Nivus ocm pro cf Instruction Manual

Instruction manual
OCM Pro CF
®
OCM Pro CF - Rev. 09 as of 07.06.2016 page 1

Instruction Manual for

OCM Pro CF Measurement Device

(Original Instruction manual – German)
NIVUS GmbH
Im Taele 2 75031 Eppingen, Germany Phone +49 (0) 72 62 / 91 91 - 0 Fax +49 (0) 72 62 / 91 91 - 999 E-mail: info@nivus.com Internet: www.nivus.com
valid as of Software Revision No. 5.08
Firmware Radar: v1.00
Branch offices
page 2
®
IVUS AG
NIVUS Sp. z o.o.
Hauptstrasse 49 CH - 8750 Glarus Tel.: +41 (0)55 6452066 Fax: +41 (0)55 6452014 E-Mail: swiss@nivus.com Internet: www.nivus.de
NIVUS Austria
Mühlbergstraße 33B A-3382 Loosdorf Tel.: +43 (0)2754 567 63 21 Fax: +43 (0)2754 567 63 20 E-Mail: austria@nivus.com Internet: www.nivus.de
NIVUS France
14, rue de la Paix F - 67770 Sessenheim Tel.: +33 (0)3 88071696 Fax: +33 (0)3 88071697 E-Mail: france@nivus.com Internet: www.nivus.com
NIVUS U.K. Ltd
Wedgewood Rugby Road Weston under Wetherley Royal Leamington Spa CV33 9BW, Warwickshire Tel.: +44 (0)1926 632470 E-mail: info@nivus.com Internet: www.nivus.com
NIVUS U.K.
1 Arisaig Close Eaglescliffe Stockton on Tees Cleveland, TS16 9EY Phone: +44 (0)1642 659294 E-mail: info@nivus.com Internet: www.nivus.com
ul. Hutnicza 3 / B-18 PL - 81-212 Gdynia Tel.: +48 (0) 58 7602015 Fax: +48 (0) 58 7602014 E-Mail: poland@nivus.com Internet: www.nivus.pl
NIVUS Middle East (FZE)
Building Q 1-1 ap. 055 P.O. Box: 9217 Sharjah Airport International Free Zone Tel.: +971 6 55 78 224 Fax: +971 6 55 78 225 E-Mail: Middle-East@nivus.com Internet: www.nivus.com
NIVUS Korea Co. Ltd.
#411 EZEN Techno Zone, 1L EB Yangchon Industrial Complex, Gimpo-Si Gyeonggi-Do 415-843, Tel. +82 31 999 5920 Fax. +82 31 999 5923 E-Mail: korea@nivus.com Internet: www.nivus.com
Instruction manual
OCM Pro CF
®
OCM Pro CF - Rev. 09 as of 07.06.2016 page 3
Translation
If the device is sold to a c ountry in the European currency area, th is in­struction handbook m ust be translated into the lan guage of the country in which the device is to be used. Should the translated text be unclear, the original instruction handbook (German) must be c onsulted or the manufacturer contacted for c larifica­tion.
Copyright
No part of this publication may be reproduced, transmitted, sold or dis­closed without prior permission. Damages will be claimed for violations. All rights reserved.
Names
The use of general desc riptive names, trade names, t rademarks and the like in this handbook does not entitle the reader to assume they may be used freely by everyone. T hey are often protected registered tradem arks even if not marked as such.
Instruction manual
OCM Pro CF
page 4 OCM Pro CF - Rev. 09 as of 07.06.2016
®
1 General ................................................................................. 7
2 Safety Instructions and Hazard Warnings ......................... 9
2.1 Used Hazard Warnings ................................................................. 9
2.2 Safeguards and Precautions ....................................................... 10
2.3 Liability Disclaimer ....................................................................... 10
2.4 User’s Responsibilities ................................................................ 11
2.5 Device Identification .................................................................... 12
2.6 Installation of Spare Parts and Parts subject to wear and tear ... 13
2.7 Device Versions .......................................................................... 13
3 Overview and Intended Use .............................................. 14
3.1 Overview ..................................................................................... 14
3.2 Intended Use ............................................................................... 16
4 Specifications .................................................................... 17
5 Storing, Delivery and Transport ....................................... 18
5.1 Receipt ........................................................................................ 18
5.2 Delivery ....................................................................................... 18
5.3 Storing ......................................................................................... 18
5.4 Transport ..................................................................................... 18
5.5 Return .......................................................................................... 18
6 Functional Description ...................................................... 19
6.1 General ........................................................................................ 19
6.2 Level measurement using water ultrasound ............................... 23
6.3 Level Measurement using Pressure ............................................ 24
6.4 Level Measurement using external Leve l Sensor ....................... 24
6.5 Flow Velocity Detection ............................................................... 25
6.6 Flow velocity via Surface Radar OFR ......................................... 27
7 Installation and Connection .............................................. 28
7.1 Installation Instructions ................................................................ 28
7.1.1 Fastening Wall Mount Enclosure ................................................ 28
7.1.2 Wall Mount Enclosure Dimensions ............................................. 29
7.2 Electrical Installation.................................................................... 30
7.2.1 Connection of Transmitter in Wall Mount Enclosure ................... 30
7.2.2 Sensor connection - Wall mount enclosure ................................ 34
7.2.3 Wall Mount Enclosure Overvoltage Protection ........................... 38
7.3 Connection of the panel mount enclosure................................... 41
7.3.1 Fastening the panel mount enclosure ......................................... 41
7.3.2 Panel Mount Enclosure Dimensions ........................................... 41
7.3.3 Panel Mount Enclosure Transmitter Connection ........................ 41
7.3.4 Panel mount enclosure sensor connection ................................. 43
7.3.5 Panel Mount Enclosure Overvoltag e Pr otec t ion ......................... 47
7.4 Power Supply Wall and Panel Mount Enclosur e ......................... 49
7.5 Regulator Mode ........................................................................... 50
7.5.1 General ........................................................................................ 50
7.5.2 Construction of Measurement Section ........................................ 52
7.5.3 Regulator Mode Wiring Diagram ................................................. 53
7.5.4 Control Algorithm ......................................................................... 53
7.6 Communication ........................................................................... 54
7.6.1 General ........................................................................................ 54
7.6.2 Communication Options .............................................................. 56
7.6.3 Communication Setup via Acc es s Portal .................................... 57
7.6.4 Data Transmission ...................................................................... 59
Instruction manual
OCM Pro CF
®
OCM Pro CF - Rev. 09 as of 07.06.2016 page 5
8 Initial Start-Up .................................................................... 65
8.1 General ........................................................................................ 65
8.2 Operator Panel ............................................................................ 66
8.3 Display ......................................................................................... 67
8.4 Operation Basics ......................................................................... 69
9 Parameter Setting .............................................................. 70
9.1 Setting Basics .............................................................................. 70
9.2 Operation Mode (RUN) ............................................................... 73
9.3 Display Menu (EXTRA) ............................................................... 77
9.4 Parameter Menu (PAR) ............................................................... 79
9.5 Parameter Menu (PAR) ............................................................... 79
9.5.1 Parameter Menu "Measurement Place" ...................................... 79
9.5.2 Parameter Menu “Level “ ............................................................ 86
9.5.3 Parameter Menu „velocity “ ......................................................... 98
9.5.4 Parameter Menu "Analog Inputs “ ............................................. 105
9.5.5 Parameter Menu "Digital Inputs " .............................................. 107
9.5.6 Parameter Menu "Analog Outputs" ........................................... 109
9.5.7 Parameter Menu "Digital Outputs “ ........................................... 111
9.5.8 Parameter Menu "Control unit " ................................................ 114
9.5.9 Parameter Menu "Settings “ ...................................................... 122
9.5.10 Parameter Menu "Storage Mode “ ............................................ 124
9.5.11 Data Structure on Memor y Card ............................................... 128
9.5.12 Parameter Menu "Communication “ .......................................... 130
9.6 Signal Input/Output Menu (I/O) ................................................. 136
9.6.1 I/O Menu „Analog inputs ” ......................................................... 136
9.6.2 I/O Menu "Digital Inputs ” .......................................................... 137
9.6.3 I/O Menu „Analog Outputs” ....................................................... 137
9.6.4 I/O Menu „Digital Outputs” ........................................................ 138
9.6.5 I/O Menu „Sensors” ................................................................... 138
9.6.6 I/O Menu "Interfaces" ................................................................ 141
9.6.7 I/O Menu "Controller" ................................................................ 141
9.6.8 I/O-Menu "Memory Card" .......................................................... 142
9.6.9 I/O-Menu Communication ......................................................... 145
9.7 Calibration and Calculation Menu (CAL) ................................... 145
9.7.1 Cal-Menu "Level“ ....................................................................... 145
9.7.2 Cal-Menu "Flow Velocity “ ......................................................... 146
9.7.3 Cal-Menu "Analog Outputs “ ..................................................... 149
9.7.4 Cal-Menu "Relay Outputs “ ....................................................... 150
9.7.5 Cal-Menu "Simulation “ ............................................................. 151
10 Parameter Tree................................................................. 152
11 Troubleshooting .............................................................. 162
12 Verification of the Measurement Systems ..................... 166
12.1 General ...................................................................................... 166
12.2 Verification of Combi Sensor with Pressure Measurement Cell166
12.3 Verification of external Level Measurement .............................. 167
12.4 Verification and Simulation of Input and Output Signals ........... 168
12.5 Verification of Flow Velocity Measurement ............................... 168
13 Maintenance and Cleaning ............................................. 170
13.1 Transmitter ................................................................................ 170
13.2 Sensors ..................................................................................... 170
14 Accessories ..................................................................... 171
15 Table "Manning - Strickler Coefficients “ ...................... 172
Instruction manual
OCM Pro CF
page 6 OCM Pro CF - Rev. 09 as of 07.06.2016
®
16 Emergency ....................................................................... 173
17 Dismantling/Disposal ...................................................... 173
18 Table of Pictures .............................................................. 173
19 Index ................................................................................. 177
20 Certificates and A p prov al s ............................................. 179
Instruction manual
OCM Pro CF
®
OCM Pro CF - Rev. 09 as of 07.06.2016 page 7

1 General

Important
READ CAREFULLY BEFORE USE KEEP IN A SAFE PLACE FOR LATER REFERENCE
This Instruction manual for the flow measurement unit OCM Pro CF is intended for the initial start-up of the unit depicted on the title page. This manual is orient­ed exclusively to qualified expert personnel.
Read this instruction manual carefully and completely prior to installation and connection since it contains relevant information on this product. Observe the notes and particularly follow the warning notes and safety instructions. Keep this manual in a safe place and make sure it is available for the users of this product at any time.
If you should have problems to understand information contained within this in­struction manual either contact the manufacturer or one of the distributors for further support. The manufacturer cannot be held responsible for damage to persons or material due to incorrectly understood information in this instruction.
In case of selling the instrument this instruction manual shall be provided to the purchaser since it is a part of the standard delivery.
Detailed information on how to operate the complete system can be found in the accompanying instruction manual oft NIVUS, Sensors etc.

Personnel requirements

Installation, commissioning and maintenance shall be executed only by person­nel meeting the demands as follows:
- Exper t per sonn el with rel evant tra in ing an appr opr ia te qua lif icati on
- Personnel authorised by the plant operator
Qualified personnel
within the context of this documentation or the safety notes on the product itself are persons who are sufficiently familiar with installation, mounting, start­ing up and operation of the product and who have the relevant qualifications for their work; for example.
- Training, instruction or authorisation to ac t iv ate/ deac t ivate, is ol ate, ground,
and mark electric circuits and devices/systems according to the safety en­gineering standards.
- Education and instruction according to the standards of safety engineering
regarding the maintenance and us e of adequa te safety equipment.
- First aid training
Instruction manual
OCM Pro CF
page 8 OCM Pro CF - Rev. 09 as of 07.06.2016
®

Applicable documentation

For the installation and operation of the complete system extra instruction man­uals or technical descriptions may be required apart from this manual.
- Technical Instructions for correlation sensors and Electronic box
- Technical and Installation Instruction for Radar sensors OFR
These manuals are provided with the auxiliary units or sensors.
Instruction manual
OCM Pro CF
®
OCM Pro CF - Rev. 09 as of 07.06.2016 page 9
DANGER
WARNING
WARNING
CAUTION

2 Safety Instructions and Ha zard Warnings

2.1 Used Hazard Warning s

The general warning symbol indicates the risk of personal injuries or death. In the text section the general warning symbol is used in conjunction with the signal words described below.
Hazard warnings
Indicates an immediate high risk which may result in death or severe personal injury if not avoided.
Danger of electrical shock
Indicates a possible danger by electrical power with moderate risk which may result in death or severe personal injury if not avoided.
Warning notice
Indicates a possible danger with moderate risk which may result in death or severe personal injury if not avoided.
Notes for caution
Indicates a possible danger with moderate risk that may result in minor or moderate injury or may result in property damage, if not avoided.
Important Note
Indicates a situation that could cause damage on this instrument if it is not avoided.
Contains information that should be highlighted.
Note
Indicates a situation that will not result personal injury.
Instruction manual
page 10 OCM Pro CF - Rev. 09 as of 07.06.2016
®
WARNING
WARNING
WARNING
WARNING

2.2 Safeguards and Precautions

Germ contamination
Please note that due to the operation in the waste water field the measure­ment system and cables may be loaded with dangerous disease germs. Re­spective precautionary measures must be taken to avoid damage to one’s health.
Wear protective clothing.
Observe regulations for health and safety at work
Before starting installation w ork , observing the work safety regulations need to be checked.
Failure to do so may cause personal injury..
Do not disable safety devices!
It is strictly prohibited to disable the safety devices or to change the way they work.
Failure to observe may cause personal injury as well as to system damage.
OCM Pro CF

