCM F delivery and shall be available to
users at any time. The safety instructions contained therein must be followed.
In case of selling the OCM F this technical description must be provided to the
purchaser.
The operation of the complete system is described in the separate manual
>Technical Instruction for Doppler Sensors< and >Installation Instructions for
Correlation and Doppler Sensors<.
Instructions on how to connect external level sensors are provided with the
standard delivery of the according sensors (e.g. NivuCompact, i-Series sensors…).
Instruction Manual
OCM F
OCM F - Rev. 04 as of 18.02.2014Page 7
3General Notes on Safety and Danger
3.1General Danger Signs
Cautions
are framed and labelled with a warning triangle.
This indicates an immediate high risk threatening life and limb.
Danger by electric voltage
is framed and labelled with the Symbol on the left.
Warnings
are framed and labelled with a “STOP“-sign.
This indicates a possible risk to persons as well as possible damage to facilities and material.
Notes
are framed and labelled with a “hand“
For connection, initial start-up and operation of the OCM F the following information and higher legal regulations (e.g. in Germany VDE), such as Exregulations as well as safety requirements and regulations in order to avoid accidents, must be kept.
All operations, which go beyond steps to install, to connect or to program the
device, must be carried out by NIVUS staff only due to reasons of safety and
guarantee.
3.2Special Danger Notes
WARNING
Germ contamination
Please note that due to the operation in the waste water field the measurement system and cables may be loaded with dangerous disease germs. Respective precautionary measures must be taken to avoid damage to one’s
health.
3.3Turn-off procedure
For maintenance, cleaning and repairs (authorised staff personnel only!) the
device shall be disconnected from mains.
Instruction Manual
Page 8 OCM F - Rev. 04 as of 18.02.2014
®
3.4 Device Identification
The instructions in this manual apply only for the type of device indicated on the
title page. The nameplate is fixed on the on the bottom of the device and contains the following:
− Name and address of manufacturer
− CE label
− Type and serial number
− Year of manufacture
− Ex-label (on Ex-version devices only) as mentioned in chapter Special Dan-
ger Notes.
It is important for enquiries and replacement part orders to specify article number as well as serial number of the respective transmitter or sensor. This ensures correct and quick processing.
OCM F
Fig. 3-1 Transmitter nameplate
This instruction manual is a part of the device and must be available for the
user at any time.
The safety instructions contained within must be followed.
In addition to this instruction manual please see the "Technical Instruction of
Doppler Sensors" as well as the "Installation Instruction for Correlation and
Doppler Sensors" to correctly install and to operate the complete system.
WARNING
Do not disable safety devices!
It is strictly prohibited to disable safety measures or to change the way
they work!
Instruction Manual
OCM F
OCM F - Rev. 04 as of 18.02.2014Page 9
2 Display
3 Keypad
4 Cable Glands
5 Terminal Clamp Housing
6 USB-B Interface
7 Pipe Sensor with retaining element
8 Wedge Sensor (Flow Velocity)
4 Overview and use in accordance with the requirements
4.1Overview
1 Clear view door
Fig. 4-1 Overview
4.2Use in accordance with the requirements
WARNING
Damage due to improper use
The device is exclusively intended to be used for purposes as described
above.
Modifying or using the devices for other purposes without the written consent
of the manufacturer will not be considered as use in accordance with the requirements.
Damages resulting from this are left at user’s risk.
The device is designed for a lifetime of approx. 10 years. After that period an
inspection in addition with a general overhaul has to be made.
The measurement device type OCM F including the respective sensor technology is intended to be used for continuous flow measurement and control tasks of
slight to heavy polluted media in part filled and permanent full pipes, channels or
similar.
Here the allowed maximum values, as specified in chapter 4.3 shall be strictly
kept. All cases which vary from these conditions and are not passed by NIVUS
GmbH in writing are left at owner’s risk.
Instruction Manual
OCM F
Page 10OCM F - Rev. 04 as of 18.02.2014
®
Transmitter Approval:
Note:
For installation and initial start-up the conformity certificates and test certificates of the respective authorities as well as applicable national regulations
shall be followed.
Important Note
The transmitter and the sensors always have to be installed outside of Exzones!
Ex Approval
The Ex-version of the transmitter is designed for use in areas featuring explosive
atmosphere according to Zone 1.
II(2)G [Ex ib] IIB
WARNING
The approval is only valid in connection with the respective indication on the
transmitter or the sensor nameplate.
The OCM F Ex version is adjusted to the NIVUS Doppler sensors, type KDA
requirements regarding the intrinsically safe system review according to
EN 60079-25.
In case of using sensors from third party manufacturers the operator must
carry out a system review according to EN 60079-25!
The required specifications of the OCM F Ex version can be taken from the
EC-type examination certificate IBExU07ATEX1081.
Note:
The Ex approval of the active sensors is part of the "Technical Instructions for
Doppler Sensors”.
Instruction Manual
OCM F
OCM F - Rev. 04 as of 18.02.2014Page 11
Power supply
85 to 260 V AC, 47 to 63 Hz
Power consumption
max. 18 VA (7 VA typical)
Enclosure
Material:Polycarbonate
Ex-Approval (optional)
II(2)G [Ex ib] IIB
Operating temperature
-20 °C to +60 °C (-4 °F to +140 °F)
Storage temperature
-30 °C to +70 °C (-22 °F to +158 °F)
Max. humidity
90 %, non-condensing
Display
back-lit full graphic LC display, 128 x 64 pixel
Operation
6 keys, menu driven in German, English, French and Polish
Inputs
1 x 4 – 20 mA for external level measurement (2-wire sensor)
Outputs
Controller
three-step controller, quick close control, adjustable slide valve posi-
4.3Specifications
or 24 V DC ±15 %, 5 % residual fluctuation
-
- Weight: approx. 1200 g
- Protection: IP 65
- Mounting wall or DIN rail mount
Ex: -20 °C to +40 °C (-4 °F to +104 °F)
-
- 2 x 0/4 – 20 mA, 122 bit resolution for external level measurement
and external set points
- 4 x digital input
- 1 compact Doppler active sensor, type KDA, connectable
- 3 x 0/4 – 20 mA, load 500 Ohm, 12 bit resolution, accuracy better
than 0.1 % (after adjustment)
- 5 switchable relays, loadable up to 230 V AC / 2 A (cos. ϕ 0,9 )
tion in error case, auto-flush function in case of blocked slide valve
4.4Installation of Spare Parts and Parts subject to Wear and Tear
We herewith particularly emphasize that replacement parts or accessories,
which are not supplied by us, are not certified by us, too. Hence, the installation
and/or the use of such products may possibly be detrimental to the device’s ability to work.
Damages caused by using non-original parts and non-original accessories are
left at user’s risk. Appropriate accessories and spare parts can be found in chapter 13.3.
Instruction Manual
Page 12 OCM F - Rev. 04 as of 18.02.2014
®
4.5 User’s Responsibility
In the EEA (European Economic Area) national implementation of the framework directive 89/391/EEC and corresponding individual directives, in particular the directive 89/655/EEC concerning the minimum safety and health requirements for the use of work equipment by workers at work, as amended,
are to be observed and adhered to.
In Germany the Industrial Safety Ordinance must be observed.
The customer must (where necessary) obtain any local operating permits re-
quired and observe the provisions contained therein. In addition to this, he must
observe local laws and regulations on
- safety of work materials and tools (safety equipment and maintenance)
- disposal of products (laws on wastes)
- disposal of materials (laws on wastes)
- cleaning (cleansing agents and disposal)
OCM F
- environmental protection.
Connections
Before operating the device the user has to ensure, that the local regulations
(e.g. for operation in channels) on installation and initial start-up are taken into
account, if this is both carried out by the user.
This instruction manual is a part of the device and must be available for the
user at any time.
The safety instructions contained within must be followed.
In addition to this instruction manual please see the "Technical Instruction of
Doppler Sensors" as well as the "Installation Instruction for Correlation and
Doppler Sensors" to correctly install and to operate the complete system.
It is strictly prohibited to disable the safety devices or to change the way they
work!
Instruction Manual
OCM F
OCM F - Rev. 04 as of 18.02.2014Page 13
2 Acoustic coupling layer with sonic converter behind
3 Temperature sensor
4 Electronics
5Pressure measurement cell (option)
6 Duct to pressure measurement (option)
7 Cable gland
8 Sensor cable
5Function principle
5.1General
The OCM F is a permanent measurement system for flow measurement and
flow control. The device is designed to be used primarily in slight to heavy polluted media with various compositions. It can be operated in partial and permanent filled channels and pipes with various shapes and dimensions.
The measurement method is based on the ultrasound Doppler principle.
Hence, it is indispensable for the system’s capability to work that the water
contains particles which are able to reflect the ultrasonic signal sent by the
sensor (dirt particles, gas bubbles or similar).
The OCM F utilises an active compact Doppler sensor Type KDA (after this
named >KDA sensor<). This KDA sensor is available as flow velocity and combi
sensor. The combi sensor Type “KDA“ can be combined with a sensorintegrated pressure measurement cell for hydrostatic level measurement.
1 Ground plate
Fig. 5-1 Construction of combi sensor Type “KDA“ with additional
pressure measurement cell
Instruction Manual
OCM F
Page 14OCM F - Rev. 04 as of 18.02.2014
®
2 Sensor enclosure
3Double nipple
4 Spigot nut
5 Cable gland
6 Sensor cable
7 Adjustment aid (screw M4)
8 Retaining element
1 Sensor head
Fig. 5-2 Construction pipe sensor, type KDA
5.2Level Measurement using Pressure
The combi sensor type “KDA“ additionally contains a hydrostatic level measurement via integrated pressure measurement cell.
The piezo-resistive pressure sensor operates according to the relative pressure
principle, i.e. the pressure of the standing water column above the sensor is direct proportional to the flow level.
During initial start-up procedure, the pressure sensor is going to be adjusted by
entering a manually investigated reference value.
Instruction Manual
OCM F
OCM F - Rev. 04 as of 18.02.2014Page 15
5.3Flow Velocity Detection
The flow velocity sensor, type “KDA“ operates according to the continuous Doppler principle (CW-Doppler) using 2 built-in piezo crystals with a slope of 45°.
The crystal surfaces are arranged parallel to the slope of the flow velocity sensor. One of the crystals continuously operates as ultrasonic transmitter, the other
one as receiver detecting the reflected ultrasonic signal.
The sensor enclosure enables acoustic coupling of the high-frequency ultrasonic
signal between piezo crystal/enclosure and enclosure/medium. Due to that reason an ultrasonic signal with an angle of 45° is sent permanently against the flow
direction of the medium to be measured. As soon as the signal hits dirt particles,
gas bubbles or similar a portion of the sonic energy is reflected, being converted
into an electric signal by the receiving crystal subsequently.
Caused by the movement of the reflecting particles in relation to the acoustic
source the frequency of the ultrasonic signal is shifted. The resulting frequency
shift is directly proportional to the particles’ movement within the medium and
hence represents the flow velocity.
The sensor processes the received reflection signal, converting it to be sent to
the transmitter.
Due to varying velocities within the flow profile, vorticity, rotation of single reflecting particles, surface waves etc. a frequency mixture is emerging. This mixture is
evaluated directly within the KDA sensor regarding statistic considerations related to average flow velocity. The frequency mixture is indicated on the transmitter
display in >I/O / v-Histogram< (see chapter 9.5.6).
It is recommended to verify the measurement if conditions are disadvantageous
from a hydraulic standpoint. Verification should not be based on the CW-Doppler
method since in this case it is not possible to spatially allocate recorded flow velocities.
In this case the VDI/VDE Directive 2640 is very helpful and important.
NIVUS recommends the portable meter Type >PVM/PD< or >PCM Pro< as calibration measurement or the NIVUS initial start-up service.
Instruction Manual
Page 16 OCM F - Rev. 04 as of 18.02.2014
®
OCF-Type
00
Enclosure
W0w all mount IP 65
Power Supply
AC85 - 265 V AC, 47-63 Hz
DC20 - 28 V DC
Approvals
0non
EIntrinsically saf e s ensor supply in Ex zone 1
OCF-00W0
Standard version for various pipe and channel shapes. 5 relays, 3 mA
outputs (galv. isolated), 1 mA input (galv. isolated w ith 2-w ire sensor
supply) or f or external level measurement , integrated 3-s tep controller
5.4 Unit Versions
OCM F
The OCM F transmitter is available in different versions. The tables below give a
brief overview on the various possibilities.
The transmitters primarily vary in terms of power supply and Ex-protection. The
current type of device is indicated by the article number, which can be found on
a weatherproof label on the bottom of the enclosure.
From this article key the type of device can be specified.
Fig. 5-3 Type key for OCM F measurement transmitter
Instruction Manual
OCM F
OCM F - Rev. 04 as of 18.02.2014Page 17
Transmitter:
min. temperature: - 30 °C (-22 °F)
KDA-Sensor:
min. temperature: - 30 °C (-22 °F)
6Storing, Delivery and Transport
6.1Receipt
Please check your delivery if it is complete and in working order according to
the delivery note immediately after receipt. Any damage resulting from transport
or transit shall be reported to the carrier instantly. An immediate, written report
must be sent to NIVUS GmbH Eppingen as well.
Please report any shortcoming due to delivery to your representative or directly
to NIVUS Eppingen within two weeks in writing.
