Thank you for choosing a HiTECH/ NIVELCO instrument.
We are sure that you will be satisfied throughout its use.
1. INTRODUCTION
APPLICATION
The EASYTREK SCD - 300 series compact ultrasonic transmitters from HiTECH/NIVELCO are designed to measure the level of free flowing solids, granules and
powders.
The unit does not touch the material to be measured and does not in clude any moving parts. Thus, it is not ex posed to mechanical loading, no abrasive effec t is
expected and regular maintenance is not required.
A Total beam angle of 5° at –3 dB is a feature of all HiTECH/NIVELCO’s ultrasonic sensors designed for the level measurement of free flowing solids.
This uniquely narrow beam angle ensures reliable measurement in narrow silos with uneven side walls or sometimes even in the presence of dusting.
Furthermore, as a result of the narrow beam angle – the emitted ultrasonic s ignals have an outstanding focusing – a sufficient signal penetration through dust is
ensured.
PRINCIPLE OF OPERATION
The ultrasonic level meter ing technology is based on the principle of measuring
the time required for the ultrasound pulses to make a round trip from the sensor to
the level to be measured and back.
The sensor emits an ultrason ic pulse trai n and receives the ec hoes refl ected. The
intelligent electronic device processes the received signals by selecting the
echoes reflected from the surface and calculates the distance from the time o
flight between the sensor and the surface of the medi um. This is the basis f or all
other output signals (level or volume) of the EasyTREK! For measuring the level o
the medium the greatest distance of the application (H) has to be programmed.
X
rr
D
XD
5 m0,7 m
10 m1,2 m
20 m2 m
30 m3 m
40 m3,8 m
50 m4,7 m
Diameters correspo nding to the
5° beam angle
X = 16,5 ft. D = 28.0”
X = 33.0 ft. D = 4.0 ft.
X = 65.0 ft. D = 7.0 ft.
X = 99.0 ft. D = 9.9 ft.
X = 131.0 ft. D = 13.0 ft.
X = 197.0 ft. D = 15.0 ft.
Minimum measu ring dist ance (Xm) is the construction defined smallest distance within w hich measuremen t is not possib le (Dead Band; see 5.3. Parameters P05).
In special applications this range should be extended with programming (close end blocking)
Maximum measuring distance (X
possible over this distance i.e. maximum distance of the application H must not be greater than X
): is the construction defined greatest distance, which can be measured by the unit under ideal conditions. No measurement is
M
. Under unfavourable circumstances such as bad reflection or heavy
M
dusting of the material the measuring capability may be reduced up to the half of the unit’s best performance.
scd3404a0600p_01 ♦ 5 / 36
THE FOLLOWING TYPES OF APPLICATIONS ARE POSSIBLE DEPENDING ON THE COMMUNICATION AND WHAT THE OUTPUT SIGNAL IS USED FOR:
1. Using the unit as a three - or four -wire current transmitter.
Normally, we use the analogue (4…20 mA) o utput signal of the EasyTREK. The application parameters of the device are set through HART communication at
installation (right after installation or in a laboratory, prior to installation). In this case the short address of the device should stay the factory default: P19 = 0.
2.Using both, current transmission and digital (HART) signal transfer in single transmitter systems.
Digital signal transfer is also used beside the standard utilis ation of the output current of the Eas yTREK. In this case, there can be one or more devices in the
current loop that use analogue
signals (with their total resistance being R
The short address of the EasyTREK should stay the factory default: P19 = 0. This application can be achieved w ith using a PE-10 or a PR-1 type
MultiCONT unit as the HART master which ensures the power supply of the EasyTREK too.
3.Simultaneous control of several EasyTREK transmitters with the help of a MultiCONT.
In this case all of the EasyTREK s keep the connection with the MultiCONT through HART communication only.
This means that the measurement values are collected in cycles, and that the modifications of the transmitter settings are arbitrary.
The short addresses of the units are P19 = 1 ... 15. All types of setting and programming tasks can be done through a MultiCONT.
