Thank you for choosing NEWMAR as the power products supplier to your company. NEWMAR’s Rackmount
Pure Sine Wave Power Inverters are designed and built for full reliability at multiple locations and variety of
applications. These intelligent, dependable inverters provide economical AC Power for all your network needs.
Operators spanning global continents have deployed the Rackmount Pure Sine Wave Power Inverters as the
choice for high availability AC power support from a DC source.
This manual contains information and technical details for all models in the Rackmount Pure Sine Wave Power
Inverter family. The general operation procedures are common, however in some instances, all or part of the
information will not apply to the specific model purchased. Refer to the specific model details page in Chapter 8:
Technical Specifications.
This user’s manual contains important technical instructions to be followed by qualified personnel
responsible for the installation, start-up and maintenance of this unit. We recommend that this manual
be read attentively to insure safe and reliable operation of this equipment.
Should you require any assistance, please call our Application
Engineering department at:
Tel: 800.854.3906 or 714.751.0488
Fax: 714.957.1621
Email: techservice@newmarpower.com
2. IMPORTANT SAFETY INSTRUCTIONS
2-1 UL Safety Statement
SAVE THESE INSTRUCTIONS - This manual contains important inverter instructions that should be followed during
installation and maintenance of the Rackmount Pure Sine Wave inverter unit.
To reduce the risk of electric shock, install the inverter in a temperature and humidity controlled indoor environment,
free of conductive contaminants. Ambient temperature should not exceed 50
¾ Depending on use, the AC output of the inverter may require a customer installed disconnect or fusing. For
telecom use, a GFCI has not
¾ The following precautions should be respected when working on the inverter:
Remove watches, rings, or other metal objects.
Use tools with insulated handles.
Wear rubber gloves and boots.
2-2 Other Safety Notes
¾ Upon receipt, examine the shipment box for damage. Notify the carrier immediately, before opening if damage is
evident.
¾ Do not open or disassemble the inverter, warranty will be voided.
been provided. The inverter offers standard AC short circuit protection.
o
C (122oF).
Page 3
¾ Do not operate near water or in excessive humidity.
¾ Keep liquid and foreign objects from entering the inverter.
¾ Install the inverter in a well-ventilated area. Do not block front air vents, or rear air exhausts of the unit.
¾ Do not operate the inverter close to combustible gas or open fire.
¾ Do not plug appliances with surging loads, or half bridge rectified loads, into the inverter.
¾ Do not operate the inverter if the unit is leaking any liquid or if a white powdery residue is found to be present.
¾ Temperature: The inverter should be operated in an ambient temperature range of 0°C to +50°C or output
efficiency may be affected. Air flow to the inverter must not be impeded.
¾ Reduced air flow: Installation of the equipment in a rack should be such that the amount of air flow required for
safe operation of the equipment is not compromised.
¾ Mechanical loading: Mounting of the inverter in a rack should be level and balanced.
¾ Wiring: Adequate input power must be supplied to the inverter for proper use; correct wiring sizes must be
respected.
¾ Grounding: Reliable grounding of rack-mounted equipment should be maintained.
¾ Inverter DC power connection must be from a VDC source within the technical specifications of the unit under
installation.
2-3 Symbols
PROTECTIVE GROUNDING TERMINAL: A terminal, which must be connected to earth ground prior to
making any other connection to the equipment.
This symbol indicates the word "phase".
3. PRODUCT OVERVIEW
3-1 System Features
The Rackmount Pure Sine Wave series inverter is a highly reliable DC-AC inverter system, designed with
advanced power electronics and microprocessor technology offering the following features:
Self-Diagnosis
The Rackmount Pure Sine Wave series inverter is equipped with a self diagnosis microprocessor, able to identify
and show all failure messages on the LED/LCD display, with visual/audio alarm.
High Frequency Architecture
With its high frequency architecture design, the Rackmount Pure Sine Wave series inverter features high
efficiency, light weight and compact design.
Modular Design
Rackmount Pure Sine Wave inverters use a modular design structure, resulting in easy maintenance, and high
MTBF.