Mistakes cannot be rectified later!
6.2Delivery
The standard delivery of the OCM F measurement transmitter contains:
6.3Storing
− the instruction manual with the certificate of conformity. All required steps to
correctly install and to operate the measurement system are listed herein.
− a OCM F transmitter
− a screwdriver with a 2.5 mm (0.098 in) blade for connecting the sensor inside
the terminal clamp housing
Additional accessories such as sensors, pressure compensation element (in
case of using sensors, type “KDA” with integrated pressure measurement cell
combi sensor), overvoltage protection, separate level measurements etc. depending on order. Please check by using the delivery note.
The following storing conditions must be strictly adhered to:
The devices must be protected from corrosive or organic solvent vapours, radioactive radiation as well as strong electromagnetic radiation.
Instruction Manual
Page 18 OCM F - Rev. 04 as of 18.02.2014
®
6.4 Transport
6.5 Return
OCM F
Sensor and Transmitter are conceived for harsh industrial conditions. Despite
this do not expose them to heavy shocks or vibrations.
Transportation must be carried out in the original packaging.
The units must be returned at customer cost to NIVUS Eppingen in the
original packaging.
Otherwise the return cannot be accepted!
Instruction Manual
OCM F
OCM F - Rev. 04 as of 18.02.2014Page 19
7Installation
7.1General
For electric installation the local regulations in the respective countries
(e.g. VDE 0100 in Germany) must be referred to.
The OCM F power supply must be separately protected by a 6 A slow-blow
fuse and has to be isolated from other facility parts (separate turn-off, e.g. by
using an automatic cut-out with >B< characteristics).
Before feeding the rated voltage the transmitter and sensor installation must be
correctly completed. The installation should be carried out by qualified personnel
only. Further statutory standards, regulations and technical rulings have to be
taken into account.
All outer circuits, wires and lines connected to the device must have a minimum
isolation resistance of 250 V. If the voltage exceeds 42 V DC an isolation resistance with 500 kOhm min. will be required.
The cross-sectional dimension of the power supply wires must be 0.75 mm
(0.03 in
tion rating is IP 65.
The maximum allowed switching voltage on the relay contacts must not exceed
250 V. According to Ex protection it must be checked if the devices power supplies must be integrated into the facility’s emergency shutdown conception.
2
) and must be in accordance to IEC 227 or IEC 245. The device protec-
2
7.2Enclosure Dimensions
Fig. 7-1 Wall mount enclosure
Instruction Manual
Page 20 OCM F - Rev. 04 as of 18.02.2014
®
7.3 Transmitter Installation and Connection
Important Note:
- Ensure the installation is completed properly!
7.3.1 General
- Comply with the existing legal and/or operational directives!
- Improper handling can cause injuries and/or damage to the devices!
The transmitters mounting place has to be selected according to certain criteria.
Please strictly avoid:
- direct sunlight (use weatherproof cover if necessary)
- objects with strong electromagnetic fields (e.g. frequency converters, electric
motors with high power consumption or similar)
- corrosive chemicals or gas
- mechanical shocks
- installation close to footpaths or travel ways
- vibrations
- radioactive radiation
The clear view door of the measurement transmitter is provided with a protection
foil for protection during transport and from scratches during assembly. This protection foil has to be removed immediately after the assembly.
Clear view door
The clear view door as well as the display of the measurement transmitter is
provided with a protection foil for protection during transport and from scratches
during assembly. This protection foil has to be removed immediately after the
assembly.
OCM F
If the view door or the display protection foil has been exposed to direct solar
radiation for a long period, it cannot be removed easily.
In this case view door or display can be cleaned using spirit or if necessary with
car polish. If this is not successful, door or display must be replaced by NIVUS.
This service is subject to charge.
7.3.2 Safety Instructions for the Cabling
If connections are placed to the OCM F, the following warnings and information
must be observed, in addition to the warnings and information found in the individual chapters for installation.
Instruction Manual
OCM F
OCM F - Rev. 04 as of 18.02.2014Page 21
7.3.3Hints for the avoidance of Electrostatic Discharge (ESD)
Important Note:
Since the OCM F does not require any power source please disconnect the
unit from mains prior to maintenance works to minimise danger and risks due
to electrostatic discharge.
The sensitive electronic components inside the device can be damaged by static
electricity, which can impair the device performance or even cause the device to
fail. The manufacturer recommends the following steps to prevent any damage
to the device caused by electrostatic discharges:
− Make sure to discharge any static electricity from your body before touching
the electronic modules of the unit (such as circuit boards as well as their
components). To do so touch a grounded metallic surface, such as the enclosure frame or a metal pipe.
− Avoid any unnecessary movements to prevent built-up static charges.
− Use antistatic containers or packaging to transport the static sensitive com-
ponents.
− Prevent damage to internal electronics from electrostatic discharges (ESD)
by discharging your body to a grounding point (e.g. use of wrist strap)
− Do not touch components sensitive to static electricity outside of antistatic
working areas. Always use antistatic floor covering and working surfaces if
possible.
7.4Electrical Installation
Important Note:
All installation work, which is described in the following section, must be carried out by NIVUS staff only due to reasons of safety and guarantee.
Instruction Manual
Page 22 OCM F - Rev. 04 as of 18.02.2014
®
7.4.1 Transmitter Connection
Important Note:
Each time before opening the enclosure please ensure to disconnect the
measurement system from any voltage.
Important Note
Never remove the faceplate!
Important Note
Water or dirt must not leak into the terminal housing. Please seal the housing
with the supplied lid and both screws respectively.
Installation Wall Mount Enclosure:
Ensure the installation is completed properly!
The most simple way to install a wall mount enclosure is to fasten a DIN rail with
a length of 210 mm (8.3 in.) and then to snap-on the enclosure.
It is possible to install the enclosure by using 3 screws as well. Use a pan head
screw with a head diameter of 5.5 ... 8.0 mm (0.22 ... 0.32 in.) for this. This
screw must be screwed into the mounting plate protruding 4 mm (0.16 in.). Then
hang the enclosure on the screw and additionally fix it with 2 more screws from
the terminal clamp housing. Please observe to screw them at least 40 mm into
the wall or 50 mm into appropriate dowels (to be set).
General
The wall mount enclosure can be equipped with cable glands and comes with
following installation parts:
OCM F
− 1 glands M16 x 1.5
− 2 glands M20 x 1.5
With the supplied glands the following outer cable cross-sections can be connected reliably:
− M16 x 1,5 3,5 mm – 10,5 mm
− M20 x 1,5 6,0 mm – 14,0 mm
To be able to use cable diameters outside of the tolerance, glands must be used
which ensure IP 65 minimum protection. Unused lead-ins have to be locked with
an appropriate dummy plug before the initial start-up.
In terms of electric connection please note the device configuration since unspecified inputs, outputs as well as power supply connections are not connected.
Instruction Manual
OCM F
OCM F - Rev. 04 as of 18.02.2014Page 23
Important note
Before the first connection it is necessary to have a slight pressure on the
screw of the clamping connection to ensure safe opening and a correct connection. All further clamps are tension spring clamps with screw clamps.
On power supply and relay clamps one copper wire with a maximum crosssection of 2.5 mm² (0.01 in.) can be connected per clamp. Connection is made
by using terminal clamps and a screwdriver with a 3.5 mm (0.14 in.) blade.
Fig. 7-2 Connection Enclosure
Instruction Manual
OCM F
Page 24OCM F - Rev. 04 as of 18.02.2014
®
Fig. 7-3 Clamp wiring OCM F
Instruction Manual
OCM F
OCM F - Rev. 04 as of 18.02.2014Page 25
7.4.2KDA Sensor Connection
Important Note:
Always disconnect the measurement system from mains prior to connecting
any sensors.
For use of the KDA sensors in the Ex-area, the sensor cables must not be
directed past the mechanical shield between the termination blocks. Use only
the two cable connections of the Ex-connection block!
The sensor cable has to be connected to the transmitter at the termination block
using tension spring clamps or connectors with screw clamps depending on version.
− Lead the sensor cable from outside through the cable gland.
− Now connect the sensor cables to the connection board as descripted in the
wiring diagram
− Tighten the cable gland to fix the sensor cable.
The diagram below applies in case of connecting a KDA flow velocity combi
sensor:
Fig. 7-4 Connection of 1 wedge or pipe sensor (no Ex), Type K0 or R0
Fig. 7-5 Connection of 1 KDA combi sensor (no Ex) with integrated
pressure measurement cell, Type KP
Instruction Manual
OCM F
Page 26OCM F - Rev. 04 as of 18.02.2014
®
Fig. 7-6 Connection of 1 KDA wedge or pipe sensor (Ex), Type K0 or R0
Fig. 7-7 Connection of 1 KDA combi sensor (Ex) with integrated pres-
sure measurement cell, Type KP
The pressure compensation element serves as connection socket for cable
extension at the same time.
Please observe not to exceed the maximum cable length of 250 m (820 ft)
between KDA sensor and transmitter by taking the maximum permissible resistance into account.
If the level measurement is carried out by a 2-wire probe, (NivuBar, NivuCompact 2-wire echo sounder or similar) which is supplied by the OCM F,
please follow the wiring diagram below:
Fig. 7-8 Connecting an ext. 2-wire sensor (no Ex) for flow level meas-
urement
Instruction Manual
OCM F
OCM F - Rev. 04 as of 18.02.2014Page 27
Fig. 7-9 Connecting a NIVUS i-Serial sensor for level measurement in
Ex-Zone 1
Important Note
The Zone 1 Ex approval of i-Series sensors is guaranteed thanks to protection
encapsulation category "Ex m". These sensors hence must not be connected
to the intrinsically safe terminal clamps (Ex ia) of the transmitter.
This would cancel the protection rating of the intrinsically safe terminal clamps
(47/46) of the transmitter and thus invalidate the according Ex approval.
Fig. 7-10Connecting an ext. 2-wire sensor (Ex) for flow level measure-
ment
If the mA signal for level measurement is provided from an external transmitter
(such as NivuMaster) connect to clamps as follows:
Fig. 7-11Connecting an external flow level measurement via NivuMaster
Instruction Manual
Page 28OCM F - Rev. 04 as of 18.02.2014
®
7.5OCM F Power Supply
Depending on the type of OCM F used, it can be supplied, with 85-260 V AC.
Also possible is a 24 V DC supply. The two slide switches located above the
terminals serve as additional power switch.
Fig. 7-12Slide switch position in terminal clamp housing
OCM F
A transmitter with 24 V DC cannot be operated with alternating current, just as
it is impossible to operate a 230 V AC transmitter with direct current.
When operated with alternating current, the direct current supply clamps 4 and 5
both provide a voltage of 24 V and max. capacity of 100 mA (turn on 24 V
switch!). Please note, when using this supply voltage (e.g. for digital inputs with
control signals), it must not be shielded through the complete switchgear in order
to maintain disturbing interferences on a low level.
Fig. 7-13AC model power supply
Instruction Manual
OCM F
OCM F - Rev. 04 as of 18.02.2014Page 29
Fig. 7-14DC model power supply
7.6Overvoltage Protection Precautions
Using overvoltage protection elements for sensor protection reduces the possible maximum cable length.
The series resistance is 0.3 Ohm per wire and must be added to the maximum permissible total resistance (please refer to the "Technical Instruction of
Doppler Sensors" manual)
For effective protection of the OCM F transmitter it is necessary to protect power
supply and mA inputs and outputs.
NIVUS recommends surge arrestors type:
>EnerPro< 220 Tr< (at 230 V AC) or
>EnerPro 24 V< (at 24 V DC).
For mA outputs and inputs type:
>DataPro 2x1 24 V / 24 V<
The flow velocity sensor is internally protected against overvoltage. In case of an
expected high hazard potential it is possible to protect the sensor by using a
combination of the Types:
For Ex-Sensors:
>SonicPro 3x1 24 V / 24 V Ex< and >DataPro 2x1 12 V / 12 V 11μH Tr (N)<
For Non-Ex-Sensors:
>SonicPro 3x1 24 V / 24 V< and >DataPro 2x1 24 V / 24 V Tr<
Instruction Manual
OCM F
Page 30OCM F - Rev. 04 as of 18.02.2014
®
Fig. 7-15Connecting the overvoltage protection for power supply and
analog inputs and outputs
Instruction Manual
OCM F
OCM F - Rev. 04 as of 18.02.2014Page 31
Fig. 7-16Overvoltage protection compact Doppler active sensor
Fig. 7-17Overvoltage protection compact Doppler active sensor (Ex)
When using the sensors in Ex areas the electrical values of overvoltage protection elements as well as capacities and inductance of the KDA sensor cable shall be considered additionally!
The NIVUS cable lengths below are allowed for use in Ex areas:
- unilateral overvoltage protection: 135 m
- double-sided overvoltage protection: 120 m
Please observe the non-reversed connection (p-side to transmitter) as well as
a correct, straight wiring supply.
Ground (earth) must lead to the unprotected side. Incorrect wiring will deactivate the overvoltage protection function!
Instruction Manual
Page 32 OCM F - Rev. 04 as of 18.02.2014
®
7.7 Regulator Mode
7.7.1 General
Knowledge in control technologies is necessarily required to correctly and
safely set the regulator!
