New Yorker Boiler FR Installation Manual

INSTALLATION, OPERATING
Be
AND SERVICE INSTRUCTIONS
FR™ SERIES
HORIZONTAL TUBE BOILER
As an ENERGY STAR® Partner, New Yorker Boiler Co., Inc. has determined that the FR-HGS, FR-HGSII, FR-98, FR-122, FR-147, FR-173, FR-205 and FR-232 water boilers meet the ENERGY STAR guidelines for Energy
efciency established by the
United States Environmental Protection Agency (EPA).
®
nonoitamrofnignikeesnehW.rotcartnocgnitaehruoyllac,reliobotsriaperroecivresroF
.lebaLgnitaRnonwohssarebmuNlaireSdnarebmuNledoMrelioBedivorp,reliob
rebmuNledoMrelio
ebmuNlaireSrelio
taDnoitallatsnI
RF
rotcartnoCgnitaeH rebmuNenohP
sserddA
104183-02 - 7/12
Price - $5.00
IMPORTANT INFORMATION - READ CAREFULLY
All boilers must be installed in accordance with National, State and Local Plumbing, Heating and Electrical Codes and the regulations of the serving utilities. These Codes and Regulations may differ from this instruction manual. Authorities having jurisdiction should be consulted before installations are made. In all cases, reference should be made to the following Standards:
USA BOILERS A. Current Edition of American National Standard ANSI/NFPA 31, “Installation of Oil Burning Equipment”, for recommended installation practices. B. Current Edition of American National Standard ANSI/NFPA 211, “Chimneys, Fireplaces, Vents, and Solid Fuel Burning Appliances”, For Venting requirements. C. Current Edition of American Society of Mechanical Engineers ASME CSD-1, “Controls and Safety Devices for Automatically Fired Boilers”, for assembly and operations of controls and safety devices. D. All wiring on boilers installed in the USA shall be made in accordance with the National Electrical Code and/or Local Regulations.
The following terms are used throughout this manual to bring attention to the presence of
hazards of various risk levels, or to important information concerning product life.
DANGER
Indicates an imminently hazardous situation which, if not avoided, will result in death, serious injury or substantial property damage.
WARNING
Indicates a potentially hazardous situation which, if not avoided, could result in death, serious injury or substantial property damage.
Indicates a potentially hazardous situation which, if not avoided, may result in moderate or minor injury or property damage.
Indicates special instructions on installation, operation, or maintenance which are important but not related to personal injury hazards.
CAUTION
NOTICE
NOTICE
This boiler has a limited warranty, a copy of which is printed on the back of this manual. The warranty for this boiler is valid only if the boiler has been installed, maintained and operated in
accordance with these instructions.
2
DANGER
DO NOT store or use gasoline or other ammable vapors or liquids in the vicinity of this boiler or any other appliance.
WARNING
Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury or loss of life. Failure to follow all instructions in the proper order can cause personal injury or death. Read and understand all instructions, including all those contained in component manufacturers manuals which are provided with the boiler before installing, starting-up, operating, maintaining or servicing this boiler. Keep this manual and literature in legible condition and posted near boiler for reference by owner and service technician.
This boiler requires regular maintenance and service to operate safely. Follow the instructions con­tained in this manual.
Installation, maintenance, and service must be performed only by an experienced, skilled and knowledgeable installer or service agency.
All heating systems should be designed by competent contractors and only persons knowledgeable in the layout and installation of hydronic heating systems should attempt installation of any boiler.
Installation is NOT complete unless a pressure relief valve is installed into the tapping located on top of Shell Assembly near rear of boiler - See Piping and Trim Sections of this manual for details.
It is the responsibility of the installing contractor to see that all controls are correctly installed and are operating properly when installation is complete including verifying that the limit sensor is fully installed (seated in bottom of Well).
Failure to properly install Limit Sensor may result in property damage, personal injury or loss of life due to elevated operating temperatures and/or pressures.
This boiler is NOT suitable for installation on combustible ooring, unless installed with a combustible oor shield constructed in accordance with NFPA 31. A concrete pad is not sufcient to protect combustible ooring. Concrete over wood joists is considered combustible ooring.
DO NOT install boiler on carpeting.
