4-Channel, ±10 V, 16-Bit, Simultaneous, Channelto-Channel Isolated Analog Voltage Output Module
This document describes how to use the National Instruments 9269
and includes specifications and terminal assignments for the NI 9269.
Visit ni.com/info and enter rdsoftwareversion to determine
which software you need for the modules you are using. For
information about installing, configuring, and programming the
system, refer to the system documentation. Visit
enter
cseriesdoc for information about C Series documentation.
NoteThe safety guidelines and specifications in this
document are specific to the NI 9269. The other
components in the system might not meet the same safety
ratings and specifications. Refer to the documentation for
each component in the system to determine the safety
ratings and specifications for the entire system. Visit
ni.com/info and enter cseriesdoc for information
about C Series documentation.
ni.com/info and
NI 9269 Operating Instructions and Specifications2ni.com
Safety Guidelines
Operate the NI 9269 only as described in these operating
instructions.
Hot SurfaceThis icon denotes that the component may be
hot. Touching this component may result in bodily injury.
Safety Guidelines for Hazardous Voltages
If hazardous voltages are connected to the module, take the
following precautions. A hazardous voltage is a voltage greater
than 42.4 V
CautionEnsure that hazardous voltage wiring is
or 60 VDC to earth ground.
pk
performed only by qualified personnel adhering to local
electrical standards.
CautionDo not mix hazardous voltage circuits and
human-accessible circu its on the same module.
CautionMake sure that devices and circuits connected to
the module are properly insulated from human contact.
CautionWhen module terminals are hazardous voltage
LIVE (>42.4 V
/60 VDC), you must ensure that devices
pk
and circuits connected to the module are properly
insulated from human contact. You must use the NI 9971
connector backshell kit to ensure that the terminals are
not accessible.
Figure 1 shows the NI 9971 connector backshell.
Figure 1. NI 9971 Connector Backshell
NI 9269 Operating Instructions and Specifications4ni.com
Safety Guidelines for Hazardous Locations
The NI 9269 is suitable for use in Class I, Division 2, Groups A, B,
C, D, T4 hazardous locations; Class I, Zone 2, AEx nA IIC T4,
and Ex nA IIC T4 hazardous locations; and nonhazardous
locations only. Follow these guidelines if you are installing the
NI 9269 in a potentially explosive environment. Not following
these guidelines may result in serious injury or death.
CautionDo not disconnect I/O-side wires or connectors
unless power has been switched off or the area is known
to be nonhazardous.
CautionDo not remove modules unless power has been
switched off or the area is known to be nonhazardous.
CautionSubstitution of components may impair
suitability for Class I, Division 2.
CautionFor Zone 2 applications, install the system in an
enclosure rated to at least IP 54 as defined by IEC 60529
and EN 60529.
Special Conditions for Hazardous Locations Use in Europe
This equipment has been evaluated as Ex nA IIC T4 equipment
under DEMKO Certificate No. 07 ATEX 0626664X. Each module
is marked II 3G and is suitable for use in Zone 2 hazardous
locations, in ambient temperatures of –40 °C ≤ Ta ≤ 70 °C. If you
are using the NI 9269 in Gas Group IIC hazardous locations, you
must use the device in an NI chassis that has been evaluated as
Ex nC IIC T4, EEx nC IIC T4, Ex nA IIC T4, or Ex nL IIC T4
equipment.
NI 9269 Operating Instructions and Specifications6ni.com
Special Conditions for Marine Applications
Some modules are Lloyd’s Register (LR) Type Approved for
marine applications. To verify Lloyd’s Register certification, visit
ni.com/certification and search for the LR certificate, or
look for the Lloyd’s Register mark on the module.
CautionTo meet radio frequency emission requirements
for marine applications, use shielded cables and install
the system in a metal enclosure. Suppression ferrites
must be installed on power supply inputs near power
entries to modules and controllers. Power supply and
module cables must be separated on opposite sides of the
enclosure and must enter and exit through opposing
enclosure walls.
The NI 9269 has four 2-terminal detachable screw-terminal
connectors that provide connections for 4 analog output channels.
AO0+
AO0–
AO1+
AO1–
AO2+
AO2–
AO3+
AO3–
0
1
0
1
0
1
0
1
Figure 2. NI 9269 Terminal Assignments
NI 9269 Operating Instructions and Specifications8ni.com
Yo u can connect a load to each channel of the NI 9269. Connect the
positive lead of the load to the AO+ terminal. Connect the ground
of the load to the corresponding AO– terminal. Refer to Figure 3
for an illustration of how to connect a load to the NI 9269.
