nilan CTS700-TOUCH, Compact P Air, Compact P Polar Air Installation Instructions Manual

INSTALLATION INSTRUCTIONS
CTS700-TOUCH
BY NILAN
Compact P / Compact P Polar - AIR (English)
Version 2.30 - 14.08.2018
TABLE OF CONTENTS
afety
S
Heat pump domestic hot water ................................................................................................................................................................................................................. 5
Heat pump for central heating.................................................................................................................................................................................................................... 5
Disposal............................................................................................................................................................................................................................................................................................. 6
Ventilation system .................................................................................................................................................................................................................................................. 6
Heatpump .......................................................................................................................................................................................................................................................................... 6
General information
Introduction.................................................................................................................................................................................................................................................................................. 7
Unit type........................................................................................................................................................................................................................................................................................... 7
Product description ................................................................................................................................................................................................................................................ 7
The external unit..................................................................................................................................................................................................................................................... 10
Overview of temperature sensors ..................................................................................................................................................................................................... 11
Dimensional drawing ......................................................................................................................................................................................................................................... 12
Pipe diagram ............................................................................................................................................................................................................................................................... 13
Accessories................................................................................................................................................................................................................................................................................14
Electrical preheating element for frost protection.......................................................................................................................................................... 14
Water heating element incl. regulation .........................................................................................................................................................................................14
Electrical heating element ........................................................................................................................................................................................................................... 14
Pollen filter.....................................................................................................................................................................................................................................................................14
EM box ................................................................................................................................................................................................................................................................................ 14
CO2 sensor..................................................................................................................................................................................................................................................................... 14
Safety group.................................................................................................................................................................................................................................................................15
Safety features ........................................................................................................................................................................................................................................................15
Flexible silencing...................................................................................................................................................................................................................................................... 15
Trolley................................................................................................................................................................................................................................................................................. 15
SHW hot water tank ............................................................................................................................................................................................................................................ 15
Installation
Installing the internal unit......................................................................................................................................................................................................................................... 16
Transport into the dwelling ........................................................................................................................................................................................................................ 16
Positioning of unit.................................................................................................................................................................................................................................................. 16
Installing the external unit........................................................................................................................................................................................................................................17
Installation transport of external unit.............................................................................................................................................................................................17
Sound data......................................................................................................................................................................................................................................................................18
Installing the external unit .......................................................................................................................................................................................................................... 19
Fixing of external unit to substrate.................................................................................................................................................................................................... 20
Foundation..................................................................................................................................................................................................................................................................... 20
Condensate drain ...................................................................................................................................................................................................................................................21
Electrical installation
Safety.................................................................................................................................................................................................................................................................................. 22
Connections overview....................................................................................................................................................................................................................................... 22
User panel....................................................................................................................................................................................................................................................................................23
Touch panel .................................................................................................................................................................................................................................................................. 23
Dimensional drawing user panel............................................................................................................................................................................................................ 23
Placement of the Touch panel ................................................................................................................................................................................................................. 24
Mounting the wall bracket ........................................................................................................................................................................................................................... 25
Electrical connections unit....................................................................................................................................................................................................................................... 26
Safety.................................................................................................................................................................................................................................................................................. 26
Compact P AIR............................................................................................................................................................................................................................................................ 26
Electrical connections accessories................................................................................................................................................................................................................. 27
External electrical preheating element ........................................................................................................................................................................................ 27
2
Compact P / Compact P Polar - AIR (English)
Electric heating element................................................................................................................................................................................................................................. 28
ater heating element .................................................................................................................................................................................................................................... 29
W
CO 2 sensor ................................................................................................................................................................................................................................................................... 31
Cooker hood and EM box.................................................................................................................................................................................................................................33
SHW hot water tank............................................................................................................................................................................................................................................. 34
Other electrical connections.................................................................................................................................................................................................................................. 35
User selection 1........................................................................................................................................................................................................................................................ 35
User selection 2 ....................................................................................................................................................................................................................................................... 36
External room sensor......................................................................................................................................................................................................................................... 37
Fire protection .......................................................................................................................................................................................................................................................... 37
Common alarm........................................................................................................................................................................................................................................................... 38
External heat supply .......................................................................................................................................................................................................................................... 38
External underfloor heating control .................................................................................................................................................................................................39
Smart Grid ......................................................................................................................................................................................................................................................................39
Connecting EHD damper ................................................................................................................................................................................................................................ 40
BAH Geothermal heater ................................................................................................................................................................................................................................. 41
Active cooling function..................................................................................................................................................................................................................................... 42
BY NILAN
Plumbing installation
Condensate drain, internal unit.......................................................................................................................................................................................................................... 43
Important information...................................................................................................................................................................................................................................... 43
Hot water tank....................................................................................................................................................................................................................................................................... 44
Connection overview.......................................................................................................................................................................................................................................... 44
Connection .................................................................................................................................................................................................................................................................... 44
Hot water circulation.......................................................................................................................................................................................................................................... 45
Solar coil............................................................................................................................................................................................................................................................................ 45
Softened water ........................................................................................................................................................................................................................................................ 45
Central heating...................................................................................................................................................................................................................................................................... 46
Water connection overview, internal unit...................................................................................................................................................................................46
Connections overview, external unit................................................................................................................................................................................................ 47
Insulation of hoses from the outdoor unit...................................................................................................................................................................................47
Check list for the central heating system prior to start-up.................................................................................................................................... 48
Plumbing connections for accessories........................................................................................................................................................................................................ 49
Safety group ............................................................................................................................................................................................................................................................... 49
Safety group with anti-scald protection....................................................................................................................................................................................... 50
Hot water heating element (accessory) - duct mounted............................................................................................................................................ 51
Output chart, hot water heating element ...................................................................................................................................................................................52
Hot water tank........................................................................................................................................................................................................................................................... 53
Connecting to SHW hot water................................................................................................................................................................................................................... 54
Connecting to DHW hot water ................................................................................................................................................................................................................. 55
Ventilation mounting
Duct system.............................................................................................................................................................................................................................................................................. 56
Legislation...................................................................................................................................................................................................................................................................... 56
Ducts..................................................................................................................................................................................................................................................................................... 56
Unit.......................................................................................................................................................................................................................................................................................... 56
Extract air........................................................................................................................................................................................................................................................................57
Supply air......................................................................................................................................................................................................................................................................... 57
Roof stack....................................................................................................................................................................................................................................................................... 57
Initial regulation................................................................................................................................................................................................................................................................... 58
Important information...................................................................................................................................................................................................................................... 58
Initial regulation connectors...................................................................................................................................................................................................................... 58
Pressure fall diagram......................................................................................................................................................................................................................................... 58
Startup
Central heating...................................................................................................................................................................................................................................................................... 59
Filling with water..................................................................................................................................................................................................................................................... 59
Topping up water.................................................................................................................................................................................................................................................... 59
Check the particle filter .................................................................................................................................................................................................................................. 59
3
Troubleshooting
mergency operation.....................................................................................................................................................................................................................................................60
E
Emergency operation domestic hot water................................................................................................................................................................................. 60
Emergency operation central heating.............................................................................................................................................................................................61
Domestic hot water.......................................................................................................................................................................................................................................................... 62
Errors and solutions domestic hot water ....................................................................................................................................................................................62
Central heating...................................................................................................................................................................................................................................................................... 62
Failures and solutions central heating............................................................................................................................................................................................ 62
4
Compact P / Compact P Polar - AIR (English) BY NILAN
Safety
Starting the external unit
The external AIR unit is equipped with a compressor heater, which heats up the compressor prior to starting and in case of low outdoor temperatures. This facilitates start-up and extends the compressor’s service life.
CAUTION
The compressor heater must be left on for a minimum of 3 hours before starting the compressor for the first time.
Power supply
CAUTION
Always disconnect mains electricity to the unit if a fault occurs which cannot be rectified via the control panel.
CAUTION
If a fault occurs on the electricity-conducting elements of the unit, always contact an authorised electrical installer to rectify the fault.
CAUTION
Always disconnect mains electricity to the unit before opening the doors, e.g. for installation, inspection, cleaning and filter change.
