Rev. 02 del 03/08/2017
Redatto da R&D
Approvato da MKT
24-CHANNEL ETHERNET DATA LOGGER
with Embedded Web Server
DATALOGGER
NI2400
SPECIFIC WARNINGS
To guarantee the IP protection during the installation, expect to seal the instrument cables
(with silicone or foam) after having tightened the cable-gland.
Through the installation expect suitable protections to avoid product overheating (eg. a
shelter to avoid direct sunlight); similarly for low temperatures. Do not open in case of bad
weather conditions (rain, snow, etc). Expect the recurring substitution of the hygroscopic
salts.
Do not install in small locations and/or without ventilation, with high humidity, in potentially
dangerous areas or where is prescribed the use of explosion proof components.
Electrical connections on the product must be executed only from qualied and expert personnel, in compliance with actual rules and regulations.
For external network powering, the plug at the end of the cord has ground contact; the
grounding of the powering is provided from the plug inserted in the socket. The product
powering source must be divided from dangerous voltage parts with double insulation and
must guarantee an insulation of at least 3000 Vrms.
Be sure to have, in the plant, a suitable protection from electric short circuit (for example
high sensitivity differential circuit-breaker at the root of the AC/DC power supply unit).
Before any maintenance on the product, the powering must be disconnected.
Avoid any action that can short-circuit the rechargeable battery poles.
To enable the product protections, expect a connection to the ground plant through a proper
green-yellow grounding connector; this connector must be connected to the proper ground
clamp (or to any bolt if it is a metal cabinet).
Verify periodically rechargeable battery voltage; expect a substitution after roughly 5 years
and if the voltage measured on the poles is too low (eg. 10.5V for a battery with nominal
voltage 12V) and investigate on the causes.
Using the product differently from the one expected from the manufacturer can compromise
safety conditions.
The use of parts other than original spare parts could lead to irregular functioning or even
dangerous situations for person and things.
www.ruggedaq.com
03
DATALOGGER
INDEX
QUICK START6
1
Overview6
DEVICE OVERVIEW6
Connections6
Front Panel6
Rear Panel8
Cabling8
Overview8
Power Supply8
Connecting PSU9
Analog Channels Connection9
Examples10
Digital Inputs Connection
Example19
Digital Output Connection20
RS485 SmartModbus Connection
Multiplexers Connection 21
SETUP22
2
POWERING THE DATALOGGER22
Default NI2400 Settings22
Direct connection (LOCAL) to the Datalogger
REMOTE CONNECTION TO THE DATALOGGER 23
IP Computer Settings23
Overview23
Description23
WEB CONNECTION AND OPENING25
Overview25
Description25
CONNECTION THROUGH DHCP26
Overview26
Description26
Display and Keyboard Functionality29
Keyboard Overview29
Display Overview30
Firmware and Web Updates – Vibrating Wire
Firmware Update
Data Download32
Datalogger Stop and Switch Off
Display Language Setup37
18
20
22
32
35
WEB INTERFACE39
3
WEB PAGES FUNCTIONALITY39
Web interface Language setup40
Configuration of local analog channels40
Input Configuration43
Multiplexer Configuration47
MODBUS SENSORS51
What’s Modbus?51
Digital Sensors Configuration
Output Configuration and Alarms 1&254
Virtual Channel Alarm55
Tips56
DATALOGGER CONFIGURATION58
Overview58
Configuration -> Datalogger58
ALARMS61
Overview61
Configuration61
SMS Configuration62
Email Configuration63
SMTP Configuration64
FTP Configuration64
Channel Alarm Types65
Low and High Thresholds65
Derivate65
Examples65
DIGITAL INPUTS CONFIGURATION66
Example of Digital Input IN1 Configuration69
Example of Digital Input IN2 Configuration71
VIRTUAL CHANNELS73
Overview73
Why are Virtual Channels Implemented? 73
Scripts74
Virtual Channel Configuration76
Common Errors and Warnings77
ADVANCED CONFIGURATION 79
Overview79
Connections79
Measure log data transfer81
Account Management82
52
Date and Time83
Energy Management84
Info84
CHARTS84
Overview84
Activation85
Setup and use85
MODBUS TCP (SCADA INTEGRATION) 90
4
Overview90
COMMUNICATION
Communication Bus90
Measure Register90
Timestamp details91
Flag’s Register91
Sensor Acquired92
Examples92
Input X Valid92
Input X Alarm92
REGISTER MAP
General92
Analog Sensors Locations93
Digital Sensors Locations93
Multiplexers Sensors Locations94
Digital Inputs Locations96
Virtual Channels Locations97
SENSOR BASE ADDRESS98
Local Sensors (Analog)98
Digital Sensors (Smart Modbus)98
Multiplexers98
Digital Inputs98
Virtual Channels98
Event Log Registers99
STATUS REGISTERS99
Datalogger Status100
Next Acquisition100
Firmware Version101
Model Info101
Serial Number101
Device Name102
External Digital Input / Output Status102
90
92
INTERNET OF THINGS103
5
Overview 103
ADD A DEVICE ON EXOSITE PORTAL103
CONFIGURE THE DATALOGGERS
IOT Section106
Connections Configuration106
Acquisition Configuration107
ADD DATA SOURCES108
CREATE THE DASHBOARD AND ADD WIDGETS 110
This chapter is about different product’s features, starting from a device overview, and it
will show how to connect every available sensor:
1. Front and Rear panel
Connection for:
2.Power Supply
3.Analog sensors
4.Digital Inputs
5.RS485 SmartModbus Sensors
6.Multiplexer boards
DEVICE OVERVIEW
NI2400 is a universal datalogger, capable of reading 0..25mA Current Loop and
Transmitter, -10..10V, Vibrating Wire, NTC, PT100, PT200, PT500, PT1000, Ratiometric,
Wheatstone Bridge, Thermocouple, Potentiometer and SmartModbus RS-485 Digital
Sensors.
It provides a maximum of 24 channels when using only 2 wires sensors.
NI2400 is expandable with SmartMux device.
Connections
Front Panel
Figure 2
The majority of connections are located In NI2400’s front panel:
• RS-232: it can be used to connect a 3G Modem to expand connectivity
• Ethernet: This port is used to connect the device to an existing LAN. Internal Web Server
can be browsed to configure and download acquired data. It can be used for Internet connection (Cloud, FTP and EMAIL connections)
• USB Host: it allows the user to download measures, events and alarm logs to a pendrive,
or to update the firmware
• V OUT: this connector is designed to output the same voltage applied to V IN. It can be
turned off automatically when logger is in sleep mode or be kept always on.
• RS-485#2 – V OUT: This is SmartMux port, which allows the connection of 16 SmartMux
in daisy chain and offers power supply.
• RS-485#1 – V OUT: This is SmartModbus port, which allows digital sensors connections
and offers power supply.
• V IN: This port is to power the datalogger. It’s designed to work in 10-30V range.
• PWR-CONFIG: This port will allow the selection of Power supply. A jumper between two
rightmost connections is needed to let the datalogger be powered up.
• ANALOG INPUTS: This 8 terminal blocks is used to connect analog sensors. Starting from
bottom-left to bottom-right we find channels from 1 to 12, and from top-left to top-right
we find channels from 13 to 24.Every 6 connections, there is a Ground connector designed
to be the termination of shielded cables.
Figure 1
www.ruggedaq.com
06
www.ruggedaq.com
07
1
DATALOGGER
NI2400
NI2400
1
DATALOGGER
NI2400
NI2400
Rear Panel
Figure 3
NI2400’s rear panel has 2 Digital Inputs and 1 Digital Output.
• Digital Inputs IN1 IN2 can be configured to read rain meters and anemometers, or similar
pulse sensors (optoisolated, Min input voltage is 5V and Min current input is 2mA, while
Max input voltage is 24V and Max current is 10mA, Max frequency 1KHz, accuracy 0.1Hz).
• Digital Output is a relay output (for alarms), volt-free closure (low voltage, 30V 2A).
Connecting PSU
The logger should be configured before powering it up.
New datalogger are shipped already configured (as it follows) to be powered from external
power source.
Rightmost pins of PWR CONFIG must be short-circuited to allow the datalogger to use
V-IN source.
Connect V-IN to the right Power Supply Unit.
Picture below shows connections.
Cabling
Overview
This chapter will explain every connection to datalogger, how to optimize connections
availability and to use proper connectors to avoid unexpected behavior (malfunctions).
Power Supply
NI2400 can be supplied with 10V to 30V. In order to grant correct functioning of every
connected sensor or device, and its internal circuitry, at least 2A PSU is needed. If Analog
Sensors, External Modems, RS485 SmartModbus Sensors are powered from NI2400, a
more powerful PSU should be used.
Warning: ALL V-OUT connections on the front panel - in the upper terminal block expose the same V-IN applied. If you apply 24V to V-IN, 24V will be exposed.
Since NI2400 can work in a wide range of voltage, use has to choose the right one to
power external devices connected.
Analog Channels Connection
NI2400 can handle sensors up to a total of wires of 48
Examples:
2 wires sensors: up to 24 channels
4 wires sensors: up to 12 channels
6 wires sensors: up to 8 channels
User can also mix sensors type and the datalogger will shift positions with this rule:
• 6 Wires sensors first
• 4 Wires sensors middle
• 2 Wires sensors last
With this simple rule, it will maximize connection simplicity
Here are few examples:
www.ruggedaq.com
08
www.ruggedaq.com
09
1
DATALOGGER
NI2400
NI2400
1
DATALOGGER
NI2400
NI2400
Example 1 (2 wires sensors)
User connects 4 sensors, all of them are 2 wires:
First of all we configure the datalogger to read this sensors, as shown in Figure 4.
Figure 4
Now we can proceed with physical configuration.
SENSOR1 will be connected to channel 1, A and B terminals.
SENSOR2 will be connected to channel 2, A and B terminals.
SENSOR3 will be connected to channel 3, A and B terminals.
SENSOR4 will be connected to channel 4, A and B terminals.
Wiring schemes are available from web server, or in the APPENDIX of this manual.
Example 2 (4 wires sensors)
User connects 3 sensors, all of them are 4 wires:
First of all we configure the datalogger to read this sensors, as shown in Figure 6.
Figure 6
Now we can proceed with physical configuration.
SENSOR1 will be connected to channel 1, A and B terminals, and channel 2, A and B terminals.
SENSOR2 will be connected to channel 3, A and B terminals, and channel 4, A and B terminals.
SENSOR3 will be connected to channel 5, A and B terminals, and channel 6, A and B terminals.
Wiring schemes are available from web server, or in APPENDIX of this manual.
S1 S2S3S4
www.ruggedaq.com
Figure 5
010
www.ruggedaq.com
011
1
DATALOGGER
NI2400
NI2400
S2S2
S1
S4
Figure 7
DATALOGGER
NI2400
1
SENSOR1 will be connected to channel 1, A and B terminals, channel 2, A and B terminals,
and channel 3, A and B terminals.
SENSOR2 will be connected to channel 4, A and B terminals, channel 5, A and B terminals,
and channel 6, A and B terminals.
SENSOR3 will be connected to channel 7, A and B terminals, channel 8, A and B terminals,
and channel 9, A and B terminals.
Wiring schemes are available from web server, or in APPENDIX of this manual.
NI2400
Example 3 (6 wires sensors)
User connects 3 sensors, all of them are 6 wires:
First of all we configure the datalogger to read this sensors, as shown in Figure 8.
Figure 8
Figure 9
S1S2S3
www.ruggedaq.com
012
www.ruggedaq.com
013
DATALOGGER
NI2400
1
Example 4 (4 wires and 2 wires mix)
User connects 4 sensors, 2 of them are 4 wires, while the other 2 are 2 wires.
First of all we configure the datalogger to read this sensors, as shown in Figure 10.
Figure 10
NI2400
1
Figure 11
DATALOGGER
NI2400
NI2400
S1
S2S2
S3S4
According to rules mentioned at the beginning of this chapter, we will start with 4 wires
sensors, followed by 2 wires sensors.
SENSOR1 will be connected to channel 1, A and B terminals, and channel 2, A and B
terminals.
SENSOR2 will be connected to channel 3, A and B terminals, and channel 4, A and B
terminals.
SENSOR3 will be connected to channel 5, A and B terminals.
SENSOR4 will be connected to channel 6, A and B terminals.
Wiring schemes are available from web server, or in APPENDIX of this manual.
Example 5 (6 wires and 2 wires mix)
User connects 3 sensors, 1 of them is 6 wires, while the other 2 are 2 wires.
First of all we configure the datalogger to read this sensors, as shown in Figure 12.
Figure 12
According to rules mentioned at the beginning of this chapter, we will start with 6 wires
sensors, followed by 2 wires sensors.
SENSOR1 will be connected to channel 1, A and B terminals, channel 2, A and B terminals,
and channel 3, A and B terminals.
SENSOR2 will be connected to channel 4, A and B terminals.
SENSOR3 will be connected to channel 5, A and B terminals.
Wiring schemes are available from web server, or in APPENDIX of this manual.
www.ruggedaq.com
014
www.ruggedaq.com
015
1
DATALOGGER
NI2400
NI2400
1
DATALOGGER
NI2400
NI2400
Figure 13
S1
Example 6 (6 wires and 4 wires mix)
User connects 3 sensors, 1 of them is 6 wires, while the other 2 are 4 wires.
First of all we configure the datalogger to read this sensors, as shown in Figure 14.
S2
S3
Figure 15
S3
S1
Example 7 (6 wires, 4 wires and 2 wires mix)
User connects 5 sensors, 1 of them is 6 wires, other 2 are 4 wires, and the last 2 are 2 wires.
First of all we configure the datalogger to read this sensors, as shown in Figure 16.
S2
S3
Figure 14
According to rules mentioned at the beginning of this chapter, we will start with 6 wires
sensors, followed by 4 wires sensors.
SENSOR1 will be connected to channel 1, A and B terminals, channel 2, A and B terminals,
and channel 3, A and B terminals.
SENSOR2 will be connected to channel 4, A and B terminals, and channel 5, A and B terminals.
SENSOR3 will be connected to channel 6, A and B terminals, and channel 7, A and B terminals.
Wiring schemes are available from web server, or in APPENDIX of this manual.
www.ruggedaq.com
016
Figure 16
According to rules mentioned at the beginning of this chapter, we will start with 6 wires
sensors, followed by 4 wires and 2 wires.