High Efficiency
Rackmount Pure Sine Wave series inverters offer advanced soft-switching designs which increase operating
efficiency and reduce switching noise.
Page 4
Advanced Protection Features:
¾ Input reverse polarity-proof protection
¾ Internal over temperature protection
¾ Output overload protection
¾ Output over/under voltage protection
¾ Output short circuit protection
¾ DC input short circuit protection: fuse and breaker
¾ AC input short circuit protection: breaker
¾ Input over/under voltage protection
¾ Fan failure detection and protection
3-2 Block Diagram
Rackmount Pure Sine Wave Inverter Block Diagram
AC BYPASS
INPUT
DC INPUT
BREAKER
FILTER
DC to DC Converter
DC
BYPASS RELAY
DC
DC to AC Inverter
DC
AC
OUTPUT RELAY
FILTER
OUTPUT
AC
Rackmount Pure Sine Wave inverters feature IGBT (Insulated Gate Bipolar Transistor) technology, minimizing
weight and dimension, while enhancing output short circuit reliability and overload capacity.
Output voltage is provided in one of two ways:
1) From AC input bypass mode: (Off-Line Mode)
2) From DC to AC inverter mode: (On-Line Mode)
Either mode is front panel programmable; the selected operational mode will predetermine the “default” output.
In the first option, Off-Line mode
, AC output power will be supplied through the AC bypass mode in its “normal”
operation. Upon AC input failure, output power will be diverted through the DC to AC inverter mode. Once AC mains
are restored, the unit will revert from inverter mode to bypass mode.
In the second option, On-Line mode
, AC output power will be provided directly by the inverter from the VDC source.
Should the DC source or inverter fail, the system will transfer its output power through the bypass mode. Once the
DC power source is restored, the system will revert to “inverter” mode.
Transfer time from inverter to bypass, or bypass to inverter is < 4 ms.
The Off-line/On-line mode is changed from one to the other by pressing the ON button for less than 3 seconds when
normal
output is available. The operational mode cannot be changed during an abnormal or fault condition.
3-3 Front Panel
MAJORPOWER.COM
Tel: 514.369.4919 Fax: 514.369.4817
http://www.majorpower.com
Page 5
¾ON/OFF buttons:
These are the two power buttons for turning on or turning off the inverter.
Once the inverter is on, the “ON” button works as the On-Line <=> Off-Line mode switching button.
¾INVERTER ON Indicates the INVERTER has been turned on and is working normally (output is available to
support load equipment).
¾ OVERLOAD Means that the inverter is in overload condition, or that there is an output short circuit.
¾ DC ABNORMAL Means that the input DC voltage is “abnormal” and requires verification.
¾ FAULT Indicates that the inverter is in “fault” condition. See Section 6-3 Alarms
**If utility by-pass is not being used, and AC input is not present, the fault LED will remain on.
¾LCD Display Selection Buttons
The following data: (output voltage, output frequency, load, input dc voltage, bypass ac voltage, bypass ac
frequency, etc.) and system status can be shown sequentially on the LCD display by pressing these two buttons.
For more information – Refer to Section 5 Operation
¾Ventilator
The ventilator on the front panel provides inverter cooling. Do NOT
obstruct this vent or the fan exhaust in the
back of the unit!
¾Circuit Breaker (DC Input Breaker)
The DC circuit breaker will be tripped if there is a “short circuit” condition within the inverter. Reverse polarity
protection (input) and overload protection are integrated within the internal circuitry and neither of these faults
should trip the DC breaker.
3-4 Rear Panel
¾Communication Interface
Rackmount Pure Sine Wave inverter provides two standard and integrated communication interfaces
a) RS-232 interface.
b) Dry Contact interface.
Option) SNMP/Web Adapter card is available; please contact your Sales Distributor for information.
¾FAN
Inverter cooling is provided by DC fans. Forced air flow is from front-to-back.
