nilan Comfort 252 TOP, CTS150, Comfort 302 Top, Comfort 200 Top Installation Instructions Manual

INSTALLATION INSTRUCTIONS
CTS150 B
Y NILAN
Comfort 252 / 302 Top (English)
Version 2.03 - 07.07.2017
TABLE OF CONTENTS
afety
Warnings........................................................................................................................................................................................................................................................................................... 4
Power supply................................................................................................................................................................................................................................................................... 4
Disposal............................................................................................................................................................................................................................................................................................. 4
Ventilation system....................................................................................................................................................................................................................................................4
General information
Introduction.................................................................................................................................................................................................................................................................................. 5
General information prior to installation.........................................................................................................................................................................................5
Final inspection......................................................................................................................................................................................................................................................................... 5
How to set up the ventilation system.................................................................................................................................................................................................. 5
Unit type........................................................................................................................................................................................................................................................................................... 6
Product description..................................................................................................................................................................................................................................................6
Dimensional drawing ............................................................................................................................................................................................................................................. 7
Accessories................................................................................................................................................................................................................................................................................... 8
Electrical preheating element for frost protection.............................................................................................................................................................. 8
User option/cooker hood solution ..........................................................................................................................................................................................................8
Pollen filter F7................................................................................................................................................................................................................................................................ 8
Water trap...........................................................................................................................................................................................................................................................................8
Vibration absorbers.................................................................................................................................................................................................................................................8
Flexible silencing..........................................................................................................................................................................................................................................................9
Installation
Installation..................................................................................................................................................................................................................................................................................10
Placement of the unit ........................................................................................................................................................................................................................................ 10
Top unit ............................................................................................................................................................................................................................................................................. 10
Electrical installation
Electrical connections.................................................................................................................................................................................................................................................... 11
Safety.................................................................................................................................................................................................................................................................................. 11
Connection overview.......................................................................................................................................................................................................................................... 11
User panel....................................................................................................................................................................................................................................................................................12
CTS150 control-panel ...................................................................................................................................................................................................................................... 12
Connecting the user-panel .......................................................................................................................................................................................................................... 12
Electrical connection, unit......................................................................................................................................................................................................................................... 13
Supply.................................................................................................................................................................................................................................................................................. 13
Unit ........................................................................................................................................................................................................................................................................................ 13
Electrical connections assessories................................................................................................................................................................................................................. 14
User select/cooker hood solution ....................................................................................................................................................................................................... 14
External electrical preheating element ........................................................................................................................................................................................ 15
Plumping
Condensate drain................................................................................................................................................................................................................................................................ 16
Important information ..................................................................................................................................................................................................................................... 16
Connection bottom............................................................................................................................................................................................................................................... 17
Plumping connections for accessories........................................................................................................................................................................................................ 18
Water lock with ball (option)....................................................................................................................................................................................................................... 18
Ventilation installation
Duct system.............................................................................................................................................................................................................................................................................. 19
Legislation...................................................................................................................................................................................................................................................................... 19
Ducts..................................................................................................................................................................................................................................................................................... 19
Unit.......................................................................................................................................................................................................................................................................................... 19
Extract air........................................................................................................................................................................................................................................................................ 20
Supply air......................................................................................................................................................................................................................................................................... 20
2
Roof stack....................................................................................................................................................................................................................................................................... 20
I
nstallation example.............................................................................................................................................................................................................................................21
Balancing...................................................................................................................................................................................................................................................................................... 21
Important information...................................................................................................................................................................................................................................... 21
Balancing connectors......................................................................................................................................................................................................................................... 21
Pressure drop diagram .................................................................................................................................................................................................................................... 22
Software settings
User-panel.................................................................................................................................................................................................................................................................................. 23
Functions.......................................................................................................................................................................................................................................................................... 23
Alarms ................................................................................................................................................................................................................................................................................ 23
Settings.......................................................................................................................................................................................................................................................................................... 24
Installing of PC programme......................................................................................................................................................................................................................... 24
PC-setting tool .......................................................................................................................................................................................................................................................... 26
List of adjustable parameters ................................................................................................................................................................................................................. 27
Operation..................................................................................................................................................................................................................................................................................... 28
Bypass function........................................................................................................................................................................................................................................................ 28
Humidity control...................................................................................................................................................................................................................................................... 28
Replacing the filter................................................................................................................................................................................................................................................29
Comfort 252 / 302 Top (English)
BY NILAN
3
Safety
Warnings
Power supply
CAUTION
A
lways disconnect mains electricity to the unit if a fault occurs which cannot be rectified via the
control panel.