Heat pump domestic hot water
CAUTION
Avoid direct contact with the heating system pipes in the heat pump as they can get very hot.
CAUTION
To protect the heat pump against damage, it is fitted with the following safety equipment:
• Electronic temperature monitoring
The heat pump must undergo suitable service inspections under applicable legislation and regulations to keep it in good condition and in compliance with safety and environmental requirements.
Responsibility for maintenance of the heat pump rests with the owner/user.
Heat pump for central heating
CAUTION
To secure the heat pump against damages, it is fitted with the following safety equipment
• Expansion systems for central heating and buffertank
• Safety valve for central heating and buffertank
• Low and high pressure switch for compressor
The heat pump must undergo suitable service inspections under applicable legislation and regulations to keep it in good condition and in compliance with safety and environmental requirements.
Responsibility for maintenance of the heat pump rests with the owner/user.
5
Disposal
V
entilation system
Heatpump
Nilan units mainly consist of recyclable materials. They should therefore not be d
isposed of with household refuse. Take them to your local recycling centre.
Concerning disposal of units with heat pumps, it is important to contact the local a
uthorities for information about correct handling of these. The heatpump contains the refrigerant R134a, which is harmful to the environment if not handled correctly.
6
Compact P / Compact P Polar - AIR (English)
BY NILAN
General information
Introduction
General information prior to installation
T
he following documents are supplied with the unit:
• Installation instructions/Software instructions
• User manual
• Wiring diagram
The instructions can be downloaded from the Nilan website: http://www.nilan.dk/en-gb/frontpage/ download
If you have further questions on unit installation after reading the instructions, contact your nearest Nilan distributor, who can be found on www.nilan.dk/en-gb/frontpage/download/dealers.
The purpose of these instructions is to give the installer advice on correct installation and maintenance of the unit.
The unit must be started up immediately after installation and connection to the duct system. In periods where the ventilation system is not in operation, humid air from the rooms may penetrate into the ducts and form a condensate. The condensate may leak out of the valves and damage furniture and floors. In addition, condensate may form inside the unit, damaging the unit's electronics and fans.
The unit is supplied fully tested and ready for operation.
Unit type
Product description
C
ompact P AIR is a ventilation unit with an integral heat exchanger that also produces hot water for
domestic use as well as central heating via an air/water heat pump.
Compact P is designed for air flows of up to 275 m 3 /h at 100 Pa external counter-pressure. Compact P XL can handle air flows up to 430 m 3 /h at 100 Pa external counter-pressure.
The ventilation part draws the humid, vitiated air out of the dwelling via the bathroom, WC, kitchen and utility room and introduces fresh air into the habitable rooms, i.e. living room, bedrooms and office. The cold outdoor air is heated up in the heat exchanger (heat recovery) by the warm extract air.
In addition to a (counterflow) heat exchanger, Compact P has an integral heat pump. The heat pump uses the heat remaining in the extracted air following heat recovery in the heat exchanger to produce hot water. In case of high hot water consumption, there is a 1.5 kW electric supplement heater in the hot water tank, which can also be used to heat the water.
In the winter, the heat pump can be used to heat the supply air (inlet air) during periods in which no domestic hot water is being produced. The supply air can be heated to 34 °C.
As it is a reversible heat pump, it can be used in summer to cool the supply (inlet) air. Compact P is able to cool the supply air by up to 10 °C. However, it will not function as an air conditioning unit, as it operates with a relatively low air change rate. Cooling of the supply air removes humidity from the indoor air, providing good comfort for persons in the dwelling, even if the indoor temperature is high. Compact P is able both to provide cooling and produce domestic hot water, so it could be said that the cooling of the supply air is "free of charge".
7
The energy-efficient and low-noise AIR air/water heat pump heats the home via floor heating or low-
emperature radiators. It extracts energy from the outside air and functions at temperatures as low as
t
-22 ºC. The heat pump has an electrical power supply to help it to function during very cold periods. The AIR unit has a reversible cooling circuit, which means that it can also be used to cool the home during the summer, using either the floor heating system or fan coils.
The AIR air/water heat pump can also be used to help produce hot water for domestic use, either by pre-heating the water in a buffer tank, or directly in a Compact P hot water tank, if bought with a solar coil.
8
The installation's internal unit
1 2
3
5 4
6
7
8
9
10
11
12
13
14
15
16
17
18
20
21
22
23
24
25
19
Compact P / Compact P Polar - AIR (English)
BY NILAN
Compact P: AIR:
1. Duct connections . Lid for filter changes
2
3. Control panel (touch screen), can be detached
4. Extract air filter
5. Outdoor air filter (this is the location for
pollen filter, if one is installed, as an additional purchase)
6. Counterflow heat exchanger
7. Heat pump for ventilation and hot water
8. Automatic control system
9. Fans
10. 100% bypass damper
20. 2 x 3 kW additional electrical central heating lements
e
21. 8 l expansion tank for central heating circuit
22. Safety valve and manometer for the central
heating circuit
23. 50 l buffer tank
24. Feed cock and particle filter for the central
heating circuit
25. Circulation pump for circulation to the
external unit
11. Preheating element (Polar version only)
12. LAN cable (for connection to router or PC)
13. Condensate drain with water trap
14. 180 l hot water tank (DHW)
15. 1.5 kW electrical supply heating (with overheating cut-out; which has to be pressed in again if activated)
16. Electronically monitored sacrificial anode
17. Solar coil (SOL version only)
18. Plumbing connections
19. Connection panel
9
The external unit
1. Evaporator element 2
. Ventilator
3. Condensate drain with integrated heating cable
4. Heat pump
5. Connectors to internal unit (liquid)
6. Communication to internal unit and electrical connection
10
Overview of temperature sensors
Compact P / Compact P Polar - AIR (English) BY NILAN
T2
T1
T3
T18
T6
T5
T4
T11
T12
T20
T23
T17
T16
Temperature sensors in the unit Temperature sensors outside
the unit
T1: Outdoor air T2: Supply air (inlet) T3: Extract air (outlet) T4: Extract air after heat exchanger T5: Condenser T6: Evaporator
T7: Supply air after heating element (accessory) T8: Outdoor air before preheating element (accessory) T9: On heating element (accessory) TExt: External temperature sensor (accessory)
Temperature sensor in internal unit
Temperature sensor in external unit
T18: Buffer tank (flow) T16: Before condenser (to
external unit) T17: After condenser (from external unit) T20: Outdoor temperature T23: Evaporator surface
Temperature sensors in the hot water tank
T11: Top of tank T12: Bottom of tank
11
Dimensional drawing
900
2065
120
179
399
141
337
160
160
119
97
328
160
610
1
2
3
4
962
1301
905
542
485
nternal unit:
I
Connections:
External unit:
1. Outdoor air
2. Supply air (inlet)
3. Extract air (outlet)
4. Discharge air
Internal unit weight: 257 kg External unit weight: 125 kg
All dimensions in mm
12
Pipe diagram
Compact P / Compact P Polar - AIR (English)
BY NILAN
1" fl ow
1" re turn
External AIR unit Internal AIR unit
18. Connection 1"
1
9. Flexible hose 1"
20. Shutoff valve
21. P1 circulation pump 130 mm
23. Electrical supply heating 2 x 3 kW
24. Temperature sensor T18 buffer tank (flow)
25. Flexible hose 10 mm
26. Automatic vent 3/8"
27. Expansion tank 8 litre
Buffe r tank
3/4" flow
3/4" return
28. Manometer 2
9. Safety valve 2.5 bar
30. Shutoff valve with particle filter
31. P2 circulation pump
37. Feed tap 1/2"
50. Temperature sensor T23 evaporator element
51. Temperature sensor T20 outdoor temperature
52. Temperature sensor T17 after condenser
53. Temperature sensor T16 before condenser
13
Accessories
E
lectrical preheating element for frost protection
In longer periods of sub-zero temperatures, the high-efficiency counterflow heat e
xchanger will ice up. To avoid icing, it is recommended that an electrical
preheating element is mounted.
The preheating element uses very little energy, but ensures efficient heat recovery without de-icing, thus achieving an overall saving in energy consumption.