¾AC Output Receptacles
NEMA 5-20R/5-15R × 4 or IEC-320 x 4
Page 6
¾AC Input Terminal
Terminal for bypass VAC input voltage. A 115 VAC, 20 amp circuit is recommended for full power operation.
¾AC Input Breaker
Breaker for AC input
¾DC Input Terminal
Terminal for VDC input voltage
¾Dry Contact Terminal
Dry contact terminal is connected to two Form C relays. One is for “DC abnormal” and the other one is for
“FAULT”.
When input DC voltage or fault occurs, the internal contact relay will open/close.
The terminal can support 5A / 250VAC
3-5 Bypass Switching and Grounding
I nv er ter R el ay
INV-L
INV-N
Chassis
B yp ass R el ay
O/P
DC I/P
AC I/P
+
-
GND
AC L
AC N
GND
DC/AC
AC Bypass
Chassis
Operation = Off – Line Mode:
AC input supplied from local service panel,
AC I/P neutral to earth connection provided externally.
(Usually service panel)
Operation = On– Line Mode:
DC input supplied from battery/DC power system
Inverter originated AC, therefore neutral to earth connection provided internally to chassis.
Grounding:
Chassis to Earth Ground connection should be made per customer installation specifications or prevailing safety
jurisdiction authority.
The inverter external safety ground plane is not switched by operation in any mode. Typically - the chassis is
mounted in a rack or a conductor to ground plane is installed.
4. INSTALLATION
4-1 Delivery
Upon receipt of goods, check the condition of the package. Should the package or unit be damaged, refuse
receipt and/or contact your shipper immediately to initiate your claim.
4-2 Installation Procedures
¾ Mount unit using the brackets and screws supplied in the hardware kit.
Page 7
¾ Please check that the input DC voltage meets the VDC specification of the inverter, and verify the correct DC
polarity connections have been made to the inverter.
¾ Connect the DC input voltage cables before engaging the front panel DC breaker.
¾ Use the following recommended cable sizes when connecting power to the inverter.
Model Capacity DC Input AC InputAC Output
24-1000RM 1 KVA #6 AWG #12 AWGNEMA 5-15R
48-1000RM 1 KVA #10 AWG #16 AWGNEMA 5-15R
48-2000RM 2 KVA #6 AWG #12 AWG NEMA 5-20R/5-15R
48-1000IRM 1 KVA #10 AWG #16 AWGIEC-320
48-2000IRM 2 KVA #6 AWG #12 AWGIEC-320
125-1000RM 1 KVA #12 AWG #16 AWGNEMA 5-15R
125-2000RM 2 KVA #12 AWG #12 AWG NEMA 5-20R/5-15R
4-3 Installation Tool Kit
Contents of the tool kit include:
• Poly zip bag containing twelve M4 screws and two 6-32 screws,
• Two large mounting brackets (23” or 24” rack mount),
• Two small mounting brackets (19” rack mount),
• One protective cover for AC input,
• One RS232 Cable.
4-4 Locking Hardwire Adapter
¾ The optional adapter is a reliable locking NEMA 5-15 plug on one end and terminal screws on the other end.
The plug-to-terminal conversion is used to secure bare wire load circuit wiring to the output sockets of the
inverter. The adapter includes strain relief for the wires being connected to the terminals.
Documents Also Available: Application Note # AN-001
5. OPERATION
5-1 Connecting to the Input Power
¾ Turn off the DC breaker before connecting the DC voltage to the input terminal. The DC terminal strip will
accommodate ring terminals with wire sizes recommended in Chapter 4-2.
¾NOTE: Sparks will occur if the breaker is “on” when connecting the input DC voltage. This is a normal condition
due to the charging current draw from the DC voltage charging the internal capacitor of the inverter.
¾ Once the DC power has been connected, engage the DC breaker to operate the inverter.
5-2 Connecting the Loads
¾ Calculate the total power consumption (VA) of the load being attached to the output. Make sure that the total
power consumption does not exceed the rated load of the inverter.
¾ The load consumption can be monitored on the front screen of the inverter using the data button.