SENSOR1 will be connected to channel 1, A and B terminals, channel 2, A and B terminals,
and channel 3, A and B terminals.
www.ruggedaq.com
017
1
DATALOGGER
NI2400
NI2400
1
DATALOGGER
NI2400
NI2400
SENSOR2 will be connected to channel 4, A and B terminals, and channel 5, A and B terminals.
SENSOR3 will be connected to channel 6, A and B terminals, and channel 7, A and B terminals.
SENSOR4 will be connected to channel 8, A and B terminals.
SENSOR5 will be connected to channel 9, A and B terminals.
Wiring schemes are available from web server, or in APPENDIX of this manual.
Example
In order to configure a trigger, connect it to DIGITAL INPUTS IN1 (or IN2, not showed here):
TRIGGER
Figure 18
Open NI2400’s web server, at “Channels Configuration -> Digital Inputs” page.
Select Trigger in the IN1 Input field:
S1
Figure 17
Digital Inputs Connection
NI2400 has 2 digital inputs (on rear panel) that can be configured, independently, as “Trigger” or
“Rainmeter/Anemometer”.
If they are configured as Trigger, a pulse on the channel will start an acquisition of all configured
channels.
If they are configured as Rainmeter/Anemometer, input frequency will be measured and logged
in measure log.
Readable signal specifications:
• Min 5V (2mA max)
• Max 24V (10mA max)
• Max Frequency 1KHz
• Accuracy: 0.1Hz
Inputs are optoisolated.
S2
S3
S3
S4S5
Figure 19
Edge parameter (Up and Down) indicates if the trigger will raise voltage between poles or drop
it, or if it’s a “rectangular” wave, you can choose to use rising front or falling front.
Number of reading indicates how many acquisition cycles will be performed after a trigger event.
In order to use Triggers the NI2400 should not go in sleep mode. Check Energy
Management section to configure the datalogger to avoid switch off (by selecting Always ON).
For more information about how to configure Digital Inputs, refer to Digital Inputs section.
www.ruggedaq.com
018
www.ruggedaq.com
019
1
DATALOGGER
NI2400
NI2400
1
DATALOGGER
NI2400
NI2400
Digital Output Connection
NI2400 is provided with a Digital Output (NC / NO), which can drive low voltage (max 30V,
2A). It’s a relay, so it is a volt-free switch.
In order to handle higher voltages or currents, use internal relay to drive a rugged heavy
duty relay.
RS485 SmartModbus Connection
NI2400 can read digital sensor over the RS-485 SmartModbus port.
The port used for sensors connection is RS-485#1.
WARNING: RS-485#2 PORT DOES NOT WORK WITH DIGITAL SENSORS AS IT IS
DESIGNED TO WORK ONLY WITH MULTIPLEXERS.
RS-485#1 port presents 5 connections:
• Data – : can be named as B or “inverting pin” or TxD-/RxD-
• Data + : can be named as A or “non inverting pin” or TxD+/RxD+
• GND: it is the reference pin. It is recommended to use GND (SC, C, or reference pin)
while connecting RS-485 sensors.
• +V: NI2400 can power RS485 sensors. It provides the same power source applied to
NI2400 VIN. Be careful to choose the right supply to power both datalogger and sensor.
• GND: same as +V, is the negative connection of power supply.
RS-485 allows daisy chain connections. The example below shows an NI2400 datalogger
with four temperature and humidity probes connected in daisy chain.
WARNING: BE CAREFUL ON CABLE DIMENSIONS, AS THEY ARE AFFECTED FROM
TOTAL LENGTH AND PROBE NUMBERS. BE SURE TO CHOOSE A CABLE OF THE
RIGHT SIZE FOR YOUR PROJECT.
Example
Figure 21
Not all probes have a signal GND (SC) pin, and in the example above, the probe was not
connected to signal ground.
Multiplexers Connection
Figure 20
The minimum distance between two nodes (NI2400 to probe, or probe to probe) is 30 cm.
www.ruggedaq.com
020
NI2400 offers Analog Sensors expandability through Multiplexers.
Multiplexers are expansion boards that can read up to 24 sensors each, with connections
logic similar to NI2400 (explained in Multiplexer Section), which will be connected to channel 22/23/24 of NI2400.
More than one Multiplexer can be connected to NI2400, up to 16 Units, daisy chained to
RS-485#2 and channels 22/23/24.
www.ruggedaq.com
021
DATALOGGER
NI2400
NI2400
DATALOGGER
NI2400
22
NI2400
SETUP
POWERING THE DATA LOGGER
The NI2400 is supplied not powered to avoid that during transport the backup battery will discharge.
To begin working with the NI2400 proceed as follows:
• Connect external powering (battery charger or photovoltaic panel);
ATTENTION: Do not invert battery polarity, otherwise the data logger may be damaged
or stop working.
Default NI2400 Settings
The network card is setup from as follows:
IP Address: 192.168.1.100
Subnet Mask: 255.255.255.0
Gateway: 192.168.1.1
DNS1: 0.0.0.0
DNS2: 0.0.0.0
To connect with the NI2400 is necessary to setup PC network card in the same class of the
data logger, but with different IP (eg. 192.168.1.200).
REMOTE CONNECTION TO THE DATALOGGER
This manual contains all basic information to properly connect the NI2400 to the network
through ethernet connection.
There is also a description of the procedure to set the logger and connect it through DHCP.
IP Computer Settings
Overview
Here you will learn how to set the computer IP address to allow the connection with the
NI2400.
Description
Open control panel and then: Network and Internet – Network Centre and Sharing
Direct connection (LOCAL) to the Datalogger
To connect and manage the NI2400 through its on-board web pages, after the proper con-
guration of PC network card, connect the PC to the NI2400 through an Ethernet crossover
cable (supplied). Once connected through the supplied cable, open any internet browser
and put, in the address bar, NI2400 IP address (default 192.168.1.100).
After a few seconds you will be asked for the data logger access credentials.
NOTES:
• The NI2400 is compatible with the main internet browsers (FireFox, IE9, Safari, Chrome).
FireFox is recommended to manage the NI2400.
•First page upload can take some time.
Following are the default credentials:
User “Admin” User
User: Admin User: User
Psw: Admin Psw: User
www.ruggedaq.com
022
www.ruggedaq.com
023
DATALOGGER
NI2400
NI2400
DATALOGGER
NI2400
22
NI2400
Then click on LAN connection and enter Properties
(1)
Select “Use this IP: “and write data you see in the picture below.
A new window will open “Properites-LAN connection ”
Select “Internet protocol version 4 (TCP/IPv4) (3), and click on Properties (4).
(2)
WEB CONNECTION AND OPENING
Overview
Here you will learn how to connect the NI2400 to the network and how to access the WEB.
Description
Connect the NI2400 through Ethernet cable (Look at the 2 different block diagrams)
ROUTER
DATA LOGGER
PC
PC
DATA LOGGER
www.ruggedaq.com
Open thel browser and write in the search bar the NI2400 IP address “192.168.1.100” and
024
then enter user and password:
User: Admin
Password: Admin
www.ruggedaq.com
025
DATALOGGER
NI2400
NI2400
CONNECTION THROUGH DHCP
Overview
Here you will learn how to connect the NI2400 through DHCP. This option will allow the user
to use either the NI2400 webserver and the usual Internet connection.
Note. The router must be connected to a DHCP server
Description
When you are connected to the NI2400 web server (192.168.1.100 IP address to be written
in the search bar), select “Advanced” from left menu and then “Connections”.
DATALOGGER
NI2400
22
NI2400
Click OK and close all windows.
Control from display the new IP address (see picture below).
NOTES
The IP address shown in the picture has been assigned by the router.
1. Flag “ DHCP Enable” and then start NI2400 reboot.
2. After Rebooting, IP address has to be setted up – look at chapter “Computer IP settings”
3. In few steps (summary):
4. Open Control Panel and then “Network Centre and Sharing” window
5. Enter “LAN Connection”and open Properties
6. Select: Internet protocol version 4 (TCP/IPv4) and then click on Properties
7. This time – unlike before - select “Obtain an IP address automatically”.
www.ruggedaq.com
026
www.ruggedaq.com
027
DATALOGGER
NI2400
NI2400
DATALOGGER
NI2400
22
NI2400
Now you should enter the IP address shown in the display – instead of default IP address
192.168.1.100 - in order to enter in the NI2400 web server.
Display and keyboard functionality
Through the NI2400 keyboard and instructions shown on the display is possible to perform
some simple operations without using a computer connected to NI2400.
NOTE:
Some operations (data download on USB key, FW update, network card enabling, etc…) can require the NI2400 to automatically restart; this is normal.
Keyboard Overview
“Up” key
“Left” key
“reset” key
“Right” key
“Down” key
“reset” keys
“Up”, “Down”, “Left” e “Right” keys are used to move within menus and submenus and to
select the options. The “Enter” key is used to conrm the option.
The reset keys are used in case the NI2400 stops working. Pushing both keys at the same
time, you reboot the datalogger.
www.ruggedaq.com
028
www.ruggedaq.com
029
DATALOGGER
NI2400
NI2400
DATALOGGER
NI2400
22
NI2400
Display Overview
Display main page has three icons in the middle and some information in the upper and
lower part of the display.
The information shown in the main page are:
• Date and time
• IP address
• External powering voltage or internal batteries percentage.
• Internal temperature
Date and Time
Icons
DL: It shows NI2400 current status.
To return to main menu press
ACQUISITION
START DL
STOP DL
It is possible to see in real time the current acquired channel. Selecting “Acquisition” between one measureing cycle and the other, an
extemporaneous acquisition will be instantly executed.
Start the data logger if not already running.
Stop the data logger if running.
IP address
Powering
Temperature
Icons in the main page have the following meaning:
LOG: It shows last reading stored for each sensor congured on the NI2400. Through “Right”
and “Left” keys is possible to browse the different sensors.
Humidity
on early models
TEST FTP
TEST MAIL
TEST ALL
SYS: Here you can nd NI2400 connection parameters (network card), calibration values
and functions to download data on USB pen drive, update rmware and NI2400 stop (in
safety mode before cutting the power).
Test FTP parameters with sample le.
Test Mail parameters with sample email.
Test both FTP and Mail.
To return to main menu press “Enter” key.
www.ruggedaq.com
030
www.ruggedaq.com
031
DATALOGGER
NI2400
NI2400
DATALOGGER
NI2400
22
NI2400
ATTENTION: Do not use at the same time the web interface and display functionality.
When you select SYS menu, the NI2400 enters in conguration mode: in this status the
NI2400 WILL NOT PERFORM THE CONFIGURED ACQUISITIONS. Once you ended the operations in SYS menu, you must return in the main page (with the three icons).
Firmware and Web Updates – Vibrating Wire Firmware Update
To update NI2400 web pages and rmware refer to “ FW & WEB UPDATES – Vibr. Wire FW
Update” manual.
Data download
It is possible to download data (readings, log events and log alarms les) in two ways:
• PC (through web interface)
• USB (through USB pen drive)
• Select through keyboard (“Right” and “Left” keys) the SYS menu and press “Enter” key;
If the NI2400 has an acquisition in progress, is necessary to wait its end. In this case will be
displayed the following screen:
• When the acquisition ends, it will be displayed the following screen:
To download data through a PC connected to the NI2400, rst congure the PC network
card (with the NI2400’s same class but with different IP). Through the pages “Data Monitor –
Measures, Events, Alarms” is possible to download les as CSV format (compatible with the
most common spreadsheets eg. Microsoft Excel, Apple Numbers, Open Ofce Calc etc…)
To download data through USB pen-drive (supplied):
• Through “Up” and “Down” keys select the option “Download data on USB” and press
“Enter” key;
www.ruggedaq.com
032
www.ruggedaq.com
033
DATALOGGER
NI2400
NI2400
DATALOGGER
NI2400
22
NI2400
• The following screen will be displayed and the NI2400 will be automatically restarted;
At restart you will be asked to insert the USB pen-drive and to press “Enter” key to start
data download;
• Once the copy is ended, the following message will be displayed; press “Enter” to
proceed;
• Disconnect the USB pen-drive and press “Enter”. The NI2400 will be restarted and the
acquisition will proceed as previously set.
NOTE: the USB pen-drive in the NI2400 must be FAT32 formatted. Other format will
prevent the NI2400 to identify the USB pen-drive and the copy can’t be executed.
• Once the USB pen-drive is mounted, data copy will start automatically (according to
NI2400 acquisitions quantity, the copy could take a few minutes).
• During the copy will be displayed the following screen:
ATTENTION: Do not disconnect the USB pen-drive or cut o the NI2400 pow
ering during the copy, since the copy can be incomplete or corrupted.
Datalogger Stop and Switch O
When is necessary to cut off the power from the NI2400 (for maintenance or other) is strongly recommended to stop the NI2400 following these steps.
Select, through keyboard, DL -> Stop DL.
Select, through keyboard (Right and Left keys), the SYS menu and press “Enter”;
-
www.ruggedaq.com
034
www.ruggedaq.com
035
DATALOGGER
NI2400
NI2400
DATALOGGER
NI2400
22
NI2400
If the NI2400 has an acquisition in progress, is necessary to wait its end. In this case will be
displayed the following screen:
• When the acquisition ends, it will be displayed the following screen:
You will see the following screen:
Now is possible to cut off the NI2400 power (eg. Extract the “V IN” clamp.
NOTE:
This switch o procedure allows NI2400 to end all the writing/reading cycles
on the SD memory card. If NI2400 power is cut without software shutdown,
a scandisk may occur at next boot.
• Using “Up” and “Down” keys select “System shutdown” and press “Enter”:
Display language setup
To modify display language:
• Select “SYS” menu and press “Enter” key:
www.ruggedaq.com
036
www.ruggedaq.com
037
DATALOGGER
NI2400
NI2400
DATALOGGER
NI2400
32
NI2400
• Through “Up” or “Down” keys select “English” and press “Enter” key:
• The selected language will be displayed. Using “Left” and “Right” key is possible to slide
among the different languages. Select the chosen language and press “Enter” key:
WEB INTERFACE
WEB PAGES FUNCTIONALITY
Follows a brief description of the main NI2400 web pages.
STATUS: Shows NI2400 status. In this page is shown the current NI2400 mode:
Run: NI2400 is set and started. It will start acquisitions according to selected congura-
tion.