When boiler is installed on concrete which is over a material that is subject to melting (PVC, PEX radiant tubing, etc.) a combustible oor shield must be used.
DO NOT operate on masonry oors, which may contain moisture.
DO NOT tamper with or alter the boiler or controls.
Retain your contractor or a competent serviceman to assure that the unit is properly adjusted and maintained.
Have Firetubes cleaned at least once a year - preferably at the start of the heating season to remove soot and scale. The inside of combustion chamber should also be cleaned and inspected at the same time.
When cleaning this boiler, DO NOT damage combustion chamber. If damaged, combustion chamber must be replaced immediately.
Oil Burner and Controls must be checked at least once a year or as may be necessitated.
DO NOT operate boiler with jumpered or absent controls or safety devices.
DO NOT operate boiler if any control, switch, component, or device has been subject to water.
Boiler materials of construction, products of combustion and the fuel contain alumina, silica, heavy metals, carbon monoxide, nitrogen oxides, aldehydes and/or other toxic or harmful substances which can cause death or serious injury and which are known to the state of California to cause cancer, birth defects and other reproductive harm. Always use proper safety clothing, respirators and equipment when servicing or working nearby the boiler.
3
WARNING
This boiler contains very hot water under 12 - 15 PSI pressure. DO NOT unscrew any pipe ttings nor attempt to disconnect any components of this boiler without positively assuring the water is cool and has
no pressure. Always wear protective clothing and equipment when installing, starting up or servicing this
boiler to prevent scald injuries. DO NOT rely on the pressure and temperature gauges to determine the temperature and pressure of the boiler. This boiler contains components which become very hot when the boiler is operating. DO NOT touch any components unless they are cool.
High water temperatures increase the risk of scalding injury. If this boiler is equipped with a tankless heater for domestic water supply, a ow regulator and automatic mixing valve must be installed properly
in tankless heater piping. See Piping and Trim Sections of this manual for details.
This boiler needs fresh air for safe operation and must be installed so there are provisions for adequate
combustion and ventilation air.
This boiler must be connected to an approved chimney or vent system in good condition. Serious
property damage could result if the boiler is connected to a dirty or inadequate chimney or vent system. The interior of the chimney ue must be inspected and cleaned before the start of the heating season for any obstructions. A clean and unobstructed chimney ue is necessary to allow noxious fumes that could cause injury or loss of life to vent safely and will contribute toward maintaining the boiler's efciency.
DO NOT operate boiler with the absence of an approved vent system.
This boiler is supplied with controls which may cause the boiler to shut down and not re-start without service. If damage due to frozen pipes is a possibility, the heating system should not be left unattended in cold weather; or appropriate safeguards and alarms should be installed on the heating system to prevent damage if the boiler is inoperative.
This boiler is designed to burn No. 2 fuel oil only. DO NOT use gasoline, crankcase drainings, or any oil containing gasoline. Never burn garbage or paper in this boiler. DO NOT convert to any solid fuel (i.e. wood, coal). DO NOT convert to any gaseous fuel (i.e. natural gas, LP). All ammable debris, rags, paper, wood scraps, etc., should be kept clear of the boiler at all times. Keep the boiler area clean and
free of re hazards.
All boilers equipped with burner swing door have a potential hazard which if ignored can cause severe
property damage, personal injury or loss of life. Before opening swing door, turn off service switch to
boiler to prevent accidental ring of burner outside the combustion chamber. Be sure to tighten swing
door fastener completely when service is completed.