2.3 Liability Disclaimer

Disconnect from power supply
Disconnect the instrument from power supply before you begin to execute maintenance, cleaning and/or repair works. Repair works shall be executed solely by expert personnel.
Disregarding may lead to electrical shocks.
Important Note
The entire measurement system shall be installed and put into oper ation only by qualified personnel.
The manufacturer reserves the right to change the contents of this document in­cluding this liability disclaim er without pr ior notice and cannot be held responsi­ble in any way for possible consequences resulting from such changes.
For connection, initial start-up and operation of the OCM Pro CF the following in­formation and higher legal regulations (e.g. in Germany VDE), such as Ex­regulations as well as safety requirements and regulations in order to avoid ac­cidents, must be kept. All operations on the device which go beyond installation or connection measures in principle shall be carried out by NIVUS staff or personnel author­ised by NIVUS due to reasons of safety and guarantee. The manufacturer is not liable for failures resulting from improper or inappropriate use.
Instruction manual
OCM Pro CF
®
OCM Pro CF - Rev. 09 as of 07.06.2016 page 11

2.4 User’s Responsibilities

Important Note
In the EEA (European Economic Area) national implementation of the frame­work directive 89/391/EEC and corresponding individual directives, in particu­lar the directive 89/655/EEC concerning the minimum safety and health re­quirements for the use of work equipment by workers at work, as amended, are to be observed and adhered to.
The customer shall obtain any local operating permits required and observe the provisions contained therein. In addition to this, he must observe local laws and regulations on
- personnel safety (accident prevention regulations)
- safety of work materials and tools (safety equipment and maintenance)
- disposal of products (laws on wastes)
- disposal of materials (laws on wastes)
- cleaning (cleansing agents and disposal)
- environmental protection

Connections:

As an operator make sure prior to activating the OCM Pro CF that duri ng ins ta l­lation and initial start-up, if executed by the operator himself, the local regula­tions (such as regulations for electrical connection, operation in channels) are observed.
Instruction manual
page 12 OCM Pro CF - Rev. 09 as of 07.06.2016
®

2.5 Device Identification

The instructions in this manual are valid only for the type of device indicated on the title page. The nameplate is fixed on the bottom of the device and contains the following:
- Name and address of manufacturer
- CE label
- Type and serial number
- Year of manufacture
- Ex-label (on Ex-version devices only) as mentioned in chapter Specifica-
tions.
It is important for queries and replacement part orders to specify type, year of manufacture and serial number (Article no. if necessary). This ensures correct and quick processing.
OCM Pro CF iin front panel enclosure with S4/M4 backplane:
OCM Pro CF
OCM Pro CF in wall mount enclosure with S3/M3 backplane:
OCM Pro CF in wall mount enclosure with S4/M4 backplane:
Ex nameplate:
Fig. 2-1 OCM Pro CF nameplates
Instruction manual
OCM Pro CF
®
OCM Pro CF - Rev. 09 as of 07.06.2016 page 13
OCP-
Type S4
M4
R4
F0 W0
00 IN MA MI MG
A4 D4
0 E
OCP-
Intrinsically safe sensor supply in Ex zone 1
Internet communication via GPRS (GSM antenna required) (for W0
Power Supply
100-240 V AC / 47-63 Hz
9-36 V DC
ATEX Approval s
none
Internet communication via internal ISDN modem (for W0 enclosure)
Standard version w ith 2 relays, 2 mA output (galv. isolated), 1 mA input (galv. isolated w ith 2-w ire sensor supply) or for external level measurement
Multifunctional version w ith 5 relays, 4 mA outputs (galv. isolated), 4 digital inputs, 5 analog inputs (1 of them galv. isolated with 2-w ire sensor supply), integrated 3-point step controller with flush function, connecting options for up to 3 sensors
Panel mounting IP54 / IP20, no data transmission available
Construction
Wall-mounting IP65
Data Transm ission
without Internet comm unication (for F0 enclosure)
Internet communication via Intranet (for W0 enclosure)
Internet communication via internal analog modem (for W0 enclosure)
Multifunctional version w ith 5 relays, 4 mA outputs (galv. isolated), 4 digital inputs, 5 analog inputs (1 of them galv. isolated with 2-w ire sensor supply), integrated 3-point step controller with flush function, connecting options for one Radar sensors, type OFR

2.6 Installation of Spare Parts and Parts subject to wear and tear

We herewith particularly emphasize that replacement parts or accessories, which are not supplied by us, are not certified by us, too. Hence, the installation and/or the use of such products may possibly be detrimental to the device’s abil­ity to work or even lead to instrument failure. Damages or measurement errors caused by the use of non-original parts and non-original accessories are left at user’s risk. You can find spare parts or ac­cessories in chapter 14.

2.7 Device Versions

The OCM Pro CF measurement transmitter is available in different versions. The type key below gives a brief overview on the various possibilities. The transmitters vary in terms of the number of inputs and outputs, enclosure construction, data transmission options, power supply and Ex protection. The current type of device is indicated by the article number, which can be found on a weatherproof label on the bottom of the enclosure. From the type key below the type of device can be specified precisely.
Fig. 2-2 Type key for OCM Pro CF measurement transmitters
Instruction manual
page 14 OCM Pro CF - Rev. 09 as of 07.06.2016
®

3 Overview and Intended Use

3.1 Overview

OCM Pro CF
A Wall mount enclosure B Panel mount enclosure 1 Slot with plugged Memory Card 2 USB interface (for service purposes only) 3 Keypad 4 Graphic display 5 Cable glands (only wall mount enclosure) 6 Terminal clamp housing with cover (only wall mount enclosure)
Fig. 3-1 Overview enclosure
Instruction manual
OCM Pro CF
®
OCM Pro CF - Rev. 09 as of 07.06.2016 page 15
Flow velocity wedge sensor, type POA-V200/V2D0
Flow velocity wedge sensor, type CS2
Flow velocity pipe sensor, type CS2, with sensor screw joint and retaining element
Flow velocity pipe sensor, type POA, with sensor screw joint and retaining element
Flow velocity wedge sensor, type CSM-V1D0
Air-ultrasonic level sensor, type DSM
Electronic Box, type EBM
1 Flow velocity wedge sensor, type POA-V2H1/V2U1 2 3 4 5 6 Air-ultrasonic level sensor, type OCL-L1 7 Flow velocity wedge sensor, type CSM-V100 8 9 10 11 Flow velocity radar sensor, type OFR
Fig. 3-2 Overview sensors and electronic box
Instruction manual
page 16 OCM Pro CF - Rev. 09 as of 07.06.2016
®
Transmitter:
CAUTION

3.2 Intended Use

OCM Pro CF
Important Note
The device is exclusively intended to be used for purposes as described below.
Modifying or using the devices for other purposes without the written consent of the manufacturer will not be considered as use in accordance with the re­quirements.
Damages resulting from this are left at user’s risk. The device is designed for a lifetime of approx. 10 years. After that period an
inspection in addition with a general overhaul must be carried out.
The measurement device type OCM Pro CF including the respective sensor technology supplied by NIVUS is intended to be used for continuous flow meas­urement of slight to heavy polluted media in part filled and full channels, pipes or similar. Here the allowed maximum values, as specified in chapter 0, must be strictly kept. All cases which vary from these conditions and are not approved by NIVUS GmbH in written form are left at owner’s risk.
Important Note
Install the device outside of Ex zones! The Ex approval of the sensors is part of the „Technical Description for Corre-
lation Sensors“.

Ex-Identification

II (2)G [Ex ib Gb] IIB
Damages invalidate the Ex protection
Damage might invalidate the Ex protection. The OCM Pro CF then is not allowed to be used in Ex area any longer. Protect the OCM Pro CF from shocks, drops or other damage.
Note
The approval is only valid in connection with the respective indication on the device nameplate.
The Ex-version of OCM Pro CF is matched to the NIVUS sensors regarding the assessment of intrinsically safe electrical systems according to EN 60079-25.
In case of using sensors from third party manufacturers the operator must carry out a system review according to EN 60079-25!
The required specifications of the OCM Pro CF Ex version can be taken from the EC-type examination certificate TÜV 00 ATEX 1572.
Instruction manual
OCM Pro CF
®
OCM Pro CF - Rev. 09 as of 07.06.2016 page 17
Supply power
100 – 240 V AC, +10% /-15%, 47 to 63Hz Max. consumption
AC: 31 VA / DC: 34 W
Typ. consumption
1x POA-V1U1 + 1x NMC0 + 1 relay energised,
Wall mount enclosure
Material: Polycarbonate
Panel mount enclosure
Material: Polycarbonate
Ex-Approval (optional)
II (2)G [Ex ib Gb] II B
Operating temperature
-20°C to +50°C [Ex: -20°C to +40°C]
Storage temperature
-30°C to +70°C
Max. humidity
80%, non-condensing
Display
Back-lit graphic display, 128 x 128 pixel
Operation
18 keys, dialog mode in German, English, French, Czech, Italian,
Inputs
1 x 4-20 mA for external level measurement (2-wire sensor)
Outputs
2 x (type S4) or 4 x (type M4) 0/4-20 mA, load 500 Ohm,
Data memory
1 MB internal data memory for programming and saving of readings
Storage cycle
1 to 60 minutes
Data transmission
Modbus TCP using integrated web server coupling via networks

4 Specifications

or 9- 36 V DC
230 V AC: (rounded) 14 W 1x POA-V1U1 + 1 relay energised, 230 V AC = (rounded) 14 W
-
- Weight: approx. 3400g
- Protection: IP 65
-
- Weight: approx. 2800 g
- Protection: IP 54 (front side), IP 20 (reverse side)
Spanish, Polish, Danish, Swedish
-
- 1 x RxTx-Bus for NIVUS air-ultrasonic sensor type OCL/DSM
- 1 x (type S4) or 4 x (type M4) 0/4-20 mA 12 bit resolution for external
level measurement, external control set points and external units data storage, accuracy +/- 0.4 % of final value (20 mA)
- 4 digital inputs (t ype M4 onl y)
- 1 (type S4) or 2/3 (type M4) velocity sensors (POA, CS2 or electronic
box EBM + CSM) connectable
-
12 bit resolution, accuracy better than 0.1 %
- 2 x (type S4) or 5x (type M4) switchable relays, loadable up to 230 V
AC / 2 A (cos. φ 0.9), minimum switching load 10 mA
-
- optional plug-in Compact Flash Card up to 128 MB
-
(for panel mount enclosure only)
- (LAN /WAN, Internet)
- Internet via Ethernet
- internal ISDN-, GPRS- or analog modem (optional)
Sensors (optional)
For the specifications on t he according sensors please see the a ppropriate instruction manuals or tech­nical descriptions.
Instruction manual
page 18 OCM Pro CF - Rev. 09 as of 07.06.2016
®
max. Temperature: + 70°C

5 Storing, Deliver y and Transport

5.1 Receipt

Check your delivery according to the delivery note for completeness and intact­ness immediately after receipt. Report any damage in transit to the carrier im­mediately. Send a written report to NIVUS GmbH Eppingen as well. Report any delivery incompleteness in writing to your representative or directly to NIVUS Eppingen within two week s
Mistakes cannot be rectified later!

5.2 Delivery

The standard delivery of the OCM Pro CF measurement system contains:
- the instruction manual with the certificate of conformity. Here, all necessary
steps to correctly install and to operate the transmitter are listed.
OCM Pro CF

5.3 Storing

5.4 Transport

- one OCM Pro CF transmitter, type S4, M4 or R4
- one pc. of evaluation software type NivuSoft 2.0 for Windows
Check any additional accessories by using the delivery note.
Maintain the storage conditions:
min. Temperature: - 30°C max. humidity: 80 %, non-condensing
During the storage always protect the device from corrosive or organic solvent vapours, radioactive radiation and strong electromagnetic radiation.
Protect the measurement system from shock and impact loads and vibrations. The transportation must be carried out in the original packaging.
®
Vista, 7 or 8

5.5 Return

The units must be returned at customer cost to NIVUS Eppingen in the original packaging free of charge. Returns with insufficient pos tage will not be accepted!
Instruction manual
OCM Pro CF
®
OCM Pro CF - Rev. 09 as of 07.06.2016 page 19