¾ Should the total load exceed the capacity of the inverter, remove uncritical loads until the total load is within the
capacity of the inverter. Distribute removed loads to alternate sources or additional inverters
Page 8
¾ Only two hardwire adapters will fit on the integrated NEMA duplex outlets of the inverter. Loads should be
(ON)
)
(D)
(D)
distributed so not to exceed current ratings of hardware and cable.
5-3 Front Panel Operation of Sequence
(Software Version 0.0 or 3.1)
1. Make sure that the complete installation has been carried out correctly. When the breaker is turned on or the
utility input is available, the LCD of the inverter will display either following message:
2. Press the “ON” button for a minimum of one full second
SYSTEM IS AT
SYSTEM IS AT
OFF-LINE MODE
ON-LINE MODE
(and Release within 10seconds) to start the system
power. (if you press the ON
key less than 1 second, the CPU will not start up correctly). The inverter is in a
normal operation condition when either of the following messages appear on the LCD screen:
5-3a Programming the Inverter
INVERTER : STD BY
BYPASS : ON
INVERTER : ON
BYPASS : STD BY
The INVERTER will automatically initiate self-checks and start-up after 10 seconds.
Press ON Button
at least 1 full sec.
Press the ON key for
entry into
programming pages.
SET F=60 V= 115
I/P F=60 V= 118
Chang Setting?
No(OFF
Yes
10SEC Time Out.
O/P FREQ=60HZ
Sure(ON)
SEL.
O/P VOL=120V
Sure(ON)
SEL.
Press the OFF key to enter into
the INVERTER main start-up
procedure or wait 10 secs.
Start-Up Sequence
INVERTER On
SET = Last Programmed Setting for Operation
I/P = Bypass Circuit Sensor – If Present.
Page 9
5-4 “DATA” button
You can use the "DATA" button to select the following information which is displayed on the LCD screen:
A) Output voltage:
Shows present output voltage.
B) Inverter voltage:
Shows present “inverter” voltage.
C) Output frequency:
Shows present output frequency.
OUTPUT VOLT.
*** □□□.□V ***
INVERTER VOLT.
*** □□□.□V ***
OUTPUT FREQ.
*** □□.□ Hz ***
D) Bypass AC voltage:
Shows present input bypass AC voltage.
BYPASS AC VOLT
*** □□□.□V ***
E) Bypass AC frequency:
Shows present input bypass AC frequency.
BYPASS AC FREQ
*** □□.□Hz ***
F) Input DC voltage:
Shows the input DC voltage.
INPUT DC VOLTAGE
*** □□.□V ***
G) Output current:
Shows present output current.
OUTPUT CURRENT
*** □□.□ A ***
H) Output VA:
Shows present output Volt-Amp
Page 10
OUTPUT VA
*** □□□□ VA ***
I) Output power:
Shows present output power (Watt)
OUTPUT POWER
*** □□□□ W ***
J) Temperature:
Shows the temperature inside the INVERTER
TEMPERATURE
*** □□.□ º C ***
K) Firmware Version:
Shows the CPU firmware version
FIRMWARE VERSION
5-5 “STATUS” button
You can use the "STATUS" button to select the following information which is displayed on the LCD screen:
A) Output status:
a) When the input bypass voltage is normal and INVERTER output voltage is from DC to AC inverter, LCD
shows
INVERTER : ON
BYPASS : STD BY
b) When the output is from input bypass AC, LCD shows
INVERTER : STD BY
BYPASS : ON
c) When the INVERTER is turned off by firmware, LCD shows
*** V □.□ ***
** OUTPUT **
OUTPUT OFF
d) When the INVERTER is turned off by software, LCD shows
** OUTPUT **
SCHEDULE OFF
Page 11
B) DC to AC inverter status
a) When the INVERTER is normal, LCD shows
** INVERTER **
NORMAL
b) When the inverter is over temperature (may be caused by overload, high ambient temperature or fan
failure), LCD shows.
** INVERTER **
OVER TEMPERATURE
c) When the temperature inside the INVERTER is too high, LCD shows.
