NILAN - CTS700
Modbus User Guide
30030066-NILAN - CTS700
Date: 20180420
Modbus User Guide
Responsible: AKO
20010008E – Standard document template
Nilan A/S ● Nilanvej 2 ● 8722 Hedensted ● Danmark Tlf +45 76752500 ● Fax +45 76752525 ●
Page 2/20
Table of Contents
1. Revision history .................................................................................................................. 4
2. References ......................................................................................................................... 4
3. Abbreviations and terms ...................................................................................................... 4
4. Introduction ....................................................................................................................... 4
5. General Provisions .............................................................................................................. 4
5.1. Addressing .................................................................................................................. 4
5.2. Using PLC ................................................................................................................... 4
5.3. System Device Addressing ............................................................................................ 5
5.4. Console application ..................................................................................................... 5
6. Modbus Registers Description ............................................................................................. 5
6.1. Control registers .......................................................................................................... 5
6.2. Ventilation ................................................................................................................... 5
6.2.1. Filter settings ....................................................................................................... 5
6.2.2. Outdoor air filter ................................................................................................... 5
6.2.3. Extract air filter .................................................................................................... 6
6.2.4. Operation mode .................................................................................................... 6
6.2.5. Fan speed settings ................................................................................................ 6
6.2.6. Humidity control ................................................................................................... 6
6.2.7. Active cooling settings ........................................................................................... 6
6.2.8. Ventilation at low outdoor temperature ................................................................... 7
6.2.9. CO2 control .......................................................................................................... 7
6.2.10. After heating element .......................................................................................... 7
6.2.11. Temperature regulation ....................................................................................... 7
6.2.12. Temperature overview ......................................................................................... 7
6.2.13. Frost protection or de-icing .................................................................................. 8
6.2.13.1.
6.2.13.2. Polar setting: ............................................................................................... 8
6.2.13.3. EHD setting: ................................................................................................ 8
6.2.13.4. BAH setting: ................................................................................................ 9
6.2.14. De-icing heat exchanger ...................................................................................... 9
6.2.15. De-icing heat pump ............................................................................................. 9
6.3. Hot water production ................................................................................................... 9
6.3.1. DHW domestic hot water ....................................................................................... 9
6.3.1.1. Standby functions .......................................................................................... 9
6.3.1.2. Hot water settings ......................................................................................... 9
6.3.1.3. Antilegionella settings .................................................................................. 10
6.3.1.4. Compressor settings hot water production ..................................................... 10
6.3.1.5. Temperature overview .................................................................................. 10
6.3.2. SHW pre-heating domestic hot water ................................................................... 10
6.3.2.1. Hot water settings ....................................................................................... 10
6.3.2.2. Temperature overview .................................................................................. 10
6.3.3. DHW supplement domestic hot water ................................................................... 11
6.4. Central heating .......................................................................................................... 11
6.4.1. Standby functions ............................................................................................... 11
6.4.2. Cooling and heating at the same time ................................................................... 11
6.4.3. Temperature regulation GEO ................................................................................ 11
6.4.4. Temperature regulation AIR ................................................................................. 12
6.4.5. Buffer tank settings ............................................................................................. 12
External setting: .......................................................................................... 8
nilan@nilan.dk ● www.nilan.dk
30030066-NILAN - CTS700
Date: 20180420
Modbus User Guide
Responsible: AKO
20010008E – Standard document template
Nilan A/S ● Nilanvej 2 ● 8722 Hedensted ● Danmark Tlf +45 76752500 ● Fax +45 76752525 ●
Page 3/20
6.4.6. Outdoor weather compensation ........................................................................... 12
6.4.7. Hot water production ........................................................................................... 13
6.4.8. Cooling with GEO ................................................................................................ 13
6.4.9. Cooling with AIR ................................................................................................. 13
6.4.10. Compressor settings GEO .................................................................................. 13
6.4.11. Limited fan speed outdoor unit AIR .................................................................... 13
6.4.12. De-icing outdoor unit AIR .................................................................................. 13
6.4.13. Fan settings AIR ................................................................................................ 14
6.4.14. Compressor settings AIR .................................................................................... 14
6.5. General settings ......................................................................................................... 14
6.5.1. Language ........................................................................................................... 14
6.5.2. Smart Grid ......................................................................................................... 14
6.5.3. Smart Grid Hot water settings .............................................................................. 14
6.5.4. Smart Grid Central heating settings ...................................................................... 15
6.5.4.1. At low electricity prices ................................................................................. 15
6.5.4.2. At overcapacity of electricity ......................................................................... 15
6.5.5. Service............................................................................................................... 15
6.6. Information ............................................................................................................... 15
6.6.1. Compact P all device data .................................................................................... 15
6.6.2. GEO all devices data ........................................................................................... 16
6.6.3. AIR9 all devices data ........................................................................................... 17
6.8. Alarm list .................................................................................................................. 17
6.8.1. Alarm list control................................................................................................. 17
6.8.2. Alarm list .......................................................................................................... 18
nilan@nilan.dk ● www.nilan.dk
Date: 20180420
Modbus User Guide
Responsible: AKO
20010008E – Standard document template
Nilan A/S ● Nilanvej 2 ● 8722 Hedensted ● Danmark Tlf +45 76752500 ● Fax +45 76752525 ●
Date
Author
Comment
Revision
Status
20180228
AKO
Document created
1
Draft
20180301
AKO
Added information about console application
2
Draft
20180420
AKO
Added registers: 20004, 20223
3
Final
Abbreviation/term
Description
PLC
Programmable Logic Controller
1. Revision history
2. References
Modbus protocol specification:
http://modbus.org/docs/Modbus_Application_Protocol_V1_1b3.pdf
Modbus over TCP/IP: http://modbus.org/docs/Modbus_Messaging_Implementation_Guide_V1_0b.pdf
Abbreviations and terms
3.