= 250 … 600 Ω) and one HART master device.
t
scd3404a0600p_01 ♦ 6 / 36
2. TECHNICAL DATA
2.1.GENERAL DATA
Type
EasyTREK SCD– 3 - 4
EasyTREK SCD– 3 - 8 Ex*
Housing material PP+ Aluminium Aluminium
Total beam angle (-3dB) 5°
Process temperature -22ºF (–30°C) ... + 140ºF (60°C) - 4ºF (–20°C) ... +140ºF (60°C)
Process pressure (absolute) 0,07 ... 0,11 MPa (0,7 … 1,1 bar) 10 PSI – 16 PSI
Power supply / consumption 11,4 … 40 V DC / 3,6 W, 11,4 … 28 V AC / 4 VA
Output
Analogue 4 … 20 mA, R
Digital communication HART
= 600 ohm, Galvanic isolation; protection against surge transients
tmax
Relay SPST ; 48 V AC / 5A; A12
Accuracy
±( 0,2% of the measured distance + 0,1% of the range)
Resolution 0.39” (10 mm)
Damping 3 … 1000 s
Electric connection
6 x 2,5 mm
2
∅ 7,5 mm shielded cable ; standard length 9.8 ft (3 m) ; (to order up to 98 ft. (30m)
Electric protection Class III
Ingress protection IP65
Ex marking* n.a.
*Pending
ATEX II 1D IP 65 T 130 °C
2.2.SPECIAL DATA
Type
SCD-34 - 4
SCD-34 - 8 Ex*
Maximum measuring distance** (XM) 49 ft. (15 m) 98 FT. (30 m) 197’ (60 m)
Minimum measuring distance** (Xm) 1.6 ft. (0,5 m) 2 ft. (0,6 m) 3.28 FT. (1 m)
Ultrasound frequency 40 kHz 30 kHz 15 kHz
Sensor face PVC foam
Mass 7.7 lbs. (~ 3.5 kg) 7.7 lbs. (~ 3.5 kg) 14.0 lbs. (~ 6.5 kg)
SCD-33 - 4
SCD-33 - 8 Ex*
SCD-31 - 4
SCD-31 - 8 Ex*
*Under optimal circumstances of reflection and stabilised sensor temperature
scd3404a0600p_01 ♦ 7 / 36
2.3.ACCESSORIES
• Installation and Programming Manual
• Guaranty Certificate
• Manufacturer’s Declaration
• EView Light configuration software and description on CD
ACCESSORIES TO BE ORDERED
• Split flange (order code: SFA – 35)
• EView configuration software CD
• HART modem
2.4.ORDER CODES
Range Code
197 ft (60 m)
99 ft (30 m)
49 ft. (15 m)
scd3404a0600p_01 ♦ 8 / 36
EasyTREK
1
3
4
* The order code of an Ex version should end in “Ex”
Selecting optimal location for the transmitter various considerations should be made.
If the measured material is granule (material s ize > 5 mm) and th e t ank roof is do me s haped or con ical, do n ot
install the transmitter in the centre of the tank/silo. In gen eral the transmitter can be installed on the radius
r= (0,3 … 0,5) R.
Avoid that the 5° conical beam angle of the transmitter contact the tank/silo wall. In case the transmitter is
mounted close to the wall, it should be tilted (S ee section “Aiming”). Protect the transmit ter electronics from
overheating due to direct sunshine. The same way no disturbing objects such as ladder, grid, thermometer, etc
should intrude into the beam cone. Heavy air movement can make measurement more difficult or even unable.
Device should be protected against direct sunshine no to let its temperature increase into excessive range.
GRAVITY FILLING
Select a location that is as
far away from the filling
point(s) as possible.
PNEUMATIC FILLING
Select a location where the speed of the in-fl owing
material is the smallest.
r
R
Suggest ed lo c ation (vie w from above)
40 m3,8 m50 m4,7 m
MOUNTING (see illustration of mounting options on the next page)
The EasyTREK consists of a sensor that is attached to the aiming arm (a pipe with a ball-joint housing incor porating a ball joint) that is attached to the housing of the
electronics. It is recommended to mount the transmitter on the roof of the tank/silo using a flange (see drawing above). The Ball-joint housing has a screw-hole
diameter of 125 mm for fixing it. For easy installation we recommend using our special flange with a split insertion, available in four sizes of DN125/ 150/20 0/300 (to be
ordered separately). Removing the split insertion, the flange is to be put around the aiming arm and the ball-joint housing is to be fixed to the split flange. It is essentia l
to use the washers and the bolts (4 pcs each) deliv ered with the split flange. The ball-joint w ill be pressed to the housing by a spring allowi ng adjustment/aiming.
The 4 pcs of M12 bolts have to be tightened only after completing the adjustments/aiming.
scd3404a0600p_01 ♦ 10 / 36
When the entire tilting range of the aiming arm is required, the thickness of the roof can not exceed the values specified below.
The EasyTREK can also be mounted on existing (manhole) covers, access lids or for instance on a steel structure lowered into a larger ( ex.: 0.5 x 0.5 m) opening on
the roof. This solution is to be used with roofs thicker than 350 …380 mm.
Diameter of the
Opening
D
160 mm 110 mm
190 mm 150 mm
230 mm 200 mm
300 mm 280 mm
340 mm 300 mm
Maximum Thickness
of the Roof
V
Illustration of mounting
scd3404a0600p_01 ♦ 11 / 36
4. WIRING
4.1.WIRING CONDITIONS
•The transmitter is SELV supplied. In the case of DC supply the connection is
independent of polarity.
• Only SELV circuits can be switched on to the relay output.
• The house must be grounded to have noise protection; it should be
grounded to the equipotential bonding net.
•3-wire DC powered devices can be created by connecting one of the power
supply wires to the white wire of the current output ( GND). In this case the
current output becomes galvanically non-isolated.
•The units and the cables should be arranged so that the fastening outside
the device relieves the end of the cable of any traction.
4.2.CONNECTION CABLE EXTENSION
Brown
Supply
Green
I
+ HART
OUT
Grey
White
Pink
Relay outpu t
Yellow
• It is advised to use a terminal box when cable extension is necessary.
The shielding should be connected to the shielding of the extension cable and
it should be grounded at the proces s ing unit.
Grounding
Colour codes of the outputs
Housing
scd3404a0600p_01 ♦ 12 / 36
Multiple SCD-300 transmitters connected to a MultiCONT process control unit
Power is supplied from a common external source, the relays are not used.
DEVICES
MultiCONT
26 27 28
Shielding
Grey
Brown
24 V AC/DC
Green
White
Trial and laboratory programming of the SCD-300 transmitters
Output current test
mA
Grey
EasyTREK
White
SELV
supply
Brown
Green
HART communication and power supply of one SCD-300 transmitter from the
MultiCONT process control unit.
SCD-3_ _-4
SCD-3_ _-4
SCD-3_ _-4SCD-3_ _-4
scd3404a0600p_01 ♦ 13 / 36
5. PUTTING INTO OPERATION, ADJUSTING, PROGRAMMING
5.1.PUTTING INTO OPERATION
After switching on the correc tly wired unit the transducer begins to click audibly. In about 20 … 50 s the ECHO LED goes on and a signal between 4 ... 20 mA
appears on the current output. When first powering the unit, it measures with the standard manufacturer’s settings (see some of the most important parameters
below).
Default parameters
All the transducers get the same factory default parameters that can also be reset later if needed. Some of the most important parameters of the EasyTREK
SCD-300 series can be found below.
⇒ Measurement mode: level (LEV),
⇒ 4 mA is assigned to the
⇒ 20 mA is assigned to the
⇒ Current output holds last value in case of error
⇒ Damping: 300 s
All the other measurement values are set to fit the values suitable for standard tasks. The functions used in special cases are switched off.
AIMING THE SENSORS
When the material to be measured i s being filled or empt ied, because o f the formation of an angle of repos e, the vertically installed transmitter will experience a weak
signal. This can be eliminated in most cases by tilting the unit, so the aiming device is a very important part of these transmitters. The proper aiming can be set and
checked while the transmitter is being used, desirably when the silo / t ank is almost empty . Usually it is best that the transmitter points to the middle of the bottom of
the silo/tank.
X
maximum measuring distance (minimum level)
M
X
minimum measuring distance (maximum level)
m
In cases when the silo is narrow, and the height / diameter value equals to or is more than 5, tilting is
usually not necessary. Aiming should also be checked when the silo / tank is full, because the echo can
be adversely weak even when c oming from a nearby surface. This us ually happens when the angle of
repose is big. In this case an optimal solution must be found in which the echo coming from any
distance is acceptable. The SERVICE PARAMETERS that can be reached dur ing progra mmin g provid e
help for set-up. That means that the aiming adjustment and the programming should be done at the
same time.
scd3404a0600p_01 ♦ 14 / 36
5.1.1.STATUS INDICATION SIGNALS IN MEASURING MODE
HART respond signals
The properly installed device with factory default settings gives the following
responses to the COM3 universal HART command:
primary value Level
secondary value Level
tertiary value Distance
quaternary value Temperature (See P01 programming).
5.2.SAFETY REGULATIONS OF THE EX APPROVED UNITS
Ex certified devices are approved for Zone 20 and Zone 21 areas.
Transmitters must not be installed in the dust path of the pneumatic filling!
Neither the device, nor a ny part of it should be used as a flame-proof barrier of a
Zone 20 area.
The cable outside the unit should be fixed so that it is tension-free.
The terminal box should be selected in accordance with the electrical class of the
area.
LED status signals on the unit
Green LED COM
Lights up during HART programming.
Red LED ECHO
Lights up when the device gets proper echoes.
5.3.PROGRAMMING
HART interface of the EasyTREK enables full access and programming of the complete parameter set.
