NILAN - CTS700
Modbus User Guide
30030066-NILAN - CTS700
20010008E – Standard document template
Nilan A/S ● Nilanvej 2 ● 8722 Hedensted ● Danmark Tlf +45 76752500 ● Fax +45 76752525 ●
Page 2/20
Table of Contents
1. Revision history .................................................................................................................. 4
2. References ......................................................................................................................... 4
3. Abbreviations and terms ...................................................................................................... 4
4. Introduction ....................................................................................................................... 4
5. General Provisions .............................................................................................................. 4
5.1. Addressing .................................................................................................................. 4
5.2. Using PLC ................................................................................................................... 4
5.3. System Device Addressing ............................................................................................ 5
5.4. Console application ..................................................................................................... 5
6. Modbus Registers Description ............................................................................................. 5
6.1. Control registers .......................................................................................................... 5
6.2. Ventilation ................................................................................................................... 5
6.2.1. Filter settings ....................................................................................................... 5
6.2.2. Outdoor air filter ................................................................................................... 5
6.2.3. Extract air filter .................................................................................................... 6
6.2.4. Operation mode .................................................................................................... 6
6.2.5. Fan speed settings ................................................................................................ 6
6.2.6. Humidity control ................................................................................................... 6
6.2.7. Active cooling settings ........................................................................................... 6
6.2.8. Ventilation at low outdoor temperature ................................................................... 7
6.2.9. CO2 control .......................................................................................................... 7
6.2.10. After heating element .......................................................................................... 7
6.2.11. Temperature regulation ....................................................................................... 7
6.2.12. Temperature overview ......................................................................................... 7
6.2.13. Frost protection or de-icing .................................................................................. 8
6.2.13.1.
6.2.13.2. Polar setting: ............................................................................................... 8
6.2.13.3. EHD setting: ................................................................................................ 8
6.2.13.4. BAH setting: ................................................................................................ 9
6.2.14. De-icing heat exchanger ...................................................................................... 9
6.2.15. De-icing heat pump ............................................................................................. 9
6.3. Hot water production ................................................................................................... 9
6.3.1. DHW domestic hot water ....................................................................................... 9
6.3.1.1. Standby functions .......................................................................................... 9
6.3.1.2. Hot water settings ......................................................................................... 9
6.3.1.3. Antilegionella settings .................................................................................. 10
6.3.1.4. Compressor settings hot water production ..................................................... 10
6.3.1.5. Temperature overview .................................................................................. 10
6.3.2. SHW pre-heating domestic hot water ................................................................... 10
6.3.2.1. Hot water settings ....................................................................................... 10
6.3.2.2. Temperature overview .................................................................................. 10
6.3.3. DHW supplement domestic hot water ................................................................... 11
6.4. Central heating .......................................................................................................... 11
6.4.1. Standby functions ............................................................................................... 11
6.4.2. Cooling and heating at the same time ................................................................... 11
6.4.3. Temperature regulation GEO ................................................................................ 11
6.4.4. Temperature regulation AIR ................................................................................. 12
6.4.5. Buffer tank settings ............................................................................................. 12
External setting: .......................................................................................... 8
nilan@nilan.dk ● www.nilan.dk