30030066-NILAN - CTS700
Page 4/20
4. Introduction
This document, the Modbus Model Guide, describe Modbus register model of NILAN CTS-700.
5. General Provisions
In this chapter described general provisions of using Modbus protocol on NILAN CTS-700.
Columns description:
1. Register Number – Contain address of register in Modbus. (See Using PLC).
2. Slave ID – Contain slave address of target board (See System Device Addressing).
3. Function – Short description of register value.
4. R – Read permission (“+” - Reading is allow, “-” - Reading is deny).
5. W – Write permission (“+” - Writting is allow, “-” - Writting is deny).
6. Reset – If marked with “+” value will be applied after restart of the system.
7. Value – Contain all possible value of the register. Some of the register, which has Function “Apply value” must be write with specific key for applying of the parameter.
5.1. Addressing
Modbus client connect to a system using Modbus RTU over TCP/IP. It means that for connect to the system client must establish connection to board's IP address to port 502 Board's IP address by default set to 192.168.5.107 and can be changed by Modbus (See Fejl! Henvisningskilde ikke fundet.) or Touch Display.
5.2. Using PLC
In case using of PLC after connect need read register
the registers number (column 1) must be incremented for 1.
addressing changes no require.
nilan@nilan.dk ● www.nilan.dk
20003
. If read data is equal to “-1” –
all of
Otherwise – register
30030066-NILAN - CTS700
Date: 20180420
Modbus User Guide
Responsible: AKO
20010008E – Standard document template
Nilan A/S ● Nilanvej 2 ● 8722 Hedensted ● Danmark Tlf +45 76752500 ● Fax +45 76752525 ●
System
Boards amount
Address
Compact P
1
Compact P - 1
Compact P + GEO
2
Compact P – 1 GEO – 4
Compact P + AIR9
3
Compact P – 1 AIR9 – 4
Register Number
Slave ID
Function
R W Reset
Values
20000
1
Reset target board (reset key:
57005)
- +
57005 – must be write to restart system
20002
1
PLC clarification of addressing
+ -
Constant value: -1 or 65535
20003
1
PLC clarification of addressing
+ -
Constant value: 0
20004
1
Request saving data flash on both system (reset key: 48815)
- +
48815 – must be write for storing value in the system
Register Number
Slave ID
Function
R W Reset
Values 20100
1
Set ventilation on pause
+ +
0 - Off; 1 - On
Register Number
Slave ID
Function
R W Reset
Values
20102
1
Outdoor air filter Days between filter change
+ +
30 <-> 180
20103
1
Outdoor air filter Days to next filter change
+ -
30 <-> 180
Page 5/20
5.3. System Device Addressing
The CTS-700 can include up-to 3 boards. Due of this to access to them must be used following slave ID:
5.4. Console application
For testing a Modbus register model were implemented console application. It is called Modbus Master Console. The Modbus Master Console provide possibility to read and write data trough Modbus. It is support Modbus functions: 3, 4, 6, 16. For connection should be used Board IP address and Slave board ID according to System Device Addressing. Register number must be used with any changes of address.
6. Modbus Registers Description
6.1. Control registers
6.2. Ventilation
6.2.1. Filter settings
6.2.2. Outdoor air filter
nilan@nilan.dk ● www.nilan.dk
30030066-NILAN - CTS700
Date: 20180420
Modbus User Guide
Responsible: AKO
20010008E – Standard document template
Nilan A/S ● Nilanvej 2 ● 8722 Hedensted ● Danmark Tlf +45 76752500 ● Fax +45 76752525 ●
Register Number
Slave ID
Function
R W Reset
Values
20106
1
Extract air filter Days between filter change
+ +
30 <-> 180
20107
1
Extract air filter Days to next filter change
+ -
30 <-> 180
Register Number
Slave ID
Function
R W Reset
Values
20120
1
Operating mode
+ +
0 - Auto; 1 - Cooling; 2 ­Heating
Register Number
Slave ID
Function
R W Reset
Values 20140
1
Fan speed level 1 - supply air
+ -
20 <-> 100
20141
1
Fan speed level 1 - extract air
+ -
20 <-> 100
20142
1
Fan speed level 2 - supply air
+ -
20 <-> 100
20143
1
Fan speed level 2 - extract air
+ -
20 <-> 100
20144
1
Fan speed level 3 - supply air
+ -
20 <-> 100
20145
1
Fan speed level 3 - extract air
+ -
20 <-> 100
20146
1
Fan speed level 4 - supply air
+ -
20 <-> 100
20147
1
Fan speed level 4 - extract air
+ -
20 <-> 100
Register Number
Slave ID
Function
R W Reset
Values 20160
1
Low humidity level
+ +
15 <-> 45
20161
1
Fan speed at low humidity
+ +
101 - Level 1; 102 - Level 2; 103 - Level 3
20162
1
Fan speed at high humidity
+ +
102 - Level 2; 103 - Level 3; 104 - Level 4
20163
1
Timeout high humidity