Water heating element incl. regulation
A water heating element can be used to increase supply air temperature to the d
esired level. It is fitted in the supply air duct and must be connected to the
primary heat supply.
Supplied with a two-way regulating valve, temperature sensor and frost thermostat.
Electrical heating element
An electric heating element allows the supply air temperature to be raised to the d
esired level. Electric heating elements are supplied for mounting in the supply
air duct, and are provided with the necessary sensors.
Pollen filter
The unit is supplied as standard with filter sheet.
I
f persons in the dwelling suffer from a pollen allergy, there is an option for mounting a pollen filter in the outdoor air inlet to minimise the pollen in the indoor air.
EM box
With an EM box it is possible to divide the extract air between the kitchen and
athroom.
b
If the cooker hood is operating via the unit and is switched on, air extraction from the bathroom reduces slightly to allow sufficient air for the cooker hood to extract kitchen fumes.
CO2
14
sensor
The EM box has a metal filter which efficiently separates grease particles from the cooker hood air, thus protecting the unit.
Fitting a CO2 higher ventilation levels in the event of high CO2 level in the extracted air. CO levels can be programmed.
sensor means the ventilation speed can be pre-programmed to run
2
Safety group
Safety features
Compact P / Compact P Polar - AIR (English)
The safety group consists of:
T
he safety group, which is made of brass, consists of a stop valve with an integral non-return valve, a safety valve and drain cock. It can be installed directly beneath the hot water tank.
During periods with cooling ventilation, hot water in the tank can reach very high t
emperatures - up to 80 ºC.
A maximum temperature of up to 60 ºC can be set in the control system to prevent scalding, but active cooling is then limited.
To make full use of the cooling function, scalding protection should be fitted that mixes hot water with cold to bring the temperature down.
BY NILAN
If a solar panel is used to supplement hot water heating, scalding protection must be fitted.
Flexible silencing
To facilitate later servicing of the unit, we recommend fitting a flexible connection between the unit and the duct system.
Nilan's sound damping flexi-hose gives good sound damping both to the duct system and to roof stacks.
Trolley
A trolley makes it possible to lift the unit of the pallet without physical strain. T
he same trolley can be moved to wheel the unit around.
SHW hot water tank
If there is a large demand for hot water, a 250 litre hot water tank can be c
onnected. The hot water tank is heated by the central heating system’s heat pump and/or via solar panels. The water runs from the SHW tank, through the DHW tank in Compact P, before running into the domestic hot water supply.
15
Installation
Installing the internal unit
Transport into the dwelling
Compact P is supplied in one piece on a pallet, packed in cardboard.
It is fitted at the factory with 4 lifting straps, one for each top corner. This makes it possible to lift in the unit with a crane. When lifting the units with the supplied straps, these must be at an angle of max. 45° from the vertical.
Nilan also offers a lifting trolley, with which the unit can be lifted directly off the pallet and into the building. If the filter box is removed, the unit can be manoeuvred through an ordinary door.
Positioning of unit
ATTENTION
When setting up the unit, consideration must always be given to future servicing and maintenance.
It must be easy to replace filters, and it must be possible to perform tasks such as removing the heat exchanger, replacing fans and other components.
ATTENTION
A minimum free space in front of the unit of 60 cm is recommended.
It is important that the unit is level in order to achieve proper run-off from the condensate tray.
The unit should be positioned on a level and vibration-free substrate. In itself, the unit is low-noise and low-vibration, but even so, account must be taken of possible vibrations which could be transferred to building parts. We recommend maintaining a minimum 10 mm gap from building parts and other fixed equipment.
ATTENTION
For noise reasons, it is recommended that the unit is positioned with its rear panel against an outer wall.
At the lower rear and sides there are punched areas which can be clipped out. This avoids the necessity of cutting holes yourself.
The rear angle iron on the base frame can be removed, allowing the unit to be pushed up against the wall, thereby concealing the water connections.
16
ATTENTION
If a screen is mounted over the Compact P, it must be easy to dismantle this.
Compact P / Compact P Polar - AIR (English) BY NILAN
Installing the external unit
Installation transport of external unit
The external AIR unit is supplied film-wrapped and fastened with straps to a transport pallet.
If ground conditions allow, it is recommended that a lifting truck is used to move it.
ATTENTION
If the AIR unit is lifted in using a crane, please notice that the weight is not evenly distributed at the front and back.
17
Sound data
The sound from the AIR unit's external unit can be propagated depending on where it is sited relative to the building and the underlying surface, as well as on other surrounding objects and surfaces.
Q = 2 (free-standing) Q = 4 (against a wall) Q = 8 (in a corner)
Sound effect L
dB(A) 7/6 ºC - 30/35 ºC = 46 db(A) in accordance with EN14511, EN12102 and
WA
EN3743/1
Sound pressure L
dB(A) calculated in accordance with EN13487:2003:
pA
Distance in metres 1 2 6 10 21 Location factor 2 38 32 22 18 12 Location factor 4 41 35 26 21 15 Location factor 8 44 38 28 24 18
18
Compact P / Compact P Polar - AIR (English) BY NILAN
Installing the external unit
The external unit must always be installed on a firm, vertical and vibration-free surface and secured to some solid material if possible. Account must also be taken of the prevailing wind direction during the heating season, as the performance of the heat pump will be limited if the external unit is exposed to strong winds.
A windbreak can be installed if required. However, clearance distances as detailed below must be observed.
The following horizontal minimum distances to building components etc. must be observed in order to ensure optimum functioning of the heat pump.
L 50 cm
L 40 cm
L 40 cm
L 35 cm
If it is wished to install the AIR unit against the building, it is important not to install it close to any bedrooms due to the noise from the fan.
Locate the AIR unit in such a way that the intake air is drawn from the building's surface. This is because solar heating of the wall during the day and general heat loss from the building supplies additional energy to the air, which can then improve the efficiency of the heat pump. If the AIR unit is located with the extract directed at the wall, this will result in cold and damp air being blown against the building, adding extra energy to the air.
19
Fixing of external unit to substrate
629,90
45
962
542
If the external unit is placed in a windy area, e.g. on a roof, it will be necessary to fix it to the substrate using the 6 pre-drilled holes in the base.
347,45 65
Compressor unit
Foundation
ATTENTION
Place the AIR unit on a stable base, ideally a cast foundation.
926
932
Possible mounting holes
512
506
A
A
10
min. 250 mm
1301
Adjustable feet
ca.990 mm
80
150 mm
ca.595 mm
150 mm
20
Soakaway Electrical conduit min. 50mm
Compact P / Compact P Polar - AIR (English) BY NILAN
Condensate drain
During operation, condensate will form in the external unit’s evaporator, and which has to be run off to a drain. There is a tube measuring xx m connected to the evaporator’s condensation surface which leads to a drain.
The condensate drain must be insulated against frost, although it is supplied with a 1.5 m heating cable, which also helps to keep the condensate drain frost-free. The heating cable starts operating at outdoor temperatures of < 2 ºC.
ATTENTION
The condensate must be directed away in a way that avoids damaging the building.
If draining the condensate off into gravel, it must be ensured that it is run off into frost-free subsoil:
If the external unit is located close to the building, the condensate can be drained into a downpipe. Remember to install a water trap:
21
Electrical installation
Safety
ATTENTION
All work must be carried out by qualified personnel and in accordance with applicable legislation and regulations.
ATTENTION
It is important that power is disconnected when working with the unit's electrical components.
It is important to check that cables have not been damaged or pinched during connection and use.
Connections overview
21 3
a cb
9
4 5 6 7 8
1. Power cable to Compact P
2. Grommets (a: Transmission cable between internal unit and Compact P, b: Sensor T18 to buffer tank, c: 3-way valve for SHW tank)
3. Screw terminal for heating/cooling control (HEAT+COM: heating control. COM+COOL: cooling control)
4. Signal cable to AIR heat pump external unit
5. RJ45 plug for T21, T22 and anode in SHW tank
6. Plug for additional electric heating in SHW tank
7. Power cable for additional electric heating in buffer tank
8. Electrical connection cable for AIR heat pump internal unit + Compact
9. Electrical connection for AIR heat pump external unit
22
Compact P / Compact P Polar - AIR (English) BY NILAN
User panel
Touch panel
At delivery of the unit, the Touch panel is integrated in the front, but can be moved if you want to place it in e.g. the kitchen or living room.
ATTENTION
An ordinary LAN cable must be used, not a crow over cable, max 50 m.
If you want to crimp a RJ45 plug on to a cable, you must notice the following:
1. Green/white
2. Green
3. Orange/white
4. Empty
5. Empty
6. Orange
7. Brown/white
8. Brown Use RJ45 T568 type A plug and RJ45 crimping tool.
The touch user panel should be located in a prominent place to allow changes to be made to settings and for observing operational warnings or alarms.
Touch panel seen from below:
1. Locking clip
2. Power connection
3. USB stick
Dimensional drawing user panel
23
Placement of the Touch panel
elow is shown how the touch panel can be moved out of the unit. The following page shows how to
B mount the wall bracket for the Touch panel.
1. Unscrew the two screws at the top of the lid so it can be removed.
3. The Touch panel is lifted by pressing the lock clamp at t
he bottom.
2. At the top is the aperture plate that is intended to block the hole when the touch panel is removed.
4. Unscrew the cover and hang it next to the hole.
5. Unscrew the Touch panel wires from the circuit board, r
emove the wall bracket and mount it where the Touch
panel is to be hung.
7. Connect the touch panel as shown in the above iagram, see accompanying electrical diagram. The blue
d and blue/white wires should not be used.
24
6. Route the wire from the Touch panel down into the Compact P, where it is connected to the circuit board.
8. Fix the aperture plate to the cover in front of the circuit board. Re-attach the lid and secure with the two screws at the top, giving you a nice white surface.
Compact P / Compact P Polar - AIR (English)
BY NILAN
Mounting the wall bracket
he Touch panel can be mounted on the wall using the integral wall-bracket.
T
1. The wall bracket is fixed to the wall with two screws. 2.a. Insert the RJ45 plug into the wall bracket with the top f the plug aligned with the dotted line in the wall bracket,
o and with the RJ45 release tab facing away from the wall.
2.b. You can fit the RJ45 plug to the cable yourself. For
t
his purpose, a spacer is supplied.
2.c. The top of the RJ45 plug must be flush with the dotted
l
ine in the wall fitting. The spacer fits between the plug
and the cable relief bracket.
The spacer is attached to the LAN cable which is located behind the large door.
3. The cable may be routed down from the wall fitting or into a hole in the wall behind it.
4. Push the touch panel down over the wall bracket until a
lick is heard.
c The panel may be removed from the wall by pressing the locking clip.
5. The touch panel is ready for use.
25
Electrical connections unit
Safety
ATTENTION
All work must be carried out by qualified personnel and in accordance with applicable legislation and regulations.
ATTENTION
It is important that power is disconnected when working with the unit's electrical components.
It is important to check that cables have not been damaged or pinched during connection and use.
Compact P AIR
Heat pump, internal AIR unit Heat pump, external AIR unit
One electrical connection for the entire unit. 3 x 400, N, Earth, 16A
Safety switch
230V 50 Hz 16A
Safety switch
20m communications cable with plug connector for internal unit
26
T8
Compact P / Compact P Polar - AIR (English) BY NILAN
Electrical connections accessories
External electrical preheating element
If Compact P has not been purchased in the Polar version with integral preheating element, there is an option for purchasing an external electrical preheating element for subsequent installation.
The electric preheating element is mounted in the outdoor air duct before the unit with the necessary temperature sensor, and connected to an external power supply.
Min. 32 cm
7 8
1x230V ~ 50 Hz max. 16A
ATTENTION
It is important that the temperature sensor for the heating element is positioned at least 32 cm after the preheating element in order to achieve correct regulation.
The T8 outdoor air temperature sensor is positioned before the external preheating element and connected to the Compact P control system, to allow it to perform regulation via the outdoor air temperature. If it is not wished to regulate the functions via the outdoor air temperature, T8 may be deactivated in the software under the frost protection section:
The preheating element has a three-stage safety system against overheating.
1. There is a operating thermostat which regulates the heat and ensures that the supply air temperature does not fall below -1 °C
2. There is a max. thermostat, which shuts down the preheating element if the temperature rises above 50 °C
3. There is a manual safety thermostat, which shuts down the preheating element if the temperature rises above 100 °C
ATTENTION
When mounting the electric preheating element, there must be a safety gap of minimum 15 cm from any flammable material. The heating element must be insulated with a fire retardant insulation material, but the cover on the connection box must not be insulated.
A dimensional drawing is available under the section on the electric heating element.
27
Electric heating element
Min. 50 cm Min. 32 cm
If it is wished to control the supply air temperature, it will be necessary to fit a heating element.
The electrical post-heating element can be purchased for installation in the air injection channel. The required sensor and unit connector are included.
Trim the black RJ45 connector wire at the shrink-fit sleeve and connect the wire to the circuit board.
T7
1x230V ~ 50 Hz max. 16A
0-10V GND
Wire 1
Wire 2
0-10V
GND
T7
Wiring diagrams are supplied with the products. The heating element settings can be found on the display under menu option: Ventilation/Heating element.
The wires are routed alongside the duct and drawn through the bushing on top of the Compact P, routed down to the circuit board and mounted in accordance with the wiring diagram.
ATTENTION
When mounting the electric heating element, there must be a safety gap of minimum 15 cm from any flammable material. The heating element should be insulated with a Fire-retardant insulation material. The lid of the connection box should however not be insulated.
Dimensional drawing: Positioning options:
Ø160
28
Compact P / Compact P Polar - AIR (English) BY NILAN
Water heating element
If it is wished to control the supply air temperature, it will be necessary to fit a heating element.
A water heating element can be purchased for fitting in the supply air duct (inlet air), and comes with the necessary sensor and connection to the unit.
Connecting the sensors
T7
Min. 50 cm
B44
T9
B44
T7
T9
T7: Temperature sensor - T9: Temperature sensor heating element - B44: Frost protection
ATTENTION
When B44 frost protection is mounted, the jumper in the same connections should be removed.
The wires are routed alongside the duct and drawn through the bushing on top of the Compact P, routed down to the circuit board and mounted in accordance with the wiring diagram. Configure the heating element in the display, under menu item: Ventilation/Heating element.
29
Electrical connection for 2-way valve
1 . A 24V autotransformer is supplied and should be installed in a suitable position in the unit.
ATTENTION
The valve must not be connected to a 230V power supply.
The wires are routed alongside the duct and drawn through the bushing on top of the Compact P, routed down to the circuit board and mounted in accordance with the wiring diagram.
Dimensional drawing:
83
310
Ø 160
440
238
22
300
32
31
3/4" RG
3/4" RG
30
Compact P / Compact P Polar - AIR (English) BY NILAN
CO 2 sensor
It is possible to purchase a CO 2 sensor as an accessory if it is wished to control the ventilation level via the CO
level in the dwelling.
2
CAUTION
Always disconnect the power supply to the unit before opening the covers or working with electrical installations.
The T3 sensor is factory installed ( in the exhaust). Install the CO
1. Remove the T4 sensor in the heat exchanger. 2. Remove the heat exchanger by pulling the strap (do nut cut).
sensor in the unit as follows:
2
3. Pierce a hole into the foam over the crossbar, (where
the heat exchanger is positioned) to gain access to the recess in the top cover.
5. Install the CO 2 sensor in the top cover, using self-
threading screws (Included in the CO
sensor kit).
2
4. Route the wire from the CO 2 sensor through this cavity.
6. Route the wire from the CO routing to the automatic mechanism. Then secure wire using zip ties.
sensor through the cable
2
31
7. Reinstall heat exchanger. R
emember to reinstall the T4 sensor.
Route the wire from the CO
sensor to the circuit board and connect it as shown below:
2
Connect the three wires as follows:
G
ND: Blue Out: Black 24V: Brown
32
Compact P / Compact P Polar - AIR (English) BY NILAN
Cooker hood and EM box
There are several benefits from connecting the cooker hood to the home’s ventilation system. Firstly, there is full heat recovery of heat from cooking.
Secondly, the unit is able to provide balance in the ventilation. If the cooker hood does not run via the ventilation and if the house is new and airtight, use of the cooker hood will create a negative pressure in the home, minimising the suction effect from the cooker hood and also creating smoke problems, for instance if a wood-burning stove or open fire is installed and in use. By running the cooker hood via the unit, the unit can increase the supply air as the volume of extract air from cooker hood operation goes up. In this way, a balance can be maintained in the home, and the cooker hood will retain its full suction power.
In the case of ventilation of a large home/building, with more than one bathroom, there may be problems creating sufficient air capacity for the cooker hood. In these cases, an EM box will be an ideal addition, as it minimises the extract air from the other high-humidity rooms for the short period that the cooker hood is in use, and in this way ensures sufficient air for extraction via the cooker hood.
ATTENTION
If the cooker hood is connected to the ventilation system, it is important that it is fitted with a good grease filter and that this can be regularly cleaned.
User selection 1
User selection 2
EM box
The potential free contact for the cooker hood is connected to user selection 1 or 2, which are programmed in the unit's software under the section ‘General settings’. User selection 2 is chosen if an EM box is to be installed.
33
SHW hot water tank
1. 2.
he SHW hot water tank is connected to Compact P AIR connection panel as shown below. The SHW
T tank has its own power supply via a Schuko plug.
1. RJ45 plug for transmitting top temperature (T21), bottom temperature (T22) and anode monitoring in the SHW tank.
2. Plug for control of additional electric heating in the SHW tank.
34
Schuko plug
1x230V 50Hz 10A
Compact P / Compact P Polar - AIR (English)
BY NILAN
Other electrical connections
U
ser selection 1
It is possible to override the unit's functions via an external signal from a potential free contact
The User selection function can be used for many purposes, e.g. in the case of a wood burning stove or open fire. Initial settings of the ventilation system should be set up with a slight underpressure, so that humidity in the air is not forced into the building elements. This is of course a disadvantage when lighting a wood burning stove, as smoke will enter the room. You can use a dry contact to configure one of Fan stages (e.g. fan stage 4) to run with a slight over-pressure instead, to push the smoke through the chimney as intended.
Connection to CTS700 control system:
Potential free contact
User selection 1 is programmed in the unit's software under General settings. See the options in the
oftware instructions.
S
35
User selection 2
s with User selection 1, it is also possible with User selection 2 to override the unit's functions via an
A external signal from a potential free contact. The difference is that by activating User selection 2, the control system also transmits an output signal.
User selection 2 has the higher priority and is therefore used for cooker hood operation if a cooker hood is connected to the ventilation system. Normally fan speeds 3 or 4 are set for cooker hood operation. The output signal can be used for connecting an EM box or external damper which is to assume a particular setting during cooker hood operation.
There are many other uses for User selection 2 which we shall not discuss further in these instructions.
Connections:
Potential free contact
Output signal
36
Compact P / Compact P Polar - AIR (English)
BY NILAN
External room sensor
f the unit is not intended to be controlled on the basis of the ambient temperature measured by the
I exhaust air at T3, an external room sensor can be connected.
The room sensor should be positioned in the room that should serve as reference for the entire house.
Use NTC sensor (product number 23995).
Fire protection
fire thermostat or external fire automatic can be connected. It must be a joined signal, when it is
A broken the Compact P register it as a fire and stop the unit.
Note! If the unit is connected to external fire automatic, you set the software: General Settings/ S
ervice/Auto reset for external fire alarm to "On".
37
Common alarm
f the unit is located in a place where access is poor or infrequent, and if the control panel is also located
I here, it may be hard to observe any alarms.
An external alarm in the form of a light or acoustic signal, etc., can be connected to the unit.
External heat supply
ompact P is able to control an external room heating such as electric radiators or a floor heating
C system.
The room temperature is monitored by the Compact P, which block the external heating supply when there is no need for heating. If Compact P cannot achieve the desired room temperature through the ventilation, the external heating supply is released until the room temperature is in the desired level.
The external heat supply is connected via relay 8, and set in the touch-display under the menu: Ventilation-/Temperature regulation
A maximum effect of 500W can be connected (Compact P Polar need to have a transfer relay mounted).
38
Smart Grid
A
B
2.
3.
1.
Compact P / Compact P Polar - AIR (English)
BY NILAN
External underfloor heating control
o avoid the heat pump producing heat when there is no need for it, it is advisable to connect the
T underfloor heating control on the telestats to AIR/GEO.
A screw terminal is mounted on the connections panel for controlling heating/cooling. Remove the jumper on HEAT and COM and connect the signal from the underfloor heating control here. Closed contact set: heating required! Open contact set: no heating required!
Smart Grid
I
f you wish to run Smart Grid, you will need to update to Software version xx and connect the Smart
Grid modem to Compact P, as shown.
The Smart Grid signal is connected to the LC circuit board in the Compact P, which will also control AIR and GEO, if connected. Connect the signal directly, without resistance, as these are pre-installed in the cable.
1. Remove the white plate. 2. Route the wires from the SG through the hole in the top of the unit.
3. Connect the wires: SG-A: black, SG-B: red, GND: blue
Smart Grid is programmed in the unit's software under General settings. See the options in the
oftware Instructions.
S
39
Connecting EHD damper
To conduct outdoor air down through a geothermal pipe in the ground makes good sense. The air is heated during the winter and cooled in the summer by the ground.
But passing outdoor air through such a geothermal system may not be the best idea in the spring and autumn, but taking it directly through a roof vent is recommended.
The CTS700 control system has a built-in function that measures whether the geothermal pipe or roof vent provides the best option for air intake.
It measures the outdoor temperature during a stabilising period from the geothermal pipe and roof vent respectively. The measurement indicates where it is best to direct the outdoor air. CTS700 sets the EHD damper to the best option, and continues ventilation for a set period, referred to in the program as holding time.
The EHD damper is connected via relay 7 and set on the display menu item: Ventilation / Frost protection or de-icing / Frost protection.
EHD
ATTENTION
Damper, geothermal pipe and roof vent are not supplied by Nilan.
ATTENTION
When using a geothermal pipe, the "Low ventilation a low outdoor temperature" feature cannot be used.
40
Compact P / Compact P Polar - AIR (English) BY NILAN
BAH Geothermal heater
A geometric preheater has two functions:
1. It acts as frost protection in the winter, heating up the outdoor air and protecting the unit against icing up
2. It can then be used to cool down outdoor air in the summer, supplying cooled air to the home
The heater is set on the display under: Ventilation/frost-protection or de-icing
18
T8
11
16
18
Pdiff.
T8
11. Condensation drain
12. Shut-off valves
13. Particle filter
14. Filling and drain cocks
15. Safety valve
16. Bleed screw
17. Expansion tank
18. Pressostat
19. Circulation pump
19
13
12
12
1517
14
12
14
19
T8. Outdoor temperature sensor
ATTENTION
Circulation pump, heater and brine circuit are not supplied by Nilan.
41
Active cooling function
he AIR unit has a reversible cold circuit, which means that it can be used to actively cool the home,
T using either the underfloor heating system or fan coils.
Active cooling using the underfloor heating
There is an external temperature sensor connected to digital input 10. When the contact is closed, the AIR unit goes into cooling mode and cools the home down to a pre-set value. When the contact is broken again, the AIR unit returns to normal operation.
The external temperature sensor often has an infra-red sensor, which measures the temperature of the floor and stops the cooling function before condensation forms on the floor.
Active cooling using fan coils
T
here is an external temperature sensor connected to digital input 10. When the contact is closed, the AIR unit goes into cooling mode and cools the home down to a pre-set value. At the same time, relay output 10 is activated, which can control a three-way valve so that the water is directed out to fan coils instead of going into the floor. When the switch is deactivated, the AIR unit returns to normal operation.
42
Compact P / Compact P Polar - AIR (English) BY NILAN
Plumbing installation
Condensate drain, internal unit
Important information
Compact P is supplied with a reinforced 20 mm condensate drain hose with integral water trap.
ATTENTION
The condensate drain should be installed with an even fall of at least 1 cm per m to the nearest drain. Similarly, the overflow from the safety valve for the cold water supply must be led to a prominent drain.