CAUTION
I
f a fault occurs on the electricity-conducting elements of the unit, always contact an
authorised electrical installer to rectify the fault.
CAUTION
A
lways disconnect mains electricity to the unit before opening the doors, e.g. for installation,
inspection, cleaning and filter change.
Disposal
Ventilation system
Nilan units mainly consist of recyclable materials. They should therefore not be d
isposed of with household refuse. Take them to your local recycling centre.
4
General information
Introduction
General information prior to installation
T
he following documents are supplied with the unit:
• Installation instructions/Software instructions
• User manual
• Wiring diagram
The instructions can be downloaded from the Nilan website: http://www.nilan.dk/da-dk/forside/ download
If you have further questions on unit installation after reading the instructions, contact your nearest Nilan distributor, who can be found on www.nilan.dk/forhandlere.
The purpose of these instructions is to give the installer advice on correct installation and maintenance of the unit.
The unit must be started up immediately after installation and connection to the duct system. In periods where the ventilation system is not in operation, humid air from the rooms may penetrate into the ducts and form a condensate. The condensate may leak out of the valves and damage furniture and floors. In addition, condensate may form inside the unit, damaging the unit's electronics and fans.
The unit is supplied fully tested and ready for operation.
Final inspection
How to set up the ventilation system
T
his list is for helping the installer with the settings to be made in consultation with the user or client.
Function Settings
Setting for filter change period Days:
If low-speed ventilation is required in case of low outdoor t
emperature
Yes/No
Speed: A
t °C:
If low-speed ventilation is required in case of low air humidity Yes/No Speed:
If high-speed ventilation is required in case of high air humidity Yes/No Speed:
The set speed for basic ventilation Speed:
The desired room temperature °C:
Comfort 252 / 302 Top (English)
BY NILAN
5
Unit type
P
roduct description
Comfort 252 / 302 Top is a ventilation unit with heat recovery. The unit is designed for air flows up to 253/345 m3/h at 100 Pa external duct pressure.
The unit draws the humid, vitiated air out of the dwelling via the bathroom, WC, kitchen and utility room and introduces fresh outdoor air into habitable rooms such as living room, bedrooms and office. The cold outdoor air is heated up in the heat exchanger by the warm exhaust air.
Comfort 252 / 302 Top is supplied as standard with a G4 filter in the outdoor air and extract air ducts. If it is wished to filter the outdoor air for pollen, an F7 filter can be purchased as an accessory and mounted subsequent.
1. Duct connections 2
. Electrical connections
3. Extract air filter G4
4. Outdoor air filter G4 (F7 filter is fitted here)
5. Bypass damper
6. Counterflow heat exchanger
7. Condensate drain
8. Supply air fan (inlet air)
9. Extract air fan (outlet air)
10. Automatic control system
6
Dimensional drawing
A
ll dimensions are in mm.
Connections:
1
. Fresh air (outdoor air)
2. Supply air
3. Extract air
4. Discharge air
5. Condensate drain
Comfort 252 / 302 Top (English)
BY NILAN
7
Accessories
E
lectrical preheating element for frost protection
In longer periods of sub-zero temperatures, the high-efficiency counterflow heat e
xchanger will ice up. To avoid icing, it is recommended that an electrical
preheating element is mounted.
