The Signet 2000 Micro Flow Rotor Sensor is constructed of Polyphenylene Sulfi de (PPS)
which provides high material strength. The 2000 offers two fl ow ranges starting at 0.11 or
1.13 lpm (0.03 or 0.3 gpm), for clean process liquids, regardless of fl uid color or opacity.
This sensor can be connected to fl exible tubing or rigid pipe, and uses standard hardware
for mounting. Only one moving part and a low pressure drop across the sensor reduces
operating costs and maintenance requirements.
Features
• Operating range 0.11 to 12.11 lpm (0.03 to 3.2 U.S. gpm)
• Simple mounting
• ¼ in. NPT or ISO threads for simple pipe or tubing connection
Mounting tabs for metric M3 or
standard #6 screws on 68 mm
(2.68 in.) bolt circle
Top View
bar
1.7
1.4
1.0
0.7
0.3
0
psi
25
20
15
10
5
0
0 0.511.522.53
0 1.9 3.8 5.7 7.6 9.5 11.4
gpm
lpm
Pressure Drop Across Sensor vs. Flow Rate
3-2000-1X3-2000-2X
36 mm (1.42 in.)
81 mm
(3.2 in.)
Side View
Refer to your local Georg Fischer Sales offi ce for the most
current warranty statement.
All warranty and non-warranty repairs being returned must
include a fully completed Service Form and goods must be
returned to your local GF Sales offi ce or distributor.
Product returned without a Service Form may not be
warranty replaced or repaired.
Signet products with limited shelf-life (e.g. pH, ORP, chlorine
electrodes, calibration solutions; e.g. pH buffers, turbidity
standards or other solutions) are warranted out of box but not
warranted against any damage, due to process or application
failures (e.g. high temperature,
mishandling (e.g. broken glass,
chemical poisoning, dry-out) or
damaged membrane, freezing
and/or extreme temperatures).
Product Registration
Thank you for purchasing the Signet line of Georg Fischer
measurement products.
If you would like to register your product(s), you can now
register online in one of the following ways:
• Visit our website www.gfsignet.com and
click on Product Registration Form
• If this is a pdf manual (digital copy),
click here
Dimensions
Safety Information
1. Depressurize and vent system prior to installation/removal.
2. Confi rm chemical compatibility before use.
3. Do not exceed maximum temperature/pressure
specifi cations.
4. Wear safety goggles or faceshield during installation/
service.
5. Do not alter product construction.
Warning / Caution / Danger
Indicates a potential hazard. Failure to follow all warnings
may lead to equipment damage, injury, or death
Personal Protective Equipment (PPE)
Always utilize the most appropriate PPE during
installation and service of Signet products.
Pressurized System Warning
Sensor may be under pressure, take caution to vent
system prior to installation or removal. Failure to do so
may result in equipment damage and/or serious injury.
Note / Technical Notes
Highlights additional information or detailed procedure.
2
Signet 2000 Micro Flow Sensor
Compatible Instrument Wiring Specifi cations
0°
30°30°
General
Flow Range:
-11 & -12 version ............0.11 to 2.6 lpm (0.03 to 0.7 gpm)
-21 & -22 version............1.13 to 12.11 lpm (0.3 to 3.2 gpm)
Linearity .............................±1.2% of full range
Repeatability ......................±0.5% of full range
Connections.......................1/4 in. NPT (male) or
ISO 7/1 - R1/4 (male)
Wetted Materials
Sensor Body and Cover ....40% glass fi lled Polyphenylene
Sulfi de
®
Rotor ..................................PEEK
Cover O-ring ......................
, natural, unfi lled
FKM
Electrical
Power ................................5 to 24 VDC ±10%, regulated,
10 mA max.
Output type: Open-collector, sinking, 10 mA
max.
Cable Length .....................7.6 m (25 ft), can be extended up
to 300 m (1000 ft)
Cable Type ........................2-conductor twisted pair w/shield
(Belden 8451)
Max. Pressure/Temperature Ratings
0 °C to 80 °C (32 °F to 176 °F) @ 5.5 bar (80 psi) max
Black (5 to 24 VDC)
Red (Signal out)
Signet 2000
Shield (DC return)
Black
Shield
Red
10 kΩ
Technical Notes:
• Use 2-conductor twisted-pair shielded cable for
sensor cable splices up to 300 m (1000 ft) max.
• Maintain cable shield through cable splice.
• Route sensor cable away from AC power lines.
• AUX power required when used with any Signet
8550 Process Pro Flow Transmitter.
+
-
Gnd.
Input
Signet
Instrument
Blk
Power
Red
Freq. input
Shld
Gnd
Other
Instrument
5 to 24
VDC
Other
Instrument
Shipping Weight
250 g (9.6 oz)
Standards and Approvals
• Manufactured under ISO 9001 for Quality and ISO 14001
for Environmental Management and OHSAS 18001 for
Occupational Health and Safety
Recommended Sensor Position
Recommended
mounting angles
Vertical mounting
not recommended
PEEK® is a registered trademark of Victrex plc.
Technical Notes:
• Horizontal surface mount (±30°) recommended for
optimum performance.
• Suitable for clean fl uids only. Suspended solids will
cause mechanical failure.
• 1/4 in. NPT or ISO 7/1 - R1/4 (male) port connections
• NEMA 4X/IP65 splashproof enclosure.
Signet 2000 Micro Flow Sensor
3
Sensor Mount Instructions
1
Remove sensor then use correct
2
screws for panel material.
120°
#6 or M3 metric
screws recommended
Mounting surface
Fitting Installation
CAUTION:
• Maximum pipe fi tting torque: 13 Nm (10 lb)
• DO NOT overtighten. Failure to observe torque specifi cation may
permanently damage sensor ports.
Pipe fittingPipe
K-Factors
The K-Factors listed below represent
the number of pulses the sensor will
generate for each engineering unit of
fl uid which passes. They are listed in
U.S. gallons, liters and ml by sensor
model: