This parameter enables the user to assign the automation with a name other than the original, to facilitate identication (e.g. northern gate).
A name comprising maximum 24 characters, including spaces, is admitted.
Series
This parameter can be set with a value from 0 to 63; the factory setting is “0”.
The series is a number that has to be assigned to each gearmotor, receiver or other device potentially connectable on a BusT4 network, to dene its “clas-
sication area”. Subsequently, when using automations in a complex system, all devices with the same series number can be controlled simultaneously.
Address
This parameter can be set with a value from 1 to 128; the factory setting is “2” for Receivers and 3 for Control Units.
The address is a number that has to be assigned to each gearmotor, receiver or other device potentially connectable on a BusT4 network, to distinguish it
from other devices in a series. Therefore all devices within a series must have a different address from one another.
Group
This parameter can be set with a value from 1 to 14, or “None”; the factory setting is “None”.
The function enables the user to assign a number to a device to be controlled (for example a gearmotor or other device potentially connectable to a BusT4
network), which enables this device to belong to a specic “command group”.
Several devices, even if they belong to different series, can form part of the same group. Up to 14 groups of devices can be created and, in particular, the
same device may be inserted in 4 different groups.
In a device network, use of this function enables:
- simultaneous control of different devices inserted in a group, even if some of these belong to different series;
- use of a single receiver, installed in one of the devices belonging to the group, to control all the devices belonging to the group.
Firmware version (not modiable)
This function enables the display of the version of the rmware present in a device.
Hardware version (not modiable)
This function enables the display of the version of the hardware present in a device.
Serial number (not modiable)
This function enables the display of the serial number identifying a specic device. This number is different for each device, even if of the same model.
Password management:
This function is useful to restrict access by unauthorised personnel to all or some of the programming functions of a device. If a device is password protected,
the user must perform the “log in” procedure to proceed with a programming session, followed by the “log out” procedure on completion of the programming
procedure. Note – the “log out” procedure enables the user to prevent access by unauthorised personnel, by re-activating the existing password. Caution!
– In programming the password on multiple devices (for example, on the Oview, control unit, receiver, etc.), it is advisable to use the same password for all
devices, including the Oview. This will avoid the need to repeat the login procedure each time the device is changed during use of Oview and the connected
Software.
Two types of password can be programmed on the devices (including Oview).
- the user password, containing 6 alphanumeric characters maximum. Caution! – Do not use uppercase letters.
- the installer password, containing 6 alphanumeric characters maximum. Caution! – Do not use uppercase letters.
CONTROL UNIT FUNCTIONS
Installation
Bluebus search (0x0a)
This function enables start-up of the procedure for learning the devices connected to the Bluebus input and the HALT input of the control unit of an automa-
tion. Important – To activate the device search, press “Start”.
Position programming
• reverse rotation (0xa3)
This parameter type is ON/OFF; the factory setting is “OFF” (standard motor rotation). This function
reverses the rotation direction of the encoder to align it with the direction of the motor; the factory setting is “OFF” (standard rotation direction of the encoder).
Important – When you modify this parameter, you must then run the open/close position learning procedure.
• open (0x18)
This function is expressed in encoder pulses. During an opening manoeuvre, this enables programming of the precise point (position) of the door opening
travel limit. To do so, use the hold-to-run ”open” and ”close” buttons; this enables you to determine the desired position and save it with the “OK” button. If
the motor has a mechanical limit switch, the position is not displayed.
• open deceleration (inverters only) (0x24)
This function is expressed in encoder pulses. During the opening manoeuvre this enables programming of the precise point (position) at which the door should
start decelerating before reaching the limit switch. To do so, use the hold-to-run ”open” and ”close” buttons; this enables you to determine the desired position and save it with the “OK” button.
• partial open 1 (0x1b)
This function is expressed in encoder pulses. During the opening manoeuvre this enables programming of the precise point (position) at which the door stops
travel (partial open). To do so, use the hold-to-run ”open” and ”close” buttons; this enables you to determine the desired position and save it with the “OK”
button. If the motor has a mechanical limit switch, the position is not displayed, but the closing time is displayed instead.
• partial open 2 (0x1c)
This function is expressed in encoder pulses. During the opening manoeuvre this enables programming of the precise point (position) at which the door stops
travel (partial open). To do so, use the hold-to-run ”open” and ”close” buttons; this enables you to determine the desired position and save it with the “OK”
button. If the motor has a mechanical limit switch, the position is not displayed, but the closing time is displayed instead.
• partial open 3 (0x1d)
This function is expressed in encoder pulses. During the opening manoeuvre this enables programming of the precise point (position) at which the door stops
travel (partial open). To do so, use the hold-to-run ”open” and ”close” buttons; this enables you to determine the desired position and save it with the “OK”
button. If the motor has a mechanical limit switch, the position is not displayed, but the closing time is displayed instead.
• close deceleration (inverters only) (0x25)
This function is expressed in encoder pulses. During the closing manoeuvre this enables programming of the precise point (position) at which the door should
start decelerating before reaching the limit switch. To do so, use the hold-to-run ”open” and ”close” buttons; this enables you to determine the desired position and save it with the “OK” button.
• close (0x19)
This function is expressed as a percentage. During a closing manoeuvre, this enables programming of the precise point (position) of the door closing travel
limit. To do so, use the hold-to-run ”open” and ”close” buttons; this enables you to determine the desired position and save it with the “OK” button. If the
motor has a mechanical limit switch, the position is not displayed.
Deceleration (inverters only) (0x44)
This parameter can be set with a value from 20% to 100%; the factory setting is 20%. This function enables you to program the speed of the motor while
learning the open and close positions and during the nal phase of deceleration. Important – Always set this to the minimum speed required to operate the
door. Setting too high a speed can make it difcult to precisely determine the stop position.
Braking level (0x35)
This parameter sets a delay for the activation/deactivation of the brake when starting a cycle. The range is 0 to 2.5s; the factory setting is 0s.
The parameter is divided into 4 items numbered 1 - 4 at the top right of the Oview screen. Select the delay time in “ms” for brake deactivation for:
- Value 1: start opening
- Value 2: start closing
- Value 3: stop opening
- Value 4: stop closing
Board version (0x03)
This displays the type of control unit and motor. The following board versions are available:
This function enables the user to delete the conguration of a control unit and the relative stored data, selecting items from a series. These items are:
❒ bluebus devices – enables deletion of the conguration of the Bluebus devices and the STOP input;❒ positions – enables deletion of all memorised positions;❒ function values – enables deletion of all values and settings of functions envisaged on the control unit;❒ all – deletes all data in the control unit memory, except for the reserved parameters: series, address, hardware version, software version, serial number. It
also loads the default values for sectional doors and shutters.
❒ all fast action doors (0x7C) – deletes all data in the control unit memory, except for the reserved parameters: series, address, hardware version, software
version, serial number. It also loads the default values for fast action doors.
Basic parameters
Automatic closure (0x80)
This parameter is ON/OFF; the factory setting is “OFF”. The function enables the auto close function after an open manoeuvre in the control unit. If the function
is active (ON) the automatic closure manoeuvre starts at the end of the wait time programmed in the function “pause time”. If the function is not active (OFF)
the Control unit operation mode is “semiautomatic”. Note: auto close does not operate in hold-to-run close mode.
Pause time (0x81)
This parameter is expressed in seconds and can be set with a value from 0 to 250 sec.; the factory setting is 40 sec. This function enables programming on
the Control unit of the required wait time which must pass between the end of an Opening manoeuvre and the start of a Closing manoeuvre. IMPORTANT
– This function is only enabled if the “automatic closure” function is active.