+ +
0 <-> 180
20164
1
Average humidity
+ -
0 <-> 100
Register Number
Slave ID
Function
R W Reset
Values 20180
1
Allow active cooling
+ +
On/Off
20181
1
High fan speed when cooling
+ +
On/Off
20182
1
Fan speed when cooling
+ +
103 - Level 3; 104 - Level 4
20183
1
Minimum cooling supply temp (C)
+ +
5 <-> 30
20184
1
Cooling priority to hot water
+ +
On/Off
Page 6/20
6.2.3. Extract air filter
6.2.4. Operation mode
6.2.5. Fan speed settings
6.2.6. Humidity control
6.2.7. Active cooling settings
nilan@nilan.dk ● www.nilan.dk
30030066-NILAN - CTS700
Date: 20180420
Modbus User Guide
Responsible: AKO
20010008E – Standard document template
Nilan A/S ● Nilanvej 2 ● 8722 Hedensted ● Danmark Tlf +45 76752500 ● Fax +45 76752525 ●
Register Number
Slave ID
Function
R W Reset
Values
20200
1
Low fan speed at low outdoor temperature
+ +
0 - Off; 1 - On 20201
1
Below outdoor temperature
+ +
-20 <-> 10
20202
1
Fan speed at low outdoor temperature
+ +
101 - Level 1; 102 - Level 2;
Register Number
Slave ID
Function
R W Reset
Values 20220
1
CO2 level, fan speed 2
+ +
400 <-> 800
20221
1
CO2 level, fan speed 3
+ +
800 <-> 1200
20222
1
CO2 level, fan speed 4
+ +
1200 <-> 1600
Register Number
Slave ID
Function
R W Reset
Values
20240
1
After heating element type
+ - -
0 - None; 1 - Water ; 2 ­Electrical
20241
1
Min. supply air temperature (C)
+ +
5 <-> 30
20242
1
Max. Supply air temperature (C)
+ +
5 <-> 50
Register Number
Slave ID
Function
R W Reset
Values 20260
1
Wanted room temperature (C)
+ +
5 <-> 40
20261
1
Summer/winter mode switch (C)
+ +
5 <-> 30
20262
1
Offset Summer/winter switch (C)
+ +
0 <-> 10
20263
1
Master sensor indoor temperature
+ -
0 - T3; 1 - Te xt
20264
1
Temperature regulation deadband
+ +
0 <-> 10
20266
1
Bypass damper offset (C)
+ +
0 <-> 10
20267
1
Regulation deadband external room heating
+ +
0 <-> 10
Register Number
Slave ID
Function
R W Reset
Values 20280
1
Text room temperature ©
+ -
-40 <-> 160
20281
1
Tex t room temperature State
+ -
0 - Ok; 1 - Fault; 2 - Missing; 3
- Missing
20282
1
T1 outdoor air temperature (C)
+ -
-40 <-> 160
20283
1
T1 outdoor air temperature State
+ -
0 - Ok; 1 - Fault; 2 - Missing; 3
- Missing
Page 7/20
6.2.8. Ventilation at low outdoor temperature
6.2.9. CO2 control
6.2.10. After heating element
6.2.11. Temperature regulation
6.2.12. Temperature overview
nilan@nilan.dk ● www.nilan.dk
30030066-NILAN - CTS700
Date: 20180420
Modbus User Guide
Responsible: AKO
20010008E – Standard document template
Nilan A/S ● Nilanvej 2 ● 8722 Hedensted ● Danmark Tlf +45 76752500 ● Fax +45 76752525 ●
20284
1
T2 supply air temperature (C)
+ -
-40 <-> 160
20285
1
T2 supply air temperature State
+ -
0 - Ok; 1 - Fault; 2 - Missing; 3
- Missing
20286
1
T3 extract air, room temperature (C)
+ -
-40 <-> 160
20287
1
T3 extract air, room temperature State
+ -
0 - Ok; 1 - Fault; 2 - Missing; 3
- Missing
20288
1
T4 discharge air, after heat exchanger (C)
+ -
-40 <-> 160
20289
1
T4 discharge air, after heat exchanger State
+ -
0 - Ok; 1 - Fault; 2 - Missing; 3
- Missing
20290
1
T5 discharge air, after heat pump (C)
+ -
-40 <-> 160
20291
1
T5 discharge air, after heat pump State
+ -
0 - Ok; 1 - Fault; 2 - Missing; 3
- Missing
20292
1
T6 evaporator temperature (C)
+ -
-40 <-> 160
20293
1
T6 evaporator temperature State
+ -
0 - Ok; 1 - Fault; 2 - Missing; 3
- Missing
20294
1
T7 supply air temperature after­heater (C)
+ -
-40 <-> 160
20295
1
T7 supply air temperature after­heater State
+ -
0 - Ok; 1 - Fault; 2 - Missing; 3
- Missing
20296
1
T8 outdoor air before pre-heater
+ -
-40 <-> 160
20297
1
T8 outdoor air before pre-heater State
+ -
0 - Ok; 1 - Fault; 2 - Missing; 3
- Missing
20298
1
T9 temperature in water after heater
+ -
-40 <-> 160
20299
1
T9 temperature in water after heater State
+ -
0 - Ok; 1 - Fault; 2 - Missing; 3
- Missing
Register Number
Slave ID
Function
R W Reset
Values
20300
1
Frost protection
+ -
0 - None; 1 - External/Polar; 2 ­EHD; 3 - BAH
Register Number
Slave ID
Function
R W Reset
Values 20320
1
T8 temperature sensor
+ +
0 - Off; 1 - On
Register Number
Slave ID
Function
R W Reset
Values 20340
1
Start frost protection below (C)
+ +
1.0 <-> 5.0
20341
1
Set point for pre-heater T4 (C)
+ +
1.0 <-> 4.0
Register Number
Slave ID
Function
R W Reset
Values 20360
1
EHD offset (C)
+ +
0 <-> 10
20361
1
EHD hold time (min)
+ +
0 <-> 24
20362
1
EHD stabilisation (min)
+ +
1 <-> 10
Page 8/20
6.2.13. Frost protection or de-icing
6.2.13.1. External setting:
6.2.13.2. Polar setting:
6.2.13.3. EHD setting:
