Nidec NE200, NE300 User Manual

W
NE200/NE300
)JHIQFSGPSNBODF WFDUPSDPOUSPMESJWF
User Manual
Serial No -3101A003
Scan QR to follow us
NE200/300 Series Drive User Manual
NE200/300 General Driver

Relative Documentations

User Guide in Chinese:
3101A002/NE200/NE300 User Guide 31019006/NE400/NE600 User Guide
User Guide in English:
3101A003/NE200/NE300 User Guide 3101A004/NE400/NE600 User Guide
Control Techniques China
Service Tel400-887-9230
NE200/300 Series Drive User Manual

Safety Information

Warning: A Warning contains information which is essential for avoiding a safety hazard.
Caution: A Caution contains information which is necessary for avoiding a risk of damage to the product or other equipment.
Use
This series of drive is used to control the variable speed operation of three-phase motor and cannot be used for single-phase motor or other applications. Otherwise, drive failure or fire may be caused. This series of drive cannot be simply used in the applications directly related to the human safety, such as medical equipment. This series of drive is produced under strict quality management system. Redundancy or bypass solution is necessary if the drive failure may cause severe accident or loss.
Installation If the drive is found to be damaged or parts missing, the drive cannot be installed. Otherwise, accident may be caused. When handling and installing the product, please hold the product from bottom. Do not hold the enclosure only. Otherwise, your feet may be injured, and the drive may be damaged because of dropping. The drive shall be mounted on the fire-retardant surface, such as metal, and kept far away from the inflammables and heat source. Keep the drilling scraps from falling into the inside of the drive during the installation; otherwise, drive failure may be caused.
When the drive is installed inside the cabinet, the electricity control cabinet shall be equipped with fan and ventilation port. And ducts for radiation shall be constructed in the cabinet.
Wiring The wiring must be conducted by qualified electricians. Otherwise, there exists the risk of electric shock or drive damage. Before wiring, confirm that the power supply is disconnected. Otherwise, there exists the risk of electric shock or fire. The grounding terminal PE must be reliably grounded, otherwise, the drive enclosure may become conductive. To ensure the safety, the drive and the motor must be grounded. Please do not touch the main circuit terminal. The wires of the drive main circuit terminals must not contact the enclosure. Otherwise, there exists the risk of electric shock. The connecting terminals for the
braking resistor are +and PB. Please do not connect terminals other
than these two. Otherwise, fire may be caused.
Wiring
The power supply cannot connect to output terminals U-V-W, otherwise, the drive will be damaged. It is forbidden to connect the output terminal of the drive to the capacitor or LC/RC noise filter with phase lead, otherwise, the internal components of the drive may be damaged Please confirm that the power supply phases, rated voltage are consistent with that of the nameplate, otherwise, the drive may be damaged. The wires of the main circuit terminals and the wires of the control circuit terminals shall be laid separately or in
Warning
Caution
NE200/300 Series Drive User Manual
a square-crossing mode, otherwise, the control signal may be interfered. When the length of the cables between the drive and the motor is more than 100m, it is suggested to use output reactor to avoid the drive failure caused by the over-current of the distribution capacitor. The drive which equipped with DC reactor must connect with DC reactor
between the terminal of P1(+) otherwise the drive will not display
after power on.
Operation
Power supply can only be connected after the wiring is completed and the cover is installed. It is forbidden to remove the cover in live condition; otherwise, there exists the risk of electric shock. When auto failure reset function or restart function is set, isolation measures shall be taken for the mechanical equipment, otherwise, personal injury may be caused. When the drive is powered on, even when it is in the stop state, the terminals of the drive are still live. Do not touch the drive terminals; otherwise electric shock may be caused. The failure and alarm signal can only be reset after the running command has been cut off. Otherwise, personal injury may be caused.
Operation
Do not start or shut down the drive by switching on or off the power supply, otherwise the drive may be damaged. Before operation, please confirm if the motor and equipment are in the allowable use range, otherwise, the equipment may be damaged. The heat sink and the braking resistor have high temperature. Please do not touch such devices; otherwise, you may be burnt.
When it is used on lifting equipment, mechanical contracting brake shall also be equipped. Please do not change the drive parameter randomly. Most of the factory set parameters of the drive can meet the operating requirement, and the user only needs to set some necessary parameters. Any random change of the parameter may cause the damage of the mechanical equipment. In the applications with mains frequency and variable frequency switching, the two contactors for controlling the mains frequency and variable frequency switching shall be interlocked.
Maintenance & Inspection In the power-on state, please do not touch the drive terminals; otherwise, there exists the risk of electric shock. If cover is to be removed, the power supply must be disconnected first. Wait for at least 10 minutes after power failure or confirm that the CHARGE indicator is off before maintenance and inspection to prevent the harm caused by the residual voltage of the main circuit electrolytic capacitor to persons. The components shall be maintained, inspected or replaced by qualified electricians.
Maintenance & Inspection
The circuit boards have large scale CMOS IC. Please do not touch the board to avoid the circuit board damage caused by static electricity.
NE200/300 Series Drive User Manual
Revision History
Date
Version
Description
2020/4/2
1.0
Issued for the first time
2020/5/19
1.1
Add “Modbus Address” column in parameter brief list
2020/6/12
1.2
Add contents of chapter 9 and re-structure the manual
NE200/300 Series Drive User Manual

Contents

Chapter 1 NE200/300 Product Introduction ....................................................... 1
1.1 Product Nameplate Description ............................................................ 1
1.2 Model Description ................................................................................. 1
Chapter 2 Wiring of System ............................................................................... 2
2.1 Wiring diagram of system ..................................................................... 2
2.2 Description of Peripheral Devices for Main Circuit ............................... 2
2.3 Attention for Main Circuit Wiring ........................................................... 4
2.4 Motor Wiring ......................................................................................... 4
Chapter 3 Installation ......................................................................................... 7
3.1 Environment ......................................................................................... 7
3.2 Mounting Direction and Space ............................................................. 7
3.3 Wiring preparation for driver ................................................................. 7
3.4 Terminal diagram of main circuit ......................................................... 10
3.5 Control Terminal Wiring ...................................................................... 13
3.6 Functions of Control Circuit Terminals ................................................ 16
3.7 Control board schematic drawing ....................................................... 24
Chapter 4 Operation and application ............................................................... 27
4.1 Keypad ............................................................................................... 27
4.2 Function code viewing and modification ............................................. 29
4.3 Display status of keypad..................................................................... 29
4.4 Password Setting ............................................................................... 30
4.5 Typical application .............................................................................. 30
Chapter 5 Parameter description ..................................................................... 33
5.1 Group 0 Basic Function ...................................................................... 33
5.2 Start and stop group (F1) ................................................................... 38
5.3 Auxiliary running function group (F2) .................................................. 42
5.4 Vector Control Parameters (F3) .......................................................... 48
5.5 V/F Control Parameters (F4) .............................................................. 54
5.6 Motor parameters group (F5) ............................................................. 57
5.7 Input terminals group (F6) .................................................................. 60
5.8 Output terminals group (F7) ............................................................... 69
NE200/300 Series Drive User Manual
5.9 PID Parameters (F8) ........................................................................... 75
5.10 PLC and Multi-steps group (F9) .......................................................... 80
5.11 Wobble frequency running group (FA) ................................................ 83
5.12 Fixed-length control group (Fb) ........................................................... 84
5.13 Protection and fault parameters group (FC) ........................................ 84
5.14 Communication parameters group (Fd) .............................................. 87
5.15 Operation interface & display group (FE) ............................................ 88
5.16 Running history record group (FF) ...................................................... 90
5.17 Protection Parameters (FP) ................................................................ 92
Chapter 6 Fault information and trouble shooting ............................................ 94
6.1 Fault information and solutions. .......................................................... 94
6.2 Warning information ............................................................................ 98
6.3 The general fault diagnosis and solutions ........................................... 98
Chapter 7 Routine Repair and Maintenance .................................................. 100
7.1 Routine Maintenance ........................................................................ 100
7.2 Periodic Maintenance........................................................................ 101
7.3 Component Replacement ................................................................. 102
7.4 Warranty............................................................................................ 102
Chapter 8 Technical Data and model selection .............................................. 103
8.1 Technical features ............................................................................. 103
8.2 NE200 Technical data ....................................................................... 105
8.3 NE300 Technical data ....................................................................... 107
8.4 Product Dimensions and weight ........................................................ 109
8.5 Keypad .............................................................................................. 113
8.6 Braking Resistor and Unit ................................................................. 115
8.7 Model selection of system ................................................................. 120
Chapter 9 Options .......................................................................................... 123
9.1 NE300 advanced control PCBA diagram .......................................... 123
9.2 Wiring of control circuit ...................................................................... 124
9.3 Options .............................................................................................. 128
Appendix A: Modbus Communication Protocol ............................................... 137
Appendix B: Adapted encoder instruction ........................................................ 144
Appendix C NE300 Closed-loop Control ......................................................... 145
Appendix D Parameters Brief .......................................................................... 154
NE200/300 Series Drive User Manual
Chapter 1 NE200/300 Product Introduction 1

Chapter 1 NE200/300 Product Introduction

1.1 Product Nameplate Description

Fig.1-1 Nameplate

1.2 Model Description The digits and letters of the drive model number on the nameplate indicate

information such as the product series, power supply class, power ratings and software/hardware versions. NE300-4T0300G/0370P means this model can be used as 30kW heavy duty and 37kW normal duty.
Fig.1-2 Product Model Description
NEXXX-4T0300G/0370Pn
NE □ □ □ -4T0300G/0370Pn
0118□ □ □ □
Model No. Power Rating Input Spec.
Output Spec.
Product Barcode
Company Info.
NE □ □ □
4T
0220
G B -M
Product Series
NE200 NE300
Voltage Rating
2S:200~240V 4T:380~440V
Power Rating
0004—(0.4kW) 0007—(0.75kW) 0015—(1.5kW) ~
1320—(132kW)
~ 9000—(900kW)
Structure Code
DefaultStandard
--MCompact
--UUp in down out
--DDown in down out
--FFreestanding
Brake Unit
DefaultNone
B=Brake unit
Application Type
GHeavy duty P– Normal duty
1
NE200/300 Series Drive User Manual
2 Chapter 2 Wiring of System

Chapter 2 Wiring of System

2.1 Wiring diagram of system

2.2 Description of Peripheral Devices for Main Circuit

Circuit breaker
2
R
S T
N
S T
R
V W
U
P1
M
Isolation
Switch
Breaker or
Fuse
AC input
reactor
Contactor
DC
reactor
Braking unit
Braking
resistor
EMI
output filter
EMI
input filter
AC
output reactor
Motor
NE200/300 Series Drive User Manual
Chapter 2 Wiring of System 3
The capacity of the circuit breaker shall be 1.5 ~ 2 time of the rated current of the drive. The time features of the circuit breaker shall fully consider the time features of the drive overload protection.
Leakage circuit breaker
Because the drive output is the high-frequency pulse voltage, there will be high-frequency leakage current. Specialized leakage circuit breaker shall be installed at the input end of the drive. B type leakage circuit breaker is suggested, and the leakage current value shall be set as 300mA.
Contactor
Frequent open and close of contactor will cause drive failure, so the highest frequency for the open and close of contactor shall not exceed 10 times/min. When braking resistor is used, to protect the braking resistor from over-heat damage, thermal protection relay shall be installed to control the disconnect of the contactor at power supply side
Input AC/DC reactor
The drive power supply capacity shall be more than 600kVA or 10 times of the drive capacity. If there is switch type reactive-power compensation capacitor or load with silicon control at the same power line, there will be high peak current flowing into drive power input circuit, causing the damage of the rectifier components. When the voltage unbalance of the three-phase power supply exceeds 3%, the rectifier component will be damaged. The input power factor of the drive is required to be higher than 90%. In case of above situations, install the AC reactor at the input end of the drive or DC reactor to the DC reactor terminal.
Input noise
The input noise filter can reduce the noise that flows from the power supply to the drive or the drive to power supply.
Thermal protection relay
Although the drive has motor overload protection function, when one drive drives two or more motors or multi-pole motors, to prevent the motor over temperature failure, thermal protection relay shall be installed between the drive and each
motor, and the motor overload protection parameter FC.00 shall be set as “0”
(motor protection disabled).
Output noise filter
When the noise filter is applied to the output side of drive, the conduction and radiation interference can be reduced.
Output AC reactor
When the cable connecting the drive and the motor is longer than 100m, it is suggested to install AC output reactor to suppress the high-frequency oscillation
NE200/300 Series Drive User Manual
4 Chapter 2 Wiring of System
to avoid the damage to motor insulation, large leakage current and frequent drive protective actions.

2.3 Attention for Main Circuit Wiring

2.3.1 Power Supply Wiring

It is forbidden to connect the power cable to the drive output terminals; otherwise, the internal components of the drive will be damaged. To facilitate the input side over current protection and power failure maintenance, the drive shall connect to the power supply through the circuit breaker or leakage circuit breaker and contactor. Please confirm that the power supply phases, rated voltage are consistent with that of the nameplate, otherwise, the drive may be damaged.

2.4 Motor Wiring

It is forbidden to short circuit or ground the drive output terminals; otherwise the internal components of the drive will be damaged. Avoid short circuit the output cable and the drive enclosure, otherwise there is the risk of electric shock. It is forbidden to connect the output terminals of the drive to the capacitor or LC/RC noise filter with phase lead, otherwise, the internal components of the drive may be damaged. When contactor is installed between the drive and the motor, it is forbidden to switch on/off the output contactor during the running of the drive; otherwise, there will be large current flowing into the drive, triggering the drive protection action. Length of cable between the drive and motor If the cable between the drive and the motor is too long, the higher order harmonic leakage current will cause impact on the drive and the peripheral devices. It is suggested that output AC reactor be installed when the motor cable is longer than 100m, and that carrier frequency be set as follows:

2.4.1 Grounding Wiring

The drive will produce leakage current. The higher the carrier frequency is, the larger the leakage current will be. The leakage current of the drive system is more than 3.5mA, and the exact value of the leakage current is determined by the site conditions. To ensure the safety, the driver and the motor must be grounded. The grounding resistance shall be less than 10ohm. For the grounding wire diameter requirement, refer to 8.7 Model selection of system Do not share grounding wire with the welding machine and other power equipment. Cable length
between
drive and motor
Less than
50 m
Less than
100 m
More than
100 m
Carrier frequency
(F0.15)
Less than 10kHz
Less than
6kHz
Less than
4kHz
NE200/300 Series Drive User Manual
Chapter 2 Wiring of System 5
In the applications with more than 2 drivers, keep the grounding wire from forming a loop.
Fig.2-1 Grounding Wiring

2.4.2 Countermeasures against conduction and radiation interference

Fig.2-2 Countermeasures for Conduction and Radiation Interference
When the input noise filter is installed, the wire connecting the filter to the drive power input terminal shall be as short as possible. The filter enclosure and mounting cabinet shall be large area reliably grounded to reduce the back-flow impedance of the noise current Ig. The wire connecting the drive and the motor shall be as short as possible. The motor cable adopts 4-core cable, among which the grounding wire shall be one end grounded at the drive side, the other end connected to the motor enclosure. The motor cable shall be sleeved into the metal tube. The input power wire and output motor wire shall be kept away from each other if possible. The equipment and signal cables vulnerable to interference shall be kept far away from the drive. Key signal cables shall adopt shielding cable. It is suggested that the shielding layer shall be grounded with 360-degree grounding method and sleeved into the metal tube. The signal cable shall be kept far away from the drive power input wire and output motor wire. If the signal cable must cross the power input wire and output motor wire, they shall be laid orthogonal. When analog input of voltage or current is adopted for remote frequency setting, twisted shielding cable shall be used. The shielding layer shall be connected to
Driver Driver Driver Driver Driver Driver
Input filter
Driver
Shielding
cable
Z
N
Z
E
I
g
NE200/300 Series Drive User Manual
6 Chapter 2 Wiring of System
the grounding terminal PE of the drive, and the signal cable shall be no longer than 50m. The wiring of TA/TB/TC shall be separated from wiring of other main circuit terminals. It is forbidden to short circuit the shielding layer and other signal cables or equipment.
NE200/300 Series Drive User Manual
Chapter 3 Installation 7

Chapter 3 Installation

3.1 Environment

Avoid installing the product in the sites with oil mist, metal powder and dust. Avoid installing the product in the sites with hazardous gas and liquid, and corrosive, combustible and explosive gas. Avoid installing the products in salty sites. Do not install the product in the sites with direct sunlight. Do not mount the product on the combustible materials, such as wood.
Keep the drilling scraps from falling into the inside of drive during the installation. Mount the product vertically in the electric control cabinet, mount the cooling fan or air conditioner to prevent the ambient temperature from rising to above 40 ºC. For the sites with hash environment, it is recommended to mount the drive heat sink outside the cabinet.

3.2 Mounting Direction and Space In order not to reduce the drive cooling effect, the drive must be mounted

vertically, and certain space must be maintained, as shown in Fig. 3-1(1)
Fig.31 Mounting direction and Space/Installation diagram
When installing multiple drives vertically upside and downside, the air
deflector is required as Fig.3-1(2)

3.3 Wiring preparation for driver

3.3.1 NE200 wiring preparation

3
50 50
(1)
(2)
NE200/300 Series Drive User Manual
8 Chapter 3 Installation
Fig.3-2 NE200 2P 200V 0.4~2.2kW(GB)/3P 400V 0.75(GB)~5.5kW(PB)
Wiring preparation: Open cover along the ‘O’ direction, close it along the
opposite direction, see Fig. 3-2.