Typically there are sluice gate valves, knife gate valves or iris gate valves with
electrically driven three-step controller in use. Analog-driven slide valves cannot
be used.
We recommend the following regulating times (time elapsed between valve
completely open and completely closed) for the selection of gate valves:
≤ 300 mm (11.8 in) diameter: min. 60 seconds
≤ 500 mm (19.7 in) diameter: min. 120 seconds
≤ 800 mm (31.5 in) diameter: min. 240 seconds
≤ 1000 mm (39.4 in) diameter: min. 300 seconds
For the correct driving as well as for error monitoring of the slide valve, the WayEnd-Switches “OPEN“ and “CLOSE“ as well as the torque switches “CLOSE“
are a mandatory requirement. These signals have to be connected to the digital
inputs 1-3 of the measurement transmitter. Please note to select gold-plated
contacts in order to ensure contact reliability. Connect a signal relay between
switches and measurement transmitter digital input to safely conduct the 10 mA
input current.
Analog position feedback to the measurement transmitter is not planned.
The measurement transmitter OCM F operates as a three-step controller with
surge detection, quick close control, slide valve monitoring and automatic flush
function.
To drive the regulating unit, the relays 4 and 5 are assigned as default. Hence,
relay 4 as “slide valve closed“ and relay 5 as “slide valve open“ are defined.
Analog input 2 is assigned for entering external setpoints (see Fig. 7-19).
OCM F
The assignment of the digital outputs for the regulator cannot be modified.
The input current on the digital inputs of the OCM F is 10 mA. Please ensure
contact reliability by selecting sufficient contact materials on the end switch of
the control slide valve.
Instruction Manual
OCM F
OCM F - Rev. 04 as of 18.02.2014Page 33
1 Hand-slide valve
2 Ultrasonic sensor P-Series
3 Regulation-slide valve
4 Install pipe sensor using nozzle or tapping saddle
7.7.2Construction of Measurement Section and Control Section
You can find a detailed description of measurement and control sections in the
"Installation Instruction for Correlation and Doppler Sensors" manual.
Fig. 7-18Setup of a controlled system such as a discharge control
Instruction Manual
Page 34OCM F - Rev. 04 as of 18.02.2014
®
7.7.3Connection for Controller Operation
OCM F
Fig. 7-19Wiring diagram for controller operation
Instruction Manual
OCM F
OCM F - Rev. 04 as of 18.02.2014Page 35
max. slide valve runtime
max. flow
7.7.4Control Algorithm
If the regulator function is selected (see also Chapter 9.4.8), relay 4 is used for
“CLOSE SLIDE VALVE“ and relay 5 for “OPEN SLIDE VALVE“ function. This
assignment cannot be modified.
The digital inputs are free programmable for position feedback. To ensure correct and failsafe slide valve drive necessarily use the messages "PATH OFF“,
"PATH ON“ and "TORQUE CLOSED“ of the slide valve drive.
The input current per digital input is 10 mA.
In case of driving the slide valves via the digital inputs always use all the
3 messages. Activating one message only may result in disturbed regulator
operation.
The regulator can be operated with external or internal set point.
External setpoints have to be routed to analog input 4 (clamps 41+ and
42 GND).
In case of using a 4-20 mA signal as external setpoint, this signal can be monitored for cable breaks and short circuits. If errors should occur the OCM F is going to access the internal setpoint ( in case of using external 4-20 mA setpoints and error monitoring always set the internal setpoint additionally!).
The following equation applies for the internal calculation of the slide valve control time:
control time = (setpoint – flow
actual value
) • P_factor •
Instruction Manual
Page 36 OCM F - Rev. 04 as of 18.02.2014
®
8 Initial start-up
8.1 Notes to the User
OCM F
For proper start-up of the entire system it might be necessary to additionally
refer to the accessories manuals below.
>Installation instructions for Correlation and Doppler sensors<
>Technical instructions for Doppler sensors<
These manuals are part of the accessories standard delivery.
Before you connect and operate the OCM F you should strictly follow the notes
below!
This instruction manual contains all necessary information to program and to
operate the device, addressing qualified technical staff who have appropriate
knowledge about measurement technology, automation technology, information
technology and waste water hydraulics.
To ensure a correct function of the OCM F this instruction manual must be read
thoroughly!
It is vital to read and comply with the safety instructions!
The OCM F must be wired in accordance with the wiring diagram, see Fig. 7-3!
If any problems regarding installation, connection or programming should occur
please contact our technical division or our service centre.
NIVUS GmbH
Service hotline, Phone +49 (0)7262 9191-888
or by e-Mail to: Hotline-worldwide@nivus.com
For initial start-up of the complete system, the instruction manuals of the accessories have also to be read. These manuals are included in the accessories delivery.
8.2 General Principles
The initial start-up is not allowed until the installation has been finished and
checked. To exclude faulty programming this instruction manual must be read
before the initial start-up. Please get familiar with the OCM F programming via
display and keyboard by, reading the instruction manual before you begin to
program the device.
After transmitter and sensors are connected (see chapters 7.4.1 and 7.4.2) the
parameters must be set.
Instruction Manual
OCM F
OCM F - Rev. 04 as of 18.02.2014Page 37
2 Escape key
3 Confirm key (ENTER)
2 Flow
3 Total
4 Relay status
8.3Keypad
In the most cases all you need is:
- geometry of the measurement place and dimensions
- used sensors and positioning
- display units
- span and function of analog and digital outputs
The OCM F user surface was designed in a way that even unfamiliar users are
able to easily set up basic settings in dialog mode which ensure reliable device
operation.
For extensive programming, difficult hydraulic conditions, in case of absence of
expert staff or if a setup and error protocol is required, the programming should
be carried out by the manufacturer or an expert company which is authorised by
the manufacturer.
For data input there is a comfortable 6-button keypad available.
Due to mechanic and electronic reasons the keypad has a membrane cover with
abrasion-proof labelling.
8.4Display
1Arrow keys (control)
Fig. 8-1 Keypad
OCM F has a large back-lit graphic display with a resolution of 128 x 64 pixel.
This enables convenient communication.
1 Name of measurement place
Fig. 8-2 Main screen
Instruction Manual
OCM F
Page 38 OCM F - Rev. 04 as of 18.02.2014
®
2 Velocity
3 Medium temperature
4 Current date / system time
5 Digital input status
RUN
Standard operation mode. It allows to display day totals and, if
PAR
This menu is the most extensive of the OCM F. It is for the com-
I/O
This menu includes information about internal operation of the
CAL
Set maximum and minimum measurable flow velocity here. Calibra-
EXTRA
This sub-menu includes basic display settings: contrast, language,
After confirming with >ENTER< the auxiliary screen appears.
1 Level
Fig. 8-3 Auxiliary screen
There are 5 basic menus available for selection, programming and diagnostic
options which are visible in the display headline. These menus can be accessed
via the arrow buttons >left< or >right<.
available, error messages. Furthermore it is possible to set the time
of 24 h-totalizing and to reset the daily totalizer.
plete parameter setting of dimensions of the measurement place,
sensors, analog and digital inputs and outputs and regulator function, damping and system reset.
OCM F. All current values can be displayed, as well as the values
of analog and digital outputs and relays. Additionally it is possible to
indicate the current flow velocity as well as the flow velocity distribution.
tion of analog outputs as well as simulation of analog and digital
outputs and calculated volumes is possible too.
units, decimal digits, system times and totalizer pre-sets.
Instruction Manual
OCM F
OCM F - Rev. 04 as of 18.02.2014Page 39
navigates downward in the respective submenu (e.g. PAR/
press once ; toggle between indication mode and overview menu
press once ; toggle between indication mode and overview menu
delete values
press once; toggle from RUN menu to overview menu
8.5Operation Basics
The entire operation of the OCM F is menu driven.
To navigate within the menu structure use the 4 control keys (see chapter 8.3).
>up<
- navigates upward in the respective submenu (e.g.
PAR/measurement place/name)
- select pre-set values e.g. units (m, cm, l/s, m³/s etc.)
- increase values
>down<
>left<
>right<
>ESC<
>ENTER<
-
measurement place/name)
- select pre-set values e.g. units (m, cm, l/s, m³/s etc.)
- decrease values,
- set decimal point
-
(main menu)
- jump across in main or submenu
- jump across between identical measurement values (e.g. span of
analog outputs 1 – 3)
-
(main menu)
- jump across in main or submenu
- jump across between identical measurement values (e.g. span of
analog outputs 1 – 3)
-
- each key action in menu jumps back one level until
RUN menu
-
(main menu)
- activate a submenu
- accept and store values, units and so on
Instruction Manual
Page 40 OCM F - Rev. 04 as of 18.02.2014
®
9 Parameter Setting
9.1 Basics
The transmitter in the background operates with the settings which have been
entered at the beginning of the parameter setting. The system will not ask to accept the modifications before the settings or modifications have been finished.
Enter the PIN below in order to accept modifications.
Never give the PIN code to any unauthorised persons. Even do not l eave the
code next to the equipment or write it down on it. The code number protects
against unauthorized access.
The unit will accept modified parameters if entered correctly performing a restart subsequently. The OCM F is ready for operation after approx. 20-30 seconds.
It is possible to save modified parameters at the end of the parameter setting
procedure.
Entered parameters may be saved at the end of the setting procedure (>accept
changes<) or rejected by pressing >cancel<. It is also possible to jump back to
the previous level using the >back< function. This enables the user to modify
settings which might have been forgotten without the need to buffer previously
modified settings.
2718
OCM F
type in 2718 if prompted.
Fig. 9-1 Screen on end of parameter setti n g
Modifications concerning language, units and contrast do not require the PIN
code to be entered as these settings influence just the way of representation and
not measurement or output.
If parameter settings are not going to be modified but just verified by selecting
each parameter, there will be no PIN request at the end of the dialog.
Instruction Manual
OCM F
OCM F - Rev. 04 as of 18.02.2014Page 41
Day values
Please select submenu >Info<. This menu contains the total flow values of the
9.2Operation Mode (RUN)
After mounting and installing sensor and transmitter (see previous chapters) activate the power supply.
On initial start-up the unit will prompt the language selection:
Fig. 9-2 Language selection
Select the desired language with the >up< or >down arrow keys< and confirm
with >ENTER<.
This menu is a display menu for saved day totals and error messages. Containing the following submenus, it is not required for parameter setting:
Fig. 9-3 Operation mode selection
past 7 days (see Fig. 9-4).
Presumed the transmitter was operated without any interruption in the past
seven days. Otherwise it shows the total for the uninterrupted days of operation.
Only the first 3 days will be indicated after selecting. Browse to other days by
using the arrow key >down<.
The oldest day total will be overwritten as soon as the 24h-total of the 8. day
has been created des (circular memory function).
The flow totals of 24 hours will be indicated. Totalization normally is carried out
at 00:00 h (midnight). If desired, this value can be modified under RUN – day
values - cycle (see Fig. 9-5).
Additionally, you can erase all day counters under >erase counter<. Due to
safety reasons it is required to enter the PIN >2718< and confirmation with
ENTER after erasing.
Instruction Manual
OCM F
Page 42 OCM F - Rev. 04 as of 18.02.2014
®
2 Day values
3 Current day with cumulated total
4 24 h-day totals
5 Date
2 programmable time of future totalising in <hours : minutes : seconds>
Error messages
This menu is to monitor any interruptions in the unit function. Errors are go-ing
1 Time of day totalising
Fig. 9-4 Day values
1 current time of day totalising
Fig. 9-5 Time of day totalising
If the transmitter is disconnected from mains at the time of totalising set, it is
not possible to create or to save a total for the respective day.
If the unit has been shut down temporarily within 24 hrs. the flow rate missed
during the inoperative period is not going to be considered for totalising. There
will be no averaging interpolated replacing the lost flow rate!
to be saved and ordered by type of error, date and time.
Selecting the menu will always indicate the latest/last error message. Browse
through error messages using the keys >left< and >right<.
Pressing the >ENTER<-key will delete all error messages one by one.
The maximum number of stored error messages is limited to 10. The oldest of
11 error messages will be overwritten as soon as saved old error messages
are not going to be erased (circular memory function).
Following error messages are possible:
- “Doppler-Sensor“ - at interruption of the sensor communication or with de-
fective KDA sensor
- "external level “ – at interruption of communication to external level meas-
urement or if value falls below the limit of 3.5 mA
- "external level short-circuit“ – in case of exceeding the input signal 20 mA
- "temperature“ – in case of exceeding maximum or minimum permissible
temperature ranges by +/-10 °C (as from -30 or +60 °C) or if the temperature
sensor should be defect
- “ext. set point“ – if external set point is not available
- “control unit“ – in case of error of the control unit ("Valve OPEN", "Valve
CLOSED", "Valve TORQUE")
Instruction Manual
OCM F
OCM F - Rev. 04 as of 18.02.2014Page 43
2 Number of stored error messages
3 Time of error message
4 Date of error message
5 Type of error / error message
1 Error number
Fig. 9-6 Error message
Remaining errors are NOT going to be written into the error memory anew if
once they have been deleted. As soon as the error occurs repeatedly (or if the
power supply has been interrupted for a short period) the same error will be
saved into the error memory again.