Parameters can be accessed by two ways:
- with a HART modem and EView or Eview light configuration software run on a PC
- by the HiTECH/NIVELCO made MultiCONT multichannel controller
This instruction de scribes parameters and f eatures behind th em but does not deal with technical details for their selection and editing of their values. Compact Disk
attached to the transmitt er cont ains detailed i nformatio n on th e Eview co nfigurat ion s oftwar e (to install on PC ) and its descriptio n. Pro grammin g b y the MultiC ONT can
be taken from its Installation and Programming Manual.
Continuous measuring is going on during programming in accordance with the last programmed parameter set. This way the analog output signal
(4-20mA) continuously represents the actual value. The digital (HART) communication depends on the communication software. The new, modified
parameter set will be valid after returning to measurement mode. The device changes back to measurement mode automatically in 1 minute after
programming through HART communication has been finished or discontinued.
scd3404a0600p_01 ♦ 15 / 36
5.4.PARAMETERS –DESCRI PTIO N AND PRO G RAMMI NG
5.4.1.MEASUREMENT CONFIGURATION
P00: - c b a Application/Engineering Units
Programming of this parameter will result in loading the factory default with the corresponding engineering units.
a Operating (measurement) mode
1
b
0
1
c Calculation system
0
1
FACTORY DEFAULT: 001
DEVICE CAN BE OPERATED WITH TWO DIFFERENT ENGINEERING UNIT SYSTEMS, BUT FOR THE SAKE OF EASY OVERVIEW ONLY THE
METRIC SYSTEM WILL BE USED!
Free flowing solids level measurement
Engineering units (according to “c”)
Metric US
m ft
cm inch
ATTENTION!
( according to „c”)
Metric
US
scd3404a0600p_01 ♦ 16 / 36
V
VOLV
P01: - - b a Measurement Mode
Values transmitted by HART protocol, current output and the switching points of the relays will be interpreted into the engineering units of the
(measured or calculated) process value corresponding to the programmed measurement mode. On the other hand, the higher the “a” of the
programmed parameter value the more (measured or calculated) process values can be transmitted through HART (e.g. if P01=0 only the Distance, if
P01=4 Distance, Level and Volume; Exception: P01=2 or 4.)
a MEASUREMENT MODE
0
1
2
3
4
Distance Distance
Level
Level in percent
Volume
Volume in percent
TRANSMITTED
PROCESS VARIABLES
Level
Volume
LEV
Factory settings
PRIMARY VARIABLES
TRANSMITTED THROUGH
HART
DIST
LEV
LEV%
VOL
VOL%
LEV
OTHER VARIABLES TRANSMITTED
THROUGH HART
Secondary: LEV
Tertiary: DIST
Quaternary: Temp
Facto ry settings
Xm
DIST
H
P11
P10
P11
P10
LEV
LEV %
OL
OL %
0
100
[%]
0
scd3404a0600p_01 ♦ 17 / 36
100
[%]
P02: - c b a Calculation units
a Temperature
0
1
°C
°F
This table is interpreted according to P00(c), P01(a) and P02(c) and is irrelevant in case of percent age measurement ( P0 1( a)= 2 or 4 )
Volume Weight (set also P32
b
Metric US Metric US
3
m
0
1
ft3 tone lb (pound)
litre gallon tonne tonne
c
The value of character c has no significance at devices for solids
FACTORY DEFAULT: 000
P03: - - - a Values displayed – Rounding (Not used at EasyTREK)
P04: - - - - Maximum measuring distance (H and XM)
Maximum measuring distance is the greatest distance (H) between the sensor surface and the farthest surface to be measured in the application.
Factory default of this parameter is the m axi mum di stan ce (X
be set for the maximum distance (H) to be measured, whereas H ≤ X
Basic feature of the ultrasound level meter s is their not bein g a ble to measure next to the sensor surface. Within this range the measurement can not be
interpreted, thus it should be avoided that material level get into this range. By en teri ng a v alue, hig her tha n the fact ory def ault , the m ini mu m mea surin g
range will be extended and fixed to that value. Manual close-end-blocking would be used for example to bl ock out the echo originatin g from the bott om
rim of a stand-off pipe or from any object protruding into the ultrasonic cone near to the transmitter.
Automatic Close-end-blocking (Automatic Dead Band control)
By using the factory default value, the unit will automatically be adjusted to the smallest possible dead band (X
in disadvantageous mountings greater than the dead band.
). In ideal cases this can be smaller and
m
Manual close-end-blocking P05 = X
Entering greater value in P05 than X
> Xm
B
will represent the extension of the close end blocking.