Config: NI2400 is in conguration mode. No acquisitions are in progress. In this mode is
possible to modify conguration parameters (channel congurations, acquisition time,
etc…), delete and download logs.
“Cong” mode is expected only for “Admin” user
Stop: NI2400 is stopped. No acquisitions are in progress. In this mode is possible to
download logs but is not possible to change the conguration.
• Display interface language will be changed in the selected one.
NOTE:
actually the available languages are ITALIAN ENGLISH AND FRENCH
Moreover is possible to start, stop and set the NI2400 in conguration mode.
CONFIGURATION-ACQUISITIONS: in this page is possible to set acquisition frequency.
CHANNELS CONFIGURATION-LOCALS: in this page is possible to set local analog channels
on the NI2400.
CHANNELS CONFIGURATION –MULTIPLEXER: in this page is possible to set multiplexer
boards and their channels.
ATTENTION: For sensors wiring it is necessary refers to the schemes on the NI2400 web
pages.
CHANNELS CONFIGURATION - DIGITALS: In this page is possible to set digital channels to
allow the NI2400 to read digital instruments.
DATA MONITOR - MEASURE: In this page is possible to display last NI2400 acquisition
cycle. It’s also possible to download NI2400 executed and saved acquisitions.
www.ruggedaq.com
038
www.ruggedaq.com
039
DATALOGGER
NI2400
NI2400
DATALOGGER
NI2400
33
NI2400
Web interface language setup
To modify the web interface language, connect the NI2400 and access to web interface with
the user (Admin or User) that needs to change the language
Then:
• Select , from left menu, “Advanced” and in the submenus “Account Management”;
Figure 22
• In the page that will be displayed select “Language”;
To set up the local analog channels of the NI2400:
• enter the NI2400 with user Admin;
• make sure that the NI2400, in page STATE, is in Cong mode before proceeding. If it is
not in Cong mode, push on CONFIGURE to set up the NI2400 in conguration mode;
Figure 23
• from the left menu, select the page
chAnnElSconfigurATion and afterward the entry locAl;
• Insert the password in the eld “Old password”;
• Press on “Save changes”.
Now the web interface will be converted in the selected language. To convert also the left
menu is necessary to refresh the web page pressing F5 or the specic symbol on internet
browser address bar.
NOTE:
To avoid that the browser will keep the old language is necessary to completely delete
internet browser cache.
Conguration of local analog channels
In this manual is explained how to set up the local analog channels on the NI2400.
NOTE: it is important to make sure that the software conguration of channels coincides
with the physical wirings of sensors on channels. This is necessary to power correctly the
sensors.
Figure 24
The page
and edit the local analog channels of the NI2400.
LOCALChA NNe LSCONFIGURATION opens. In this page it is possible to enable
www.ruggedaq.com
040
www.ruggedaq.com
041
DATALOGGER
NI2400
NI2400
Figure 25
Add the proper sensor that you want to read.
• If your sensor requires two wires (for example a current loop 2W) Add 2 wires sensor
• If your sensor requires four wires (for example a volt 2ch with external supply) Add 4
wires sensor
• If your sensor requires six wires (for example a ratiometric sensor) Add 6 wires sensor
DATALOGGER
NI2400
33
NI2400
For example, if you push on button add 4 wires sensor in the underlying table a 4 wires sen-
sors is added and it is possible to congure it.
Figure 26
After this selection press EDIT to setup sensors channel. Then, the rst page of conguration
of the selected channel opens. In this page it is possible to select:
Figure 27
Input conguration
The page
eters of conguration.
INp UTCONfIgUrA TIONis composed by a table which contains all the input param-
www.ruggedaq.com
042
Figure 28
www.ruggedaq.com
043
DATALOGGER
NI2400
NI2400
DATALOGGER
NI2400
33
NI2400
Particularly:
INp UT
ACQUISITION: the acquisition interval “personalized” for the channel
Id e NTIfICA TION
d e SCrIp TION
Me A SU re Ty p e
p Ow e rSUp p Ly
M e A SUre UNIT
w A rM -Up [Se C]
CONve rSION
ze rOre AdINg
Se NSIb ILITy
Non-editable eld. It indicates the input that is conguring. The
character “_A” or “_B” is added in case of a channel with 2 inputs (ex: 1_A, 1_B)
Field editable from the user. Name to assign to the sensor. This
eld is exported as the heading of the column containing the
measurements of sensor in le .CSV type “Measurements”
Field editable from the user. Description ascribable to the sensor
for a better identication. This eld is present only in le .CSV
type “log measurements”
Type of measurements to read on this input.
Power supply (output voltage or current) that the NI2400 will
supply to the connected sensor. In case it is present “external”,
the NI2400 doesn’t supply any power supply Different power
supplies are proposed according to the “TYPE OF MEASURMENT” selected.
Electrical unit of measure of the sensor. For some types of sensors it is possible to choose between different units of measure
(ex for vibrating wire: digit, Hz, µs).
Field editable from the user. “Warm-up” time of the sensor. It
indicates how long the sensor is powered by the NI2400 before
starting the measurement cycle. For some types of measure-
ments, this eld could be disabled.
This eld allows to select which conversion to realize between
LINEAR and POLYNOMIAL. It is also possible to decide to realize
NO conversion (in this case the reading is expressed in electrical
unit). This eld is necessary to convert the reading of the sensor
from electrical unit (mA, mV, digit, etc.) to engineering unit (kPa,
mm, mbar, etc.)
This eld is enabled if the linear conversion has been selected.
For further information, please refer to manual “Linear and Polynomial Conversion Quick Start”
This eld is enabled if the linear conversion has been selected.
For further information, please refer to manual “Linear and Polynomial Conversion Quick Start”
p OLy NOM IA LCOe ffICIe NTA-b -C-d
e NgINe e rINgUNIT
e x CITA TION
d e LA y
rANge
STA rTfre QUe NCy
STOp fre QUe NCy
gAIN
ex CITA TIONfA CTOr(%)
ex CITA TIONSCA LINgSp e e d
NUM b e rOfde CIM ALS
Sk Ip p e d
This eld is enabled if the polynomial conversion has been selected. For further information, please refer to manual “Linear
and Polynomial Conversion Quick Start”
Field editable from the user. This eld is enabled if the linear or
polynomial conversion is selected. It represents the acronym of
the unit of measure of the reading after the conversion in engineering unit.
This eld is enabled only for the type of measurement “Vibrating
Wire” or “Vibrating Wire + Thermistor”. It indicates (in msec) the
period of each stimulation phase
This eld is enabled only for the type of measurement “Vibrating
Wire” and “Vibrating Wire + Thermistor”. It indicates (in msec)
the stabilization period, i.e. how long the NI2400 waits before
starting the reading phase
This eld allows to set up the range of functioning of the sensor.
If AUTORANGE is congured, the NI2400 decides automatically
with which range it is going to do the measurement. This implies
an increase in the reading time of the sensor.
This eld is enabled only for the type of measurement “Vibrating
Wire” or “Vibrating Wire + Thermistor”. It indicates the frequency of the research start.
This eld is enabled only for the type of measurement “Vibrating
Wire” or “Vibrating Wire + Thermistor”. It indicates the frequency of the research end.
Amplication factor applied to sensors’ signal. Raise this parameter only if sensor is placed far from datalogger and datalogger
provides unexpected or wrong readings.
Maximum amplitude of sensor excitation signal. Lower this parameter only if sensor is placed close to datalogger and provides
unexpected or wrong readings.
This parameter sets adapting speed of excitation signal during
vibraing wire reading.
Number of decimals recorded for this channel
The Data logger does not read the channel, but CSV le will be
populated with “skipped” values. This is to ensure compatibility
with software population layer in case of sensor change/removal.
Some fields will be grayed out depending on chosen sensor.
www.ruggedaq.com
044
www.ruggedaq.com
045
DATALOGGER
NI2400
NI2400
DATALOGGER
NI2400
33
NI2400
NOTE: in case of a channel with 2 inputs, the second conguration webpage is
completely identical to that described above. Other elds could be “blocked”
because they are connected to the conguration executed on input 1.
The second table on the page it is necessary to set up the possible alarm thresholds for the
selected input. In particular:
ALA rM Ty p e
hIgh
Thre ShOLd
LOw Thre ShOLd
High: the input is in alarm only if the reading exceeds
the value indicated in eld
Low: the input is in alarm only if the reading is lower
than the value indicated in eld
Derivate: the input is in alarm only if the reading
differs from the previous reading of a value greater
than or equal to the value indicated in eld
Thre ShOLd
Field editable from the user. It indicates the numerical
value to assign to the high threshold. The value has to
be inserted taking into account the unit of measure of
the reading.
Field editable from the user. It indicates the numerical
value to assign to the low threshold. The value has to
be inserted taking into account the unit of measure of
the reading.
hIghThre ShOLd
LOw Thre ShOLd
d e rIvA Te
• Once the conguration of webpage ended, or of 2 webpages in case of a channel with 2
inputs, push
SAvEmodificATionS to conrm the created conguration.
• It is possible to visualize the scheme of connection of the just congured channel pushing
on
wiringSchEmE in page locAlchAnnElSconfigurATion.
Figure 29
Multiplexer Conguration
Here is shown the standard conguration of an sensor connected to a channel of the multiplexer.
• Open page
localfrom left menu;
localchannelconfiguration and select the itemchannelsconfiguration/
d e rIvA Te Thre ShOLd
vCA LA rM w IThLOgICALOp e rA TIONS
Field editable from the user. It indicates the numerical
value to assign to the derived threshold. The value has
to be inserted taking into account the unit of measure
of the reading.
Enabling this tick, the congured alarm is no longer
connected to the single input. The channels that adopt
this option will be “linked” to each other by logical
operations (AND, OR, NOT and XOR). If this eld is
enabled, therefore it will be necessary to congure a
virtual channel with an opportune logical operation.
NOTE: the values inserted in alarm thresholds have to take into account the
possible linear or polynomial conversion that has been congured. If the user
congured a conversion, the threshold values have to be inserted in engineering unit. If the user didn’t congured any conversion, the thresholds values
Modbus is a serial communication protocol, made by Modicon in 1979 to link their PLC. It
has become a de facto standard in communication protocol, and it’s now a commonly available means of connecting industrial electronic devices.
Advantages in industrial sectors are:
• developed with industrial applications in mind
• openly published and royality-free
• easy to deploy and mantain
• moves raw bits or words without placing many restriction on vendors
Modbus enables communication among many devices connected to the same network, for
example a system that measures temperature and humidity and communicates the results to
a computer. Modbus is often used to connect a supervisory computer with a remote terminal
unit (RTU) in supervisory control and data acquisition (SCADA) systems. Many of the data
types are named from its use in driving relays: a single-bit physical output is called a coil, a
single-bit physical input is called a discrete input or a contact.
Figure 37
• pushing on EdiT it is possible to set up all sensor parameters, as you do for a local analog
channel. The conguration of an analog channel on multiplexer is not different from that
of a local analog channel.
NOTE: once the conguration of all channels of multiplexer ended, it is advised
to push on LOCK. In this way, the conguration is “blocked” and the removal
of one or more sensors doesn’t modify the position of those that are cong-
ured yet.
ATTENTION: the addition of a new sensor to a multiplexer that has been already
congured could cause a change in sensors position on multiplexer channels.
In case of sensors that are physically already connected to the multiplexer, it is
necessary to check that their positions are the same. If the positions changed,
it is necessary to re-wire the sensors to the multiplexer.”
OBJECT TYPEACCESSSIZE
CoilRead-Write1-bit
Discrete Input/ContactRead-Only1-bit
Input RegisterRead-Only16-bits
Holding RegisterRead-Write16-bits
www.ruggedaq.com
050
www.ruggedaq.com
051
DATALOGGER
NI2400
NI2400
Digital Sensors Conguration
For digital sensors, the NI2400 family offers an in-depth conguration. After choosing Baudrate and Maximum RS485 Address (Fig.1), the User can “Save Changes” and start the con-
guration of the sensors.
DATALOGGER
NI2400
33
Click “Next” to proceed the conguration. Fig.4 shows MODBUS parameters. These are usually provided by the sensor’s manufacturer and reported in either the datasheet or instruction
manual.
NI2400
Figure 40
Figure 38
Figure 39
By clicking “Edit” (Fig.2) on the sensor row to congure, the system shows typical sensor (IPI,
H-LEVEL, TILTMETER) and a SmartModbus element (Fig.3).
SmartModbus is selected if the User has a generic modbus sensor.
Figure 41
Modbus Address is sensor’s modbus address, usually settable from the sensor.
Pre Measure Actions:
Some sensors require either a command or a condition to be true before actually pushing
the data in the right register.
Send Command enabled orders the NI2400 to push data (Value eld) in a sensor’s register
www.ruggedaq.com
052
www.ruggedaq.com
053
DATALOGGER
NI2400
NI2400
DATALOGGER
NI2400
33
NI2400
(Reg Address (hex)). You can “Force Multiple Reg” o “Write Coil”.
Wait Condition enabled let the NI2400 check if Coil, Input or Holding are less, more, equal
or different from a chosen Value. It allows also to wait for a certain time.
Endianess allows to select if the sensor use a Little Endian or Big Endian data type.
Acquire Measures:
This section is the actual data reading from the modbus sensor. On most sensors, this is the
only section the User should care of.
Measure n enabled allows the NI2400 to read the register (Holding, Input or Coil) at the
specied “Reg Address (hex)”. Data Type is Signed or Unsigned Integer, Float and Fixend
Point.
Register Number&Order let the User choose which register and in which order data is
stored in. Usually is reported in sensor’s datasheet or instruction manual.
Endianess allows to select if the sensor use a Little Endian or Big Endian data type.
Post Measure Actions:
As Pre Measure Actions, this is not always required, but some sensors need a register to be
written in order to return in standby or reset. Settings are quite similar to Pre Measure Ac-
tions’ Send Command, which can be enabled or not, and actions are Force Multiple Reg,
Write Coil (Register Address is specied in Reg Address (hex) eld) and Wait Time.
Endianess allows to select if the sensor use a Little Endian or Big Endian data type.
Output conguration and alarms 1 & 2
This are channel related settings. The user can specify channel name, a short description,
and data conversion.