6 Functional Descripti on

6.1 General

The OCM Pro CF is a stationary measurement system for flow measurement and storage of the detected measurement data. Type M4 additionally allows to use a 3-step controller to drive a slide valve or similar flow control actuator. Fur­thermore up to 4 external measurement values can be stored. Wall mount en­closure units can be accessed remotely using the TCPIP protocol via Internet. The device is designed to be used for measurements primarily in slight to heavy polluted media with various compositions. It can be operated in part filled and full channels and pipes with various shapes and dimensions.
Important Note
The method of flow velocity investigation is based on the ultrasound reflection principle. Hence, it is indispensable for the system to work that there are particles in the water, which are able to reflect the ultrasonic signal sent by the sensor (dirt particles, gas bubbles or similar). Alternative the surface velocity can be measured by using an OFR radar sensor. This sensor must not get in contact with the medium.
The OCM Pro CF type S4 either uses a POA or a CS2 sensor which simultane­ously determines f low veloc it y and flo w level. Alternatively, a CSM sensor in con-junction with the electronic box EBM may be connected, which however merely is a flow velocity sensor. Type M4 allows to connect up to 3 POA or CS2 sensors or type EBM electronic boxes with type CSM sensors at the same time to accurately detect the flow ve­locity at one common measurement point. In order to connect a type OFR surface radar the first sensor input can be used. Use a transmitter type R4 for this kind of connection.
Instruction manual
OCM Pro CF
page 20 OCM Pro CF - Rev. 09 as of 07.06.2016
®
h
v
sensor type POA/CS2
sensor type OCL
OCP/S4
AI external level Sensor 4
Sensor 1
h
v
sensor type CSM
sensor type DSM
Sensor 2 Sensor 3
Electronic Box type EBM
OCP/S4
AI external level Sensor 4
Sensor 1 Sensor 2 Sensor 3
h
Sensor type OFR
OCP/S4 + R4
AI external level Sensor 4
Sensor 1 Sensor 2 Sensor 3
Fig. 6-1 Possible combinations OCP type S4 / R4
Note
A maximum of one OFR surface radar can be connected.
Instruction manual
OCM Pro CF
®
OCM Pro CF - Rev. 09 as of 07.06.2016 page 21
Mounting plate
Acoustic coupling layer
Temperature sensor
Level sensor (optional)
Elektronics
Pressure sensor (optional)
Duct for pressure measurement (optional)
1 2 3 4 Flow velocity sensor 5 6 7 8 9 Cable gland
Fig. 6-2 Possible combinations OCP type M4
Note
A maximum of one air-ultrasonic sensor type OCL or DSM (with EBM) may be connected to a measurement system.
Fig. 6-3 Basic design POA wedge sensor
Instruction manual
page 22 OCM Pro CF - Rev. 09 as of 07.06.2016
®
Mounting plate
Acoustic coupling layer
Flow velocity sensor for positive flow direction
Pressure sensor (optional)
Duct for pressure measurement (optional)
Temperature sensors (sensors without pressure cell only)
Protective hose (optional)
Mounting plate
Acoustic coupling layer
Cable gland
Sensor cable
1 2 3 4 Water-ultrasonic level sensors (optional) 5 Electronics 6 7 8 9 Protective cover for sensor cable and protective hose fastening 10 Sensor cable 11
OCM Pro CF
Fig. 6-4 Basic design CS2 wedge sensor
1 2 3 Temperature sensor 4 Flow velocity sensor 5 6
Fig. 6-5 Basic design CSM wedge sensor V100
Instruction manual
OCM Pro CF
®
OCM Pro CF - Rev. 09 as of 07.06.2016 page 23
2 Sensor for level measurement (P-Series or i-series sensors)
3 Combi holder made of stainless steel (ZUB0OFRHAL)
2
•lt
c
hl=
h
= filling level
c
= sound transit time
t1
= time between transmit and receive signal
1 Sensor OFR
Fig. 6-6 Overview radar, level sensor and holder

6.2 Level measurement using water ultrasound

Depending on the selected sensor type, the water-ultrasonic combi sensor may contain up to 2 different built-in level measurements: water-ultras onic and h y­drostatic level measurement. In this case type POA contains one sensor crystal; type CS2 uses 2 sensor crystals with different dimensions. The sensor type CSM does not have an optional level measurement available; it is a pure flow velocity sensor.
The water-ultrasonic level measurement uses one or more horizontal sensor crystal(s) utilising the ultrasonic transit time method. Here the period between transmission and reception of a signal reflected from the water surface is meas­ured.
The sound travel time in water is 1480 m/s (4.85 fps) at 20 °C (68 °F). The divergence depending on the temperature is 0.23 % per Kelvin. To ensure a level measurement which is accurate to the millimetre, the medium temperature is constantly investigated and the sound transit time is corrected re­spectively for calculation purposes. The fixed level, which is determined by the sensor crystal position, is added to the determined value h1. This results in the total level h.
Instruction manual
page 24 OCM Pro CF - Rev. 09 as of 07.06.2016
®
i-3
i-6
i-10
i-15
4 mA (empty) 0% span
20 mA (full) 100% span

6.3 Level Measurement using Pressure

Depending on the type of sensor used, the sensor may have an additional inte­grated hydrostatic level measurement available. The piezoresistive pressure sensor used operates according to the relative pressure principle, where the pressure of the standing water column above the sensor is directly proportional to the fill level. Fluctuations of the atmospheric pressure are compensated by using a small pipe integrated within the sensor cable. This small pipe is exposed to the atmosphere. This sensor enables to measure fill levels even if the combi sensor is installed out of the channel bottom centre. During initial start-up procedure the sensor is going to be calibrated by using a manually investigated reference value. An additional height due to the sensor in­stallation position will be added as well .

6.4 Level Measurement using external Level Sensor

Depending on the kind of level measurement selected an external 4-20 mA sig­nal can be used for level input (e.g. by using an i-Series sensor).
OCM Pro CF
Note
The i-Series sensors feature pre-programmed measurement ranges. Please refer to detailed information in the instruction manual for i-Series sensors.
i-Series sensors can be also operated without a HART modem. In parameter „Value at 20 mA“ enter the measurement span of the sensor.
Depending on the sensor installation height it may be necessary to additionally enter a negative offset.
distance to sensor face in m
distance to sensor face in m
Span (value at 20 mA) 2.875 5.7 9.7 14.5
Fig. 6-7 Measurement range of i-Series sensors
3.0 6.0 10.0 15.0
0.125 0.300 0.300 0.500
Instruction manual
OCM Pro CF
®
OCM Pro CF - Rev. 09 as of 07.06.2016 page 25

6.5 Flow Velocity Detect io n

The piezo crystal which has a slope towards the flow direction operates as a flow velocity sensor. Here an ultrasonic burst with a defined angle is sent into the medium. All the particles in the measurement path (air, dirt, suspended sol­ids) reflect a small amount of the ultrasonic signal. Depending on shape and size of the particle a particular signal results. Hence, the multitude of the reflected signals results in a reflection pattern (see Fig. 6-8). This pattern is going to be received by the piezo crystal again, converted to electric signals and loaded into a digital signal processor (DSP) which is built in the active sensor.
Fig. 6-8 Situation at first signal reception
After a certain period a second ultrasonic burst is sent into the medium. The newly generated reflection signal is saved in the DSP too.
In various flow levels there are different flow velocities (flow velocity profile). De­pending on the level, the reflecting particles’ movement away from the first measurement point therefore varies. Hence, a distorted reflection pattern results (see Fig. 6-9). At the same time slightly different reflections occur: some parti­cles have been turning around and thus have another shape of reflection; some particles are no longer within the measurement range and others have now moved into the measurement range.
Fig. 6-9 Situation at second signal detection
The DSP checks both the received reflection patterns for similarities using the cross correlation method. All existing signal differences are rejected so that two similar but temporarily offset signal patterns are left for velocity evaluation. Depending on the flow levels both patterns are subdivided into up to 16 mea­surement windows. Then, in each measurement window the lag t of the signal pattern is investigated (see Fig. 6-10).
Instruction manual
OCM Pro CF
page 26 OCM Pro CF - Rev. 09 as of 07.06.2016
®
Fig. 6-10 Echo signal images and evaluation
Based on the beam angle, the interval between both transmitted signals and the lag of the signal pattern therefore in each single measurement window the flow velocity can be determined. Stringing the single flow velocities together mathematically results in the flow profile of the acoustic path which then is indicated on the OCM Pro display and can be read there for inspection and control purposes.
Fig. 6-11 Investigated flow profile
If there are appropriate banking distances on the measurement place available, based on the known channel geometry and the velocity distribution a 3-dimensional flow distribution can be rendered (see Fig. 6-12) (> finite ele­ment< principle.
Instruction manual
OCM Pro CF
®
OCM Pro CF - Rev. 09 as of 07.06.2016 page 27
Fig. 6-12 Computed 3-dimensional flow profile
From this flow velocity distribution and the channel shape, the channel dimen­sions and the filling level the flow volume is calculated and displayed. This vol­ume can either be a free programmable analog signal or an impulse signal as well.

6.6 Flow velocity via Surface Radar OFR

The OFR surface radar OFR is aligned as to face towards the flow direction. Ini­tially emitting radar waves, the instrument then receives the waves reflected from the water surface. From the difference between transmitted and received frequencies it is possible to compute the velocity of the movement (Radar­Doppler-Effect). By using complex integrated algorithms the transmitter now calculates the fol­lowing values from the determined velocity of the water surface:
- The flow profile
- The average velocity of the wetted geometry
Fig. 6-13 Measurement using the surface radar
Instruction manual
page 28 OCM Pro CF - Rev. 09 as of 07.06.2016
®

7 Installation and Connection

7.1 Installation Instructions

- Observe appropriate installation!
- Follow applicable legal or operational guidelines!
- Inappropriate use may result in injuries and/or damage on instruments!
The unit’s mounting place must be selected according to certain criteria. Strictly avoid :
- direct sunlight (use weatherproof cover if necessary, e.g. NIVUS Art. No.
ZMS01800)
- objects radiating strong heat
- permissible ambient temperature: -20° C to +40° C
- objects with strong electromagnetic fields (frequency converters, high volt-
age power lines or similar)
- corrosive chemicals or gases
OCM Pro CF
- mechanic shocks
- vibrations
- radioactive radiation
- direct installation close to footpaths or travel ways

7.1.1 Fastening Wall Mount Enclosure

For fastening the wall mount enclosure, depending on place of mounting, use 4 machine screws size M5 with suitable length as well as the necessary nuts and shims. Or use 4 wood screws, min. diameter 4.5 mm (0.1772 in). These screws must penetrate min. 40 mm (1.575 in) into the wall or min. 50 mm (1.97 in) into appropriate d o wels.
The clear view door as well as the display of the measurement transmitter are covered with a protection foil for protection during transport and from scratches during assembly. This protection foil must be removed immediately after the as­sembly!
Note
If the view door and display protection foil have been exposed to direct solar radiation for a long period, they cannot be removed easily.
This problem may be solved by using methylated spirit or car polish if required to clean the clear view door or the display. If these measures should not be suc­cessful, clear view door as well as display can be replaced by NIVUS (subject to costs).
Instruction manual
OCM Pro CF
®
OCM Pro CF - Rev. 09 as of 07.06.2016 page 29
CAUTION

7.1.2 Wall Mount Enclosure Dimensions

Fig. 7-1 Wall mount enclosure

Hints to avoid electrostatic discharge (ESD)

ESD Risks:
Maintenance procedures which do not require power supply of the instrument shall not be executed before the unit has been disconnected from mains pow­er in order to minimise danger and ESD risks.
Disconnect the iXT from mains power!
The sensitive electronic components inside the unit may get damaged by static electricity. This may impair the instrument’s performance or even lead to instru­ment failure.
The manufacturer recommends the following steps to prevent the device from getting damaged due to electrostatic discharge:
- Discharge static electricity from your body before touching the instrument’s
electronic components.
- Avoid unnecessary movements to reduce the risk of building up static elec-
tricity
- Wear a properly grounded antistatic wrist strap to discharge your body and
to keep away static electricity.
Touch components which ar e sensiti v e to electr ost atic bui ld-up only in antistatic working areas. Use antistatic floor coverings and working surfaces always if possible
Instruction manual
page 30 OCM Pro CF - Rev. 09 as of 07.06.2016
®
CAUTION

7.2 Electrical Installat i on

For electric installation the local regulations in the respective countries (e.g. VDE 0100 in Germany) must be referred to.
Before feeding the rated voltage the transmitter and sensor installation must be correctly completed. The installation shall be carried out by qualified personnel only. Legal standards, provisions and technical regulations need to be observed.
Secure your plant sections
The OCM Pro CF power supply must be separately protected by a 6 A slow-

7.2.1 Connection of Transmitter in Wa ll Mount Enclosure

blow fuse and has to be isolated from other facility parts (separate turn-off, e.g. by using an automatic cut-out with >B< characteristics).
Before feeding the rated voltage the transmitter and sensor installation must be correctly completed. Check the installation for correctness. Observe that installation shall be carried out exclusively by expert personnel. Take further statutory standards, regulations and technical rulings into account.
All outer circuits, wires and lines connected to the device must have a minimum isolation resistance of 250 V. If the voltage exceeds 42 V DC an isolation re­sistance with 500 kOhm min. will be required. The cross-sectional dimension of the power supply wires must be 0.75 mm2 (0.03 in2) and must be in accordance to IEC 227 or IEC 245. The maximum al­lowed switching voltage on the relay contacts must not exceed 250 V and not undershoot 10 mA. According to Ex protection it must be checked if the devices power supplies must be integrated into the facility’s emergency shutdown conception.
OCM Pro CF

General

- The OCM Pro transmitter is available in 3 different versions:
- st andard vers i on t ype >S4<
- Type >M4< with extended connections for up to 3 flow velocity sensors, digi-
tal inputs as well as additional analog inputs / outputs plus controller func­tion.
- Type >R4< featuring extended options to connect a Type OFR radar sensor.
All three models have the same clamp terminal marking. The transmitters M4 and R4 merely have additional connecting options which have not been equipped in type S4.
Important Note
The terminal clamp wiring of wall mount and panel mount enclosure signifi­cantly vary from each other. The wiring diagram of the wall mount enclosure cannot be used for the wiring of a panel mount enclosure! The same applies in reverse.
Instruction manual
OCM Pro CF
®
OCM Pro CF - Rev. 09 as of 07.06.2016 page 31
The wall mount enclosure has cable glands and dummy plugs. Some of them are screwed in or are enclosed as spare parts or additional parts. Number and size of cable glands and dummy plugs depend on the type of transmitter.