Close again after photo (0x86)
• active (0x84)
This parameter is ON/OFF; the factory setting is “OFF”. The function enables the automation to remain in the Open position only for the time required for a
vehicle or person to transit. When this interval elapses the Automatic Closure manoeuvre is activated automatically, which in turn is started after a time as set
in the function “wait time”. Important – When the function is active (ON), operation varies according to the parameter set in the function “Automatic closure”:
❒ with the function “Automatic closure” active (ON), the Opening manoeuvre is stopped immediately after disengagement of the photocells and, after the
wait time set in “wait time”, the automation starts up the Closure manoeuvre.
❒ with the function “Automatic closure” not active (OFF), the automation completes the entire Opening manoeuvre (even if the photocells are disengaged
beforehand) and, after the wait time set in “wait time”, the automation starts up the Closure manoeuvre.
Caution! – The function “close again after photo” is disabled automatically if a Stop command is sent during the manoeuvre in progress, to stop the manoeuvre. It does not work in hold-to-run close mode.
• mode (0x86)
This parameter is factory set on the mode “open until disengage”. The function has 2 operating modes:
❒ open all – when this mode is enabled, if the safety devices (photocells) are activated during a Closure manoeuvre, the automation starts to perform a
complete Opening manoeuvre. On the other hand, if the safety devices are disengaged, the automation starts the automatic closure manoeuvre after the
wait time as programmed in the function “closure delay time” has elapsed;
❒ open until disengage – when this mode is enabled, if the safety devices (photocells) are activated during a Closure manoeuvre, the automation starts to
perform an Opening manoeuvre, which proceeds until the photocells are disengaged. At this point the manoeuvre is shut down and the automation starts
the closure manoeuvre after the wait time as programmed in the function “closure delay time” has elapsed. Note – If the “Automatic closure” function is
not active, the Control unit switches to “open all” mode.
Wait time (0x85)
This parameter is expressed in seconds and can be set with a value from 0 to 250 sec.; the factory setting is 5 sec. This function enables programming on
the Control unit of the required wait time to pass between the end of an Opening manoeuvre and the start of a Closing manoeuvre.
Always close (0x87)
• active (0x86)
This parameter is ON/OFF; the factory setting is “OFF”. This function is useful in the event of a power failure, even brief. In fact, during an Opening manoeuvre
if the automation shuts down due to a power failure and the function is active (ON), the Closure manoeuvre is performed normally when the electrical power
is restored. On the contrary, if the function is not active (OFF), the automation remains stationary when the power is restored. Note – For reasons of safety,
when the function is active, the Closure manoeuvre is preceded by a wait time as programmed in the function “pre-ashing time”. Note: auto close does not
operate in hold-to-run close mode.
• mode (0x8a)
This parameter is factory set on the mode “always close”. The function has 2 operating modes:
❒ standard – For this mode, refer to the function “active” under the item “always close”;❒ save automatic closure - Enabling this mode, you may obtain two results when power is restored after a power failure: a) execution of automatic closure,
observing the time as programmed in the function “pre-ashing time”, if the timeout interval of this time was in progress at the time of the power failure;
b) execution of closure manoeuvre if the automatic closure was in progress at the time of the power failure and the manoeuvre had not been completed.
Note – If the automatic closure manoeuvre was cancelled before the power failure (for example, by sending the Halt command), the Closure manoeuvre is
not performed when the power is restored.
Wait time (0x89)
This parameter is expressed in seconds and can be set with a value from 0 to 20 sec.; the factory setting is 5 sec. This function enables programming on the
Control unit of the required wait time to pass between the end of an Opening manoeuvre and the start of a Closing manoeuvre.
Pre-ashing (0x93)
• active (0x94)
This parameter is ON/OFF; the factory setting is “OFF”. When this function is set to “ON” it enables the activation of a ashing time, which passes between
activation of the ashing light and the start of an Opening or Closing manoeuvre. This time is adjustable and useful to for an advance indication of a hazardous
situation. Important – When this function is not active (OFF), the ashing light is switched on at the same time as the start of the manoeuvre.
• time in opening (0x95)
This parameter is expressed in seconds and can be set with a value from 0 to 10 sec.; the factory setting is 3 sec. This function programs the ashing time
which indicates the imminent start of an Opening manoeuvre: it is associated with the pre-ashing function.
• time in closing (0x99)
This parameter is expressed in seconds and can be set with a value from 0 to 10 sec.; the factory setting is 3 sec. This function programs the ashing time
which indicates the imminent start of a Closing manoeuvre: it is associated with the pre-ashing function.
Block automation (0x9a)
This parameter is ON/OFF; the factory setting is “OFF”. This function enables automation operation to be disabled, by setting the value to “ON”. In this case
no type of command is acknowledged or performed, with the exception of “High priority step-step”, “Release”, “Release and close” and “Release and open”.
Block keys (0x9c)
This parameter is ON/OFF; the factory setting is “OFF”. This function disables operation of the keys present on the control unit.
Test mode (0xA9)
This parameter automatically sets the behaviour of inputs and outputs when using specic safety devices. The following modes are available at this time:
0: all inputs and outputs use their factory settings or settings made by the installer;
1: operation with photocell barriers with test device.
This mode uses ING1 input (as the photocell input) and the trafc light OUT-TL1 output. When starting a closing manoeuvre, a test is run which activates the
output and checks that the input deactivates. Normal operation is then restored. Important – if the mode is reset to 0, OUT-TL1 returns to its set value, while
ING1 is set to not connected to avoid unintentional commands.
Brake mode (0x36)
This parameter sets the parking brake's operating mode. There are 3 modes:
0: brake disabled (not powered);
1: brake negative. During the manoeuvre, the brake is powered to release it and allow the motor to run. When the manoeuvre is completed,
power to the brake is shut off, thus automatically engaging it.
2: brake positive. During the manoeuvre the brake is not powered and the motor is free to run. When the manoeuvre is completed, the brake
is powered up, thus engaging it.
3: brake negative. For 208V three-phase power
4: brake positive. For 208V three-phase power
The factory setting is mode 1.
Short inversion value (0x31)
This parameter is expressed in seconds and can be set with a value from 0,1 to 5 seconds; the factory setting is 3 seconds. This function enables programming of the brief inversion activated by the control unit as a safety manoeuvre following detection of an obstacle or delivery of a “Stop” command.
Exclusion position (0xa4)
This parameter is expressed in seconds and can be set with a value from 0 to 300 seconds; the factory setting is 50 seconds. Note – the “0” setting is considered the fully closed position of the automation. This function enables the programming of the maximum limit, over which the control unit automatically
disables the inversion manoeuvres envisaged in the obstacle detection functions, if the latter are active.
FOTO exclusion position (0xaf)
This parameter is expressed in seconds and can be set with a value from 0 to 4000 seconds; the factory setting is 0 seconds. Note – the “0” setting is considered the fully closed position of the automation. This function programs the maximum limit within which the control unit automatically inhibits monitoring
of the photocells (FOTO address).
Position compensation (0xfc)
• automatic compensation (0x97)
This parameter is ON/OFF; the factory setting is “OFF”. This function is useful if using a 8K2 resistive type or OSE optical type sensitive edge. The function
enables recovery of the extension of metal ropes of the automation usually caused by wear over prolonged operation. If the sensitive edge trips at the fully
closed position, the control unit will stop the motor a few encoder pulses (compensation value) earlier the next time the door is closed.