nilan@nilan.dk ● www.nilan.dk
30030066-NILAN - CTS700
Date: 20180420
Modbus User Guide
Responsible: AKO
20010008E – Standard document template
Nilan A/S ● Nilanvej 2 ● 8722 Hedensted ● Danmark Tlf +45 76752500 ● Fax +45 76752525 ●
Register Number
Slave ID
Function
R W Reset
Values 20380
1
BAH under temperature (C)
+ +
-10 <-> 10
20381
1
BAH above temperature (C)
+ +
15 <-> 35
20382
1
BAH regulation deadband (C)
+ +
0 <-> 10
Register Number
Slave ID
Function
R W Reset
Values 20400
1
Outdoor temperature for de-icing (C)
+ +
-10 <-> 1
20401
1
Maximum time de-icing (min)
+ +
10 <-> 90
20402
1
Minimum time between de-icing (min)
+ +
15 <-> 180 20403
1
Extract fan speed during de-icing
+ -
1 / 2 / 3 / 4
20404
1
Supply fan speed during de-icing
+ +
0 - Normal; 1 - Extract
Register Number
Slave ID
Function
R W Reset
Values 20420
1
Evaporator defrost T6
+ +
0 - Off; 1 - On
20421
1
Maximum time de-icing (min)
+ +
1 <-> 30
20422
1
Minimum time between de-icing (min)
+ +
1 <-> 180 20423
1
Start de-icing (C)
+ +
-15 <-> 0
20424
1
Stop de-icing (C)
+ +
0 <-> 15
Register Number
Slave ID
Function
R W Reset
Values 20440
1
Pause hot water production
+ +
0 - Off; 1 - On
20441
1
Pause duration days
+ +
1 <-> 180
Register Number
Slave ID
Function
R W Reset
Values 20460
1
Hot water set point (C)
+ +
10 <-> 60
20461
1
Frost protection hot water tank (C)
+ +
0 - Off; 1 - On
20462
1
El-supplement activated below (C)
+ +
30 <-> 65
20463
1
Scalding protection (C)
+ +
40 <-> 80
20464
1
Electrical supplement heater
+ +
0 - Off; 1 - On
Page 9/20
6.2.13.4. BAH setting:
6.2.14. De-icing heat exchanger
6.2.15. De-icing heat pump
6.3. Hot water production
6.3.1. DHW domestic hot water
6.3.1.1. Standby functions
6.3.1.2. Hot water settings
nilan@nilan.dk ● www.nilan.dk
30030066-NILAN - CTS700
Date: 20180420
Modbus User Guide
Responsible: AKO
20010008E – Standard document template
Nilan A/S ● Nilanvej 2 ● 8722 Hedensted ● Danmark Tlf +45 76752500 ● Fax +45 76752525 ●
Register Number
Slave ID
Function
R W Reset
Values 20480
1
Start anti legionella manuel
+ +
0 - Off; 1 - On
20481
1
Automatic anti legionella
+ +
0 - Off; 1 - Weekly; 2 - Monthly
20482
1
Day for antilegionella
+ +
1 <-> 28
20483
1
Time for antilegionella
+ +
0 <-> 23
Register Number
Slave ID
Function
R W Reset
Values 20500
1
Minimum time between start-up
+ -
0 <-> 10
20501
1
Time between stop and start-up
+ -
0 <-> 10
Register Number
Slave ID
Function
R W Reset
Values
20520
1
T11 top temperature in DHW water tank (C)
+ -
-40 <-> 160
20521
1
T11 top State in DHW water tank
+ -
0 - Ok; 1 - Fault; 2 - Missing; 3
- Missing
20522
1
T12 bottom temperature in DHW water tank (C)
+ -
-40 <-> 160
20523
1
T12 top State in DHW water tank
+ -
0 - Ok; 1 - Fault; 2 - Missing; 3
- Missing
Register Number
Slave ID
Function
R W Reset
Values 20540
4
Wanted water temperature (C)
+ +
10 <-> 45
20541
4
Frostprotection SHW water tank
+ +
0 - Off; 1 - On
20542
4
Minimum water temperature (C)
+ +
10 <-> 50
20543
4
Scalding protection T21 (C)
+ +
40 <-> 90
20544
4
Electrical supplement heater
+ +
0 - Off; 1 - On
20545
4
Maximum heat pump temperature T17 (C)
+ +
40 <-> 55
Register Number
Slave ID
Function
R W Reset
Values
20580
4
T21 top temperature in DHW water tank (C)
+ -
-40 <-> 160
Page 10/20
6.3.1.3. Antilegionella settings
6.3.1.4. Compressor settings hot water production
6.3.1.5. Temperature overview
6.3.2. SHW pre-heating domestic hot water
6.3.2.1. Hot water settings
6.3.2.2. Temperature overview
nilan@nilan.dk ● www.nilan.dk
Date: 20180420
Modbus User Guide
Responsible: AKO
20010008E – Standard document template
Nilan A/S ● Nilanvej 2 ● 8722 Hedensted ● Danmark Tlf +45 76752500 ● Fax +45 76752525 ●
20581
4
T21 top State in DHW water tank
+ -
0 - Ok; 1 - Fault; 2 - Missing; 3
- Missing
20582
4
T22 bottom temperature in DHW water tank (C)
+ -
-40 <-> 160
20583
4
T22 top State in DHW water tank
+ -
0 - Ok; 1 - Fault; 2 - Missing; 3
- Missing
Register Number
Slave ID
Function
R W Reset
Values 20584
4
Setpoint supplement heating (C)
+ +
10 <-> 45
20585
4
Maximum heat pump temperature T17 (C)
+ +
40 <-> 55
Register Number
Slave ID
Function
R W Reset
Values 20600
4
Pause central heating
+ +
0 - Off; 1 - On
20601
4
Pause duration (days)
+ +
1 <-> 180
20602
4
Power central heating
+ +
0 - Off; 1 - On
Register Number
Slave ID
Function
R W Reset
Values
20620
4
Cooling and heating at the same time
+ +
0 - Off; 1 - On
Register Number
Slave ID
Function
R W Reset
Values 20640
4
Setpoint supply flow temperature (C)