Transmitter type S4:

2 glands M20 x 1.5 1 gland M16 x 1.5 2 dummy plugs M20 x 1.5 2 dummy plugs M16 x 1.5

Transmitter type M4:

2 glands M20 x 1.5 3 glands M16 x 1.5 2 dummy plugs M20 x 1.5 2 dummy plugs M16 x 1.5

Transmitter type R4:

2 glands M20 x 1,5 3 glands M16 x 1,5 2 dummy plugs M20 x 1,5 2 dummy plugs M16 x 1,5
With the supplied glands the following outer cable cross-sections can be con­nected reliably:
M16 x 1.5: 3.5 mm – 10.5 mm (0.138 – 0.413 in) M20 x 1.5: 6.0 mm – 14.0 mm (0.236 – 0.591 in)
To be able to use cable diameters outside of the tolerance, glands must be used which ensure IP65 minimum protection. Unused lead-ins have to be locked tightly with an appropriate dummy plug be­fore the initial start-up.
The transmitter is equipped with terminal clamps which ensure reliable connec­tion of single and multi-wired cables with cross-sectional areas of 0.18-2.5 mm² (0.007 – 0.098 in) in order to connect power supply as well as digital / analog outputs and inputs. The sensors (flow velocity, combi, air-ultrasonic or 2-wire level sensors) are equipped with connection plugs due to better handling of the wall mount enclo­sure. The pre-configured cable tips of the NIVUS sensors or single and multi­wired cables with cross-sectional areas of 0.18-2.5 mm² (0.007-0.098 in) can be connected to these plugs. The 7-pole plug-and-socket connections of the 3 flow velocity sensors can be switched with each other. Switching between 7-pole and 9-pole plug rail (9 poles = level sensors) is impossible due to mechanical configuration.
For terminal clamp connection it is necess ary to use a slotted screwdriver with a
3.0 mm or 3.5 mm (0.118-0.138 in) blade. In order to connect the sensors to the terminal strips of the wall mount enclosure use a slotted screwdriver with a 2.0 mm or 2.5 mm (0.079-0.098 in) blade.
Instruction manual
OCM Pro CF
page 32 OCM Pro CF - Rev. 09 as of 07.06.2016
®
The terminal clamps are normally unscrewed on delivery. Nevertheless this must be checked before connecting the power supply or the signal wires.
Note
While connecting, it is helpful to exert slight pressure on the terminal clamp screw.
This ensures safe cable connection by opening the clamp.
Important Note
Close the terminal clamp compartment of the wall mount enclosure by using the accompanying cover and both screws. Closing prevents water or dirt from leaking in.
Observe to not reverse the cover during installation (steeply bevelled side up). The specified protection degree cannot be guaranteed if the cover is not in­stalled correctly.
Instruction manual
OCM Pro CF
®
OCM Pro CF - Rev. 09 as of 07.06.2016 page 33
GND potentials insulated from each other: Internal wiring: b2 + b15; b3 + a14
DI1, DI2, DC-, AI1, AI2, AI3, AI4, AO1, AO2, AO3, AO4
Fig. 7-2 Wiring diagram wall mou nt enclosure OCM Pro CF
Instruction manual
page 34 OCM Pro CF - Rev. 09 as of 07.06.2016
®

7.2.2 Sensor connection - Wall mount enclosure

The sensor cable has to be connected to the transmitter at the terminal block. The diagram below applies in case of connecting a flow velocity or water­ultrasonic combi sensor:
Fig. 7-3 Connecting a flow velocity or water-ultrasonic combi sensor
on the OCM Pro type S4W0 / M4W0
OCM Pro CF
Fig. 7-4 Connecting a second velocity sensor to the OCM Pro type
M4W0
Fig. 7-5 Connecting a third velocity sensor to the OCM Pro type M4W0
Instruction manual
OCM Pro CF
®
OCM Pro CF - Rev. 09 as of 07.06.2016 page 35
Fig. 7-6 Connection electronic box Type EBM with water-ultrasonic
sensor Type CSM and air-ultrasonic sensor Type DSM to Type S4W0 / M4W0
Fig. 7-7 Connection 2, ele ctronic box Type EBM with water-ultrasonic
sensor Type CSM to Type M4W0
Fig. 7-8 Connection 3, ele ctronic box Type EBM with water-ultrasonic
sensor Type CSM to Type M4W0
Instruction manual
OCM Pro CF
page 36 OCM Pro CF - Rev. 09 as of 07.06.2016
®
Fig. 7-9 Connecting a flow velocity sensor with integrated pressure
measurement cell to type W0
Fig. 7-10 Connecting an OFR flow velocity sensor to Type R4W0
Note
The pressure compensation element serves as connection socket for cable extension at the same time. Please observe not to exceed the maximum cable length of 135 m (443 ft.) in Ex areas and 250 m (750 ft.) in Non-Ex areas be­tween sensor and transmitter by taking the maximum permissible resistance into account.
Fig. 7-11 Connecting the air-ultrasonic sensor type LUS to type
M4W0 / S4W0
Instruction manual
OCM Pro CF
®
OCM Pro CF - Rev. 09 as of 07.06.2016 page 37
CAUTION
If the level measurement is carried out by a 2-wire probe (NivuBar, NivuCompact 2-wire echo sounder or similar) which is supplied by the OCM Pro, please follow the wiring diagram below:
Fig. 7-12 Connecting a 2-wire sensor (EX for level measurement)
Do not connect cables without shields
If using sensors in Ex areas DO NOT lay the sensor cable past the mech anica l shield between the terminal blocks.
Otherwise Ex protection is not guaranteed anymore.
Note
Use only the 3 cable connections located directly below the sockets! If using an i-Series (Ex) sensor do not connect the sensor to the Ex clamps. i-Sensors shall be connected to non-Ex clamps.
Fig. 7-13 Connecting a 2-wire sensor for level measurement to type W0
If the mA signal for level measurement is provided from an external transmitter (such as NivuMaster) connect to clamps as follows:
Instruction manual
page 38 OCM Pro CF - Rev. 09 as of 07.06.2016
®
Fig. 7-14 Connecting external level measurement from NivuMaster to
type W0

7.2.3 Wall Mount Enclosure Overvoltage Protection

For effective protection of the OCM Pro transmitter it is necessary to protect power supply as well as mA-output using overvoltage protection devices. NIVUS recommends surge arrestors types EnerPro 220Tr, EnerPro 24Tr (for 24 V DC) for the mains supply, as well type DataPro 2x1 24/24Tr for mA-outputs. The flow velocity sensor as well as the air-ultrasonic sensor type OCL are inter­nally protected against overvoltage. If higher voltages are expected to occur they can be protected by combining the types DataPro 2x1 12/12-11μH-Tr (N) as well as SonicPro 3x1 24 V/24 V
OCM Pro CF
Important Note
If using the sensors in Ex areas consider the connected loads of the overvolt­age protection devices as well as capacity and inductance of the NIVUS sen­sor cables (POA, CS2, OCL, EBM) additionally!
The maximum permissible NIVU S cab le len gths in Ex areas are:
- single-side overvoltage protection: 135 m (443 ft.)
- double-side overvoltage protection: 120 m (394 ft.)
Note
The use of overvoltage protection elements for sensors in Non-Ex areas will reduce the maximum possible cable length. The line resistance is 0.3 Ohm/wire. This resistance must be taken into ac­count considering the allowed total resistance (see "Technical Instructions for Correlation Sensors" for details)
Note
Observe the non-reversed connection (p-side to transmitter) as well as a cor­rect, straight wiring supply. Ground (earth) must lead to the unprotected side.
The overvoltage protection devices are ineffective if wired incorrectly!
Instruction manual
OCM Pro CF
®
OCM Pro CF - Rev. 09 as of 07.06.2016 page 39
Fig. 7-15 Wall mount enclosure - connecting the overvoltage protection
for power supply and analog inputs and outputs
Instruction manual
OCM Pro CF
page 40 OCM Pro CF - Rev. 09 as of 07.06.2016
®
Fig. 7-16 Overvoltage protection water-ultrasonic sensor or electronic
box, wall mount enclosure
Fig. 7-17 Overvoltage protection air-ultrasonic sensor, type OCL, wall
mount enclosure
Instruction manual
OCM Pro CF
®
OCM Pro CF - Rev. 09 as of 07.06.2016 page 41

7.3 Connection of the panel mount enclosure

7.3.1 Fastening the panel mount encl osur e

First the panel must be cut out accordingly (see Fig. 7-18). Then, after the en­closure has been inserted, tighten the 4 clamps integrated in the sides of the en­closure for fastening. The panel mount enclosure can be fastened by using the 4 built-in clamps

7.3.2 Panel Mount Enclosure Dimensions

Fig. 7-18 Panel mount enclosure

7.3.3 Panel Mount Enclosure Transmitter Connection

General Prior to connection please see the instructions in Chap. 7.3.
The transmitter is equipped with terminal clamps which ensure reliable connec­tion of single-wired and multi-wired cables featuring cross-sectional areas of
0.18–2.5 mm² in order to connect power supply as well as digital / analog out­puts and inputs. For terminal clamp connection it is necess ary to use a slotted screwdriver with a
3.0 mm or 3.5 mm blade.
Note
While connecting, it is helpful to exert slight pressure on the terminal clamp screw.
This ensures safe cable connection by opening the clamp.
Instruction manual
OCM Pro CF
page 42 OCM Pro CF - Rev. 09 as of 07.06.2016
®
b15
AI1
b16
AI
2
b17
GND AI 1/2
a15
AI3
a16
AI
4
a17
GND AI 3/4
b18
AO1
b
19
AO
2
b
20
G
ND AO 1/2
a18
AO
3
a19
A
O
4
a2
0
GN
D AO 3/4
b12
DI1
b13
D
I
2
b14
GND DI 1/2
a
1
2
D
I
3
a13
DI
4
a
1
4
G
ND DI 3/4
M
ode
m
b9
b10
a9
a10
a
11
c9
c10
c11
b2+
b
3
GN
D
a3
PE
a2
N
a1L
1
a4Ö
b
4
C
OM
c4Sa5
Ö
b5
COM
c5Sa6Ö
b6
CO
M
c6Sa7
Ö
b7
COM
c
7
S
a8
Ö
b
8
C
O
M
c8S
a2
1
GND E
x
b21
AI5
c21
+Ex
c28
c
29
c27c26c25
c24
c23c2
2
b29b
28
b2
7
b2
6
b25
b24
b2
3b22
100 - 240 V
47. ..63 H z
RxT
x-
Rx
Tx+
GND Ex
US+
RxT
x-
Rx
Tx+
GND Ex
US+
9 - 36 V DC
power supply
ON
OFF
ON
OF
F
ser i al interface
relay 1 relay 2 relay 3 r el ay 4 relay 5
Ex-area
input ext er nal lev el measurement
power
supply
air us
connection v-sensor 3
sh
iel
d
sh
iel
d
connection v-sensor 2
connection
v-sensor 1
ultrasonic level
sensor (air us)
s
hie
ld
a29
a28
a27
a26
a25
a24
a23
a22
Rx
Tx-
RxTx+
GND Ex
US+
Fig. 7-19 Wiring diagram OCM Pro CF panel mount enclosure
Instruction manual
OCM Pro CF
®
OCM Pro CF - Rev. 09 as of 07.06.2016 page 43
OCM Pro (R4)
black (shield, no earth) red 10 V blue white green
Radar
+ 1 • 2 • 0,34 mm²
max. 150 m
LIYC 11Y 2 • 1,5 mm²
a22 a25 a26 a27 a29
outer shield
supply
RxTx -
+
UE-GND
RxTx +

7.3.4 Panel mount enclosure sensor connection

Sensor cables are connected to panel mount enclosures on the reverse side of the transmitter. Follow the wiring diagram below to connect a flow velocity or wa­ter-ultrasonic combi sensor:
Fig. 7-20 Connecting a flow velocity or water-ultrasonic combi sensor to
the OCM Pro CF, type S4F0 / M4F0
Fig. 7-21 Connecting an OFR flow velocity sensor to Type R4F0
Fig. 7-22 Connecting a second flow velocity sensor to type M4F0
Instruction manual
OCM Pro CF
page 44 OCM Pro CF - Rev. 09 as of 07.06.2016
®
Fig. 7-23 Connecting a third flow velocity sens or to type M4F0
Fig. 7-24 Connection electronic box Type EBM with water-ultrasonic
sensor Type CSM and air-ultrasonic sensor Type DSM to Type S4F0 / M4F0
Fig. 7-25 Connection 2, electronic box Type EBM with water-ultrasonic
sensor Type CSM to Type M4F0
Instruction manual
OCM Pro CF
®
OCM Pro CF - Rev. 09 as of 07.06.2016 page 45
Fig. 7-26 Connection 3, electronic box Type EBM with water-ultrasonic
sensor Type CSM to Type M4F0
Fig. 7-27 Connecting a flow velocity sensor with integrated pressure
measurement cell to type F0
Note
The pressure compensation element serves as connection socket for cable extension at the same time. Please note that the maximum cable length between sensor and transmitter (considering the maximum permissible line resistance) shall not exceed 135 m in Ex areas. The maximum cable length in non-Ex areas is 250 m.
Fig. 7-28 Connecting an air-ultrasonic sensor type OCL to type F0
If the level measurement is carried out by a 2-wire probe (NivuBar, NivuCompact 2-wire echo sounder or similar) which is supplied by the OCM Pro, please follow the wiring diagram below:
Instruction manual
OCM Pro CF
page 46 OCM Pro CF - Rev. 09 as of 07.06.2016
®
CAUTION
+
-
OCM Pro
24 V DC
+
-
I = 4 - 20 mA
+
-
Insert
wire bridge
A2Y 2 x 2 x 0,8 or similar, max. 150m (492.15ft)
Ex !
2-wire sensor (e.g. type NivuCompact) or pressure probe (e.g. NivuBar Plus)
no
b2 b3
b15 b17
AE 1
GND AE 1/2
Fig. 7-29 Connecting a 2-wire sensor EX for level measurement to type
F0
Do not connect cables without shields
If using sensors in Ex areas DO NOT lay the sensor cable past the mechani­cal shield between the terminal blocks.
Otherwise Ex protection is not guaranteed anymore.
Fig. 7-30 Connecting a 2-wire sensor for level measurement to type F0
If the mA signal for level measurement is provided from an external transmitter (such as NivuMaster), connect to clamps as follows:
Fig. 7-31 Connecting external level measurement to type F0
Instruction manual
OCM Pro CF
®
OCM Pro CF - Rev. 09 as of 07.06.2016 page 47