30030066-NILAN - CTS700
20010008E – Standard document template
Nilan A/S ● Nilanvej 2 ● 8722 Hedensted ● Danmark Tlf +45 76752500 ● Fax +45 76752525 ●
Page 3/ 20
6.4.6. Outdoor weather compensation ........................................................................... 12
6.4.7. Hot water production ........................................................................................... 13
6.4.8. Cooling with GEO ................................................................................................ 13
6.4.9. Cooling with AIR ................................................................................................. 13
6.4.10. Compressor settings GEO .................................................................................. 13
6.4.11. Limited fan speed outdoor unit AIR .................................................................... 13
6.4.12. De-icing outdoor unit AIR .................................................................................. 13
6.4.13. Fan settings AIR ................................................................................................ 14
6.4.14. Compressor settings AIR .................................................................................... 14
6.5. General settings ......................................................................................................... 14
6.5.1. Language ........................................................................................................... 14
6.5.2. Smart Grid ......................................................................................................... 14
6.5.3. Smart Grid Hot water settings .............................................................................. 14
6.5.4. Smart Grid Central heating settings ...................................................................... 15
6.5.4.1. At low electricity prices ................................................................................. 15
6.5.4.2. At overcapacity of electricity ......................................................................... 15
6.5.5. Service............................................................................................................... 15
6.6. Information ............................................................................................................... 15
6.6.1. Compact P all device data .................................................................................... 15
6.6.2. GEO all devices data ........................................................................................... 16
6.6.3. AIR9 all devices data ........................................................................................... 17
6.8. Alarm list .................................................................................................................. 17
6.8.1. Alarm list control................................................................................................. 17
6.8.2. Alarm list .......................................................................................................... 18
nilan@nilan.dk ● www.nilan.dk
20010008E – Standard document template
Nilan A/S ● Nilanvej 2 ● 8722 Hedensted ● Danmark Tlf +45 76752500 ● Fax +45 76752525 ●
Added information about console application
Added registers: 20004, 20223
Programmable Logic Controller
1. Revision history
2. References
• Modbus protocol specification:
http://modbus.org/docs/Modbus_Application_Protocol_V1_1b3.pdf
• Modbus over TCP/IP:
http://modbus.org/docs/Modbus_Messaging_Implementation_Guide_V1_0b.pdf
Abbreviations and terms
3.
30030066-NILAN - CTS700
Page 4/20
4. Introduction
This document, the Modbus Model Guide, describe Modbus register model of NILAN CTS-700.
5. General Provisions
In this chapter described general provisions of using Modbus protocol on NILAN CTS-700.
Columns description:
1. Register Number – Contain address of register in Modbus. (See Using PLC).
2. Slave ID – Contain slave address of target board (See System Device Addressing).
3. Function – Short description of register value.
4. R – Read permission (“+” - Reading is allow, “-” - Reading is deny).
5. W – Write permission (“+” - Writting is allow, “-” - Writting is deny).
6. Reset – If marked with “+” value will be applied after restart of the system.
7. Value – Contain all possible value of the register. Some of the register, which has Function
“Apply value” must be write with specific key for applying of the parameter.
5.1. Addressing
Modbus client connect to a system using Modbus RTU over TCP/IP. It means that for connect to
the system client must establish connection to board's IP address to port 502
Board's IP address by default set to 192.168.5.107 and can be changed by Modbus (See Fejl!
Henvisningskilde ikke fundet. ) or Touch Display.
5.2. Using PLC
In case using of PLC after connect need read register
the registers number (column 1) must be incremented for 1.
addressing changes no require.
nilan@nilan.dk ● www.nilan.dk
20003
. If read data is equal to “-1” –
all of
Otherwise – register
30030066-NILAN - CTS700
20010008E – Standard document template
Nilan A/S ● Nilanvej 2 ● 8722 Hedensted ● Danmark Tlf +45 76752500 ● Fax +45 76752525 ●
Reset target board (reset key:
57005)
57005 – must be write to
restart system
PLC clarification of addressing
Constant value: -1 or 65535
PLC clarification of addressing
Request saving data flash on both
system (reset key: 48815)
48815 – must be write for
storing value in the system
Outdoor air filter Days between filter
change
Outdoor air filter Days to next filter
change
Page 5/ 20
5.3. System Device Addressing
The CTS-700 can include up-to 3 boards. Due of this to access to them must be used following
slave ID:
5.4. Console application
For testing a Modbus register model were implemented console application. It is called Modbus
Master Console. The Modbus Master Console provide possibility to read and write data trough
Modbus. It is support Modbus functions: 3, 4, 6, 16. For connection should be used Board IP
address and Slave board ID according to System Device Addressing. Register number must be
used with any changes of address.