3.3.2 NE300 wiring preparation

1) NE300 wiring preparation for the plastic enclosure driver
Fig.3-3a NE300 3P 400V 1.5~11kW(GB)/2.2~15kW(PB)
Fig.3-3b NE300 3P 400V 15~22kW(GB)/18.5~30kW(PB)
There are 2 type plastic enclosure drivers, see Fig.3-3a/b Dismantled/mounted keypad: Push out keypad like Fig.3-3a(1),then
take off it along the ‘P’ direction. Mount it along the opposite direction.
Wiring preparation (Fig.3-3a): Loosen the clip 3/4, then open along the ‘O’
direction, take off along the ‘P’ direction. Take off along the opposite
Control Board
Main
Terminal
O
Keypad
Cover
Clip4
Hole4
Slot
Clip2
Clip1
Clip3
Hole3
Hole1
Hole2
Control
Board
Option
Main
Terminal
(1) (2)
(3)
P
O
O
P
Control
Board
Main terminal
O
Clip3
Hole5/6
Clip1/2
Clip4
Hole3/4
Hole1/2
Option
(1) (2)
(3)
Clip5
Clip6
Two side
Two sides
Two side
Twosides
Cover1
Cover2
NE200/300 Series Drive User Manual
Chapter 3 Installation 9
direction.
Wiring preparation (Fig.3-3b): Loosen the clip 1/2, then open along the ‘O’
direction, take off cover1 along the ‘P’ direction. Loosen the clip 3-6
2) NE300 Metal-sheet enclosure type A
Fig.3-4 NE300 3P 400V 30~250kW(G)/37-280kW(P)
The AC-in and AC-out of some drivers are at two sides of driver.
Dismantling cover1: dismantle the screw 1/2, open cover1 along ‘O’
direction, and take off it along ‘P’ direction.
Dismantling cover2: dismantle the screw 3/4, open cover2 along ‘O’
direction, take off it along ‘P’ direction.
3) NE300 Metal-sheet enclosure type B
Fig.3-5 NE300 3P 400V 160~315kW(G)185~355(P)
Dismantling cover1: dismantle the screw 1/2, open cover1 along ‘O’
direction, and take off it along ‘P’ direction.
Dismantling cover2: dismantle the screw 3/4, open cover2 along ‘O’
direction, take off it along ‘P’ direction.
The wiring holes at two sides of driver, break it to create holes for wiring.
4) NE300 Metal-sheet enclosure type C
Screw1
O
O
Screw2
Cover1
Screw3
Screw4
Cover2
Control
Board
Option
Main terminal
(1) (2) (3)
O
O
Screw1
Screw2
Screw3
Cover1
Screw4
Cover2
Control
Board
Option
Main Terminal
Wiring hole
NE200/300 Series Drive User Manual
10 Chapter 3 Installation
Fig.3-6 NE300 3P 400V 355~500kW(G)/400~560P
Unlock and open door, then start to wiring. The wiring holes at two sides of driver, break it for wiring.
5) NE300 Metal-sheet enclosure type D
Fig.3-7 NE300 3P 400V 560~800kW(G)/630~900kW(P)
Unlock and open door, then start to wiring. The wiring holes at two sides of driver, break it for wiring.

3.4 Terminal diagram of main circuit

Wiring
hole
Option
Control
Board
Main
terminal
Control
Board
Option
Main
terminal
Wiring
hole
NE200/300 Series Drive User Manual
Chapter 3 Installation 11

3.4.1 NE200-4T0007G/0015PB~4T0022GB-M/2S0004GB~2S000 15GB

Terminal diagram of main circuit
Terminal Symbol
Terminal description
Grounding terminal PE
RS
Single-phase AC input terminals
RS T
Three-phase AC input terminals
(+)PB
Terminals reserved for braking resistor
UVW
Three-phase AC output terminals

3.4.2 NE200-4T0015GB~4T0040GB/4T0055PB/2S0022GB

Terminal diagram of main circuit
Terminal Symbol
Terminal description
Grounding terminal PE
RS
Single-phase AC input terminals
RST
Three-phase AC input terminals
(+)(-)
DC bus - + terminals for common bus DC input
(+)PB
Terminals reserved for braking resistor
UVW
Three-phase AC output terminals

3.4.3 NE300-4T0015G/0022PB~4T0220G/0300PB

Terminal diagram of main circuit
Terminal Symbol
Terminal description
Grounding terminal PE
RST
Three-phase AC input terminals
(-) (+)
DC bus - + terminals for common bus DC input
(+)PB
Terminals reserved for braking resistor
UVW
Three-phase AC output terminals
NE200/300 Series Drive User Manual
12 Chapter 3 Installation

3.4.4 NE300-4T0300G/0370P~4T1100G/1320P

Terminal diagram of main circuit
Terminal Symbol
Terminal description
Three-phase AC input terminals
RST
DC bus - + terminals for common bus DC input
(-)(+)
Reserved for DC reactor connecting terminal.
Short circuited with copper plate as factor setting
P1(+)
Three-phase AC output terminals
UVW
Grounding terminal PE
3.4.5 NE300-4T1320G/1600P-U/-D~4T2500G/2800P-U/-D
Terminal diagram of main circuit
Terminal Symbol
Terminal description
Grounding terminal PE
RST
Three-phase AC input terminals
(-)(+)
DC bus - + terminals for common bus DC input
P1(P)(+)
Reserved for DC reactor connecting terminal;
Short circuited with copper plate as factor setting
UVW
Three-phase AC output terminals

3.4.6 NE300-4T1600G/1850P-F~4T3150G/3550P-F

Terminal diagram of main circuit
Terminal Symbol
Terminal description
Grounding terminal PE
NE200/300 Series Drive User Manual
Chapter 3 Installation 13
RST
Three-phase AC input terminals
(-)(+)
DC bus - + terminals for common bus DC input
P1(+)
Reserved for DC reactor connecting terminal;
Short circuited with copper plate as factor setting
UVW
Three-phase AC output terminals

3.4.7 NE300-4T3550G/400P-F~4T5000G/5600P-F

Terminal diagram of main circuit
Terminal Symbol
Terminal description
Grounding terminal PE
RST
Three-phase AC input terminals
(-)(+)
DC bus - + terminals for common bus DC input
P1(+)
Reserved for DC reactor connecting terminal;
Short circuited with copper plate as factor setting
UVW
Three-phase AC output terminals

3.4.8 NE300-4T5600G/6300P-F~4T8000G/9000P-F

Terminal diagram of main circuit
Terminal Symbol
Terminal description
Grounding terminal PE
RST
Three-phase AC input terminals
(-)(+)
DC bus - + terminals for common bus DC input
P1(+)
Reserved for DC reactor connecting terminal;
Short circuited with copper plate as factor setting
UVW
Three-phase AC output terminals

3.5 Control Terminal Wiring

3.5.1 Control Terminal Wiring of NE200

NE200/300 Series Drive User Manual
14 Chapter 3 Installation
Fig.3-8 Control Terminal Wiring of NE200(Example: 0022GB~0040GB)
(RST)
(multi-speed terminal 1)
X1~X5
Voltage range 012V
Braking resistor
Motor
power grounding
Analog output1
Relay output
switchable
AI reference voltage
External power
(multi-speed terminal 2)
Shielded cable
Main Circuit
Control Circuit
power supply
digital input 1
digital input 2 digital input 3 digital input 4
digital input 5
digital input 6
digital input 7
Muti-function inputs
communication terminal
power/public terminal
muti-function digital input terminal
Analog terminal
Analog input
need fly line
power grounding
circuit braker contactor
NE200/300 Series Drive User Manual
Chapter 3 Installation 15

3.5.2 Control Terminal Wiring of NE300

Fig 3-9 Control Terminal Wiring of NE300 (Example: NE300-4T0220G/0300PB and below)
Apply to 0015G/0022PB~02
20G/0300PB
Apply to 0300G/0370P~9000G
2
(RST)
(FJOG)
(速端子3)
communication terminal
power/public terminal
muti-function digital input terminal
Analog terminal
Extensible terminal
DC reactor
Circuit braker
contactor
SC Plate
power grounding
mortor grounding
Motor
Braking resistor
Main Circuit
Control Circuit
Muti-function input 3
Muti-function input 4
Muti-function input 5
Muti-function input 6
Muti-function input 7
Muti-function input 2
Muti-function input 1
Muti-function input 8
(multi-speed terminal 3
(Expansion board
Analog output1
Relay output 1
Analog output2
Relay output 2
(Expansion board
(Expansion board
3 phase AC power supply
Modbus RS485
Expansion
interface
NE200/300 Series Drive User Manual
16 Chapter 3 Installation

3.6 Functions of Control Circuit Terminals

3.6.1 NE200 Standard configuration of control circuit
terminals
Type
Termin
Terminal function
Technical specification
Digital
input
&
output
X1
X5
Multi-functional input terminals 15
Optical-isolator input Frequency range:0200Hz Voltage range: 012V
Y1
Open collector output
Optical-isolator output maximum output current: 50mA Output voltage range024V
GND
Terminal ref. grounding
24V
24V
24V±5%, Maximum load :200mA, with overload and short circuit protection
Analog
input
10V
Analog input reference voltage
Open circuit voltage up to 11V; Maximum output 30mA
AI1
Analog input channel 1
Input Voltage range010V Input impedance100kΩ
AI2
Analog input channel 2
Input Voltage range010V Input impedance100kΩ Input current range030mA Current Input impedance 500Ω, 0~20mA or 0~10V analog input can be selected through DIP switch SW1
GND
Terminal ref. grounding
Analog
output
AO
Analog output 1
020mA: Allowed load impedance 200~500Ω 010V: Allowed load impedance ≥1kΩ. With SC protection; 0~20mA or 0~10V analog output can be selected through DIP switch SW2
GND
Analog grounding
NE200/300 Series Drive User Manual
Chapter 3 Installation 17
Type
Termin
Terminal function
Technical specification
Relay output
TA/TB/
TC
Relay output 1
TATBNC; TATCNO Contact capacity250VAC/1A 30VDC/1A
RS485
485+
485 differentials positive
Rate: 1200/2400/4800/9600/19200/38 400bps. Max. parallel 127 No.s; SW3 select adapted resistor; Max. Length 500m. (twisted shielding cable)
485-
485 differential negatives
GND
486 shielding grounding
Internal isolated with COM
Fig.3-10 Arrangement of Control Circuit Terminals
NE200-2S0004GB~
NE200-4T0022GB-M
NE200-2S0022GB~
NE200-4T0040G/0055PB
NE200/300 Series Drive User Manual
18 Chapter 3 Installation

3.6.2 NE200 Control Circuit Connection External controller Dry contacts wiring diagram is as below. (for X1-X5

multifunction input)
Fig.3-11 NE200 control circuit wiring diagram
External controller NPN with common emitter wiring diagram is as below.
(for X1-X5 multifunction input)
Fig.3-12 NE200 NPN common emitter wiring mode
Y1 multi-functional output terminal adopt external power supply wiring
mode.
Controller
of User
Driver
GND
X5
X1
12V
12V
DriverController
of User
NPN
NE200/300 Series Drive User Manual
Chapter 3 Installation 19
Fig.3-13 NE200 Y1 wiring diagram for external power supply
Fig.3-14 NE200 wiring diagram for analog input

3.6.3 NE200 keypad wiring

Fig.3-15 T-568B standard
Table 3-1 T568B Standard
Pin No.
Color
Pin No.
Color
1
Orange/White
8
Brown
2
Orange
3
Green/White
4
Blue
5
Blue/ White
6
Green 7 Brown/White
Grounding for
shielding cable
Driver
GND
AI1
10V
NE200/300 Series Drive User Manual
20 Chapter 3 Installation
The cables connecting keypad and control board use standard RJ-45 Interface, namely both sides are connected according to EIA/TIA568B standard. Users can make the cable by themselves or purchase general internet cable from market as keypad cable.
3.6.4 NE300 Standard configuration of control circuit
terminals
Type
Termin
Terminal function
Technical specification
Digital
input
X1
X3
Multi-functional input terminals 13
Optical-isolator input Frequency range:0200Hz Voltage range: 024V
X4 X5
Multi-functional input or Single pulse input 4, 5
Multi-functional inputsame as X1 X3 Single Pulse input:0.1Hz50kHz Voltage range024V
COM
multi-functional input terminals common end
Internal isolated with GND
Digital output
24V
24V
24V±5%, Maximum load :200mA, with overload and short circuit protection
Y1
Open collector output 1
Optical-isolator output maximum output current: 50mA Output voltage range024V
DO
Open collector or high speed pulse output
Output frequency: 050kHz Can be used as the normal open collector.
COM
Open collector output common end
Internal isolated with GND
Analog
input
10V
Analog input reference voltage
Open circuit voltage up to 11V; Internal isolated with com; Maximum load 30mAwith overload and short circuit protection
AI1
Analog input channel 1
Input Voltage range010V Input impedance100kΩ
AI2
Analog input channel 2
Input Voltage range010V Input impedance100kΩ Input current range030mA Current Input impedance 500Ω, 0~20mA or 0~10V analog input can be selected through DIP switch SW2
GND
Analog grounding
Internal isolated with COM
NE200/300 Series Drive User Manual
Chapter 3 Installation 21
Type
Termin
Terminal function
Technical specification
Analog
output
AO1
Analog output 1
0/420mA: Allow output impedance 200~500Ω 010V: Allowed output impedance ≥10kΩ. With SC protection, 0~20mA or 0~10V analog output can be selected through DIP switch SW1
GND
Analog grounding
Internal isolated with COM
Relay
output
TA/TB/T
C
Relay output 1
TATBNC; TATCNO Contact capacity250VAC/1A 30VDC/1A
RS485
485+
485 differentials positive
Rate: 1200/2400/4800/9600/19200/38400 bps. Max. parallel 127 No.s; SW3 select adapted resistor; Max. Length 500m. (twisted shielding cable)
485-
485 differential negatives
GND
486 shielding grounding
Internal isolated with COM
Fig.3-16 Control circuit terminals diagram

3.6.5 NE300 Control Circuit Connection External controller Dry contacts wiring mode is as below. (X1-X5

multifunction input)
NE200/300 Series Drive User Manual
22 Chapter 3 Installation
Fig.3-17 NE300 dry contacts wiring diagram for external controller
External controller NPN with common emitter wiring mode is as below.
(X1-X5 multifunction input)
Fig.3-18 NE300 NPN common emitter wiring diagram
1) For NE30-i /O Lite option X6-X8 and NE300 closed-loop non-standard board X1-X5, the type of power supply input (PNP mode/NPN mode and internal/external power supply) can be selected by setting short wiring at terminal PLC-P24 or terminal PLC-COM. The wiring diagram is shown in Fig 9-2 to Fig 9-5 in chapter 9. Note: Please do not short connect terminal P24 and terminal COM. Otherwise, the driver will be damaged
2Internal power supply NPN mode: short connect terminal PLC-P24 Please do not short connect terminal PLC-COM. Otherwise, the driver will be damaged. 3Internal power supply PNP mode: short connect terminal PLC-COM. Please do not short connect terminal PLC-P24. Otherwise, the driver will be damaged. 4External power supply: remove off the shorting wire at terminal PLC-COM and terminal PLC-P24
Control of
user
Driver
Grounding for
shielding cable
Control of
user
Driver
NPN
NE200/300 Series Drive User Manual
Chapter 3 Installation 23
Y1/Y2, DO: The multi-functional output terminals adopt drive internal +24V
power supply wiring mode.
Fig.3-19 NE300 wiring mode of internal +24V power supply
Y1/Y2, DO: The multi-functional output terminals adopts external power
supply wiring mode
Fig.3-20 External power supply wiring mode
Analog input wiring mode
Fig.3-21 Wiring mode of analog input terminal
NE300 keypad wiring
Y1/Y2
24V
COM
Relay
Driver
Driver
24V
Y1/Y2
COM
External power
20-28V
Grounding for
shielding cable
Driver
GND
AI1
10V
NE200/300 Series Drive User Manual
24 Chapter 3 Installation
Fig.3-22 T568B standard
Pin No.
Color
1
White/Orange
2
Orange
3
Green/White
4
Blue 5 Blue/ White
6
Green
7
Brown/White
8
Brown
Table 3-2 T568B standard
The cables connecting keypad and control board use standard RJ-45 Interface, namely both sides are connected according to EIA/TIA568B standard. Users can make the cable by themselves or purchase general internet cable from market as keypad cable.

3.7 Control board schematic drawing

3.7.1 NE200 Control board schematic drawing

Fig.3-23 NE200 Control board schematic drawing
Control circuit terminal
Terminal to power board
Terminal to keypad
Jump switch
Earthing point
NE200/300 Series Drive User Manual
Chapter 3 Installation 25

3.7.2 NE200 DIP switch setting instruction

Fig.3-24 NE200 DIP switch setting

3.7.3 NE300 Control board schematic drawing

Fig.3-25 Control board schematic drawing
Note: X, Y and Z indicates the terminal, there are no the printing symbols. There are no printing symbols on 303PU01. X: Terminal for keypad Y: Terminal for writing the software. (2Pin terminal Z: DIP switches CN3: Terminals 1 for options PCBA CN5: Terminal for drive PCBA Earthing: Earthing point of control PCBA
3.8.2.1 NE300 Control circuit periphery accessories selection
Earthing
Standard Control Board303PU01
Y:Terminal
for writing
the software
(2Pin)
Z:DIP
switches
XTerminal to keypad
CN5Terminal to drive PCBA
CN3Terminal to options PCBA
Termina
Function
Default
AI2
I: 0~20mA input; V: 010V input
010V
AO1
I: 0~20mA output; V: 010V output
010V
NE200/300 Series Drive User Manual
26 Chapter 3 Installation
Terminal codes
Terminal
screw
Tightening
torque(N·m)
Wire
Spec.mm2
Type of Wire
10V, AI1, AI2, AO1, GND 485+, 485-
M3
0.50.6
0.75
Twisted pair
Shielded cable
24V, X1, X2, X3, X4, X5, COM, Y1, DO, COM, TA, TB, TC
M3
0.50.6
0.75
Shielded cable
3.8.2.2 NE300 DIP switch setting instruction
Fig.3-26 NE300 DIP switch setting
Terminal
Function
Default
AI2
I for current input(0/4~20mA); V for voltage input (010V)
010V
AO1
I for current output(0/4~20mA); V for voltage output (010V)
010V
RS485
User selected resistor
ON
NE200/300 Series Drive User Manual
Chapter 4 Operation and application 27

Chapter 4 Operation and application

4.1 Keypad

The keypad of NE200/300 series drives is the main unit of accepting command, displaying and modifying parameters. This series has 2 types of LED/LCD(Optional) keypads. LED keypad is with potentiometer and the LCD is MFK key without potentiometer. The LED keypad outline is as follows. LED keypad model nameNEF-LED01
LCD keypad model name (option)NEF-LCD01
Fig.4-1 Keypad Diagram

4.1.1 Keypad button description

Table 4-1 Button description
Keys
Name
Function
PRG
Programming key
Entry and exit of primary menu
ENTER
Confirmation key
Enter the next level menu or confirm the data setting
Increase key
Increase of the value or function code
4
NE200/300 Series Drive User Manual
28 Chapter 4 Operation and application
Decrease key
Decrease of the value or function code
>>
Shift key
Select the to be displayed parameters in turn under stop interface or running interface; Choose the to be modified digits when setting parameters.
RUN
Running key
Run the drive under keypad operation mode.
STOP
Stop/reset
Stop the drive at running status; Reset operation in the fault alarm status. Its function is limited to setting of code FE.02.
Knob
Potentiometer
Adjust setting value when potentiometer is set up as input. (For LED keypad)
MFK
Multi-Function key
MFK’s function is set by FE.01(0~7). The function is
different while FE.01 is equal to the different value. (For LCD keypad)

4.1.2 Keypad indicators

Table 4-2 Descriptions of Indicators
Symbol of Indicator
Meanings
Running Status
RUN
Light On: Running Light Off: Stopped Blinking: Running at zero frequency
FWD
Light On: Running forward steadily Light Off: Running reverse or stop Light Blinking: Speed up or speed down forward
REV
Light On: Running reverse steadily Light Off: Running forward or stop Blinking: Speed up or speed down reverse
TRIP
Light On: Trip (Fault) Light off: Normal
REMOT
Light On: Be controlled by the terminals Light Off: Be controlled by the keypad Blinking: Be controlled by communication.
Unit
Hz
Light On: Current frequency is running frequency Blinking: Current frequency is set frequency
A
Current unit indicator
V
Voltage unit indicator
RPM
Light On: Current speed is running speed Blinking: Current speed is set speed
%
Light on: Current value is running data
NE200/300 Series Drive User Manual
Chapter 4 Operation and application 29

4.1.3 Digital display zone

It is four-digit LED display. Be able to display setup frequency, output frequency, various monitoring data and alarm code
.