The preheating element uses very little energy, but ensures efficient heat recovery without de-icing, thus achieving an overall saving in energy consumption.
User option/cooker hood solution
It is possible to activate user selection mode via a potential-free contact. When t
he contact is activated the unit change to fan level four and overrides all other
functions.
The set include a distribution cable with two RJ12 connectors and 10 m cable to connect to eg a cooker hood or a contact.
Pollen filter F7
The unit is supplied as standard with a G4 filter.
I
f persons in the dwelling suffer from a pollen allergy, there is an option for mounting a F7 pollen filter in the outdoor air inlet to minimise the pollen in the indoor air.
Water trap
To ensure that the condensate can drain off freely, a water trap must be established.
The water trap must be regularly checked for water. In the summer season, where no condensation will occur, there is a risk of the water trap drying out. The Nilan water trap contains a ball which cease to prevent "false" air intake into the unit, so that condensate can run freely out of the unit.
Vibration absorbers
4 pc. of vibration absorbers are placed under the unit and secure an effective d
imming of the vibrations of the unit againt the surface.
8
Flexible silencing
To facilitate later servicing of the unit, we recommend fitting a flexible c
onnection between the unit and the duct system.
Nilan's sound damping flexi-hose gives good sound damping both to the duct system and to roof stacks.
Comfort 252 / 302 Top (English)
BY NILAN
9
Installation
Installation
Placement of the unit
ATTENTION
W
hen fitting the unit you should always take future service and maintenance in consideration.
It must be easy to replace the filters and ef it must be possible to take out the heat exchanger, fan or other components.
ATTENTION
A minimum distance of 60 cm in front of the unit is recommended for workspace.
ATTENTION
T
he unit must be installed level for the sake of the condensate drain.
The unit is low-noise and low-vibration. However potential vibrations spreading from the unit to the individual building parts must be taken into account. To detach the system from the floor, we recommend that the system is placed on vibration absorbers. To other building parts and other fixtures there should be a distance of about 10 mm.
The unit can be installed both inside and outside the building envelope because it is isolated and meets the requirements for heat loss.
Top unit
Min. 20 cm
Min. 50 cm
Min. 60 cm
Service area in front of the unit
ATTENTION
I
f a cover is used to protect the unit, this must be easy to remove.
10
Electrical installation
Electrical connections
Safety
ATTENTION
A
ll work must be carried out by qualified personnel and in accordance with applicable legislation
and regulations.
ATTENTION
I
t is important that power is disconnected when working with the unit's electrical components.
It is important to check that cables have not been damaged or trapped during connection and use.
C
onnection overview
All connections are at the top of the unit in the right side, seen from the front.
1. Connecting 230V (remember grounding)
2. Connecting userpanel
3. Connecting PC (USB AB kabel)
Comfort 252 / 302 Top (English)
BY NILAN
11
User panel
C
TS150 control-panel
The control-panel comes standard with 4 m cable mounted with RJ11 connectors at each end. One plug is mounted in the control-panel and the second plug is mounted in the unit.
The cable can be extended to max. 50 m. A 4 wired ribbon flatcable twisted in pairs 2x2, 25 mm2 with
RJ11 connectors are neededmed RJ11 (telephone cable).
Connecting the user-panel
12
Electrical connection, unit
S
upply
CAUTION
P
ower sypply including safety switch must be installed by a certified electrician.
It comes with a power cable for connection in socket. It is important for the unit to be bonded to earth.
Unit
Power supply
Safety switch
Comfort 252 / 302 Top (English)
BY NILAN
13
Electrical connections assessories
U
ser select/cooker hood solution
User selection of the CTS150 control, is a connector cable connected to the unit. A 10 m cable are connectet to a potential-free contact. When the contact is activated the unit change to fan level four and overrides all other functions.
User selection can be used to run a cooker hood with the unit. It can also be used to ventilate out of balance in supply and extract ventilation.