Conversion:
Linear: if sensor output is linear, the systems needs to know Zero Point (Ez) and Sensibility(S)
and Number of Decimals (eld will be enabled). The output will be equal to Sx - Ez
Polynomial: if sensor output is not linear this allows the user to specify sensor output curve,
and enable Zero Reading (Ez), Poly.Coeff. A, B, C and D and Number of Decimals. The output will be equal to Ax3 + Bx2 + Cx + D - Ez
Engeneering Units: to complete data with the right engeneering unit like bar,°C, °F, %HR
and so on.
Number of Decimals: after linear or poly conversion, here are the number of decimal digits
the system will round the value at.
Skipped: the system will ignore this sensor
Virtual channel alarm
This section enables Logical Operations with Virtual Channels Alarm. Virtual Channels section allows logial operations between alarms, (AND, OR, XOR, NOT).
Figure 42Figure 43
www.ruggedaq.com
054
www.ruggedaq.com
055
DATALOGGER
NI2400
NI2400
Tips
Multiple Sensor in one single Modbus Device
Our System allows the user to connect one single Modbus device providing information
coming from different sensors.
What if a sensor has more than 2 channels?
The NI2400 allows to create another sensor with the same Modbus address (Fig.9,10,11), so
user can select 4 (or more, creating other sensors) registers to read data from.
Pre Measure Actions (if required) will be set only in rst sensor (relative to the Modbus slave
device) and Post Measure Actions will be set only in last sensor (always relative to the Modbus slave device)”
DATALOGGER
NI2400
33
NI2400
Figure 45
Figure 47
Figure 44
Figure 46
www.ruggedaq.com
056
Figure 48
www.ruggedaq.com
057
DATALOGGER
NI2400
NI2400
DATALOGGER
NI2400
33
NI2400
DATALOGGER CONFIGURATION
Overview
This chapter will explain following webserver configuration pages:
• Change Datalogger’s name
• Acquisition speed and precision
• IoT Enabling
Configuration -> Datalogger
Figure 49
Serial Number: This is the device serial number. It is composed by 8 decimal digits.
Identification: A short string (16 characters maximum) to identify the datalogger.
Identification is used for USB data export. Admitted characters are:
Letters (a-z, A-Z)
Numbers (0-9)
Only this special characters: ._()[]-{}
Non-admitted characters will be substituted with _ (underscore) character.
Measurement Settings (Standard, High Precision, Fast): These are 3 different measure
configurations. User can also modify settings, these are recommended settings.
Fast Measurement: The datalogger does not execute analog autocalibration.
Relay Warmup: Delay time between relay activation and acquisition process
ADC Average Number: Number of average computed by Analog to Digital Converter
Simultaneous Relay Number: number of simultaneously activated relays
Relay time Gain: Relay excitation time (tens of milliseconds)
ADC Speed: ADC Sample rate, in SPS (Sample per Seconds)
Relay Discharge: before acquisition process, all relays are set to short circuit to discharge
capacitors.
Relay Reset: Optimization of relays movements
Turn Off Analog During Warm-up: during sensor’s warm-up, analog board is temporarily
turned off
Analog always on: Analog circuits are turned on at first acquisition cycle (in RUN) and then
won’t be turned off (except when CONFIG or STOP mode are set). This allows faster acquisition rates. In Test Measure mode, analog board is turned on temporarily then turned off
again. If datalogger will go in sleep mode, analog circuit should be re-initialized at next
acquisition cycle.
This page is dedicated to low levels tweaks to improve stability and correct readings.
www.ruggedaq.com
058
Polynomial digit: This field establishes number of decimal digits for channel with Linear or
Polynomial conversions. This number is used if the channel is left at “DEFAULT”. A single
channel can override this setting in its own setting page.
www.ruggedaq.com
059
DATALOGGER
NI2400
NI2400
DATALOGGER
NI2400
33
NI2400
Enable VW Tracking: This option will speed up Vibrating Wire Excitation by lowering the
time needed for frequencies scan.
VW Noise subtraction: It performs a noise analysis of the channel, to have a better SNR
after excitation.
VW Excitation: This field enables the excitation of Vibrating Wire. If it’s disabled, no excitation will be applied while reading vibrating wire, thus making the reading impossible. It
can be used to test with functions generators.
Thermocouple break check: before TC readings, NI2400 inspects TC circuitry to check
total resistance. If value is out of thresholds, TC will be flagged as broken, and NAN, +FS
or -FS will be recorded. If Thermocouple break check is disabled, this control won’t be executed. It is useful to disable this control when using calibrators or mV sources connected as
thermocouple, since their behavior is not the same as Thermocouple’s wire.
FTP file name format: it allows choice between different file name’s formats.
ALARMS
Overview
• NI2400 can handle alarms of both channel (reading out of a determined range) and
device (malfunction, wrong configuration etc.)
• Alarms can be recorded on Alarm logs and can be sent via SMS, EMAIL, FTP or activate
through NI2400’s Digital Output (refer to Chapter1 for more info).
• A first configuration must be done in the Alarm Configuration page (on the web server,
click on “Configuration” and “Alarms”). The following screen will be prompted.
Simple steps to configure alarms:
• Select Output
• Select “Delay”
• Select “End”
Configuration
Low Battery Alarm Threshold: An alarm will be triggered if V IN voltage drops below this
threshold.
IOT Configuration
IOT Enable: This checkbox, enables the communication with Exosite cloud. Read dedicat-
ed chapter for more info.
WARNING: BEWARE OF ENABLING THIS FIELD. BEFORE ENABLING THIS FIELD, BE
SURE TO DELETE ALL MEASURE LOG PRESENT IN MEMORY. IF MEMORY IS NOT
CLEAR, AT THE FIRST ACQUISITION, THE DATALOGGER WILL PROCESS EXISTING DATA AND TRY TO EXPORT TO EXOSITE CLOUD. USUALLY THIS OPERATION
REQUIRES FEW HOURS AND THE DATALOGGER WILL BE STRUCK PROCESSING THIS
DATA FOR NECESSARY TIME.
IOT Cik: This field is dedicated to the CIK field, gathered from Exosite cloud after the cre-
ation of a device. Read dedicated chapter for more info.
Download/Upload Calibration: itallows logger calibration saving or restoring.
Default Settings Recover: It will restore default settings
Reboot: it reboots the datalogger
www.ruggedaq.com
060
Figure 50
In the “SENSOR” section, it is possible to select how NI2400 will handle Sensor’s alarm:
Enabling any of this checkbox will modify datalogger’s action:
• Send SMS will send an SMS (if RS232 modem is connected) with the Alarm
www.ruggedaq.com
061
DATALOGGER
NI2400
NI2400
DATALOGGER
NI2400
33
NI2400
• Send email will send an email (if RS323 modem OR Ethernet connection with internet is
connected) with the Alarm, to specified recipient (see next section)
• Upload on FTP will upload the Alarm Log’s row (if RS232 modem OR Ethernet connection with internet is connected) with the alarm triggered
• Enable Digital Output will trigger the backpanel’s terminal block to control an external
Alarm system
• Frequency increase will increase acquisition frequency to gather more information about
the event that has triggered the alarm. Acquisition Frequency is set at 1 minute when the
channel is in ALARM. If the datalogger is configured to read different sensors, and more
than one sensor is in alarm, reading frequency will probably be lower.
There are pretty much the same options in the “NI2400” Section, except for Frequency
increase.
Event Nr. Dropdown menu will let you choose the number of events in alarm at which
the datalogger triggers the alarm. 1 means at the first occurrence, 2 will skip first value in
alarm, and if it still in alarm during next acquisition the alarm will be triggered, otherwise
there will be no alarm event.
End Dropdown menu will let you choose the number of events after which the datalogger
will cease to trigger. NEVER is the option to disable this feature, and let the datalogger
trigger EVERY set alarm.
After configuration, click Save to proceed.
If you selected SMS, email or FTP, the relative configuration option will be activated.
This page will let you select SMS recipient for triggered alarms.
Number: the recipient(s) of the SMS
Sensor Alarm: if you have selected SMS in sensors alarms this will let you use the current
recipient for the sensor alarm
NI2400 alarm: if you have selected SMS in NI2400 alarm this will let you use the current
recipient for the datalogger’s alarm
Add Measure in alarm: it will attach measure value to the SMS.
Text: it allows a small text writing (up to 30 characters) contained in the SMS
Tries: it makes you choose the number of tries if SMS send fail.
Click save to proceed.
Email Configuration
SMS Configuration
Figure 51
Figure 52
This page will let you select the email recipient for triggered alarms.
Address: the email address of the recipient
Sensor Alarm: if you have selected email in sensors alarms this will let you use the current
recipient for the sensor alarm
Datalogger alarm: if you have selected email in datalogger alarm this will let you use the
current recipient for the datalogger’s alarm
Object: email’s object
Text: a small text (30 charaxters) to be sent with email
SMTP Configuration: it will open a new page to configure SMTP parameters
Save Changes to proceed
www.ruggedaq.com
062
www.ruggedaq.com
063
DATALOGGER
NI2400
NI2400
SMTP Configuration
DATALOGGER
NI2400
33
This page allows FTP connection configuration. Sending Measure Table is related to
Measure log transfer and this is explained in the related section.
FTP Configuration table allows to setup all parameters for FTP server connection. If the
server is not on the same LAN, a 3G modem or Internet connection is required.
Server: it is the server address
Folder: it allows to specify subfolder to be used. The directory MUST exist
Username and Password: credentials used to connect to the server
Port: port used to connect to the server
Tries: number of attempts in case of failure.
Save changes to continue
WARNING: Only standard FTP (not encrypted) is supported.
NI2400
Figure 53
This page allows the setup of SMTP parameter .
SMTP Server: the smtp server to send mail
Port: port used to communicate with SMTP Server
Username and Password: Credentials to be used to send email
Retry: number of retry(ies) in case of transmission errors.
Send test email: it will send an email to check if parameters are correct
WARNING: Only standard SMTP (not encrypted) is supported.
FTP Configuration
Channel Alarm Types
Thresholds in NI2400 alarm settings are here described.
WARNING: all alarms evaluations are computed AFTER linear or polynomial conversion, if any.
Low and High Thresholds
Thresholds are basically limits to sensor’s ranges. If a threshold is overcome (lower value so
low threshold, or higher value so high threshold), the alarm is triggered.
Derivate
Derivate alarm will analyze, at n sample, value of n-1 sample and compare to n sample.
If value(n)-value(n-1)>threshold, an alarm is triggered.
Examples
www.ruggedaq.com
Figure 54
064
Derivate alarm, linear conversion
(Ln*S+Lz)-(Ln-1*S+Lz) > threshold
Ln is last sample, while Ln-1 is second-last sample. S is sensibility parameter and Lz is offset
(Zero reading) in linear conversion’s channel settings.
www.ruggedaq.com
065
DATALOGGER
NI2400
NI2400
DATALOGGER
NI2400
33
NI2400
DIGITAL INPUTS CONFIGURATION
The NI2400 has two digital inputs (IN1 & IN1) on its back side.
To set up a digital input it is necessary:
• to select the entry
• the page digiTAlinpuTSconfigurATion opens. In this page it is possible to set up 1 or
both digital inputs independently;
chAnnElconfigurATion, then digiTAlinpuTS;
Figure 55
The digital inputs could be congured to acquire a
e M OM e Te r. The trigger could be used with a seismic station and it is used to start one or
more acquisitions extemporaneous.
NOTE: in case of a rain gauge or anemometer, no elaboration of reading is considered
(ex: average speed, maximum, instantaneous, daily storage, etc.)
TrIgge ror an rAINgA Uge or an AN-
Figure 56
www.ruggedaq.com
066
www.ruggedaq.com
067
DATALOGGER
NI2400
NI2400
DATALOGGER
NI2400
33
NI2400
• in this page you could nd the following elds:
INx INp UT (X is 1 or 2)Using the drop-down menu, it is possible to select
the type of digital input between 4 possibilities:
- d ISAb Le d
- TrIgge r
- rAINgA Ug e
- w INd gAUge
The input has to be congured according to the sen-
sor that is connected.
ACQUISITIONfre QUe NCy
Se NSIb ILITy
Sampling rate of selected channel (wind gauge, rain
gauge)
This eld enables only for RAIN GAUGE and AN-
EMOMETER. If it is well congured, it allows to
transform the counts in engineering units (ex: from
“counts” to “mm”)
Example of digital input IN1 conguration
Here is shown the standard conguration of a digital input congured as
• open page
digiTAlinpuTSfrom left menu;
digiTAlinpuTconfigurATion and select the entry chAnnElSconfigurATion /
TriggEr.
e dge
UNITM e A SUre
NUM b e rOfre A d INgS (TrIgge r)
This eld enables only for TRIGGER. It is possible to
select between two entries:
change could be high-low (DOWN) or low-high (UP).
Therefore, if on the input generally there is no voltage
and you want to do an acquisition with the NI2400,
in case a voltage arrives on the input (ex: 5Vdc) it is
necessary to select Up. This because you pass from a
low (0Vdc) to a high (5Vdc) state.
This eld enables only for RAIN GAUGE and WIND
GAUGE. It indicates the unit of measure of the read
value.
Editable eld. Numerical value. This eld enables only
for TRIGGER. It indicates how many extemporaneous
and consecutive acquisitions the NI2400 has to do
with a trigger. Acquisitions are done independently
from the congured acquisition interval. These data
are stored and so they could be exported in CSV le.
Up or dOw N. The state
Figure 57
• in eld inpuTin1 select TriggEr;
Figure 58
• in eld EdgEselect up;
NOTE: if you enable the digital inputs, the NI2400 is in permanent acquisition. This
means that, even if the NI2400 is in Timed, he will never go in “low consumption” mode.
This situation has to be taken into account in case it is necessary to optimize the consumptions (for example with batteries or solar panel)
www.ruggedaq.com
068
NOTE: in this example it has been selected UP because we supposed there is any voltage
on digital input IN1 and that in case of a trigger, a voltage of 5Vdc is applied.
www.ruggedaq.com
069
DATALOGGER
NI2400
NI2400
DATALOGGER
NI2400
33
NI2400
•In eld numbErofrEAdingS (TriggEr) insert the number of acquisitions you want that the
NI2400 does after a trigger signal (ex.5)
Figure 59
• Push SAvEchAngES to conrm the conguration.
Example of digital input IN2 conguration
Here is shown the standard conguration of a digital input congured as rAingAugE.