AO+
Load
AO–
Note
NI 9269
Figure 3. Connecting a Load to the NI 9269
You must use 2-wire ferrules to create a secure
connection when connecting more than one wire to a
single terminal on the NI 9269.
The analog output channels are floating with respect to earth
ground and each other. Each channel has a digital-to-analog
converter (DAC) that produces a voltage signal. Each channel
provides an independent signal path, enabling you to update all
four channels simultaneously. Each channel also has overvoltage
and short-circuit protection. Refer to the Specifications section for
more information about the overvoltage and short-circuit
protection. Refer to Figure 4 for an illustration of the output
circuitry for one channel of the NI 9269.
Isolated
DAC
NI 9269
Amp
Overvoltage/
Short-Circuit
Protection
AO+
AO–
Figure 4. Output Circuitry for One Channel of the NI 9269
When the module powers on, the channels output the startup
voltage. Refer to the Specifications section for more information
about startup voltage. Refer to the software help for information
about configuring startup output states in software. Visit
ni.com/info and enter cseriesdoc for information about
C Series documentation.
NI 9269 Operating Instructions and Specifications10ni.com
Wiring for High-Vibration Applications
If an application is subject to high vibration, National Instruments
recommends that you either use ferrules to terminate wires to the
detachable screw-terminal connector or use the NI 9971 backshell
kit to protect the connections. Refer to Figure 5 for an illustration
of using ferrules. Refer to Figure 1 for an illustration of the
NI 9971 connector backshell.
Figure 5. 2-Terminal Detachable Screw-Terminal Connector with Ferrule
Each channel of the NI 9269 has a nominal output voltage range of
±10 V and can drive up to ±10 mA of current. The total output
current of all channels is limited to ±20 mA. For example, if the
output current of AO0 is ±10 mA, the output current of
AO<1, 2, 3> is limited to ±10 mA total or ±3.33 mA each.
If you want to increase the nominal output voltage range, you can
cascade up to four output channels for a maximum of ±40 V
nominal. For example, if you want two channels with a nominal
output voltage range of ±20 V each, connect AO<0, 1> and
AO<2, 3> as shown in Figure 6. The output current of the cascaded
channels flows across two channels, limiting the total output
current to ±10 mA.
NI 9269 Operating Instructions and Specifications12ni.com
Figure 6. Increasing the Output Voltage Range of the NI 9269
AO<2, 3>–
NI 9269
AO<2, 3>+
AO<0, 1>–
AO<0, 1>+
AO0+
AO0–
AO1+
AO1–
AO2+
AO2–
AO3+
AO3–
Load
Load
Cascading more than four output channels of multiple NI 9269
modules violates the electrical safety and overvoltage protection
ratings.
Because the NI 9269 outputs can source and sink current, it is not
possible to increase the current drive by connecting output
channels in parallel.
This module supports a low-power sleep mode. Support for sleep
mode at the system level depends on the chassis that the module is
plugged into. Refer to the chassis manual for information about
support for sleep mode. If the chassis supports sleep mode, refer to
the software help for information about enabling sleep mode. Visit
ni.com/info and enter cseriesdoc for information about
C Series documentation.
Typically, when a system is in sleep mode, you cannot
communicate with the modules. In sleep mode, the system
consumes minimal power and may dissipate less heat than it does
in normal mode. Refer to the Specifications section for more
information about power consumption and thermal dissipation.
NI 9269 Operating Instructions and Specifications14ni.com
Specifications
The following specifications are typical for the range –40 to 70 °C
unless otherwise noted. All voltages are relative to the AO– signal
on each channel unless otherwise noted.
Output Characteristics
Number of channels .......................... 4 analog output channels
Measurement Category I is for measurements performed on
circuits not directly connected to the electrical distribution system
referred to as MAINS voltage. MAINS is a hazardous live electrical
supply system that powers equipment. This category is for
measurements of voltages from specially protected secondary
circuits. Such voltage measurements include signal levels, special
equipment, limited-energy parts of equipment, circuits powered by
regulated low-voltage sources, and electronics.
CautionDo not connect to signals or use for
measurements within Measurement Categories II,
III, or IV.
Measurement Category II is for measurements performed on
circuits directly connected to the electrical distribution system.
This category refers to local-level electrical distribution, such as
that provided by a standard wall outlet, for example, 115 V for U.S.
or 230 V for Europe.