** AMBIENT **
OVER TEMPERATURE
d) When the INVERTER output is in “short circuit” detection mode, LCD shows.
** INVERTER **
SHORT CIRCUIT
e) When the INVERTER output is overloaded beyond rated capacity, LCD shows.
** INVERTER **
OVERLOAD
f) When the fan is in “fault”, LCD shows.
** INVERTER **
FAN FAILURE
g) When the INVERTER voltage is “too high”, LCD shows.
** INVERTER **
OVER VOLTAGE
h) When the INVERTER voltage is “low”, LCD shows.
** INVERTER **
UNDER VOLTAGE
C) Bypass AC status
a) When the input bypass voltage is normal, LCD shows.
Page 12
** BYPASS AC **
NORMAL
b) When the input bypass voltage is normal and INVERTER output is in “bypass mode”, LCD shows
INVERTER : STD BY
BYPASS : ON
c) When the input bypass voltage is “too low”, LCD shows.
** BYPASS AC **
UNDER VOLTAGE
d) When the input bypass voltage is “too high”, LCD shows.
** BYPASS AC **
OVER VOLTAGE
e) When the input bypass is “over” normal frequency range, LCD shows.
** BYPASS AC **
OUT OF FREQ.
f) When the output is overloaded, LCD shows.
** BYPASS AC **
OVER LOAD
D) Input DC status
a) When the input DC voltage is normal.
** INPUT DC **
NORMAL
b) When the input DC voltage is under threshold, the LCD shows.
** INPUT DC **
LOW VOLTAGE
c) When the input DC voltage is over threshold, the LCD shows.
d) When the input DC voltage is under voltage, the INVERTER will switch to bypass mode (if bypass AC is
available) and LCD shows.
** INPUT DC **
HIGH VOLTAGE
Page 13
e) When the input DC voltage is over voltage, INVERTER will switch to bypass mode (if bypass AC is
available) and LCD shows.
5-6 Error message
If the following messages appear on the LCD screen, contact Majorpower at once.
DC UNDER VOLT
INVERTER OFF
DC OVER VOLT
INVERTER OFF
** INVERTER **
SOFTSTART FAIL
EEPROM
NOT AVAILABLE
EEPROM
checksum error
6. MAINTENANCE AND TROUBLESHOOTING
6-1 Maintenance
¾ Make sure that the inverter vents are not blocked.
¾ Use a vacuum cleaner to clear any dust from the fan area.
¾ When cleaning the case or front panel, use a soft, dry cloth, only. If the case or front panel is very dirty, use a
neutral, non-abrasive detergent. Do not
¾ Regular service, and movement of the inverter, should be performed by a qualified service technician.
¾ Avoid spilling liquid on the Inverter.
use alcohol or ammonia based solutions.
Page 14
6-2 Troubleshooting
Problem Possible cause Action to take
Turn on or reset the
circuit breaker.
Apply correct DC
polarity.
Apply correct DC
voltage.
AC voltage or frequency
may be out of range.
Remove unnecessary
loads or redistribute
loads to other inverters.
Use 2400 bps baud rate
and re-test.
Refer to the wire
connection in chapter 7.
Check for blocked vents,
or non-working fan.
LEDs do not light up
“FAULT” LED lights up*
“OVERLOAD” LED is ON
Communication fault.
“FAULT”LED lights, LCD
OVERTEMPERATURE
The circuit breaker is “off”
DC cable polarity
installation
DC input is “over” or
“under” voltage.
Bypass AC fail
Inverter failure. Call for service.
Output was “short”. Load may be abnormal
The power drawn from
the inverter exceeded
the load rating of the
inverter.
Incorrect transmission
rate.
Wrong wire connection.
Temperature inside
the inverter is too high.
*NOTE - If utility by-pass is not being used,
and AC input is not present, the fault LED will
remain on.
6-3 Alarms
¾ Inverter Alarm Classifications
¾ Fault Alarm Indicator includes:
Bypass AC Input High or Low Voltage
Bypass AC Input Frequency Out of Range
Fan Fail
Inverter Internal Failure
Output Load Sensing “short” condition
High Temperature
¾ Overload Indicator includes:
The AC power drawn from the inverter exceeded the
load rating of the inverter.