• compensation value (0x2e)
This parameter can be set with a value from 0 to 20; the factory setting is “2”. This parameter enables programming of a number of encoder pulses on the
control unit, required for the “position compensation” function. This parameter is only effective if the parameter “automatic compensation” is active (ON).
Work time (0xa7)
Sets the maximum duration of the manoeuvre. When it times out, the manoeuvre is aborted.
• mode
❒ manual: in this mode, the work time is taken from the congurable parameter “maximum work time”.❒ automatic: in this mode, the control unit measures the time taken to complete the manoeuvre after position learning, and sets a slightly higher value.
• maximum time
This parameter ranges from 0 to 120s, and represents the maximum time within which a manoeuvre must be completed in the manual mode; the default
value is 60s.
❒ value 1: opening time❒ value 2: closing time
Advanced parameters
INPUT conguration
This item covers the commands available and associable with inputs 1-2-3 present on the control unit of an automation. The commands available for each
input are described in Table 1; while the command categories and relative operating modes are described in Tables 1a, 1b, 1c etc. Important – For correct
operation of the control unit, the command programmed on an input must be associated with the corresponding command category and lastly the required
operating mode.
For congure an input, proceed as follows:
01. In the section “Advanced parameters” select the item “input conguration” and then the input to be programmed. Select the command and conrm with
“OK”.
02. Then, still in ”Advanced parameters”, select “command conguration” and select the category of the command selected in step 01. Finally, select the
operating mode. There are three available inputs:
• Input 1
This programs Input 1, by assigning a command from among those listed in Table 1. Input 1 is factory set to “step-by-step” command, with the “Industrial
Mode” operating mode for sectional doors – with “open - stop - close - open” mode for high-speed doors.
• Input 2
This programs Input 2, by assigning a command from among those listed in Table 1. Input 2 is factory set to “open”, “opening” category and “open-stopopen” mode.
• Input 3
This programs Input 1, by assigning a command from among those listed in Table 1. Input 3 is factory set to “close” command, with the “Industrial Mode”
operating mode for sectional doors – with “open - stop - close - open” mode for high-speed doors.
TABLE 1: INPUT CONFIGURATION
COMMANDCOMMAND CATEGORYDESCRIPTION
No commandDoes not perform any command.
Step-by-stepStep-by-step Program the desired mode from
those given in Table 1-A (“Command conguration”
> “step-by-step” > operating mode ...)
Partial open 1Partial open Program the desired mode from those
BlockWhen this command is sent, the control unit is
ReleaseWhen this command is sent, the control unit is re-
Timed Courtesy lightThis command enables activation of the courtesy
When this command is sent the control unit activates the application to complete the Opening manoeuvre until the position is reached as set in the
function “partial open 2”(Control unit functions >
installation > positions > partial open 2). Input congured as normally open.
When this command is sent the control unit acti-
vates the application to complete the Opening manoeuvre until the position is reached as set in the
function “partial open 3”(Control unit functions >
installation > positions > partial open 3). Input congured as normally open.
This command is factory assigned to Input 2, in
mode “open - stop - open”. When this command
is sent the control unit activates the application to
complete the Opening manoeuvre until the position
is reached as set in the function “opening” (Control
unit functions > installation > positions > opening).
Input congured as normally open.
This command is factory set to Input 3, with operating mode “close - stop - close”. When this command is sent the control unit activates the application to complete the Closing manoeuvre until the
position is reached as set in the function “closing”
(Control unit functions > installation > positions >
closing). Input congured as normally open.
When this command is sent, the control unit stops
the manoeuvre in progress gradually and in a short
time (not instantly). Input congured as normally
open.
When this command is sent, the control unit acti-
vates the application to complete the next manoeu-
vre following the previous one (or still in progress)
according to the sequence of manoeuvres as envisaged in the programmed sequence. Important
– This command is performed even if the control
unit is set with the command “block” (see Table 1).
Input congured as normally open
When this command is sent the control unit acti-
vates the application to complete the Opening manoeuvre until the position is reached as set in the
function “opening” (Control unit functions > installation > positions > opening). Input congured as
normally open.
When this command is sent the control unit acti-
vates the application to complete the Closing manoeuvre until the position is reached as set in the
function “closing”(Control unit functions > installation > positions > closing) and the automation is
then blocked. Input congured as normally open.
blocked and does not perform any type of command, with the exception of “High priority stepstep”, “Release”, “Release and close” and “Release
and open”. Input congured as normally open.
leased restoring normal operating status (all commands sent can be performed). Input congured as
normally open.
light on the control unit and that programmable on
Output 1. The courtesy light remains active for the
time as programmed in the function “courtesy light
time” (Control unit functions > advanced parameters
> output conguration > courtesy light time). For the
courtesy light connected to Output 1, the command
is only enabled when this output is programmed in
“courtesy light” mode (Control unit functions > advanced parameters > output conguration > output
1 (ash) > courtesy light). Note – When the courtesy
light is already active and the “courtesy light timer”
is sent again, the time set in “courtesy light time” is
reset. Input congured as normally open.
Courtesy light: on/offThis command enables activation and deactivation
Apartment blockStep-by-step Program the required operating
StopStop in closure Program the desired mode from
Emergency stop (0x28) When this command is sent, the door opens re-
Interlocking (0x29)When this command is sent, the control unit stops
Apartment block openOpening Program the required operating mode,
Photo
Safety function
Photo 1
Safety function
Photo 2
Safety function
Photo 3
Safety function
Release and openWhen this command is sent, the control unit is re-
Release and closeWhen this command is sent, the control unit is re-
Automatic opening activeThis command enables the activation or deactiva-
Deactivate automatic openingThis command enables deactivation of the “auto-
mode, ss apartment block 1 (“command conguration” > “step-by-step” > operating mode: ss apart-
ment block 1)
those listed in Table 1-L (“command conguration”
> “Stop in closure” > mode ...)
apartment block 1 open (“command conguration”
> “opening” > operating mode apartment block 1
open)
Photo Program the desired mode from those listed
in Table 1-F (“command conguration” > “photo”
> mode ...)
Photo 1 Program the desired mode from those listed in table 1-G (“command conguration” > “photo
1” > mode ...)
Photo 2 Program the desired mode from those listed in table 1-H (“command conguration” > “photo
2” > mode ...)
Photo 3 Program the desired mode from those listed in table 1-I (“command conguration” > “photo
3” > mode ...)
of the courtesy light on the control unit and that
programmable on Output 1. For the courtesy light
connected to Output 1, the command is only enabled when this output is programmed in “courtesy
light” mode (Control unit functions > advanced parameters > output conguration > output 1 (ash)
> courtesy light). CAUTION! – The courtesy light is
switched off automatically if the relative time interval
elapses, as programmed in the function “courtesy
light time” (Control unit functions > advanced parameters > output conguration > courtesy light
time). Input congured as normally open.
This command is factory set to Input 1, with operating mode “ss apartment block 1” and operating
sequence “open- stop - close - open”. When the
command is sent, the control unit makes the automation run the manoeuvre following that previously
(or still) in execution, according to the order of manoeuvres given in the programmed sequence. Note
– This apartment block step-by-step command is
used for apartment blocks and in general envisages programming of all apartment block transmitters
with a single “apartment block step-by-step” key.
Input congured as normally open.