Instruction Manual
Page 44OCM F - Rev. 04 as of 18.02.2014
®
Info
This point provides comprehensive information on unit type, transmitter serial
9.3Display Menu (EXTRA)
This menu allows to modify settings such as units, language, system time as
well as the display itself. The following submenus are available:
Fig. 9-7 Extra-submenus
Due to reasons of limited space it is not possible to indicate the entire menu on
the display. This can be seen from the black scroll bar on the right-hand side of
the display.
Scroll through the menu using the up and down keys.
OCM F
no. and software version (see Fig. 9-8). The menu is subdivided into 4 pages.
Pressing the arrow buttons >left< or >right< will take you through the pages.
Among other information these pages contain information on last parameter
setting / parameter change as well as mains power failure which might have
been occurred.
Fig. 9-8 System information
Fig. 9-9 Additional system information
Instruction Manual
OCM F
OCM F - Rev. 04 as of 18.02.2014Page 45
Unit system
Here you can select between indication and calculation. Select from: metric
Units
This menu contains the following sub menus:
Format
Choose display formats for velocity and totals here.
Language
Select from German, English, French or Polish.
Display
Allows to adjust display settings regarding contrast. Use >down< to de-
system (litre, cubic meters, cm/s etc.), English system (ft, in, gal/s, etc.) and
American system (fps, mgd. etc.)
Fig. 9-10Selecting the unit system
- Flow rate
- Velocity
- Level
- Total
For each of these four measured values you can select a unit which appears
on the display. Depending on the unit system selected, there are various units
available.
Fig. 9-11Selecting the units
The position of the decimal point can be defined as displayed in Fig. 9-12. The
unit automatically determines the decimal digit position of the current flow rate
indication and hence cannot be set to a fixed position.
Fig. 9-12Selecting the display format
crease; and >up< to increase values in 5 %-steps.
The display contrast can be adjusted on the main page of the menu as well.
Instruction Manual
OCM F
Page 46 OCM F - Rev. 04 as of 18.02.2014
®
System time
In order to perform various control or memory functions, the unit includes an
Totalizer
This menu allows to newly set the totalizer indicated on the main screen. This
internal clock saving dates of year, weekdays and week numbers. The clock
settings can be modified if required (different time zones, summer time / winter
time etc.). First select the menu point “Info”:
Fig. 9-13 system time - submenus
The complete system time is indicated after the settings have been confirmed:
Fig. 9-14 complete system time
This menu point is for indicating purposes only. Hence the system time can-not
be adjusted here. Modifications can be carried out in the individual menus >set
date< and >set time< (Fig. 9-13). Select between 12 h or 24 h mode in >set format< submenu.
feature is normally used when replacing a transmitter which has to indicate the
same value as before replacement.
After the new value has been set confirm using the "Enter“-key and type in the
PIN “2718“. (2 faulty entries allowed). Otherwise the modified value will not be
accepted.
Fig. 9-15 Totalizer modification
Fig. 9-16 PIN-Code request
Instruction Manual
OCM F
OCM F - Rev. 04 as of 18.02.2014Page 47
Name
NIVUS recommends to coordinate and to define names according to names
9.4Parameter Menu (PAR)
This menu is the most important regarding the unit settings. It nevertheless is
sufficient in most cases to set only some essential parameters, which usually
are:
− Channel shape
− Channel dimensions
− Sensor types
− Analog output (function, measurement range and measurement span)
− Relay output (function and values)
All other functions are additions which are required in special cases only.
(Regulator mode or for special hydraulic applications). These settings are normally made with the help of our service personnel or by an authorised ex-pert
company.
The parameter menu >PAR< includes eight partially very extensive submenus
which are described individually on the following pages.
9.4.1Parameter Menu „Measurement Place“
This menu is one of the most important basic menus for parameter setting as the
measurement place is going to be defined here.
The menu cannot be indicated completely due to restricted display space. Similar to many well-known PC applications, this is readily identifiable from the black
bars on the right-hand side of the screen.
stated in the respective documents. Names may contain up to 15 letters.
After the submenu >Name< has been selected the basic setting „NIVUS“ will
come up. There is a cursor blinking below the first digit.
Fig. 9-17submenu – name
Use "Up“ and "Down“ keys to scroll the menu.
Underneath the measurement place name you can find a table with 20 lines containing all uppercase and lowercase letters as well as a large number of special
characters (see Fig. 9-18). Use the arrow keys >up< and >down< to jump across
2 lines up or down at each key action.
Instruction Manual
OCM F
Page 48 OCM F - Rev. 04 as of 18.02.2014
®
2 Selected character
3 Selection list
Channel shape
You can select between following standard profiles according to ATV A110:
To complete the name of the measurement place use the four arrow keys and
confirm your selection with >ENTER<. The cursor subsequently will jump one
digit to the right enabling you to choose the next character.
Delete unused characters by entering space. By pressing the both keys >right<
+ >down< or + >up< you can move the cursor to the right. Using the keys >left<
+ >down< or + >up< will move the cursor to the left.
1 Current name (of the measurement place)
Fig. 9-18 Setting the name (of the measurement place)
You can obtain the same movements as well if you move the cursor to the
rightmost or leftmost edge of the table by using >left< or >right<. As soon as the
cursor has reached the rightmost or leftmost edge of the table it will jump to the
desired position by one step on pressing >left< or >right< again.
Exit this part of the program with ESC. Decide to accept the new name, to correct the new name (= Back) or to abort the procedure subsequently
(see Fig. 9-19).
Type in the respective channel dimensions depending on the profile chosen
Fig. 9-20Channel shape selection
Select channel shape with >Up< and >Down< keys.
Confirm selection with >Enter<.
The selected profile will be indicated in the bottom line of the display.
Fig. 9-21Selected profile screen
If the existing profile does not comply with the options to select from, choose
>Custom shape< in this case
Confirm with >Enter<.
After having >custom shape< selected, first choose >channel dimensions<.
before.
Please observe indicated units!
Choosing >Custom shape< will indicate a table of 32 possible breakpoints on
the display. As described above, enter the relations between height-width or
height-area and enter the according value pairs.
Fig. 9-22List of breakpoints for >Custom shape<
Instruction Manual
OCM F
Page 50OCM F - Rev. 04 as of 18.02.2014
®
Sludge level
The sludge level set is going to be calculated as non-moving channel sub-area
Low-flow volume
This parameter serves to suppress lowest movements or apparent volumes
Q
: measurement values lower than this one will be set to >0<. Only positive
V
: Low-flow volumes in applications with large profiles and filling levels can
In order to define the zero point of the channel start by entering 0 – 0 in breakpoint 1. All further breakpoint can be set freely regarding height as well as
width/area.
There may be different distances between individual level points. Furthermore it
is not required to use all of the 32 breakpoints possible. The OCM F however is
going to use a linearization function between the breakpoints. Decrease the distance between breakpoints in case of heavy and irregular fluctuation within the
area.
Fig. 9-23breakpoints for >Custom shape<
and will be subtracted from the wetted hydraulic total area prior to performing
flow calculation.
Q
min.
arising. Used mainly to measure overflow volumes in constructions which are
permanently flooded by receiving water.
min
values are allowed to be set. These values are going to be considered as absolute values and therefore have positive as well as negative effects.
min
be suppressed by means of this parameter. Lowest velocity fluctuations within
longer periods of time may cause apparently large volume fluctuations which
cannot be gated by using the value of Qmin.
Flow velocities below this value will be set to „0“ which will set the calculated
volume to „0“ as well.
Only positive values are allowed to be set. These values are going to be considered as absolute values and therefore affect positive as well as negative
velocities!
Both setting options of low-flow suppression have an OR relation between
each other.
Instruction Manual
OCM F
OCM F - Rev. 04 as of 18.02.2014Page 51
9.4.2Parameter Menu “Level“
Fig. 9-24Selection low-flow volumes
The suppression of low-flow volumes is no offset but a limit value.
Fig. 9-25Menu level measurement
This menu defines any parameter regarding level measurement. The start
screen depicted below as well as the parameters to be set may vary depending
on the sensor type selected.
Fig. 9-26Example in case of external level sensor
Basically determine the sensor type first (see Fig. 9-27).
Fig. 9-27Determine the sensor type
Instruction Manual
OCM F
Page 52OCM F - Rev. 04 as of 18.02.2014
®
Sensor type
No.
Pressure trans.
01
Level measurement by a KDA combi sensor which is directly
Constant level
02
Use this point to set parameters for constantly full filled pipes and chan-
ext. Sensor
03
In this case the level is measured by using external transmitters such
connected to OCM F according Fig. 7-5.
Offset installation e.g. due to sedimentation or high dirt load is possible.
Level measurement in case of flooding is possible as well.
1 Sedimentation or soiling
Fig. 9-28Sensor type 1: Pressure int.
nels. Such applications normally do not require level measurements.
The constant filling level must be set under >value< and is used for flow
calculation. This parameter is helpful too at initial start-up or in case of
performing tests without having level values available.
Fig. 9-29Sensor type 2: Constant level
Type NivuMaster with echo sounder or an external 2-wire sensor such
as NivuCompact (non-Ex) or i-Series sensor for Ex-Zone 1. Connect as
shown in
Fig. 7-8, Fig. 7-11 or i-Series connection plan Fig. 7-9.
Instruction Manual
OCM F
OCM F - Rev. 04 as of 18.02.2014Page 53
ext. Sensor (Ex)
04
Level measurement by external Ex 2-wire sensor supplied by OCM F
Mounting height
Only visible, if sensor type no. 1 is selected. This value is set to 5 mm
Fig. 9-30Sensor type3: 22 wire probe
e.g. a pressure probe, type NivuBar Plus or echo sounder type NivuCompact). Connect as described in Fig. 7-10.
Fig. 9-31Sensor type 4: 2-wire probe Ex
Please select the appropriate level measurement method prior to planning the
facility.
The transmitter will access only the clamps which have been programmed in
the menu!
Due to this reason please observe correct sensor connection
(see chapter 7.4.2)
(0.19 in) as KDA combi sensors in standard, which is the position of the diaphragm above the channel bottom. There is no need to modify this value
unless the sensor is going to be installed higher or lower. If installed higher
(on a block or similar) enter 5 mm (0.19 in) plus additional height, if installed
lower subtract from 5 mm (0.19 in) and enter the total height.
Instruction Manual
OCM F
Page 54 OCM F - Rev. 04 as of 18.02.2014
®
Value
Enter a fixed value for the level here. Only visible, if sensor type no. 2 is se-
Measurement range
Select between measurement ranges 4-20 mA or 0-20 mA. Only visible,
Value at 0 mA
Enter a level value for 0 mA here.
Value at 4 mA
Enter a level value for 4 mA here.
Value at 20 mA
Enter a level value for 20 mA here.
Offset
This entry will move the zero point of the external sensor. Only visible, if sen-
Damping
This value is to damp a fluctuating signal of an external level measurement.
i-3
i-6
i-10
i-15
lected. This value is set to 0.1 m (3.9 in) as standard.
if sensor type no. 3 is selected.
Only visible if 0-20 mA has been selected as measurement range for sensor
type no. 3. This value is set to 0 m (0.0 in) as standard.
Only visible, if sensor type no. 3 or 4 is selected.
This value is set to 0 m (0.0 in) as standard.
Only visible, if sensor type no. 3 or 4 is selected.
This value is set to 4 m (13.1 ft) as standard.
sor type no. 3 or 4 is selected. This value is set to 0 m (0.0 in) as standard.
Only visible, if sensor type no. 3 or 4 is selected.
This value is set to 0 s as standard and can be set to up to 10 s.
9.4.3 Information on how to connect i-Series sensors
The i-Series sensors feature pre-programmed measurement ranges. Please
refer to the according instruction manual. The sensor can be operated even
without HART modem.
Setting the parameter "Value at 20 mA" requires to enter the measurement
span of the sensor. Depending on the installation height of the sensor a negative offset value may be additionally necessary.
4 mA (empty) 0% span
Distance to sensor face in m
20 mA (full) 100% span
Distance to sensor face in m
Measurement span
(value at 20 mA)
Fig. 9-32 i-Series sensors measurement range
3.0 6.0 10.0 15.0
0.125 0.300 0.300 0.500
2.875 5.7 9.7 14.5
Instruction Manual
OCM F
OCM F - Rev. 04 as of 18.02.2014Page 55
Sensor type
Select between wedge or pipe sensor. The standard setting is wedge sensor.
Mounting height
This menu point is to modify the installation height of the flow velocity sensor.
Install. direction
Installation direction is set to “positive“ per default. This parameter should not
9.4.4Parameter Menu „Flow Velocity“
Fig. 9-33Sensor settings
The standard setting is 15 mm (0.59 in) which is equivalent to the position of
the sensor centre above the channel bottom. This setting does not need to be
modified unless the sensor has been installed higher or lower. If the sensor
has been installed higher enter the additional mounting height plus 15 mm
(0.59 in) and modify parameter “h-crit” (see Chap. 9.6.2) additionally, if installed lower subtract the missing height from 15 mm (0.59 in) and enter
overall height.
Never countersink flow velocity sensors without pressure measurement cell
deeper than 8 mm into the channel bottom (see "Installation Instruction for
Correlation and Doppler Sensors")!
Never countersink flow velocity sensors with integrated pressure measurement cell into the channel bottom!!!
Otherwise the measurement might fail!
be modified. It is going to be used only for special applications where the flow
velocity sensor is heading upstream (unlike heading downstream towards the
flow direction as in standard applications) but is to detect positive velocities
however. This is the only case which requires to set “negative“ here.