TABLE OF CONTENTS
I. General Information ..............................5
II. Pre-Installation ......................................8
III. Knockdown Boiler Assembly .............10
IV. Water Piping and Trim ........................12
V. Venting .................................................17
VI. Electrical ..............................................19
VII. Oil Piping .............................................23
VIII. System Start-Up ..................................25
4
IX. Operating .............................................31
X. Maintenance & Service Instructions .36
XI. Boiler Cleaning .................................... 37
XII. Troubleshooting ..................................40
XIII. Repair Parts ......................................... 43
XIV. Burner Specications ......................... 51
Appendix A - Low Water Cut-Off ........52
I: GENERAL INFORMATION
Figure 1A: FR-HGS and FR-HGSII Water Boiler (Heat Only), Beckett Burner
Figure 1B: FR-98-W Thru FR-232-W Water Boiler With or Without Tankless Heater, Beckett Burner
5
I: GENERAL INFORMATION (continued)
Figure 1C: FR-265-W Thru FR-462-W Water Boiler With or Without Tankless Heater, Beckett Burner
TABLE 1: DIMENSIONAL DATA (SEE FIGURES 1A THRU 1C)
Dimensions - Inches
Boiler Model
A B C D E F G
FR-HGS 31-7/8 19-7/8 18-3/8 25-3/4 31-3/8 3-1/8 5-7/8 9.5
FR-HGSII 31-7.8 19-7/8 18-3/8 26-1/2 31-3/8 3-1/8 6-7/8 9.0
FR-98/122 37-7/8 19-7/8 18-3/8 25-1/4 30-1/2 3-7/8 5-7/8 20.0
FR-147/173 46-5/8 21-7/8 21-5/8 30-1/4 35-3/4 5-3/8 6-7/8 40.0
FR-205/232 51-1/8 21-7/8 25-7/8 29-3/4 40-3/4 6-1/8 7-7/8 46.0
FR-265/305 51-1/8 21-7/8 25-7/8 34 38-3/4 6-1/8 7-7/8 52.0
FR-350/400 58 25-7/8 27-7/8 35-3/4 40-7/8 6-1/8 9-7/8 70.0
FR-462 58 25-7/8 33-7/8 35-3/4 46-3/4 6-1/8 9-7/8 80.0
NOTE: 1. FR Series is available as a Packaged Water Boiler Only.
2. Maximum Working Pressure: Water 30 PSI Shipped Standard
Content - Gallons
Approx. Water
6
I: GENERAL INFORMATION (continued)
TABLE 2: RATING DATA
Burner
Boiler Model
No.
* FR-HGS
* FR-HGSII 1.30 182 106 --- 158 7 8 x 8 15 85.0
* FR-98-W 0.85 119 104 --- 90 6 8 x 8 15 86.4
* FR-122-W 1.10 154 132 --- 11 5 6 8 x 8 15 85.1
FR-147-W 1.25 175 154 --- 134 7 8 x 8 15 86.7
FR-173-W 1.50 210 184 --- 160 7 8 x 8 15 85.9
FR-205-W 1.75 245 215 --- 187 8 8 x 8 15 86.0
FR-232-W 2.00 280 242 --- 210 8 8 x 8 15 85.1
FR-265-W 2.40 336 N/A 265 230 10 8 x 12 15 (82.2)
FR-305-W 2.75 385 N/A 305 265 10 8 x 12 18 (83.4)
FR-350-W 3.00 420 N/A 350 304 10 8 x 12 20 (83.1)
FR-400-W 3.50 490 N/A 400 348 10 8 x 12 20 (82.0)
FR-462-W 4.00 560 N/A 465 402 10 12 x 12 20 (82.7)
* Boiler Model Sufx: P = Packaged (Otherwise Shipped Knockdown)
Capacity
GPH MBH
0.80 112 100 --- 87 6 8 x 8 15 87.8
1.00 140 122 --- 106 6 8 x 8 15 86.3
DOE
Heating
Capacity -
MBH
AHRI
Gross
Output -
MBH
AHRI NET
Ratings -
MBH
Minimum Chimney
Requirements
Round In.
Dia.
Rectangle
In. x In.
Height
Ft.
AFUE %
(Thermal Effy)
7
II: PRE-INSTALLATION
A. INSPECT SHIPMENT carefully for any signs of
damage.
1. All equipment is carefully manufactured, inspected and packed. Our responsibility ceases upon delivery of crated boiler to the carrier in good condition.
2. Any claims for damage or shortage in shipment
must be led immediately against the carrier by the
consignee. No claims for variances from, or shortage in orders, will be allowed by the manufacturer unless presented within sixty (60) days after receipt of goods.
B. LOCATE BOILER near nal position before removing
crate. See Figures 1A thru 1C. Using hand truck or pipe rollers under skid, move boiler into position along side installation site.
CAUTION
DO NOT drop boiler. DO NOT bump boiler jacket
against oor.