FACTORY DEFAULT: automatic close end blocking (Xm as per the table)
scd3404a0600p_01 ♦ 19 / 36
P06: - - - - Far-end blocking
Far-end blocking is the range below the level
set in parameter P06. Far-end blocking can
be used to avoid disturbing effec ts of stirrers
or heaters at the bottom of the tanks.
When the unit detects ec hoes in this range it
gives special signals.
When level sinks below far-end bloc king:
- Message of "Sub 0" appears in EView (in
level and volume measurement mode)
- Current output holds value corresponding to
far-end blocking distance
When level rises above far- end blocking:
The calculation of level and volume will be bas ed on the programmed tank dimensions, th erefor e the me asured or calculated process values will not
be influenced in any way, by the value of far-end blocking.
FACTORY DEFAULT: 0
LEV
T
S
I
D
LEV=level
VOL=volume
0
4mA
20mA
I
out
DIST
H
“SUB 0” display
below this level
P06
Far-end blocking
scd3404a0600p_01 ♦ 20 / 36
5.4.2.CURRENT VALUE
P08: - - - - Fixed output current
With this step the output current can be s et as a fix value, selected between 3,8 mA and 20,5 mA. This function is not operational as per the factory
default: 0. Attention: fixing output current will make settings in P10, P11, P12 and P19 irrelevant.
FACTORY DEFAULT: 0
P10: - - - - Value (of distance, level o r volume) assigned to 4 mA current output
P11: - - - - Value (of distance, level o r volume) assigned to 20 mA current output
Values are interpreted according to P01(a). Please note that in case of programming for (LEV or VOL) % measurement the min and max value has to
be entered in the relevant engineering units of LEV (m, ft) or VOL (m
3
, ft3).
Assignments can be made so that the proportion between th e change of the (measured or calculated) process value and the change of the current
output be either direct or inverse. E.g. lev 1m assigned to 4mA and lev 10m assigned to 20mA represents direct proportion and lev 1m as signed to
20mA and lev 10 m assigned to 4mA represents inverse proportion.
Level dis pl ay
X
m
[m]
DIST
LEV
Level transmission
20,5 mA
Level % display
FACTORY DEFAULT: P10: 0, P11: X
P12: - - - a Erro r indication by the curren t output
In case of error the EasyTREK will provide one of the current outputs below for the time the failure prevails.
a Error indication (according to NAMUR)
0
HOLD last value
1
2
P11
P10
0
– Xm .(See P04 and P05)
M
3,8 mA
0420
Factory settingsFactory settings
I
out
[m ]A
0100
3,6 mA
22 mA FACTORY DEFAULT: 0
LEV %
[ ]
%
scd3404a0600p_01 ♦ 21 / 36
5.4.3.RELAY OUTPUT
P13: - - - - Relay functions
a Relay functions Also to set:
0
1
DIFFERENTIAL
LEVEL CONTROL
(Hysteresis control)
If the value selected for controlling the relay
increases over P14 : relay energises
decreases below P15 : rel a y de- energises
“no ECHO” indicated by energised relay —
ERROR INDICATION
2
“no ECHO” indicated by de-energised relay —
FACTORY DEFAULT: 2
P14: … Relay parameter – Setpoint value
FACTORY DEFAULT: 0
P15: - - - - Relay parameter – Setpoint value
Level
Relay
P14
P15
Energised:
De-energised:
Keep at least 2 cm
difference between
Time
P14, P15
P14 and P15
Relay set points are to be programmed for two-point control. Values should be set in the quantity selected for transmitting in parameter P01.
Keep at least 20 mm difference between P14 and P15
FACTORY DEFAULT: 0
P19: - - - - HART short add r ess
Short address is to enter here. The 00 short address is suitable for loop with one device only, when both analogue signal and HART is able to carry
information. For other settings see instruction in the manual for the configuration software EView supplied with the unit.
FACTORY DEFAULT: P19 = 00
scd3404a0600p_01 ♦ 22 / 36
5.4.4.MEASUREMENT OPTIMALIZATION
P20: - - - a Damping
This parameter can be used for reduction of unwanted fluctuation of the displayed value and the output.
a
0
1
2
3
4
5
6
7
8
9
Damping time [s]
None For test only
3 Not recommended Not recommended
6 Not recommended Not recommended
10 Not recommended Not recommended
30 Applicable Not recommended
60 Recommended Applicable
This parameter is important for the optimalisation of the of the QUEST+ software echo evaluation.
a Estimated angle of repose
0
1
2
No angle of repose α ≅ 0
α< 15°
α > 15°
The optimal setting of this parameter can be done with the help of checking the echo strength in
the read out parameter P72 indicating the echo amplitude in dB.
The ideal setting of P23 is at which the parameter value in P72 becomes the best (nearest “0”).