+ +
5 <-> 50
20641
4
Temperature regulation deadband (C)
+ +
0 <-> 5 20642
4
Maximum supply flow (C)
+ +
20 <-> 55
20643
4
Electrical supplement heater
+ +
0 - Off; 1 - On
20644
4
Delay electrical supplement heater (min)
+ +
0 <-> 60 20645
4
T13 brine before evaporator (C)
+ -
-40 <-> 160
20646
4
T13 brine before evaporator State
+ -
0 - Ok; 1 - Fault; 2 - Missing; 3
- Missing
20647
4
T14 brine after evaporator (C)
+ -
-40 <-> 160
20648
4
T14 brine after evaporator State
+ -
0 - Ok; 1 - Fault; 2 - Missing; 3
- Missing
20649
4
T16 before condenser (C)
+ -
-40 <-> 160
20650
4
T16 before condenser State
+ -
0 - Ok; 1 - Fault; 2 - Missing; 3
- Missing
6.4. Central heating
30030066-NILAN - CTS700
Page 11/20
6.3.3. DHW supplement domestic hot water
6.4.1. Standby functions
6.4.2. Cooling and heating at the same time
6.4.3. Temperature regulation GEO
nilan@nilan.dk ● www.nilan.dk
30030066-NILAN - CTS700
Date: 20180420
Modbus User Guide
Responsible: AKO
20010008E – Standard document template
Nilan A/S ● Nilanvej 2 ● 8722 Hedensted ● Danmark Tlf +45 76752500 ● Fax +45 76752525 ●
20651
4
T17 after condenser (C)
+ -
-40 <-> 160
20652
4
T17 after condenser State
+ -
0 - Ok; 1 - Fault; 2 - Missing; 3
- Missing
20653
4
T18 supply flow (C)
+ -
-40 <-> 160
20654
4
T18 supply flow State
+ -
0 - Ok; 1 - Fault; 2 - Missing; 3
- Missing
20655
4
T20 outdoor temperature (C)
+ -
-40 <-> 160
20656
4
T20 outdoor temperature State
+ -
0 - Ok; 1 - Fault; 2 - Missing; 3
- Missing
Register Number
Slave ID
Function
R W Reset
Values 20680
4
Setpoint supply flow temperature (C)
+ +
5 <-> 50
20681
4
Temperature regulation deadband (C)
+ +
0 <-> 5 20682
4
T16 before condenser (C)
Not working
20683
4
T16 before condenser State
Not working
20684
4
T17 supply flow outdoor unit (C)
+ -
-40 <-> 160
20685
4
T17 supply flow outdoor unit State
+ -
0 - Ok; 1 - Fault; 2 - Missing; 3
- Missing
20686
4
T18 supply flow buffer tank (C)
+ -
-40 <-> 160
20687
4
T18 supply flow buffer tank State
+ -
0 - Ok; 1 - Fault; 2 - Missing; 3
- Missing
20688
4
T20 outdoor temperature (C)
+ -
-40 <-> 160
20689
4
T20 outdoor temperature State
+ -
0 - Ok; 1 - Fault; 2 - Missing; 3
- Missing
20690
4
T23 evaporator (C)
+ -
-40 <-> 160
20691
4
T23 evaporator State
+ -
0 - Ok; 1 - Fault; 2 - Missing; 3
- Missing
Register Number
Slave ID
Function
R W Reset
Values 20700
4
Electrical supplement heater
+ +
0 - Off; 1 - On
20701
4
Maximum buffer temperature (C)
+ +
20 <-> 50
20702
4
Minimum buffer temperature (C)
+ +
10 <-> 50
20703
4
Delay electrical supplement heater
+ +
0 <-> 60
Register Number
Slave ID
Function
R W Reset
Values 20720
4
Regulation mode
+ +
0 - Setpoint; 1 - Curve
20721
4
Supply temperature (C) at -20 C outdoor temperature
+ +
0 <-> 50
20722
4
Supply temperature (C) at -10 C outdoor temperature
+ +
0 <-> 50
20723
4
Supply temperature (C) at 0 C outdoor temperature
+ +
0 <-> 50
20724
4
Supply temperature (C) at 10 C outdoor temperature
+ +
0 <-> 50
Page 12/20
6.4.4. Temperature regulation AIR
6.4.5. Buffer tank settings
6.4.6. Outdoor weather compensation
nilan@nilan.dk ● www.nilan.dk
30030066-NILAN - CTS700
Date: 20180420
Modbus User Guide
Responsible: AKO
20010008E – Standard document template
Nilan A/S ● Nilanvej 2 ● 8722 Hedensted ● Danmark Tlf +45 76752500 ● Fax +45 76752525 ●
20725
4
Supply temperature (C) at 20 C outdoor temperature
+ +
0 <-> 50 20726
4
Curve offset
+ +
-10 <-> 10
Register Number
Slave ID
Function
R W Reset
Values 20740
4
Hot water production wanted
+ -
0 - Off; 1 - SHW; 2 - DHW
20741
4
Compressor level (%)
+ +
0 <-> 100
Register Number
Slave ID
Function
R W Reset
Values 20760
4
Passive cooling
+ +
0 - Off; 1 - On
20761
4
Way of cooling
+ +
0 - Floor; 1 -Fan coils
Register Number
Slave ID
Function
R W Reset
Values 20780
4
Cooling
+ +
0 - Off; 1 - On
20781
4
Setpoint cooling (C)
+ +
5 <-> 25
Register Number
Slave ID
Function
R W Reset
Values
20800
4
Time between compressor start (min)
+ -
0 <-> 10 20801
4
Minimum off time (min)
+ -
0 <-> 10
20802
4
Compressor pressure at 0V
+ -
0 <-> 10
20803
4
Compressor pressure at 10V
+ -
0 <-> 10
20804
4
Compressor heating limit
+ -
0 <-> 100
20805
4
Min. control signal compressor (V)
+ -
0 <-> 10
20806
4
Max. control signal compressor (V)
+ -
0 <-> 10
Register Number
Slave ID
Function
R W Reset
Values 20820
4
Limitation above temp. (C)
+ +
0 <-> 30
20821
4
Limited (%)
+ +
20 <-> 100
Register Number
Slave ID
Function
R W Reset
Values 20840
4
Forced de-icing
+ +
0 - Off; 1 - On
20841
4