9.4.5Parameter Menu „Digital Inputs“
Fig. 9-34Digital inputs – submenu
Select from digital inputs 1 – 4 using the >left< or >right< arrow keys as long as
the regulator function is active. This section enables to set and the digital input
signals „switch OPEN“, „switch CLOSE“ and „torque switch“.
The OCM F requires these inputs for regulator operation.
The function >Stop v-measurement< is exclusively available for digital input 4.
Instruction Manual
OCM F
Page 56 OCM F - Rev. 04 as of 18.02.2014
®
Function
Each digital input chosen by pressing >left< or >right< will be assigned to a
Logic
Toggle between inverse and non-inverse input by pressing >up< or >down<
Name
The name of a digital input can have up to 3 characters. These names will be
Fig. 9-35 Digital inputs functions
certain function as long as the regulator function is active.
Select from:
- „inactive“ (The digital input has no function.)
- DI1 „torque switch“ (the torque switch for the closed condition is connect-
ed to the selected digital input.)
- DI2 „switch CLOSE“ (the slide end switch for closed condition is routed to
the selected digital input.)
- DI3 „switch OPEN“ (he slide end switch for open condition is wired to the
selected digital input.)
- DI4 „control v-measure“ (he digital input is used to block/release the
measurement using an external signal such as flood messages or limit values for measurement start or similar. Indicated as: 0 l/s, inputs and outputs
set will de-energise)
arrow keys. This means that e.g. slide valve signals can be configured as being normally closed and cable breaks can be detected without any problem.
The default setting is „non-inverse“.
indicated in the main screen and in overview menu; see overview menu. Set
the names as described in chapter
Please observe that the digital inputs are passive and therefore shall be supplied by an external 24 V DC power supply!
The signal current is 10 mA. Please ensure reliable conductivity by using relay
or end switch contacts made of high quality material.
9.4.1.
Instruction Manual
OCM F
OCM F - Rev. 04 as of 18.02.2014Page 57
Function
The selected analog output is going to be assigned to a function.
2 Start measurement
3 Stop measurement (obstruction, standing water or no water etc.)
9.4.6Parameter Menu “Analog Outputs“
Fig. 9-36Menü Analogausgang
Innerhalb dieses Menüs kann zwischen den Analogausgängen 1-3 mit den Pfeiltasten >rechts< oder >links< gewählt werden.
Select from various functions:
- Not active (no analog signal output)
- Flow rate (output of analog signal which is proportional to calculated flow
volume)
- Level (output of analog signal which is proportional to measured filling level)
- Velocity (output of analog signal which is proportional to mean flow velocity
averaged from measured individual velocities)
- Temperature (output of measured water temperature as analog signal)
- Constant current (calculates from the ratio between valid readings to total
readings resulting from velocity measurement, output as analog signal). This
function is not conceived for control purposes, but for monitoring, remote
analysis and for determination of sensor cleaning intervals.
1 Analog output
Fig. 9-37Analog output signal quality
The Fig. 9-37 signal quality shows the analog output signal if the signal quality
has been programmed. The signal will steeply rise at the beginning of the measurement (2).
The signal is damped in order to avoid heavy signal fluctuation.
Instruction Manual
OCM F
Page 58 OCM F - Rev. 04 as of 18.02.2014
®
Span
After having a function selected (flow, level, velocity, signal quality or tempera-
Value at 0 mA
Enter the measurement value at 0 m.
Value at 4 mA
Enter the measurement value at 4 mA.
Value at 20 mA
Enter the measurement value at 20 mA.
Error mode
If this parameter has been enabled it is possible to set the analog output to a
As soon as e.g. the sensor is going to be removed from the medium or no velocity can be measured at all (3), the signal first slopes gently getting steeper
subsequently.
After selecting >Function< it is possible to set “span“, “value at 0/4” or 20 mA
and “error mode” for flow, filling level, velocity, temperature or signal quality (see
Fig. 9-38).
Constant current (the analog output can be set to output a constant current
which is independent from any readings). After choosing the function a new window comes up in order to enter the desired initial current value (max.
20.475 mA, see Fig. 9-39).
Fig. 9-38 Selection flow
Fig. 9-39 Selection constant current
ture) toggle between measurement ranges of 0-20 mA or 4-20 mA here.
Example:
A measurement place is partially tending to backwater formation. Negative
values shall be recorded as well; the following recording or process conducting
system however has only one analog input left available. In this case the analog output signal is set to have a "floating” behaviour.
This means that flow = 0 is going to output the 12 mA analog signal:
4 mA = -100 l/s
20 mA = 100 l/s
Backwater will cause the analog signal to decrease, positive flow will cause
the signal to increase.
defined value in case of error. After activation the points “Error input mask” as
well as “Value at errors” can be selected (see
Fig. 9-40).
Instruction Manual
OCM F
OCM F - Rev. 04 as of 18.02.2014Page 59
Error input mask
This point is accessible only if error mode has been activated. Output signals
Value at errors
Visible only if error mode has been enabled. This parameter is to define the
can be assigned to the respective error here. Available are Doppler-sensor,
external level, temperature, external set point input and slide valve. Velocity is
currently not yet available.
Choose the desired function with the >up< or >down< arrow keys and confirm
by pressing ENTER. A tick will appear as soon as the function has been confirmed. Pressing ENTER once more will deactivate the function again. Leave
this point by pressing ESC, see Fig. 9-41
All errors will be saved in the error memory (see Chap. 9.2 section “Error messages”).
Fig. 9-40Extended submenu analog output
Fig. 9-41Error input mask
desired analog output condition if an error should occur (see also Fig. 9-42)
The following functions are available:
- hold last value (holds the last value prior to error)
- constant 0.0 mA
- constant 3.6 mA
- constant 4.0 mA
- constant 20.457 mA
Fig. 9-42Programming error output
Instruction Manual
Page 60 OCM F - Rev. 04 as of 18.02.2014
®
Limit flow rate
Relay will energise if a flow limit value (to be set) has been exceeded and will
Limit level
Relay will energise if a level limit value (to be set) has been exceeded and will
Limit velocity
Relay will energise if a velocity limit value (to be set) has been exceeded and
Limit temperature
Relay will energise if a temperature limit value (to be set) has been exceeded
Volume impulse pos.
Relay will output volume-proportional impulses if the flow direction is positive.
Volume impulse neg.
Relay will output volume-proportional impulses if the flow direction is negative
Error signalling
Error message output via relay. >Error input screen< can be selected as soon
Error input screen
It is possible to assign the relay output to the respective error here.
9.4.7 Parameter Menu "Digital outputs“
Fig. 9-43 Relay selection menu
This menu allows to select between relays 1-5 using the >right< or >left< arrow
keys.
Relays 4 (close slide valve) and 5 (open slide valve) are dedicated to regulator
functions if the regulator has been enabled. It is not possible to modify this
assignment!
Select parameter “relay function” to indicate available functions.
OCM F
Fig. 9-44 Relay outputs – submenu
de-energise if flow falls below a second limit value (to be set).
de-energise if level falls below a second limit value ( to be set).
will de-energise if velocity falls below a second limit (value to be set).
and will de-energise if medium temperature falls below a second limit (value to
be set).
Weighting and impulse duration are free programmable
(= backwater). Weighting and impulse duration are free programmable.
as this parameter has been activated.
Instruction Manual
OCM F
OCM F - Rev. 04 as of 18.02.2014Page 61
The choices are:
Switching mode
It is possible to select between >normally open< and >normally closed<.
Switch point on
Defines the “ON” point for the selected limit value. This value is required for all
Switch point off
Defines the “OFF” point for the selected limit value. This value is required for
Time delay on
The “ON” event in case of reaching the limit value can be delayed by up to
Doppler sensor, external fill level, temperature, external setpoint and slide
valve. The velocity is not available.
Choose the desired function with the >up< or >down< arrow keys and confirm
by pressing ENTER. A tick will appear as soon as the function has been confirmed. Pressing ENTER once more will deactivate the function again, pressing ESC will exit the menu (see also Fig. 9-45). All errors will be saved in the
error memory (see Chap 9.2 section “Error messages”)
Fig. 9-45Error input mask
After the relay function has been defined (limit flow rate, limit level, limit velocity,
or limit temperature) another window will appear enabling to define the function
parameters depending on the function chosen. The respective parameters are
ON and OFF points, ON and OFF delays as well as modifications of the name
which might come into effect on the screen (see Fig. 9-46).
Fig. 9-46Limit value parameter
The relay is going to energise if >normally open< has been selected and the
according value has been reached, if >normally close< has been selected the
relay will energise immediately after the parameter has been set and will deenergise as soon as the according value has been reached.
limit functions.
all limit functions.
9999 seconds max. The relay will not energise before the time set is expired
and the limit value is present yet.
If the value falls below the limit threshold for a moment the cycle will begin
anew.
Instruction Manual
OCM F
Page 62 OCM F - Rev. 04 as of 18.02.2014
®
Time delay off
The “OFF” event in case of reaching the limit value can be delayed by up to
Name
The relay output name may consist of 3 characters max., which will be indicat-
Impulse duration
Set impulse duration from 0.1 to 1.0 seconds. The impulse-pause-ratio is 1:1;
Volume impulse
Defines the impulse value. The measured volume will be added internally until
9999 seconds max. The relay will not de-energise before the time set is expired and the limit value is present yet. If the value falls below the limit threshold for a moment the cycle will begin anew.
ed in main menu and in overview menu. Set the name as described in Chap-
9.4.1.
ter.
If the impulse function has been selected the options below have the following
functions:
Fig. 9-47 Impulse parameters / impulse duration
the default setting is 0.5 seconds.
It is useful to extend impulse duration e.g. in case of using slow SPS (PLC)
inputs or sluggish mechanic counters.
the value set has been reached (e.g. 1 m³). Then an impulse signal with the
duration set will be output and the internal counter will be set to 0 again. The
course of events will repeat again subsequently.
9.4.8 Parameter Menu “Control Unit“
Fig. 9-48 Control unit basic settings
This menu allows you to adjust the transmitter to almost any waste water application for optimum performance. It enables to execute slide valve and torque
monitoring as well as quick close control or automatic flush functions. The digital
inputs >PATH OFF<, >PATH ON< and >TORQUE CLOSED< have to be activated for the control unit to operate.
You can find more comprehensive information on setup and functional principle
in chapter 7.7 Regulator Mode.
It is absolutely necessary to have sound knowledge on control technology to
correctly and safely set the regulator!
Instruction Manual
OCM F
OCM F - Rev. 04 as of 18.02.2014Page 63
Non active
The function is disabled.
Internal set point
The set point is determined in the OCM F.
External set point
The set point is pre-set externally using the dedicated analog input 2. This can
Input range
Measurement range selection of external set point between 4-20 and 0-20 mA.
Value at 0/4 mA
The flow values can be set to 0/4 mA.
Value at 20 mA
Flow values for 20 mA can be entered here.
Int. Set point
This parameter is to determine the internal flow set point in l/s.
Min. variation
This parameter defines the permissible setpoint deviation of the control sys-
Cycle time
The processing interval of the controller.
active
active
be accomplished e.g. by using a process conducting system.
It is recommended to always set the “internal set point” since the system will
switch to internal automatically as soon as the external set point 4-20 mA fails.
Fig. 9-49Setting the external setpoint
Linearization of set point input: set point start is at 0/4 mA, set point end is at
20 mA.
Fig. 9-50Control unit settings
tem without a regulating event is allowed to be executed.
The setting reduces the oscillation tendency of the system. If there is no setpoint deviation tolerance defined, the system will constantly attempt to exactly
adjust the actual value according to the setpoint. Due to this reason the regulating unit might be driven permanently which may result in mechanical defects
or higher wear and tear. Normally the deviation should be approx. 10 % of the
setpoint value.
Short intervals will accelerate the control behaviour, but are going to result in
oscillation of the control circuit as from a certain point. A long interval is going
to reduce the oscillation tendency of the controller but will however increase
inertia of the regulating system.
Instruction Manual
OCM F
Page 64 OCM F - Rev. 04 as of 18.02.2014
®
average flow velocity
distance between regulating unit and measurement
Slide valve run
Use this parameter to monitor spindle breaks, slide valve gate breaks, gear
the end switch CLOSED after the slide run time has expired
Min. pulse time
This parameter can be considered as quite similar to the I-component of
Max. pulse time
This parameter defines the maximum control impulse duration of the regulating
P-Factor
The proportionality factor indicates, to which degree the regulating time is go-
Quick close function:
Guideline:
time/shifter time
Interval =
defects, power failures on the regulating unit or other malfunction sources
which may reveal because the regulating unit does not move although control
signals are being generated.
An error message is going to be generated if the controller unit does not reach
(see Chap. 9.2 sub item “Error messages“)
Guideline:
Slide run time to be set = time between open and closed condition of slide valve
during permanent operation • 1,2 ......2,0.
(the longer the slide run time the lower the factor)
The slide run time has an effect similar to the P-factor and has to be set!
There will be no error message generated e.g. in case of a broken spindle if
the slide run time has not been set!