7.3.5 Panel Mount Enclosure Overvoltage Protection

Fig. 7-32 Panel mount enclosure - connecting the overvoltage protec-
tion for power supply and analog inputs and outputs (panel mount enclosure)
Instruction manual
OCM Pro CF
page 48 OCM Pro CF - Rev. 09 as of 07.06.2016
®
1p
2p
1
2
DataPro
2 x 1 12 V / 12 V
11µTr (N)
1.5 mm² min.
OCM Pro
red
blue
a22 a25 a26 a27 a29
outer shield
supply
RxTx -
+
UE-GND
RxTx +
1.5 mm² min.
white
green black
1p
2p
1
2
SonicPro
3 x 1 24 V / 24 V
3p 3
water ultrasonic sensor
Radar
Fig. 7-33 Overvoltage protection water-ultrasonic sensor or electronic
box or OFR radar, panel mount enclosure
Fig. 7-34 Overvoltage protection air-ultrasonic sensor type OCL, panel
mount enclosure
Instruction manual
OCM Pro CF
®
OCM Pro CF - Rev. 09 as of 07.06.2016 page 49

7.4 Power Supply Wall and Panel Mount Enclosure

Depending on the type of OCM Pro used the unit can be powered with 85­260 V AC (type: A4) or 8- 36 V DC (type: D4). The two slide switches located above the terminals serve as additional ON or OFF switches.
Wall mount enclosure
Fig. 7-35 Position of slide switch on the bus board
Important Note
A transmitter with 9-36 V DC cannot be operated with alternating current, just as it is impossible to operate a 230 V AC transmitter with 9-36 V direct current.
When operated with alternating current, the direct current supply clamps b2 and b3 both provide a voltage of 24 V and a maximum capacity of 100 mA (turn on 24 V switch!).
Please note, when using this supply voltage (e.g. for digital inputs with control signals), it must not be shielded through the complete switchgear in order to maintain disturbing interferences on a low level.
Panel mount enclosre
Instruction manual
OCM Pro CF
page 50 OCM Pro CF - Rev. 09 as of 07.06.2016
®
Fig. 7-36 AC model power supply
Fig. 7-37 DC model power supply

7.5 Regulator Mode

7.5.1 General

An OCM Pro Type >M4< is required as soon as the transmitter itself shall be used to control the flow rate. Type >M4< has he following features:
- 1 exter na l set po int input
- 2 digital outputs to drive the regulator slide valve
- 2 digital inputs for the slide valve monitoring
If you operate an OCM Pro CF, type S4 for flow rate control please use a suffi­cient external controller and program it according to manufacturer specifications.
Note
Knowledge in control technology is necessarily required in order to correctly and reliably set the controller!
Instruction manual
OCM Pro CF
®
OCM Pro CF - Rev. 09 as of 07.06.2016 page 51
Use sluice gate valves, knife gate valves or iris gate valves with electric-drive three-step controller as control elements. Analog-drive slide valves cannot be used. We recommend the following regulating times (time elapsed between valve completely open and completely closed) for the selection of gate valves: </= 300 mm (11.8 in) diameter: min. 60 seconds </= 500 mm (19,7 in) diameter: min. 120 seconds </= 800 mm (31.5 in) diameter: min. 240 seconds </= 1000 mm (39.4 in) diameter: min. 300 seconds
For the correct driving as well as for error monitoring of the slide valve, the Way­End-Switches “OFF“ and “ON“ as well as the torque switches “ON“ are a manda­tory requirement. These signals have to be connected to the digital inputs of the OCM Pro CF. Please note to select gold-plated contacts in order to ensure con­tact reliability. Connect a signal relay between switches and OCM Pro CF digital input to safely conduct the 10 mA input current. Analog position feedback to OCM Pro CF is not planned. The OCM Pro CF operates as a three-step controller with surge detection, quick close control, slide valve monitoring and automatic flush function. To drive the regulating unit, the digital inputs 4 and 5 are assigned as default. Hence, digital output 4 as “slide valve closed“ and digital output 5 as “slide valve open“ are defined. Analog input 4 is determined for input of external setpoint values (see chapter
7.3.5)
Note
- The assignment of the digital outputs to the regulator cannot be modified.
- The input current on the digital inputs of the OCM Pro CF is 10 mA. Please
ensure contact reliability by selecting sufficient contact materials on the end switch of the control slide valve.
Instruction manual
page 52 OCM Pro CF - Rev. 09 as of 07.06.2016
®

7.5.2 Construction of Measurement Section

For details on the construction measurement and control sections please refer to the "Installation Instruction for Correlation and Doppler sensors”.
OCM Pro CF
Fig. 7-38 Setup of a controlled system suc h as a discharge control
Instruction manual
OCM Pro CF
®
OCM Pro CF - Rev. 09 as of 07.06.2016 page 53

7.5.3 Regulator Mode Wiring Diagram

7.5.4 Control Algorithm

Fig. 7-39 Regulator mode wiring diagram
Note Always use all 3 messages for slide valve control via digital inputs.
Activating one message only may result in disturbed regulator operation.
If the regulator function is selected (see also chapter 9.5.8) relay 4 is going to self-activate for the function “SLIDE VALVE CLOSED“ and relay 5 for “SLIDE VALVE OPEN“. This assignment cannot be modified. The digital inputs are free programmable for position feedback. To ensure cor­rect and failsafe slide valve drive necessarily use the messages "PATH OFF“, "PATH ON“ and "TORQUE OFF“ of the slide valve drive. The input current per digital input is 10 mA.
Instruction manual
page 54 OCM Pro CF - Rev. 09 as of 07.06.2016
®
The regulator can alternatively be operated with external or internal set point. External setpoints to be used always have to be routed to analog input 4. In case of using a 4-20 mA signal as external setpoint, this signal can be moni­tored for cable breaks and short circuits. If errors should occur the OCM Pro is going to access the internal setpoint (à in case of using external 4-20 mA set­points and error monitoring always set the internal setpoint additionally!).
The following equation applies for the internal calculation of the slide valve con­trol time:
control time = (setpoint – flow

7.6 Communication

7.6.1 General

Note
actual value
OCM Pro CF
max. slide valve runtime
) • P_factor •
max. flow
Communication can be used only in conjunction with the wall mount enclosure unit!
Programming can be executed with the panel mount enclosure unit as well; the transmitter however is not equipped with an Ethernet interface!
The OCM Pro CF wall mount enclosure unit allows remote access via Internet. This means that the unit can be operated via Internet connection and PC or Lap­top keyboard as if being on-site. Requirements:
- Intranet or TCP/IP network or:
- Internet access
- current Internet Explorer or Firefox (no Opera or similar)
- Java
There is no need to install any additional software if there is the latest Internet browser and the latest Java plug-in available on your network PC/Laptop. If you wish to access the unit via the NIVUS Internet portal it is necessary to have a permanent Internet connection established (modem or DSL). Once hav­ing programmed the OCM Pro CF and setting up data transmission the unit can be accessed from any PC in the world!
®
Note
Do not confuse OCM Pro CF remote access and process conducting systems. The OCM Pro CF requires direct dialog with the user via PC. There is no real­time access. It is not possible to carry out automatic data transmission.
Instruction manual
OCM Pro CF
®
OCM Pro CF - Rev. 09 as of 07.06.2016 page 55
Depending on the user’s status the following functions are either accessible or locked:

Viewer

- operational conditions, progress lines, sensor status etc. can be selected
and viewed
- saved data and parameter files can be downloaded
- settings can be selected but cannot be modified permanently
- data files cannot be deleted
- no updates possible

Operator

- operational conditions, progress lines, sensor status etc. can be selected
and viewed
- saved data and parameter files can be downloaded
- device settings can be modified permanently
- data files can be deleted
- memory card can be formatted
- device updates possible

Administrator

All rights see operator level. Additionally:
- setting up new units
- administration of unit levels, sub-users and operating levels
Depending on the type of transmitter (see Chapter 2.5) there are various ways for data communication. Select from:
- Ethernet
- Analog modem
- ISDN modem
- GSM/GPRS modem
Important Note
Using remote access options is associated with connection costs on the part of the instrument as well as on the part of the operator/viewer. These costs depend on:
- Providers choice
- Connection time
- Connection period
- Flat rate or similar arrangement
They are not influenced by NIVUS. The system administrator is responsible for the amount of future communica-
tion expenses arising.
Instruction manual
page 56 OCM Pro CF - Rev. 09 as of 07.06.2016
®

7.6.2 Communication Options

There are several different options available for communication with the OCM Pro CF. These options are:
- direct Ethernet connection between PC/Laptop and OCM Pro CF using a
- Ethernet level connection via TCP/IP, network connection via Ethernet hub
- Connection via network server using DHCP (Dynamic Host Configuration
- Internet connection via access portal (see Fig. 7-42)
- connection to SCADA systems via Modbus TCP (Ethernet)
- data and alarm transmission via E-mail or FTP server
OCM Pro CF
cross-link cable
or switch (see Fig. 7-40) It is necessary to use patch cables.
Protocol) and/or DNS (Domain Name Server). This setup is depicted in Fig. 7-41.
It is required to use an OCM Pro CF equipped with according hardware such as analog modem, ISDN modem or GPRS to set up such a connection. The setup is described in Chapter 7.6.3.
Fig. 7-40 Communication without server
Fig. 7-41 Communication with server
Instruction manual
OCM Pro CF
®
OCM Pro CF - Rev. 09 as of 07.06.2016 page 57
1. Select your unit on >www.nivus.com< using the access portal.
2. The portal will “wake up” the unit sending a direct call.
3. The OCM Pro CF is setting up Internet access logging in to the portal subsequently.
4. The portal is going to establish a connection between unit and user using the internal OCM Pro CF web server
Fig. 7-42 Communication via Inter net

7.6.3 Communication Setup via Access Portal

Important Note
Setting up an Internet communication for one or several NIVUS flow mea­surement units requires an initial setup by NIVUS or a company authorised by NIVUS.
Important Note
Setting up a modem connection (analog, ISDN, GPRS or similar) will cause communication expenses depending on the connection chosen. Please ob­serve while transmitting data.
After the initial setup has been finished successfully following units, which are equipped with the same transmission system, can be set up by the customer or the customer’s system administrator. A "Start portal" is required to start Internet connection.
This start portal is available under http://www.domoport.de/ To start communication, enter the address mentioned bef ore int o your bro wser’s address line. This will take you to the homepage of the provider (Domoport). Enter your "Username" and "Password". You are going to receive both codes after the initial setup has been carried out by NIVUS. You can modify the names and passwords yourself.
.
Instruction manual
OCM Pro CF
page 58 OCM Pro CF - Rev. 09 as of 07.06.2016
®
Fig. 7-43 Starting the communication
Important Note
Do not forward user names and passwords to unauthorised persons! Keep user names and passwords separated from each other and in a way
which avoids misuse.
The data is transferred using SSL encryption, making it inaccessible to third par­ties. After entering the valid user name and password a selection page will ap­pear. This page indicates any measurement place registered for this user. The measurement places can be selected directly from here.
Fig. 7-44 Measurement place selection
After selecting the desired measurement place and clicking the "Connect" but­ton communication with the selected OCM Pro CF will be established. User name and password are going to be verified again and the homepage contained in the OCM Pro CF will be transmitted. This may take between 15 and 120 seconds depending on modem type and quality of connection.
Instruction manual
OCM Pro CF
®
OCM Pro CF - Rev. 09 as of 07.06.2016 page 59