The “Dry Contact” terminal is the interface for two Form C relays. The relays are used for switching the voltage
provided by the user’s external alarm system.
One contact set is for “DC Abnormal” and the other one is for “FAULT”. When alarms in each classification
trigger, the relay switches state. (Ref: Sec. 6-3 Alarms) Connection to the terminal should be made to external
sensor circuits with appropriate sized wire. The terminal can support 5A / 250VAC in either NC or NO
configurations.
¾ NC: Normally Closed
¾ CO: Common
¾ NO: Normally Open
7-2 SNMP Expansion Card Slot (WEB)
Remote monitoring is a prime consideration and requirement to manage multiple network elements from a central
location. SNMP remote access as easy as; installing the plug-n-play card, configuring your network IP address, and
attaching the network interface cable.
The SNMP Kit includes:
¾ Interface electronics card
¾ Cover plate
¾ RS-232 to RJ-45 custom cable
¾ Quick installation guide
¾ CDROM with utilities and MIB
The integrated expansion card slot is located on the rear of the inverter behind a protective cover plate. [Ref: 3-4 Rear
Panel] Installation of the SNMP card and cover plate is easily achieved using a standard #2 cross point screw driver.
Card IP address programming required PC interface. Instructions for installation are included in the kit. (kit sold
separately)
7-3 RS-232 Communication Port (GUI)
The RS-232 communication port provides the following features using a GUI software package:
1) Communicates Fault, DC abnormal, Overload, Inverter Fail etc.
2) Monitor and display output voltage, output load, input dc voltage and temperature.
3) Coupled with PC software application port, provides scheduled on/off function for inverter.
Inverter data will be transmitted at 2400 baud rate. Signal is 8 bit, 1 stop bit, and no parity bit.
All information is provided in GUI format and intended for local maintenance monitoring.
Page 16
HARDWARE:
BAUD RATE 2400 bps
DATA LENGTH 8 bits
STOP BIT 1 bit
PARITY NONE
CABLING:
COMPUTER (female) - INVERTER (male)
PIN2 (RXD) ------------------ PIN2 (TXD)
PIN3 (TXD) ------------------ PIN3 (RXD)
PIN4 (PNP) ------------------ PIN4 (PNP)
PIN5 (COMMON) --------------- PIN5 (COMMON)
PIN6 (PNP) ------------------ PIN6 (PNP)
PIN7 (PNP) ------------------ PIN7 (PNP)
8. TECHNICAL SPECIFICATIONS
24-1000RM
DC Input
Voltage 20-30 VDC
Rated Current 50 Amps
Protection Fuse and DC Breaker
Efficiency >85% (full linear load),
AC Output
Capacity 1KVA / 800W
Voltage 100, 110, 115, 120 VAC
Voltage Regulation ±2%
Frequency 50/60Hz ± 0.2Hz
Wave Form Pure Sine Wave
THD (linear load) 3% 120 V/100%
THD (SPS load) 5% 120 V/100%
Crest Factor 3:1
Receptacles (4) NEMA 5-20 R outlets
Utility Power (Bypass)
Voltage (Nominal) 120 VAC
Frequency 50/60± 5 Hz
Protection AC Circuit Breaker
Protection
Short For 1 second; Switch to
Bypass, then shutdown
Overload 105-125% for 3 minutes;
126-150% for 3 seconds;
>150% for 1 second;
Switch to bypass
Temperature 55 ± 5º(Inside the case)
Safety
Safety UL / cUL