1. LOCATE so that vent pipe connection to chimney will be short and direct.
2. BOILER IS NOT SUITABLE FOR INSTALLATION ON COMBUSTIBLE FLOOR unless installed with a Combustible Floor Shield constructed in accordance with NFPA31.. Boiler cannot be installed on carpeting.
3. FOR BASEMENT INSTALLATION, provide
a solid elevated base, such as concrete, if oor is not level, or if water may be encountered on oor
around boiler.
WARNING
Do not support boiler by placing blocks at the four (4) corners of the boiler. Boiler base must be evenly supported under entire base.
Concrete over wood joists is considered combustible flooring. Do not operate on
masonry oors, which may contain moisture.
4. PROVIDE SERVICE CLEARANCE of at least 48” clearance from front jacket panel for servicing and removal of front tankless heater.
5. For minimum clearances to combustible materials. See Figure 2.
NOTICE
Clearance to venting is for single wall vent pipe. If Type L vent is used, clearance may be
reduced to the minimum required by the vent pipe
manufacturer.
Figure 2: Minimum Installation Clearances to Combustible Materials (Inches)
C
A
Above
6 24 18 6 6
NOTE 1: Listed clearances comply with American National
Standard NFPA 31, Standard for the Installation of Oil Burning Equipment.
B
Front
Chimney
Connector
D
Rear
E
Sides
8
NOTE 2: FR™ Series boilers can be installed in rooms
with clearances from combustible material as listed above.
Listed clearances cannot be reduced for alcove or closet installations.
NOTE 3: For reduced clearances to combustible material, protection must be provided as described in the ANSI/NFPA 31 standard.
II: PRE-INSTALLATION (continued)
C. PROVIDE COMBUSTION AND VENTILATION
AIR. Local and National Codes may apply and should be referenced.
WARNING
Adequate combustion and ventilation air must
be provided to assure proper combustion and to maintain safe ambient air temperatures.
DO NOT install boiler where gasoline or other
ammable vapors or liquids, or sources of
hydrocarbons (i.e. bleaches, fabric softeners, etc.) are used or stored.
1. Determine volume of space (boiler room). Rooms communicating directly with the space in which the appliances are installed, through openings not furnished with doors, are considered a part of the space.
3
Volume(ft
2. Determine total input of all appliances in the space.
Add inputs of all appliances in the space and round
the result to the nearest 1000 BTU per hour.
3. Determine type of space. Divide Volume by total input of all appliances in space. If the result is greater than or equal to 50 ft3/1000 BTU per hour, then it is considered an unconned space. If the result is less than 50 ft3/1000 BTU per hour then the space is considered a conned space.
4. For boiler located in an unconned space of a conventionally constructed building, the fresh
air inltration through cracks around windows
and doors normally provides adequate air for combustion and ventilation.
5. For boiler located in a conned space or an unconned space in a building of unusually tight
construction, provide outdoor air.
Outdoor air may be provided with the use of two
permanent openings which communicate directly or by duct with the outdoors or spaces (crawl or attic) freely communicating with the outdoors. Locate one opening within 12 inches of top of space.
) = Length(ft) x Width(ft) x Height(ft)
Locate remaining opening within 12 inches of
bottom of space. Minimum dimension of air opening is 3 inches. Size each opening per following:
a. Direct communication with outdoors.
Minimum free area of 1 square inch per 4,000 BTU per hour input of all equipment in space.
b. Vertical ducts. Minimum free area of 1 square
inch per 4,000 BTU per hour input of all equipment in space. Duct cross-sectional area shall be same as opening free area.
c. Horizontal ducts. Minimum free area of 1
square inch per 2,000 BTU per hour input of all equipment in space. Duct cross-sectional area shall be same as opening free area.
Alternate method for boiler located within
conned space. Use indoor air if two permanent
openings communicate directly with additional
space(s) of sufcient volume such that combined volume of all spaces meet criteria for unconned
space. Size each opening for minimum free area of 1 square inch per 1,000 BTU per hour input of all equipment in spaces, but not less than 100 square inches.