When this command is sent, the control unit stops
the manoeuvre in progress and activates the ap-
plication to execute the set operating mode. Input
congured as normally closed.
gardless of its position. The input must remain
active. The safety equipment is ignored and all
close commands are also ignored (button press,
automatic closure, etc.). Only the hardware safeties remain active. The door's operation is restored
when the input is deactivated. Input congured as
normally closed.
the manoeuvre in progress. Input congured as
normally closed. It is used together with an output
congured as Interlocking (see Interlocking output)
When this command is sent, the control unit acti-
vates the application to perform the opening ma-
noeuvre only until the limit switch is reached. Note
– This command is useful when using control photocells or a magnetic detector loop. Input congured as normally open.
When this command is sent, the control unit acti-
vates the application according to the selected ma-
noeuvre type. Input congured as normally closed.
When this command is sent, the control unit acti-
vates the application according to the selected ma-
noeuvre type. Input congured as normally closed.
When this command is sent, the control unit acti-
vates the application according to the selected ma-
noeuvre type. Input congured as normally closed.
When this command is sent, the control unit acti-
vates the application according to the selected ma-
noeuvre type. Input congured as normally closed.
leased (restoring normal operating status) and ac-
tivates the application to execute an Opening ma-
noeuvre. Input congured as normally open.
leased (restoring normal operating status) and acti-
vates the application to execute a Closing manoeu-
vre. Input congured as normally open.
tion of the function for bluebus control photocells
and inputs congured in “apartment block open”
mode. Note – the factory setting of this function is
“active”. For example, if this function is active, when
the control photocells are engaged, the control unit
activates the application to execute an Opening
manoeuvre. Input congured as normally open.
matic opening active” mode described above. Input congured as normally open.
COMMAND CONFIGURATION
This item covers the command categories associable with inputs 1 - 2 - 3 (refer to the section “input conguration - Table 1” to check the commands available). Each command category features various operating modes as described in a table (1-A, 1-B, etc.):
Step-by-step
In this command category the user can select one of the operating modes specied in Table 1-A.
TABLE 1-A: COMMAND CONFIGURATION
MODEDESCRIPTION
Industrial modeThis runs the sequence “open in semiautomatic- close in hold-to-run”.
Open - stop - close - stopThis executes the above sequence.
Open - Stop - Close - OpenOperating mode set in factory (Input 1 - “step-by-step” command). This ex-
Open - Close - Open - CloseThis executes the above sequence.
Apartment block 1 step-by-stepRuns the sequence “close - stop - open - open”, until it reaches the fully open
Apartment block 2 step-by-stepRuns the sequence “close - stop - open - open” until the fully open position
Step-by-step 2This executes the sequence “open - stop - close - open”. Important – When
Hold-to-runThe Opening or Closing manoeuvre is executed exclusively if the transmitter
Partial open
In this command category the user can select one of the operating modes specied in Table 1-B.
ecutes the above sequence.
position. Note – If another command is sent after this one, the application
executes the Closing manoeuvre with the same sequence.
is reached. Note – If another command is sent after this one, the application
executes the Closing manoeuvre with the same sequence.
Important – When sending a command, if the transmitter key is held down for
more than 2 seconds, the control unit activates a Stop.
sending a command, if the transmitter key is held down for more than 2 sec-
onds, the control unit activates a “partial open 1” command (input conguration > Table 1).
key is held down (hold-to-run).
TABLE 1-B: COMMAND CONFIGURATION
MODEDESCRIPTION
Open - stop - close - stopOperating mode set in factory. This executes the above sequence.
Open - Stop - Close - OpenThis executes the above sequence.
Open - Close - Open - CloseThis executes the above sequence.
Apartment block 1 step-by-stepThis executes the sequence “close - stop - partial open 1- partial open 1”
Apartment block 2 step-by-stepThis executes the sequence “close - stop - partial open 1 - partial open 1”
Hold-to-runThe Partial open 1 or Closing manoeuvre is executed exclusively if the trans-
Industrial modeThis runs the sequence “open in semiautomatic- close in hold-to-run”.
Open
In this command category the user can select one of the operating modes specied in Table 1-C.
until the position is reached as programmed in the function “Partial Open 1”.
Note – If another command is sent after this one, the application executes the
Closing manoeuvre with the same sequence.
until the position is reached as programmed in the function “Partial Open 1”.
Note – If another command is sent after this one, the application executes
the Closing manoeuvre with the same sequence. Important – When sending
a command, if the transmitter key is held down for more than 2 seconds, the
control unit activates a Stop.
mitter key is held down (hold-to-run).
TABLE 1-C: COMMAND CONFIGURATION
MODEDESCRIPTION
Open - Stop - OpenOperating mode set in factory (Input 2 - “open” command). This executes the
Apartment block 1This executes the sequence “open - open”. Important – When sending a com-
Apartment block 2This executes the Opening sequence.
Open 2Important – When sending a command, if the transmitter key is held down for
Hold-to-run OpenThe Opening manoeuvre is executed exclusively if the transmitter key is held
Close
In this command category the user can select one of the operating modes specied in Table 1-D.
above sequence.
mand, if the transmitter key is held down for more than 2 seconds, the control
unit activates a Stop.
more than 2 seconds, the control unit activates a “partial open 1” command
(input conguration > Table 1).
down (hold-to-run).
TABLE 1-D: COMMAND CONFIGURATION
MODEDESCRIPTION
Close - stop - closeOperating mode set in factory (Input 3 - “close” command). This executes the
Apartment block 1 closeThis executes the sequence “close - close”.
Apartment block 2 closeThis executes the sequence “close - close”. Important – When sending a
Hold-to-run closeThe Closing manoeuvre is executed exclusively if the hold-to-run command
Stop
In this category, you can choose one of the operating modes listed in table 1-E.
above sequence.
command, if the transmitter key is held down for more than 2 seconds, the
control unit activates a Stop.
is used.
TABLE 1-E: COMMAND CONFIGURATION
MODEDESCRIPTION
StopOperating mode set in factory. When the control unit receives the command,
Stop and brief inversionWhen the control unit receives the “stop” command, it stops the manoeuvre
Photo
In this category, you can choose one of the operating modes listed in table 1-F.
it stops the manoeuvre in progress gradually and in a short time (not instantly).
in progress and activates the application to perform a brief inversion in the
opposite direction.
TABLE 1-F: COMMAND CONFIGURATION
MODEDESCRIPTION
Stop and inversionOperating mode set in factory. When the control unit receives the command,
Stop and brief inversionWhen the control unit receives the command, it stops the Closing manoeuvre
StopWhen the control unit receives the command is stop the current Close ma-
Photo 1
In this category, you can choose one of the modes listed in table 1-G.
it stops the Closing manoeuvre in progress and activates a total inversion
(Opening). Caution! – During execution of the Opening manoeuvre, this command is ignored.
in progress and activates the application to perform a brief inversion in the
opposite direction (Opening). Caution! – During execution of the Opening manoeuvre, this command is ignored.
noeuvre. Caution! – During execution of the Opening manoeuvre, this command is ignored.
TABLE 1-G: COMMAND CONFIGURATION
MODEDESCRIPTION
StopWhen the control unit receives the command is stop the current Close ma-
Temporary stopWhen the control unit receives the command, it stops the Closing manoeuvre
Photo 2
In this category, you can choose one of the modes listed in table 1-H.
noeuvre. Caution! – During execution of the Opening manoeuvre, this command is ignored.
for the entire time that the command remains active. Otherwise, when the
command is no longer active, the control unit activates the application to
perform an Opening manoeuvre. Caution! – During execution of the Opening
manoeuvre, this command is ignored.
TABLE 1-H: COMMAND CONFIGURATION
MODEDESCRIPTION
Stop and inversionOperating mode set in factory. When the control unit receives the command,
Stop and brief inversionWhen the control unit receives the command, it stops the Opening manoeu-
StopWhen the control unit receives the command, it stops the Opening manoeu-
Photo 3
In this category, you can choose one of the modes listed in table 1-I.
it stops the Opening manoeuvre in progress and activates a total inversion
(Closing). Caution! – During execution of the Opening manoeuvre, this command is ignored.
vre in progress and activates the application to perform a brief inversion in
the opposite direction (Closing). Caution! – During execution of the Opening
manoeuvre, this command is ignored.
vre in progress. Caution! – During execution of the Opening manoeuvre, this
command is ignored.
TABLE 1-I: COMMAND CONFIGURATION
MODEDESCRIPTION
Temporary stopOperating mode set in factory. When the control unit receives the command,
StopWhen the control unit receives the command, it stops the manoeuvre in pro-
Alt in opening
In this category, you can choose one of the modes listed in table 1-L.
it stops the Closing manoeuvre for the entire time that the command remains
active. Otherwise, when the command is no longer active, the control unit
activates the application to perform an Opening manoeuvre.
gress.
TABLE 1-L: COMMAND CONFIGURATION
MODEDESCRIPTION
None
StopOperating mode set in factory. When this type of function is set, when the
Stop and brief inversionWhen the control unit receives the command, it stops the Opening manoeuvre
Alt and inversionWhen the control unit receives the command, it immediately stops the Closing
Stop in closure
In this category, you can choose one of the modes listed in table 1-M.
control unit receives the command, it stops the Opening manoeuvre in pro-
gress immediately.
in progress immediately and activates the application to perform a brief inver-
sion in the opposite direction (Closing).
manoeuvre in progress and activates the application to perform a total inver-
sion of the manoeuvre in the opposite direction (Opening).
TABLE 1-M: COMMAND CONFIGURATION
MODEDESCRIPTION
None
StopOperating mode set in factory. When the control unit receives the command,
Stop and brief inversionWhen the control unit receives the command, it stops the Closing manoeuvre
Alt and inversionWhen the control unit receives the command, it immediately stops the Closing
Stop in pre-closure (0x6e)
In this category, you can choose one of the modes listed in table 1-N for sensitive edge intervention within the inhibition position
it stops the Closing manoeuvre in progress.
in progress immediately and activates the application to perform a brief inver-
sion in the opposite direction (Opening).
manoeuvre in progress and activates the application to perform a total inver-
sion of the manoeuvre in the opposite direction (Opening).
TABLE 1-N: COMMAND CONFIGURATION
MODEDESCRIPTION
StopOperating mode set in factory. When the control unit receives the command,
NoneThe edge is ignored and the manoeuvre continues until the door reaches the
it immediately stops the Closing manoeuvre in progress.
set closed position.
OUTPUT CONFIGURATION
This item covers the functions available and associable with Outputs 1 (ash) - 2 - 3 present on the control unit of an automation. Each output has various
functions as described in a table (Table 2, Table 3, etc.):
Red trafc light (0x0d)This function indicates activity of the application during the phases of a Clos-
ing manoeuvre.
slow ashing = execution of Closing manoeuvre;
light permanently on = application in maximum Closing position;
light off = application in other positions.
The OUT-TL2 output at 24V DC / max 5W is used
Green trafc light (0x0e)This function indicates activity of the application during the phases of an
One way trafc light (0x1a)This function operates as follows:
One-way trafc light ashing (0x1b)This function operates as follows:
Two-way alternating trafc light (0x1a)This function operates as follows:
Door status (0x1e)This function operates as follows:
When the door is open, OUT-TL2 is activated and all others remain off.
sca (0x01)The programmed light indicates the operating status of the control unit.
Gate open (0x02)The programmed light indicates the operating status of the control unit.
Gate closed (0x03)The programmed light indicates the operating status of the control unit.
Service light (0x04)The programmed light indicates the count of manoeuvres completed and
Flasher at 24V (0x17)This function enables the ashing light to indicate execution of a manoeuvre in
Electric lock 1 (0x07)With this function programmed, when an Opening manoeuvre is performed
Electric block 1 (0x09)With this function programmed, when an Opening manoeuvre is performed
Opening manoeuvre.
slow ashing = execution of Opening manoeuvre;
light permanently on = application in maximum Opening position;
light off = application in other positions.
The OUT-TL3 output at 24V DC / max 5W is used
OUT-TL2 and OUT-TL3 are active when the door is open, and deactivated in
all other conditions.
The function uses outputs OUT-TL2 and OUT-TL3 at 24V / 5W
OUT-TL2 ashes when opening and stays active with the door open, deactivated in all other conditions.
OUT-TL3 ashes when closing and stays active with the door stationary in any
position other than fully open; deactivated in all other conditions.
The function uses outputs OUT-TL2 and OUT-TL3 at 24V / 5W
When an open command is sent from inside, OUT-TL2 (green trafc light) is
activated, giving priority to the person inside.
When an open command is sent from outside, OUT-TL3 (green trafc light) is
activated, giving priority to the person outside.
When the door is closed or closing, both trafc lights are deactivated (red
trafc light).
For the system to operate in this mode, the commands must be sent to the
control unit as follows:
Commands from inside: Input 2 congured as Open
Commands from outside: Input 3 congured as Open
The function uses outputs OUT-TL2 and OUT-TL3 at 24V / 5W
When the door is closed, OUT-TL1 is activated and all others remain off.
When a door is in any position other than fully open or closed, OUT-TL3 is
activated and all others remain off.
The function uses outputs OUT-TL1, OUT-TL2 and OUT-TL3 at 24V / 5W
light off = application in maximum Closing position;
slow ashing = application Opening manoeuvre execution phase;
quick ashing = application Closing manoeuvre execution phase;
light permanently on = application in maximum Opening position.
The OUT-TL1 output at 24V DC / max 5 W is used
light on = application in maximum Opening position;
light off = application in other positions.
The OUT-TL1 output at 24V DC / max 5 W is used
light on = application in maximum Closing position;
light off = application in other positions.
The OUT-TL1 output at 24V DC / max 5 W is used
therefore the need (or not) for system maintenance operations.
light on for 2 sec at start of Opening manoeuvre = number of manoeuvres
less than 80%;
light ashing during execution of entire manoeuvre = number of manoeuvres
between 80 and 100%;
light always ashing = number of manoeuvres over 100%.
The OUT-TL1 output at 24V DC / max 5 W is used
progress with ashes at regular intervals (0.5 sec ON, 0.5 sec OFF).
The OUT-TL2 output at 24V DC / max 5 W is used
the electric lock is activated for a time as set in the function “electric lock time
– output conguration”.
The OUT-TL2 output at 24V DC / max 5 W is used
the electric lock is activated for a time as set in the function “electric lock time
– output conguration”.
The OUT-TL2 output at 24V DC / max 5 W is used
Suction cup 1 (0x0b)With this function programmed, the suction cup is activated when the appli-
Courtesy light (0x06)This function type is ON/OFF. Important – For safety reasons, as the light is
Radio channel 1 (0x0f)When a transmitter sends a command, this output is activated. This mode is
Radio channel 2 (0x10)When a transmitter sends a command, this output is activated. This mode is
Radio channel 3 (0x11)When a transmitter sends a command, this output is activated. This mode is
Radio channel 4 (0x12)When a transmitter sends a command, this output is activated. This mode is
cation is in the maximum Closing position. Note – The suction cup is disabled
in all other situations. When the suction cup is disabled, before an Opening
manoeuvre is started, the time interval as programmed in the function “suc-
tion cup time – output conguration” is activated, which delays the start of
the manoeuvre.