4.2 Function code viewing and modification

The keypad of the NE200/300 drive adopts three levels menu structure to carry out operations such as parameter setting. The three levels are: Groups of function code (level-1 menu) Function code (level-2 menu) Function code setup value(level-3 menu)
Note:
At level 3 menu, pressing PRG key or ENTER key can return to level-2 menu. The difference between them is that: Pressing ENTER will save the setup and return to the level 2 menu and then automatically shift to the next function code; while pressing PRG key will directly return to level 2 menu without saving the parameter, and stay at current function code. Below is the example of modifying the function code F9.01 from 10.00Hz to
20.00Hz. (The number of bigger font size refers to the blinking digit),
50.00
-F0- -F9-
F9.00
F9.01
10.0010.0020.00
F9.02
-F9-
PRG
ENTER
ENTER
>>
ENTER
PRG
PRG
Fig.4-2 Example of 3 levels menu operating
At level-3 menu, if the parameter has no blinking digit, it indicates that this function code cannot be modified. The possible reasons include:
1) The function code is an unchangeable parameter, such as actual detection
parameter, running record parameter, etc.
2) The function code cannot be modified in running status. It can be modified
only after the drive running is stopped.

4.3 Display status of keypad

Blinking: Current value is set data
Hz+A
Light on: Current value is PID running value Blinking: Current value is the setup PID value
NE200/300 Series Drive User Manual
30 Chapter 4 Operation and application
Displaying status include the stopped state parameter display, the running status parameter display, the function code edition display and the fault warning condition display etc.
1) The stop status parameter display
The drive is at stop state. The LED displays the stop state parameters. You can press “>>” to by turns display different parameters at stop state. (User can set which parameters are to be displayed at stop state in FE group function codes.)
2) The running state parameter display
The drive is running and the LED displays the running state parameters. You can press “>>” to display by turns the different running state parameters. (User can set which parameters are to be displayed at running state in FE group function codes.)
3) Fault and warning state
If the drive has detected a warning signal, it comes into warning state and blinks the warning code. If the warning signal disappeared, the warning code will automatically disappear. If the drive has detected an error, it comes into fault state and show the fault code steadily. And the indicator TRIP will light on. By pressing the “>>”key, user can view the parameters value of stop state. If you want to see the details of fault
information, press the “PRG” key to enter programming state and check
parameter group FF. User can reset the drive by STOP key, terminal or communication. If the fault signal still exists, the keypad keeps displaying the fault code.
4) Function code setting state
No matter it is under stop state, running state or warning/fault state, it is valid to press PRG key to enter parameter setting. The detailed setting method is instructed in this manual section-4.2.

4.4 Password Setting

The drive provides user password setting function. When FP.00 is set to non-zero value, which is the user password, the password protection turns valid after exiting the editing status. When the user goes to FP group again and
presses ENTER, it shows “0000”. Correct password should be input to unlock the
protection status to enter FP group again. To disable this password protection, user need to input the correct password first and then change FP.00=0.

4.5 Typical application

4.5.1 Open loop synchronizer debugging

1 To set the motor rated frequency (F0.10), motor type (F5.00=2), motor
rated power (F5.02), Polarity number (F5.01, it can be unset, but the rotate speed will not be accurate), rated current(F5.03) according to the motor nameplate.
2 To set the max/upper limit frequency (F0.11/F0.12) according to
working conditions. 3 To set the driver as open-loop vector control. (F0.01=1) 4 Tuning motor: Set F5.10=2 as rotary tuning, when the driver displays
-At- “on screen, press “RUN” button to start tuning.
NE200/300 Series Drive User Manual
Chapter 4 Operation and application 31
The driver will automatically save synchronous motor parameters F5.11~F5.14. When the motor is on rotary tuning, it must be noted that the acceleration and deceleration time are F0.19 and F0.20, which cannot be set too small. If rotary tuning is not allowed on site, static tuning(F5.10=1) should be conducted, the synchronous motor counter EMF shall be set manually
(F5.14). Note:There are two commonly used method to represent the synchronous motor counter EMF.
a) Volt per thousand rotation b) Rated frequency corresponds to the amount of voltage
NE series invertors uses the second representation. Note: when the motor is on rotary tuning or running, the motor occurs
unstable vibration, skip flow fault, current limiting fault, then need to turn down the current loop parameter properly.

4.5.2 Closed loop debugging

Incremental encoder parameters(F3.46=1)
1) To set some motor related parameters, like the motor type, rated power, rated current, motor polarity, rated rotation speed and so on according to motor nameplate.
2) To set encoder pulse number (F3.14), PG direction (F3.16), F3.54, F3.55, F3.56.
3) To set the control mode as closed-loop control mode (F0.01=2)
4) Waiting for the rotary tuning completed (if the encoder with Z signal, users do not have to set the encoder pulse, encoder direction related parameters, these parameters can be gotten from rotary tuning, but need to set the related function of parameter.
Resolver encoder(F3.46=3)
1) To set some motor related parameters, like motor type, rated current, motor polarity, rated rotation speed and so on according to motor nameplate.
2) To set the related parameters of resolver encoder. F3.47~F3.50.
3) To set the control mode (F0.01=2) as closed-loop control mode
4) Waiting for the rotary tuning completed.
Note:
a) The internal driver rated slip is calculated from the synchronous speed
of the motor (120*f/P)-rated rotation speed, so the set rated rotation speed should be lower than motor synchronous rotation speed.
b) When there is no Z signal in the encoder of asynchronous motor, the
encoder pulse can be set and run to 50Hz with an open loop to check the motor rotation speed and the running direction of encoder and motor.(F3.62=0 means same direction. F3.62=1 means that the
NE200/300 Series Drive User Manual
32 Chapter 4 Operation and application
direction between encoder and motor is reverse, you can set F3.16 or exchange the A/B wires to make it reverse.)
c) As to the 24V differential PG option, when the encoder is
non-differential, it can short connect the PG option terminals 24V,A+,B+, and the encoder terminals, A/ B/ Power/ Ground, should be accordingly connected to PG option’s terminals, A-/ B-/ 24V/ COM (or short connect PG option’s terminals, COM/ A-/ B- , and encoder terminals, A/ B/ Power/ Ground, short connect to PG card terminals A+, B+,24V, COM, which is mainly determined by the type of encoder.

4.5.3 DC common bus

A part of drivers of NE200/NE300 can share DC common bus, please to contact our technic support engineer if you want to share DC common bus. While sharing bus, the master driver is AC-in and AC-out, connect the DC bus of the slaver driver to the DC bus of the master. Warning! Usually, the power of the slaver driver can t be more than the 15% of the power of the master driver
because the rectifier and capacitor’s capacity limitation of the master driver.
NE200/300 Series Drive User Manual
Chapter 5 Parameter description 33

Chapter 5 Parameter description

Note:
The value in the “【】” indicates the factory default value of the parameter.

5.1 Group 0 Basic Function

F0.00 Reserved
Range:
Drive type display
0~10
This parameter of NE200 is reserved, show the type of drive of NE300. 0: Type G (Heavy duty) 1: Type P (Normal duty)
F0.01 Control mode
Range: 02 0
0: No vector Sensor vector control-1 This mode offers excellent vector control performance while insensitive to motor parameters. It is applicable to most applications. 1: No vector Sensor vector control-2 Precise speed sensor-less vector control technology realizes AC motor decoupling, enabling the DC motorization of running control. It’s applicable to high performance applications and features high precision of speed and torque and eliminates the need for pulse encoder.
2: Reserved 2: Vector control with encoder
3: V/F control It is applicable to the common applications where load requirement is not high such as fan and pump loads. It can be also used in applications where one drive drives multiple motors.
F0.02 Run command control mode
Range: 02 0
0: Operation keypad control (“LOCAL/REMOT” indicator OFF) Running commands are controlled by RUN and STOP keys on operation keypad. 1: Terminal control (“LOCAL/REMOT” indicator ON) Running commands are controlled by the multifunctional input terminals such as FWD, REV, JOGF, JOGR, etc. 2: Serial communication control (“LOCAL/REMOT” indicator blinks) Start & stop is controlled by the communication serial port. Modbus card is inbuilt.
F0.03 Frequency reference 1 (Freq. ref. 1)
Range: 08 0
5
NE200/300 Series Drive User Manual
34 Chapter 5 Parameter description
F0.04 Frequency reference 2 (Freq. ref. 2)
Range: 18 1
0: Digital setup
The initial value is the value of F0.06 “UP/DOWN preset frequency”. The
reference frequency value can be changed through the keys “▲” and “▼” on the keypad or multi-function terminals UP/DOWN (select through F0.08). The modification recording options in case of power failure is determined by the parameter F0.09. If setting is not saved in power failure, the reference frequency
value will recover to default value F0.06 “UP/DOWN Preset Frequency” upon
power recovery. 1: Terminal AI1 2: Terminal AI2 It means that the frequency is determined by the analog input terminal. AI1 refers to voltage input 0~10V. AI2 can be used as either voltage input of 0V~10V or
current input of 0/4mA ~20mA, which can be selected by the SW1/SW2 DIP switch on the control board.
3: PULSE setup
The reference frequency is given by the terminal pulse. Pulse signal
reference specification: voltage 9V ~12V and frequency range 0Hz ~200Hz.
The reference frequency is given by the terminal pulse. Pulse signal
reference specification: voltage 9V ~30V and frequency range 0kHz ~50kHz. 4: Communication It means that the frequency source is given by the host computer via the communication mode. 5: MS (Multi-step) Speed When this mode is selected, group F6 “Input Terminals” and Group F9 “Multi-step
speed and PLC” parameters shall be set to determine the relative relationship
between the reference signal and the reference frequency. 6: Programmable Logic Controller (PLC) When PLC mode is selected, Group F9 “Multi-step Speed and PLC” parameters shall be set to determine the reference frequency. 7: PID When PID is selected to be reference, Group F8 “PID Parameters” shall be set. The running frequency of the drive is the value after PID regulation. 8: keypad potentiometer Note In Freq. ref. 1, the Multi-step option is prior to other frequency reference options. If the terminal has selected multi-speed and active, the Freq. ref. 1 is determined by multi-speed no matter what value has F0.03 setup. In option of Freq. ref. 1+ the Freq. ref. 2, the UP/DOWN digital setting of Freq. ref. 1 will be Up/Down overlapped on Frequency ref.-2. And the F0.06 Up/Down preset value is invalid. Pulse reference can only be input from the multifunction input terminals X4 or X5.
NE200/300 Series Drive User Manual
Chapter 5 Parameter description 35
F0.05 Frequency setting selection
Range: 06 0
This parameter is used to select the frequency reference channel. The frequency reference is realized through combination of frequency setting 1 and frequency setting 2. 0: Frequency reference 1 The frequency reference is determined by the selected channel of freq. ref-1. 1: Frequency reference 2 The frequency reference is determined by the selected channel of freq. ref-2 2: Frequency reference 1 + Frequency reference 2 5: MIN (Frequency reference 1, Frequency reference 2) 6: MAX (Frequency reference 1, Frequency reference 2) The frequency reference is determined by frequency setting 1 and frequency setting 2 after the corresponding arithmetic. 3: Terminal switching between Freq. ref.1 & Freq. ref.2 The frequency reference can switch between the Frequency ref. 1 and Frequency ref.2 through the multifunction input terminal. When the terminal with “Freq. source switching” setting is active, the frequency reference is determined by freq. ref.-2. When the terminal with “Freq. source switching” setting is invalid
or the terminal has no setting of “Freq. source switching”, the frequency
reference is determined by frequency ref.-1. 4: Terminal switching between (Freq. ref.1+ Freq. ref.2) & Freq. ref.1 When the “Freq. source switching” terminal is invalid, the frequency
reference is determined by Freq. ref.1+ Freq. ref.2. When the “Freq. source
switching” terminal is active, the frequency reference is determined by Freq. ref.1
F0.06 UP/DOWN Preset Freq.
Range: 0.00Max frequency50.00Hz
When the frequency source has selected “Digital setup” or “Terminals UP/DN”, this function code is the initial value of frequency digital setup of the drive.
F0.07 Terminal UP/DOWN rate
Range: 0.0150.00Hz/s1.00Hz/s
Terminal UP/DOWN rate is the changing rate in terminal or keypad and setting.
F0.08 UP/DOWN function source select
Range: 021
This parameter is used to select the UP/DOWN channel in Digital frequency reference setting. 0: Active in both keypad and terminal UP/DOWN 1: Active only in keypad UP/DOWN 2: Active only in terminal UP/DOWN
F0.09 UP/DOWN data saving selection
Range: 020
0: Setting data saved in power failure This option means the frequency upon power recovery is the frequency after Up/Down setting before power failure.
NE200/300 Series Drive User Manual
36 Chapter 5 Parameter description
1: Setting not saved in power failure This option means that the frequency upon power recovery is the preset Up/Down frequency value in F0.06. The Up/Down modification before power failure is cleared. 2: Setting cleared to 0 after stop The Up/Down setting during running will be cleared after the drive stop. The frequency upon restart will be preset Up/Down frequency value in F0.06. And the modification part is cleared.
F0.10 Basic frequency
Range: 0.10550.0Hz50.00Hz
F0.11 Max frequency
Range: MAX [50.00Hz, Freq. upper limit, Reference frequency] 550.0Hz50.00Hz
F0.12 Freq. upper limit
Range: Freq. lower limitMax freq.50.00Hz
F0.13 Freq. lower limit
Range: 0.00Frequency upper limit0.00Hz
F0.14 Max output voltage
Range: 110440VDepend on model
The basic frequency (Fb) is the Min. output frequency when the drive output the Max. voltage. Usually, the motor rated frequency can be treated as basic frequency. The max frequency (F
max
) is the highest frequency that the drive can output. The frequency upper limit (FH ) and frequency lower limit (FL) are the maximum and minimum operating frequency of the motor set according to the production process technique requirements. The maximum output voltage Vmax is the output voltage when the drive is in basic operating frequency. Normally it is the motor rated voltage. The relationship of basic frequency, Max output frequency, frequency upper limit, the maximum output voltage and the Max. output voltage is shown in Fig.5-1
Fig.5-1 V/F characteristic diagram
F0.15 Carrier freq.
Range1.016.0kHzDepend on Model
This parameter is used to adjust the carrier frequency of the drive. The drive power ratings and according carrier frequency value range is show as following Tab.5-1. The adjustment of carrier frequency will have influences on motor noise, motor temperature rising, and drive temperature rising as shown on Tab.5-2.
Tab.5-1 Drive power ratings and according carrier frequency
V
Max
F
b
F
Max
F
L
F
H
Output
Frequency
Output voltage
NE200/300 Series Drive User Manual
Chapter 5 Parameter description 37
Model
Range
Factory default value
Type G: 2.211kW Type P: 415kW
1.016.0kHz
8.0kHz
Type G: 1522kW Type P: 18.530kW
1.010.0kHz
6.0kHz
Type G: 3045kW Type P: 3755kW
1.010.0kHz
4.0kHz
Type G: 5575kW Type P: 7590kW
1.06.0kHz
3.0kHz
Type G: ≥90kW Type P: ≥110kW
1.03.0kHz
2.0kHz
Table 5-2 the temperature influences of carrier frequency
Carrier frequency
Low → high
Motor noise
High →low
Motor temperature rise
High → low
Output current waveform
Poor → Good
drive temperature rise
Low →high
Leakage current
low → high
External radiation interference
low to high
F0.16 Carrier freq. auto-adjust
Range: 0~10
0: Disable (No- adjustment) Carrier frequency will not be adjusted automatically according to the temperature of drive. 1: Able (Auto-adjustment) Drive can automatically adjust carrier frequency through detection of temperature and the weight of load. The auto-adjusts is to keep drive running at light load with low noise and keep the temperature within control at heavy load, and thus maintain the reliable and continuous running.
F0.17 Keypad direction
Range: 0~10
This parameter is used to select the motor rotation direction when the drive running command channel is keypad. 0: Forward rotation 1: Reverse rotation
F0.18 Motor wiring direction
Range: 0~10
The drive output FWD direction might be different from FWD direction of motor. User can change the motor phases wiring sequence or change this parameter to make them agree with each other. 0: Positive sequence 1: Reversed sequence
NE200/300 Series Drive User Manual
38 Chapter 5 Parameter description
F0.19 Acc. time1
Range: 0.13600sDepend on model
F0.20 Dec. time1
Range: 0.13600sDepend on model
Acceleration time: The time that the drive accelerates from 0Hz to maximum output frequency (F0.11). Deceleration time: The time that the drive decelerates from maximum frequency (F0.11) to 0Hz. This series drive has defined 4 types of Acc/Dec time. Here, Acc/Dec time 1 is defined, and Acc/Dec time 2~4 can be defined in F2.03F2.08. User can select different Acc/Dec time by external multifunction input terminal. Acc.1/Dec.1 is taken as default.
Fig.5-2 Schematic diagram for acceleration/deceleration time
Note The default value of acceleration and deceleration time:
7.5kW and below: 6.0 seconds 11kW~22kW: 20.0 seconds 30kW~110kW: 60.0 seconds 132kW and above: 90.0 seconds