7.6.4 Data Transmission

Fig. 7-45 Connecting
After connection has been established successfully, first of all a static page with current measurement values (flow, fill level and flow velocity) will be indicated on the right-hand side of the screen. These numeric values can be refreshed auto­matically in intervals of 2, 5 or 10 seconds by clicking the according field below and setting the cycle time subsequently.
Fig. 7-46 Static communication page
Clicking the >Remote Control< button on the left-hand side of the screen will ini-
TM
tially start a Java If the Java
TM
by clicking the Java open up a direct link to Java
applet.
software is not installed on the PC, it can be downloaded for free
TM
button (next to the word >Remote Control<) which will
TM
.
Note
TM
Remote control is not possible if the free Java installed on the operator PC!
runtime environment is not
The Java© Applet is third party software and NIVUS therefore cannot accept any liability of the use of it.
Download and installation of programs or software may damage your comput­er and is therefore completely left at user’s risk!
Instruction manual
OCM Pro CF
page 60 OCM Pro CF - Rev. 09 as of 07.06.2016
®
Fig. 7-47 JavaTM-Applet starting
After starting Java the same manner as if being on-site. The OCM Pro can now be operated by using the PC keyboard (arrow keys >left<, >right<, >up<, >down< and >Enter<, >ESC< and >ALT<) exactly the same way as if using the keys on the unit front board. It is possible to operate the virtual keys on the screen by clicking with the mouse as well. Please observe the delay occurring due to the kind of transmission (à no quick consecutive control entries, but always one movement at a time after the previ­ous command has been executed visibly).
TM
successfully, the OCM Pro CF display now is indicated in
Fig. 7-48 Visualisation of onlin e connection
By clicking the control element >File Download< underneath the >Remote Con­trol< button it is possible to directly download data from the plugged memory card. Information on the card will NOT be deleted automatically which ensures data to be available on later downloads. After double-clicking the desired file can be either opened directly or downloaded in uncompressed original format or as compressed gzip-file. The .gz-files can be unpacked for further use with WinZip.
Instruction manual
OCM Pro CF
®
OCM Pro CF - Rev. 09 as of 07.06.2016 page 61
2 ZIP-file area
3 Delete area (to be moved into backup folder)
The file size will be reduced by approx. 75% by using the .gz-format and hence is recommended particularly if large measurement place files have to be trans­mitted via analog modem and GPRS (saves money and time). You can find more information on the OCM Pro file structure and how to use the single files in chapter 9.5.11.
Note
It is not possible to transfer data files if the memory card is not plugged and storage is disabled!
1 Uncompressed downloadable files in original format
Fig. 7-49 Selecting the file to transmit or to delete
Fig. 7-50 Saving transmitted files on PC
The selected file can be deleted by double-clicking on it in area 3 (see Fig. 7-49). In order to be able to read or to transmit the file later, this action will move the file into a backup folder which has been created automatically.
Instruction manual
OCM Pro CF
page 62 OCM Pro CF - Rev. 09 as of 07.06.2016
®
Fig. 7-51 Created backup folder
Files which have been moved into the back up folder w ill be del eted irre vocab ly from the OCM Pro CF memory card if clicked again for deleting.
Fig. 7-52 Contents of created backup folder
Fig. 7-53 Deleting a file permanently
Note
Transmitting the measurement place file without deleting it or moving it into the backup folder will cause to attach all future readings to the transmitted file. This is going to blow up the size of the file as “old” data which have been transmitted before are going to be trans mit ted aga in!
Instruction manual
OCM Pro CF
®
OCM Pro CF - Rev. 09 as of 07.06.2016 page 63
2 Resolution
3 Update button
4 Scale of readings
5 Time axis
6 Scale grid
Note
Deleting a file (moving it into the backup folder) while having a file with the
The screen below comes up after clicking:
same name in the target folder will cause the older file to be overwritten with­out any additional warning!
A click on the >Trend< button on the left-hand side enables to indicate a trend graph parallel to the trend screen indicated on the OCM Pro CF to visualise data stored in the internal unit memory. The range of data to be indicated covers a maximum of 90 days.
1 Display range
Fig. 7-54 Online trend graph
Flow volume, fill level, average flow velocity and medium temperature are going to be indicated as coloured progress lines. The units here are equal to the units indicated on the OCM Pro display (see Chap. 9.3). The readings on the y-axis are going to be scaled according to a grid in steps of
0.1, 0.2, 0.5, 1, 2, 5, 10 ..... up to a maximum of 10000. Here the selected scale
unit is equal to a horizontal grid line (see Fig. 7-54, point 6).
Instruction manual
OCM Pro CF
page 64 OCM Pro CF - Rev. 09 as of 07.06.2016
®
Set the start point for the trend graph to be indicated under point 1. The resolu­tion (scale of the time axis) can be set under point 2. Select here between 10 minutes, 1 hour, 6 hours or 24 hours/grid line. A click on the >Update< button (point 3 in Fig. 7-54) will refresh the screen by the new measurement data which have been collected whilst watching.
Note
If the selected start date/time of the trend is the current date/time or if the time axis range allows to view a greater range than selected by start date/time and resolution this will cause the screen to indicate older values than selected additionally.
Log out the on-site unit by using the >Logout< button located on the left-hand side of the screen as well. This will take you back to the NIVUS homepage.
Note
If no data transmission has been executed for 5 minutes, the OCM Pro CF will automatically interrupt the connection in order to avoid unnecessary expens­es.
Instruction manual
OCM Pro CF
®
OCM Pro CF - Rev. 09 as of 07.06.2016 page 65

8 Initial Start-Up

8.1 General

Notes to the user

Before you connect and operate the OCM Pro CF you should strictly follow the notes below! This instruction manual contains all necessary information to program and to operate the device, addressing qualified technical staff who have appropriate knowledge about measurement technology, automation technology, information technology and waste water hydraul ic s. To ensure a correct function of the OCM Pro CF this instruction manual must be read thoroughly! The OCM Pro CF must be wired in accor dance w it h the wiring di agram, see chapter 7! If any problems regarding installation, connection or programming should occur please contact our hotline +49 (0)7262 9191-955.

General Principles

The initial start-up is not allowed until the installation has been finished and checked. To exclude faulty programming this instruction manual must be read before the initial start-up. Please get familiar with the OCM Pro CF programming via display and keyboard by reading the instruction manual before you begin to program the device. After transmitter and sensors are connected (see chapters 7.2.3 and 7.3.3) the parameters must be set. In the most cases all you need is:
- geometry of the measurement place and dimensions
- used sensors and positioning
- displ a y units
- span and function of analog and digital outputs
The OCM Pro CF user surface has been designed in a way which allows even unfamiliar users to easily set up basic settings in graphic dialog mode ensuring reliable device operation. Either let the manufacturer or an expert company authorised by the manufactur­er do programming works as soon as the following requirements are prevailing:
- ext ensi ve progr am ming
- difficult hydraulic conditions
- special channel shapes
- lack of expert personnel
- if a setup and error protocol is required
Instruction manual
page 66 OCM Pro CF - Rev. 09 as of 07.06.2016
®
2 Numeric and alphabetic keys
3 Shift key
4 0 / - navigation key
5 Control key
6 Confirmation key (ENTER)
7 Escape key

8.2 Operator Panel

A comfortable 18-button keypad featuring partly multiple key assignment is available to input data.
OCM Pro CF
1 Decimal place / Info key
Fig. 8-1 Operator panel
Instruction manual
OCM Pro CF
®
OCM Pro CF - Rev. 09 as of 07.06.2016 page 67
2 Indicates activated service mode
3 Calibration menu
4 Display menu
5 Current system time (automatically alternates with medium temperature)
6 Fields indicating digital output conditions
7 Total
8 Filling level (height)
9 Flow velocit y
10 Flow rate
11 Operation menu
12 Parameter menu
13 Symbol indicati ng acti ve co m m unication
14 Status menu of inputs, outputs and sensors

8.3 Display

OCM Pro CF has a large back-lit graphic display with a resolution of 128 x 128 pixel. This ensures to comfortably read current values.
1 Indicates activated data storage
Fig. 8-2 Display
Instruction manual
OCM Pro CF
page 68 OCM Pro CF - Rev. 09 as of 07.06.2016
®
RUN
Standard operation mode. Apart fr om indicating the names of
PAR
This menu is the most extensive of the OCM Pro CF. It is for the
I/O
This menu includes information about internal operation of the
CAL
Here it is possible to adjust height (depth) and flow velocity of analog
EXTRA
This sub-menu includes basic display settings: contrast, background
Five basic menus can be selected, visible in the headline of the display. They can be selected individually. The menus are:
measurement places, time, flow rate, level and average flow velocity optionally allows to indicate the flow velocity distribution. Additionally it is possible to show day totals and error messages including time stamps or to graphically indicate the history of flow volumes, filling level and average flow veloci ty.
complete parameter setting of dimensions of the measurement place, sensor selection, analog and digital inputs and outputs, storage, data transmission and regulator function.
OCM Pro CF. All current values can be displayed, as well as the values of analog and digital outputs and relays. Additionally, echoes of the sensors and single velocities are displayed. It further allows to determine the remaining capacity as well as the remaining memory time on an optionally plugged memory card resulting from the cycle time
outputs and to simulate analog as well as digital outputs. To detect very low volumes occurring at minimum levels which do not allow to reliably detecting the flow velocity, it is possible to set up an automatic flow calculation based on the manning formula here.
lighting, language, units, system times and totalizer presets.
Instruction manual
OCM Pro CF
®
OCM Pro CF - Rev. 09 as of 07.06.2016 page 69
These buttons are used for parameter setting and to enter digits. In

8.4 Operation Basics

The entire operation is menu driven and supported by explanatory graphics. To navigate within the menu structure use the 4 control keys (see chapter 8.3).
-
Use these buttons to select main menus.
Buttons for scrolling within menus.
Selected submenus can be entered, inputs can be opened. The “Enter“-key further serves to confirm data entries.
Escape submenus step by step. Cancels entered data.
some sub menus the buttons are to input letters (e.g. name of measuring point). Function compares with mobile phone or cell phone buttons: multiple quick pressing switches over to the next letter. The cursor will jump to the next digit if no key is pressed for approx.
The key “dot/i“ serves for entering digits. In RUN-Mode it also recalls internal information on device, software version, MAC address, serial no. of transmitter and connected NIVUS sensors. Furthermore it restarts communication between transmitter, flow velocity sensor and air-ultrasonic sensor.
2 seconds.
This button is to switch between uppercase and lowercase letters in text entry mode. Further it is used to delete and to insert data. In the rest of the parameter setting mode it enables/disables various functions, as well as SHIFT-key between various programming options.
Instruction manual
page 70 OCM Pro CF - Rev. 09 as of 07.06.2016
®
2718
If prompted enter this number into the OCM Pro.

9 Parameter Setting

9.1 Setting Basics

The transmitter in the background operates with the settings which have been entered at the beginning of the parameter setting. Just after you finish the new entries, the system asks to accept the new values. If “yes”, it is needed to enter the PIN code.
Important Note
The PIN code protects against unauthorized access. Never give the PIN code to any unauthorised persons. Even do not leave the
code next to the equipment or write it down on it.
If a faulty code has been entered three times the parameter mode will be abort­ed. The unit will proceed to operate using the values set earlier. If the correct code has been entered the modified parameters are accepted and the system resets. This reset will take approx. 20-30 seconds.
Besides having the option to save modified parameters or to reject any modifica­tion by pressing >No< at the end of the parameter setting procedure, it is possi­ble to jump back to the previous level using the >Back< function. This enables the user to modify settings which might have been forgotten without the need to buffer previously modified settings.
OCM Pro CF
Fig. 9-1 Screen at end of parameter setting
If parameter settings are not going to be modified but just verified by selecting each parameter, there will be no request at the end of the dialog. Modifications concerning language, units, contrast and display brightness do not require the PIN code as these settings influence just the way of representation and not measurement or the output of measurement values.
Instruction manual
OCM Pro CF
®
OCM Pro CF - Rev. 09 as of 07.06.2016 page 71
Note
This instruction manual describes all programming options of the OCM Pro CF. Depending on the device type various inputs and outputs as well as communication and data transmission features may not be available. They may be programmable, but may not be available to be used as outputs or to be connected (see also Specifications in Chapter 0). This applies for the transmitter type S4, which has only 2 analog outputs, 2 relay outputs, 1 analog input and no digital input. This device cannot be op­erated as a controller. It can be operated with 2 analog outputs and 2 relay outputs only. Please use transmitter type M4 for the additional functions de­scribed above.
After mounting and installing sensor and transmitter (see previous chapters as well as "Installation Instructions for Pipe and Wedge Sensors") activate the power supply. The initial start-up dialog is the language selection:
Fig. 9-2 Language selection
Select the desired language by using the arrow keys and press >Enter< to con­firm.
Please press key once
The transmitter begins communication with the sensor and coordinates both processor programs. At the same time, the firmware version numbers of CPU and sensor will be indicate d, which is nec ess ar ily required if problems during programming should arise. You will need to note this information. It is required as soon as questions on programming should arise.
Instruction manual
OCM Pro CF
page 72 OCM Pro CF - Rev. 09 as of 07.06.2016
®
2 Serial number OCM Pro CF
3 Transmitter firmware version with date of creation
4 CS2 sensor firmware version with date of creation
5 POA sensor 2 firmware version with date of creation
6 POA sensor 3 firmware version with date of creation
7 OCL sensor firmware version with date of creation
8 EBM electronic box firmware with date of creation
1 Sensor number
2 Firmware version with date of creation
3 Serial number
4 Sensor type
1 MAC address OCM Pro CF
Fig. 9-3 Info on firmware and version number
Pressing the "right" arrow key indicates additional information on the connected and activated sensors:
Fig. 9-4 Additional sensor information
Instruction manual
OCM Pro CF
®
OCM Pro CF - Rev. 09 as of 07.06.2016 page 73
Standard
Display (basic screen) with information about the name of measurement place,
Graphics
Indicates the velocity distribution in a vertical measurement path.
accordingly. The selected height as well as the current velocity can be read from