6. Modbus Registers Description
6.1. Control registers
6.2. Ventilation
6.2.1. Filter settings
6.2.2. Outdoor air filter
nilan@nilan.dk ● www.nilan.dk
30030066-NILAN - CTS700
20010008E – Standard document template
Nilan A/S ● Nilanvej 2 ● 8722 Hedensted ● Danmark Tlf +45 76752500 ● Fax +45 76752525 ●
Extract air filter Days between filter
change
Extract air filter Days to next filter
change
0 - Auto; 1 - Cooling; 2 Heating
Fan speed level 1 - supply air
Fan speed level 1 - extract air
Fan speed level 2 - supply air
Fan speed level 2 - extract air
Fan speed level 3 - supply air
Fan speed level 3 - extract air
Fan speed level 4 - supply air
Fan speed level 4 - extract air
Fan speed at low humidity
101 - Level 1; 102 - Level 2;
103 - Level 3
Fan speed at high humidity
102 - Level 2; 103 - Level 3;
104 - Level 4
High fan speed when cooling
103 - Level 3; 104 - Level 4
Minimum cooling supply temp (C)
Cooling priority to hot water
Page 6/ 20
6.2.3. Extract air filter
6.2.4. Operation mode
6.2.5. Fan speed settings
6.2.6. Humidity control
6.2.7. Active cooling settings
nilan@nilan.dk ● www.nilan.dk
30030066-NILAN - CTS700
20010008E – Standard document template
Nilan A/S ● Nilanvej 2 ● 8722 Hedensted ● Danmark Tlf +45 76752500 ● Fax +45 76752525 ●
Low fan speed at low outdoor
temperature
Below outdoor temperature
Fan speed at low outdoor
temperature
101 - Level 1; 102 - Level 2;
After heating element type
0 - None; 1 - Water ; 2 Electrical
Min. supply air temperature (C)
Max. Supply air temperature (C)
Wanted room temperature (C)
Summer/winter mode switch (C)
Offset Summer/winter switch (C)
Master sensor indoor temperature
Temperature regulation deadband
Regulation deadband external room
heating
Tex t room temperature State
0 - Ok; 1 - Fault; 2 - Missing; 3
- Missing
T1 outdoor air temperature (C)
T1 outdoor air temperature State
0 - Ok; 1 - Fault; 2 - Missing; 3
- Missing
Page 7/ 20
6.2.8. Ventilation at low outdoor temperature
6.2.9. CO2 control
6.2.10. After heating element
6.2.11. Temperature regulation
6.2.12. Temperature overview
nilan@nilan.dk ● www.nilan.dk
30030066-NILAN - CTS700
20010008E – Standard document template
Nilan A/S ● Nilanvej 2 ● 8722 Hedensted ● Danmark Tlf +45 76752500 ● Fax +45 76752525 ●
T2 supply air temperature (C)
T2 supply air temperature State
0 - Ok; 1 - Fault; 2 - Missing; 3
- Missing
T3 extract air, room temperature (C)
T3 extract air, room temperature
State
0 - Ok; 1 - Fault; 2 - Missing; 3
- Missing
T4 discharge air, after heat
exchanger (C)
T4 discharge air, after heat
exchanger State
0 - Ok; 1 - Fault; 2 - Missing; 3
- Missing
T5 discharge air, after heat pump (C)
T5 discharge air, after heat pump
State
0 - Ok; 1 - Fault; 2 - Missing; 3
- Missing
T6 evaporator temperature (C)
T6 evaporator temperature State
0 - Ok; 1 - Fault; 2 - Missing; 3
- Missing
T7 supply air temperature afterheater (C)
T7 supply air temperature afterheater State
0 - Ok; 1 - Fault; 2 - Missing; 3
- Missing
T8 outdoor air before pre-heater
T8 outdoor air before pre-heater
State
0 - Ok; 1 - Fault; 2 - Missing; 3
- Missing
T9 temperature in water after heater
T9 temperature in water after heater
State
0 - Ok; 1 - Fault; 2 - Missing; 3
- Missing
0 - None; 1 - External/Polar; 2 EHD; 3 - BAH
Start frost protection below (C)
Set point for pre-heater T4 (C)
Page 8/ 20
6.2.13. Frost protection or de-icing
6.2.13.1. External setting:
6.2.13.2. Polar setting:
6.2.13.3. EHD setting:
nilan@nilan.dk ● www.nilan.dk
30030066-NILAN - CTS700