5.2 Start and stop group (F1)

F1.00 Start mode
Range: 010
F1.00 Start mode
Range: 020
0: Start directly The driver starts according to the start frequency (F1.01) and the start frequency holding time (F1.02). 1: DC brake first and then start at start frequency The driver performs DC braking first and then starts in mode-0. It is applicable to the applications of small inertia loads where reverse rotation is likely to occur.
Real ACC time
ACC time given
Real DEC time
DEC time given
F
Max
Output Frequency
F
set
Time
NE200/300 Series Drive User Manual
Chapter 5 Parameter description 39
2: Speed tracking and start
The driver detects the motor rotation speed firstly and then starts from the detected speed and Acc./Dec. to preset frequency. This realizes the smooth starting without impact. Note: The 18.5kW and above ratings has inbuilt speed tracking card.
F1.01 Start freq.
Range: 0.1060.00Hz0.50Hz
F1.02 Start freq. holding time
Range: 0.010.0s0.0s
Start frequency is the initial frequency at which the drive starts, see FS as shown in Fig.5-3; holding time of starting frequency is the time during which the drive operates at the start frequency, see t1 as shown in Fig.5-3:
Fig.5-3 Start frequency and Start frequency holding time
Note: Starting frequency is not restricted by the frequency lower limit.
F1.03 DC brake current at start (Rated current)
Range: 0.0%
G: 0.0~100.0%
P: 0.0~80.0%
F1.04 DC brake time at start
Range0.0~30.0s0.0s
These parameters are only valid when the start mode selects “DC brake first and
then start at start frequency” (F1.00=1). The higher the DC brake current is, the
higher the brake force. Note: If DC brake time or brake current is zero, the DC braking is invalid.
F1.05 Acc. /Dec. mode
Range: 010
0: Linear The output frequency increases or decreases linearly. The speed changes according to preset acceleration/ deceleration time. NE200/300 series has 4 types of Acc./Dec. time which can be selected via multifunctional input terminals.
Output
Frequency
Time
F
Max
F
s
t
1
NE200/300 Series Drive User Manual
40 Chapter 5 Parameter description
1: S-curve The output frequency increases or decreases along the S curve. S curve is generally used in the applications where smooth start and stop is required such as elevator and conveyor belt. Refer to F1.06 and F1.07 for S curve parameter setting.
F1.06 Time of S-curve initial stage
Range: 10.050.0%30.0%
F1.07 Time of S-curve rising stage
Range: 10.080.0%40.0%
The parameters of F1.06 and F1.07 are valid only when Acceleration /Deceleration mode is S-curve (F1.05=1) and F1.06+F1.07≤90%.
Starting stage of S-curve is shown in Fig.5-4 as “, where the changing rate of output frequency increases from 0; Rising stage of S-curve is shown in Fig.5-4 as “”, where the changing rate of output frequency is constant; Ending stage of S-curve is shown in Fig.5-4 as “”, where the changing rate of output frequency decreases to zero.
Fig.5-4 S-curve acceleration/deceleration
F1.08 Stop mode
Range: 0~20
0: Deceleration to stop After receiving the stop command, the drive reduces its output frequency according to the Dec time, and stops when the frequency decreases to zero. 1: Coast to stop After receiving the stop command, the drive stops PWM output immediately and the load gradually stop under the effect of mechanical inertia. 2: Deceleration +DC braking After receiving the stop command, the drive reduces its output frequency according to the Dec time and performs DC braking when its output frequency reaches the preset trigger frequency for DC braking. The relative parameters are defined in F1.09~F1.12.
F1.09 DC brake trigger frequency at stop
Range: 0.00~max frequency0.00Hz F1.10 DC brake waiting time at stop
Range: 0.00~10.00s0.00s
Freq.
Time
ACC time
DEC time
1
3
2
1
3
2
NE200/300 Series Drive User Manual
Chapter 5 Parameter description 41
F1.11 DC brake current at stop
Range:0.0~100.0%Drive rated current 0.0%
F1.11 DC brake current at stop (Rated current)
Range: 0.0% G Type: 0.0~100.0% P Type: 0.0~80.0%
F1.12 DC brake time at stop
Range: 0.0~30.0s0.0s
DC brake trigger frequency at stop is the frequency at which DC brake action begins during Dec-to-stop process. DC brake waiting time at stop: The holding time before doing the DC on brake. During this holding time the drive stops the output. It is used to prevent the over-current or over-voltage faults caused by DC brake when the speed is relatively high. DC brake current at stop: It refers to the DC braking injection amount. The higher this value, the stronger the DC brake effect. DC brake time at stop: It refers to the time span when DC braking is acting. Note: When DC brake current or DC brake time at stop is zero, it indicates there is no DC brake process.
F1.13 Energy consumption brake validity
Range: 0~10
0: Disabled 1: Enabled For large rotary inertia applications where rapid stop is required, the drive can be equipped with matched braking unit and braking resistors and proper braking parameters setting to realize fast braking and stop. Note: For NE300, is only valid for 22kW and above.
F1.14 Energy consumption brake action voltage
Range: 380V: 650~750V700V 220V: 360~390V380V
This parameter is to set the action voltage of DC bus for energy consumption brake. The proper setting can get effective brake of the load.
F1.15 Power failure and fault restart
Range: 0~30
0: Disable Drive will not automatically restart after power recovery until run command is given. 1: Enabled for power failure In case of power failure and power-on again, if STOP command is not given during restart-waiting time (F1.16), drive will restart automatically. 2: Enabled for fault After drive get faults during running, if the stop command is not given during fault stage or restart-waiting time (F1.16), the drive will restart automatically after fault reset. 3: Enabled for both power failure and fault The automatic restart function is enabled for both power failure recovery and faults reset situations as explained above. Note:
NE200/300 Series Drive User Manual
42 Chapter 5 Parameter description
The user shall be very caution in using this function. The inappropriate setting might cause damage of machinery or injury of human.
F1.16 Waiting time for restart
Range: 0.0~3600s0.0s
This parameter defines the waiting time before restart and over-voltage reset delay time.
F1.18 Rotational speed tracking
direction inspection
0~10
F1.19 Rotational speed tracking
direction inspection time
10~1000ms50ms
F1.18 and F1.19 only for NE300. F1.18 is for selecting whether the rotational speed tracking direction inspection is valid. 0: Disable 1: Enable Notes for F1.19: The motor start method is the DC brake mode while the motor frequency is below 2Hz, and the set value of DC brake current and brake time is not zero. The motor start method is normal from the zero frequency if the set value of the DC brake current and brake time is zero.

5.3 Auxiliary running function group (F2)

F2.00 Jog running freq.
Range: 0.0~50.005.00Hz
F2.01 Jog Acc. time
Range:
0.1~360.0s6.0s
0.0~3600.0s20.0s
F2.02 Jog Dec. time
Range:
0.1~360.0s6.0s
0.0~3600.0s20.0s
These parameters define the frequency and Acc/Dec time of the JOG operation. In JOG operation, the drive starts according to starting mode 0 (F1.00=0 direct start) and stops according to stopping mode 0 (F1.08=0 Deceleration to stop). The Jog acceleration time refers to the time the drive takes to accelerate form 0Hz to Max. output frequency F0.11; the jog deceleration time refers to the time the drive takes to decelerate from Max. output frequency F0.11 to 0Hz. Note: When the jog Acc./Dec. time is set to 0, the drive jog deceleration mode is “coast to stop”.
NE200/300 Series Drive User Manual
Chapter 5 Parameter description 43
F2.03 Acceleration time2
Range:
0.1~360.0s6.0s
0.0~3600.0s20.0s
F2.04 Deceleration time2
Range:
0.1~360.0s6.0s
0.0~3600.0s20.0s
F2.05 Acceleration time3
Range:
0.1~360.0s6.0s
0.0~3600.0s20.0s
F2.06 Deceleration time3
Range:
0.1~360.0s6.0s
0.0~3600.0s20.0s
F2.07 Acceleration time4
Range:
0.1~360.0s6.0s
0.0~3600.0s20.0s
F2.08 Deceleration time4
Range:
0.1~360.0s6.0s
0.0~3600.0s20.0s
These parameters are to define Acc/Dec time 2, 3 and 4 respectively (Acc/Dec time 1 is defined in F0.19 and F0.20). Acc/Dec time 1, 2, 3 and 4 can be selected via external multifunction input terminals. If all terminals related with Acc/Dec time are invalid, the drive will take Acc/Dec time 1 as Acc/Dec time. However, when the drive chooses PLC or JOG operation, Acc/Dec time will not be controlled by external terminals, but be set by parameter of PLC or JOG.
F2.09 Skip freq. 1
Range: 0.00~300.0Hz0.00Hz
F2.09 Skip freq. 1
Range: 0.00~320.0Hz0.00Hz
NE200/300 Series Drive User Manual
44 Chapter 5 Parameter description
F2.10 Skip freq. 2
Range: 0.00~320.0Hz0.00Hz F2.11 Skip frequency amplitude
Range: 0.00~15.00Hz0.00Hz
To avoid mechanical resonant, the drive can skip over some running points, which is called skip frequency. As shown in Fig.5-5. NE300 drives can set two skip frequency points, and the skip frequency amplitude can overlap or nesting. If overlapped, the range broadens. When all, skip-freq. points value, are set to 0.00 Hz, the jump function will be disabled. Only one, skip frequency1, point for NE200.
Fig.5-5 Skip Frequency
F2.12 Anti-reverse control
Range: 0~10
For some equipment, reverse operation may cause equipment damage. This function can be used to prevent reverse operation. 0: Reverse rotation allowed 1: Reverse rotation not allowed
F2.13 Fwd/ Rev switch dead-zone time
Range: 0.0~3600s0.0s
It refers to the transition waiting time at zero frequency in process of rotation direction switching, i.e. from forward to reverse or from reverse to forward, as shown Fig.5-6.
Fig.5-6 FWD/REV switching
F2.14 Freq. lower-limit treatment
Range: 0~10
This parameter is used to select the running status of the drive when the setup frequency is lower than the frequency lower limit. 0: Run with frequency lower limit
Effective freq. given
Set freq. signal
Skip freq. 1
Skip freq. 2
Skip freq.
amplitude
Skip freq.
amplitude
Forward
Reversal
Output freq.
Time
t
1
NE200/300 Series Drive User Manual
Chapter 5 Parameter description 45
1: Zero frequency operation
F2.15 Reserved
F2.16 Energy-saving control select
Range: 0~11
0: Disable 1: Enable
‘0’ means the energy-saving control mode is disabled. ‘1’ means the energy-saving control mode is enabled.
To adjust the output current to degrease the energy-saving of motor by inspecting the current of load while the motor is working in no-load or light-load status. Note: This function is enabled while controlled by V/F mode.
F2.17 AVR function
Range: 0~22
0: Disabled 1: Enabled 2: Disabled only at speed-down AVR means automatic output voltage regulation. When the input voltage deviates from rated value, AVR function can maintain constant voltage output. Normally AVR function is recommended to be active. At process of “deceleration to stop”
F2.18 Over modulation
Range: 0~11
0: Enabled 1: Disabled When the over modulation function is enabled, the drive voltage output capacity can be improved. However, if the output voltage is too high, the output current harmonics will increase.
F2.19 Droop control
Range: 0.0010.00Hz0.00Hz
When multiple drives drive the same load, the unbalanced load distribution due to difference speed causes the drive with faster speed to carry heavier load. The droop control characteristics makes the speed droop change along with the addition of load, which can lead to balanced load distribution. This parameter is used to adjust the frequency change value of the drive with droop speed.
F2.20 Fan control mode
Range: 010
0: Auto mode The fan always runs when the drive is running. After the drive stops three minutes, the internal temperature detection program will be activated to stop the fan or keep the fan running according to the IGBT’s temperature.
NE200/300 Series Drive User Manual
46 Chapter 5 Parameter description
1: Always Running The fan always runs when the drive is power on.
F2.21Instant-power-failure treatment
Range020
0: Disabled
1: Drop frequency (Reserved)
1: Drop frequency
2: Stop directly When the bus voltage is lower than the instant power failure frequency drop point, the drive stops according to stop mode (F1.08).
F2.22 Instant-power-failure freq. drop point
Range: 380V: 410600V420V 220V: 210260V230V
F2.23 Instant-power-failure freq. drop rate
Range: 1~800
These parameters define the value of the power failure frequency drop point and power failure frequency drop rate. The larger the value is, the greater the regulation intensity is, and the larger the parameter is, the more likely the current waveform will oscillate
F2.24 Motor speed display ratio
Range0.0500.0%100.0%
The motor speed display on the keypad is the actual motor speed×F2.24.
F2.25 UP/DOWN drop to minus frequency
Range011
0: Enabled 1: Disable
F2.26 ENTER key function
Range030
0: No special action 1: Fwd/Rev switching: When the keypad control the start and stop, press ENTER key under monitoring status will switch the rotation direction. 2: Under monitoring status, Run for forward; Enter for Reverse; STOP for stop. 3: Jog running Note: When MFK key defines RUN as forward, MFK as reverse, and STOP as stop (FE.01=7), the ENTER key shall not switch the rotation direction.
F2.27 Freq. resolution
Range010
0: 0.01Hz. The drive Max running frequency can be up to 320.0Hz. 1: 0.1Hz. The drive Max running frequency can be up to 3200.0Hz.
NE200/300 Series Drive User Manual
Chapter 5 Parameter description 47
F2.28 Acc./Dec time unit
Range010
0: 0.1s. The drive longest Acc./Dec time is 3600 seconds 1: 0.01s. The drive longest Acc./Dec time is 360 seconds
F2.29 High freq. modulation mode
Range010
0: Asynchronous modulation 1: Synchronous modulation When the frequency resolution is 0.01Hz, the regulation is fixed to be asynchronous modulation. When the frequency resolution is 0.1Hz, the regulation is asynchronous if this parameter F2.29=0; if this parameter F2.29=1, the carrier frequency will be modulated according to present running frequency.
F2.31 IO output Freq. baseline select while vector control
Range010
0: Baseline is the frequency after Acc./Dec. speed. 1: Baseline is the real output frequency.
This function code is used to select the baseline frequency of AO and IO input. Example: The 0~10V signal is the comparative linear output between the frequency after Acc./Dec. speed and frequency of max. output while F2.31=0. The 0~10V signal is the comparative linear output between the real output frequency and the max. output frequency while F2.31=1.
F2.32 PWM modulation mode
Range010
0: uplink 16Hz discrete modulation mode (5-stage mode), downlink 12Hz continuous modulation mode (7-stage mode) 1: fixed as z continuous modulation mode (7-stage mode)
F2.33 Threshold value of Zero Freq. running
Range0.0550.00Hz
F2.34 Range between start Freq. and threshold value of Zero Freq.
Range0.0550.00Hz
This function code is used for the ‘Range between start Freq. and threshold value of Zero Freq’ control.
Example: See fig. 5-7 The given channel of CCI current. Process of start: The drive will be started while CCI is up to or over Ib, and the given is up to fb, in the meantime, give the related frequency while the CCI value is ok after Acc. Speed during the Acc./Dcc. Duration given. Process of stop: The drive will be stopped till the CCI current is Ia, will not be stopped instantly while the CCI current is Ib. Note: fa is defined as ‘Threshold value of Zero Freq. running’ (F2.33), fb-fa is defined as ‘Range between start Freq. and threshold value of Zero Freq’ (F2.34).
NE200/300 Series Drive User Manual
48 Chapter 5 Parameter description
These function codes are used to avoid the start-stop of drive continually, used to realize the stand-by and sleep-mode.
Fig. 5-7 Range between start Freq. and threshold value of Zero Freq.