6. Louvers and Grilles of Ventilation Ducts
a. All outside openings should be screened and
louvered. Screens used should not be smaller than 1/4 inch mesh. Louvers will prevent the entrance of rain and snow.
b. Free area requirements need to consider the
blocking effect of louvers, grilles, or screens protecting the openings. If the free area of the louver or grille is not known, assume wood louvers have 20-25 percent free area and metal louvers and grilles have 60-75 percent free area.
c. Louvers and grilles must be xed in the open
position, or interlocked with the equipment to open automatically during equipment operation.
9
III: KNOCK-DOWN BOILER ASSEMBLY
A. REMOVAL OF BOILER from skid.
1. Remove all boiler-to-skid hold down fasteners.
2. FR-HGS thru FR-232: Carefully walk boiler to the edge of skid. Tilt the boiler back, allowing an edge
to rest on the oor, and remove the skid.
FR-265 thru FR-462: A mechanical lifting device
may be required to safely remove boiler from skid.
B. TEST HEAT EXCHANGER FOR LEAKS before
proceeding with jacket assembly.
1. Install pressure relief valve supplied, a hose to the city water to a valve in the supply tapping. Plug remainder of tappings.
2. Fill boiler with water and apply a pressure of at least 10 psig but no more than 25 psig, to prevent weeping from seat of relief valve.
WARNING
Do not apply more than 30 psig to boiler.
CAUTION
If front ue box or rear smoke box fasteners are
removed, tighten them to 26 ft/lbs when replacing them.
C. INSTALLING THE JACKET
1. Attach lower rear jacket panel to left side and right side jacket panels with the screws provided so that the assembled components make a “U” shape and can stand alone (see Figure 22).
2. Approaching the boiler from the rear, place the assembled jacket pieces from Step 1 around the boiler so that the lower rear panel passes below the rear smokebox.
3. Attach the lower front panel, upper front panel, and upper rear panel. Make sure the jacket clearance holes line up properly with the appropriate boiler extensions and tappings.
4. Attach the top panel assembly (left and right pieces).
D. INSTALLATION OF BOILER CONTROLS
1. Install provided pressure/temperature gauge into ¼” NPT coupling located on front or top of the boiler. Tighten so not to have any water leaks. See Figures 1A thru 1C.
2. Mount the limit control. Thread the provided immersion well into the 3/4” NPT tapping located on the front or top of boiler, see Figures 1A thru 1C. Place the Aquastat Control on immersion well and tighten clamp screws to secure control to immersion well. Apply heat transfer paste (not furnished) to limit sensor and fully insert limit sensor into immersion well such that the tip on the limit sensor touches the bottom of the immersion well. See Figure 3.
10
3. Mount burner to front re door and wire according
to instructions provided with the burner. Refer to Figure 4.
Figure 3: Limit Sensor Insertion
III: KNOCK-DOWN BOILER ASSEMBLY (continued)
Figure 4: Burner Mounting
11
IV: WATER PIPING AND TRIM
WARNING
Failure to properly pipe boiler may result in improper operation and damage to boiler or structure.
Oxygen contamination of boiler water will cause corrosion of iron and steel boiler components, and can lead to boiler failure. New Yorker’s Standard Warranty does not cover problems caused by oxygen
contamination of boiler water or scale (lime) build-up caused by frequent addition of water.
A. DESIGN A PIPING SYSTEM and install boiler which
will prevent oxygen contamination of boiler water and frequent water additions.
1. There are many possible causes of oxygen contamination such as:
a. Addition of excessive make-up water as a result
of system leaks.
b. Absorption through open tanks and ttings.
c. Oxygen permeable materials in the distribution
system.
2. In order to insure long product life, oxygen sources should be eliminated. This can be accomplished by taking the following measures:
a. Repairing system leaks to eliminate the need for
addition of make-up water.
b. Eliminating open tanks from the system.
c. Eliminating and/or repairing ttings which allow
oxygen absorption.
d. Use of non-permeable materials in the
distribution system.
e. Isolating the boiler from the system water by
installing a heat exchanger.
3. Connect System supply and return piping to boiler. See Figures 6A and 6B. Also, consult Residential Hydronic Heating Installation and Design I=B=R Guide. Maintain minimum ½ inch clearance from hot water piping to combustible materials.
NOTICE
System supply and return piping must be connected to correct boiler pipe.