20010008E – Standard document template
Nilan A/S ● Nilanvej 2 ● 8722 Hedensted ● Danmark Tlf +45 76752500 ● Fax +45 76752525 ●
BAH under temperature (C)
BAH above temperature (C)
BAH regulation deadband (C)
Outdoor temperature for de-icing (C)
Maximum time de-icing (min)
Minimum time between de-icing
(min)
Extract fan speed during de-icing
Supply fan speed during de-icing
Maximum time de-icing (min)
Minimum time between de-icing
(min)
Pause hot water production
Frost protection hot water tank (C)
El-supplement activated below (C)
Electrical supplement heater
Page 9/ 20
6.2.13.4. BAH setting:
6.2.14. De-icing heat exchanger
6.2.15. De-icing heat pump
6.3. Hot water production
6.3.1. DHW domestic hot water
6.3.1.1. Standby functions
6.3.1.2. Hot water settings
nilan@nilan.dk ● www.nilan.dk
30030066-NILAN - CTS700
20010008E – Standard document template
Nilan A/S ● Nilanvej 2 ● 8722 Hedensted ● Danmark Tlf +45 76752500 ● Fax +45 76752525 ●
Start anti legionella manuel
Automatic anti legionella
0 - Off; 1 - Weekly; 2 - Monthly
Minimum time between start-up
Time between stop and start-up
T11 top temperature in DHW water
tank (C)
T11 top State in DHW water tank
0 - Ok; 1 - Fault; 2 - Missing; 3
- Missing
T12 bottom temperature in DHW
water tank (C)
T12 top State in DHW water tank
0 - Ok; 1 - Fault; 2 - Missing; 3
- Missing
Wanted water temperature (C)
Frostprotection SHW water tank
Minimum water temperature (C)
Scalding protection T21 (C)
Electrical supplement heater
Maximum heat pump temperature
T17 (C)
T21 top temperature in DHW water
tank (C)
Page 10/ 20
6.3.1.3. Antilegionella settings
6.3.1.4. Compressor settings hot water production
6.3.1.5. Temperature overview
6.3.2. SHW pre-heating domestic hot water
6.3.2.1. Hot water settings
6.3.2.2. Temperature overview
nilan@nilan.dk ● www.nilan.dk
20010008E – Standard document template
Nilan A/S ● Nilanvej 2 ● 8722 Hedensted ● Danmark Tlf +45 76752500 ● Fax +45 76752525 ●
T21 top State in DHW water tank
0 - Ok; 1 - Fault; 2 - Missing; 3
- Missing
T22 bottom temperature in DHW
water tank (C)
T22 top State in DHW water tank
0 - Ok; 1 - Fault; 2 - Missing; 3
- Missing
Setpoint supplement heating (C)
Maximum heat pump temperature
T17 (C)
Cooling and heating at the same
time
Setpoint supply flow temperature (C)
Temperature regulation deadband
(C)
Electrical supplement heater
Delay electrical supplement heater
(min)
T13 brine before evaporator (C)
T13 brine before evaporator State
0 - Ok; 1 - Fault; 2 - Missing; 3
- Missing
T14 brine after evaporator (C)
T14 brine after evaporator State
0 - Ok; 1 - Fault; 2 - Missing; 3
- Missing
T16 before condenser State
0 - Ok; 1 - Fault; 2 - Missing; 3
- Missing
6.4. Central heating
30030066-NILAN - CTS700
Page 11 /20
6.3.3. DHW supplement domestic hot water
6.4.1. Standby functions
6.4.2. Cooling and heating at the same time
6.4.3. Temperature regulation GEO
nilan@nilan.dk ● www.nilan.dk
30030066-NILAN - CTS700
20010008E – Standard document template
Nilan A/S ● Nilanvej 2 ● 8722 Hedensted ● Danmark Tlf +45 76752500 ● Fax +45 76752525 ●
T17 after condenser State
0 - Ok; 1 - Fault; 2 - Missing; 3
- Missing
0 - Ok; 1 - Fault; 2 - Missing; 3
- Missing
T20 outdoor temperature (C)
T20 outdoor temperature State
0 - Ok; 1 - Fault; 2 - Missing; 3
- Missing
Setpoint supply flow temperature (C)
Temperature regulation deadband
(C)
T16 before condenser State
T17 supply flow outdoor unit (C)
T17 supply flow outdoor unit State
0 - Ok; 1 - Fault; 2 - Missing; 3
- Missing