FACTORY DEFAULT: 0
Granules
particle size >2-3 mm
DUST
particle size < 1-2 mm
scd3404a0600p_01 ♦ 23 / 36
P24: - - - a Target tracking speed
g
With this parameter the evaluation can be sped up at the expense of the accuracy.
a Tracking speed Remark
0
1
2
Standard For most applications
Fast For fast changing level
Special
For very special cases only, as this reduces the maximum measuring range to 50% of the nominal value! The
measuring window (P25 and P33) is inactive and the EasyTREK will respond practically instantly to any target.
FACTORY DEFAULT: 0
P25: - - - a Selection of Echo within the measuring window
A so-called measuring window is formed around the echo signal. The position of this measuring window determines the flight time for calculation of the
distance of the target. (the picture below can be seen on the test oscilloscope)
Received
signal
amplitude
Some applications involve multiple (target + disturbing) echoes even within the measuring window. Basic echo selection will be done by the Quest +
software automatically. This parameter only influences the echo selection within the measuring window.
a Echo in the window to be select ed Remarks
0
1
2
With the highest amplitude For most applications (both liquids and solids)
First one For applications with multiple echoes within the Measuring Window
Largest one Recommended for applications with floating material in the air
P27: - - - - Lev el wane rate (emptying speed) [m/h]
Use these parameters to provide additional protection against echo loss in applications involving dust during the filling process (powders, dusting
granules). Reliability of the measurement can be enhanced by the correct setting of this parameter.
These parameters must not be smaller than the fastest possible filling/emptying rate of the actual technology.
FACTORY DEFAULT: 500
P28 - - - a Echo-loss handling
a
0
1
2
3
Echo-loss error
indication
Delayed
None During an echo-loss the displayed value on the EView and the analogue output value will hold last value.
Advance to full
Immediate
No echo-loss
4
indication in case of
empty tank/silo
FACTORY DEFAULT: 0
Remark
During short periods of echo-loss, both Eview and the analogue output will hold last value. The current output
holds last value for twice as long as set in P20 before going to the "Error Indication Mode" set in P12.
HART
Holding value
Error Code 2
Echo loss
Echo LED goes out
2 * ”P20” time
Current 22 mAP12=2
Current output
Holding value
Holding last va lueP12=0
Current 3,6 mAP12=1
When echo-loss occurs during filling, the displayed value on the EView and the analogue output value shifts
towards the "full" tank/silo state with the level elevation rate (filling speed) set in P26
In case of an echo-loss, ‘no Echo’ will appear in EView and the outputs will change according to the "Error
Indication Mode" set in P12.
Echo-loss may occur in completely empty tanks with a spherical bottom due to deflection of the ultrasonic beam, or
in case of silos with an open outlet. If the echo is lost when the tank /silo is completely empty, the indication will
correspond to empty tank, in all other cases echo-loss indication will function according to the “Delayed”.
scd3404a0600p_01 ♦ 25 / 36
P29 Blocking out of object
One object in the tank/silo disturbing measurement can be blocked out.
Enter distance of the object from the transducer. Use the Echo Map (P70) to read out the precise distance of disturbing objects.
FACTORY DEFAULT: 0
P31: Sound velocity at 20 °C (m/sec or ft/sec depending on P00(c) )
Use this parameter if the sound velocity in the gases above the measured surface differs largely from that of in air.
Recommended for applications where the gas is more or less homogeneous. If it is not, the accuracy of the measurement can be improved using the
32-point linearization (P48, P49).
For sound velocities in various gases see s ect ion “ Sound Veloc it ies ” .
If you enter value (other than “0”) of specific gravity in this parameter, the weight will be displayed in EView instead of VOL.
FACTORY DEFAULT:
0 [kg/dm
3
] or [lb/ft3] depending on P00(c)
P33: (m) Manual echo selection by moving the Measuring Window
A so-called measuring window is formed around the echo signal (See scheme on the next page.)
The distance of the target will be calculated from the flight ti me in acco rd anc e with th e posi t ion of the
measuring window.
Use this parameter if the EasyTREK unambiguously selects a wrong echo; for example the echo
reflected from the surface is muc h weaker than the interfering one(s) (see figure beside and on next page).
Enter the distance of the correct echo and the software will move the measuring window and
calibrate itself to the echo found there.
To determine the distance of the corr ect echo, e ither use the Echo Map (to load-in a value from the
Echo Map, see paramet er P70), or measur e the dista nce with an appropriate d evice, and enter this
value in P33.
If this parameter has been used (P33 is not 0), its value will be continuously updated with the valid echo position.