ATTENTION
If the unit is assembled outside the climate screen, it is important to secure the condensate drain against icing. Frost protection of the unit is the installer's responsibility.
The connection of the water trap must be air-tight, otherwise air will be sucked into the unit and condensate will remain in the unit. This could lead to water damage if the condensate overflows the condensate tray and from there out of the unit.
After mounting the water trap, its function is tested as follows: Fill the condensate tray with water and operate the unit at the highest fan speed. Allow it to run for several minutes. Check that there is no water in the condensate tray when the test is finished (the unit must be connected to the duct system and the lid must be closed during the test).
The water trap may dry out and thus prevent water escaping from the condensate tray, as air will blow into the unit. The water trap should therefore be checked at regular intervals, especially in the summer, and filled with water as necessary.
Must not be cut
- this is a water trap
The water trap is integrated in the hose running from the condensate tray to the drain, and is fitted by the factory.
43
Hot water tank
110 248
Connection overview
Compact P front
1
4
240
3
310
200
2
Compact P back
Connections:
1. Connection for 3/4” circulation pipe
2. Hot water outlet 3/4"
3. Cold water intake 3/4"
4. Return supplementary coil 3/4"
5. Supply supplementary coil 3/4"
Supplementary coil is only standard on Compact P SOL models.
5
The coil is located in the bottom, and has an external diameter of 22 mm and is 8,500 mm long, equivalent to 0.6 m
2
.
Connection
ATTENTION
All work must be performed by qualified personnel and in accordance with relevant legislation and provisions.
Nilan's hot water tanks are double-enamelled, ensuring long life. The efficient foam insulation protects against unnecessary heat loss.
All connection nozzles for water have 3/4" thread and are located in the tank bottom.
The tank is also fitted with an electronically-monitored sacrificial anode that automatically displays a warning on the display when it needs changing.
44
Compact P / Compact P Polar - AIR (English) BY NILAN
CAUTION
Changing the anode when notified on the display is important. Failure to do so can cancel the guarantee on the hot water tank.
The tank is fitted with a 1.5 kW supplementary electrical heater deactivated by default and activated via the control panel if required.
ATTENTION
The supplementary heating must not be activated before the water tank is full of water.
Hot water circulation
If wished, hot water circulation can be established by fitting a non-return valve and a circulation pump for domestic water to the tank's circulation connector (1).
If hot water circulation is not established, the connector must remain closed with the factory-mounted shut-off plug.
ATTENTION
Hot water circulation can lead to a significant heat loss in the pipes, diverting a good proportion of the heat pump's output. To avoid this, circulation pipes and the hot water loop must be insulated with at least 30 mm mineral wool.
It is advisable to set a timer so that the circulation pump is not running constantly.
Solar coil
All Compact P SOL models have integral supplementary coil, see connections list.
The solar coil with a surface area of 0.6 m connected to other heat sources.
ATTENTION
If a solar collector or other heat source is connected to a Compact P model, it is recommended that a safety group is connected to the hot water outlet to secure against scalding.
2
is intended for solar heating systems, though it can also be
Softened water
If it is wished to soften water with salt in a Nilan hot water tank, the following must be observed:
• The hardness of the water must be at least -2° dh (proportion of alkaline earths 0,4 mmol/l)
• The conductivity must be between 13 mS/m og 150 mS/m (millisiemens per m)
• The pH value must be between 6.5 and 9.5
• The chlorine content must be under 250 mg Cl/l
If the above criteria are exceeded, the anode current will be too high, the anode will break down too quickly and the water will begin to smell bad.
CAUTION
Demineralised water (double ion exchange) must not be used as the tank will corrode very rapidly. Demineralised water is also called totally desalinated water and deionised water.
45
Central heating
Water connection overview, internal unit
6
10
9
7
3
5
4
1
3
Front Front
8
1
2
560
425
275
270
2
4
1. Feed to central heating, 3/4"
2. Return from central heating, 3/4"
3. Feed from external unit (hot), 1"
4. Return to external unit (cold), 1"
5. Circulation pump between external and internal units
6. Buffer tank
7. Filling and drain cock
8. Stop valve with particle filter
9. Safety valve (central heating)
10. Manometer (central heating)
46
110
175
205
332
962
542
111
Compact P / Compact P Polar - AIR (English) BY NILAN
Connections overview, external unit
432
197 69
55
165
Condensate drain
449
1
869
2
Hole for connections
View from below
1. Feed to internal unit (hot), fitted with 1" flexible hose
2. Return from internal unit (cold), fitted with 1" flexible hose
Insulation of hoses from the outdoor unit
It is important, that the brine hoses between the inside and outside units is well insulated, according to current standards. This is done to avoid heat loss and achieve good operation.
A detail that is often forgotten is the schrader valve in the outdoor unit. It is very important that it is also insulated.
CAUTION
If the brine hoses is not well insulated, the AIR heat pump will use significantly more energy and in worst case, there will not be enough heat in the house.
47
Check list for the central heating system prior to start-up
he check list is used when starting and delivering the system, and it should always be filled in. See the
T other sections in the manual for further information.
Electrical connection and controls Checked - date Notes
The power supply is connected and secured in
ccordance with the wiring diagram and manual
a
The control panel is installed in a place that can easily
e seen by the user
b
Central heating circuit Checked - date Notes
The central heating circuit is sealed
The central heating circuit has been vented after filling
Central heating circuit pressure, overpressure Bar
The opening pressure for the central heating circuit’s
afety valve is correct
s
The circulation pump is rated correctly for the
nstallation
i
The circulation pump is in constant operation or is
ontrolled by the heating pump
c
48
Compact P / Compact P Polar - AIR (English) BY NILAN
Plumbing connections for accessories
Safety group
CAUTION
A safety device must be connected to the hot water tank.
When water is heated to 60 °C, it expands by 2%. A pressure tank could burst without a safety valve keeping excess water out. The safety valve should therefore drip during warming up.
Installation:
The following should be remembered during installation: a. The double nut is attached to the water heater’s cold water pipe so that the arrows are pointing in towards the water heater (in the direction of the flow). The joint with the water heater is sealed using a threaded washer. b. The joint between the double nut and the system is sealed using fibre packing. c. The rubber ring seal (the O-ring) is fitted to the unit so that it can function as a seal between the safety valve and the unit in such a way that the valve is locked.
The end of the overflow pipe must be visible, and it must be able to run out safely via the drain.
ATTENTION
As water expands as it heats up, the safety valve will drip.
ATTENTION
It is up to the installation engineer to tell the customer where the safety valve is and how it works, and also that it must be regularly checked at least twice a year in order to prevent incrustation.
49
Safety group with anti-scald protection
The control system contains as standard a temperature limit for domestic hot water of 65 ºC. This setting prevents users from scalding themselves when the hot tap is turned on.
It also means that when Compact P is in cooling mode, cooling will stop when the domestic hot water reaches a temperature of 65 ºC.
If the cooling requirement is higher than this, the temperature limit may be raised to 80 ºC, but in this case an anti-scald device must be mounted under the hot water tank, to prevent users from scalding themselves when turning on the hot tap.
The anti-scald device mixes hot water with cold water, thus bringing down the temperature and avoiding scalding. This will extend the period for which Compact P can perform cooling.
CAUTION
If a solar panel is connected to the hot water tank, an anti-scald device must be mounted.
2
1
8
6
7
5
1. Hot water from the hot water tank
2. Cold water to the hot water tank
3. Stop cock cold water
4. Pressure relief valve (6 bar or 10 bar)
5. The overflows from the safety valve are led to a prominent drain
6. Cold water supply
7. Domestic hot water for the dwelling
8. Mixing valve for domestic hot water for the dwelling (can be set between 35 - 60 ºC)
3
4
50
Compact P / Compact P Polar - AIR (English) BY NILAN
Hot water heating element (accessory) - duct mounted
CAUTION
Connection of the hot water heating element must be carried out by an authorised plumber.
CAUTION
If the control unit is installed outdoors or external to the building, it must be protected against frost.
The heater is for duct connection, and cannot be integrated into the unit.