T18 supply flow buffer tank (C)
T18 supply flow buffer tank State
0 - Ok; 1 - Fault; 2 - Missing; 3
- Missing
T20 outdoor temperature (C)
T20 outdoor temperature State
0 - Ok; 1 - Fault; 2 - Missing; 3
- Missing
0 - Ok; 1 - Fault; 2 - Missing; 3
- Missing
Electrical supplement heater
Maximum buffer temperature (C)
Minimum buffer temperature (C)
Delay electrical supplement heater
Supply temperature (C) at -20 C
outdoor temperature
Supply temperature (C) at -10 C
outdoor temperature
Supply temperature (C) at 0 C
outdoor temperature
Supply temperature (C) at 10 C
outdoor temperature
Page 12/ 20
6.4.4. Temperature regulation AIR
6.4.5. Buffer tank settings
6.4.6. Outdoor weather compensation
nilan@nilan.dk ● www.nilan.dk
30030066-NILAN - CTS700
20010008E – Standard document template
Nilan A/S ● Nilanvej 2 ● 8722 Hedensted ● Danmark Tlf +45 76752500 ● Fax +45 76752525 ●
Supply temperature (C) at 20 C
outdoor temperature
Hot water production wanted
0 - Off; 1 - SHW; 2 - DHW
Time between compressor start
(min)
Compressor pressure at 0V
Compressor pressure at 10V
Min. control signal compressor (V)
Max. control signal compressor (V)
Limitation above temp. (C)
De-icing start temperature (C)
De-icing stop temperature (C)
Page 13/ 20
6.4.7. Hot water production
6.4.8. Cooling with GEO
6.4.9. Cooling with AIR
6.4.10. Compressor settings GEO
6.4.11. Limited fan speed outdoor unit AIR
6.4.12. De-icing outdoor unit AIR
nilan@nilan.dk ● www.nilan.dk
30030066-NILAN - CTS700
20010008E – Standard document template
Nilan A/S ● Nilanvej 2 ● 8722 Hedensted ● Danmark Tlf +45 76752500 ● Fax +45 76752525 ●
Maximum time de-icing (min)
Minimum time between de-icing
(min)
Minimum control signal (V)
Maximum control signal (V)
Time between compressor start
(min)
Minimum off time compressor (min)
Low outdoor temperature (C)
Compressor pressure at 0V
Compressor pressure at 10V
Minimum control signal compressor
(V)
Maximum control signal compressor
(V)
0 – EN
32
33
44
47
72
117
128 - PL
Page 14/ 20
6.4.13. Fan settings AIR
6.4.14. Compressor settings AIR
6.5. General settings
6.5.1. Language
– DA
– DE
– FI
– FR
– IT
– NO
6.5.2. Smart Grid
6.5.3. Smart Grid Hot water settings
nilan@nilan.dk ● www.nilan.dk
30030066-NILAN - CTS700
20010008E – Standard document template
Nilan A/S ● Nilanvej 2 ● 8722 Hedensted ● Danmark Tlf +45 76752500 ● Fax +45 76752525 ●
Raise hot water temperature (C)
Electric supplement heater
Raise central heating heating temp
(C)
Electric supplement heater
Raise central heating heating temp
(C)
0 – Compact P
1 – Compact P Polar
Page 15/ 20
6.5.4. Smart Grid Central heating settings
6.5.4.1. At low electricity prices
6.5.4.2. At overcapacity of electricity
6.6. Information
6.5.5. Service
6.6.1. Compact P all device data
– Cooling
nilan@nilan.dk ● www.nilan.dk
30030066-NILAN - CTS700
20010008E – Standard document template
Nilan A/S ● Nilanvej 2 ● 8722 Hedensted ● Danmark Tlf +45 76752500 ● Fax +45 76752525 ●
0 – activated
1 – not activated
Heat pump high pressure alarm
Warm water sacrificial anode
Warm water electric supply
0 – Active
1 – Not active
Heating or cooling blocked
0 – Heating
1 – Hot water production
Page 16/ 20
6.6.2. GEO all devices data
– Cooling
nilan@nilan.dk ● www.nilan.dk
30030066-NILAN - CTS700
20010008E – Standard document template
Nilan A/S ● Nilanvej 2 ● 8722 Hedensted ● Danmark Tlf +45 76752500 ● Fax +45 76752525 ●
Circulation pump outdoor unit
0 – Floor heating
1 – Hot water
Buffer tank supplement heater