5.4 Vector Control Parameters (F3)

F3.00 Speed loop proportional gain 1
Range: 1~30001000
F3.01 Speed loop integral time 1
Range: 1~3000300
F3.02 Switching frequency 1
Range: 0.060.00Hz5.00Hz
F3.03 Speed loop proportional gain 2
Range: 1~3000800
F3.04 Speed loop integral time 2
Range: 1~3000200
F3.05 Switching frequency 2
Range: 0.060.00Hz10.00Hz
F3.00 and F3.01 are PI adjustment parameters when the running frequency is lower than switching frequency 1 (F3.02). F3.03 and F3.04 are PI adjustment parameters when the running frequency is higher than switching frequency 2. PI parameter of frequency range between the switching frequency 1 and switching frequency 2 is the linear conversion from two groups of PI parameters, as shown in the fig.5-8:
0
Real freq. given
Initial freq. given
f
a
Initial freq.
given
CCI current input
I
Max
I
min
I
b
I
a
I
c
F
min
F
Max
fa:Threshold value of Zero Freq. running
fb:fa+Range between start Freq. and
threshold value of Zero Freq.
fc:Freq. while CCI input current value is I
c
fbf
c
NE200/300 Series Drive User Manual
Chapter 5 Parameter description 49
Fig.5-8 Schematic diagram of speed loop PI parameter
The speed dynamic response characteristics of the vector control can be adjusted by setting the proportional coefficient and integration time of the speed regulator. Increasing the proportional gain or reducing the integration time can accelerate the dynamic response of the speed loop. However, if the proportional gain is too large or the integration time is too short, it will cause the oscillation of the system.
F3.06 Speed loop filtering time constant
Range: 0500ms 2ms/3ms
This parameter determines the value of speed loop filtering time and don’t need to be adjusted generally.
F3.07 Current loop proportional coefficient
Range: 060003000 F3.08 Current loop integral coefficient
Range: 060001500
These function codes define the current loop PID parameters; they influence directly the control precision and speed dynamic response and needs no adjustment generally.
F3.09 VC Slip compensation
Range: 0.0200.0%100.0%
When the load increase, the motor slip increases, and motor speed drops down. Using this slip compensation parameter, the motor speed can be maintained constant. The adjustment is instructed as follows: When the motor speed is lower than the target value, increase the vector control slip compensation value. When the motor speed is higher than the target value, decrease the vector control slip compensation value.
F3.10 Torque control
Range: 060
0: Torque control disabled When the torque control is disabled, the drive performs speed control. The drive outputs frequency according to the setup frequency command; and the output torque automatically matches the load torque. 1: AI1 as torque reference.
Freq.
PI parameter
(F3.00,F3.01)
(F3.03,F3.04)
(F3.02)
(F3.05)
NE200/300 Series Drive User Manual
50 Chapter 5 Parameter description
2: AI2 as torque reference. 3: Pulse input as torque reference.
4: Reserved
4: Pulse
5: Keypad digital setting as torque reference. 1~5: Torque control is active When the drive is in torque control, the drive output the torque according to the torque command which is defined in this parameter. And the output frequency will automatically matche to the load speed. But the output frequency is limited F3.12. Note: Analog and pulse input physical quantity is corresponding to torque setup Torque control is valid only when the Control Mode is sensor-less vector control-2 or vector control with encoder speed feedback.
F3.11 Torque digital setting
Range: 0.0200.0%50.0%
This parameter is used to define the value of torque digital setting.
F3.12 Torque control speed limit
Range: 050
This parameter is used to define the value of speed limit when the drive is running in torque control mode. 0: digital setting (F3.13) 1: AI1 2: AI2 3: PULSE input 4: Serial communication 5: Keypad potentiometer
F3.13 Torque control speed limit setting
Range: 0.00550.0Hz50.00Hz
Setting the value of torque control upper limit digital setting (F3.12 =0).
F3.14 Encoder pulse number
Range: 1~99991000
Setting the pulse quantity per circle of Encoder. Note: The operation status of motor will be abnormal if the pulse quantity of encoder set is not correct while controlled by the vector sensor. Please exchange the wiring of the A,B phases or adjust the value of F3.16 if the operation status of motor is abnormal still while the pulse quantity set is right.
F3.15 Motor and PG reduction ratio
Range: 0.010~50.0001.000
Set this function code as 1 if the PG is on the axle of motor. Set this function code as the real reduction gear ratio because there is a reduction gear ratio between motor axle and PG while the PG is not installed on the axel of motor.
NE200/300 Series Drive User Manual
Chapter 5 Parameter description 51
F3.16 PG direction
Range: 0~1 0
0: Forward 1: Reverse Don’t need to re-wiring while found the wiring sequence is not right, you can set this function code as 1.
F3.17 ACC/DEC limit controlled by PG
Range: 0~1 0
0: Limited This means the real output frequency will limit the frequency after ACC/DEC speed while controlled by PG option. 1: No limited
F3.18 SVC speed calculation filter
Range: 0~15 5
F3.19 SVC mode
Range: 0~1 0
F3.20 SVC mode2 flux weaken coefficient
Range: 20~500% 100%
F3.21 Field-weakening function
Range: 010
0: Disabled 1: Enabled
F3.22 Torque limit compensation coefficient while constant power output
Range: 60.0300.0%200%
This parameter is used to compensate the torque limit in constant power zone. Appropriate setting can improve the drive Acc/Dec time and output torque.
F3.23 Reserved
Reserved
F3.24 Torque ref. terminal single modulation
Range: 0.00~10.00%0.00%
F3.25 Torque ref. terminal total modulation
Range: 0.0~100% 50.0%
When the torque reference is digital mount, this parameter sets the single time modulation amount and total modulation amount.
F3.26 Torque limit in vector control mode
Range: 0.0300.0%150.0%
When it is asynchronous motor vector control, this value is the torque limit value of motoring and generating. When it is synchronous motor control, this value is the motor’s electric torque limit.
NE200/300 Series Drive User Manual
52 Chapter 5 Parameter description
F3.27 Torque boost cut-off frequency in torque control mode
Range: 0.0015.00Hz12.00Hz
F3.28 Torque boost amount in torque control mode
Range: 0.020.0%15.0%
This parameter is valid when vector torque control mode (F3.10 ≠0). It is used to boost the given torque volume at low speed, i.e. the final given torque value is calculated on given torque value, F3.27, and F3.28.
F3.31 Synchronous motor initial position detection
Range: 022
0Drive runs without detecting the motor rotor initial position 1In first-run after power on, the motor rotor initial position will be detected. If it is not first-run, the motor rotor initial position will not be checked. 2Detect the motor rotor initial position at every run.
F3.32 Synchronous motor initial position detection current
Range50120%90%
This is to set the detection current value for motor’s initial position. The smaller
the current value, the lower the detection noise; but too small current value might cause incorrect detection.
F3.33 Initial position detection pulse width
Range01200us0us
When the setting value of this parameter is 0, the detection pulse width of detection position is searched gradually from small pulse to larger pulse according to preset detection current value. When this parameter is not 0, the detection position pulse width will be calculated from this parameter and thus decrease the initial position detection time. This parameter will be automatically filled with actual pulse width after parameter tuning operation.
F3.34 Initial position detection pulse width actual value
Range01200us0us
This value is the actual pulse width in every time position detection.
F3.35 Synchronous motor braking torque limit
Range0.0300.0%150.0%
This parameter is to set the synchronous motor braking torque limitation. If the motor gets over-voltage fault during running, try to reduce this parameter setting value.
F3.36 Synchronous motor flux weakening mode
Range010
0Flux weakening mode is invalid 1Flux weakening mode is valid
NE200/300 Series Drive User Manual
Chapter 5 Parameter description 53
F3.37 Max flux weaken current
Range0100%50%
The actual running flux-weakening current is equal to the theoretical flux-weakening current by flux-weakening gain. The larger this parameter, the
better of the motor’s dynamic performance. But too high value will cause
vibration. Normally set it to 50.
F3.38 Flux weaken regulation proportional coefficient
Range030001500
F3.39 Flux weaken regulation integration coefficient
Range030001500
Adjust the flux weaken output current automatically according to the rotation speed, bus voltage and counter emf and so on. The larger proportional integral coefficient, the quicker speed responding, it causes the oscillation of motor while the motor works in flux weaken status.
F3.40 Synchronous motor low speed Min. current
Range0100%30%
Set the synchronous motor’s minimum current when the motor is at low speed.
(The percentage of motor’s rated current). This function is used to improve the load carrying performance at low frequency.
F3.41 Synchronous motor low speed carrier frequency
Range1.016.0KHz2.0KHz
This is to set the synchronous motor’s carrier frequency at low speed. When the motor is running at low speed, the lower carrier frequency will help to reduce the motor rotation pulsation, but it will come with some noise from changing carrier frequency. When this parameter setting is higher than preset carrier frequency (F0.15), this parameter will become invalid.
F3.42 Synchronous motor Min excitation current
Range-100100.0%8.0%
Set the Min. excitation current of synchronous motor.
F3.43 V/F Start switching Frequency
Range050.00Hz0
When the operating frequency is lower than F3.43, the converter runs constant current VF, and the current value is subject to F3.40. When the running frequency is higher than F3.43, the converter runs vector. This parameter is only available for NE200, but not for NE300
F3.44 Synchronous motor position evaluating low speed filter
Range210040
F3.45 Synchronous motor position evaluating high speed filter
Range210015
NE200/300 Series Drive User Manual
54 Chapter 5 Parameter description
The above 2 parameters are to set the motor’s position evaluating filtering coefficient. Normally take the default value.

5.5 V/F Control Parameters (F4)

F4.00 V/F curve setting
Range: 040
0: Linear V/F. It is suitable for common constant torque load. 1~3: Multi-power decreasing torque. It is suitable for the centrifugal loads such as fan and pump, as shown Fig.5-9. 4: Multiple-points V/F. It can be defined by setting F4.01~F4.06 parameters. as shown Fig.5-10
Fig.5-9 Torque-reducing curve
Fig.5-10Multi-points V/F curve
F4.01 V/F freq. F1
Range: 0.0~F4.0310.00Hz
F4.02 V/F voltage V1
Range: 0~100.0%20.0%
F4.03 V/F freq. F2
Range: F4.01~F4.0525.00Hz
F4.04 V/F voltage V2
Range: 0~100.0%50.0%
F4.05 V/F freq. F3
Range: F4.03~F0.1040.00Hz
F4.06 V/F voltage V3
Range: 0~100.0%80.0%
Six parameters of F4.01 to F4.06 define multi segments V/F curve, shown as Fig.5-10. The V/F curve is generally set in accordance with the load characteristics of the motor.
Input
volt.
Output freq.
Linear
1.5 power
1.2 power
2.0 power
Basic freq.(F0.10)
Max volt.(F0.14)
Output
freq.
Output
Volt.
100%
F4.01
F4.02
F4.03
F4.04
F4.05
F4.06
F0.10
NE200/300 Series Drive User Manual
Chapter 5 Parameter description 55
F4.07 Torque boost
Range: 0.0~30.0%0.0%
F4.08 Manual torque boost cutoff point
Range: 0.00~60.00Hz50.00Hz
To compensate the low frequency torque characteristics of V/F control, it can boost the output voltage when the drive is running at low frequency. When the torque boost is set to 0.0, the drive will adopt auto torque boost. Torque boost cutoff point frequency: Under this frequency, the torque boost is valid. If it exceeds this frequency point, the torque boost is inactive. Refer to Fig.5-11 for details.
Fig.5-11 Schematic Diagram for torque boost
Note: If the torque boost is set to be too large, the motor may be over heat, and the drive might get over-current fault. When the drive drives synchronous motor, manual torque boost function is recommended to be used and V/F curve should be adjusted according to the motor parameters
F4.09 Slip compensation coefficient
Range: 0.0~200.0%0.0%
F4.10 Slip compensation filtering time
Range: 0.012.55s0.20s
Setting the parameters can compensate the motor rotation slip due to change of load torque in the V/F control. With this compensation, the drive regulates the output frequency according to the change of load torque and thus increases the motor mechanical performance.
Output
Volt.
Output freq.
Manual torque boost cutoff freq.(F4.08)
Basic Freq.
(F0.10)
Manual
boost
(F4.07)
Max volt.
F0.14)
NE200/300 Series Drive User Manual
56 Chapter 5 Parameter description
Fig.5-12 Auto slip compensation
In rated torque state, the value of slip compensation is: Slip compensation gain (F4.09) × Rated slip (Synchronous speed- Rated speed) Motoring state: Increase the gain of slip compensation (F4.09) gradually when the actual speed is lower than the reference speed. Generating state: Increase the gain of slip compensation (F4.09)) gradually when the actual speed is higher than the reference speed. Note: The value of automatic slip compensation is related to the motor’s rated slip; therefore, the motor rated speed (F5.04) must be set correctly. Slip compensation is disabled when Slip compensation coefficient is set to “0”.
F4.11 V/F separation control voltage source
Range: 0~50
0: Disabled V/F separation control is disabled. The drive adopts common V/F control. 1~4: The output voltage and frequency are controlled separately. The drive outputs frequency according to the frequency setup and runs according to Acc./Dec time. But the voltage is regulated independently by the voltage reference source defined in this parameter and Acc./Dec according to F4.13(V/F separation voltage rising time). Note: Analog and pulse input maximum physical quantity is corresponding to maximum output voltage (F0.14).
F4.12 V/F separation voltage digital setting
Range: 0maximum output voltage 380V
This parameter is used to set the value of the output voltage when voltage source is digital setting in V/F separation control.
F4.13 V/F separation voltage rising time
Range: 0.0s1000.0s0.0s
This parameter is used to set the value of the output Voltage acceleration time when the voltage is controlled independently. The acceleration time is the time that the voltage accelerates from 0 to maximum voltage.
n
T
Compensation freq. f
Freq. after compensation
Synchronization speed
Load torque
NE200/300 Series Drive User Manual
Chapter 5 Parameter description 57
F4.14 V/F oscillation suppression
Range: 0.0s500.0sDepend on model
When this parameter is set to be 0, the V/F oscillation suppression is invalid. The larger this value, the stronger the suppression effect. Normally setting value of 100~300 will take suppression effect.

5.6 Motor parameters group (F5)

F5.00 Motor type
Range: 020
F5.01 Motor polarity number
Range: 2564
F5.02 Rated power
Depends on modelRange:
0.16553.5kW
0.4~999.9kW
F5.03 Rated current
Depends on modelRange:
0.01655.35A
0.1~999.9A
F5.04 Rated rotation speed
Depends on modelRange:
065535RPM
0~24000
F5.00F5.04 are used to set the controlled motor parameters. In order to ensure the control performance, please set F5.00F5.04 correctly by referring to values on motor nameplate.
Note On V/F control, the motor power shall be matched to the drive power. Normally
the motor power is only allowed to be 2 steps lower than that of the drive or 1 step higher. While in SVC or VC control, the motor power must exactly match that of the drive, otherwise, the control performance could not be ensured.
F5.05 No-load current I0
Depends on modelRange:
0.01655.35A
0.1~999.9A
F5.06 Stator resistance R1
Depends on modelRange:
165535 mΩ
NE200/300 Series Drive User Manual
58 Chapter 5 Parameter description
1~65535 mΩ (Drive rated power ≤22kW) 0.16553.5mΩ(Drive rated power>22kW)
F5.07 Leakage Inductive reactance X
Depends on modelRange:
0.01655.35mH
0.01655.35mH(Drive rated power≤22kW) 0.00165.535mH(Drive rated power>22kW)
F5.08 Rotor resistance R2
Depends on modelRange:
165535mΩ
165535mΩ(Drive rated power≤22kW) 0.16553.5mΩ(Drive rated power>22kW)
F5.09 Mutual Inductive reactance Xm
Depends on modelRange:
0.16553.5mH
0.16553.5mH(Drive rated power≤22kW) 0.01655.35mH(Drive rated power>22kW)
The above parameters are instructed in the fig.5-13 as below:
Fig. 5-13 Asynchronous motor equivalent circuit
In the Fig.5-13, R1, Xl, R2, X2, Xm, and I0 represent resistance of stator, leakage inductance of stator, resistance of rotor, leakage inductance of rotor, mutual inductance and no-load current respectively. The setting of F5.07 is the sum of leakage inductance of stator and leakage inductance of rotor. After motor rated power (F5.02) is changed, the drive will automatically change F5.03F5.09 to adapt to the rated motor power.
U
1
R
1
jX
1
R
m
X
m
jX
2
s
R
2
I
0
I
1
I
2
NE200/300 Series Drive User Manual
Chapter 5 Parameter description 59
F5.10 Auto tune
Range: 0~20
0: No operation 1: Static tuning, it is suitable to the situation as the motor is not easy to disconnect from the load. Action description: Set the function code to 1 and press RUN key for confirmation, and then the drive will conduct static tuning. 2: Rotary tuning To ensure the dynamic control performance of the drive, please select rotary tuning. During the rotary tuning, the motor must be disconnected with the loads (i.e. no-load). Action description: Set the function code to 2 and press RUN key for confirmation, the drive will conduct static rotary first, and then accelerate to 80% of motor rated frequency according to the acceleration time set in F0.19, holding this frequency for a while, and finally decelerate to zero speed according to deceleration time set in F0.20.
F5.11 Synchronous motor stator resistor Rs
Depends on modelRange
165535mΩ
165535mΩ (for drive≤22kW) 0.16553.5mΩ (for drive>22kW)
F5.12 Synchronous motor D-axis inductance Ld
Depends on modelRange
0.01~655.35mH
0.01~655.35mH (for drive≤30kW) 0.001~65.535mH(for drive>22kW)
F5.13 Synchronous motor Q-axis inductance Lq
Depends on modelRange
0.01~655.35mH
0.01~655.35mH (for drive≤30kW) 0.001~65.535mH(for drive>22kW)
F5.14 Synchronous motor counter EMF constant
Range0.1~6553.5V300.0V
Synchronous motor stator resistance is defined as half of the resistance of any two lines among U V W. Synchronous motor counter EMF constant is defined as voltage of any two lines among UVW when the motor is driven to rated frequency (F0.10).
NE200/300 Series Drive User Manual
60 Chapter 5 Parameter description
F5.11~F5.14 are the main parameters that affect the drive control performance. The values are automatically filled and saved accordingly after tuning operation until next time modification or next time parameter tuning. Note: Static tuning can only acquire F5.11~F5.13 values, while dynamic tuning can acquire all 4 values for F5.11~F5.14.