The heater is supplied as an accessory and consists of: Heating element with temperature sensor T9 and frost thermostat B44, actuator, regulator valve and autotransformer.
Must be activated via the control system.
The system should be connected, bled and checked for leaks. The system can then be started. Check and clean the sediment trap after flushing the system appropriately.
2
3
Supply
4
1
Return
1. Water heating element
2. Actuator and regulation valve: Danfoss AME 140/24V 0-10V signal, 2-way valve VZ2 Kv0,4 (supplied by Nilan) Kvs-value MUST be checked compared to the supply.
Differential pressure: 0.1-0.6 bar
At a supply temperature of 60°C, a cooling effect of 20°C over the heater is calculated at maximum heat output.
3. Bleed valve (not supplied by Nilan)
4. Sediment trap (not supplied by Nilan)
51
IMPORTANT, concerning Danfoss Actuator type AME 140:
Mandatory procedure for refitting the actuator:
1. Disconnect from mains electricity. Remove actuator cover.
2. Disengage the gear by holding the button under the housing in while screwing the spindle upwards as far as it will go (counter-clockwise)
3. Fit actuator and reconnect mains electricity.
4. Switch DIP switch no. 1 to ON and then OFF.
5. Automatic calibration will run for up to 6 minutes. (The diode will flash during calibration before becoming constant).
6. Fit actuator cover.
Output chart, hot water heating element
Water side Air side
Temperature supply/return
[°C] [m3/h] [kPa] [kW] [m3/h] [°C] [°C] [Pa]
40/30
60/40
Flow Pressure loss Output Air volume Temperature
before HWH*
0,04 0,85 0,52 100 16 31,1 2
0,06 1,25 0,64 135 16 29,8 3
0,08 2,18 0,87 210 16 28,1 6
0,11 4,65 1,32 400 16 25,7 17
0,17 9,62 1,98 800 16 23,2 53
0,19 11,9 2,23 1000 16 22,5 77
0,04 0,69 0,94 100 16 43,5 2
0,05 1,00 1,16 135 16 41,1 3
0,07 1,75 1,58 210 16 38,0 6
0,10 3,70 2,40 400 16 33,5 17
0,16 7,66 3,58 800 16 29,1 53
0,18 9,48 4,03 1000 16 27,8 77
Temperature after HWH*
Pressure loss over HWH*
0,03 0,40 1,06 100 16 47,0 2
0,04 0,58 1,30 135 16 44,2 3
0,05 1,00 1,76 210 16 40,5 6
70/40
0,08 2,09 2,64 400 16 35,3 17
0,11 4,25 3,9 800 16 30,3 53
0,13 5,24 4,38 1000 16 28,8 77
*(HWH) hot water heating element
52
Compact P / Compact P Polar - AIR (English)
BY NILAN
Hot water tank
he AIR unit can be connected to an external hot water tank (SHW) and to the hot water tank in the
T Compact P (DHW). A three-way valve, which can be purchased as an accessory, is required.
Buffe r tank
1" fe ed
1" re turn
External AIR unit Internal AIR unit
3/4" feed
3/4" return
SHW ( DHW)
18. Connection 1" 1
9. Flexible hose 1"
20. Stop valve
21. P1 circulation pump 130 mm
23. Additional electric heating 2 x 3 kW
24. Temperature sensor T18 buffer tank (feed)
25. Flexible hose 10 mm
26. Automatic vent 3/8"
27. Expansion tank 8 litre
28. Manometer 2
9. Safety valve 2.5 bar
30. Stop valve with particle filter
31. P2 circulation pump
37. Filling cock 1/2"
43. 3-way valve
44. Temperature sensor T21 hot water tank top
45. Temperature sensor T22 hot water tank bottom
50. Temperature sensor T23 evaporator surface
51. Temperature sensor T20 outdoor temperature
52. Temperature sensor T17 after condenser
53. Temperature sensor T16 before condenser
53
Connecting to SHW hot water
The cold water from the domestic supply is pre-heated in the AIR heat pump’s SHW tank to 45 °C (factory setting 40 °C), after which it is fed to the DHW tank in the Compact P, where it is heated to the desired feed temperature.
AIR unit seen from the front
5
AIR unit seen from below DHW tank SHW tank seen from below
4
6 7
1
3
AIR unit seen from below DHW tank
2
SHW tank seen from the front
1. Feed to the heat pump coil in the SWH tank from the AIR heat pump's 3-way valve
2. Return from the heat pump coil in the SHW tank to the AIR heat pump
3. Connection of domestic cold water supply
4. Flow of pre-heated domestic water from the SHW tank to the DHW tank in the Compact P
5. Flow of domestic hot water from the DHW tank
6. Connection of hot water circulation
7. Phial pocket
54
Compact P / Compact P Polar - AIR (English) BY NILAN
Connecting to DHW hot water
If the demand for domestic hot water is so great that the Compact P unit's heat pump cannot cope, the AIR unit can be connected to the DHW tank’s solar coil to help heat up the domestic hot water.
4
1
DHW tankAIR unit seen from belowAIR unit seen from the side
3
2
1. Supply flow to the solar coil in the DHW water tank form the AIR heat-pump
2. Return flow from the solar coil in the DHW water tank to the AIR heat-pump
3. Connection to the supply of cold water
4. Supply flow of domestic hot water from the DHW water tank
55
Ventilation mounting
Duct system
Legislation
ATTENTION
All work must be carried out by qualified personnel and in accordance with applicable legislation and regulations.
Ducts
There are two systems for transporting air round the building.
Spiral tubes
Spiral tubes are metal ducts which are cut to size with an angle grinder, screwed together with bends and manifolds and laid out in accordance with the working drawing. The duct pipes are typically laid at the rafter ends and fixed with perforated band or suspended with suspension band. Avoid unnecessary bends in the ducting.
To avoid noise transmission, where sound is transmitted from room to room, a sound damper must be mounted in each room.
The ducts must be insulated to avoid heat loss and condensation. In some cases this can be avoided if the ducts are led through the ordinary insulation or inside the climate screen.
NilAIR tubes
NilAIR tubes are a flexible system which is easy to mount. The tubes are easily cut to size with a hobby knife and laid according to the working drawing without use of bends and manifolds. A manifold box is installed after the unit and the tubes run from this out to the various rooms.
With NilAIR tubes it is unnecessary to mount sound dampers in each room, as there is no risk of noise transmission.
If the tubes are led outside the climate screen they must be insulated to avoid heat loss and condensation. This is easier than with spiral tubing, as NilAIR tubes are easier to lead through ordinary insulation.
NilAIR tubes are more flexible than spiral tubing and can therefore be laid in places where ordinary spiral tubing would be impossible.
Unit
Nilan recommends mounting a flexible connection between the unit and the duct system.
This is to avoid oscillations from the unit being transmitted to the duct system, but also to ease future servicing where it is necessary to move the unit.
Nilan offers flexible silicing, which, apart from providing a flexible connection between the unit and the duct system, also dampen the passage of sound from the unit to the duct system.
Flexible silencing are insulated for condensation, but it may be necessary to insulate them further to meet local requirements for duct system insulation.
56
Compact P / Compact P Polar - AIR (English)
BY NILAN
Extract air
xhaust valves are mounted in the moisture-generating rooms and strategically placed where they can
E extract the moisture air most effectively.
Moisture-generating rooms:
• Bathroom
• Toilet
• Kitchen
• Utility room
Supply air
Supply air valves are mounted in habitable rooms and strategically positioned to give the minimum annoyance. For example, it is not recommended to mount incoming air valves over areas where people sit, as the air in some cases can be perceived as a draught.
Habitable rooms:
• Living room
• Kitchen-living room
• Bedroom
• Office
Roof stack
The roof inlet and outlet must be positioned and designed to limit pressure fluctuations in the ventilation system caused by wind impact, and also to prevent access by birds and other animals, and to ensure that the inlet and closed duct system are kept free of plant parts and foreign objects.
The air inlet must be located to minimise the risk of short-circuiting from the discharge air, having regard to the prevailing wind direction.