Is any alarm or error present
Page 17/ 20
– On
6.6.3. AIR9 all devices data
– Cooling
6.7. Alarm list
6.7.1. Alarm list control
nilan@nilan.dk ● www.nilan.dk
30030066-NILAN - CTS700
20010008E – Standard document template
Nilan A/S ● Nilanvej 2 ● 8722 Hedensted ● Danmark Tlf +45 76752500 ● Fax +45 76752525 ●
Reset all warning and alarms.
The value 48815 must be
written to reset all events.
ID000 - (EventNone) Undefined
error
0 - Event isn't present
1 - Event is present
ID001 - (EventSystemStart) Unit
start up
0 - Event isn't present
1 - Event is present
ID002 - (EventSystemStop) Unit has
stopped
0 - Event isn't present
1 - Event is present
ID005 - (DbmRTDBVerisonNotEqual)
Error in realtime database (RTDB)
0 - Event isn't present
1 - Event is present
ID007 - (EventFilterINLETWarning)
Outdoor air filter must be changed
0 - Event isn't present
1 - Event is present
ID008 (EventFilterEXTHAUSTWarning)
Extract air filter must be changed
ID012 (EventHeaterOverHeatAlarm) Safety
active for electrical after heating
surface
0 - Event isn't present
22514
ID014 - (EventHeaterFrostWarning)
Risk of ice in the water after heating
surface
ID015 (EventHeaterFrostLongAlarm)
Increased risk of ice
after heating element
0 - Event isn't present
22516
ID016 - (EventHeaterFrostAlarm)
High risk of ice in the water after
heating element
ID018 (EventCompressorOverSwitch) Too
many compressor starts
0 - Event isn't present
22519
ID019 - (EventProcInit) Software
initialization failure
0 - Event isn't present
1 - Event is present
ID020 - (EventDefrostingTime) Deicing time exceeded
0 - Event isn't present
1 - Event is present
ID021 - (EventFireThermAlarm)
Brandindgang aktiveret
0 - Event isn't present
1 - Event is present
ID024 (EventMainTaskTimeIsExceeded) Too
long start-up of a function
0 - Event isn't present
22528
ID028 - (EventSlaveFound) Slave
device connected
0 - Event isn't present
1 - Event is present
ID029 - (EventSlaveLost) Lost
communication with slave device
0 - Event isn't present
1 - Event is present
ID031 - (EventDefrostFail) Failure in
de-icing
0 - Event isn't present
1 - Event is present
ID041 - (EventFrostProtection)
Page 18/ 20
6.7.2. Alarm list
1 - Event is present
in the water
1 - Event is present
1 - Event is present
1 - Event is present
1 - Event is present
1 - Event is present
1 - Event is present
nilan@nilan.dk ● www.nilan.dk
30030066-NILAN - CTS700
20010008E – Standard document template
Nilan A/S ● Nilanvej 2 ● 8722 Hedensted ● Danmark Tlf +45 76752500 ● Fax +45 76752525 ●
Frostprotection hot water tank active
ID044 - (EventAnodeFail) Failure on
anode in domestic hot water tank
0 - Event isn't present
22545
ID045 - (EventAntiLegionella) Start
anti legionella
0 - Event isn't present
1 - Event is present
ID046 - (EventAntiLegionellaFail)
Failure in anti legionella function
0 - Event isn't present
1 - Event is present
ID047 - (EventDefrostFailW)
EventDefrostFailW
0 - Event isn't present
1 - Event is present
ID049 - (EventHeatHighPressure)
Compressor high pressure alarm
0 - Event isn't present
1 - Event is present
ID062 - (EventRTDBParamWarning)
Database errors
0 - Event isn't present
1 - Event is present
ID065 (EventSlaveTypeWasChangedWarn)
Changed type of slave device
ID066 - (EventCompressHighPress)
High pressure fault on the
compressor
0 - Event isn't present
22567
ID067 - (EventCompressLowPress)
Lov pressure fault on the compressor
0 - Event isn't present
1 - Event is present
ID068 (EventNotOptimalSlaveRegulMode)
Systems operation conflict !