5.7 Input terminals group (F6)

F6.00 Terminal Command mode
Range: 030
This parameter defines four different control modes that control the drive operation through external terminals. 0: Two-wire mode 1 This mode is the most commonly used two-line mode. The forward/reverse rotation of the motor is decided by the commands of FWD and REV terminals, as shown in Fig.5-14.
Run command
Stop Forward Reverse
Stop
K2 K1
0 0
1 1
1 0
0 1
FWD REV COM
K1
K2
AC drive
Fig.5-14 Two-wire mode 1
1: Two-wire mode 2 In this mode, both function RUN (Run command) and F/R (Running direction) are used: If RUN is enabled, the drive will startup. If F/R is selected but disabled, the drive will run forward. If F/R is selected and enabled, the drive will run reverse. When F/R is not selected, the running direction is defined by function code (F0.17) Terminals wiring is show in Fig.5-15.
Run command
Stop
Forward
Reverse
Stop
K2 K1
0 0
1 1
1 0
0 1
RUN
F/R
COM
K1
K2
AC drive
Fig.5-15 Two-wire mode 2
2: Three-wire mode 1 In this mode, FWD and REV terminal control the forward and reverse direction of the motor; but the pulse signal is effective. HLD is holding terminal, i.e. when HLD is ON, the pulse signal of FWD and REV is hold; when HLD is OFF, the holding of FWD and REV is removed. The drive is stopped by disconnecting the HLD terminal. As shown in Fig.5-16
NE200/300 Series Drive User Manual
Chapter 5 Parameter description 61
FWD
REV
COM
SB3
SB1
AC drive
HLD
... ......
SB2
Fig.5-16 Three-wire mode 1
3: Three-wire mode 2 In this mode, RUN terminal control run command, while F/R decides the motor rotation direction. When HLD is ON, the RUN pulse signal is hold; when the HLD is off, the holding of RUN is removed. Stop command is conducted by disconnecting the HLD terminal. As shown in Fig.5-17. When F/R is not selected, the running direction is defined by function code (F0.17).
RUN
F/R
COM
K
SB1
AC drive
HLD
... ...
SB2
Run
direction
Forward Reverse
K
0 1
Fig.5-17 Three-wire mode 2
F6.01 X1 terminal function selection
Range: 0601
F6.02 X2 terminal function selection
Range: 0602
F6.03 X3 terminal function selection
Range: 0608
F6.04 X4 terminal function selection
Range: 06017
F6.05 X5 terminal function selection
Range: 06018
F6.06 AI1 terminal function selection
Range: 0600
F6.06 X6 terminal Function selection
Range: 0600
F6.07 AI2 terminal function selection
Range: 0600
F6.07 X7 terminal Function selection
Range: 0600
F6.08 Reserved
F6.08 X8 terminal function selection
Range: 0600
NE200/300 Series Drive User Manual
62 Chapter 5 Parameter description
F6.09 Reserved
F6.09 AI1 terminal function selection
Range: 0600
These parameters are used to set the functions of the multifunctional digital input terminals. Refer to table 5-3 for details. Note: For NE300, X6~X8 terminals are on the IO option PCB.
Table 5-3 Function list for digital input terminals
Value
Function
Description
0
NULL
This is to define invalidity of the terminal. The drive shall have no action even there is pulse input. The undefined terminals can be set into NULL to avoid mistaken action.
1
Forward (FWD)
Control the forward rotation and reverse rotation of the drive via the external terminals
2
Reverse (REV)
3
RUN
Control the drive running via the external terminal.
4
F/R running direction
Control the direction of the drive. inactive state: Forward; Active state: Reverse rotation.
5
HLD self-hold selection
Running signal self-hold terminal, refer to F6.00 terminal command modes setup.
6
Forward rotation Jog (FJOG)
Terminals JOG running. FJOG is prior. For details regarding frequency and Jog acceleration/deceleration time during the Jog running, refer to F2.00, F2.01 and F2.02 function codes.
7
Reverse rotation Jog (RJOG)
8
RESET (RST)
The terminal defined as RST can be used to do fault reset under fault status; In running status, activating this terminal will stop the drive according to preset stop mode.
9
Frequency source switching
When the frequency reference selection (F0.05) is set to 3, this terminal is used to switch Freq. reference1 and Freq. reference2. When the frequency source selection (F0.05) is set to 4, it performs switching between frequency ref. 1 and (freq. ref.1 + freq. ref.2)
10
Terminal UP
When the frequency is given by the external terminals, it is used to modify increment and decrement commands of frequency. When the frequency source is set to digital setup, it can be used to
11
Terminal DOWN
NE200/300 Series Drive User Manual
Chapter 5 Parameter description 63
Value
Function
Description
adjust up & down the setup frequency.
12
UP/DOWN setup clear
When the frequency reference is digital frequency reference, this terminal can be used to clear the frequency value modified by UP/DOWN and thus restore the reference frequency to the setup value of F0.06.
13
Coast to stop
The drive locks the output, and the motor stop process is beyond the drive control. It is the general method adopted when the load has high inertia and no requirement for the stop time.
14
DC injection braking
Once his terminal is enabled, the drive directly switches to the DC brake status. Intensity of DC brake follows DC braking current preset in F1.11.
15
Acceleration/deceleration prohibit
Protect the drive from affecting by the external signals (except stop command), and maintain the current frequency.
16
Drive running prohibit
Once this terminal is enabled, if the drive is on running status, the drive will coast to stop immediately, if the drive is on stop status, the drive cannot start. This is mainly used in applications where needs safety linkage.
17
Multi-step terminal 1
It can realize 16 steps of speed through the combination of digital status of these four terminals. Refer to attached table 5-4 for multi-speed setting details. K1~K4 correspond to terminals 17~20.
18
Multi-step terminal 2
19
Multi-step terminal 3
20
Multi-step terminal 4
21
Torque control disabled
The torque control of drive is inactive.
22
Acc/Dec time selector 1
It can select four types of speed-up/speed-down time through the combination of digital status of these two terminals. Refer to table 5-5 for details.
23
Acc/Dec time selector 2
24
External pause normally open input
The drive decelerates to stop, but al l the running parameters are saved in memory, such as PLC parameter, wobble frequency parameter and PID parameters. After this pause signal disappears, the drive restores to the status before stop.
25
External pause normally closed input 26
External fault normally open
After the external fault signal is sent to the drive, the drive reports fault and stops.
27
External fault normally closed
28
Run command switching
When Run command (F0.02) is 0 or 2,
NE200/300 Series Drive User Manual
64 Chapter 5 Parameter description
Value
Function
Description
to terminal
this terminal forces the run command switching to terminal control.
29
Run command switching to Keypad
When Run command (F0.02) is 1 or 2, this terminal forces the run command switching to keypad control.
30
External stop terminal; same to STOP key in keypad control mode.
This is to define an external stop terminal. In keypad control mode, this terminal can stop the drive. It is same as STOP key on keypad.
31
Reserved
Reserved
32
PLC status reset
Drive reset to the first step of PLC running.
33
Wobble freq. pause
The drive pauses at the present frequency. Once this terminal is disabled, the drive resumes the wobble frequency running.
34
Wobble freq. status reset
The drive returns to wobble center frequency.
35
PID pause
PID is inactive temporarily, and the drive maintains the current frequency output.
36
PID parameters switching
If the terminal is valid, PID control switches to second group PID parameters.
37
PID direction reversion
If this terminal is enabled, PID action direction is opposite to the direction set in F8.04.
38
Timing drive input
If the terminal is valid, drive starts the timing, otherwise zero-clear.
39
Counter signal input
The input terminal of counting pulse.
40
Counter clear
Clear the counter status.
41
Actual length clear
When the function terminal is enabled, actual length in fixed length control will be cleared to zero.
42
FWD running (FWD NC)
Control the drive forward or reversed by external terminals.
43
REV running (REV NC)
44
HLD (Normally Open)
Running signal self-hold terminal, refer to F6.00 terminal command modes setup.
45
Torque increase
When the torque reference is given by discrete signal, this function realizes the torque increasing, decreasing, and increment clearing. Refer to F3.24 and F3.25 for torque increment and adjustment range.
46
Torque increase clear
47
Torque decrease
48
One key recover user parameter (Valid in stop state)
If the user has done the parameter backup operation before, drive can be reset to those parameters setting by this
NE200/300 Series Drive User Manual
Chapter 5 Parameter description 65
Value
Function
Description
terminal under stop state.
49~56
Reserved
Reserved
57
Pulse input
High speed pulse input. This function is only valid for X4 & X5. And X4 has priority when there are 2 routes input.
58
Single phase
measuring speed input
Single phase measuring speed input. Only valid for X4 and X5. Take X4 as priority when there are 2 routes input.
59
Speed measuring
input A
Measuring speed input A. It is only valid for X4
60
Speed measuring
input B
Measuring speed input B. It is only valid for X5
Table 5-4 Multi-steps running selection guide
K4
K3
K2
K1
Freq. Setup
Parameter
OFF
OFF
OFF
OFF
F0.06
F0.06
OFF
OFF
OFF
ON
Multi-step freq.1
F9.00
OFF
OFF
ON
OFF
Multi-step freq.2
F9.01
OFF
OFF
ON
ON
Multi-step freq.3
F9.02
OFF
ON
OFF
OFF
Multi-step freq.4
F9.03
OFF
ON
OFF
ON
Multi-step freq.5
F9.04
OFF
ON
ON
OFF
Multi-step freq.6
F9.05
OFF
ON
ON
ON
Multi-step freq.7
F9.06
ON
OFF
OFF
OFF
Multi-step freq.8
F9.27
ON
OFF
OFF
ON
Multi-step freq.9
F9.28
ON
OFF
ON
OFF
Multi-step freq.10
F9.29
ON
OFF
ON
ON
Multi-step freq.11
F9.30
ON
ON
OFF
OFF
Multi-step freq.12
F9.31
ON
ON
OFF
ON
Multi-step freq.13
F9.32
ON
ON
ON
OFF
Multi-step freq.14
F9.33
ON
ON
ON
ON
Multi-step freq.15
F9.34
Table 5-5 Acc/Dec time selection table
Terminal 2
Terminal 1
Acc/Dec time selection
OFF
OFF
Acc time 1/ Dec time 1
OFF
ON
Acc time 2/ Dec time 2
ON
OFF
Acc time 3/ Dec time3
NE200/300 Series Drive User Manual
66 Chapter 5 Parameter description
ON
ON
Acc time 4/ Dec time4
F6.10 Analog Nonlinear Selection
Range: 0~30
0: None F6.11F6.15 are used to define AI1 inputs, F6.16F6.20 are used to define AI2 inputs, and F6.21F6.25are used to defined pulse inputs. They are independent and do not interfere to each other. 1: AI1 All the parameters from F6.11 to F6.25 are nonlinear setting points for the AI1 channel, as shown in Fig.5-18. The AI1 filter time F6.15 is taken. And AI2 setting points F6.16~6.20 are taken as 0.00~10.00V input and its corresponding
0.00~100.00%.setup value. And pulse input setting points are taken as
0.00~50.00 kHz and its corresponding 0.00~100.00% setup value. 2: AI2 All the parameters from F6.11 to F6.25 are nonlinear setting points for the AI2 channel, as shown in Fig.5-18. The AI2 filter time F6.20 is taken. And AI1 setting points F6.16~6.20 are taken as 0.00~10.00V input and its corresponding
0.00~100.00% setup value. And pulse input setting points are taken as
0.00~50.00 kHz and its corresponding 0.00~100.00% setup value. 3: Pulse input All the parameters from F6.11 to F6.25 are nonlinear setting points for the PULSE input channel, as shown in Fig.5-18. The pulse filter time F6.25 is taken. And AI1 setting points F6.16~6.20 are taken as 0.00~10.00V input and its corresponding 0.00~100.00% setup value. AI2 setting points F6.16~6.20 are taken as 0.00~10.00V input and its corresponding 0.00~100.00% setup value.
Fig.5-18 Analog input non-linear curve
F6.11 AI1 minimum input
Range: 0.0~F6.130.00V
F6.12 AI1 minimum Input corresponding setup
Range: -200%~ 200.0%0.0%
Analog input
Corresponding setup
F6.11 F6.13 F6.16F6.18 F6.21 F6.23
F6.12
F6.14
F6.17
F6.19
F6.22
F6.24
NE200/300 Series Drive User Manual
Chapter 5 Parameter description 67
F6.13 AI1 Max. input
Range:F6.1110.00V10.00V
F6.14 AI1 Max. Input corresponding setup
Range: -200%~ 200.0%100.0%
F6.15 AI1 input filter time
Range: 0.0150.00s0.05s
F6.16 AI2 Min. input
Range: 0.00F6.180.00V
F6.17 AI2 Min. Input corresponding setup
Range: -200%~ 200.0%0.0%
F6.18 AI2 Max. input
Range: F6.1610.00V10.00V
F6.19 AI2 Max. Input corresponding setup
Range: -200%~ 200.0%100.0%
F6.20 AI2 input filter time
Range: 0.0150.00s0.05s
F6.21 Pulse Min. input frequency
Range: 0.00F6.23 0.00kHz
F6.22 Pulse Min. input frequency Corresponding setup
Range: -200%~ 200.0%0.0%
F6.23 PULSE Max. input frequency
Range:F6.21~50.00kHz50.00kHz
F6.24 PULSE input Maximum Frequency Corresponding setup
Range: -200%~ 200.0%100.0%
F6.25 Pulse filter time
Range: 0.0150.00s0.05s
The above function codes define the relationship between the analog input (AI1, AI2, Pulse input) voltage and their corresponding value. When the analog input voltage exceeds the setup maximum input or minimum input range, the excess part will be calculated as maximum input or minimum input, as shown in Fig.5-19.
Fig.5-19 Analog input linear curve
F6.26 Terminal up/down initial increment
Range:0.00~10.00kHz0.01Hz
Min analog
input
Max analog
input
Max analog input corresponding setup
%
V
Min analog
input
Max analog
input
Max analog input corresponding setup
Min analog input
corresponding setup
%
V
Min analog input
corresponding setup
NE200/300 Series Drive User Manual
68 Chapter 5 Parameter description
Fig.5-20 Terminal up/down initial increment
F6.27 Freq. ref. 2 datum
Range: 0~10
When the frequency reference 2 is analog or pulse setting, its base frequency is defined by this parameter. 0: Maximum frequency 1: Frequency reference 1 Note: For NE200, select the frequency at 10V point as datum while this function code is the analog. For NE300, select the frequency datum while this function code is the analog and pulse.
F6.28 Delay duration of X1 terminal close
Range: 0.0~100.0s0
F6.29 Delay duration of X1 terminal open
Range: 0.0~100.0s0
F6.30 Delay duration of X2 terminal close
Range: 0.0~100.0s0
F6.31 Delay duration of X2 terminal open
Range: 0.0~100.0s0
F6.32 Pos. and Neg. logic terminal X 1
Range: 0000 Units: Logic of X1 terminal Tens: Logic of X2 terminal Hundreds: Logic of X3 terminal Thousands: Logic of X4 terminal
F6.33
Pos. and Neg. logic terminal X 2
Range: 0000 Units: Logic of X5 terminal Tens: Logic of AI1 terminal Hundreds: Logic of AI2 terminal
F6.33
Pos. and Neg. logic terminal X 2
Range: 0000 Units: Logic of X5 terminal Tens: Logic of X6 terminal Hundreds: Logic of X7 terminal Thousands: Logic of X8 terminal
Notes: Terminal 24252627424344 and 49 are not impacted by F6.33. Pos. logic of Xi terminal: Be valid while connecting between Xi and COM. Neg. logic of Xi terminal: Be valid while disconnecting between Xi and COM.
t
UpDown
Signal
F2.26
Freq.
Follow terminal Up/Down rate
NE200/300 Series Drive User Manual
Chapter 5 Parameter description 69