New Yorker
circulator to supply sufcient ow (GPM) to
allow a 20°F temperature differential in the system. When sizing the system circulator, the pressure drop of all radiators, baseboard and radiant tubing and all connecting piping must be considered.
a. If this boiler is used in connection with
12
®
recommends sizing the system
refrigeration systems, the boiler must be installed so that the chilled medium is piped in parallel with the heating boiler using appropriate valves
to prevent the chilled medium from entering the boiler. See Figure 5. Also, consult Residential Hydronic Heating Installation and Design I=B=R Guide.
Figure 5: Recommended Piping for Combination
Heating and Cooling (Refrigeration) System
b. If this boiler is connected to heating coils located
in air handling units where they may be exposed to refrigerated air, the boiler piping must be
equipped with ow control valves to prevent
gravity circulation of boiler water during the operation of the cooling system.
c. If boiler is used with an Indirect-Fired Domestic
Hot Water Heater, install the Indirect-Fired Domestic Hot Water Heater as a separate heating zone. Refer to the Indirect-Fired Domestic Hot Water Heater Installation, Operating, and Service Instructions for additional information.
d. Use a system bypass if the boiler is to be
operated in a system which has a large volume or excessive radiation where low boiler water temperatures may be encountered (i.e. converted gravity circulation system, etc.) The bypass should be the same size as the supply and return lines with valves located in the bypass and return line as illustrated in Figures 6A and 6B in order
to regulate water ow for maintenance of higher
boiler water temperature. Set the bypass and return valves to a half throttle position to start.
IV: WATER PIPING AND TRIM (continued)
Operate boiler until the system water temperature reaches its normal operating range. Adjust the valves to maintain 180°F to 200°F boiler water temperature and greater the 120°F return temperature. Adjust both valves simultaneously. Closing the boiler return valve while opening the bypass valve will raise the boiler return temperature. Opening the boiler return valve while closing the by-pass valve will lower the boiler return temperature.
e. A water boiler installed above radiation level
must be provided with a low water cutoff device as part of the installation.
B. INSTALL SAFETY RELIEF VALVE. See Figures
6A and 6B. Safety Relief Valve must be installed with spindle in the vertical position. Installation of the relief valve must be consistent with ANSI/ASME Boiler and Pressure Vessel Code, Section IV.
WARNING
Installation is NOT complete unless a safety relief valve is installed as shown in Figure 4. Safety (relief) valve discharge piping must be piped near
oor to eliminate potential of severe burns. Do
not pipe in any area where freezing could occur. Do not install any shut-off valves, plugs or caps.
C. INSTALL DRAIN VALVE IN RETURN PIPING.
See Figures 6A and 6B.
D. OIL, GREASE, AND OTHER FOREIGN
MATERIALS which accumulate in new hot water
and a new or reworked system should be boiled
out, and then thoroughly ushed. A qualied water
treatment chemical specialist should be consulted for recommendations regarding appropriate chemical compounds and concentrations which are compatible with local environmental regulations.
E. AFTER THE BOILER AND SYSTEM HAVE
BEEN CLEANED AND FLUSHED, and before
relling the entire system add appropriate water
treatment chemicals, if necessary, to bring the pH between 7 and 11.
13
14
Figure 6A: Recommended Water Piping for Circulator Zoned Heating Systems
IV: WATER PIPING AND TRIM (continued)
Figure 6B: Recommended Water Piping for Zone Valve Zoned Heating Systems
IV: WATER PIPING AND TRIM (continued)
15
IV: WATER PIPING AND TRIM (continued)
F. CONNECT TANKLESS HEATER PIPING AS
SHOWN IN FIGURE 7.
WARNING
Install automatic mixing valve at tankless heater outlet to avoid risk of burns or scalding due to
excessively hot water at xtures. Adjust and
maintain the mixing valve in accordance with the manufacturer's instructions. Do not operate tankless heater without mixing valve.
THE FOLLOWING GUIDELINES SHOULD BE FOLLOWED WHEN PIPING THE TANKLESS HEATER:
1. FLOW REGULATION — If ow through the
heater is greater than its rating, the supply of adequate hot water may not be able to keep up
with the demand. For this reason a ow regulator
matching the heater rating should be installed in
the cold water line to the heater. The ow regulator
should preferably be located below the inlet to the heater and a minimum of 3’ away from the inlet so that the regulator is not subjected to excess temperatures that may occur during “off” periods when it is possible for heat to be conducted back
through the supply line. The ow regulator also limits the ow of supply water regardless of inlet
pressure variations in the range of 20 to 125 psi.