De-icing start temperature (C)
+ +
-10 <-> -1
20842
4
De-icing stop temperature (C)
+ +
-10 <-> 10
Page 13/20
6.4.7. Hot water production
6.4.8. Cooling with GEO
6.4.9. Cooling with AIR
6.4.10. Compressor settings GEO
6.4.11. Limited fan speed outdoor unit AIR
6.4.12. De-icing outdoor unit AIR
nilan@nilan.dk ● www.nilan.dk
30030066-NILAN - CTS700
Date: 20180420
Modbus User Guide
Responsible: AKO
20010008E – Standard document template
Nilan A/S ● Nilanvej 2 ● 8722 Hedensted ● Danmark Tlf +45 76752500 ● Fax +45 76752525 ●
20843
4
Maximum time de-icing (min)
+ +
5 <-> 60
20844
4
Minimum time between de-icing (min)
+ +
30 <-> 90
Register Number
Slave ID
Function
R W Reset
Values 20860
4
Minimum control signal (V)
+ -
0 <-> 10
20861
4
Maximum control signal (V)
+ -
0 <-> 10
Register Number
Slave ID
Function
R W Reset
Values
20880
4
Time between compressor start (min)
+ -
0 <-> 10 20881
4
Minimum off time compressor (min)
+ -
0 <-> 10
20882
4
Low outdoor temperature (C)
+ -
-30 <-> -1
20883
4
Compressor pressure at 0V
+ -
0 <-> 10
20884
4
Compressor pressure at 10V
+ -
0 <-> 10
20885
4
Compressor heating limit
+ -
0 <-> 100
20886
4
Minimum control signal compressor (V)
+ -
0 <-> 10
20887
4
Maximum control signal compressor (V)
+ -
0 <-> 10
Register Number
Slave ID
Function
R W Reset
Values
20900
1
Change language
+ +
0 – EN 32 33 44 47 72 117 128 - PL
Register Number
Slave ID
Function
R W Reset
Values 21500
1
Smart Grid Enable
+ + +
0 - Off; 1 - On
Register Number
Slave ID
Function
R W Reset
Values
Page 14/20
6.4.13. Fan settings AIR
6.4.14. Compressor settings AIR
6.5. General settings
6.5.1. Language
– DA – DE – FI – FR – IT
– NO
6.5.2. Smart Grid
6.5.3. Smart Grid Hot water settings
nilan@nilan.dk ● www.nilan.dk
30030066-NILAN - CTS700
Date: 20180420
Modbus User Guide
Responsible: AKO
20010008E – Standard document template
Nilan A/S ● Nilanvej 2 ● 8722 Hedensted ● Danmark Tlf +45 76752500 ● Fax +45 76752525 ●
21501
1
Raise hot water temperature (C)
+ +
0 <-> 10
21502
1
Electric supplement heater
+ +
0 - Off; 1 - On
Register Number
Slave ID
Function
R W Reset
Values
Register Number
Slave ID
Function
R W Reset
Values
21503
4
Raise central heating heating temp (C)
+ +
0 <-> 10 21504
4
Electric supplement heater
+ +
0 - Off; 1 - On
Register Number
Slave ID
Function
R W Reset
Values
21505
4
Raise central heating heating temp (C)
+ +
0 <-> 10
Register Number
Slave ID
Function
R W Reset
Values 21520
1
System power
+ +
0 - Off; 1 - On
Register Number
Slave ID
Function
R W Reset
Values 21580
1
Fire alarm auto reset
+ +
0 - Off; 1 - On
21581
1
Lock user settings
+ +
0 - Off; 1 - On
Register Number
Slave ID
Function
R W Reset
Values
21680
1
Product type
+ -
0 – Compact P 1 – Compact P Polar
21770
1
System state
+ -
0 – Auto 1 2 – Heating
21771
1
Supply fan speed
+ - % 21772
1
Extract fan speed
+ -
%
21773
1
Bypass damper
+ -
0 – Closed 1 – Open
21774
1
After heating element
+ - % 21775
1
Compressor state
+ -
0 – Off
Page 15/20
6.5.4. Smart Grid Central heating settings
6.5.4.1. At low electricity prices
6.5.4.2. At overcapacity of electricity
6.6. Information
6.5.5. Service
6.6.1. Compact P all device data
– Cooling
nilan@nilan.dk ● www.nilan.dk
30030066-NILAN - CTS700
Date: 20180420
Modbus User Guide
Responsible: AKO
20010008E – Standard document template
Nilan A/S ● Nilanvej 2 ● 8722 Hedensted ● Danmark Tlf +45 76752500 ● Fax +45 76752525 ●
100 – On
21776
1
Actual air humidity
+ - % 21778
1
CO2 level
+ -
ppm
21779
1
Fire alarm
+ -
0 – activated 1 – not activated
21780
1
User programme 1
+ -
0 – Off 1 – On
21781
1
User programme 2
+ -
0 – Off 1 – On
21782
1
User programme 2 out
+ -
0 – Off 1 – On
21783
1
Allow external cooling
+ -
0 – Off 1 – On
21784
1
Allow external heating
+ -
0 – Off 1 – On
21785
1
Anti legionella
+ -
0 – Off 1 – On
21786
1
Heat pump high pressure alarm
+ -
21787
1
Warm water sacrificial anode
+ -
1 – OK 3 – Failure
21788
1
Warm water electric supply
+ -
0 – Off 1 – On
21789
1
De-icing heat exchanger
+ - 21790
1
De-icing heat pump
+ -
21791
1
Four-way valve
+ -
0 – Open 1 – Closed
21792
1
Alarm
+ -
0 – Active 1 – Not active
21793
1
Heating or cooling blocked
+ - 21794
1
BAH brine pressostat
+ - 21795
1
Heat valve
+ - 21796
1
Hot water valve
+ -
Register Number
Slave ID
Function
R W Reset
Values 21839
4
Product type
+ -
8 – GEO
21840
4
System state
+ -
0 – Auto 1 2 – Heating
21841
4
Compressor level
+ - % 21842
4
Brine circulation pump
+ - % 21843
4
Central heating pump
+ -
%
21844
4
Three-way valve
+ -