The user selection set /cooker hood set consists of the following:
• A distributor connector that attaches to the unit in the connector for the control panel
• 10 m of cable with a RJ12 plug mounted in the distributor connector
The user-panel is connected to the distributor connector instead of the unit.
ATTENTION
I
f the 10 m cable is not enough, it is possible to make a longer cable. It is important that the two outer compounds are used in the RJ12 connector. (The four in the middle are used by the user­panel)
14
External electrical preheating element
I
f the unit is the non-Polar version, an external preheating element can be purchased for retro-fitting.
The electric preheating element is mounted in the outdoor air duct before the unit with the necessary temperature sensor.
1x230V ~ 50 Hz max. 16A
7 8
Min. 32 cm
T
It is important that the sensor is placed at least 32 cm from the preheating element to achieve correct r
egulation.
The preheating element is fitted with a three-step safety system to prevent o
verheating.
1. A thermostat regulates heat and ensures that the supply air temperature does not go below -1 °C
2. A max. thermostat switches off the preheating element if the temperature exceeds 50 °C
3. A manual safety thermostat can be used to switch off the preheating element if the temperature exceeds 100 °C
ATTENTION
W
hen mounting the electric preheating element, there must be a safety gap of minimum 15 cm from any flammable material. The heating element must be insulated with a fire retardant insulation material, but the cover on the connection box must not be insulated.
Dimensional drawing:
Ø160
Positioning options:
Comfort 252 / 302 Top (English)
BY NILAN
15
Plumping
Condensate drain
Important information
T
he unit is supplied with dia. 20 mm condensate drain (PVC, GF-fittings).
ATTENTION
A
water trap must be established in the condensate drain in order to ensure that condensate
can drain off.
ATTENTION
I
f the unit is assembled outside the climate screen, it is important to secure the condensate drain against icing with a heating cable. Frost protection of the unit is the installer's responsibility.
During operation, a underpressure of up to 500 Pa may develop in the drain, corresponding to 50 mm water column. This water trap must therefore be mounted as shown in order to prevent drying out and return flow.
The connection of the water trap must be air-tight, otherwise air will be let into the unit and condensate will remain in the unit. This could lead to water damage if the condensate overflows the condensate tray and from there out of the unit.
After mounting the water trap, its function is tested as follows (the unit must be connected to the duct system and the lid must be closed).
The condensation tray are filled with water and the unit is operated at the highest fan speed. Allow it to run for several minutes. Check that there is no water in the condensation tray when the test is finished.
The water trap may dry out and thus prevent water escaping from the condensate tray, as air will be sucked into the unit. The water trap should therefore be checked at regular intervals, especially in the summer, and filled with water as necessary. Increasing the height of the water trap compared to the minimum requirements will minimize the need tor refilling.
INFO
N
ilan offers a water trap with a ball. The ball ensures that no air is sucked into the unit through the condensate drain if the water trap dries out. This ensures that water in the condensate tray can drain off and it makes it unnecessary to check the condensate drain so often.
16
Connection bottom
Ø20 mm
min. 50 mm
min. 50 mm
Ø20 mm
min. 170 mm
Connection of water trap generally Connection of Nilan water trap with ball
Comfort 252 / 302 Top (English)
BY NILAN
17
Plumping connections for accessories
W
ater lock with ball (option)
Connections for Nilan water lock:
1. Water lock with Ø32 mm spout
2. Reduction spout to Ø20 mm
3. Reduction piece to ¾" RG
4. Reduction spout for ½" hose
18
Ventilation installation
Duct system
Legislation
ATTENTION
A
ll work must be carried out by qualified personnel and in accordance with applicable legislation
and regulations.
Ducts
T
here are two systems for transporting air round the building.
Spiral tubes
Spiral tubes are metal ducts which are cut to size with an angle grinder, screwed together with bends and manifolds and laid out in accordance with the working drawing. The duct pipes are typically laid at the rafter ends and fixed with perforated band or suspended with suspension band. Avoid unnecessary bends in the ducting.