CautionDo not connect to signals or use for
measurements within Measurement Categories III or IV.
NI 9269 Operating Instructions and Specifications22ni.com
Hazardous Locations
U.S. (UL) ..........................................Class I, Division 2,
Groups A, B, C, D, T4;
Class I, Zone 2,
AEx nA IIC T4
Canada (C-UL) .................................Class I, Division 2,
Groups A, B, C, D, T4;
Class I, Zone 2,
Ex nA IIC T4
Europe (DEMKO)............................. Ex nA IIC T4
Safety Standards
This product meets the requirements of the following standards of
safety for electrical equipment for measurement, control, and
laboratory use:
•IEC 61010-1, EN 61010-1
•UL 61010-1, CSA 61010-1
NoteFor UL and other safety certifications, refer to the
product label or the Online Product Certification section.
Refer to the product Declaration of Conformity (DoC) for
additional regulatory compliance information. To obtain product
certifications and the DoC for this product, visit ni.com/
certification
, search by module number or product line, and
click the appropriate link in the Certification column.
To meet these specifications, you must panel mount the system and
either affix ferrules to the ends of the terminal wires or use the
NI 9971 backshell kit to protect the connections.
Operating vibration
Random (IEC 60068-2-64)......... 5 g
, 10 to 500 Hz
rms
Sinusoidal (IEC 60068-2-6) ....... 5 g, 10 to 500 Hz
Operating shock
(IEC 60068-2-27).............................. 30 g, 11 ms half sine,
50 g, 3 ms half sine,
18 shocks at 6 orientations
Environmental
National Instruments C Series modules are intended for indoor use
only but may be used outdoors if installed in a suitable enclosure.
Refer to the manual for the chassis you are using for more
information about meeting these specifications.
Operating temperature
(IEC 60068-2-1, IEC 60068-2-2) .....–40 to 70 °C
Storage temperature
(IEC 60068-2-1, IEC 60068-2-2) .....–40 to 85 °C
NI 9269 Operating Instructions and Specifications26ni.com
Ingress protection.............................. IP 40
Operating humidity
(IEC 60068-2-56).............................. 10 to 90% RH,
noncondensing
Storage humidity
(IEC 60068-2-56).............................. 5 to 95% RH,
noncondensing
Maximum altitude............................. 2,000 m
National Instruments is committed to designing and manufacturing
products in an environmentally responsible manner. NI recognizes
that eliminating certain hazardous substances from our products is
beneficial to the environment and to NI customers.
For additional environmental information, refer to the NI and the Environment Web page at
ni.com/environment. This page
contains the environmental regulations and directives with which
NI complies, as well as other environmental information not
included in this document.
EU CustomersAt the end of the life cycle, all products
must be sent to a WEEE recycling center. For more
information about WEEE recycling centers and National
Instruments WEEE initiatives, visit
environment/weee
.
ni.com/
Calibration
Yo u can obtain the calibration certificate and information about
calibration services for the NI 9269 at
ni.com/calibration.
Calibration interval ........................... 1 year
NI 9269 Operating Instructions and Specifications28ni.com
Where to Go for Support
The National Instruments Web site is your complete resource for
technical support. At
ni.com/support you have access to
everything from troubleshooting and application development
self-help resources to email and phone assistance from
NI Application Engineers.
National Instruments corporate headquarters is located at
11500 North Mopac Expressway, Austin, Texas, 78759-3504.
National Instruments also has offices located around the world to
help address your support needs. For telephone support in the
United States, create your service request at
ni.com/support
and follow the calling instructions or dial 512 795 8248. For
telephone support outside the United States, contact your local
branch office:
Australia 1800 300 800, Austria 43 662 457990-0,
Belgium 32 (0) 2 757 0020, Brazil 55 11 3262 3599,
Canada 800 433 3488, China 86 21 5050 9800,
Czech Republic 420 224 235 774, Denmark 45 45 76 26 00,
Finland 358 (0) 9 725 72511, France 01 57 66 24 24,
Germany 49 89 7413130, India 91 80 41190000,
Israel 972 3 6393737, Italy 39 02 41309277, Japan 0120-527196,
NI 9269 Operating Instructions and Specifications30ni.com
National Instruments, NI, ni.com, and LabVIEW are trademarks of National Instruments Corporation. Refer to the
Terms of Use section on
product and company names mentioned herein are trademarks or trade names of their respective companies.
For patents covering National Instruments products/technology, refer to the appropriate location: Help»Patents
in your software, the