9.2 Operation Mode (RUN)

If older sensors are in use it may not possible to indicate the sensor information completely.
Important Note
During the final inspection a system reset is performed and the OCM Pro CF is shipped subsequently. The unit hence is reset to factory defaults. Inde­pendent from this, we recommend to execute one more system reset (PAR/Settings/System reset) prior to programming parameters in order to ensure a defined basic state.
Then parameters can be set.
This menu is a display menu for standard operation mode. The following sub menus are available:
Fig. 9-5 Operation mode selection
time, flow quantity, level and average velocity.
Pressing the "arrow up“ or "arrow down“ keys will move the indicator line
the bottom line of the display (see Fig. 9-6). This graphic indication enables to understand the current flow conditions at the chosen measurement place. The velocity profile should be evenly distributed and should not have any errors (see Fig. 9-7). In case of very unfavourable conditions change the position of the flow velocity sensor. For more details please refer to the "Installation Instruction for Correlation and Doppler sensors". Graphics are not availbale if a surface radar sensor is used.
Instruction manual
OCM Pro CF
page 74 OCM Pro CF - Rev. 09 as of 07.06.2016
®
2 Maximum Measured Velocity
3 Measurement Window Indication
4 Level Measurement W indow no.
5 Level Value
6 Velocity Measurement Window no.
7 Velocity Value
very good profile, area
good profile, strongly
suitable profile ill-suited profile
unsuitable profile
Day totals
The submenu >INFO< (see Fig. 9-8) allows to view the flow totals of the past 7
is value can be reset to >0< at
1 Maximum Height
Fig. 9-6 Flow velocity distribution
free of backwater
Fig. 9-7 Flow velocity profiles
Note
This function is not available as soon as an OFR radar sensor is connected.
tending to backwater
days (see Fig. 9-9), presumed the transmitter has been operated without any interruption in the past seven days. Otherwise it shows the total for the uninterrupted days of operation). Totalisation normally is carried out at 00:00 h (midnight). If desired, this value can be modified under RUN – Day Total s - Interval (see Fig. 9-10) Additionally, you can get information about partial total value since the last reset (comparable with rout mileage counters in cars). Th any time by pressing the >ALT<-key. This reset does not influence the totaliser.
Instruction manual
OCM Pro CF
®
OCM Pro CF - Rev. 09 as of 07.06.2016 page 75
2 Day total
Error Messages
This menu is to monitor any interruptions in the unit function. Errors are going to
Trend
Operates like an electronic writer. Average cycle values of level, average flow
Fig. 9-8 Info menu
1 Sub total
Fig. 9-9 Day val ues
Fig. 9-10 Time of daily totalising
be saved and ordered by type of error, date and time. Pressing the >ALT< key will delete all error messages one by one (from the latest one back to the oldest one).
Note
When deleting an error message at a time when the error still is due to be dealt with, this error will NOT be written into the error memory again. The error will be saved in the memory not before it has disappeared and arisen again (or if the power supply has been interrupted briefly).
velocity and height (level) will be recorded for the past days. Values can be individually selected and viewed in a submenu..
Fig. 9-11 Trend value selection (varying screens)
Instruction manual
OCM Pro CF
page 76 OCM Pro CF - Rev. 09 as of 07.06.2016
®
2 Minimum value occurred
3 Graph
4 Period indicated
The period within which values have been averaged is indicated on the bottom line of the graphic display. New values will be added as vertical lines on the right-hand side each time after the programmed storage cycle has expired (see Fig. 9-21). This is why the oldest value moves to the left-hand side of the display and from there into the internal memory area. By using the arrow keys >left< and >right< you can scroll within the time axis in order to view older data sets. Browse through day values using the arrow keys >up< and >down<. This enables to determine and to evaluate previous meas­urements, trends, dry weather periods as well as possible measurement prob­lems which have been occurred some days before. The internal memory has a capacity of 90 days. Subsequently, saved data will be overwritten erasing the oldest data sets first. Indicated measurement values will be scaled automatically during scrolling and therefore might change in order to ensure the best reading available. The memory time interval can be set in the PAR - Me mory Mode - Interval menu.
1 Maximum value occurred
Fig. 9-12 Trend graph example
Note
All trend graphic values saved previously will get lost if the memory interval or any other parameter is going to be modified.
Instruction manual
OCM Pro CF
®
OCM Pro CF - Rev. 09 as of 07.06.2016 page 77
Units
This menu contains the following sub menus:
Unit System
Here you can select between the metric system (litre, cubic meters, cm/s etc.),
Language
German, English, French, Czech, Italian, Spanish, Polish and Danish are
Display

9.3 Display Menu (EXTRA)

This menu allows to modify settings such as basic screen, units, language as well as the display itself. The following submenus are available:
Fig. 9-13 Extra submenus
Fig. 9-14 Unit system selection
Fig. 9-15 Selection of individual units
- Flow
- Velocity
- Level
- Total
For each of these 4 measured values you can select a unit which appears on the display. Depending on the unit system selected, there are various units available.
English system (ft, in, gal/s, etc.) and American system (fps, mgd etc.).
available for communication and indication of messages on the Display.
allows to adjust display settings regarding contrast and brightness. Use and
to decrease; and to increase values. and modify values in 5
% steps, and in steps of 1 %.
Instruction manual
OCM Pro CF
page 78 OCM Pro CF - Rev. 09 as of 07.06.2016
®
System Time
In order to perform various control and memory functions, the unit includes an
2 Week no.
3 Time
Set Total-Counter
This menu allows to newly set the totalizer indicated on the main screen. This
After the new value has been set confirm twice using the "Enter“ key and type in
Otherwise the new value will not
internal system clock saving dates of year, weekdays and week numbers. The clock settings can be modified if required (different time zones, summer time / winter time etc.). First select the menu point >Info<:
Fig. 9-16 System time submenu
The current system time is indicated after the settings have been confirmed:
1 Date
Fig. 9-17 System time screen
This menu point is for indicating purposes only. Hence the system time cannot be adjusted here. Modifications can be carried out in the individual menus “Date” and "Time“. The according week number will bet set automatically as soon as the date has been set.
feature is normally going to performed in case of replacing a transmitter which has to indicate the same value as before replacement.
the PIN “2718“ (up to 2 faulty entries possible). be accepted.
Fig. 9-18 Totalizer modification
Instruction manual
OCM Pro CF
®
OCM Pro CF - Rev. 09 as of 07.06.2016 page 79

9.4 Parameter Menu (PAR)

9.5 Parameter Menu (PAR)

Fig. 9-19 PIN request
This menu is the most extensive and most important regarding the OCM Pro CF settings. It nevertheless is sufficient in most cases to set only some essential pa­rameters, which usually are:
- name of measurement place
- channel profile
- channel dimensions
- flow velocity measurement sensor type
- level measurement sensor type
- analog output (function, measurement range and measurement span)
- relay output (function and values)
All other functions are additions which are required in special cases only (special channels, regulator mode, storage mode or for special hydraulic applications). These settings are normally made with the help of our service personnel or by an authorised expert company. The parameter menu which are described individ ual ly on the follo win g page s .

9.5.1 Parameter Menu "Measurement Place"

>PAR< includes twelve partially very extensive submenus
Fig. 9-20 Submenu measurement place
Instruction manual
page 80 OCM Pro CF - Rev. 09 as of 07.06.2016
®
Name (of
NIVUS recommends to coordinate and to define names according to names
After the submenu >Name of Measurement Place< has been selected the basic
2 menu
OCM Pro CF
This menu is one of the most important basic menus for parameter setting as the measurement place is going to be defined here. The menu cannot be indicated completely due to restricted display space. Simi­lar to many well-k nown PC app lications, this is readily identifiab le from the black bars on the right-hand side of the screen.
Use "Up“ and "Down“ keys to scroll the menu.
measurement place)
stated in the respective construction documents. Names may contain up to 21 letters. Setting the name is quite similar to operating a mobile phone:
setting "nivus" will come up. Toggle between uppercase and lowercase letters by using the >up< or >down< keys. Pressing the "Alt“ key will either turn on or off a selection of special characters. The special characters can be selected individually with the >left< or >right< arrow keys, confirm your selection with “Enter”.
1 name of measurement place
Fig. 9-21 Setting the name of the measurement place
Enter the desired name with the keypad, where each key has assigned three let­ters and a number (see Chapter Fehler! Verweisquelle konnte nicht gefund- en werden.). Select between these four characters by briefly pressing a key several times. The cursor will jump to the next character if a key has not been pressed for two seconds.

Description of Keys:

Moves the cursor to the left-hand or the right-hand side. Moving the cursor to the left-hand side will delete the character
left of the cursor. Moving the cursor to the right-hand side creates a space
character. Toggle between uppercase and lowercase letters.
Shift to uppercase letters. Shift to lowercase letters. Confirm the entered name with “Enter“ and exit the menu.
Instruction manual
OCM Pro CF
®
OCM Pro CF - Rev. 09 as of 07.06.2016 page 81
Subdivide Geometry
This is a special parameter which enables to easily set parameters for large
Channel Profile(s)
If the profile has not been subdivided first select the zone (bottom, centre, top)
Pipe (radius)
special profiles with convex tops. This parameter will not be required for the very most applications! Mainly, authorised NIVUS personnel is going to use this function; which nevertheless will be described here briefly. This parameter allows to subdivide special profiles with convex tops and possibly with a bottom featuring a dry weather channel into 2 or 3 level / height zones, which facilitates the programming of the total profile dimensions. Pressing the >ALT< key will switch between the 3 options described below:
- NO (no profile subdivision, standard setting)
- 2 (subdivide in 2 level / height zones)
- 3 (subdivide in 3 level / height zones)
Fig. 9-22 Profile divided into 3 zones
with the >ALT< key and set the desired profile subsequently. You can select between following standard profiles according to German ATV A110: (see dimensions to enter in brackets)
-
- Egg, h:w = 1,5:1 (radius)
- Rectangle (channel height and channel width)
- U-Profile (channel height and radius)
- Trapezoid (channel height, trapeze width bottom/top, height)
- custom profile (spot heights and according channel widths)
- 2r Egg, h:w = 1:1 (radius)
- Q= f(h)
Fig. 9-23 Channel shape selection
Instruction manual
OCM Pro CF
page 82 OCM Pro CF - Rev. 09 as of 07.06.2016
®
Channel Dimensions
Type in the respective channel dimensions depending on the profile chosen
Select channel shape with "Up“ and "Down“ keys. Confirm selection with “Enter“.
The selected profile will be indicated in the programming mode screen
Fig. 9-24 Selected profile
If the existing profile does not comply with the options to select from, choose >Custom shape< in such a case.
Confirm with“Enter“.
A request will come up subsequently asking for known relations.
Fig. 9-25 Custom shape menu
before.
Instruction manual
OCM Pro CF
®
OCM Pro CF - Rev. 09 as of 07.06.2016 page 83
Fig. 9-26 Screens showing various channel dimensions
Note
Please observe indicated units when entering values!
Choosing >Custom shape< will indicate a table containing a maximum of 32 possible breakpoints on the display. As described above, enter the relations be­tween >height-width< or >height-area< (Fig. 9-25) and enter the according value pairs.
Fig. 9-27 List of custom shape breakpoints
To define the zero point of the channel, star t b y enterin g 0 – 0 in break point 1. All further breakpoints can be set freely regarding height as well as width/area.
Instruction manual
OCM Pro CF
page 84 OCM Pro CF - Rev. 09 as of 07.06.2016
®
Bottom area:
Top area:
Custom profile
Bottom area:
Pipe
Centre area:
Custom profile
Top area:
Pipe
There may be different distances between individual level points. Furthermore it is not necessary to use all of the 32 breakpoints possible. The OCM Pro however is going to use a linearization function between the sin­gle breakpoints. Decrease the distance between breakpoints in case of heavy and irregular changes in the channel dimensions.
Fig. 9-28 Custom profile breakpoints
If the channel profile has been divided in two zones, the channel profiles below are available to be set:
- Pipe
- Egg
- Rectangle
- U-Profile
- Trapezoid
- 2r Egg
- Q=f(h)
-
Dividing in three zones will reveal the following setting options:
-
- Egg
- Rectangle
- U-Profile
- Trapezoid
- 2r Egg
- Q=f(h)
-
-
Instruction manual
OCM Pro CF
®
OCM Pro CF - Rev. 09 as of 07.06.2016 page 85
Sludge level
The sludge level set is considered during calculation as non-moving sub-area
Low-flow volume Q
This parameter serves to suppress lowest movements or apparent volumes
Q
: measurement values lower than this one will be set to >0<. Only positive
V
: low-flow volumes in applications with large profiles and filling levels can be
Important Note
Programming subdivided profiles requires comprehensive knowledge and experience in operating the OCM Pro.
To avoid faulty programming or if in doubt this procedure should be performed by NIVUS service personnel or expert companies authorised by NIVUS.
on the channel bottom and will be subtracted from the wetted hydraulic total area prior to performing flow calculation.
min
arising. Used mainly to measure overflow volumes in constructions which are permanently flooded by receiving water.
min
values are allowed to be set. These values are going to be considered as absolute values and therefor e have posi ti ve as well as negati ve ef f ect s.
min
suppressed by means of this parameter. Lowest velocity fluctuations within longer periods of time may cause apparently large volume fluctuations which cannot be gated by using the value of Q
min
. Flow velocities below this value will be set to „0“ which will set the calculated volume to „0“ as well. Only positive values can be set. These values are going to be considered as absolute values and therefor e aff ec t positive as well as negati ve velocities.
Both setting options of low-flow suppression have an
>OR< relation between
each other.
Fig. 9-29 Selection low-flow volumes
Note The suppression of low-flow volumes is no offset but a limit value!
Instruction manual
page 86 OCM Pro CF - Rev. 09 as of 07.06.2016
®