• 1,3
PID controllers. It defines a minimum regulating time of a regulating unit in order to ensure that calculated very short control impulses mechanically affect
the regulating unit at all. Hence the minimum control impulse duration should
be specified longer than motor start-up time + gear clearance + slide valve
clearance. If 0 has been set an impulse duration of 0.25 seconds will be used.
unit. This allows to limit the slider run time. The maximum control impulse duration should be shorter than the cycle time.
ing to be affected in case of a deviation ∆ w from setpoint w. The higher the
proportionality factor, the longer the regulating time of the slide valve at the
same control deviation..
The quick close function is used if certain conditions such as large diameters,
long slide valve run times and long dead times of the measurement section are
given. In case of sudden rainfall events this function will partially close the
open slide valve independent of the calculated regulating time.
During permanent operation this is going to be executed without any run time
interruption. This function requires “h, Q and t-quick close” to be set.
Instruction Manual
OCM F
OCM F - Rev. 04 as of 18.02.2014Page 65
h-quick close
h-quick close acts as OR-parameter related to Q-quick close. This parameter
Q-quick close
Q-quick close acts as OR-parameter related to h-quick close. This parameter
t-quick close
t-quick close is the time the regulating unit needs to move from open condition
t of Pos. “CLOSED“
This period is for error cases, e.g. interrupted sensor communication or defect
Time delay
This is the time to elapse before the position control comes into effect in case
System reset
Enables a general reset of the measurement transmitter. Entering the PIN-
defines the desired maximum flow level of the medium. “t-quick close” will be
activated as soon as this value has been reached. Depending on application,
this parameter shall be set approx. 60-80 % higher than the setpoint. Before
setting this parameter please observe waves at the measurement place as
well as the unit’s regulating deviation.
defines the desired maximum flow rate of the medium. “t-quick close” will be
activated as soon as this value has been reached. Depending on application;
this parameter shall be set approx. 10-50 % higher than the condition which
makes the system go to regulator mode during dry weather operation. Before
setting this parameter please observe the unit setpoint deviation tolerance.
(end switch: PATH ON) to the position it has whilst being in normal regulator
mode. “h-“ or “Q-quick close” are the conditions for “t-quick close” to switch.
sensor. In this case the regulating unit goes to closed condition (end switch:
PATH OFF) before it opens again for the period set in this parameter t of Pos.
“CLOSED“.
of errors. The adjustable range is 0-240 seconds.
9.4.9Parameter Menu „Setup Parameter“
WARNING
Data loss due to system reset
Selecting >system reset< is going to reset the system to the basic parameter
settings. The default settings are going to be restored and all customer modifications will be set to default condition (system general reset).
Fig. 9-51Setup parameter – submenu
This menu allows to modify measurement and output damping, to reset the system to default condition as well as to modify special settings by using the service
code.
Codes >2718< will cause the OCM F to execute a general reset. The unit will
be in initialising mode subsequently which requires the operation language to
be set.
Instruction Manual
OCM F
Page 66 OCM F - Rev. 04 as of 18.02.2014
®
Service mode
Additional system setting options are going to be revealed as soon as a spe-
Damping
Allows to adjust indication and analog output damping between 20 and 200
Stability
It is recommended to increase stability in case of irregular measurement drops
Fig. 9-52 New program start OCM F
Fig. 9-53 Choose language
The OCM F will now overwrite the flash memory restarting the program. Before
restart the unit briefly indicates unit ID (see Fig. 9-52). Subsequently the desired
language can be selected (see Fig. 9-53) and the unit will return to factory default condition.
cial code has been entered. This parameter is reserved for NIVUS service
personnel as the settings require comprehensive expert knowledge and are
not needed for common applications.
seconds. This means that if the calculated volume jumps from 0 to 100 % the
system will need the time set here to indicate and to output this jump.
due to poor hydraulic conditions..
Instruction Manual
OCM F
OCM F - Rev. 04 as of 18.02.2014Page 67
9.5Signal Input-/Output Menu (I/O)
This menu includes several submenus which both serve to assess and to check
sensors as well as to control signal inputs and outputs. It allows to indicate various values (current values of inputs and outputs, relay conditions, distribution of
frequency groups etc.), however does not enable to influence signals or conditions (offset, adjustment, simulation or similar). The menu therefore primarily
serves in order to assess the parameter settings and for error diagnosis.
Fig. 9-54I/O Menu
9.5.1I/O Menu “Digital Inputs”
Digital input values routed to the transmitter input clamps can be viewed here.
Select from either logically "OFF“ or "ON“.
Fig. 9-55Screen digital values
9.5.2I/O Menu “Analog Outputs”
This menu indicates the calculated values which have to be sent to the analog
converter as mA signals.
Fig. 9-56Screen analog values
The actual current on the output clamps will not be displayed. The only signal
visible is the one the analog output converter is receiving for output purposes.
External faulty wiring neither can be detected nor indicated in this menu.
Instruction Manual
Page 68 OCM F - Rev. 04 as of 18.02.2014
®
v = Measured flow velocity
A = Calculated area
Q = Calculated flow rate
t = Measured temperature
q = Quality of velocity measurement (damped)
9.5.3 I/O Menu „Digital Outputs”
Conditions which are calculated by the transmitter and routed to the relay for
output purposes subsequently can be viewed here. Select from either logically
"OFF“ or "ON.
Fig. 9-57 Screen digital values
The actual output condition of the relay contacts on the output clamps will not
be displayed. The only signal visible is the one the relay is receiving for output
purposes.
External faulty wiring neither can be detected nor indicated in this menu.
9.5.4 I/O Menu „Measurement Data”
OCM F
This menu is to recall current readings at a glance.
h = Measured level
Fig. 9-58 Screen measurement data
Instruction Manual
OCM F
OCM F - Rev. 04 as of 18.02.2014Page 69
2 Creation date of sensor firmware
3 Quality of velocity measurement
4 Calculated average flow velocity
5 Height measured by pressure sensor
6 Measured medium temperature
7 Velocity of sound resulting from medium temperature
8 Amplification mode of sensor
9 Amplification value of sensor
2 = frequency group (peak)
3= Measurement frequency
4= Currently measured flow velocity
5= invalid values
9.5.5I/O Menu “Sensor-Info”
This menu is to indicate various information regarding the sensor and is mainly
for service purposes.
1 Firmware version of sensor
Fig. 9-59Status of sensors and velocity evaluation
9.5.6I/O-Menu „v-Histogram”
The frequency histogram indicates the spreading of the investigated Doppler
frequency. Each bar (peak) represents a frequency group.
This is particularly important to assess and to choose measurement places as
well as to find a place for sensor installation.
1 = Quality of velocity measurement
Fig. 9-60Distribution of frequency groups
The measurement quality (0-100 %) indicates the relation between the evaluated Doppler frequency and the entire frequency spectrum measured. The higher
the quality, the more reliable the indicated flow velocity reading. There are no
limit values for the quality (Q) since the shape of the frequency distribution has
to be considered additionally. This shape is more important for hydraulic assessment than „q“.
Instruction Manual
OCM F
Page 70 OCM F - Rev. 04 as of 18.02.2014
®
There are cases where, despite comparatively high quality values, it is not
possible to correctly investigate the flow velocity reading due to poor frequency group distribution. In such cases install the flow velocity sensor in another
place. See „Installation Instruction for Correlation and Doppler Sensors “.
Quality = very good
Frequency distribution = very good
Quality = satisfactory
Frequency distribution = satisfactory
Quality = very good
Frequency distribution = poor
Fig. 9-61 Flow velocity profiles
Quality = good
Frequency distribution = good
Quality = none
Frequency distribution = none
Quality = poor
Frequency distribution = satisfactory
9.5.7 I/O Menu “External Level“
This menu is visible only if external level measurement is enabled. Here the prevailing currents on analog input 1 and the height of the external level measurement are indicated.
5 Current regulating time calculated from „Qdff” in sec./4
6 Time in seconds how long activated relay remains energised
7 Remaining cycle time
8 Status of three digital inputs
9 Status of both relays
2 time in seconds how long activated relay remains energised manually
3 status of three digital inputs
4 status of both relays
9.5.8I/O Menu “Control Unit”
This menu is visible only if the controller has been enabled in the PAR menu.
Having the controller enabled will bring up the screen below:
1 Currently measured flow rate
act
Fig. 9-63Control unit selection
9.5.9I/O Menu “Test control unit – manual mode”
DANGER
Caution – Danger of injury!
The manual controller operation directly will access any following facility areas
without any safety locking measures! This might result in personal injuries!
Manual operation is for test purposes exclusively!
Safety precautions must be taken!
This menu is visible only if the controller has been enabled. The slide valve can
be manually opened and closed for testing purposes. The arrow keys >up< and
>down< serve as manual control elements.
set
1 currently measured flow rate
Fig. 9-64Control menu for test control unit
Instruction Manual
Page 72 OCM F - Rev. 04 as of 18.02.2014
®
9.6 Calibration and Calculation Menu (CAL)
This menu is to adjust the level measurement, to adapt flow velocity and analog
outputs to following systems and to simulate relay switching events and analog
outputs.
Fig. 9-65 CAL- menu selection
9.6.1 CAL Menu “Level“
This menu allows to adjust level measurements.
Values from -1000 mm to +1000 mm (39.4 in) can be entered. This adjustment
is required only if the level measurement utilises a pressure measurement cell.
OCM F
Fig. 9-66 Submenu - level
Due to physical reasons the pressure measurement cell is subject to zero
point drift. It is recommended to adjust the pressure sensor to the zero point
regularly (recommended interval: 6 months).
Required values have to be investigated with the sensor being removed if
possible or if the water level is as low as possible. The correct filling level has
to be investigated as accurate as possible before adjusting by using another
suitable measurement method (value = 0 if the sensor has been removed from
the medium).
Enter the investigated value as reference.
Investigating the zero point of the pressure measurement cell is often carried
out by measuring the current filling level with a yardstick, a ruler or similar
without removing the sensor. After the ruler or similar has been held into the
medium, the respective reading is entered as reference value.
This is why the filling level for reference measurement purposes has to be
measured always from top down (see Fig. 12-1).
Instruction Manual
OCM F
OCM F - Rev. 04 as of 18.02.2014Page 73
min. velocity
Defines the minimum flow velocity measurement range the OCM F shall
max. velocity
Defines the maximum flow velocity measurement range the OCM F shall
Calibration factor
Here the calibration factor can be modified. The calibration factor is multiplied
h-crit.
Measuring the flow velocity is no longer possible as soon as the level falls be-
h_crit min
The flow velocity will not be calculated below "h_crit min“ and hence will be set
9.6.2CAL Menu “Flow Velocity“
Fig. 9-67Submenu – velocity
measure and process. It is set to -4 m/s per default. The minimum flow velocity
can be set to >0< if negative flow directions are not to be measured.
measure and process. It is set to 4 m/s per default.
It is not possible to measure and to output positive velocity if the maximum
value has been set to >0<!
It is not possible to measure and to output negative velocity if the minimum
value has been set to >0<!
by the measured flow velocity. The value is set to 1 per default.
low a certain level called h_crit.
The level h_crit is pre-determined by the construction of the sensor as well as
the measurement method and is set to 0.065 m (2.56 in) per default.
After initial start-up, the OCM operates using the start values found in the
Manning-Strickler table (CAL / Flow velocity / v-crit determination / ManningStrickler) until it reaches the h-crit value set.
Going through a level range of 9-12 cm featuring a decreasing trend causes
the unit to determine an application coefficient (automatic activated).
Then the OCM under h-crit operates using the investigated application coefficient.
In case of a raised sensor installation position enter + 0.065 m as installation
height here.
Example: enter 0.085 m under "h-crit“ in case of using a sensor installation
height of 0.02 m..
to >0<.
Instruction Manual
OCM F
Page 74OCM F - Rev. 04 as of 18.02.2014
®
2 h_crit min
3Range of automatic Q/h relation
4 determination of application coefficient
Auto discharge curve
Depending on the selected setting, entered values are verified and corrected if
1 h-critical
Fig. 9-68Flow velocity determination graph
necessary with the next measuring event (automatic >active<). Another option
is to permanently operate using the values entered in "Manning Strickler“,
"manual“ or "Assistant“ (automatic >inactive<).
Fig. 9-69Defining v-crit
Note
Please avoid backwater up to levels of 0.012 m if Auto discharge curve is „active".
v-crit Determination
This menu is conceived to be used for commissioning at low filling levels lower
than 6.5 cm. There are three options to determine the flow velocity:
− Manning-Strickler (if slope and roughness are known)
− Manual (if a reference value can be determined)
− Assistant (if a minimum dam-up of 6.5 cm is possible)
Instruction Manual
OCM F
OCM F - Rev. 04 as of 18.02.2014Page 75
Slope
Enter the slope at measurement point in %
Strickler -coefficient
Enter the Manning - Strickler coefficient
Comprehensive expert knowledge is required to properly utilise these parameters. We therefore recommend the NIVUS commissioning service or a thorough device training.
Fig. 9-70Selecting v-crit determination
Manning Strickler
The theoretical discharge curve is calculated using the settings under >Dimensions<, >Slope< and >Roughness<.
This function may be combined with the automatic mode. The theoretical settings within the flow velocity monitoring area (see Fig. 9-68, No. 4) will be verified using this method.
Fig. 9-71Manning Strickler v-crit determination
Please see Table „Manning - Strickler Coefficients“ in chapter 14 for more
information.