• open page
digiTAlinpuTSfrom left menu;
digiTAlinpuTconfigurATion and select the entry chAnnElSconfigurATion /
The NI2400, with this conguration, in case it receives a positive voltage on digiTAlinpuT in1,
does 5 consecutive acquisitions of all congured channels.
A practical example of the use of trigger function is that of associate NI2400 to a Seismic
Station. The majority of Seismic Stations has the possibility, in case of a seismic event, to
activated a digital output (an output voltage). If this signal is connected directly to the digi
tal input IN1 of the NI2400, when a seismic event happens the Seismic Station furnishes a
digital output on the digital input of the NI2400. The NI2400 starts to acquire all connected
sensors to verify the monitoring area after the event.
-
Figure 60
• in eld inpuTin2 select rAingAugE;
www.ruggedaq.com
070
www.ruggedaq.com
Figure 61
071
DATALOGGER
NI2400
NI2400
DATALOGGER
NI2400
33
NI2400
• in eld SEnSibiliTyinsert the sensibility of sensor (for example 0.2 mm/count);
• in eld
“mm”)
With this conguration, the NI2400 acquires the number of impulses for a period of a hour.
Once this interval ends, the NI2400 memorizes the number of counts done during this pe
riod of time.
If for example in one hour 5 counts are detached, the NI2400 applies the following conver
sion:
Once tche value is memorized, the counter sets to zero.
Alarm conguration is the same as all other channel types, with High, Low and Derivative
Thresholds. VC alarm with Logical Operations is present, as a Virtual Channel alarm can be
used in Virtual Channels Logical Alarms.
uniTofmEASurE insert the unit of measure of the done conversion (example
Figure 62
5 COUNT * 0.2 MM/COUNT = 1 MM
VIRTUAL CHANNELS
Overview
This chapter is focused on Virtual Channels (VC from now on), to understand why VC are
implemented on OM datalogger and how to configure them.
1. Why are Virtual Channels implemented in OM Family? – This paragraph shows benefits
of Virtual Channels
2. Scripts – Scripts are a fundamental section of Virtual Channels’ architecture.
3. Virtual Channels configuration – “HOW TO” use and configure Virtual Channels’ with
analog and digital sensors, digital input and multiplexers.
-
-
4. Common Errors – Here are shown common errors made during virtual channels creation,
and how to avoid them.
Why are Virtual Channels Implemented?
We usually use sensors to get a measure. Anyway, we could need a way to modify that
number because we need either a derived measure (airflow/airspeed) or an expression cal-
culated on more than 1 sensor (dewpoint or Δt between two zones for instance). We can
calculate this with spreadsheet or just let our datalogger do the work.
OM Family has this feature with Virtual Channels.
Virtual Cannels allows operations to be made on a single channel or between channels.
OM group them into Scripts, with a maximum of 5 scripts containing 16 virtual channels
each. Each Virtual Channel can handle up to 9 elements (including Virtual Channel beloning
to the same script).
www.ruggedaq.com
072
Figure 63
www.ruggedaq.com
073
DATALOGGER
NI2400
NI2400
Scripts
NI2400 automatically provides the script name during its creation. Acquisition timing can
be chosen between 1 second and 7 days, with “DEFAULT” option not overriding NI2400
global acquisition timing.
After selecting “Create” button the new script will be listed below:
DATALOGGER
NI2400
33
NI2400
Figure 64
Edit button allows the configuration of Virtual Channels contained by the selected Script.
As we see in following Figure, NI2400 provides a large toolbox to program Virtual
Channels.
Figure 66
an: selects an analog channel (prompts a dialog box to input channel number)
dig: selects a digital channel (prompts a dialog box to input channel number)
mux: selects multiplexer position (prompts two dialog boxes, the 1st for channel number,
the 2nd for mux address)
cv: selects a virtual channel (only those included in the same script, prompts a dialog box
for CV number)
Apart from this we have mathematics operations, like +, -, *, /, sin, cos, tan, pi-value.
Logical operations allow operations between alarms states. Every channel (analog, digital, virtual and mux) provides a checkbox in alarm configuration, VC Alarm with Logical
Operations. This enables alarms to be handled by virtual channels.
Figure 67
The following Virtual Channel will trigger an alarm only if one of the two channels is in
alarm.
Figure 65
www.ruggedaq.com
074
Figure 68
www.ruggedaq.com
075
DATALOGGER
NI2400
NI2400
DATALOGGER
NI2400
33
NI2400
an(1.A)an(2.A)an(1.A) XOR an(2.A)
FFF
FVV
VFV
VVF
an(1.A)an(2.A)an(1.A) AND an(2.A)
FFF
FVF
VFF
VVF
an(1.A)an(2.A)an(1.A) OR an(2.A)
FFF
FVV
VFV
VVV
Alarm configuration is the same for all channel types, with High, Low and Derivative
Thresholds. VC alarm with Logical Operation is present, as a Virtual Channel alarm can be
used in Virtual Channels Logical Alarms.
Common Errors and Warnings
In order to write Virtual Channel’s formula correctly, you should avoid typing the whole formula in the dialog box prompted by the system.
WRONG
an(1.A)NOT an(1.A)
FV
VF
Virtual Channel Configuration
By clicking “config” in the Virtual Channel row (Figure 23) the user can edit Identification (channel
name) and alarm properties.
Figure 70
Figure 69
www.ruggedaq.com
076
Figure 71
www.ruggedaq.com
077
DATALOGGER
NI2400
NI2400
DATALOGGER
NI2400
33
NI2400
As you can see this causes an error.
Formula has to be written using keys printed on the screen. The prompt should be used
ONLY to write channel number.
The same procedure applies for dig, mux and cv buttons.
ADVANCED CONFIGURATION
Overview
Advanced parameters are explained in this section.
•Connection configuration, for Ethernet and 3G modem parameters
• Measure log transfer, for FTP server configuration
• Account management, to change account passwords
• Date and Time, to change timezone or set daytime saving
• Energy management, to improve power consumption especially if battery powered
• Information about firmware versions, mac address, bootloader
This section will show how to configure Advanced parameters in the NI2400’s web server.
Connections
Figure 72
Figure 73
Figure 74
WARNING: Channel B (1.B, 2.B, and so on) can’t be used on Virtual Channels. If you need
to use the channel B of a multiaxis sensor, like Voltage 2CH, Vibrating Wire + Thermistor,
and all others, you should use 2 separate channels during configuration.
www.ruggedaq.com
078
This page allows to set network parameters.
In the first block you select which connection will be used by NI2400 to send Email and FTP
files.
Network Card Configuration
DHCP Enable: to choose whether or not to use DHCP or specify network parameters
www.ruggedaq.com
079
DATALOGGER
NI2400
NI2400
DATALOGGER
NI2400
33
NI2400
IP Address, Subnet Mask and Default Gateway, DNS Servers addresses depend on network infrastructure.
Figure 75
This settings are related to 3G modem. Parameters are usually provided by telephone operator.
WARNING: Remember to set DNS also on RS-232 2G/3G modem.
Measure log data transfer
www.ruggedaq.com
080
Figure 76
This page contains data transfer settings.
Sending Measure block allows to choose the way to send data:
None: no data transfer
Email: data will be transferred via email
FTP: data will be transferred via FTP
FTP Configuration block contains the configuration to create an FTP connection with a
user’s server.
www.ruggedaq.com
081
DATALOGGER
NI2400
NI2400
DATALOGGER
NI2400
33
NI2400
Account Management
Date and Time
Figure 77
Here it is possible to change the passwords for User and Admin accounts, and to change
web language.
Figure 78
In this screen it’s possible to change date, hour and Timezone.
www.ruggedaq.com
082
www.ruggedaq.com
083
DATALOGGER
NI2400
NI2400
DATALOGGER
NI2400
33
NI2400
Energy Management
Activation
In order to activate charts, you have to buy a key from dealer. Load Data Monitor -> Charts
page and insert the key in the right field and click Submit button.
Figure 79
This page is about Energy Management.
NI2400 can work in 2 modes:
Always On: the datalogger does not turn off itself to save energy, Ethernet connection is
available.
Timed: The datalogger turns off itself, waking up few minutes before acquisition starting.
VOUT port can be kept always on, or timed.
Info
This page contains information about firmware, web, bootloader and model. Note this
parameters in case of assistance enquiry.
CHARTS
Figure 80
Setup and Use
From the Web Server pages go in “Data Monitor” and then click “Charts”. This screen will
be loaded.
Figure 81
Overview
NI2400 is provided with a simple tool to generate Charts. It’s available on request and
need to be activated with a Purchased Key. Contact your dealer for more information.
It’s possible to export data and save charts as pdf, png or vector files.
www.ruggedaq.com
084
No chart is available at this time, and we need to create one.
Click on “Configure chart” to proceed.
The next screen will ask for Start and Stop date, and you will need a Logarithmic scale
(Log scale check) to allow different unit channels to fit the same chart and be readable.
www.ruggedaq.com
085
DATALOGGER
NI2400
NI2400
DATALOGGER
NI2400
33
Color window let the user select the color of that channels. A full palette is available.
NI2400
Figure 82
Click Next to proceed.
Sensor select screen allows channels selection, so you choose which channel(s) you want to
include in the chart. One or more sensors should be selected to go further on.
Axis selection create up to 3 vertical axis related to that channel. If different scales are
presents, this solves readability troubles.
Figure 84
Marker checkbox, will put markes points on the charts as shown here (AN_0001 has Marker
checked, other channels instead do not).
Figure 85
Figure 83
www.ruggedaq.com
086
Click Next to go on last configuration screen.
Here it is possible to choose Chart’s Title, Subtitle, Description and Name.
www.ruggedaq.com
087
DATALOGGER
NI2400
NI2400
DATALOGGER
NI2400
33
Figure 88
You can now select the new chart from “Saved charts selection” and Plot every time you
need. It can be autoupdated after every new acquisition event by checking autoupdate
flag, or manually updated with “update” button, in bottom left area of the window.
NI2400
Figure 86
Click “Plot data” to load the chart.
Figure 87
From this screen it’s possible to print or download the chart:
Figure 89
www.ruggedaq.com
088
www.ruggedaq.com
089
DATALOGGER
NI2400
NI2400
DATALOGGER
NI2400
44
NI2400
MODBUS TCP (SCADA INTEGRATION)
Overview
Modbus ADU (application data unit) is sent in form of TCP packets. All Modbus TCP ADU
are sent via TCP to registered port 502.
Modbus over TCP allows NI2400 integration in LabVIEW and SCADA systems. By reading
holding registers, it’s possible to gather all sensors data (analog, smartmodbus, multiplexers, digital inputs), events and alarm, datalogger status and information.
• It’s possible to read sensor’s alarm status.
• By integrating NI2400 in a SCADA, industrial plant remote monitoring and logging are
possible without the need on-site visits.
• Maintenance costs are reduced through centralized control and monitoring to minimize
downtime.
• Centralized alarms to improve operational effectiveness.
• Data could be available in mobility (depending on used SCADA).
Communication bus for this module is Ethernet interface.
Port used for TCP communication is 502 (Modbus TCP Standard Port)
Modbus function to use for registry reading is ReadHoldingRegister.
Measure Register
For each sensor (analogs, digitals, multiplexers and virtual channels), 16 registers will be
exported. Input A’s last acquired measure (Offset 0-1), input b (Offset 2-3), sensor’s temperature (Offset 4-5), Acquisition’s timestamp (Offset 6-7-8-9-10-11-12-13-14) and different
flags to show acquisition status and alarm status (Offset 15).
Measures will be communicated in float IEEE754 standard.
Endialess can be user configured by writing 0-1-2-3 values into configuration register at
0x5000 address.
Following table will represent 4 endianless configurations:
IEEE754 = AA:BB:CC:DD
AA = MSB
DD = LSB
Configuration=0 (default)
Timestamp details
Timestamp is composed by 9 registers, with offset 6 (MSB) to 15 (LSB). Timestamp is an
ASCII string 18 bytes long, in the following format: “dd/mm/yy hh:mm:ss”
Flag’s Register
Flag’s register is mapped as it follows:
BIT CONTENT
0Sensor acquired
1A valid Input
2B valid Input
3Valid Temp input
4A alarm Input
5B alarm Input
6Temp alarm Input
www.ruggedaq.com
090
www.ruggedaq.com
091
DATALOGGER
NI2400
NI2400
DATALOGGER
NI2400
44
NI2400
Sensor Acquired
This register is set to 1 when sensor is acquired and a new data is available. SCADA (or
Modbus Master) reads the updated register and reset it to 0 by using Coils Functions. In
this way the system is ready to note the presence of a new acquisition.
This BIT is also accessible through read/write coils functions.
Coils are mapped on flag “Sensor Acquired” having referral to base address of each sensor.
To obtain Coil address of a sensor, Use the following formula:
Coil Address = Base Address/10
Base Address computation will be shown in next pages.
Example 1
Channel: CH4
Base Address: 30
Coil Address: 3
Example 2
REGISTER MAP
General
All this registers are read-only.
Only “Sensor Acquired” BIT is read-write, using Write single/multiple coils.
Analog Sensors Locations
REGISTER ADDRESS (DEC)DESCRIPTIONSENSOR
0-1MSB-LSB Input A LOCAL CH1CH1
2-3MSB-LSB Input B LOCAL CH1CH1
4-5MSB-LSB Temperature LOCAL CH1CH1
6-14Timestamp acquisition LOCAL CH1CH1
15Flags LOCAL CH1CH1
16-17MSB-LSB Input A LOCAL CH2CH2
18-19MSB-LSB Input B LOCAL CH2CH2
Channel: DIG2
Base Address: 90
Coil Address: 9
By using Coil functions, Modbus Master will be able to read the entire Coil Vector (858
sensors) in a single Modbus transaction, to understand acquired sensors and to read only
updated measures, without the need to read the 10 registers block every time.
Input X Valid
It indicates if matching Inputs are valid or not.