To avoid noise transmission, where sound is transmitted from room to room, a sound damper must be mounted in each room.
The ducts must be insulated to avoid heat loss and condensation. In some cases this can be avoided if the ducts are led through the ordinary insulation or inside the climate screen.
NilAIR tubes
NilAIR tubes are a flexible system which is easy to mount. The tubes are easily cut to size with a hobby knife and laid according to the working drawing without use of bends and manifolds. A manifold box is installed after the unit and the tubes run from this out to the various rooms.
With NilAIR tubes it is unnecessary to mount sound dampers in each room, as there is no risk of noise transmission.
If the tubes are led outside the climate screen they must be insulated to avoid heat loss and condensation. This is easier than with spiral tubing, as NilAIR tubes are easier to lead through ordinary insulation.
NilAIR tubes are more flexible than spiral tubing and can therefore be laid in places where ordinary spiral tubing would be impossible.
Unit
Nilan recommends mounting a flexible connection between the unit and the duct system.
This is to avoid oscillations from the unit being transmitted to the duct system, but also to ease future servicing where it is necessary to move the unit.
Nilan offers flexible silicing, which, apart from providing a flexible connection between the unit and the duct system, also dampen the passage of sound from the unit to the duct system.
Flexible silencing are insulated for condensation, but it may be necessary to insulate them further to meet local requirements for duct system insulation.
Comfort 252 / 302 Top (English)
BY NILAN
19
Extract air
E
xhaust valves are mounted in the moisture-generating rooms and strategically placed where they can
extract the moisture air most effectively.
Moisture-generating rooms:
• Bathroom
• Toilet
• Kitchen
• Utility room
Supply air
Supply air valves are mounted in habitable rooms and strategically positioned to give the minimum annoyance. For example, it is not recommended to mount incoming air valves over areas where people sit, as the air in some cases can be perceived as a draught.
Habitable rooms:
• Living room
• Kitchen-living room
• Bedroom
• Office
Roof stack
The roof inlet and outlet must be positioned and designed to limit pressure fluctuations in the
ventilation system caused by wind impact, and also to prevent access by birds and other animals, and
to ensure that the inlet and closed duct system are kept free of plant parts and foreign objects.
The air inlet must be located to minimise the risk of short-circuiting from the discharge air, having
regard to the prevailing wind direction.
The air inlet should be placed a minimum of 0.5 m above the roof surface, but a minimum of 1 m over flat black roofs up to the underside of the inlet, to ensure that warm air is not drawn into the building in the summer. The air inlet should be located on the north or east sides of pitched roofs.
Sound damping should also be mounted between the unit and roof stacks to avoid noise annoyance to
neighbours.
20
Installation example
Balancing
Important information
ATTENTION
F
or the ventilation system to operate optimally, it is important that initial regulation is carried
out correctly. We recommend having this done by experts.
It is important to measure the total supply (inlet) air and extract (outlet) air. The system must have a minimum vacuum, i.e. it must draw in more air out than in, to avoid humidity being pressed into the building construction.
Balancing connectors
T
he unit has balancing connectors for measuring the supply air (inlet air) and extract air (outlet air)
volumes.
The graph can be used for roughly setting the main air flow for dry operation without condensation precipitation.
On the extract air side (outlet air), the pressure drop dP3-4 [Pa] is measured between the connectors labelled 3 and 4. The air volume qv [m3/h] is read off on the graph.
On the supply air side (inlet air), the pressure drop dP1-2 [Pa] is measured between the connectors labelled 1 and 2. The air volume qv [m3/h] is read off on the graph.
ATTENTION
T
he capacity in the pressure drop diagram is based on a dry heat exchanger.