9.5.2 Parameter Menu “Level “

Fig. 9-30 Menu level measurement
OCM Pro CF
Fig. 9-31 Level measurement – submenu
Important Note
The sensor type selection is decisive for the following programming proce­dure. An incorrect selection may lead to faulty measurements or even meas­urement failure.
This menu defines all parameters responsible for level measurement. Depend­ing on the sensor type selected the parameter start page as well as the parame­ters to enter may vary. Basically determine sensor type or sensor combination first! Move the cursor accordingly by using the >up< and >down< arrow keys. Select or de-select sensors with the >ALT< key. Confirm your selection by pressing >ENTER<.
Instruction manual
OCM Pro CF
®
OCM Pro CF - Rev. 09 as of 07.06.2016 page 87
2 Water-ultrasonic integrated into flow velocity sensor, 3 2-wire probe EX, e.g. types: NMC0 or HSB0NBP
4 Fixed value for permanently full filled applications or for testing purposes
5 Pressure measurement cell integrated into flow velocity sensor, 6 2-wire probe, e.g. types NM5-3101 or HSB0HG, i-Serie Ex
It is distinguished between the following level sensors:
1 Air-ultrasonic type >OCL< or >DSM< by NIVUS
types: POA-V1H1 or CS2-V2H1
types: POA-V1D0 or CS2-V2D0
Fig. 9-32 Determination of level sensor type
Note
When using combi sensors featuring multiple level measurements (water-
Sensor type 1: Air-ultrasonic (Air-US NIVUS)
ultrasound and pressure measurement cell, e.g. type POA-V1U1 or CS2­V2U1) it is necessary to select both level measurements in the selection menu.
Level measurement by using active air-ultrasonic sensor from top down. May be combined with the flow velocity sensor This sensor can be used to detect low flow levels, e.g. to measure nightly dis­charge. The sensor must be installed exactly in the centre of the channel vertex, (± 2°) parallel to the water surface. An air-ultrasonic sensor type OCL or DSM is required!
Instruction manual
page 88 OCM Pro CF - Rev. 09 as of 07.06.2016
®
Fig. 9-33 Sensor type 1: air-ultrasonic
Sensor type 2: Water-ultrasonic (Water-US internal)
Level measurement using a combi sensor type V1H or V2H. Level measurement using water-ultrasound from bottom up. This sensor type is for discharge detection in medium part filled areas. The sensor must be installed exactly in the bottom centre observing a maximum permissible deviation of ±2°.
OCM Pro CF
Important Note
Never use a water-ultrasonic sensor if the sensor is installed out of the centre, (e.g. sedimentation or risk of soiling)! This may result in echo loss and meas­urement failure.
In this case use a different level sensor (ultrasound from top down or pressure measurement cell).
Fig. 9-34 Sensor type 2: water-ultrasonic
Sensor type 3: 2-Wire probe EX
This selection is for level measurement by using external 2-wire Ex probes sup­plied by OCM Pro CF such as a pressure probe type NivuBar Plus or a type NivuCompact echo sounder. Can be combined with the flow velocity sensor.
Instruction manual
OCM Pro CF
®
OCM Pro CF - Rev. 09 as of 07.06.2016 page 89
Fig. 9-35 Sensor type 3: 2-wire probe EX
Note
For connection see Fig. 7-12 or Fig. 7-29.
Sensor type 4: Fixed value
This programming is designed for permanently full filled pipes and channels. Level measurement is not required for such applications. The constant filling level is entered under "Fixed value / Scale / Level" and is used for flow calcula­tion. This parameter is very helpful during initial start-up procedures or while perform­ing tests without having level readings available as well.
Fig. 9-36 Sensor type 4: fixed value
Sensor type 5: Internal pressure
Here the level is measured by using a combi sensor type V1D/V2D or V1U/V2U with integrated pressure measurement cell from bottom up. Installation on the sides, e.g. in case of sedimentation or high pollution loads is possible. Level measurement in flooded condition is possible as well.
Instruction manual
page 90 OCM Pro CF - Rev. 09 as of 07.06.2016
®
P
1
1 Sedimentation or soiling
Fig. 9-37 Sensor type 5: internal pressure
Sensor type 6: 2-wire probe
Here the level is measured by using an external 2-wire source such as the type NivuMaster echo sounder or a pressure probe type HydroBar. Both can be com­bined with the flow velocity sensor .
OCM Pro CF
Fig. 9-38 Sensor type 3: 2-wire probe
Note
For connection see Fig. 7-12 or Fig. 7-29.
Instruction manual
OCM Pro CF
®
OCM Pro CF - Rev. 09 as of 07.06.2016 page 91
Air-US NIVUS +
Combination between sensor types 1 and 5.
2-Wire probe (Ex) +
Combination between sensor types 3 or 6 and sensor type 5.
Internal Water-US +
Combination from sensor types 2 and 5.
P
1
Sensor combination examples:
On the following pages you can find the combinations possible between the dif­ferent sensor types. Such combinations are required as soon as one single level sensor is not suffi­cient for level detection covering the desired measurement range due to con­structional reasons (see also Fig. 7-47)
Internal pressure
This combination is recommended for measurement ranges from 0 cm level up to flood. In this case the air-ultrasonic sensor type OCL or DSM detects low levels; the pressure sensor detects the flood range. The pressure sensor may be installed out of the centre if the risk of sedimentation or soiling should occur (Fig. 7-39).
1 Sedimentation, soiling
Fig. 9-39 Combination: Air-ultrasound and internal pressure
internal pressure
Internal pressure
Same area of use as described under version >air-US + internal pressure<. However the air-ultrasonic sensor type OCL/DSM will be replaced by a 2-wire probe.
This combination is recommended for level measurement ranges as from approx. 0.5 cm up to flood. The pressure sensor is responsible for upper and lower measurement range. The water-ultrasonic sensor detects the medium part filled area. The water-ultrasonic sensor must be installed in the centre of the channel bottom. Otherwise there is the risk of echo loss and hence measurement failure.
Instruction manual
page 92 OCM Pro CF - Rev. 09 as of 07.06.2016
®
Air-US NIVUS +
Combination from sensor 1 and 2. The following combination covers level measurement ranges as from 0 cm up to
Internal Water-US +
Combination from sensor 2 and 6 or 3.
P
P
internal water-US
OCM Pro CF
Fig. 9-40 Water-ultrasound and internal pressure
approx. 80 % full filling. The water-ultrasonic sensor detects levels as from approx. 7 cm; the air-ultrasonic sensor detects the levels below. The water-ultrasonic sensor must be installed in the centre of the channel bottom.
Fig. 9-41 Air- and water-ultrasound
2-Wire probe
To be used in applications as described in water-US int. + air-US. An external 2-wire sensor instead of an air-ultrasonic sensor is going to be used to detect low flow levels (expediently an echo sounder).
Instruction manual
OCM Pro CF
®
OCM Pro CF - Rev. 09 as of 07.06.2016 page 93
Air-US NIVUS + Water-
Combination of options 1, 2 and 5.
Water-US internal +
Combination of options 2, 3 or 6 and 5.
Mounting height
This parameter is required only for applications where the sensor is not installed
Fig. 9-42 Water-ultrasound + 2-wire probe
US internal + Pressur e int.
This combination is recommended from 0 cm filling level up to overflow if the best possible measuring accuracy is required. In this case the pressure sensor detects the upper measurement range. The water-ultrasound sensor detects the medium range and the air-ultrasound sensor detects the low range. Please observe to install the water ultrasonic sensor in the centre of the bottom
Fig. 9-43 Sensortyp Luft-Ultraschall, Wasser-Ultraschall und Druck
2-Wire probe (Ex) + Pressure int.
Application as the combination >Air US + Water US + Pressure<. An external 2-wire probe (expediently an echo sounder) is used to detect low filling levels instead of the air-ultrasound sensor. Please observe to install the water ultrasonic sensor in the centre of the bottom.
directly on the channel bottom but is mounted in a pipe on a wedge support or out of the centre to avoid effects due to sedimentation.
Instruction manual
OCM Pro CF
page 94 OCM Pro CF - Rev. 09 as of 07.06.2016
®
The level adjustment in the CAL menu, which is required due to the higher
2 height H: mounting height air-ultrasonic sensor (OCL or DSM)
Note
The value is set to 0.000 m per default as soon as the level sensors have been selected.
The reference point in front of each level sensor is the unknown variable of the ground plate or the channel bottom / channel crest.
installation, allows to adjust the respective installation height to the available conditions and the mounting situation.
1 height h: mounting height of pressure and water-ultrasonic sensor
Fig. 9-44 Mounting height of level se nsors in case of selection air-US
NIVUS, pressure and water-US
1 height h: mounting height sensor type pressure internal
Fig. 9-45 Mounting height of level se nsors in case of selection pressure
internal or water-US internal
Instruction manual
OCM Pro CF
®
OCM Pro CF - Rev. 09 as of 07.06.2016 page 95
Select layers
This parameter will be indicated only if a sensor combination has been selected.
2 Threshold level between middle and top layers
3 Middle layer sensor
4 Threshold level between middle and bottom layer.
5 Bottom layer sensor Sensor
1 height h: mounting height sensor type air-US-NIVUS
Fig. 9-46 Mounting height level sensor in case of selection air-US NIVUS
Note
As soon as the mounting height of pressure or water-US sensors is changed, the mounting height in the PAR/Flow velocity menu must be ad­justed by the same amount!
The OCM Pro CF automatically aligns the sensors to partial layers. Layer borders however may be defined freely as well. Use the >ALT<-key to do this. Determine the threshold levels between the layers using the box in the >from< line.
1 Top layer sensor
Fig. 9-47 Select layers
After being selected the level sensors will be indicated on the screen.
Instruction manual
OCM Pro CF
page 96 OCM Pro CF - Rev. 09 as of 07.06.2016
®
Scale
Depending on the sensor type selected, a fixed value or a measurement offset
ded to the level measurement value. Negative entries are
Fig. 9-48 Overview on level sensors
as well as the measurement span according to the input signal is entered here.
Offset: this value is ad possible as well, which can be used to adjust values from the 2-wire probe. Span: the measurement span (equal to 20 mA from the OCM Pro CF analog input) shall be adjusted to the span of the analog output of the 2-wire probe used.
Fig. 9-49 2-wire sensor settings
Fig. 9-50 Screen at 2-wire sensor Ex/non-Ex
Instruction manual
OCM Pro CF
®
OCM Pro CF - Rev. 09 as of 07.06.2016 page 97
Important Note
Connect the 2-wire probes, which are supplied by the transmitter, to the Ex terminal clamps:
- wall mount enclosure: D8 + and D9
- panel mount enclosure: B 21 + and C 21 -
Set the sensor type 2 to „2-wire_probe Ex“. Failure to observe leads to loss of Ex protection.
Important Note
Connect externally supplied level signals always to the clamps in the non-Ex area (e.g. NivuMaster or i-series Ex)
- wall mount enclosure: B16 +, B18 -
- panel mount enclosure : B15 +, B17 -
Set the sensor type 2 to „2-wire_probe“ Failure to observe leads to loss of Ex protection.
Note
Note Fig. 7-12 to Fig. 7-14 and Fig. 7-29 to Fig. 7-31 for sensor connection.
Fig. 9-51 Application example for water-US + 2 Wire probe
Please note when you use combined level detection via different sensors that only one measurement method is responsible for volume calculation. The appli­cable measurement method has to be selected depending on the level/height and must be determined during the programming procedure.
Instruction manual
OCM Pro CF
page 98 OCM Pro CF - Rev. 09 as of 07.06.2016
®
Sensor type
In v-Sensor mode it is possible to change the sensor type using the >ALT< key.
applications where the flow velocity sensor is heading upstream (unlike heading
In order to ensure reliable level detection at any time, please observe the hy­draulic and metrological basic conditions. With the memory mode enabled and a plugged memory card, all possible set and measured levels will be saved. Hence, it is possible to verify and to recalcu­late values at any time. It is necessary to choose the appropriate level measurement method during the preliminary stages of project planning.
Important Note
When choosing the measurement method, please observe to connect a suffi­cient sensor which is equipped with appropriate measurement elements!
Preferably use NIVUS sensors.
Important Note
While setting combi sensors using different lev e l measuring methods in vary­ing areas, programming errors may arise very easily.
If in doubt please use the assistance provided by our commissioning service or an expert company authorised by NIVUS!!

9.5.3 Parameter Menu „velocity “

The number of sensors is set to >1< per default. This setting meets the require­ments of most applications. In case of using multiple sensors (e.g. in subdivided cross-sections) the number of sensors can be modified by using the "up" or "down" arrow keys.
Fig. 9-52 Setting the number of sensors
Select the type of sensor construction used. Installation position of the sensor is set to “positive“ per default. This parameter should not be modified! It is going to be used only for special
downstream towards the flow direction as in standard applications) but is to detect positive velocities however. This is the only case which requires to set “negative“ here
Fig. 9-53 Select sensor type and mounting positi on
.
Instruction manual
OCM Pro CF
®
OCM Pro CF - Rev. 09 as of 07.06.2016 page 99

V_sensor wedge: Flow velocit y measurement using a wedge sensor.

V_sensor tube: Flow velocity measurement using a pipe / tube sensor.

V_sensor float:

Flow velocity measurement using a sensor fastened on a float. In this case the measurment is executed from the top down.

V_sensor Pos-alpha:

Flow velocity measurement using a wedge or pipe / tube sensor installed in an angle varying from the perpendicular.

V-sensor radar:

Flow velocity measurement using a surface radar sensor installed in posit iv e or negative direction above the water surface
Instruction manual
OCM Pro CF
page 100 OCM Pro CF - Rev. 09 as of 07.06.2016
®
2 Sensor type (wedge, tube, float, Pos-alpha)
3 Installation position (positive, negative)
4 Number of sensors (1x, 2x, 3x)
5 Angle >b< is the angle varying from perpend ic ular at P os -Alpha
6 Mounting height of flow velocity sensor
Mounting place
This menu point is to modify the installation height (h) of the flow velocity
etting does not need to be modified
elevated or depressed installation must be added to or subtracted from the 0 m.
the ground plate,
1 Sensor number (1, 2, 3)
Fig. 9-54 Indication of sensor types
sensor. The standard setting is 0 mm. This s unless the wedge or tube sensor has been installed higher or lower. In case of
The reference point of the wedge sensor is the bottom edge of with the pipe sensor it is the horizontal area at the tip of the sensor. Enter the distance between water surface and the centre of the immersed flow velocity sensor crystal as soon as the sensor type "Float" has been selected. If sensor type "float" has been selected, enter the distance from the water surface to horizontal area at the tip of the pipe sensor here..
Loading...