The OUT-TL2 output at 24V DC / max 5 W is used
not controlled by a timer, use of an adequate light, able to withstand the heat
of the light emitted, is recommended.
The OUT-TL3 output at 24V DC / max 5 W is used
useful if installing external devices (for example, an auxiliary light) in the same
system to be controlled with a single transmitter. CAUTION – If this channel is
not free on the control unit's receiver, due to having been previously memorised with a command, when the channel is activated by the transmitter, the
control unit only activates the programmed output, and ignores the motor
command.
The OUT-TL3 output at 24V DC / max 5 W is used
useful if installing external devices (for example, an auxiliary light) in the same
system to be controlled with a single transmitter. CAUTION – If this channel is
not free on the control unit's receiver, due to having been previously memorised with a command, when the channel is activated by the transmitter, the
control unit only activates the programmed output, and ignores the motor
command.
The OUT-TL3 output at 24V DC / max 5 W is used
useful if installing external devices (for example, an auxiliary light) in the same
system to be controlled with a single transmitter. CAUTION – If this channel is
not free on the control unit's receiver, due to having been previously memorised with a command, when the channel is activated by the transmitter, the
control unit only activates the programmed output, and ignores the motor
command.
The OUT-TL3 output at 24V DC / max 5 W is used
useful if installing external devices (for example, an auxiliary light) in the same
system to be controlled with a single transmitter. CAUTION – If this channel is
not free on the control unit's receiver, due to having been previously memorised with a command, when the channel is activated by the transmitter, the
control unit only activates the programmed output, and ignores the motor
command.
The OUT-TL3 output at 24V DC / max 5 W is used
output 1 (ash)
In this output the user can select one of the functions specied in Table 2.
TABLE 2: OUTPUT CONFIGURATION
MODEDESCRIPTION
Not speciedThe output is never activated
sca (= gate open indicator)The programmed light indicates the operating status of the control unit.
Sca1 The programmed light indicates the operating status of the control unit.
Sca2The programmed light indicates the operating status of the control unit.
gate openThe programmed light indicates the operating status of the control unit.
light off = application in maximum Closing position;
slow ashing = application Opening manoeuvre execution phase;
quick ashing = application Closing manoeuvre execution phase;
light permanently on = application in maximum Opening position.
Output active 24 Vdc / max 10 W
light permanently on = application in maximum
Opening or Closing position;
slow ashing = application Opening manoeuvre execution phase;
quick ashing = application Closing manoeuvre execution phase;
light off = application stationary, in a different position than maximum Closing
or maximum Opening.
Output active 24 V DC / max 10 W
light permanently on = application in maximum Closing position;
slow ashing = application Opening manoeuvre execution phase;
quick ashing = application Closing manoeuvre execution phase;
light off = application stopped in maximum Opening position.
Output active 24 V DC / max 10 W
light on = application in maximum Opening position;
light off = application in other positions.
Output active 24 Vdc / max 10 W
gate closedThe programmed light indicates the operating status of the control unit.
maintenance indicator lightThe programmed light indicates the count of manoeuvres completed and the-
FlasherThis function enables the ashing light to indicate execution of a manoeuvre in
Flasher 1This function enables the asher to ash constantly at regular intervals (0.5
Flasher at 24VThis function enables the ashing light to indicate execution of a manoeuvre in
courtesy lightThis function type is ON/OFF. Important – For safety reasons, as the light is
Always onThis function enables the indicator light to remain constantly lit both during a
electric lock 1With this function programmed, when an Opening manoeuvre is performed
electric block 1With this function programmed, when an Opening manoeuvre is performed
suction cup 1With this function programmed, the suction cup is activated when the appli-
red trafc lightThis function indicates activity of the application during the phases of a Clo-
green trafc lightThis function indicates activity of the application during the phases of an Ope-
Interlocking (0x22)This output is used to create the interlocking system between 2 doors. This
radio channel no.1If this radio channel is set for the conguration of output 1 (ash), this channel
light on = application in maximum Closing position;
light off = application in other positions.
Output active 24 Vdc / max 10 W
refore the need (or not) for system maintenance operations.
light on for 2 sec at start of Opening manoeuvre = number of manoeuvres
less than 80%;
light ashing during execution of entire manoeuvre = number of manoeuvres
between 80 and 100%;
light always ashing = number of manoeuvres over 100%.
progress with ashes at regular intervals (0.5 sec ON, 0.5 sec OFF).
Output active 12 Vdc / max 21 W
sec ON; 0.5 sec. OFF) both during a manoeuvre and when the pole is stationary.
Output active 24 V DC / max 10 W
progress with ashes at regular intervals (0.5 sec ON, 0.5 sec OFF).
Output active 24 V DC / max 10 W
not controlled by a timer, use of an adequate light, able to withstand the heat
of the light emitted, is recommended.
Output active 24 Vdc / max 10 W
manoeuvre and when the pole is stationary.
Output active 24 V DC / max 10 W
the electric lock is activated for a time as set in the function “electric lock time
– output conguration”.
Output active 24 Vdc / max 10 W
the electric lock is activated for a time as set in the function “electric lock time
– output conguration”.
Output active 24 dc/ max 10 VA
cation is in the maximum Closing position. Note – The suction cup is disabled
in all other situations.
When the suction cup is disabled, before an Opening manoeuvre is started,
the time interval as programmed in the function “suction cup time – output
conguration” is activated, which delays the start of the manoeuvre.
Output active 24Vdc / max 10 W
sing manoeuvre.
slow ashing = execution of Closing manoeuvre;
light permanently on = application in maximum Closing position;
light off = application in other positions.
Output active 24Vdc / max 10 W
ning manoeuvre.
slow ashing = execution of Opening manoeuvre;
light permanently on = application in maximum Opening position;
light off = application in other positions.
Output active 24Vdc / max 10 W
use enables the user to open one door, only if the other one is closed. The
output changes status when all the following conditions are valid:
- the door is closed;
- it receives a command to open;
- no safety device prevents the manoeuvre.
The output is always active when the door is any position other than totally
closed.
To establish the connection, a 24Vdc connection interface relay must be used
between this output and an input congured as Interlocking on the second
control unit.
is activated when a command is set with the transmitter. It is useful if installing
external devices (for example, an auxiliary light) in the same system to be
controlled with a single transmitter.
WARNING – If this channel is not free on the control unit receiver, as previously
memorised with a command, the control unit activates exclusively the programmed output when the channel is activated with the transmitter, ignoring
the command to the motor.
Output active 24Vdc / max 10 W
radio channel no.2If this radio channel is set for the conguration of output 1 (ash), this channel
radio channel no.3If this radio channel is set for the conguration of output 1 (ash), this channel
radio channel no.4If this radio channel is set for the conguration of output 1 (ash), this channel
Control unit status (0x1f)This output copies the operation of the Bluebus led which determines the
is activated when a command is set with the transmitter. This mode is useful
if installing external devices (for example, an auxiliary light) in the same system
to be controlled with a single transmitter.
WARNING – If this channel is not free on the control unit receiver, as previously
memorised with a command, the control unit activates exclusively the programmed output when the channel is activated with the transmitter, ignoring
the command to the motor.