This means, that in case of a power loss, the E asyTR EK will res tart the s ignal pr ocessing with the me asuring window at t he last updated
position. To switch-off this function, set P33= 0.
FACTORY DEFAULT: 0
scd3404a0600p_01 ♦ 26 / 36
1.
2.
MANUAL ECHO SELECTION
1.
Received
signal amplitude
Window
signal (comp.)
2.
Window
signal (comp.)
Weak echo
from the surface
Eg.: 3.85 m
1.2.
measuring window
(locked on the disturbing echo)
Setting: P33=4.00 (results in shifting the measuring window to 4 m)
Disturbing echo
Eg.: 5.2 m
(flight time)
t
Transmitt ed DIST value
(of the disturbing echo)
5.2
t
3.
Window
signal (comp.)
t
Measuring Window finds the echo from the surface
t
Transmitt ed DIST value
(the value is correct)
3.85
scd3404a0600p_01 ♦ 27 / 36
5.4.5.VOLUME MEASUREMENT
P40: - - ba Tank / silo shape
ba Tank/silo shape
B0
01
02
B3
04
P41-45: - - - - Tank / silo dim ensions
Standing cylindrical tank shape: value of “b” as below bottom
Lying cylindrical tank shape: value of “b” as bellow bottom P40(b), P41, P42
Other parameters to be
set
P40(b), P41
Standing cylindrical tank/silo with conical bottom P41, P43, P44
Standing rectangular tank/silo (with ch ute
Spherical tank
)P41, P42, P43, P44, P45
P41
FACTORY DEFAULT: 00
Standing cylindrical tank/silo
with hemispherical bottom
b=0
b=1
b=3
b=2
P40
Lying cylindrical tank Spherical tank
b=3
P40
b=2
b=1
b=0
FACTORY DEFAULT: P41 ... P45 = 0
Standing cylindrical tank/silo
with conical bottom
Standing rectangular tank/silo
with or without chute
For flat bottom
P43, P44 and
P45 = 0
scd3404a0600p_01 ♦ 28 / 36
5.4.6.LINEARIZATION
P47: - - - a Linearization
Linearization is the method of assigning requested (calibrated or calculated) level, volume or flow to values measured by the transmitter.
It can be used for instance if the sound velocity is not known (LEVEL⇒LEVEL) or in the case of tank with other shape than under 5.4 . 5. (LEVEL ⇒
VOLUME).
a Linearization
0
1
Conditions of correct programming of the data pairs
The table must always start with: L(1)= 0 and r(1)= value (assigned to 0 level)
The table must be ended either with the 32
level value “0” e.g. L(j<32)= 0.
The EasyTREK will ignore data after recognising level value “0” with serial number other than “1”.
If the above conditions are not met, error codes will be sent (see chapter: Error Codes).
OFF (FACTORY DEFAULT)
ON
nd
data pair i.e. j=32 or if the linear isation t able c ontai ns less than 3 2 data-p airs j<32, i t must b e ende d with a
i
L (Left column)
Level values measured
1 0 r(1)
2 L(2) r(2)
L(i) r(i)
nn L(nn) r(nn)
nn+1 0
32
FACTORY DEFAULT: 0
P48: Number of linearization data pairs
Number of linearization data pairs entered in the table.
r (Right column)
Value assigned to transmit
scd3404a0600p_01 ♦ 29 / 36
5.4.7.INFORMATIONAL PARAMETERS
P60: - - - - Ove r a ll operating hours of the unit (h)
P61: - - - - Time elapsed si nce last switch-on (h)
P62: - - - - Operating hours of the relay (h)
P63: - - - - Numb e r o f switching cycles of the relay (h)
P64: - - - - Actual tem p er ature of the transdu cer ( °C/°F)
Broken loop of the thermometer will be indicated by Pt Error message that is initiated by a signal sent via HART. In this case the transmitter will per for m
temperature correction corresponding to 20ºC.
P65: - - - - Maximum temperature of the transducer (°C/°F)
P66: - - - - Minim um tem p erat ure of the transducer (°C/° F )
P70: - - - - Number of Echoes / Echo Map
Amplitude and position of the echoes can also be read out.
scd3404a0600p_01 ♦ 30 / 36
P71: - - - - Distance of the of Measu ring Window
P72 - - - - Amplitude of th e selected echo [dB] <0
P73: Position of the selected echo (time) : (ms)[ms]
P74: Signal to Noise Ratio
Ratio Measurement conditions
Over 70 Excellent
Between 70 and 50 Good
Under 50 Unreliable
P75: - - - - Blocking Distance
This parameter gives information about the actual close-end blocking distance (provided automatic blocking was selected in P05)
5.4.8.
