VIII. Service and Cleaning
BURNER SHUTDOWN: Open Service Switch to turn off burner.
Manual Oil Supply Valve should be closed and Electric Service to boiler turned off if boiler
will not be operated for an extended period
of time.
A. GENERAL. Inspection service and cleaning should
maintenance.
B. FIRETUBES AND COMBUSTION CHAMBER. (See
Figure 29)
1. CLEAN THE FIRETUBES a. Disconnect electric to burner and remove stack.
b.
For access to the firembes, pull top jacket panel off. Remove brass nuts, that hold canopy down. Without taking off carriage bolts, pull canopy
off.
c. Remove turbulators. d. Using a firetube brush clean firetubes. DO NOT
extend brush past the end of the bottom tubesheet.
e. Assemble the boiler in reverse order.
Units should be cleaned at least once a year, preferably at the end of each heating season.
It is not necessary to remove burner to clean boiler. Brush, scrape, or vacuum from top.
NOTE: UNITS SHOULD BE C_NED AT
LF_AST ONCE A YE/_R, PREFER_LY
AT THE END OF EACH HEATING
SEASON.
iS NOT NECESSARY TO REMOVE
BURNER TO CLEAN BOILER.
BRUSH, SCRAPE OR VACUUM
CLEAN FLUE TUBES CAREFULLY
FROM TOP WITHOUT EXTENDING CLONING TOOLS BEYOND BOTTOM OF FLUE TUBE TO
PREVENT DAMAGE TO COMBUSTION
CHAMBER,
COMBUSTION C_B_ tS A LIGHTWEIGHT CERAMIC TYPE,
TOOK BEYOND BOTTOM OF FLUE TUBES TO PRINT
DAMAGE TO COMBUSTION
CH_BER.
_-490U & _-590U AP-BgOU & AP-790U
EXTEND CLEANING
BOILER MODEL
STEP 1
DISCONNECT _DTRICAL POWER
TO O{L BURN_
STEP 2
REMOVE STACK
STEP 3
REMOVE J_K_ TOP PANEL
STEP 4- REMOVE BRA_ HEX NUTS ND WASHERS
STEP 5 REMOVECANOPY
I I
s_P 6 REMO'v_ TURBULATORS
STEP 7
R_RBE PR_EDURE
TO ASSEMBLE
CLEANING INSTRUCTIONS
Figure 29: Cleaning of AP-U Boiler
BRUSH BEYOND THIS
EXTEND _UE
POINT
COMBUSTION CHAMB_
33
Warninq: The Repair Parts list designates parts that contain refractory ceramic fibers
(RCF). RCF has been classified as a possible human carcinogen. When
exposed to temperatures about 1805°F, such as during direct flame contact,
RCF changes into crystalline silica, a known carcinogen. When disturbed as a result of servicing or repair, these substances become airborne and, if inhaled, may be hazardous to your health.
AVOID Breathinq Fiber Particulates and Dust
Precautionary Measures: Do not remove or replace RCF parts or attempt any service or repair work
involving RCF without wearing the following protective gear:
1. A National Institute for Occupational Safety and Health (NIOSH) approved respirator
2. Long sleeved, loose fitting clothing
3. Gloves
4. Eye Protection
Take steps to assure adequate ventilation.
Wash all exposed body areas gently with soap and water after contact.
Wash work clothes separately from other laundry and rinse washing machine after use to avoid contaminating other clothes.
Discard used RCF components by sealing in an airtight plastic bag. RCF and crystalline silica are not classified as hazardous wastes in the United
States and Canada.
First Aid Procedures:
If contact with eyes: Flush with water for at least 15 minutes. Seek
immediate medical attention if irritation persists.
If contact with skin: Wash affected area gently with soap and water.
Seek immediate medical attention if irritation persists.
If breathing difficulty develops: Leave the area and move to a location
with clean fresh air. Seek immediate medical attention if breathing
difficulties persist.
Ingestion: Do not induce vomiting. Drink plenty of water. Seek
immediate medical attention.
34
Loading...