EMI / RFI FCC Class A
Mechanical
Dimensions 17.32”W x 11.81”D x 3.46”H
(440x300x88mm)
2U Rackmount
Weight
24 VDC I/P, 120 VAC O/P
8kg / 17.6lbs
Page 17
48-1000RM
DC Input
Voltage 40-60 VDC
Rated Current 25 Amps
Protection Fuse and DC Breaker
Efficiency >85% (full linear load),
AC Output
Capacity 1KVA / 800W
Voltage 100, 110, 115, 120 VAC
Voltage Regulation ±2%
Frequency 50/60Hz ± 0.2Hz
Wave Form Pure Sine Wave
THD (linear load) 3% 120 V/100%
THD (SPS load) 5% 120 V/100%
Crest Factor 3:1
Receptacles (4) NEMA 5-15 R outlets
Utility Power (Bypass)
Voltage (Nominal) 120 VAC
Frequency 50/60± 5 Hz
Protection AC Circuit Breaker
Protection
Short For 1 second; Switch to
Bypass, then shutdown
Overload 105-125% for 3 minutes
126-150% for 3 seconds;
>150% for 1 second;
Switch to bypass
Temperature 55 ± 5º(Inside the case)
Safety
Safety UL / cUL
EMI / RFI FCC Class A
Mechanical
Dimensions 17.32”W x 11.81”D x 3.46”H
(440x300x88mm)
2U Rackmount
Weight
48 VDC I/P, 120 VAC O/P
7kg / 15.4 lbs
Page 18
48-2000RM
DC Input
Voltage 40-60 VDC
Rated Current 50 Amps
Protection Fuse and DC Breaker
Efficiency >85% (full linear load),
AC Output
Capacity 2KVA / 1600W
Voltage 100, 110, 115, 120 VAC
Voltage Regulation ±2%
Frequency 50/60Hz ± 0.2Hz
Wave Form Pure Sine Wave
THD (linear load) 3% 120 V/100%
THD (SPS load) 5% 120 V/100%
Crest Factor 3:1
Receptacles (4) NEMA 5-20 R outlets
Utility Power (Bypass)
Voltage (Nominal) 120 VAC
Frequency 50/60± 5 Hz
Protection AC Circuit Breaker
Protection
Short For 1 second; Switch to
Bypass, then shutdown
Overload 105-125% for 3 minutes
126-150% for 3 seconds
>150% for 1 second;
Switch to bypass
Temperature 55 ± 5º(Inside the case)
Safety
Safety UL / cUL
EMI / RFI FCC Class A
Mechanical
Dimensions 17.32”W x 11.81”D x 3.46”H
(440x300x88mm)
2U Rackmount
Weight
48 VDC I/P, 120 VAC O/P
7kg / 15.4 lbs
Page 19
125-1000RM
DC Input
Voltage 100-150 VDC
Rated Current 10 Amps
Protection Fuse and DC Breaker
Efficiency >85% (full linear load),
AC Output
Capacity 1KVA / 800W
Voltage 100, 110, 115, 120 VAC
Voltage Regulation ±2%
Frequency 50/60Hz ± 0.2Hz
Wave Form Pure Sine Wave
THD (linear load) 5% 120 V/100%
THD (SPS load) 3% 120 V/100%
Crest Factor 3:1
Receptacles (4) NEMA 5-15 R outlets
Utility Power (Bypass)
Voltage (Nominal) 120 VAC
Frequency 50/60± 5 Hz
Protection AC Circuit Breaker
Protection
Short For 1 second; Switch to
Bypass, then shutdown
Overload 105-125% for 3 minutes
126-150% for 3 seconds;
>150% for 1 second;
Switch to bypass
Temperature 55±5º (Inside the case)
Safety
Safety UL / cUL
EMI / RFI FCC Class A
Mechanical
Dimensions 17.32”W x 11.81”D x 3.46”H
(440x300x88mm)
2U Rackmount
Weight
125 VDC I/P, 120 VAC O/P
7kg / 15.4 lbs
Page 20
125-2000RM
DC Input
Voltage 100-150 VDC
Rated Current 20 Amps
Protection Fuse and DC Breaker
Efficiency >85% (full linear load),
AC Output
Capacity 2KVA / 1600W
Voltage 100, 110, 115, 120 VAC
Voltage Regulation ±2%
Frequency 50/60Hz ± 0.2Hz
Wave Form Pure Sine Wave
THD (linear load) 5% 120 V/100%
THD (SPS load) 3% 120 V/100%