Comfort 252 / 302 Top (English) BY NILAN
21
Pressure drop diagram
dp
dp
3
1
2
4
1
2
3
4
4
2
3
1
0
20
40
60
80
100
120
140
160
0 50 100 150 200 250 300 350 400
dp [Pa]
qv [m3/h]
CT250 med Klingenburg GSK 378 mm
22
Software settings
User-panel
Functions
1
2
4
3
The CTS150 control panel provides the following functions: 1
. Setting fan speeds: 0 (off) - 1 - 2 - 3 - 4
2. Green diode: On when the unit is running
3. Setting low humidity: Can be set between 15 and 45%
4. Red diode: Flashes in the event of an alarm
Alarms
If the unit is in alarm mode, the RED diode on the CTS150 control panel will flash.
Alarm description
ID Alarm Critical Signal
1. T3 temperature sensor missing No
2. T4 temperature sensor missing No
3. T8 temperature sensor missing No
4. temperature sensor missing No
5. De-icing alarm No
6. Filter alarm No
• If the unit records more than 5 de-icing registrations within 24 hours, the de-icing alarm (ID = 5) is t
riggered
• To re-activate the de-icing alarm, disconnect electricity and restart the unit
• The unit shuts down when a critical alarm is active
Reset alarm:
1. Turn the fan speed selector as follows: → 0 → 4 → 0
2. Turn the selector to the fan speed required
Comfort 252 / 302 Top (English)
BY NILAN
23
Settings
I
nstalling of PC programme
Connect the PC to the unit via the USB BF connection, for this a USB AB cable is needed. The PC application can be downloaded via NilanNet in the menu item After Sales/Software.
• Install the latest software "Installer PC Tool"
• Install the programme under: C:\programmer(x86)HVAC\installer PC Tool\PC Tool\
Example of an installation in Windows 7 (deviations may occur within other versions of Windows).
1. Click O
PEN to open the .Zip file 2. Click RUN to install the programme
3. Click N
EXT to continue 4. Checkmark
the box
for installing USB driver and click NEXT
5. Click N
EXT to approve the location of the PC application 6. Click NEXT to approve the installation of the PC application
24
7. Click Y
ES to allow changes to your PC 8. The PC programme will be installed
9. Click C
LOSE to continue the installation 10. The USB driver will be transferred
11. Click N
EXT 12. Click INSTALL to install the USB driver
13. The USB driver will be installed 14. Click F
INISH to finish
Comfort 252 / 302 Top (English)
BY NILAN
25
PC-setting tool
ID1 ID1
ID4 ID5
ID9
ID5ID8ID7
ID7
ID3
ID6
ID2
T3 T8
T4
RH
Explanation of symbols:
T3: Temperature sensor extract air
• T4: Temperature sensor in the heat exchanger extract air
• T8: Temperature sensor in outdoor air intake
• RH: Humidity sensor in extract air
• Inlet Fan: Inlet air
• Exhaust Fan: Extract air fan
26
List of adjustable parameters
ID Description Interval Default settings
1 Fan settings
Fan level 0 is not adjustable
Fan level 1 in/out (humidity low) [0 - 100] 23 / 25 %
Fan level 2 in/out (basic ventilation) [0 - 100] 40 / 45 %
Fan level 3 in/out (high humidity) [0 - 100] 65 / 70 %
Fan level 4 in/out (user selection/cooker hood) [0 - 100] 100 / 100 %
2 Setting the filter change period [1 - 360] 90 days
3
Setting the low ventilation step (step 1) at low outside t
emperatures (with preheating mounted, recommended setting
-3)
[-3 - 0 - N/A] 0 °C
The actual outdoor temperature can be read (T8)
4 Setting of the wanted indoor temperature [0 - 50] 22 °C
The actual indoor temperature can be read (T3)
5 Setting of fan level at low humidity [off, 1, 2, 3] 1 level
Setting of fan level at high humidity [off, 2, 3, 4] 3 level
The actual humidity (RH)
6 Bypass damper position (Open/closed)
7 Setting the defrosting process
Start T: Setting the temperature (T4) where de-icing can start [1 - 5] 3 °C
Start time: Setting how long time to wait before de-icing starts [1 - 10] 5 min
Stop T: Setting the temperature (T4) at which the de-icing must s
top
[2 - 12] 7 °C
Maximal time: Setting the maximum de-icing period [5 - 60] 30 min
Delay time: Setting of the minimum period between two de-icing c
ycles