5.8 Output terminals group (F7)

F7.00 Reserved
F7.00 DO terminal output definition
Range:0~310
F7.01 Y1 terminal output selection
Range: 0311
F7.02 Reserved
F7.02 Y2 terminal output
selection
Range:0~310 F7.03 Relay 1 (TA/TB/TC) output selection
Range: 03116
F7.04 Reserved
Range:
F7.04 Relay 2 (BRA/BRB/BRC) output
selection
Range:0~310
Multifunctional output terminal function selection details are shown in Table 5-6.
Table5-6: Multifunction output terminals selection
Value
Function
Description
0
NULL
The output terminal does not have any function.
1
Run
It indicates the drive is running, and there is output frequency (can be zero), terminal outputs ON signal
2
Freq. arrival (FAR)
Please refer to F7.05 for details.
3
Freq. level detection 1 (FDT1)
Please refer to F7.06 and F7.07 for details.
4
Freq. level detection 2 (FDT2)
Please refer to F7.08 and F7.09 for details.
5
Freq. detection when speed-up
When the output frequency increases to the Up detection frequency (F7.10), terminal outputs ON signal.
6
Freq. detection when speed-down
When the output frequency decreases to Down detection frequency (F7.11), terminal outputs ON signal.
7
Zero-speed running
When the drive output frequency is zero and is still in running, the terminal outputs ON signal.
8
Zero-speed
When output frequency is zero, terminal outputs ON signal.
9
PLC circulation
When the simple PLC running completes one
NE200/300 Series Drive User Manual
70 Chapter 5 Parameter description
Value
Function
Description
completion
cycle, the terminal outputs ON signal.
10
Reserved
Reserved
10
Indicate the
running step (Co-setting in DO\Y1\Y2)
It indicates the present running step. Refer to table 5-7 for details.
11
Ready for running (RDY)
When the main circuit and control circuit is power up and there is no fault protection action, the drive is ready for running and then terminal output ON signal.
12
Timing arrival
When multi-function input terminal defined as No.38 is active, the drive starts timing. And when the running time exceeds the F7.14 preset time, it output ON signal. The timing is cleared to zero if the input terminal is invalid.
13
Counting arrival
When the counting value reach the value defined in F7.13, it output ON signal.
14
Reserved
Reserved
15
Preset torque value arrival
When motor's torque exceeds reference value (set by P7.12), terminal outputs ON signal.
16
Drive fault output
When the drive is faulty, it outputs ON signal.
17
Under voltage status output
When the drive is in under voltage status, terminal outputs ON signal.
18
Drive overload pre-warning
If the output current is higher than the value defined by FC.02 (Overload Pre-alarm detection level), terminal outputs ON signal.
19
Fixed-length arrived, output a high level signals
If the actual length exceeds the preset length, terminal outputs ON signal.
20
PID in dormancy
When PID is in dormancy, terminal outputs ON signal.
21
AI1>AI2
When AI1>AI2 value, terminal outputs ON signal.
22
AI1<F7.16
When AI1<F7.16, terminal outputs ON signal.
23
AI1>F7.16
When AI1>F7.16, terminal outputs ON signal.
24
F7.16<AI1<F7.17
When F7.16<AI1<F7.17, terminal outputs ON signal.
25
Frequency lower limit arrival
When the running frequency reaches frequency lower limit, terminal outputs ON signal.
26
Multi-pumps system auxiliary pump control signal
Auxiliary pump control signal for constant pressure water supply, refer to the parameter F7.28&F7.29 instruction for details.
NE200/300 Series Drive User Manual
Chapter 5 Parameter description 71
Value
Function
Description
27
Communication setting
This can define the terminal status, see the communication appendix for details.
28
Drive running time arrival
Output signal while the drive running time ≥F7.32.
29
Running in FWD
---
30
Running in REV
---
31
Instantaneous power loss processing
---
Table 5-7 PLC Running Steps
Y2
Y1
D0
Running Step
OFF
OFF
ON
T1
OFF
ON
OFF
T2
OFF
ON
ON
T3
ON
OFF
OFF
T4
ON
OFF
ON
T5
ON
ON
OFF
T6
ON
ON
ON
T7
F7.05 Freq. arrival (FAR) detection width
Range: 0.0010.00Hz2.50Hz
If the drive’s output frequency is within the detection width of frequency, a pulse
signal will be output, as shown in Fig.5-21.
Fig.5-21 FAR detection diagram
F7.06 Frequency detection value 1 (FDT1 level)
Range: 0.00600.0Hz5.00Hz
F7.07 Frequency detection lag 1(FDT1-lag)
Range: 0.0010.0Hz1.00Hz
F7.08 Frequency detection value 2 (FDT2 level)
Range:0.00~300.0Hz 5Hz/25.00Hz
F7.09 Frequency detection lag
Range: 0.0010.0Hz1.00Hz
Output freq.
Time
Freq. given
Detection signal
Time
Detection width
NE200/300 Series Drive User Manual
72 Chapter 5 Parameter description
2(FDT2-lag)
The setting of 2 frequency arrival detection values and the action relief lag value are shown as Fig.5-22 below.
Fig.5-22 FDT level and lag diagram
F7.10 Up detection frequency
Range: 0.00550.0Hz50.00Hz
F7.11 Down detection frequency
Range: 0.00550.0Hz0.00Hz
These two parameters define the detection trigger frequency value for increasing stage and decreasing stage respectively.
F7.12 Torque detection reference
Range: 0.0~200.0%100.0%
F7.13 Preset Count value
Range: 0~99990
F7.14 Preset Timing value
Range: 0.0~6553.0s0.0s
The above parameters define the detection trigger value for torque arrival detection, counting arrival detection, and timing arrival detection.
F7.16 AI1 compare threshold 1
Range: 0.0010.00V0.00V
F7.17 AI1 compare threshold 2
Range: 0.0010.00V0.00V
F7.18 Analog compare hysteresis error
Range: 0.0030.00V0.20V
These parameters define the value of the analog comparison. Please refer to table 5-6 (value 22-24) for details.
F7.19 AO function definition
Range: 0161
F7.19 AO1 function definition
Range: 0161
F7.20 Reserved
F7.20 AO2 output selection
Range: 0160
Output freq.
FDT level
Time
Time
FDT Detection
signal
FDT
hysteresis
NE200/300 Series Drive User Manual
Chapter 5 Parameter description 73
F7.21 Y1 function definition
Range: 0160
F7.21 DO output selection
Range: 0160
For NE200, AO analog output is 0-10V or 0-20mA, customer can exchange between them by switch on board. See fig. 5-9. For NE300, AO1 can output either 0~10V or 0/4~20mA, which can be selected by the jumper on the control board. These output selection details are shown as table 5-8:
Table 5-8 Analog output terminals selection
Value
Function
Description
0
NULL
NULL
1
Running frequency
0~maximun frequency
2
setting frequency
0~maximun frequency
3
output current
02* drive rated current
4
Output voltage
0Maximum Voltage
5
PID setup
010V
6
PID feedback
010V
7
Calibration signals
5V
8
Output torque
02*motor rated torque
9
Output power
02*Drive rated power
10
DC Bus voltage
01000V
11
AI1
010V
12
AI2
010V
13
Pulse input
0.150.0KHz
14
Communication setup
See Communication appendix
15
Reserved
---
16
Output current
0~2 time rated current
F7.22 AO output range selection
Range: 010
F7.22 AO1 output range selection
Range: 010
F7.23 Reserved
---
F7.23 AO2 output range selection
Range: 010
0: 010V / 020mA 1: 210V / 420mA
NE200/300 Series Drive User Manual
74 Chapter 5 Parameter description
F7.24 Gain of AO
Range: 1200%100%
F7.24 Gain of AO1
Range: 1200%100%
F7.25 Reserved
---
F7.25 Gain of AO2
Range: 1~200%100%
The drive output and user’s instrument systems are likely to produce error; you can adjust the output gain (AO1) for the meter calibration and the change of measuring range.
F7.26 Y1 Maximum output pulse freq.
Range: Y1 Minimum output pulse freq.~50.00kHz10.00kHz
F7.26 DO Max. output pulse freq.
Range: DO Minimum output pulse freq.~50Hz10.00kHz
F7.27 Y1 Minimum output pulse freq.
Range: 0.00Y1 Maximum output pulse frequency0.00kH
F7.27 DO Min. output pulse freq.
Range: 0.00DO Max. output pulse freq.0.00kH
The above parameters define output pulse frequency range.
F7.28 Auxiliary pump start lag time
Range: 099990s
F7.29 Auxiliary pump stop lag time
Range: 099990s
The above parameters define the delay time for auxiliary pump start and stop. Refer to Fig.5-23 for details.
Fig.5-23 Constant pressure water supply auxiliary pump control signal
F7.30 Y1 Max. output
Range: 0~10
Output freq.
F0.12
Time
Time
Auxiliary pump
control signal
F7.11
Auxiliary pump
start lag time
(F7.28)
Auxiliary pump
stop lag time
(F7.29)
NE200/300 Series Drive User Manual
Chapter 5 Parameter description 75
F7.30 DO Max. output
Range: 0~10
0: 50.00 kHz, Maximum output is 50kHz. 1: 500.0Hz, Maximum output is 500Hz
F7.31 FDT/RUN signal Jog selection
Range: 0~10
0: Include jog signal 1: Do not include jog signal
F7.32 Running time arrival setup
Range: 0~65530 min0
When the drive starts running, the counting starts. Once the counting reach to the value preset in this parameter F7.32, the drive stopping and internal counter remains. But the run command rising edge conducts the clearance to the counting.
F7.33 Running time arrival stop selection
Range: 0~10
0: Do not stop 1: Stop When the internal counter value ≥F7.32, the drive can be set to stop or not by this parameter. Note: When F7.32=0, this function is invalid.
F7.34 Ao1 4mA/2.00v adjustable datum
Range: 0.0~100%20%
F7.35 Reserved
F7.35 Ao2 4mA/2.00v adjustable datum
Range: 0.0~100%20%
F7.36 Digital output terminal Pos./Neg. logic
0000 Units: Logic of Y1 terminal Tens: Reserved Hundreds: Logic of Relay 1 Thousands: Reserved
F7.36 Digital output terminal Pos./Neg. logic
0000 Units: Logic of Y1 terminal Tens: Logic of Y2 terminal Hundreds: Logic of Relay 1 Thousands: Logic of Relay 2

5.9 PID Parameters (F8)

F8.00 PID setup channel selection
Range: 040
This parameter defined the given channel of PID target quantity
NE200/300 Series Drive User Manual
76 Chapter 5 Parameter description
0: PID digital setting, Determined by F8.02. 1: AI1 terminal Taken as 0~10V analog voltage input. 2: AI2 terminal Taken as 0 ~ 10V analog voltage or 0 ~ 20mA current input, which can be selected by DIP switch setting. 3: Pulse input 4: Serial communication The input value should in 0~100.00% (0~10000). 100.00% corresponds to the full scale of PID. Note: The relationship between AI1, AI2 & pulse frequency and the actual physical quantities can be seen in F6.10 ~ F6.26. Its full range (100.0%) of actual physical quantities correspond to the PID full range
F8.01 PID feedback channel selection
Range: 071
This parameter defined the PID feedback channel 0: AI1 terminal Taken as 0~10V analog voltage input. 1: AI2 terminal Taken as 0 ~ 10V analog voltage or 0 ~ 20mA current input, which can be selected by DIP switch setting. 2: Pulse input 3: serial communication The input value should in 0~100.00% (0~10000). 100.00% corresponds to the full scale of PID. 4: AI1-AI2 AI1-AI2 as PID feedback, if the result is negative the feedback value is negative 5: AI1+AI2 AI1+ AI2 as PID feedback, if the result is bigger than the actual physical quantities (100%) the PID feedback quantity is the 100% full range. 6: MAX (AI1, AI2) Take the larger one between AI1 and AI2 as the PID feedback. 7: MIN (AI1, AI2) Take the smaller one between AI1 and AI2 as the PID feedback.
F8.02 Analog PID digital setup
Range: 0.0999.950.0
When analog PID setting channel select the digital setting (F8.00 = 0), this parameter decide the setting value of the PID.
F8.03 Analog closed loop measuring range
Range: 1.0999.9100.0
It is the setting range for analog PID setting and PID feedback value, it must match the actual measuring range. The 100% physical quantity of AI1, AI2 and pulse input correspond to analog PID range.
F8.04 PID action direction
Range: 010
NE200/300 Series Drive User Manual
Chapter 5 Parameter description 77
0: Positive When the PID reference increases, the output frequency will increase and the controlled physical value will increase, such as water supply system. 1: Negative When the PID reference increases, the motor speed decreases with setting value such as refrigeration system.
F8.05 PID proportional gain 1 (KP1)
Range0.19.91.0
F8.06 PID integration time 1
Range0.00100.0s 10.00s/3.00s
F8.07 PID differential time 1
Range0.001.000.00s
F8.08 PID proportional gain 2 (KP2)
Range0.19.91.0
F8.09 PID integration time 2
Range0.00100.010.00s
F8.10 PID differential time 2
Range0.001.000.00s
The proportional gain (KP) is the parameter that decides the sensitivity of P action in response to the deviation. The bigger the proportional gain KP is, the more sensitive the system acts and the faster the drive responses. However, oscillation may easily come into being and regulation time extends. When KP is too big, the system tends to instability. When KP is too small, the system will slow, and responses lag. Use integration time to decide the effect of integral action. The longer the integration time, the slower the response, and the worse the ability of control external disturbance variation. The smaller the integration time is, the stronger the integral take effect. The smaller integration time can eliminate the steady state error and improve control precision, fast response. However, oscillation may easily occur, and the system stability decrease, if the integration time is too small. Differential time define the effect of differential action. The bigger differential time can attenuate the oscillation caused by P action more quickly when deviations occurs and short the regulation time. However, if differential time is too big, oscillation may occur. If the differential time is small, the attenuation effect will be small when deviations come into being and the regulation time is longer. Only the right differential time can reduce regulation time.
Note: NE200/300 drive has two sets of PID parameters, determined by F8.11. The first group PID parameters are taken as default.
F8.11 PID parameters switching
Range: 020
0: No switching, use the first group parameters 1: Switching by terminalto defined the multi-function terminals to switch two groups of PID parameters. 2: Auto-switching by deviationRefer to the F8.12, F8.13 instructions.
NE200/300 Series Drive User Manual
78 Chapter 5 Parameter description
F8.12 PID para. switching Deviation 1
Range: 0.0999.920.0
F8.13 PID para. switching Deviation 2
Range: 0.0999.980.0
Two groups of PID parameters can be switched by feedback deviation from the preset PID value. It is shown in figure 5-24 as below.
Figure 5-24 PID parameters switching
F8.14 PID delay time constant
Range: 0.00100.0s0.0s
The PID control frequency output delay time setting.
F8.15 Deviation limit
Range: 0.0999.9s0.2
When the deviation of feedback value from preset value lies within the deviation limit range, PID regulator stops adjustment. The proper settings of this function can reach a balance between system output accuracy and stability.
F8.16 PID output positive limit
Range: 0.00320.0Hz50.00Hz
F8.16 PID output positive limit
Range: 0.00600.0Hz50.00Hz F8.17 PID output negative limit
Range: 0.00600.0Hz0.00Hz
The two parameters are used to limit the output range of the PID regulator. When PID regulating is set to be the frequency reference, user can adjust the negative limit of the PID for reverse control, e.g. setting F8.17=30.00Hz to limit the reversed rotation within 30Hz. When PID and other channels are combined as frequency reference, the PID positive and negative limit can be adjusted according to actual application needs. For example, when PID and AI1 is overlapped to be frequency reference, and if system requires PID to conduct fine adjust of ±5V based on AI1, both F8.16 and F8.17 are to be set as 5.00Hz.
Deviation
Deviation 1
(F8.12)
Deviation 2
(F8.13)
PID code
1stgroup
PID code 2ndgroup
NE200/300 Series Drive User Manual
Chapter 5 Parameter description 79
F8.18 PID preset freq.
Range: 0.00550.0Hz0.00Hz
F8.19 Hold time of PID preset frequency
Range: 0.03600s0.0s
When the PID operation is start, the frequency will ramp up to the PID preset frequency (F8.18) according to the Acc time. The drive will keeps running at this preset frequency for a period of time set by F8.19, and then starts to conduct PID characteristic regulating as shown in Fig.5-25.
Fig. 5-25 PID preset frequency and holding time
Note: If you do not need the preset frequency function, set the preset frequency =0.
F8.20 Enable dormancy
Range: 010
0: Disabled 1: Enabled
F8.21 Dormancy delay
Range: 0999s120s
F8.22 Dormancy threshold
Range: 0.00320.0Hz20.00Hz
F8.23 Awaken threshold
Range: 0.0100.0%80%
When the output frequency is lower than the dormancy threshold value and keeps under this threshold for a lag time defined in F8.21, PID will enter the dormant state, which means the output frequency goes to 0Hz. The drive will quit the dormant state if PID feedback value is lower than awaken threshold (F8.23).
F8.24 PID feedback offline detection range
Range: 0~100.0%0.0%
F8.25 PID feedback offline detection time
Range: 0.0~50.0s2.0s
F8.26 PID feedback offline detection Min. Frequency
Range: 0.00~50.00Hz10.00Hz
Time
Preset freq.
Holding time
Preset freq.
Output freq.
NE200/300 Series Drive User Manual
80 Chapter 5 Parameter description
When the running frequency is higher than F2.26 and feedback signal is lower than F8.24 for a period of time defined by F8.25, the drive will give alarm (PID offline).

5.10 PLC and Multi-steps group (F9)

F9.00 Multi-step freq. 1
Range: 0.00Max frequency5.00Hz
F9.01 Multi-step freq. 2
Range: 0.00Max frequency10.00Hz
F9.02 Multi-step freq. 3
Range: 0.00Max frequency15.00Hz
F9.03 Multi-step freq. 4
Range: 0.00Max frequency20.00Hz
F9.04 Multi-step freq. 5
Range: 0.00Max frequency30.00Hz
F9.05 Multi-step freq. 6
Range: 0.00Max frequency40.00Hz
F9.06 Multi-step freq. 7
Range: 0.00Max frequency50.00Hz
Define Multi-steps frequency respectively, which can be used in Multi-step speed running and simple PLC running. For Multi-steps speed running, Multi-step speed frequency can be selected by multi-step terminals. While in simple PLC running, Multi-step speed frequency is decided by present running step. It is shown in Fig.5-26.
F9.07 PLC running mode
Range: 022
0: Single cycle 1 The drive stops automatically after one cycle of operation and will start when receiving RUN command again. 1: Single cycle and hold the final value The drive will hold the operating frequency and direction of last step after completing one cycle of operation. 2: Continuous operation The drive will start next cycle of operation automatically after completing one cycle of PLC operation until receiving STOP command.
F9.08 PLC restarting mode after interrupt
Range: 010
0: Restart from first step If the drive stops during PLC operation because of receiving STOP command or fault, or power loss, it will restart from the first step after restarting. 1: Continue from the step where the drive was interrupted When the drive stops during PLC operation because of receiving STOP command or fault, it will record the already running time of the present step. After restart, the drive automatically enters the specific step where it was interrupted and run the left time of this step with the step frequency.
F9.09 PLC status recorded or not at power failure
Range: 010
If F9.09 is set to 1, the PLC operating parameters such as the PLC operating step and PLC operating time will be saved when power loss. 0: Not save 1: save
NE200/300 Series Drive User Manual
Chapter 5 Parameter description 81
F9.10 Time unit select for each duration of PLC processing
Range: 010
Define the unit of PLC running time. 0: Second 1: Minute
F9.11 PLC step1 duration (T1)
Range: 0.1360020.0
F9.12 PLC step2 duration (T2)
Range: 0.0360020.0
F9.13 PLC step3 duration (T3)
Range: 0.0360020.0
F9.14 PLC step4 duration (T4)
Range: 0.0360020.0
F9.15 PLC step5 duration (T5)
Range: 0.0360020.0
F9.16 PLC step6 duration (T6)
Range: 0.0360020.0
F9.17 PLC step7 duration (T7)
Range: 0.1360020.0
Configure the running time of each PLC running step. If the running time of the step is set to 0, the drive will skip the step and run the next step, as shown in Fig 5-26.
F9.18 Step T1 program running setting
Range: 1F/r4F/r1F
F9.19 Step T2 program running setting
Range: 1F/r4F/r1F
F9.20 Step T3 program running setting
Range: 1F/r4F/r1F
F9.21 Step T4 program running setting
Range: 1F/r4F/r1F
F9.22 Step T5 program running setting
Range: 1F/r4F/r1F
F9.23 Step T6 program running setting
Range: 1F/r4F/r1F
F9.24 Step T7 program running setting
Range: 1F/r4F/r1F
F9.18~F9.24 are used to configure the direction and Acc/Dec time of each PLC running step. There are total 8 kinds of combinations could be selected, please refer to Table 5-9 for the details.
Table5-9 PLC program running setting
Combination
Acc/Dec time
Direction
1F
Acc/Dec time 1 FForward
1r
rReverse
2F
Acc/Dec time 2 FForward
2r
rReverse
3F
Acc/Dec time 3 FForward
3r
rReverse
4F
Acc/Dec time 4 FForward
4r
rReverse
NE200/300 Series Drive User Manual
82 Chapter 5 Parameter description
Fig.5-26 Simple PLC running
Note In Fig.5-26, f1f7, a1a7, d1d7 and T1T7 respectively correspond to step
frequency, Acc Time, Dec Time and running time.
F9.25 Current step running time
Range: 0.036000 F9.25 Current running step
Range: 170
F9.26 Current running step
Range: 170
F9.26 Current step running time
Range: 0.036000
Records the step that the PLC currently operating at. Records the operating time of the step that the PLC currently running at.
F9.27 Multi-step freq. 8
Range: 0.00Max frequency50.00Hz
F9.28 Multi-step freq. 9
Range: 0.00Max frequency50.00Hz
F9.29 Multi-step freq. 10
Range: 0.00Max frequency50.00Hz
F9.30 Multi-step freq. 11
Range: 0.00Max frequency50.00Hz
F9.31 Multi-step freq. 12
Range: 0.00Max frequency50.00Hz
F9.32 Multi-step freq. 13
Range: 0.00Max frequency50.00Hz
F9.33 Multi-step freq. 14
Range: 0.00Max frequency50.00Hz
RUN
f
1
f
2
f
3
f
4
f
5
f
6
f
7
a
1
a
2
a
3
d
3
a
4
d
5
a
5
a
6
d
7
T
1
T
2
T
3
T
4
T
5
T
6
T
7
NE200/300 Series Drive User Manual
Chapter 5 Parameter description 83
F9.34 Multi-step freq. 15
Range: 0.00Max frequency50.00Hz
Define Multi-steps frequency respectively, which can be used in Multi-step speed running. The terminals defined as multi-steps decide which step to be run. (See table 5-4)
F9.35 PLC Multi-step frequency 1 selection
Range: 040
F9.36 PLC Multi-step frequency 7 selection
Range: 040
Define Multi-step 1 & 7 frequency source. When the setting is 0, the first step and the 7th step speed is F9.00 and F9.06 0: Multi-steps running 1: AI1 terminal 2: AI2 terminal 3: keypad potentiometer 4: Pulse input