0 – Heating 1 – Hot water production
21845
4
Allow external heating
+ -
0 – Allow 1 – Block
21846
4
Allow external cooling
+ -
0 – Allow 1 – Block
21847
4
Heating input
+ -
0 – None 1 – Yes
21848
4
Cooling input
+ -
0 – None 1 – Yes
Page 16/20
6.6.2. GEO all devices data
– Cooling
nilan@nilan.dk ● www.nilan.dk
30030066-NILAN - CTS700
Date: 20180420
Modbus User Guide
Responsible: AKO
20010008E – Standard document template
Nilan A/S ● Nilanvej 2 ● 8722 Hedensted ● Danmark Tlf +45 76752500 ● Fax +45 76752525 ●
21850
4
SHW supplement heater
+ -
0 – Off 1
21851
4
GEO supplement heater
+ -
0 – Off 1 – On
21852
4
Cooling circuit pressure
+ - 21853
4
Flow sensor
+ -
21854
4
High pressure alarm
+ -
0 – Failure 1 – Ok
21855
4
Low pressure alarm
+ -
0 – Failure 1 – Ok
21856
4
Brine pressure
+ -
0 – Failure 1 - Ok
Register Number
Slave ID
Function
R W Reset
Values 21899
4
Product type
+ -
9 – AIR
21900
4
System state
+ -
0 – Auto 1 2 – Heating
21901
4
Speed evaporator fan
+ - % 21902
4
Compressor level
+ - % 21903
4
Circulation pump outdoor unit
+ - % 21904
4
Central heating pump
+ -
%
21905
4
Three-way valve
+ -
0 – Floor heating 1 – Hot water
21906
4
Allow external heating
+ -
0 – Allow 1 – Block
21907
4
Allow external cooling
+ -
0 – Allow 1 – Block
21908
4
Heating input
+ -
0 – None 1 - Yes
21909
4
Cooling input
+ -
0 – None 1 – Yes
21911
4
SHW sacrificial anode
+ -
21912
4
SHW supplement heater
+ -
0 – Off 1 – On
21913
4
Buffer tank supplement heater
+ -
0 – Off 1 – On
21914
4
Cooling circuit pressure
+ - 21915
4
Flow sensor
+ -
Register Number
Slave ID
Function
R W Reset
Values 22490
1
Is any alarm or error present
+ -
0 - No, 1 – One or more
Page 17/20
– On
6.6.3. AIR9 all devices data
– Cooling
6.7. Alarm list
6.7.1. Alarm list control
nilan@nilan.dk ● www.nilan.dk
30030066-NILAN - CTS700
Date: 20180420
Modbus User Guide
Responsible: AKO
20010008E – Standard document template
Nilan A/S ● Nilanvej 2 ● 8722 Hedensted ● Danmark Tlf +45 76752500 ● Fax +45 76752525 ●
Warning or Error present
22491
1
Reset all warning and alarms.
- +
The value 48815 must be written to reset all events.
Register Number
Slave ID
Function
R W Reset
Values
22500
1, 4
ID000 - (EventNone) Undefined error
+ -
0 - Event isn't present 1 - Event is present
22501
1, 4
ID001 - (EventSystemStart) Unit start up
+ -
0 - Event isn't present 1 - Event is present
22502
1, 4
ID002 - (EventSystemStop) Unit has stopped
+ -
0 - Event isn't present 1 - Event is present
22505
1, 4
ID005 - (DbmRTDBVerisonNotEqual) Error in realtime database (RTDB)
+ -
0 - Event isn't present 1 - Event is present
22507
1, 4
ID007 - (EventFilterINLETWarning) Outdoor air filter must be changed
+ -
0 - Event isn't present 1 - Event is present
22508
1, 4
ID008 ­(EventFilterEXTHAUSTWarning) Extract air filter must be changed
+ -
0 - Event isn't present
22512
1, 4
ID012 ­(EventHeaterOverHeatAlarm) Safety active for electrical after heating surface
+ -
0 - Event isn't present 22514
1, 4
ID014 - (EventHeaterFrostWarning) Risk of ice in the water after heating surface
+ -
0 - Event isn't present
22515
1, 4
ID015 ­(EventHeaterFrostLongAlarm) Increased risk of ice after heating element
+ -
0 - Event isn't present 22516
1, 4
ID016 - (EventHeaterFrostAlarm) High risk of ice in the water after heating element
+ -
0 - Event isn't present
22518
1, 4
ID018 ­(EventCompressorOverSwitch) Too many compressor starts
+ -
0 - Event isn't present 22519
1, 4
ID019 - (EventProcInit) Software initialization failure
+ -
0 - Event isn't present 1 - Event is present
22520
1, 4
ID020 - (EventDefrostingTime) De­icing time exceeded
+ -
0 - Event isn't present 1 - Event is present
22521
1, 4
ID021 - (EventFireThermAlarm) Brandindgang aktiveret
+ -
0 - Event isn't present 1 - Event is present
22524
1, 4
ID024 ­(EventMainTaskTimeIsExceeded) Too long start-up of a function
+ -
0 - Event isn't present 22528
1, 4
ID028 - (EventSlaveFound) Slave device connected
+ -
0 - Event isn't present 1 - Event is present
22529
1, 4
ID029 - (EventSlaveLost) Lost communication with slave device
+ -
0 - Event isn't present 1 - Event is present
22531
1, 4
ID031 - (EventDefrostFail) Failure in de-icing
+ -
0 - Event isn't present 1 - Event is present
22541
1, 4
ID041 - (EventFrostProtection)
+ -
0 - Event isn't present
Page 18/20
6.7.2. Alarm list
1 - Event is present
in the water
1 - Event is present
1 - Event is present
1 - Event is present
1 - Event is present
1 - Event is present
1 - Event is present
nilan@nilan.dk ● www.nilan.dk