Crest Factor 3:1
Receptacles (4) NEMA 5-20 R outlets
Utility Power (Bypass)
Voltage (Nominal) 120 VAC
Frequency 50/60± 5 Hz
Protection AC Circuit Breaker
Protection
Short For 1 second; Switch to
Bypass, then shutdown
Overload 105-125% for 3 minutes
126-150% for 3 seconds
>150% for 1 second;
Switch to bypass
Temperature 55±5º(Inside the case)
Safety
Safety UL / cUL
EMI / RFI FCC Class A
Mechanical
Dimensions 17.32”W x 11.81”D x 3.46”H
(440x300x88mm)
2U Rackmount
Weight
125 VDC I/P, 120 VAC O/P
8kg / 17.6 lbs
Page 21
48-1000IRM
DC Input
Voltage 40-60 VDC
Rated Current 25 Amps
Protection Fuse and DC Breaker
Efficiency >85% (full linear load),
AC Output
Capacity 1KVA / 800W
Voltage 208, 220, 230, 240 VAC
Voltage Regulation ±2%
Frequency 50/60Hz ± 0.2Hz
Wave Form Pure Sine Wave
THD (linear load) 3% 120 V/100%
THD (SPS load) 5% 120 V/100%
Crest Factor 3:1
Receptacles (4) IEC 320 outlets – C13
Utility Power (Bypass)
Voltage Nominal 230 VAC
Frequency 50/60± 5 Hz
Protection AC Circuit Breaker
Protection
Short For 1 second; Switch to
Bypass, then shutdown
Overload 105-125% for 3 minutes
126-150% for 3 seconds;
>150% for 1 second;
Switch to bypass
Temperature 55±5º(Inside the case)
Safety
Safety CE Approved
EMI / RFI FCC Class A
Mechanical
Dimensions 17.32”W x 11.81”D x 3.46”H
(440x300x88mm)
2U Rackmount
Weight
48 VDC I/P, 230 VAC O/P
7kg / 15.4 lbs
Page 22
48-2000IRM
DC Input
Voltage 40-60 VDC
Rated Current 50 Amps
Protection Fuse and DC Breaker
Efficiency >85% (full linear load),
AC Output
Capacity 2KVA / 1600W
Voltage 208, 220, 230, 240 VAC
Voltage Regulation ±2%
Frequency 50/60Hz ± 0.2Hz
Wave Form Pure Sine Wave
THD (linear load) 3% 120 V/100%
THD (SPS load) 5% 120 V/100%
Crest Factor 3:1
Receptacles (4) IEC 320 outlets – C13
Utility Power (Bypass)
Voltage Nominal 230 VAC
Frequency 50/60± 5 Hz
Protection AC Circuit Breaker
Protection
Short For 1 second; Switch to
Bypass, then shutdown
Overload 105-125% for 3 minutes
126-150% for 3 seconds
>150% for 1 second;
Switch to bypass
Temperature 55±5º(Inside the case)
Safety
Safety CE Approved
EMI / RFI FCC Class A
Mechanical
Dimensions 17.32”W x 11.81”D x 3.46”H
(440x300x88mm)
2U Rackmount
Weight
48 VDC I/P, 230 VAC O/P
8kg / 17.6 lbs
Page 23
Drawing No. MPXXXNX02ABX
Page 24
9. Optional Hardware:
SNMP Remote Communication Card
:
Remote monitoring is a prime consideration and requirement to manage multiple network elements from a central
location. Remote access is established by simply installing the plug-n-play card, configuring your network IP
address, and attaching the network interface cable.
Locking - Hardwire Adapter
:
Reliable locking NEMA 5-15 plug to secure load circuits to the output sockets of the inverter. Heavy-duty design
locks the plug in place to prevent disconnecting critical loads.
[Note: Only two hardwire adapters will fit on the integrated NEMA duplex outlets of the inverter. Loads should be distributed so not to exceed current
ratings of hardware and cable.]
Page 25
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.