If sensor is configured as Volt 1CH, registers status will be:
• Input A Valid: 1
• Input B Valid: 0
• Input temp Valid: 0
For a digital single channel sensor, registers status will be:
• Input A Valid: 1
• Input temp Valid: 1
• Input B Valid: 0
20-21MSB-LSB Temperature LOCAL CH2CH2
22-30Timestamp acquisition LOCAL CH2CH2
31Flags LOCAL CH2CH2
…
…
…
…
112-113MSB-LSB Input A LOCAL CH8CH8
114-115MSB-LSB Input B LOCAL CH8CH8
116-117MSB-LSB Temperature LOCAL CH8CH8
118-126Timestamp acquisition LOCAL CH8CH8
127Flags LOCAL CH8CH8
Digital Sensors Locations
BASE_DIG+0 BASE_DIG+1
MSB-LSB Input A DIGITAL 1DIG1
Input X Alarm
It indicates if matching inputs are in alarm.
www.ruggedaq.com
092
BASE_DIG+2 BASE_DIG+3
www.ruggedaq.com
MSB-LSB Input B DIGITAL 1DIG1
093
DATALOGGER
NI2400
NI2400
DATALOGGER
NI2400
44
NI2400
BASE_DIG+2 -
MSB-LSB Input B DIGITAL 1DIG1
BASE_DIG+3
BASE_DIG+4 -
MSB-LSB Temperature DIGITAL 1DIG1
BASE_DIG+5
BASE_DIG+6 -
Timestamp acquisition DIGITAL 1DIG1
BASE_DIG+14
BASE_DIG+15Flags DIGITAL 1DIG1
………
………
………
BASE_DIG+4048 - BASE_DIG+4049MSB-LSB Input A DIGITAL 254DIG254
………
………
………
BASE_MUX+496 -
MSB-LSB Input A MUX 1- CH32MUX1 - CH32
BASE_MUX+497
BASE_MUX+498 -
MSB-LSB Input B MUX 1- CH32MUX1 - CH32
BASE_MUX+499
BASE_MUX+500 -
MSB-LSB Temperature MUX 1- CH32MUX1 - CH32
BASE_MUX+501
BASE_MUX+502 -
Timestamp acquisition MUX 1- CH32MUX1 - CH32
BASE_MUX+510
BASE_MUX+511Flags MUX 1- CH32MUX1 - CH32
BASE_DIG+4050 - BASE_DIG+4051MSB-LSB Input B DIGITAL 254DIG254
BASE_DIG+4052 - BASE_DIG+4053MSB-LSB Temperature DIGITAL 254DIG254
BASE_DIG+4054 - BASE_DIG+4062Timestamp acquisition DIGITAL 254DIG254
BASE_DIG+4063Flags DIGITAL 254DIG254
Multiplexers Sensors Locations
BASE_MUX+0 -
MSB-LSB Input A MUX 1- CH1MUX1 - CH1
BASE_MUX+1
BASE_MUX+2 -
MSB-LSB Input B MUX 1- CH1MUX1 - CH1
BASE_MUX+3
BASE_MUX+4 -
MSB-LSB Temperature MUX 1- CH1MUX1 - CH1
BASE_MUX+5
BASE_MUX+512 -
MSB-LSB Input A MUX 2- CH1MUX2 - CH1
BASE_MUX+513
BASE_MUX+514 -
MSB-LSB Input B MUX 2- CH1MUX2 - CH1
BASE_MUX+515
BASE_MUX+516 -
MSB-LSB Temperature MUX 2- CH1MUX2 - CH1
BASE_MUX+517
BASE_MUX+518 -
Timestamp acquisition MUX 2- CH1MUX2 - CH1
BASE_MUX+526
BASE_MUX+527Flags MUX 2- CH1MUX2 - CH1
………
………
…MUX3MUX3
BASE_MUX+6 -
Timestamp acquisition MUX 1- CH1MUX1 - CH1
BASE_MUX+14
BASE_MUX+15Flags MUX 1- CH1MUX1 - CH1
www.ruggedaq.com
094
…MUX4MUX4
………
www.ruggedaq.com
095
DATALOGGER
NI2400
NI2400
………
…MUX15 CH1MUX15 - CH1
………
BASE_MUX+8176 -
BASE_MUX+8177
BASE_MUX+8178 -
BASE_MUX+8179
BASE_MUX+8180 -
BASE_MUX+8181
BASE_MUX+8182 -
BASE_MUX+8190
BASE_MUX+8191Flags MUX_16 - CH_32MUX16 - CH32
Digital Inputs Locations
BASE_DIN+0 -
BASE_DIN+1
BASE_DIN+2 -
BASE_DIN+3
BASE_DIN+4 -
BASE_DIN+5
BASE_DIN+6 -
BASE_DIN+14
BASE_DIN+15Flags DigIn1DigIn1
MSB-LSB Input A MUX_16 - CH_32MUX16 - CH32
MSB-LSB Input B MUX_16 - CH_32MUX16 - CH32
MSB-LSB Temperature MUX_16 CH_32
Timestamp acquisition MUX_16 CH_32
MSB-LSB Input A DigIn1DigIn1
MSB-LSB Input B DigIn1DigIn1
MSB-LSB Temperature DigIn1DigIn1
Timestamp acquisition DigIn1DigIn1
MUX16 - CH32
MUX16 - CH32
DATALOGGER
NI2400
44
Virtual Channels Locations
BASE_DIN+22 -
BASE_DIN+30
BASE_DIN+31Flags DigIn2DigIn2
BASE_VIRT+0 -
BASE_VIRT+1
BASE_VIRT+2 -
BASE_VIRT+3
BASE_VIRT+4 -
BASE_VIRT+5
BASE_VIRT+6 -
BASE_VIRT+14
BASE_VIRT+15Flags Script1 Ch1Script1 - Ch1
BASE_VIRT+16 -
BASE_VIRT+17
BASE_VIRT+18 -
BASE_VIRT+19
BASE_VIRT+20 -
BASE_VIRT+21
BASE_VIRT+22 -
BASE_VIRT+30
BASE_VIRT+31Flags Script1 Ch2Script1 - Ch2
………
NI2400
Timestamp acquisition DigIn2DigIn2
MSB-LSB Input A Script1 Ch1Script1 - Ch1
MSB-LSB Input B Script1 Ch1Script1 - Ch1
MSB-LSB Temperature Script1 Ch1Script1 - Ch1
Timestamp acquisition Script1 Ch1Script1 - Ch1
MSB-LSB Input A Script1 Ch2Script1 - Ch2
MSB-LSB Input B Script1 Ch2Script1 - Ch2
MSB-LSB Temperature Script1 Ch2Script1 - Ch2
Timestamp acquisition Script1 Ch2Script1 - Ch2
BASE_DIN+16 -
BASE_DIN+17
BASE_DIN+18 -
BASE_DIN+19
BASE_DIN+20 -
BASE_DIN+21
www.ruggedaq.com
MSB-LSB Input A DigIn2DigIn2
MSB-LSB Input B DigIn2DigIn2
MSB-LSB Temperature DigIn2DigIn2
096
………
………
BASE_VIRT+1264 -
MSB-LSB Input A Script5 Ch16Script5 - Ch16
BASE_VIRT+1265
BASE_VIRT+1266 -
MSB-LSB Input B Script5 Ch16Script5 - Ch16
BASE_VIRT+1267
www.ruggedaq.com
097
DATALOGGER
NI2400
NI2400
DATALOGGER
NI2400
44
NI2400
BASE_VIRT+1268 -
MSB-LSB Temperature Script5 Ch16Script5 - Ch16
BASE_VIRT+1269
BASE_VIRT+1270 -
Timestamp acquisition Script5 Ch16Script5 - Ch16
BASE_VIRT+1278
BASE_VIRT+1279Flags Script5 Ch16Script5 - Ch16
SENSORS BASE ADDRESS
Following formulas will show how to get every connected sensor’s base address.
This register set handles Event Log status.
For every log, timestamp, and code is exposed.
This register set starts at Modbus address 0x3800 (14336 DEC).
This register exposes information about the datalogger. Base Address for this register is
BASE_DIN
8 CH24 CH
1241612672
www.ruggedaq.com
098
www.ruggedaq.com
099
DATALOGGER
NI2400
NI2400
DATALOGGER
NI2400
44
NI2400
0x4000 (16384 DEC) It can be read in every way, as there is no bond on alignments or
number of registers to read.
REGISTER (DEC)DESCRIPTION
16384Datalogger status
16385Next acquisition MSB
16386Next acquisition
16387Next acquisition LSB
16388Firmware version MSB
16389Firmware version LSB
16390Model info 1
16391Model info 2
16392Model info 3
16393Model info 4
16394Model info 5
16395Model info 6
16396Model info 7
16397Model info 8
16398Model info 9
16399Model info 10
16400Model info 11
16401Model info 12
16402Serial number 1
16402Serial number 2
Datalogger Status
This register contains datalogger status.
REGISTER VALUEDESCRIPTION
1Ready
2Run
3Stop
4Configuration
5Alarm
6Diagnostic
7Error
8Backup
Next Acquisition
This register, composed by 48 bits, exposes next acquisition’s timestamp, when the datalogger acquires the next sensor.
BITDESCRIPTION
0-5Seconds (0-59)
6-11Minutes (0-59)
12-16Hours (0-23)
17-21Day (1-31)
22-25Month (1-12)
26-32Year (0-99)
33-47Reserved
16403Serial number 3
16404Serial number 4
16405Device name 1
16406Device name 2
16407Device name 3
16408Device name 4
16405Device name 5
16406Device name 6
16407Device name 7
16408Device name 8
16409External digital input status (LSB) + External digital output status (MSB)
www.ruggedaq.com
0100
Firmware Version
These two registers, composed in the format A.B.CD, expose firmware version loaded on
the datalogger
REGISTERBITSDESCRIPTION
Firmware version MSB15-8A
Firmware version MSB7-0B
Firmware version LSB15-8C
Firmware version LSB7-0D
Letters A, B and C, contain binary value of versions (values from 0 to 99).
Letter D contains, if present, ASCII value of alphanumeric character that could be present at
the end of the version string to identify special firmwares. If D is not present, its value will be 0.
www.ruggedaq.com
0101
DATALOGGER
NI2400
NI2400
DATALOGGER
NI2400
54
NI2400
Model Info
This register, when chained, forms a 24 character string to identify configured datalogger
model. Chaining should be executed starting from Model info 1 to Model info 12 registers.
Example:
Model info 1 MSBModel info 1 LSBModel info 2 MSBModel info 2 LSBModel info 3 MSBModel info 3 LSB
MAXLOG
Serial Number
This register, when chained, forms an 8 characters long string to identify datalogger’s serial
number. Chaining should be executed starting from Serial Number 1 to Serial Number 4
registers.
Example:
Serial num. 1
MSB
15214796
Serial num. 1
LSB
Serial num. 2
MSB
Serial num. 2
LSB
Serial num. 3
MSB
Serial num. 3
LSB
Serial num. 4
MSB
Serial num. 4
LSB
INTERNET OF THINGS
Overview
In this chapter IoT functionality (optional) offered by NI2400 Datalogger are described,
even if it does not cover all configuration aspects that Exosite portal offers. For an accurate
description of all this aspects, please refer to the documentation page on Exosite portal:
https://support.exosite.com/hc/en-us/sections/200072708-Portals-Web-InterfaceThe first paragraph of this guide is about following steps:
1. Add a device on Exosite portal
2. Configure the datalogger
3. Add data sources
4. Create Dashboard and add desired widgets
ADD A DEVICE ON EXOSITE PORTAL
Login to the Exosite portal at https://zionos.exosite.com/login
Device Name
This register, when chained, forms a 16 characters string which represents datalogger’s
name. Chaining must be executed starting from Device name 1 register to Device name 8
register.
Example of Device name register’s chaining (Device name: Bridge_1)
Device name
1 MSB
Bridge_1
Device name
1 LSB
Device name 2
MSB
Device name
2 LSB
Device name 3
MSB
Device name
3 LSB
Device name
4 MSB
Device name
4 LSB
External digital input/outputs status
This register contains digital input/output current status.
MSB
It contains external digital output status
LSB
Figure 90
It contains external digital input status
B15B14B13B12B11B10B9B8B7B6B5B4B3B2B1B0
##O6O5O4O3O2O1##I6I5I4I3I2I1
www.ruggedaq.com
0102
www.ruggedaq.com
0103
DATALOGGER
NI2400
NI2400
And access to your portal’s homepage:
55
Figure 93
DATALOGGER
NI2400
NI2400
Figure 91
The left menu on this page is to navigate through the portal sub sections.
In order to manage (and add) devices click on Device menu item and access to the following page:
In this example a device called NI2400 has been added. You can always click on the
name of the device and review all the configurations done during the previous steps.
By clicking on the device name, you should get the following page where you can see
the CIK field:
Figure 92
In this page all devices currently added to the portal are showed. To add a new
device, click on the link at the top right of the page and you will be guided through a
step-by-step procedure to configure the device. At the end of procedure you should
get the following screen:
www.ruggedaq.com
0104
Figure 94
this field has been automatically generated by the system and will permanently identify the device in the portal.
www.ruggedaq.com
0105
DATALOGGER
NI2400
NI2400
CONFIGURE THE DATALOGGER
IOT section
Connect to the datalogger through its web server and navigate to the page Configuration →
Logger
DATALOGGER
NI2400
55
NI2400
Figure 95
In this page you have to enable the IOT feature checking IOT Enable check box and in
the IOT Cik enter the CIK obtained in the previous step in the Exosite portal.
In this way you create the association between this physical device and the virtual
device added in the Exosite portal in the previous step.
Figure 96
In this page you should configure all parameters that allow the datalogger to access
the Internet.
These settings depend on your network configuration.
Acquisition configuration
Configure the datalogger for the acquisitions that you need.
Every configured input (analog, digital, mux, virtual) is a data source for your Exosite
portal. The identification name that you give to the input is also the alias that will identify this input on the Exosite portal.
In the following example two analog sensors have been added to datalogger configuration.
The first is sensor has two inputs (VW + NTC) called AN_1_A and AN_1_B
The second sensor has just one input (Voltage) called AN_2_A
Connections Configuration
Navigate to the page Advanced > Connections
www.ruggedaq.com
0106
Figure 97
www.ruggedaq.com
Figure 98
0107
DATALOGGER
NI2400
NI2400
Figure 99Figure 100
AN_1_A, AN_1_B and AN_2_B are e xactly the alias for the data source that must be
configured in the Exosite portal in the next step.
ADD DATA SOURCES
DATALOGGER
NI2400
55
WARNING: Only use “A-Z,a-z,0-9,_” characters in Alias and channel identification.