2. TEMPERING OF HOT WATER — Installation of an automatic mixing valve will lengthen the delivery
of the available hot water by mixing some cold water with the hot. This prevents the possibility
of scalding hot water at the xtures. In addition,
savings of hot water will be achieved since the user will not waste as much hot water while seeking a water temperature. Higher temperature hot water required by dishwashers and automatic washers is possible by piping the hot water from the heater prior to entering the mixing valve. The mixing valve should be “trapped” by installing it below the cold water inlet to heater to prevent lime formation in the valve. Refer to Figure 7.
3. FLUSHING OF HEATER — All water contains some sediment which settles on the inside of the coil. Consequently, the heater should be periodically back washed. This is accomplished by installing hose bibs as illustrated and allowing water at city pressure to run into hose bib A, through the heater, and out hose bib B until the discharge is clear. The tees in which the hose bibs are located should be the same size as heater connections to minimize pressure drop.
4. HARD WATER — A water analysis is necessary to determine the hardness of your potable water. This is applicable to some city water and particularly to well water. An appropriate water softener should be installed based on the analysis and dealer’s
recommendation. This is not only benecial to the tankless heater but to piping and xtures plus the many other benets derived from soft water.
16
Figure 7: Schematic Tankless Heater Piping
V: VENTING
A. GENERAL GUIDELINES
1. Vent system installation must be in accordance with these instructions and applicable provisions of
local building codes. Contact local building or re ofcials about restrictions and installation inspection
in your area.
2. The FR™ Series is designed to be vented into a
reclay tile-lined masonry chimney or chimney
constructed from type-L vent or a factory built chimney that complies with the type HT requirements of UL103. The chimney or vent pipe
shall have a sufcient draft at all times, to assure
safe proper operation of the boiler. See Figure 8 for recommended installation.
a. Install a draft regulator (supplied by installer)
following the instructions furnished with the regulator. See Figure 9 for alternate regulator locations.
b. With any new or replacement installation the
chimney has to be considered. Chimneys that have a high heat loss become less suitable as the heat loss of the home goes down and the
efciency of the boiler goes up. Most homes
have a chimney appropriate for the fuel and the era in which the home was built. That may
have been a coal red or an inefcient oil red
boiler built into a home without insulation or storm windows. With increasing fuel prices that
home probably has been insulated and tted with
storm windows so that the heat loss of the home has been reduced. This requires less fuel to be burned and sends less heat up the chimney.
A new boiler probably has a higher efciency
than the boiler being replaced. That probably
means that the stack temperature from the new boiler will be lower than that from the old boiler and with less room air being drawn up the chimney to dilute the stack gases. The combination of a large uninsulated chimney,
reduced ring rate, reduced ring time, lower
stack temperature and less dilution air can, in some cases, contribute to the condensing of small amounts of water vapor in the chimney. Such condensation, when it occurs, can cause chimney deterioration. In extreme cases, the chimney may have to be lined to insulate the chimney and thus prevent the condensation. The addition of dilution air into the chimney may assist in drying the chimney interior surfaces.
A massive chimney on a cold, or exposed outside
wall may have produced adequate draft when it
was red with a higher input and greater volumes
of heated gases. With reduced input and volume, the draft may be severely affected. In one instance our research showed a new chimney of adequate sizing produced only -.035” W.C. after
30 minutes of continuous ring at 13.0% CO
Outside wall chimneys take longer to heat up and can have .00” W.C. draft at burner start-up. You may have to consider a special alloy chimney
ue liner with insulation around it and stabilizing
draft cap or even a draft inducing fan in severe cases.
c. For the same reasons as in (2.) above, heat
extractors mounted into the breeching are not recommended.
3. For minimum clearances to combustible materials refer to Figure 2.
2
.
Figure 8: Recommended Smoke Pipe Arrangement and Chimney Requirements
17
Loading...
+ 39 hidden pages