Manual
Enter the current level and the current flow velocity (measured using a reference) directly. The theoretical discharge curve is calculated from these values.
This function may be combined with the automatic mode. The theoretical settings within the flow velocity monitoring area (see Fig. 9-68, No. 4) will be verified using this method.
Fig. 9-72Manually setting v-crit determination
Instruction Manual
OCM F
Page 76 OCM F - Rev. 04 as of 18.02.2014
®
Assistant
The OCM guides through a menu using an artificial dam-up (e.g. using a sandbag) to determine required characteristics. The theoretical discharge curve will
be generated automatically.
This function may be combined with the automatic mode. The theoretical settings within the flow velocity monitoring area (see Fig. 9-68, No. 4).
will be verified using this method.
First ensure free discharge, then start level measurement with >ENTER<.
The OCM executes the first level measurement in free discharge. Measuring will
take 8 seconds.
Fig. 9-74 Measuring Countdown Assistant
After the first measuring, a dam-up of minimum 6.5 cm (12 cm are recommended) must be created behind the sensor by using a sandbag or similar.
The second level measurement in the dam-up cannot be started before
"h-actual“ shows stable values.
Fig. 9-75 Create dam-up – start measuring
The OCM will execute a new 8-second level measurement.
Fig. 9-76 Measuring countdown for the second measuring
Instruction Manual
OCM F
OCM F - Rev. 04 as of 18.02.2014Page 77
Adjustment
The 3 analog outputs can be adapted to following systems. Adjust between
The readings below will be indicated after the second measurement has been
finished:
Pressing >ENTER< determines and subsequently enters an application coefficient (factor) for the measurement point.
9.6.3CAL Menu “Analog Outputs“
Basic Hints on Simulation:
DANGER
High risk potential during simulation
Due to the extremely high risk potential (direct access to following plant sections) as well as incalculable effects due to poor or faulty simulation, NIVUS
herewith refuse to accept any responsibility for personal or material damages
of any kind in advance!
Simulations must be carried out by trained expert personnel exclusively!
-4 mA and 4 mA (see Fig. 9-78).
These values will be added to or subtracted from the analog outputs. Adjustment is not possible as soon as the analog output has been set to “Constant
value”.
Fig. 9-78Adjustment of analog outputs
Instruction Manual
OCM F
Page 78 OCM F - Rev. 04 as of 18.02.2014
®
Simulation
It is possible to simulate a free adjustable analog output current on the 3 ana-
WARING
WARING
Danger of injury!
The simulation of OCM F outputs will access any following facility areas with-
out any safety locking measures!
Simulations are allowed to be executed exclusively by NIVUS expert personnel or by expert companies trained by NIVUS in cooperation with experienced
users. Be sure to always observe safety precautions!
Make sure to have a safety person available
The simulation of analog inputs and outputs is allowed to be carried out by
specialist electricians only who have sound knowledge on the control system
of the facility. This requires detailed preparation.
It is absolutely necessary to have a safety person available!
The following system must be set to manual operation mode. Actuators or
similar have to be disabled if possible or have to be functionally restricted in a
way not to cause any damage.
log outputs. Select the desired analog output with the >right< or >left< keys.
After entering the PIN code >2718< you can increase or decrease the mA value in steps of 0.01 mA using the >up< or >down< keys during simulation. Furthermore it is possible to directly enter desired values to simulate by pressing
ENTER. A maximum output current of 20.475 mA can be simulated
(see Fig. 9-79).
Fig. 9-79 Simulation of analog outputs
Instruction Manual
OCM F
OCM F - Rev. 04 as of 18.02.2014Page 79
2 Simulated flow velocity
3 Simulated medium temperature
4 Calculated simulated flow value
5 Programmed relay activated by simulation
6 Analog output signals
9.6.4CAL Menu „Digital outputs“
Selecting the >Digital outputs< menu requires to enter the PIN (2718) once
again. This ensures to prevent unauthorised persons from performing simulations during operation.
Choose the desired relays to be simulated by using the >up< and >down< arrow
keys. Use ENTER to either turn the chosen relay ON or OFF directly. The relays
will de-energise if you exit the menu
.
Fig. 9-80Relay simulation
9.6.5CAL Menu „Simulation“
After entering the PIN code >2718< select between level, velocity and medium
temperature by using the >up< and >down< arrow keys. Pressing >right< or
>left< will increase or decrease the simulated flow velocity or temperature value
in steps of 1 cm or 0.1 °C.
Using ENTER enables to enter the desired simulation value directly.
The flow value which has been calculated by means of the simulated readings
will be indicated on the bottom line of the screen. Relays which might have been
set will switch and programmed mA outputs supply according current values
simultaneously. Use >up< or >down< keys to indicate output values in the bottom line of the display.
1 Simulated height/level
Fig. 9-81Simulation mode
Instruction Manual
Page 80 OCM F - Rev. 04 as of 18.02.2014
®
9.7 Parameter storage
Via the front-side USB interface, parameter can be either loaded or saved on PC
or Laptop using software tool „PaDa“. This tool is free and can be down-loaded
from www.nivus.com under >Download/Software<.
Connect the OCM F and PC/Laptop with an USB cable (Type A-B). The „Pa-Da“
software tool at present can be operated under Windows® XP, Vista and Windows® 7 (32-Bit version).
If a warning should be displayed during installation click the "Continue Anyway" button.
OCM F
PC or Laptop are not capable of detecting the OCM F transmitter however if
you select "STOP Installation" instead. In this case the software must be installed again!
Fig. 9-82 PaDa Installation Warning
After the software has been installed successfully, run the tool under Win-
dows® XP either from „Start – All Programs - NIVUS GmbH“ or via the desk-
top icon (self-installed; German, English or French).
Fig. 9-83 PaDa English
Instruction Manual
OCM F
OCM F - Rev. 04 as of 18.02.2014Page 81
Load parameters
Downloads the complete current parameter settings of the transmitter from
Load modified pa-
Loads only parameters which have been modified in the unit (varying from de-
Send parameters to
Sends previously saved parameters ("PARAM. TXT“) to OCM F in case of acci-
Send modified pa-
Use this function to send modified parameters to the transmitter. The file name
Select the desired option using the >up< and >down< arrow keys and confirm
with the Enter key. The standard installation routine will install the software under Windows® XP in the C:\Programme\PaDa directory. Parameter sets will be
saved there as well. Read out or open parameters either with EXCEL or an appropriate editor application.
from device
rameters from device
device
rameters to device
OCM F to PC/Laptop creating a file named "PARAM.TXT“.
fault) using a file named "CHGPARAM. TXT“.
dental system reset, faulty modification of specific settings or device defects.
Synchronises the parameters between PC/Laptop and OCM F. Copy the desired parameters into the same directory as the "PaDa.exe“ before transmitting.
is "CHGPARAM. TXT“.
Do not close the tool window during data transmission! The window will close
automatically as soon as the transmission has been finished successfully!
In order to prevent data from being overwritten, move parameters which have
been read out before into a separate folder.
range4-20 mA
value at 0/4 mA0
value at 20 mA4
offset0
damping3
external s ensor (Ex )
velocity
digital input
value at 4 mA0
value at 20 mA4
offset0
damping3
sensor typewedge
mounting offset0,015
mounting directionpositive
function
DI 4 stop v-measurement
logicnon-inverse
nameD1
DI 1 torque switch
DI 2 switch "CLOSE"
DI 3 switch "OPEN"
Instruction Manual
Page 84 OCM F - Rev. 04 as of 18.02.2014
®
Parameter Menu (PAR) Part 3
analog outputdefault
functionD1
inactivex
flow rate
level
velocity
temperature
constant current
output range
0-20 mA
4-20 mAx
value at 0/4 mA1 m/s
value at 20 mA0,8 m/s
errror mode
inactivex
ac t i ve
error input mask
value in error cas e
hold old value
constant 0 mAx
constant 3,6 mA
constant 4,0 mA
constant 20,475 mA
digital outputs
relay functions1
no functionx
limit flow rate
limit level
limit velocity
limit temperature
pos-total impulse
neg-total impulse
error mess ages
error input mask
nameR1
Par. below at active relaiy function only
swit ching mode
normally openx
normally closed
OCM F
Instruction Manual
OCM F
OCM F - Rev. 04 as of 18.02.2014Page 85
Parameter Menu (PAR) Part 4
default
stability60
swit ch point on
swit ch point off
time delay on0
time delay off0
nameR1
only when relay s function is "impuls e"
impulse duration5
amount1
control unit
setup paramet er
function
not active
internal set point active
external s et point active
external s et point range at 0/4 mA
external s et point range at 20 mA
max.flow rate200
int. set point flow40
control deviation5
cycle time90
shifter time120
min. Pulse time1
max. Pulse time15
P-factor70
h-Quick close function1
Q-Quick close function1000
t-Quick close funct ion60
t of Pos. “CLOSED“30
time delay0
system reset
service mode
service c ode
damping20
Instruction Manual
OCM F
Page 86 OCM F - Rev. 04 as of 18.02.2014
®
Parameter Menu (I/O)
I/O
digital input
analog output
digital output
measurement data
sensor info
v-histogram
external set point
external level
control unit
control unit test mode
Parameter Menu (CAL)
CALdefault
level
calibration
velocity
min. velocity-4,0000
max. velocity4,0000
calibration factor1,0000
h-crit.0,065
h-crit. min. 0
auto dischar. Curve
nicht aktiv
aktivx
v-crit detremination
Manning-Stricklerx
manual
assistant
slope
Strickler Coeff.
h manual
v manual
assistant
Check sensor for soiling, sedimentation, silting (
Flow level measure-
Important: no flow level no flow velocity meas-
Check level measurement parameter "Fixed value“
Transmitter
Call up error memory. Depending on error mes-
Negative flow direction
Check installation direction of the sensor, rotate
Programming
Completely check the transmitter parameter set-
Display >Error Doppler
Connection
Check cable connection. Wiring on terminal strip
Communication
Communication to sensor disturbed. Can be
11 Troubleshooting
OCM F
(>0<or >----<)
ment
minal strip. Check connection boxes, connections
for sensor cable extension or air compensation
element for correct connection or moisture. Sensor
cable connected to appropriate terminal clamp strip
(Ex or Non-Ex)?
horizontal installation).
to be removed) or mechanical damage or sensor
body and cable ( replace sensor).
urement possible!!
In case of Doppler level measurement: check sensor for horizontal installation. Check sensor function in menu >I/O - >v-Histogram<.
In case of external level measurement: check function and signal transmission (cables, clamp connections, short circuits and contact resistances).
In case of measurement with pressure cell: check
compensation channel at sensor body for obstructions. Remove yellow cap from filter element.
in case measuring in full channel without using
level measurement.
sages take the respective measures (check cables,
plug and socket connections, sensor installation).
sensor if required.
If the flow direction is reversed only occasionally
and the measurement fails subsequently set
min. value to -6,0 m/s in menu CAL-Flow vel. –
min. + max. value.
tings.
Sensor<
switched? Cables firmly connected to plugs (retighten screws, pull at cable ends)? Insulation of
single wires unintentionally clamped in?
checked by choosing menu I/O >Doppler-Info<.
Sensor should be indicated in the first line of the
following screen. Check cables for interruption or
loose connection. Check sensor for mechanical
damage.
Instruction Manual
OCM F
OCM F - Rev. 04 as of 18.02.2014Page 89
Unstable measure-
Hydraulically unsuita-
Check quality of measurement place by using the
Remove soiling, sedimentation or obstructive con-
Straighten the flow profile by installing appropriate
Increase damping.
Sensor
Check sensor installation (towards flow direction,
Check sensor for sedimentation or obstructions.
Implausible measure-
Hydraulically unsuita-
See "Unstable measurement values“.
External level signals
Check for correct connection.
Check if cables are crushed, for short circuits and
Check measurement range and span.
Check input signal in I/O menu.
Sensor
Check for correct connection.
Check if cables are crushed / for extensions/cable
Check level signal, echo profile, flow velocity
Check if sensor is installed on a vibration-free
Programming
Check if the correct shape of measurement place
Faulty Digital output
Connection
Check connections on terminal clamp strip.
Check power supply of external control relays.
In I/O menu check signals to be output.
Check output control function in calibration menu.
ment values
ment values
ble measurement
place
ble measurement
place
graphic frequency group distribution display. Relocate the sensor to a hydraulically more suitable
place (extend calming section).
structions in front of the sensor.
baffle plates and calming elements, flow straighteners or similar upstream of measurement.
horizontal installation).
improper resistive loads or current consumers
without galvanic isolation.
types, short circuits, surge arresters or improper
resistive loads.
signal, cable parameters and temperature in
I/O menu.
In case of using one or several outputs: check fol-
Programming
Output enabled?
Check if functions have been assigned to correct
Check output range (0 or 4-20 mA)
Check output span
Check offset
Check output signal in I/O menu
Following systems
Check cables and connections as well as input and
Check input range (0 or 4-20 mA) of following sysCheck input span of following system.
Check offset of following system.
PC / Laptop unable to
No device driver in-
Reinstall driver, on WINDOWS warning press
tive output channels.
ters, limit values, logic etc.
cated to controller function).
point.
ual controller operation.
rameters set? Analog input set and enabled as
setpoint? Relay outputs enabled? Observe controller status in I/O menu.
polarity.
detect device
stalled
lowing systems/indicators if they are potential-free.