In this page it is important that following field must be set in the following way:
NI2400
Figure 102
On the Exosite portal, go to the device page by clicking on Device menu item. In the
device list you should find the device (NI2400 in this example) added on chapter 1.
By clicking on this device you should reach the configuration page of this device. In
the top right of this page you have the data list where you can see the data source
associated to this device. At the moment the list should be empty; you can add data
source with the button Add Data.
Data Source Format : string
Alias : the name of the input configured on omnia in chapter 2, AN_1_A in this example
The field Data Source Name can be used to insert a description of the input; the other
field should be left to default.
After saving the configuration you should repeat the procedure for all the input configured on omnia during chapter 2.
After this steps, come back to Device page and by clicking on device name you should
see the list of all the data source added to this device, in this example AN_1_A,
AN_1_B and AN_2_A:
Figure 101
Here you should add all the data source configured on the physical device in the first
paragraph in this chapter
In this example the data source will be added AN_1_A, AN_1_B and AN_2_A.
By clicking on Add Data you get the following page:
www.ruggedaq.com
0108
www.ruggedaq.com
Figure 103
0109
DATALOGGER
NI2400
NI2400
You can also click on Data in the left menu and get the Data page with the list of all
data source configured in the portal grouped by device:
Figure 104
DATALOGGER
NI2400
55
By clicking on this button you can select a widget to be added in the list of all available
buttons:
NI2400
Figure 106
You can add data source also from this page following a procedure similar to the one
just described.
CREATE THE DASHBOARD AND ADD WIDGETS
You can create a new dashboard by selecting Dashboard in the left menu and clicking
on Add dashboard in the top right page. You can add more dashboards in the same
portal and in this page you will have the list of all added dashboards:
Figure 105
Figure 107
Since OM devices send data to Exosite portal using a custom protocol not all the widgets could be used.
For data source visualization only the following widgets can be used:
By clicking on the dashboard thumbnail you finally have access to the dashboard. Here
you can add widgets needed to monitor the data sources by clicking on ADD WIDGET
button:
www.ruggedaq.com
0110
For generic info visualization (map, device list, event list, event log …) every widget
can be used.
Once widget type is selected you have name it and than, by pressing on CONTINUE,
you can configure the widget with the following page:
www.ruggedaq.com
0111
DATALOGGER
NI2400
NI2400
Figure 108
DATALOGGER
NI2400
55
For all the widgets you can always review the data source, count and refresh rate settings by clicking on the little arrow in top right of the widget and by selecting Edit:
You can also move the widget in the screen dragging it by this icon:
NI2400
Figure 110
This page may change depending on the type of selected widget, but they’re all
almost similar.
Here you have to select the data source that should be showed in the graph.
You can select more than one data source at the same time. The data source available
are grouped by device.
the field COUNT: with this field it is possible to set the max number of data point that
should be displayed in the graph. This field makes sense only for widgets that show
more data points at the same time (line and column chart), no sense for graph that
shows only last value like gauge and image overlay.
Refresh rate: the refreshing period of the graph
In this example a line chart -Next Industries- has been added and it has been configured in order to show data source AN_1_A and AN_1_B, the last 50 points. This is the
result:
Figure 111
As it follows, some other examples:
column chart:gauge chart:
Figure 112
map chart:image overlay chart:
Figure 113
www.ruggedaq.com
Figure 109
0112
www.ruggedaq.com
0113
DATALOGGER
NI2400
NI2400
DATALOGGER
NI2400
65
NI2400
TROUBLESHOOTING
In case of NI2400 malfunctioning or irregular behavior, read the following pages and carry
out the indicated attempts before contacting our Assistance Department.
BASIC TROUBLESHOOTING
This paragraph provides basic NI2400 troubleshooting tips.
ARE YOU UP-TO-DATE?
Figure 114
For the image overlay chart there are a few additional configurations:
the background image
the position of data source label
the color (background and font) of source label
You can access to this configuration by clicking on the image itself
Figure 115
1. Verify that you installed the last version of rmware
2. Verify that you have an adequate power supply (from photovoltaic module or external
power supply) on the V IN clamp of the NI2400; check if the voltage is within the range
accepted by the NI2400 and stable.
IF THE NI2400 DOESN’T TURN ON.
Follow this step, testing after each:
1. remove power supply on V IN clamp for 10 seconds and try to reconnect.
2. verify the presence of jumper cables on the “PWR CONFIG” clamp
3. control that the power supply system works, is correctly sized and respects the characteristic declared on datasheet
4. make sure you hadn’t set the NI2400 in Timed mode using the webpage “Energy management”
NOTE: if on the display appears TELNET MODE, contact directly NEXT Industries Assistancetechnical support for assistance.
www.ruggedaq.com
0114
IF THE NI2400 DISPLAY STOPS RESPONDING
Follow this step, testing after each:
1. remove power supply on V IN clamp for 10 seconds and try to reconnect.
IT IS IMPOSSIBLE TO UPLOAD THE CONFIGURATION
Follow this step, testing after each:
1. on webpage STATUS verify that the NI2400 is in “Cong”
2. make sure that the conguration you are trying to upload has been created with the same
major release of the rmware on the NI2400.
www.ruggedaq.com
0115
DATALOGGER
NI2400
NI2400
DATALOGGER
NI2400
66
NI2400
NOTE: if what is written above is correct, the conguration le could be damaged. In this
case, the NI2400 warns with an error message and the le is no more usable. We suggest to repeat the conguration.
IF THE NI2400 STOPS DURING AN ACQUISITION
Follow this step, testing after each:
1. verify the events log and refer to manual “Codes Alarms-Events” to understand the
eventual logs
2. verify that the NI2400 is correctly supplied. If the power supply is below the minimum
threshold or over the maximum threshold of power supply, the NI2400 blocks every
activity in progress;
3. verify the alarm log to identify the problem and refer to manual “Codes Alarms-Events”
to understand the eventual logs
4. Verify if in alarm logs there is an “overcurrent” error. In case of overcurrent, the NI2400
stops the acquisition.
5. verify the available memory. In case of full memory, the NI2400 stops the acquisition.
IT IS IMPOSSIBLE TO HAVE ACCESS TO SYS MENU
power supply) on the V IN clamp of the NI2400
IF YOU ARE NOT ABLE TO ESTABLISH THE CONNECTION WITH THE NI2400 .
Follow this step, testing after each:
1. remove the power supply on V IN clamp for 10 seconds and try to reconnect.
2. reboot the PC and try to connect
3. make sure you congured appropriately the network card of the PC, that is it is part of
the same subnet mask of the NI2400.
4. make sure you are using the correct LAN cable according to the type of network you
chose.
5. make sure the NI2400 is not congured in “Timed”. In this case the network card remains
switched off. It is necessary to turn it on manually from SYS menu.
6. make sure the NI2400 is not used by another user. The NI2400 accepts only one connection at a time.
7. make sure that the last user that logged on the NI2400 had logged out. Otherwise, it is
necessary to wait until the automatic log out. This happens after the time congured in
page “Energy management” has passed. You could also reboot the NI2400, in order to
not wait for the log out.
8. in case of use of remote communication devices (ex: HSPA router connected to the
NI2400), remove them and do a test of direct connection between PC and the NI2400.
This is necessary in order to exclude problems with communication interfaces.
Follow this step, testing after each::
1. verify that the NI2400 is not acquiring. In this case, wait until the end of the acquisition or
go in “DL” menu and select “Stop DL”
IT IS NOT POSSIBLE TO DOWNLOAD DATA ON USB FLASH-DRIVE
Follow this step, testing after each:
1. verify that the USB ash-drive is formatted in FAT32;
2. verify with the PC that the USB ash-drive is read without any errors.
3. try with a different USB ash-drive
LOCAL/REMOTE COMMUNICATION
This paragraph provides NI2400 local communication (from PC through a LAN cable) and
remote communication (from PC through internet) troubleshooting tips.
ARE YOU UP TO DATE?
1. Verify that you installed the last version of rmware
2. Verify that you have the correct power supply (from photovoltaic module or external
IF USER CANNOT HAVE ACCESS TO THE NI2400 WITH AN USER
Follow this step, testing after each:
1. make sure that the access credentials are correct
2. if you logged out with a n user and you are trying to enter again with a different user,
delete the browser cache, close and re-open the browser (some browsers are congured
in order to memorize passwords)
3. make sure that the last user that logged on the NI2400 had logged out. Otherwise, it is
necessary to wait until the automatic log out. This happens after the time congured in
page “Energy management” has passed. You could also reboot the NI2400, in order to
not wait for the log out.
4. in case of use of remote communication devices (ex: HSPA router connected to NI2400),
remove them and do a test of direct connection between PC and NI2400. This is necessary
in order to exclude problems with communication interfaces.
THE CONNECTION TROUGH THE NI2400 AND COMPUTER GOES DOWN.
Follow this step, testing after each:
1. be sure that your PC is not set on Energy Saving mode
2. Try to change the LAN cable
3. Try using another LAN port of your PC or using another PC
www.ruggedaq.com
0116
www.ruggedaq.com
0117
DATALOGGER
NI2400
NI2400
4. verify that the NI2400 is not in Timed mode. In this case, once ended the timeout time
congured in webpage “Energy management”, the network card turns off if there isn’t
any data exchange.
E-MAIL SENDING
DATALOGGER
NI2400
66
THESE POINTS DO NOT DEPEND ON NEXT INDUSTRIES AND NEED TO BE RESOLVED
THROUGH YOUR ISP OR ESP.
If you don’t have any problem with the ISP and the ESP, you could proceed looking for
causes on the NI2400.
NI2400
ARE YOU UP TO DATE?
1. Verify that you installed the last version of rmware
2. Verify that you have the correct power supply (from photovoltaic module or external
power supply) on the V IN clamp of the NI2400
This paragraph provides NI2400 e-mail sending troubleshooting tips.
THE E-MAIL TRANSMISSION INVOLVES DIFFERENT DEVICES. IN THIS DOCUMENT, WE
TRY TO DETERMINE WHICH DEVICE COULD CAUSE THE PROBLEM AND THEN WE TRY
TO SOLVE IT.
The “system” is composed as follows:
1. NI2400
2. Internet Service Provider (ISP): allows the communication between NI2400 and the email server
3. E-mail Server (ESP): allows to send and to receive e-mails
IF THE NI2400 DOESN’T SEND ANY E-MAIL ALTHOUGH IT IS CONFIGURED.
Follow this step, testing after each:
1. verify the events log and refer to manual “Codes Alarms-Events” to understand eventual
logs
2. verify that the SIM is properly inserted in its slot into the communication device (HSPA
router or 2G modem) or that your network devices are properly congured to permit the
e-mail sending (rewall, port, etc)
3. verify that you inserted your SMTP server account correctly (“SMTP Server Conguration” page)
4. verify that the SMTP account is a simple authentication. The NI2400 doesn’t support SSL.
5. If you use a communication device base on mobile network, verify that there is a mobile
coverage (according to the adopted technology e.g: 2G, 3G or 4G) on the site where the
NI2400 is installed.
6. If you use a 2G (GSM/GPRS) modem, verify that there is a good 2G signal where the
NI2400 is installed. In some place there is only a 3G or 4G coverage. 2G modem is not
compatible with 3G, 4G and CDMA networks.
NOTE: it may be that the ISP (Telecom, Vodafone, AT&T, Verizon, etc.) doesn’t
coincide with the ESP (Gmail, AOL, etc.)
Resolution
FIRST OF ALL, INSURE WITH YOUR IPSP THAT:
1. The SIM card or your network is enabled to the internet
2. The e-mail transmission is allowed on the used APN or on the used network
SECONDLY, INSURE WITH YOUR ESP THAT:
1. there are no momentary breakdowns on ESP server
2. the username and password of your e-mail account are valid and accepted
3. that the e-mail account you want to use is active
www.ruggedaq.com
0118
www.ruggedaq.com
0119
DATALOGGER
NI2400
NI2400
DATALOGGER
NI2400
66
NI2400
FTP SERVER SENDING DATA
ARE YOU UP-TO-DATE?
1. Verify that you installed the last version of rmware
2. Verify that you have the correct power supply (from photovoltaic module or external
power supply) on the V IN clamp of the NI2400
THIS PARAGRAPH PROVIDES FTP SERVER SENDING DATA TROUBLESHOOTING TIPS.
The FTP transmission involves different devices. In this document, we try to determine which
device could cause the problem and then we try to solve it.
The “System” is composed as follows:
1. NI2400
2. Internet Service Provider (ISP): allows the communication between the NI2400 and FTP
server
3. server FTP: physical space in which it is possible to memorize les
Follow this step, testing after each:
1. verify the events log and refer to manual “Codes Alarms-Events” to understand the possible logs
2. if you use a HSPA router or 2G modem verify that the SIM card is properly inserted in its slot.
3. verify that you have inserted your FTP server account correctly (“Measure log data transfer” page)
4. verify that the FTP server is a basic authentication FTP (for example not MD5, KERBEROS
etc.) and that doesn’t utilize any secure layer (for example SSH/SSL, FTPS/SFTP etc.).
The NI2400 does not support secure layer and encrypted authentication (encrypted username and password).
5. if you use a mobile device, verify that there is a good coverage on the site were the
NI2400 is installed.
6. if you use 2G (GSM/GPRS) modem, verify that there is a good 2G (GSM/GPRS) signal on
the site were the NI2400 is installed. In some place there is only a 3G or 4G coverage. 2G
modem is not compatible with 3G, 4G and CDMA networks .
MEASURE
NOTE: the FTP server could be completely transferred to societies that oer an
hosting FTP service. It could also be internal. In this second case, you have to
ask for information to your IT manager.
FIRST OF ALL, INSURE WITH YOUR ISP THAT:
1. The SIM card or your network is enabled to the internet trafc through APN
2. The data transmission on FTP server is allowed on the used APN or on the used network
INSURE WITH YOUR SYSTEM ADMINISTRATOR OR WITH THE SOCIETY THAT SUPPLIES
THE HOSTING FTP SERVICE THAT:
1. there are no momentary breakdowns on FTP server
2. the username and password of FTP account are valid and accepted
3. the FTP account and the same FTP server that will be used are active
THESE POINTS DO NOT DEPEND ON NEXT INDUSTRIES AND NEED TO BE RESOLVED
THROUGH YOUR ISP OR ESP
If you don’t have any problem with the ISP and the FTP server, you could proceed looking
for causes on the NI2400.