[15 - 760] 300 min
Bypass state: Setting whether bypass is open or closed during d
e-icing
[Closed, Open] Closed
The actual temperature in the heat exchanger air output can be r
ead (T4)
8 Setting of summer-/winter switch
Switch: Setting the outside temperature where there must be a s
hift between summer-/winter switch
[5 - 30] 13 °C
Dead-band: Regulation dead-band for summer/winter switch [0 - 10] 1 °C
9 Save or load settings
Save configuration: Save the current settings
Load configuration: Upload your last saved settings
• Summer/winter operation mode changes if outdoor temperature is the set value plus the dead-band s
etting in more than 15 minutes
• De-icing is only possible, if the outdoor temperature (T8) < 1 °C
• It is only possible to run low humidity when the unit is in winter mode
Comfort 252 / 302 Top (English) BY NILAN
27
Operation
B
ypass function
When the current room temperature is above the desired temperature, there is no further need for heat recovery. In this situation, the bypass opens and diverts the outdoor air round the heat exchanger, preventing the latter from being heated by the indoor air. This results in lower internal pressure in the unit, thereby saving energy on fan operation.
The unit has a 100% bypass, which means that as well as diversion of the outdoor air round the heat
exchanger, a damper closes off the heat exchanger, preventing any outdoor air from passing through it.
Humidity control
As standard, the unit is fitted with intelligent humidity control, which automatically adjusts to the needs of the family or building.
By means of the integral humidity sensor, the control system calculates the average value for the past
24 hours. The average value is consulted when deciding whether to change the air change rate in the event of a fluctuation in the air humidity in the extract air, and at the same time it adjusts to the air humidity levels in summer and winter.
If the air humidity rises by more than 5-10% (summer/winter), forced ventilation is activated in order
to expel the humidity as quickly as possible. If the average air humidity falls below the set value for low
humidity (default value 30%), the unit will operate at a reduced level with a lower air change rate, in
order not to dry out the home even further.
This automatic humidity control helps to save energy on operation, and to ensure satisfactory comfort
in the home.
28
Replacing the filter
CAUTION
A
lways turn off the unit before replacing filters.
It is important to replace the filtes in the unit regularly, as clogged filters provides greater power consumption and reduces the ventilation.
As a standard the unit is equipped with 2 pc. of G4 filters, which will protect the fans and heat exchanger. The G4 filter should generally be replaced every 3 months and therefore the filter alarm factory setting i set to 90 days. After 90 days there will be an alarm in the control panel, as an indication to change filters.
It is possible to buy a F7 pollen filter for placement in the outdoor air intake.
Comfort 252 / 302 Top (English)
BY NILAN
29
30
Comfort 252 / 302 Top (English)
BY NILAN
31
Nilan A/S Nilanvej 2 DK-8722 Hedensted
Tlf. +45 76 75 25 00 Fax +45 76 75 25 25
nilan@nilan.dk www.nilan.dk
United Kingdom:
S L Services 25 St Leonards Road, Horsham RH13 6EH West Sussex
Tlf. +44 (0) 7919 444452
stuart315@aol.com www.nilanuk.com
Ireland:
Nilan Ireland Ballylahive, Abbeydorney
Tlf. +353 (0) 87 9798361
maurice@nilan.ie www.nilanireland.ie
Document no.B11_Comfort_252-302-Top_GB
Nilan A/S assumes no responsibility for any errors or omissions in the printed manuals or for loss or damage that may follow from the use of such published materials - whether such loss of
damage is caused by errors or inexpediencies in the material or otherwise. Nilan A/S reserves the right without prior notice to change products and manuals. All trademarks are the property
of Nilan A/S. All rights reserved.
Loading...