Two analog outputs at a time have a common
ground.
output channel.
output clamps.
tem.
"Continue anyway“.
Instruction Manual
OCM F
OCM F - Rev. 04 as of 18.02.2014Page 91
12Verification of the Measurement System
12.1General
The verification of the measurement system should be carried out by the NIVUS
service if possible or by an expert company authorised by NIVUS.
In case of an initial general verification carried out by hydraulically and technically well-versed personnel, proceed according to the guidelines described below:
− Check power supply on the OCM F. The according slide switch on the board
must be engaged (see Fig. 7-12). The main screen must be visible on the
transmitter display.
− Check the communication between flow velocity sensor or combi sensor and
transmitter at I/O/Doppler-Info
− If the sensor(s) is/are not recognised, check the connections as well as overvoltage protection elements which might have been used
− Check the level measurement
− Check the flow velocity measurement
− Check analog and digital inputs and outputs (see Chap. 9.5.1, 9.5.2 as well
as Chap. 12.2 and 12.3)
For initial assessment mainly the I/O menu as well as the >I-key< on the transmitter are helpful.
Refer to chapter 11 to locate the most prominent errors.
12.2Verification of Combi Sensor with Pressure Measurement Cell
Due to physical reasons, the level measurement using sensors with pressure
measurement cell is subject to long-term drift (see >Technical Instructions of
Doppler Sensors<). NIVUS therefore recommend to calibrate sensors with integrated pressure measurement cells twice per year regarding the zero point. The
best calibration results can be achieved if the water level is as low as possible or
by dismantling and removing the sensors from the measurement medium.
The calibration procedure is described in Chapter 9.6.1.
Adjusting the zero point by measuring the current filling level with a yardstick,
a ruler or similar in the flowing medium is tending to errors. As soon as the
ruler (or yardstick) is being put into the flowing water the resulting surge will
lead to measurement errors depending on the current flow velocity. This is
why the filling level for reference measurement purposes has to be measured
always from top down!
Instruction Manual
OCM F
Page 92OCM F - Rev. 04 as of 18.02.2014
®
Fig. 12-1 Determination of reference level under operating conditions
Flow velocity sensors with pressure measurement sensor (Type KP) must be
uninstalled as soon as the pressure level measurement fails. The sensor shall
be soaked for an appropriate period and the pressure channel (see Fig. 5-1)
shall be flushed carefully of shall be cleaned with a soft brush.
Do not use high pressure to flush the channel. This may lead to misadjustment
of the 0-point or may even destroy the built-in pressure sensor.
Furthermore never remove the ground plate (risk of leakage or sensor destruction)!
12.3Verification of external Level Measurement
Using an external level measurement (e.g. NivuMaster) needs to measure the
filling level in the channel with a yardstick (see Fig. 12-1) and to adjust the zero
point on the level transmitter if required.
Then compare output signal as well as measurement span of the external
measurement with the analog input signal and the measurement span of the
OCM F in PAR menu as well as in I/O menu and adjust accordingly if required.
Instruction Manual
OCM F
OCM F - Rev. 04 as of 18.02.2014Page 93
12.4Verification and Simulation of Input and Output Signals
The I/O menu (see Chap. 9.5) allows to verify connected sensors as well as to
check signal inputs and outputs with the aid of several submenus. Various values can be indicated (current input and output values, relay conditions, echo
profiles, single velocities etc.), signals or conditions however (offset, adjustment,
simulation or similar) cannot be influenced.
Analog output signals, relay conditions as well as the theoretical flow can be
simulated in the CAL menu (see Chap. 9.6).
12.5Verification of Flow Velocity Measurement
Use the menu I/O/v-histogram to view the frequency histogram of the V-sensor.
Chapter 8.5.6 describes how to assess the histogram.
The velocity can be verified using a portable flowmeter e.g. PCM Pro, PVM-PD,
hydrometric vane etc.). A calibration factor can be entered here if the deviation
of the flow velocity should be strong (chapter 9.6.2)
The sensor is obstructed due to build-up or soiling (to be removed) as soon as
the histogram indicates visible disturbances.
Another reason is that the sensor may have been installed at a hydraulically unfavourable position tending to low measurement quality or measurement failure
(check installation position of sensor).
Please note, that without a working level measurement it is not possible to
measure flow velocities and hence the flow cannot be computed.
If the flow velocity measurement fails, the sensor however is connected correctly
and lines, clamping connections and overvoltage protection have been checked,
the sensor possibly may be defective.
In various countries it may be necessary to carry out regular maintenance with
comparative measurements in particular applications to comply with official regulations. If desired, NIVUS is going to carry out all required verifications, hydraulic
and technical assessment, calibration, troubleshooting and repairs if an according maintenance agreement has been contracted. These services will be carried
out according to DIN 19559 incl. the agreed proof of the remaining residual error, as well as according to rules in the respective countries.
Instruction Manual
Page 94 OCM F - Rev. 04 as of 18.02.2014
®
13 Maintenance and Cleaning
OCM F
WARNING
Germ contamination
Please note that due to the operation in the waste water field sensors and
cables may be loaded with hazardous disease germs. Respective precautionary measures must be taken to avoid damage to one’s health.
Important note:
To avoid damage of the instrument the measures described in this section of
the instruction manual must be executed by trained expert personnel exclusively.
Please disconnect the unit from mains prior to maintenance, cleaning and/or
repair works.
13.1 General Maintenance
The device Type OCM F is designed to be virtually maintenance-free and free of
material wear and moreover needs no calibration.
Maintenance extents as well as the according cycles depend on the following
factors:
13.2 KDA-Sensor
WARNING
− measurement principle of the level sensor
− material wear
− measurement medium and channel hydraulics
− general regulations for the operator of this measurement plant
− ambient conditions
To ensure reliable, accurate and error-free function of the measurement system,
we recommend annual inspections of the entire measurement system by
NIVUS.
If required clean the transmitter enclosure if with a dry, lint-free cloth. For heavy
pollution NIVUS recommends the use of surface-active agents.
The use of abrasive cleansing agents is not allowed.
Damage caused by hard objects
No hard objects such as wire brushes, rods, scrapers or similar shall be used to
clean the sensor. This may result in damaged sensors, lead to measurement
failures and hence is prohibited in principle.
You can find a comprehensive description on sensor maintenance and cleaning
in the "Technical Instructions for Doppler Sensors"“.
Instruction Manual
OCM F
OCM F - Rev. 04 as of 18.02.2014Page 95
13.3Accessories (optional)
KDA-Sensor
KDA-K…
Pipe measurement section
OCM0 ZDN0
Flange
ZUB0 DN200
Flange gasket set
ZUB0 DN200-DISET
Pressure compensation element
ZUB0 DAE
Replacement filter
ZUB0 FILTER02
Pipe mounting system
ZUB0 RMS2…
ZUB0 RMS3…
ZUB0 RMS4…
Ultrasonic Doppler sensor for flow velocity or combi sensor for flow
velocity and level for connection to OCM F.
for OCM Pro CF and OCM F (short)
Flange DN 200 made of PVC with R1" thread (Pipe measurement section short)
Flange gasket set for DN 200
for connection of sensors with pressure measurement cell
Material: aluminium, plastic, degree of protection: IP54
with plug and connection hose for sensors with pressure measurement
cell for connection PCM-series transmitters as well as the ZUB0 DAE
pressure compensation element.
for temporary installation of POA, KDA, CSM and DSM wedge sensors
in pipe lines with diameters between 200 and 800 mm
Stop ball valve
ZUB0 HAHNR15
Tapping saddles
ZUB0 ABS01…
ZUB0 ABS02…
ZUB0 ABS03…
Welding nozzle
ZUB0 STU15…
You can find more accessories for sensor installation in our current price list.
for removal of pipe sensors from pipes without pressure
for installation of 1½“ pipe sensors in pipe lines
For pipe sensors; material steel or stainless steel
Instruction Manual
Page 96 OCM F - Rev. 04 as of 18.02.2014
®
Channel wall consistency
M in m
1/3
/s
k in mm
plastic (PVC, PE)
14 Table „Manning - Strickler Coefficients“
glass, PMMA, polished metal surfaces > 100 0...0,003
OCM F
≥ 100
new steel plate with protective coating;
smooth
smoothened cement plaster
asphalt coated steel plate;
concrete from steel or vacuum formwork, no joints, carefully smoothened;
planed wood, joint-free, new;
asbestos cement, new
smoothened concrete, smooth finish;
moderately rough
planed wood, well-joint
concrete, good formwork, high cement contents 80 0,8
non-planed wood; concrete pipes 75 1,5
hard-burned bricks, carefully joint;
well-manufactured ashlar facing;
concrete from joint-free wooden formwork
90...100 0,1...0,3
85...90 0,4
70...75 1,5...2,0
0,05
0,03...0,06
0,6
rolling-cast asphalt finish 70 2
ashlar masonry, well-manufactured;
moderately incrusted steel pipes;
rough
non-finished concrete, wooden formwork;
squared stones; old and swelled wood;
cement walls
non-finished concrete; old wooden formwork;
brickwork, no joints, finished;
dry stone wall, less carefully manufactured;
soil material, smooth (fine-grained)
Rougher surfaces are difficult to measure under hydraulic aspects and hence are not described here
65...70 3
60 6
Instruction Manual
OCM F
OCM F - Rev. 04 as of 18.02.2014Page 97
15Emergency
In case of emergency
− press the emergency-off button of the main system or
− set the slide switch (see Fig. 7-12) on the unit to OFF.
16Dismantling/Disposal
The device shall be disposed according to the local regulations for electronic
products.
Fig. 7-3 Clamp wiring OCM F ......................................................................................................................... 24
Fig. 7-4Connection of 1 wedge or pipe sensor (no Ex), Type K0 or R0 .......................................................25
Fig. 7-5
Fig. 7-6 Connection of 1 KDA wedge or pipe sensor (Ex), Type K0 or R0 .................................................... 26
Fig. 7-7 Connection of 1 KDA combi sensor (Ex) with integrated pressure measurement cell, Type KP ..... 26
Fig. 7-8 Connecting an ext. 2-wire sensor (no Ex) for flow level measurement............................................. 26
Fig. 7-9 Connecting a NIVUS i-Serial sensor for level measurement in Ex-Zone 1 ...................................... 27
Fig. 7-10Connecting an ext. 2-wire sensor (Ex) for flow level measurement..................................................27
Fig. 7-11
Fig. 7-12 Slide switch position in terminal clamp housing ................................................................................ 28
Fig. 7-13 AC model power supply .................................................................................................................... 28
Fig. 7-14 DC model power supply .................................................................................................................... 29
Fig. 7-15 Connecting the overvoltage protection for power supply and analog inputs and outputs ................ 30
Fig. 7-16Overvoltage protection compact Doppler active sensor ...................................................................31
Fig. 7-17
Fig. 7-18 Setup of a controlled system such as a discharge control ................................................................ 33
Fig. 7-19 Wiring diagram for controller operation ............................................................................................. 34
Fig. 9-4 Day values ......................................................................................................................................... 42
Fig. 9-5 Time of day totalising ........................................................................................................................ 42
Fig. 9-8 System information............................................................................................................................ 44
Fig. 9-9 Additional system information ........................................................................................................... 44
Fig. 9-10 Selecting the unit system .................................................................................................................. 45
Fig. 9-11 Selecting the units ............................................................................................................................. 45
Fig. 9-12Selecting the display format ..............................................................................................................45
Fig. 9-13
Fig. 9-14 complete system time ....................................................................................................................... 46
Fig. 9-18 Setting the name (of the measurement place) .................................................................................. 48
Fig. 9-19 Accepting the new name ................................................................................................................... 48
Fig. 9-25 Menu level measurement .................................................................................................................. 51
Fig. 9-26 Example in case of external level sensor .......................................................................................... 51
Fig. 9-27 Determine the sensor type ................................................................................................................ 51
Fig. 9-28 Sensor type 1: Pressure int. .............................................................................................................. 52
Fig. 9-29 Sensor type 2: Constant level ........................................................................................................... 52
Fig. 9-37 Analog output signal quality .............................................................................................................. 57
Fig. 9-48 Control unit basic settings ................................................................................................................. 62
Fig. 9-49 Setting the external setpoint .............................................................................................................. 63
Fig. 9-50 Control unit settings .......................................................................................................................... 63
Fig. 9-63 Control unit selection ......................................................................................................................... 71
Fig. 9-64 Control menu for test control unit ...................................................................................................... 71
Fig. 9-65 CAL- menu selection ......................................................................................................................... 72
Fig. 9-78 Adjustment of analog outputs ............................................................................................................ 77
Fig. 9-79 Simulation of analog outputs ............................................................................................................. 78
Fig. 9-82 PaDa Installation Warning ................................................................................................................. 80
Fig. 9-83 PaDa English ..................................................................................................................................... 80
Fig. 12-1 Determination of reference level under operating conditions ........................................................... 92
Instruction Manual
Page 100 OCM F - Rev. 04 as of 18.02.2014
®
18 Index
A
Analog outputs 57, 67
C
Cable Glands 22
Calibration menu 72
Channel shape 48
Clamp wiring 24
Connecting an i serial sensor 27
Connection 22
Control algorithm 35
Control unit 62
Copyright 3