5.11 Wobble frequency running group (FA)

The wobble frequency running function is to make the drive output frequency wobbling up and down with the setup frequency as the center. The trace of running frequency at the time axis is shown in Figure 5-27, of which the swing amplitude is set by FA-00.When FA-00 is set to 0, indicating the swing amplitude is 0, the wobble frequency function is disabled.
Fig.5-27 Wobble frequency running diagram
FA.00 Wobble frequency amplitude
Range: 0.0~50%0.0%
FA.01 Jitter frequency
Range: 0.0~50% (Relative to FA.00) 0.0%
FA.02 Jitter Time
Range: 550ms5ms
Rising time
Wobble freq. operating cycle
Acc. time
Dec. time
Time
RUN
STOP
Jitter
Freq.
Jitter time
Output
freq.
Wobble freq. amplitude
NE200/300 Series Drive User Manual
84 Chapter 5 Parameter description
FA.03 Wobble freq. rising time
Range: 0.1999.9s5.0s
FA.04 Wobble freq. dropping time
Range: 0.1999.9s5.0s
Wobble frequency amplitude: The running amplitude around setup frequency. Wobble frequency rising time: The time takes from the peak base (lowest frequency in the swing) to the peak height (highest frequency in the swing). Wobble frequency dropping time: The time takes from the peak height (highest frequency in the swing) to peak base (lowest frequency in the swing).
FA.05 Amplitude setting mode
Range: 010
This parameter is used to select the benchmark quantity of the swing amplitude. 0: Relative to the central frequency It is variable swing amplitude system. The swing amplitude varies with the change of central frequency (setup frequency). 1: Relative to the maximum frequency It is fixed swing amplitude system. The swing amplitude is fixed.

5.12 Fixed-length control group (Fb)

FB.00 Preset length
Range: 0~65530 0
FB.01 Actual length
Range: 0~65530 0
FB.02 Pulse number per unit
Range: 0.1~6553.0100.0
The preset length (PB.00), actual length (PB.01) and number of pulse per-unit (FB.02) are mainly used for fixed-length control. The length is calculated via the pulse signal input by the discrete input terminal, which needs to set the corresponding input terminal to length count input terminal. And input terminal X4 or X5 is usually used when the pulse frequency is relatively high. Actual length = counted terminal input pulse number ÷ number of pulse per unit. When the actual length FB.01exceeds the preset length FB.00, the multifunction digital output terminal defined as “length arrival terminal” will output ON signal.

5.13 Protection and fault parameters group (FC)

FC.00 Motor overload protection mode
Range: 020
0: Disabled The overload protection is disabled. Be cautious to use this function because the drive will not protect the motor in case of overload. 1: Common motor (with low speed compensation) Since the cooling effects of common motor deteriorates at low speed (below 30 Hz), the motor’s overheat protecting threshold should be lowered, which is called low speed compensation 2: Variable frequency motor (without low speed compensation) The cooling effects of variable frequency motor are not affected by the motor’s speed, so low speed compensation is not necessary.
NE200/300 Series Drive User Manual
Chapter 5 Parameter description 85
FC.01 Electro thermal protective value
Range: 20110%100%
In order to apply effective overload protection to different kinds of motors, the Max output current of the drive should be adjusted, as shown in Fig.5-28.
Fig 5-28 Motor overload protection curve
Motor overload protection coefficient calculates
Cm=(A
max/Ao
)x100%
Cm: Motor overload protection coefficient
A
max
: the max allowed current of load
Ao: rated output current of drive Generally, the Max load current is the motor rated current.
FC.02 Pre-overload detection Level
Range: 30.0200.0%160.0%
FC.03 Pre-Overload detection time
Range: 0.080.0s60.0s
FC.02 defines the current threshold for overload pre-alarm protection. The setting range is a percentage value of rated current. FC.03 defines the time during which the drive current exceeds FC.02. If the drive continuous output current lager than FC.02 for some time defined in FC.03, the drive will output pre-alarm signal (OLP2).
FC.04 Current amplitude limit
Range: 022
During the Acc/Dec running, if the drive actual current exceeds the “Current amplitude limiting level” (PC.04), the drive stops the Acc/Dec process till the
current is lower than the limit point.
In the drive’s constant speed operating process, if PC.04 is set to 2, when the
drive actual current exceeds “Current amplitude limiting level” (PC.05), the drive
will reduce output frequency till the current gets lower than the limit point. Then the drive will accelerate to the previous constant speed status.
Motor overload Protective coefficient
100%
80%
1min
Time
Output
current
200%160%
NE200/300 Series Drive User Manual
86 Chapter 5 Parameter description
0: Invalid 1: Acc./Dec. valid; Constant speed invalid 2: Valid all the time
FC.05 Current amplitude limit level
Range: Type G: 80.0~200.0%160.0% Type P: 60.0~150.0%120.0%
This parameter is used to define the current limiting level.
FC.06 Over voltage stall function
Range: 021
Over voltage stall function selection. In Drive’s Acc/Dec process, if the bus voltage exceeds the over-voltage stall point defined by FC.07, the drive will stop Acc/Dec.
In the drive’s constant speed operating process, if the bus voltage exceeds the
stall overvoltage point, the drive will raise its output frequency. The Acc/Dec time is defined by Acc/Dec time 4. 0: Invalid 1: Acc./Dec. valid; Constant speed invalid 2: Valid
FC.07 Over-voltage point for stall
Range: 110.0~150.0% Bus voltage 140.0%
Define the stall over voltage point.
FC.08 Input phase loss detection level
Range: 1100%20%
FC.09 Input phase loss detection delay
Range: 2255s10s
Input phase loss detection function can detect loss of input phase or a serious imbalance in the three-phase input, in order to protect drive. If the input phase loss detection is too sensitive, you can appropriately increase the detection level (FC.08) and detection delay time (FC.09) and vice versa. When FC.08 is set to 100%, there is no input phase’s loss protection.
FC.10 Output phase loss detection
Range: 0~11
Output phase loss detect function can detect loss of output phase or a serious imbalance in the three-phase output, in order to protect drive and motor 0: Invalid 1: Valid
FC.11 Terminal close fault detection
Range: 0100
0: Invalid 1: Valid When the drive does not allow the restart after power failure recovery (F1.15=0 or 2), and at the same time the drive run command is controlled by terminal, the drive will give “terminal close fault” (EF2) if the FWD or REV terminal close after power recovery.
NE200/300 Series Drive User Manual
Chapter 5 Parameter description 87
FC.12 Fault auto reset times
Range: 0~100
FC.13 Fault auto reset interval
Range: 2.0~20.0s/time5.0s
Auto reset function can reset OC and OU according to preset reset times(FC.12) and reset interval (FC.13). During the reset interval, the drive stops output and runs at zero-speed. After the reset has been done, the drive will start according to preset starting mode. When the “reset times” is set to 0, the reset function is disabled, and the drive directly enters protection status.
NoteOnly OC, OU has auto reset function.
FC.14 Under-voltage fault treatment
Range:0~20
0: No treatment 1: Auto reset after power recovery (reset the UU fault only, do not run after fault reset.) 2: Auto run after power recovery (Auto run time interval is F1.16)
FC.15 Fast current limit
Range:50.0~100.0%80%
FC.16 Fast current limit time
Range:0.01~1.00s0.10s
This function is to protect the drive from tripping by fast current limit in case of large impact. If the drive is in fast current limit for a long time, the drive will give fast current limit fault (LC). The smaller the fast-current-limit value, the smaller loss to the IGBT is. But too small current limit value will also cause the abnormal working of the drive. When the fast-current-limit value is set to 100%, there is no fast-current limit function.
FC.17 Overvoltage suppression mode
Range:0.01~1.00s0.20s
When the motor is in generating status, the drive will raise the output frequency automatically to avoid tripping with over-voltage fault. When this parameter is set to 0.00Hz, the suppression function is disabled.

5.14 Communication parameters group (Fd)

Fd.00 RS485 communication
Range: 010
Disable 485 communication function can effectively reduce the interference, when MODBUS communication is not used. 0: RS485 Disabled 1: RS485 Enabled
Fd.01 Local address
Range12471
Define the drive’s communicating address. The address set to 0 is for the broadcast address to realize the PC broadcasting; when the drive address is 247, it will serve as the host on the network to broadcast to other slave machines to achieve synchronization function.
Note:
NE200/300 Series Drive User Manual
88 Chapter 5 Parameter description
Local address should be the unique one; it is the foundation to realize point-to-point communication between the host and drive. When the drive is set to be host, the broadcasting interval is the response delay time defined in Fd.05. If the response delay time is set to be too short, the communication networking might get abnormal.
Fd.02 Baud rate
Range: 053
Select the baud rate of serial communication. The master and the slave must keep the same baud rate setting. Otherwise, they cannot communicate normally. Higher baud rate could have a faster communication. 0: 1200bpS 1: 2400bpS 2: 4800bpS 3: 9600bpS 4: 19200bpS 5: 38400bpS
Fd.03 Parity bit setup
Range: 020
Choose the way of parity check. The master and the slave must keep the same parity check setting. Otherwise, they cannot communicate normally. 0: Even parity check 1: Odd parity check 2: No parity check
Fd.04 Communication Timeout time
Range: 0.0100.0s0.0s
Set communication timeout detecting time. Once establishing communications, if there is no data communicating within timeout detection time (Fd.04), the drive will report communication error. If Pb.03 is set to 0, this function is disabled.
Fd.05 Response delay
Range0500ms5ms
When the drive works as the slave, this parameter refers to the time from drive receiving the host PC command to returning response frame to it. When the drive works as the host, it refers to the interval of each broadcast
Fd.06 Communication Freq. setting coefficient
Range0.0~200.0%100%
When the frequency reference is set to be serial communication (F0.03=4), the frequency of the drive as a slave will be the host frequency by the coefficient defined in this parameter.
Fd.07 Communication interrupt detection mode
Range0~10
0: Time interval between 2 packets receiving. 1: Time interval of 0005H Add. data writing

5.15 Operation interface & display group (FE)

NE200/300 Series Drive User Manual
Chapter 5 Parameter description 89
FE.00 Parameter display
Range: 010
0: Normal 3-levels menu display 1: Only display modified parameters
Note: In normal status, menu show as 3 levels. The parameters without modification will be not shown while only showing the parameters modified, the customer can be easy to look at them.
FE.01 MFK Key function selection
Range: 070
0: MFK inactive 1: JOG running Used to start Jog running, the direction is set by function code F0.17 2: FWD/REV switching MFK key is used to switch the running direction between forward and reverse. It is equivalent to modify F0.17, but it will not be saved when power lost. 3: UP/DOWN clear Used to Clear the frequency set by external terminals (UN/DOWN) , this is equal to the function of terminal “UP/DOWN clear command” 4: Running command switch MFK key is used to switch the run command mode between keypad control and remote command control (terminal command channel or serial communication command channel). And the current run command mode must be terminal or communications, otherwise this option is invalid 7: RUN for FWD, MFK for REV, STOP for STOP
FE.02 STOP key function selection
Range: 032
This parameter is used to define the STOP key functions, including stop and fault reset. 0: Active only in the keypad control mode 1: STOP key stop function active in the terminal/communication control mode 2: STOP key fault reset function active in the terminal/ communication control mode 3: STOP key stop and fault reset function active in the terminal/ communication control mode
FE.03 Running freq. (Hz) (before compensation)
Range: 032
FE.04 Running freq. (Hz) (after compensation)
Range: 030 FE.05 Reference frequency (Hz, blinking)
Range: 031
FE.06 Output current(A)
Range: 032
FE.07 Bus voltage (V)
Range: 033
FE.08 Output voltage (V)
Range: 030
FE.09 Output torque (%)
Range: 030
NE200/300 Series Drive User Manual
90 Chapter 5 Parameter description
FE.10 Reference torque (%, blinking)
Range: 030
FE.11 Rotate speed (r/min)
Range: 030
FE.12 Reference speed (r/min blinking)
Range: 030
FE.13 Output power (kW)
Range: 030
FE.14 AI1 (V)
Range: 030
FE.15 AI2(V)
Range: 030
FE.16 Analog PID feedback
Range: 030
FE.17 Analog PID setup
Range: 030
FE.18 Terminal status (no unit)
Range: 030
FE.19 Actual length
Range: 030
FE.20 Reference length
Range: 030
FE.21 Linear speed (m/s)
Range: 030
FE.22 External counting value (no unit)
Range: 030
These parameters define the display in stop and running monitoring condition. 0: No display 1: Display only in stop process 2: Display only during running 3: Display in stop and running
Explanation In stop process monitoring, if no parameter is set to show in monitor state,
reference frequency will be displayed. In running monitoring state, if no parameter is set to be displayed, the output frequency (before compensation) will be displayed. The indication for analog PID reference and analog PID feedback is “Hz” +” A”, For PID reference, the Hz+A is blinking; while for PID feedback, the Hz+A is constant ON. The terminal status is shown by four digits of LED without unit indicator, the specific meaning shown in figure 5-29.
Fig 5-29 Terminal status diagram

5.16 Running history record group (FF)

FF.00 Type of latest fault
Setting range: 027NULL
FF.01 Output freq. at latest fault
Setting range: 0Frequency upper
NE200/300 Series Drive User Manual
Chapter 5 Parameter description 91
limit0.00Hz
FF.02 Reference frequency at latest fault
Setting range: 0Frequency upper limit0.00Hz
FF.03 Output current at latest fault
Setting range: 02* drive rated current0.0A
FF.04 Bus voltage frequency at latest fault
Setting range: 01000V0V
FF.05 Running status at latest fault
Setting range: 030
FF.06 Fault history 1 (Last One)
Setting range: Same with FF.00
FF.07 Fault history 2
Setting range: Same with FF.00
Memorize the types of the latest 3 faults (See “chapter 7: fault/ alarm information
table” for the details of faults). And record the output frequency, reference
frequency, output current, DC bus voltage and running status of the latest fault for troubleshooting.
FF.08 Total power on time
Range: 065530h0
FF.09 Total running time
Range: 065530h0
The total boot time and runtime accumulated automatically by Drive.
FF.10 Reserved
Reserved
FF.11 Software version number of control board
Range: 1.0010.001.00
FF.12 Non-standard version number of software
Range: 02550
These two parameters indicate the software version of the product and also the non-standard version, which helps to identify the product.
FF.13 Heat sink temperature
Range: -30.0120.0°C FF.13 IGBT temperature
Range: 0.0140.0°C
Record the real time temperature of the heat sink/IGBT.
FF.14 Flux current
Range: -200.0200.0°C FF.15 Torque current
Range: -200.0200.0°C
FF.17 Accumulated kilowatt-hours (Upper 16 bits)
Range: -200.0200.0°C
FF.18 Accumulated kilowatt-hours (Low 16 bits)
Range: -200.0200.0°C
NE200/300 Series Drive User Manual
92 Chapter 5 Parameter description

5.17 Protection Parameters (FP)

FP.00 User password
Range: 0~99990
Any non-zero number can be set as password to activate the protection function. After this operation, password is required to access to Group PF. Otherwise all parameters of Group PF cannot be accessed. 0000: Clear the previous setup user password and disable the password protection function.
FP.01 Parameter write-in protection
Range: 0~20
0: All parameters are allowed to be modified 1: Only FP.01 and FP.03 can be modified In addition to this function code and FP.03, all parameters can be read but cannot be modified. 2: All parameters aren’t allowed read In addition to this function code and FP.03, all parameters value is shown as "0000" and cannot be modified, this can prevent irrelevant person to check.
FP.02 Parameter initialization
Range: 0~20
0: No operation 1: Clear fault history When FP.02 is set to 1, the fault records of FF.00~FF.07 will be cleared. 2: Restore to default setting When FP.02 is set to 2, the parameters (except running history and user password) are restored to defaults.
FP.03 Parameter copy
Range: 0~20
0: No action 1: Parameters download According to the type parameter of the keypad preservation (whether has motor parameters, etc), automatically download to the control board 2: Parameters upload (except motor’s parameters)
All parameters will upload to EEPROM of keypad except “Running history record”
(Group FF) and “motor parameters” (Group F5).
3: Parameters upload (all parameters)
All parameters will upload to the EEPROM of keypad except “Running history
record” (Group FF).
FP.04 Parameter upload protection
Range: 010
0: Protection enabled When the keypad has stored effective parameters, uploading parameters to keypad is invalid and report “copy fault” 1: Protection disabled No matter the panel has stored effective parameters or not, the uploading operation will upload the present parameters from the control board to the keypad panel.
NE200/300 Series Drive User Manual
Chapter 5 Parameter description 93
FP.05 G/P model selection
Range: 010
0: Type G 1: Type P
FP.07 User parameters backup
Range: 010
0: Invalid 1: Valid With this function, the operator can make backup for the parameters after setup.
FP.08 User parameters recovery
Range: 010
0: Invalid 1: Valid With this function, the operator can restore the parameters setup to the backup parameters.
Loading...