Output active 24Vdc / max 10 W
is activated when a command is set with the transmitter. This mode is useful
if installing external devices (for example, an auxiliary light) in the same system
to be controlled with a single transmitter.
WARNING – If this channel is not free on the control unit receiver, as previously
memorised with a command, the control unit activates exclusively the programmed output when the channel is activated with the transmitter, ignoring
the command to the motor.
Output active 24Vdc / max 10 W
is activated when a command is set with the transmitter. This mode is useful
if installing external devices (for example, an auxiliary light) in the same system
to be controlled with a single transmitter.
WARNING – If this channel is not free on the control unit receiver, as previously
memorised with a command, the control unit activates exclusively the programmed output when the channel is activated with the transmitter, ignoring
the command to the motor.
Output active 24Vdc / max 10 W
status of the control unit, including the diagnostics. In addition, the output is
deactivated when the safety chain (ALT, motor thermal cutout, SAFE, STOP
key on cover) is interrupted.
Output active 24 V DC / max 10 W
output 2
In this output the user can select one of the functions specied in Table 2.
output 3
In this output you can choose one of the functions described in Table 2, except for the ”asher 24” and ”control unit status” functions.
electric lock time
This parameter is expressed in seconds and can be set with a value from 0.1 to 10 sec.; the factory setting is 2 sec. This function enables programming on
the Control unit of the required time interval to pass between the end of a Closing manoeuvre and the start of an Opening manoeuvre.
suction cup time
This parameter is expressed in seconds and can be set with a value from 0.1 to 10 sec.; the factory setting is 2 sec. This function enables programming on
the Control unit of the required time interval to pass between the end of a Closing manoeuvre and the start of an Opening manoeuvre, when the suction cup
is disengaged.
Courtesy light time
This parameter is expressed in seconds and can be set with a value from 0 to 250 sec.; the factory setting is 60 sec. This function programs the courtesy
light on time for the various outputs.
It disables short circuit control on outputs (0xa6)
This parameter is of the ON/OFF type; the factory setting is “OFF”. When this function is set to ON it allows the short circuit control on outputs 1 and 2 to
be disabled
Inverter (inverters only) (0xfe)
• Inverter mode (0xad)
This parameter is of the ON / OFF type; the factory setting is “OFF”. When set to “ON”, it activates the operating logic of motors with MEIN series on-board
inverters. Important – After activating this function, you must run device learning again.
Speed management (inverters only)
• Open speed (0x42)
This parameter can be set with a value from 20% to 180%; the factory setting is 100%. The function enables programming of the required motor speed during an Opening manoeuvre. Important – After setting this parameter, you must run a few manoeuvres to allow the system to recalculate the decelerations.
• opening deceleration (0x45)
This parameter can be set with a value from 20% to 180%; the factory setting is 45%. The function enables programming of the required motor speed during the initial deceleration phase of an opening manoeuvre. Important – After setting this parameter, you must run a few manoeuvres to allow the system to
recalculate the decelerations.
• closing speed (0x43)
This parameter can be set with a value from 20% to 180%; the factory setting is 100%. The function enables programming of the required motor speed
during a Closing manoeuvre. Important – After setting this parameter, you must run a few manoeuvres to allow the system to recalculate the decelerations.
• closing deceleration speed (0x46)
This parameter can be set with a value from 20% to 180%; the factory setting is 45%. The function enables programming of the required motor speed during the initial deceleration phase of an opening manoeuvre. Important – After setting this parameter, you must run a few manoeuvres to allow the system to
recalculate the decelerations.
• deceleration speed (0x44)
This parameter can be set with a value from 20% to 100%; the factory setting is 20%. This function enables you to program the speed of the motor while
learning the open and close positions and during the nal phase of deceleration. Important – Always set this to the minimum speed required to operate the
door. Setting too high a speed can make it difcult to precisely determine the stop position.
Start up (0x8f)
The parameter can be set from 0 to 70V; the factory setting is 30V. The function sets the voltage at the start of a manoeuvre, to ensure sufcient torque at
low motor speeds. Important – This parameter must be set the value required for the motor to actually start the manoeuvre. Too high a setting can damage
the inverter and the motor by increasing the voltage too much.
Minimum frequency (0xac)
The parameter can be set from 2 to 7Hz; the factory setting is 2Hz. This sets the minimum start and stop frequency for the manoeuvre and, combined with
the start-up parameters, determines the automation's ability to start and stop moving the door. Important - Too high a setting can damage the inverter and
the motor by increasing the voltage too much.
Acceleration (0x5e)
This parameter can be set from 30 to 300rad/s2. The function sets the initial acceleration. Important - Too high a setting can damage the inverter and the
motor by increasing the voltage too much.
Deceleration (0x5f)
This parameter can be set from 30 to 300rad/s2. The function sets the deceleration. Important - Too high a setting can damage the inverter and the motor
by increasing the voltage too much.
Stop deceleration (0xae)
This parameter can be set from 50 to 500rad/s2. The function sets the emergency deceleration, when the door stops because of a safety device trip. Important - Too high a setting can damage the inverter and the motor by increasing the voltage too much.
Motor heating (0x9e)
This parameter is of the ON / OFF type; the factory setting is “OFF”. When set to “ON”, it activates heating the motor when the ambient temperature is below
5°C.
Reserved 1 (0xaa)
This parameter accesses the inverter overcurrent controls. To modify this setting, contact Nice technical service.
Reserved 2 (0xab)
This parameter accesses the inverter protection equipment. To modify this setting, contact Nice technical service.
DIAGNOSTICS
Automation position
Indicates the physical position of the encoder in encoder pulses.
Inputs / Outputs
This function enables the display of the operating status of all inputs and outputs present on the control unit. The functions of the inputs and outputs are
described in Table 4.
TABLE 4: Input/output DIAGNOSTICS
This function enables the display of the device type, operating
status, and conguration of the devices connected to the Bluebus
output.
Diagnosis 1 - IN
RADIO INPUTS (On / Off):
Channel 1Indicates when radio receiver channel 1 is active.
Channel 2Indicates when radio receiver channel 2 is active.
Channel 3Indicates when radio receiver channel 3 is active.
Channel 4Indicates when radio receiver channel 4 is active.
SERIAL RADIO INPUTSIndicates when the control unit receives a serial command via BusT4 from
BOARD KEYS:
no. 1Indicates when key 1 is pressed (= OPEN) on the control unit.
no. 2Indicates when key 2 is pressed (= STOP) on the control unit.
no. 3Indicates when key 3 is pressed (= CLOSE) on the control unit.
DIRECTION SELECTIONIndicates the status of the direction selector for a manoeuvre.
INPUT STATUS:
inp 1Indicates when input 1 is active.
inp 2Indicates when input 2 is active.
inp 3Indicates when input 3 is active.
inp altIndicates when the alt input is active.
ALT CONFIGURATIONIndicates the type of connection on the alt terminal. The connections are of
MOTOR 1 (On / Off):
Limit switch on openingIndicates when motor 1 reaches the maximum opening position.
Limit switch on closingIndicates when motor 1 reaches the maximum closing position.
MANOEUVRE THRESHOLD:Indicates the operating status of the manoeuvre limiter, expressed in levels:
DESCRIPTION
a radio receiver; these commands range from minimum 1 to maximum 15.
three types: not congured; NC; NO; 1 8K2 resistive edge; 2 8K2 resistive
edges; 1 OSE optical edge; out of range.