IF THE NI2400 DOESN’T SEND ANY DATA ON FTP SERVER ALSO IF CONFIGURED.
ARE YOU UP-TO-DATE?
1. Verify that you installed the last version of rmware
2. Verify that you have the correct power supply (from photovoltaic module or external
power supply) on the V IN clamp of the NI2400
This paragraph provides measure instruments troubleshooting tips.
ONE OR MORE VIBRATING WIRE INSTRUMENTS ARE NOT READ.
Follow this step, testing after each:
1. verify the events log and refer to the manual “Codes Alarms-Events” to understand the
eventual logs;
2. verify the instrument with a portable NI2400;
3. verify the connection of instruments on the NI2400 inputs;
4. change the parameters “Excitation time” (accepted values from 5 to 100) and “Delay
Time” (accepted values from 20 to 100) focusing on this last one;
5. try to contract the parameters “Start Frequency” and “End Frequency” according to the
value read with the portable NI2400,
6. consult the reference manual of the instrument
www.ruggedaq.com
0120
www.ruggedaq.com
0121
DATALOGGER
NI2400
NI2400
DATALOGGER
NI2400
77
NI2400
ONE OR MORE ANALOG INSTRUMENTS ARE NOT READ.
Follow this step, testing after each:
1. verify the events log and refer to the manual “Codes Alarms-Events” to understand the
eventual logs;
2. verify the instrument with a portable NI2400;
3. verify the connection of instruments on the NI2400 screw clamps;
4. verify that the congured parameters are coherent and correct according to the type of
connected instrument (power supply, warm-up time etc)
5. consult the reference manual of the instrument
APPENDIX
APPENDIX A: WIRING SCHEMES
This appendix will show how to connect different sensor types to NI2400 datalogger.
Connection schemes are sorted by number of wires (2,4,6 wires).
4..20mA Transmitter (External Supply)
2 WIRES SENSORS
Current Loop 2 Wires
Figure 117
Servo Uni Axial (External Supply)
Figure 116
www.ruggedaq.com
0122
www.ruggedaq.com
Figure 118
0123
DATALOGGER
NI2400
NI2400
DATALOGGER
NI2400
77
NI2400
Thermistor
Vibrating Wire
Figure 119
Thermocouple
Figure 121
Voltage (External Supply)
www.ruggedaq.com
Figure 120
0124
www.ruggedaq.com
Figure 122
0125
DATALOGGER
NI2400
NI2400
DATALOGGER
NI2400
77
NI2400
4 WIRES SENSORS
4..20 Transmitter
Current Loop 2 Channels (Internal and External Supply)
Figure 125
Potenziometer 4 Wires
4..20 Transmitter 2 channel (External Supply)
Figure 123
Figure 126
www.ruggedaq.com
Figure 124
0126
www.ruggedaq.com
0127
DATALOGGER
NI2400
NI2400
DATALOGGER
NI2400
77
NI2400
Potenziometer (2 Channel)
Ratiometric (External Supply)
Figure 127
Figure 129
PT100/PT200/PT500/PT1000
Servo BiAxial (External Supply)
Figure 128
www.ruggedaq.com
0128
www.ruggedaq.com
Figure 130
0129
DATALOGGER
NI2400
NI2400
DATALOGGER
NI2400
77
NI2400
Vibrating Wire with Thermistor (NTC)
Voltage 2 channels (External supply)
Voltage
Figure 131
Figure 133
6 WIRES SENSORS
2..40mA Transmitter 2 channels
www.ruggedaq.com
Figure 132
0130
www.ruggedaq.com
Figure 134
0131
DATALOGGER
NI2400
NI2400
DATALOGGER
NI2400
77
NI2400
Ratiometric
Servo UniAxial (5 Wires)
Servo Biaxial
Figure 135
Figure 137
Voltage 2 channel
Figure 136
www.ruggedaq.com
Figure 136
0132
www.ruggedaq.com
Figure 138
0133
DATALOGGER
NI2400
8
ASSISTANCE
NI2400
9
GENERAL
NI2400
SPECIFICATIONS
In the event that you need after-sale calibration, service or repair of your NI2400, please contact Next Industries’s Customer Service Department for an Authorized Return (AR) No. Next
Industries Customer Service email: service@ruggedaq.com
• View Data in real Time or Store to 2 GB Internal Memory
• GPRS Modem available
• 0.01% FS Accuracy
• Expandable up to 384 channels with multiplexers
• Ethernet, RS485, RS232 and USB Connections
• SMS and e-mail Alerts
www.ruggedaq.com
0134
PHYSICAL CHARACTERISTICS
Weight980 g (2.16 lb)
Dimensions (L x W
x H)
MaterialPlastic and metal
WiringRemovable screw terminal connectors
231 L x 138 W x 117 mm H (9.09 x 5.43 x 4.61”)
www.ruggedaq.com
0135
9
DETAILED
NI2400
SPECIFICATIONS
9
DETAILED
NI2400
SPECIFICATIONS
CPU AND MEMORY
Processor
RAM Memory1 Mbyte RAM
Mass storage
Clock accuracy
On-board sensors
ANALOG INPUTS
ARM Cortex-M3 MCU with 1 MB Flash, 120 MHz CPU, ART Accelerator,
Ethernet
2 GB SD card for data (about 5 Mega data points) and Web pages
High precision RTC (real time clock with battery back-up) temperature
compensated
Temperature (accuracy ±1%), measured inside the datalogger
Number of Inputs: 24 differential analog inputs, individually configured.
Channel expansion provided by multiplexers. There are 8 terminal blocks
(each terminal block can handle up to 3 sensors). NI2400 is designed to
work with 2 to 6-wire sensors. You can connect 2-wire sensors on each
channel and read 24 sensors, or 4-wire sensor and read 12 channels. The
system will order sensors depending on how many wires they use, placing
6 wires sensors first, 4 wires in the middle, and 2 wires last. Once software
configuration is done, a click on “Wiring scheme” button on the web
interface near the sensors will show how to physically connect the chosen
sensor to the block. It shows “relative” position, so if you start connecting
sensors from the first you will not have to leave “unused” positions (except
for the ground connection of every block, if not used).
Analog Measurements
Measurement Rate
Analog Initialization (±10V range)1.70 sec7.10 sec
Instrument Warm-UpDepends on sensor configuration
Measurement (±10V range)80 ms1.57 sec
Accuracy:0.13 %FS
ADC:
ANALOG INPUT TYPES
Current Loop
(2 Wires)
Transmitter
(3-4 Wires)
Voltage (4 Wires)
0 to 25 mA range; power supply: 24/10 Vdc, external
0 to 25 mA range; power supply: 24/10 Vdc, external
Times indicated are not valid for vibrating wire measures
Init analog phase is made only once before measurement cycle
24-bit (22 true bit) differential analog-to-digital converters, 5SPS to 1000SPS, 0-24 average function, autocalibration and auto-range
Multiplexers are needed if the total “wires” from sensors exceeds the 48
provided by NI2400.
www.ruggedaq.com
0136
Servo Inclinometer
Wheatstone Bridge (6
Wires, With Sensing)
Minimum bridge
resistance
Potentiometer ±2.5V range; power supply: 10/5 Vdc
±5V range; power supply: ± 12 Vdc (dual), external
±10mV/V range; power supply: 10/5 Vdc, external (max 10 Vdc)
200 Ω; power supply: 10/5 Vdc, external (max 10 Vdc)
Thermocouple Input Types and Ranges
www.ruggedaq.com
0137
9
DETAILED
NI2400
SPECIFICATIONS
9
DETAILED
NI2400
SPECIFICATIONS
THERMOCOUPLES
TYPE
J-200°C to 1200°C (-328 to 2192°F)± 0.62°C
K-200°C to 1372°C (-328 to 2502°F)± 0.87°C
T-200°C to 400°C (-328 to 752°F)± 0.42°C
E-200°C to 1000°C (-328 to 1832°F)± 0.78°C
R-50°C to 1768°C (-58 to 3214°F)± 2.10°C
S-50°C to 1768°C (-58 to 3214°F)± 2.81°C
B 250°C to 1820°C (482 to 3308°F)± 2.44°C
N-200°C to 1300°C (-328 to 2372°F)± 0.87°C
Cold Junction
Compensation
Accuracy:
TEMPERATURE RANGEACCURACY
± 0.25°C with stable temperature conditions (tested in climatic chamber)
ANALOG MEASUREMENTS
RTD Input
Thermistor (3000
Ω@25°C NTC)
USB DeviceUSB 2.0 full speed 5V, max 500mA, USB pendrive only
Reading
Resolution
100Ω Platinum (Pt100) RTD: range -50 to 150°C (-58 to 302°F); power supply:
1.2 mA
range -50 to 150°C (-58 to 302°F); power supply: 0.05 mA /0.1 mA/1.2
mA
1 µA at FS for 20 mA range;
1 µV at FS for ±10 mV range;
10 µV at FS for ±100 mV range;
100 µV at FS for ±1 V range;
1 mV at FS for ±10 V range;
0.1 °C for Pt100 RTD;
0.1 °C for NTC thermistor;
0.1 Hz for 6000 Hz range;
0.001 mV/V at FS for ±10 mV/V (Wheatstone bridge)
0.01% mV/mA FS (0.1% FS for Pt100 and NTC) - with Standard Measurement
Measurement
Accuracy
Switched Output
Power Supply
0.13% mV/mA FS - with Max Speed Measurement
Temperature Drift: < 10 ppm/°C, range -30 to 70°C
Input Noise Voltage: 5.42 µV pp
Input Limits : ±12V
DC Common Mode Rejection: >105 dB
Normal Mode Rejection: >90 dB
Input Impedance: 20 MΩ typical
The voltage ‘V OUT’ is switched on and off under program control. V
OUT is the unregulated input power supply ‘V IN’ (2 A)
www.ruggedaq.com
0138
www.ruggedaq.com
0139
9
DETAILED
NI2400
SPECIFICATIONS
9
DETAILED
NI2400
SPECIFICATIONS
DIGITAL I/O
Digital Output One relay output (for alarm, etc.): volt-free closure (low voltage 30V, 2A)
Two opto-isolated digital inputs
Max Input Voltage: 24V (max current: 10mA)
Digital Input:
PROTECTIONS
Min Input Voltage: 5V (max current: 2mA)
Measurement Rate (MR): max frequency 1 kHz
Accuracy: 0.1 Hz
Electro-Mechanical Relays for Measuring Each Channel:
Electrical Endurance: min 2 x 105 operations
Mechanical Endurance: 100 x 106 operations.
Circuit Protection (Gas Discharge Tubes):
DC Breakdown Voltage (@100V/s): 75V
Tolerance of DCBV: ± 20%
Impulse Breakdown Voltage (@100v/µs ): 250V
Impulse Breakdown Voltage (@1kv/µs ): 525V
Overvoltage and Reverse Polarity Protection
Short Circuit Protection on Every Output
INTERFACES
Small backlight graphic LCD 128 x 64 dpi with membrane keyboard for the
minimal local management without the PC. Keyboard for starting a data
Display & Keyboard
LAN Ethernet Iso
lated
RS232
USBUSB 2.0 pen drive only (FAT 32), 5 V 200 mA
RS485#1
Opto-Isolated
acquisition scan, sequential display of the last stored readings for each chan
nel (sensor ID, converted unit reading, unit of measure), device status, data
download and firmware/Web pages update by USB pen drive, safe mode
(back-up/format/restore internal SD card).
-
10/100 Mbps, RJ45
9-pin, DE9: DCE port for optional GSM/GPRS modem connection
Baud Rates: selectable from 9600 bps to 115.2 kbps
Default Format: 8 data bits; 1 stop bits; no parity
Connection: 5 screw clamp port for max. No.254 Modbus RS485 digital
bus sensors
Communication Interface: RS485
Communication Protocol: MODBUS RTU
Voltage ‘V OUT’: Switched on and off under program control. V OUT is
the unregulated input power supply ‘V IN’ (1 A).
Power supply management: Always on or energy safe
-
RS485#2
Opto-Isolated
Connection: 5 screw clamp port for max. 16 multiplexer boards
connection.
Communication interface: RS485
Communication protocol: MODBUS RTU
Voltage ‘V OUT’: Switched on and off under program control. V OUT is
the unregulated input power supply ‘V IN’ (1 A).
Every channel of each multiplexer board is completely independent.
www.ruggedaq.com
0140
www.ruggedaq.com
0141
9
DETAILED
NI2400
SPECIFICATIONS
9
DETAILED
NI2400
SPECIFICATIONS
SOFTWARE & FIRMWARE
• Web server on board (independent OS platform)
• Acquisition Time Interval: selectable from 1 second up to 1 week (depends
on the number of channels acquired)
• FTP client to send data/alarms on an FTP server (SFTP not supported)
• MAIL to send data/alarms to max 5 email address (SMTPS / SSL not sup
ported)
• SMS to send alarms to max 5 telephone numbers
• Data download (readings, logs) in .csv file (compatible with Microsoft Excel)
• Virtual channels management
• Languages: Italian, English and French
SYSTEM POWER REQUIREMENTS
Voltage (External
Power Supply)
External Recharge
able Batteries
Typical Current
Drain (@12 Vdc,
External Power
Supply)
10 to 30 Vdc (reverse polarity protected)
-
12 Vdc nominal
Sleep Mode(MAX): 315 µA
ON: 62 mA - ON with ethernet connected: 87 mA - ON with display ON:
115 mA
ON with display ON and ethernet connected: 142 mA
ENVIROMENTAL CONDITIONS
Operating
Temperature
Storage
-
Temperature
Relative Humidity80 %RH
Overvoltage
Category
Pollution Degree2
Sound Levels< 74 dBA
Maximum Height
of Use
-30 to 70°C (display -20 to 70°C)
-40 to 85°C (display -30 to 80°C)
II
3000 m (9800 ft)
Analog
Initialization
Measurement123 mA (with 12 mA @ 24 V sensor consumption)
115 mA
www.ruggedaq.com
0142
www.ruggedaq.com
0143
NI2400
DATALOGGER
DATALOGGERS
INTERNET OF THINGS
SENSORS
Next Industries S.r.L
Via G. Di Vittorio 2/F,
20065 Inzago (MI) - Italy
WEB SOFTWARE
T+39 02.95764356
info@ruggedaq.com
www.ruggedaq.com
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.