0 - Event isn't present
22569
ID069 - (Event_BAH_Leak) Leaking
brine circuit BAH solution
0 - Event isn't present
1 - Event is present
ID073 (EventLow_T16_T17_atDefrost) T16
or T17 to low at de-icing
0 - Event isn't present
22574
ID074 - (EventBrineLeak) Utrathed i
GEO brinekredsen
0 - Event isn't present
1 - Event is present
ID075 - (EventDeviceError) Sensor
fault
0 - Event isn't present
1 - Event is present
ID077 - (EventKlixonFault) Severe
Klixon error
0 - Event isn't present
1 - Event is present
ID078 - (EventKlixonWarning) Klixon
failure
0 - Event isn't present
1 - Event is present
ID079 (EventCompressHighPressWarning)
High pressure warning
ID080 - (EventEvapLowTemperature)
To low temper
evaporator
ID081 - (EventDHW_HeaterWasOn)
Electric supplement heater in hot
water tank is on
ID082 - (EventDHW_HeaterWasOff)
Electric supplement heater in hot
water tank is off
ID083 - (EventBufferHeaterWasOn)
Electric supplement heater central
heating on
ID084 - (EventBufferHeaterWasOff)
Page 19/ 20
1 - Event is present
1 - Event is present
1 - Event is present
1 - Event is present
ature in the
1 - Event is present
1 - Event is present
1 - Event is present
1 - Event is present
1 - Event is present
1 - Event is present
nilan@nilan.dk ● www.nilan.dk
30030066-NILAN - CTS700
20010008E – Standard document template
Nilan A/S ● Nilanvej 2 ● 8722 Hedensted ● Danmark Tlf +45 76752500 ● Fax +45 76752525 ●
Electric supplement heater central
heating off
ID085 (EventSlaveVersionIncompatible)
Slave SW not the same as master
ID086 (EventSlaveRTDB_Incompatible)
Slave RTDB not the same as master
ID087 (EventHeatPumpOvertemperature)
No optimal regulation of slave
0 - Event isn't present
22588
ID088 - (EventSGwasTurnedOn) The
Smart Grid function was enabled
0 - Event isn't present
1 - Event is present
ID089 - (EventSGwasTurnedOff) The
Smart Grid function was disable
0 - Event isn't present
1 - Event is present
ID090 (EventSGModeChangeToOption1)
The Smart Grid Low Consumption
Mode was activated.
ID091 (EventSGModeChangeToOption2)
The Smart Grid Normal m
activated.
ID092 (EventSGModeChangeToOption3)
The Smart Grid Low electricity price
mode was activated.
ID093 (EventSGM
The Smart Grid Overcapacity of
electricity mode was activated
Page 20/ 20
1 - Event is present
1 - Event is present
1 - Event is present
1 - Event is present
1 - Event is present
ode was
1 - Event is present
odeChangeToOption4)
1 - Event is present
nilan@nilan.dk ● www.nilan.dk