The air inlet should be placed a minimum of 0.5 m above the roof surface, but a minimum of 1 m over flat black roofs up to the underside of the inlet, to ensure that warm air is not drawn into the building in the summer. The air inlet should be located on the north or east sides of pitched roofs.
Sound damping should also be mounted between the unit and roof stacks to avoid noise annoyance to neighbours.
57
Initial regulation
2
4
1
3
Important information
ATTENTION
For the ventilation system to operate optimally, it is important that initial regulation is carried out correctly. We recommend having this done by experts.
It is important to measure the total supply (inlet) air and extract (outlet) air. The system must have a minimum vacuum, i.e. it must draw in more air out than in, to avoid humidity being pressed into the building construction.
Initial regulation connectors
The unit has initial regulation connectors for measuring the supply air (inlet air) and extract air (outlet air) volumes.
The graph can be used for roughly setting the main air volume for dry operation without condensation precipitation, and with approximately the same temperature for outdoor air and extract air.
On the extract air side (outlet air), the pressure drop dP4-3 [Pa] is measured between the connectors labelled 3 and 4. The air volume qv [m3/h] is read off on the graph.
On the supply air side (inlet air), the pressure drop dP2-1 [Pa] is measured between the connectors labelled 1 and 2. The air volume qv [m3/h] is read off on the graph.
ATTENTION
The capacity in the pressure drop diagram is based on a dry heat exchanger.
Pressure fall diagram
The measuring connectors are inside behind the top front panel.
58
Compact P / Compact P Polar - AIR (English) BY NILAN
Startup
Central heating
Filling with water
ATTENTION
Before starting the heat pump and the circulation pumps, the central heating circuit connected to the external unit must first be filled with water
Fill the central heating circuit with water via the feed cock until the correct water pressure is obtained. It is important that all circuits in the central heating system are open during filling.
ATTENTION
Ordinary water or all common types of antifreeze can be used
There is an automatic vent fitted to the buffer tank, which is activated when filling with water. Check that the cover on the vent is loose.
There is a Schrader valve fitted to the external unit's top hose connector for venting the connector between the internal and external units.
Once the central heating circuit has been filled to the correct water pressure, the circulation and heat pump can be started.
Topping up water
The water pressure must be carefully checked the first few days, even several times a day. It may be necessary to top up the water in the central heating circuit if the water pressure has dropped.
ATTENTION
It is important that the circulation and heating pump is switched off while topping up the water
The water pressure will stabilise after a few days, after which the checks can be reduced to once a month.
ATTENTION
If the central heating circuit requires topping up after the start-up phase, it should be checked for leaks
Check the particle filter
There may be some particulate matter in the central heating circuit, and the heating pump must be checked immediately after being put into operation.
The filter must be checked several times a day just after installation until it stays clean. With normal operation, it is enough to check the filter twice a year.
Cleaning the particle filter:
1. Switch off the heating pump on the control panel (Settings: Central heating / Standby functions / Turn off central heating)
2. Turn the shut-off valve to close off the circulation
3. Remove the filter and rinse until clean
4. Replace the filter
5. Turn the shut-off valve to open up the circulation
6. Switch the heating pump back on
59
Troubleshooting
Emergency operation
Emergency operation domestic hot water
If an error occurs in the controller or components in the Compact P, and the unit therefore stops, it will not be able to produce domestic hot water.
If the installer is not able to come right away or the error happens outside the opening hours, and you therefore cannot contact the installer, there is a possibility to get hot water by setting the unit into emergency mode.
The button for the emergency operation are located behind the large door
The emergency operation has three settings:
I - Auto: El-supplementation is controlled by the control in the unit
(standard setting)
0 - Off: El-supplementation is off and cannot be turned on again by the control in the unit
II - Manuel: El-supplementation is turned on, and cannot be turned off by the control in the unit (Don´t turn it on if there is no water in the tank)
60
CAUTION
In manual operation, the water temperature can achieve 75 °C, which can cause scalding, if you are not careful when you open the hot water.
Compact P / Compact P Polar - AIR (English) BY NILAN
Emergency operation central heating
If an error occurs in the controller or components in the AIR air/water heat pump, and the heat pump therefore stops, it will not be able to heat up the house by the central heating.
If the installer is not able to come right away or the error happens outside the opening hours, and you therefore cannot contact the installer, there is a possibility to heat up the house by setting the heat pump into emergency mode.
The buttoms for the emergency operation are located behind the large door.
ATTENTION
When the el-supplementation is in I or II the circulationpump must be in the same position.
The emergency operation for the el-supplementation has tree settings:
I - Auto: El-supplementation is controlled by the control in the unit
(standard setting)
0 - Off: El-supplementation is off and cannot be turned on again by the
control in the unit
II - Manuel: El-supplementation is turned on, and cannot be turned off by the
control in the unit
The emergency operation for the circulation pump has tree settings:
I - Auto: The circulation pump is controlled by the control in the unit
(standard setting)
0 - Off: The circulation pump is off and cannot be turned on again by the
control in the unit
II - Manuel: The circulation pump is on, and cannot be turned off by the
control in the unit
ATTENTION
In manual operation the supply flow temperature for the central heating can achieve 40 °C.
61
Domestic hot water
E
rrors and solutions domestic hot water
Probl em Possi ble cause Solut ion
The u nit produc es insuff icient do mestic ho t water The f ilters may be block ed so tha t insuffi cient air
s rea ching the unit.
i
This can occur if the fi lters are not chan ged
frequ ently enou gh.
This can occur if the un it has be en operat ing
durin g construc tion work and the filters h ave
becom e filled w ith dust and dirt.
Chang e the filt ers and, if necess ary, chan ge the
f
ilter change pe riod to a shorter Interval.
Central heating
Failures and solutions central heating
Error s Possibl e cause Solutio n
El-su pplementat ion is tu rned on m uch or al ways The h eat pump w ill not w ork effec tively, w hich
ay be due to va rious rea sons.
m
Make sure that there is no ice in the evap orator in
the o utdoor uni t. Ice pr events ai r from ge tting
throu gh. Make a manual d efrost.
AIR h as a large power co nsumption You should ex pect the electrici ty consump tion in
t
he fi rst year w ill be hi gher than estimate d.
It is quite nat ural, sin ce the ho use will dry out. T he
highe r humidity the firs t year me ans that it takes
more energy to heat up t he house.
It ca n also hap pen i the heat pum p is not running
optim ally for d ifferent reasons.
Check that the evaporato r in the outdoor u nit is
not b locked wit h leaves and other debris t hat may
preve nt air fro m getting through. Clean th e
evapo rator
Check the hoses between the outdo or unit a nd
indoo r unit is properly insulated to avoid heat
losse s.
Make sure that there is proper fl ow betwee n
outdo or unit an d indoor unit.
Make sure that there is no ice in the evap orator in
t
he ou tdoor unit . Ice pre vents air from get ting
throu gh. Make a manual d efrost.
Check that the evaporato r in the outdoor u nit is
not b locked wit h leaves and other debris t hat may
preve nt air fro m getting through. Clean th e
evapo rator
Check the hoses between the outdo or unit a nd
indoo r unit is properly insulated to avoid heat
losse s.
62
Make sure that there is proper fl ow betwee n
outdo or unit an d indoor unit.
Compact P / Compact P Polar - AIR (English)
BY NILAN
63
United Kingdom:
S L Services 25 St Leonards Road, Horsham RH13 6EH West Sussex
Tlf. +44 (0) 7919 444452
stuart315@aol.com www.nilanuk.com
Ireland:
Nilan Ireland Ballylahive, Abbeydorney
Tlf. +353 (0) 87 9798361
maurice@nilan.ie www.nilanireland.ie
Nilan A/S Nilanvej 2 DK-8722 Hedensted
Tlf. +45 76 75 25 00 Fax +45 76 75 25 25
nilan@nilan.dk www.nilan.dk
Document no.M32_Compact-P-AIR_GB
Nilan A/S disclaims all liability for errors and omissions in printed instructions - and for loss, damage or injury arising from the published material, whether this is due to errors or
inappropriate information in the material or other causes. Nilan A/S reserves the right to make changes to products and instructions without prior warning. All trademarks are the property of
Nilan A/S, and all rights are reserved.
Loading...