TEST PARAMETERS
P96: - - - - Checksum
P97: - - - - Software code (Read only parameter)
P98: - - - - Hardware code (Read only parameter)
P99: dcba Access lock by secret code
The purpose of this feature is to provide protection ag ainst accidental pr ogramming of par ameters or by a pers on. not entitled. The secret c ode can be
any value other than 0000. Setting a secret code will automatically be activated w hen the E asyTREK is returned to the Me asurement Mode. In or der to
program locked device the secret code should be entered first in P99. Thus for entering a new code or erasing the old one the knowledge of the
previous code is necessary.
scd3404a0600p_01 ♦ 31 / 36
5.4.9.ERROR CODES
Error
Code
1
No Echo
or
Err2
Err3
Err4
Err5
Err6
Err7
Err12
Err13
Err14
Error description Causes and actions to be done
Memory error Contact local agent
Bad reflection from the surface, reflection not directed
Echo loss or echo too weak to evaluate
towards the sensor, due to dusting excessive sound
absorption. Check device selection and/or adjustme nt
Hardware error Contact local agent
Calculation overflow Check settings
Code referring to sensor error or improper
installation/mounting, level in the dead band
Verify sensor for correct operation and check for
correct mounting according to Users Manual
The measurement is at the reliability threshold Change aiming or try to find a better location
No signal received within the measuring range
specified in P04 and P05.
Linearization table error: L(1) and L(2) are both zero
(no valid data-pairs)
Linearization table error: there are two same L(i) data in
the table
Linearization table error: the r(i) values are not
monotone increasing
Review programming, also look for installation mistake
See the Section ”Linearization”
See the Section “Linearization”
See the Section “Linearization”
Err15
Err16
scd3404a0600p_01 ♦ 32 / 36
Linearization table error: measured Level is higher than
the last Volume or Flow data-pair
See the Section “Linearization”
The checksum of the program in the EEPROM is wrong Contact HiTECH at 888 NIVELCO
6. MAINTENANCE, REPAIR
The device does not require rout ine maintenance. In case dust adheres to the face of t he sensor despite the self-cleaning of the sensor face through r esonance,
(ex.: static build-up) it can be cleaned by pressurised air.
Equipment sent back for repai r shou l d b e cl eaned o r ster il i s ed by the User. T he User mu st decl ar e that t he above has been carr ied out.
Repairs during or beyond the guarantee period are carried out by HiTECH/NIVELCO.
Par. Page Description Value Par. Page Description Value
d c b a d
P00 16 Application/Engineering Units P28 25 Echo loss indication
P01 17 Measurement Mode P29 26 Blocking out of disturbing object
P02 18 Calculation units P30 –
P03 - P31 26 Sound velocity in different gases
P04 18 Maximum Measuring Distance P32 26 Specific gravity
P05 19 Minimum Measuring Distance P33 –
P06 20 Far End Blocking P34 –
P07 – P35 –
P08 – P36 –
P09 – P37 –
P10 21 Transmitted value assigned to „4 mA” P38 –
P11 21 Transmitted value assigned to „20 mA” P39 –
P12 21 “Error” indication by the current output P40 28 Selection of tank shape/ open channel
P13 – P41 28 Dimensions of tank / Open Channel
P14 – P42 28 Dimensions of tank / Open Channel
P15 – P43 28 Dimensions of tank / Open Channel
P16 – P44 28 Dimensions of tank / Open Channel
P17 – P45 28 Dimensions of tank / Open Channel
P18 – P46 Level pertaining to flow Q= 0
P19 – P47 29 Linearization
P20 23 Damping P48 29 Linearization table
P21 – P49 –
Overall operating hours of the unit
Time elapsed after last switch-on
P82 – P83 –
P62 – P84 –
P63 – P85 –
P64 30 Actual temperature of the transducer P86 –
P65 30 Maximum temperature of the transducer P87 –
P66 30 Minimum temperature of the transducer P88 –
P67 – P89 –
P68 – P90 –
P69 – P91 –
P70 30 Echo Map P92 –
P71 31 Position of the measuring window P93 –
P72 31 Amplitude of the selected echo P94 –
P73 31 Position of the selected echo P95 –
P74 31 Signal / noise ratio P96 34 Software code 1
P75 33 Blocking distance value P97 34 Software code 2
P76 34 Water head of the flow P98 34 Hardware code
P77 34 TOT1 volume flow totalised P99 34 Access lock by secret code
scd3404a0600p_01 ♦ 35 / 36
HiTECH/NIVELCO
scd3404a0600p_01.doc
May 2006
reserves the right to change technical specifications without notice.
scd3404a0600p_01 ♦ 36 / 36
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.