Level 1: OK;
Level 2: THRESHOLD 1; the manoeuvre is started with a 2 second delay;
Level 3: THRESHOLD 2; the manoeuvre is started with a 5 second delay;
Level 4: MOTOR ALARM; the manoeuvre is only enabled with the hold-to-run
control.
LAST 8 MANOEUVRESIndicates any malfunctions occurring during normal operation of the applica-
AUTOMATIC OPENINGIndicates if this function is active.
Diagnosis 1 - OUT
GENERIC DATA:
Stand-byIndicates when the automation is in the standby status.
POWER:Indicates the type of electrical power used by the automation: mains (120/230
MEMORY ERRORS:
Map M1Indicates whether there is an error in the memorised data, related to the val-
RegoIndicates whether there is an error in the memorised data on the control unit
FunctionsIndicates whether there is an error in the memorised data regarding the func-
StopIndicates whether there is an error in the memorised data regarding the con-
BluebusIndicates whether there is an error in the memorised data regarding the con-
PositionsIndicates whether there is an error in the memorised data regarding positions.
ENCODER STATUS:
Abs M1Indicates whether there is a reading error or operating malfunction on the
OUTPUTS:
Out 1Indicates when output 1 is active. Caution – 12/24 V DC voltage present.
Out M1Indicates when motor 1 is in operation.
ALARMS:
Out 1 overloadIndicates an electrical overload or short circuit on output 1 or on the courtesy
Out 2 overloadIndicates an electrical overload or shortcircuit at output 2.
M1 low overtravelIndicates that the absolute encoder of motor 1 is in a position close to the
M1 high overtravelIndicates that the absolute encoder of motor 1 is in a position close to the
tion, showing the last 8 manoeuvres completed.
V AC) or backup battery (24 V DC)
ues for the force required by motor 1 to complete a manoeuvre.
regarding settable parameters.
tions programmable with Oview.
guration of the alt input.
guration of the devices connected to the bluebus input.
absolute encoder of motor 1.
light of the control unit.
minimum limit (0%), below which the motor does not function.
maximum limit (100%), over which the motor does not function.
other parameters
This function enables display of the operating status of some parameters measured by the control unit. These parameters are described in Table 5.
TABLE 5: DIAGNOSTICS of other parameters
PARAMETERDESCRIPTION
Diagnostics 2
MISCELLANEOUS PARAMETERS:
Courtesy lightIndicates the timer for shutoff of the courtesy light.
Pause timeIndicates the timer for counting the pause time between one manoeuvre and
Service voltageIndicates the voltage supplied to external devices.
Bus medium currentIndicates the current absorption of the devices connected to the bluebus out-
MOTOR 1:
TorqueIndicates the torque generated by motor 1 during the manoeuvre, calculated
SpeedIndicates the speed of motor 1 during the manoeuvre, calculated as a per-
VoltageIndicates the mean voltage to be supplied to motor 1 during the manoeuvre,
PositionIndicates the physical encoder position, as a percentage: the limits imple-
bluebus device diagnostics
This function displays the type, operating status and conguration of devices connected ot the Bluebus output. These parameters are described in Table 6.
the next.
put, calculated as a percentage.
as a percentage.
centage.
calculated as a percentage.
mented are the encoder minimum limit (equal to 0 = 0%) and the encoder
maximum limit (equal to 4096 = 100%). This data is useful to understand
whether the encoder is in an overtravel position, i.e. outside the operating
zone of the absolute encoder.
TABLE 6: DIAGNOSTICS of bluebus devices
PARAMETERDESCRIPTION
Bluebus
PHOTOCELLS
PHOTOIndicates whether the photocell is present, the relative operating status and
PHOTO IIIndicates whether the photocell is present, the relative operating status and
PHOTO 1Indicates whether the photocell is present, the relative operating status and
PHOTO 1 IIIndicates whether the photocell is present, the relative operating status and
PHOTO 2Indicates whether the photocell is present, the relative operating status and
PHOTO 2 IIIndicates whether the photocell is present, the relative operating status and
PHOTO 3Indicates whether the photocell is present, the relative operating status and
FT AIndicates whether the sensitive edge is present, the relative operating status
FT BIndicates whether the sensitive edge is present, the relative operating status
FT CIndicates whether the sensitive edge is present, the relative operating status
OPEN PHOTOIndicates whether the control photocell is present, the relative operating status
OPEN PHOTO IIIndicates whether the control photocell is present, the relative operating status
COMMANDS:
CMD 1Indicates whether the control photocell is present, the relative operating status
CMD 2Indicates whether the control photocell is present, the relative operating status
CMD 3Indicates whether the control photocell is present, the relative operating status
CMD 4Indicates whether the control photocell is present, the relative operating status
CMD 5 (SEM1)Indicates whether the “trafc light 1” control device and whether it is memo-
CMD 6 (SEM2)Indicates whether the “trafc light 2” control device and whether it is memo-
OTHER:
GATEIndicates the operating status of the application.
BLOCK AUTOMATIONIndicates when the automation is blocked following a “Block” command.
MEMORYIndicates a problem regarding the data related to bluebus devices, memo-
BUSIndicates whether there is a short circuit on the bluebus output.
STAND-BYIndicates when the control unit is in standby status.
OTHER DEVICES:
COURTESY LIGHTIndicates whether the control device is present, the relative operating status
SUCTION CUPIndicates whether the control device is present, the relative operating status
LOCKIndicates whether the control device is present, the relative operating status
TRAFFIC LIGHTS:
TRAFFIC LIGHT 1Indicates the operating status of the device.
TRAFFIC LIGHT 2Indicates the operating status of the device.
the correct memorisation in the control unit.
the correct memorisation in the control unit.
the correct memorisation in the control unit.
the correct memorisation in the control unit.
the correct memorisation in the control unit.
the correct memorisation in the control unit.
the correct memorisation in the control unit.
and the correct memorisation in the control unit.
and the correct memorisation in the control unit.
and the correct memorisation in the control unit.
and the correct memorisation in the control unit.
and the correct memorisation in the control unit.
and the correct memorisation in the control unit.
and the correct memorisation in the control unit.
and the correct memorisation in the control unit.
and the correct memorisation in the control unit.
rised correctly in the control unit.
rised correctly in the control unit.
rised in the control unit.
and whether it is memorised correctly in the control unit.
and whether it is memorised correctly in the control unit.
and whether it is memorised correctly in the control unit.
MAINTENANCE
Manual alarm threshold
A value from 0 to 16777215 (manoeuvres) can be assigned to this parameter; the factory setting is 10000 (manoeuvres). This function enables programming
of a reference limit, over which automation maintenance is required.
Partial count
This function enables the user to check the number of manoeuvres performed by an automation since it was last serviced.
Delete maintenance
This parameter is ON/OFF; the factory setting is “OFF”. This function enables deletion of the “partial count” value; this is required after performing maintenance
on the automation.
ADVANCED FUNCTIONS
Event log
This function enables the display of the events generated or received by the control unit. An “event” is a condition which changes the operating status of the
control unit, such as: activation of an input, end of a manoeuvre, photocell or stop input tripped, etc. This section displays the date and type of an event.
Firmware updates
The function can be carried out solely when the “o-view desktop” software is used, together with the O-view programmer with bluetooth module.
User permits
This function enables the installer to decide which functions and parameters are to be selected for display and modications by the user. For example, for
safety reasons, the installer can decide to prevent the user from modifying the parameters related to automation motor force and speed.
User permissions can be managed exclusively by using the “installer password” (password management, common functions). Note – All parameters of the
various functions of a control unit or receiver are factory set as disabled.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.