30030066-NILAN - CTS700
Date: 20180420
Modbus User Guide
Responsible: AKO
20010008E – Standard document template
Nilan A/S ● Nilanvej 2 ● 8722 Hedensted ● Danmark Tlf +45 76752500 ● Fax +45 76752525 ●
Frostprotection hot water tank active
1 - Event is present
22544
1, 4
ID044 - (EventAnodeFail) Failure on anode in domestic hot water tank
+ -
0 - Event isn't present 22545
1, 4
ID045 - (EventAntiLegionella) Start anti legionella
+ -
0 - Event isn't present 1 - Event is present
22546
1, 4
ID046 - (EventAntiLegionellaFail) Failure in anti legionella function
+ -
0 - Event isn't present 1 - Event is present
22547
1, 4
ID047 - (EventDefrostFailW) EventDefrostFailW
+ -
0 - Event isn't present 1 - Event is present
22549
1, 4
ID049 - (EventHeatHighPressure) Compressor high pressure alarm
+ -
0 - Event isn't present 1 - Event is present
22562
1, 4
ID062 - (EventRTDBParamWarning) Database errors
+ -
0 - Event isn't present 1 - Event is present
22565
1, 4
ID065 ­(EventSlaveTypeWasChangedWarn) Changed type of slave device
+ -
0 - Event isn't present
22566
1, 4
ID066 - (EventCompressHighPress) High pressure fault on the compressor
+ -
0 - Event isn't present 22567
1, 4
ID067 - (EventCompressLowPress) Lov pressure fault on the compressor
+ -
0 - Event isn't present 1 - Event is present
22568
1, 4
ID068 ­(EventNotOptimalSlaveRegulMode) Systems operation conflict !
+ -
0 - Event isn't present 22569
1, 4
ID069 - (Event_BAH_Leak) Leaking brine circuit BAH solution
+ -
0 - Event isn't present 1 - Event is present
22573
1, 4
ID073 ­(EventLow_T16_T17_atDefrost) T16 or T17 to low at de-icing
+ -
0 - Event isn't present 22574
1, 4
ID074 - (EventBrineLeak) Utrathed i GEO brinekredsen
+ -
0 - Event isn't present 1 - Event is present
22575
1, 4
ID075 - (EventDeviceError) Sensor fault
+ -
0 - Event isn't present 1 - Event is present
22577
1, 4
ID077 - (EventKlixonFault) Severe Klixon error
+ -
0 - Event isn't present 1 - Event is present
22578
1, 4
ID078 - (EventKlixonWarning) Klixon failure
+ -
0 - Event isn't present 1 - Event is present
22579
1, 4
ID079 ­(EventCompressHighPressWarning) High pressure warning
+ -
0 - Event isn't present
22580
1, 4
ID080 - (EventEvapLowTemperature) To low temper evaporator
+ -
0 - Event isn't present
22581
1, 4
ID081 - (EventDHW_HeaterWasOn) Electric supplement heater in hot water tank is on
+ -
0 - Event isn't present
22582
1, 4
ID082 - (EventDHW_HeaterWasOff) Electric supplement heater in hot water tank is off
+ -
0 - Event isn't present
22583
1, 4
ID083 - (EventBufferHeaterWasOn) Electric supplement heater central heating on
+ -
0 - Event isn't present
22584
1, 4
ID084 - (EventBufferHeaterWasOff)
+ -
0 - Event isn't present
Page 19/20
1 - Event is present
1 - Event is present
1 - Event is present
1 - Event is present
ature in the
1 - Event is present
1 - Event is present
1 - Event is present
1 - Event is present
1 - Event is present
1 - Event is present
nilan@nilan.dk ● www.nilan.dk
30030066-NILAN - CTS700
Date: 20180420
Modbus User Guide
Responsible: AKO
20010008E – Standard document template
Nilan A/S ● Nilanvej 2 ● 8722 Hedensted ● Danmark Tlf +45 76752500 ● Fax +45 76752525 ●
Electric supplement heater central heating off
1 - Event is present
22585
1, 4
ID085 ­(EventSlaveVersionIncompatible) Slave SW not the same as master
+ -
0 - Event isn't present
22586
1, 4
ID086 ­(EventSlaveRTDB_Incompatible) Slave RTDB not the same as master
+ -
0 - Event isn't present
22587
1, 4
ID087 ­(EventHeatPumpOvertemperature) No optimal regulation of slave
+ -
0 - Event isn't present 22588
1, 4
ID088 - (EventSGwasTurnedOn) The Smart Grid function was enabled
+ -
0 - Event isn't present 1 - Event is present
22589
1, 4
ID089 - (EventSGwasTurnedOff) The Smart Grid function was disable
+ -
0 - Event isn't present 1 - Event is present
22590
1, 4
ID090 ­(EventSGModeChangeToOption1) The Smart Grid Low Consumption Mode was activated.
+ -
0 - Event isn't present
22591
1, 4
ID091 ­(EventSGModeChangeToOption2) The Smart Grid Normal m activated.
+ -
0 - Event isn't present
22592
1, 4
ID092 ­(EventSGModeChangeToOption3) The Smart Grid Low electricity price mode was activated.
+ -
0 - Event isn't present
22593
1, 4
ID093 ­(EventSGM The Smart Grid Overcapacity of electricity mode was activated
+ -
0 - Event isn't present
Page 20/20
1 - Event is present
1 - Event is present
1 - Event is present
1 - Event is present
1 - Event is present
ode was
1 - Event is present
odeChangeToOption4)
1 - Event is present
nilan@nilan.dk ● www.nilan.dk