Document Part #: 1160915
Rev: I
ECN: 55118
Rev. Date: 5-28-14
The RD-8 and RD-3 refrigerated display showcase unit has been safety and performance-test approved by
various safety regulatory testing agencies. In the course of new installations or periodic inspections, reference to
agency approvals may be required. Following are the regulatory agency file numbers:
Solenoid Valve Hermetic Direct Acting Type Solenoid Valve for Refrigeration
Thermostat Electronic- Defrost on Demand (10 ~ 30 minutes, every 2 hours)
Drain-pipe Dimension 1.25” copper tube
Evaporator
Fan Motor
Compressor(s)
Condenser fans
6 Watt, 3 each
1.25 HP, 10 Amp Left side
10 Amp Right side
Buck and Boost Transformer required when voltage is below 210VAC
or above 253VAC
Internal Volume 26.4 ft3 for RD-3 / 53.3 ft3 for RD-8
Weight 560 lbs. for RD-3 / 900 lbs. for RD-8
Noise Less than 65 DB at 3.3 ft.
Agency Approvals UL, UL NSF
Top Shelf Tilt 7.5°
NOTE: The manufacturer reserves the right to make product improvements and change specifications without notice
5
INITIAL SET-UP
The Model RD-8 and RD-3 Remote Refrigerated Showcase, when properly installed and maintained, is
designed to provide years of trouble-free operation. This Operation Manual contains information necessary for
proper installation, maintenance and cleaning of the unit.
It is the responsibility of the installer to ensure the unit is installed and working properly. The following
instructions provide step-by-step set-up, piping, condensate drain connections, wiring, start-up, performance
and maintenance guidelines.
Following installation, please review, fill out and sign form for activation of warranty within 5 days of
installation. FAX: 1800-561-5684 or email: customerservice@vendoco.com
Additional reference manuals can be obtain at www.vendoco.com
CABINET SET-UP
Step 1: Choose a location for your new refrigerated display case. Avoid placing the cabinet near equipment that
releases heat. Avoid direct sunlight. To protect all electrical parts, do not place the cabinet where it
will be subjected to rain, splashed liquid, or excessive humidity.
Step 2: Check the airflow around the cabinet, since strong airflow may displace the cooled air in the display
case. Place the cabinet where the airflow speed is less than 60 ft/min. Also, avoid areas subject to
strong winds (see figures 1-9).
6
7
8
CONDENSATE DRAIN CONNECTION (PREFERRED METHOD)
Install the appropriate condensate drain line between the 1 ¼” copper tube outlet to a floor sink, a drain line or
other, allowing a code required air gap.
9
CONDENSATE REMOVAL METHODS (ALTERNATE)
HEATED CONDENSATE PAN
Heated condensate pan, when used, is
recommended to be placed behind the
unit and not inside the compressor
compartment.
CONDENSATE PUMP
Condensate pumps, when used, can be
placed inside the compressor
compartment or behind the unit with the
outlet connected to the nearest drain.
SVA Part Number: 1231359
10
REMOTE CONDENSER INSTALLATION
For proper operation of the RD-8 and RD-3 showcase the following installation guideline must be followed.
Failure to do so may result in loss of refrigeration capacity, premature part failure, and may void all warranty.
Remote condenser liquid line 3/8”, fitting: 3/8“Flare.
2. Outdoor ambient operating temperature: -20°F (-28°C) to 110°F (43°C)
3. Indoor operating requirements: 75°F, less than 55%RH.
4. Maximum refrigerant line length: 45 ft. (13.7 m) including fittings.
be used to minimize adding length to the line set.
90° long radius elbow fittings should
5. Maximum vertical rise without oil trap in discharge line: 15 ft. (4.6 m)
6. Minimum condenser height: Remote condenser for RD-8 and RD-3 must not be installed more than 6 ft.
(1.83 m) below the refrigerant line connections at rear of showcase unit. No part of refrigerant lines,
between machine and condenser, should fall below this point.
7. Insulate 3/8” liquid line, to limit heat exchange between lines. Liquid lines should be sloped 1/8 inch per
foot (10.4 mm/m) in the direction of refrigerant flow and insulated. Trapping is unnecessary.
8. Isolate all lines when passing through walls and room from abrasion. Support all refrigerant lines at
minimum intervals with suitable hangers and brackets.
9. Leak check with nitrogen and evacuate remote line set (This will require installation of “Schrader Tee”
in the remote air cooled condenser line set). Vacuum to a minimum of 200microns prior to opening
service valves.
10. Discharge lines carry both refrigerant vapor and oil. Since refrigerant may condense during the off
cycle, the piping should be designed to avoid liquid refrigerant and oil from flowing back into the
compressor. Discharge lines should be pitched 1/8 inch per foot (10.4 mm/m) in the direction of
refrigerant flow towards the condenser
11. Addition of refrigerant is .7oz per feet of refrigerant line added. View sight glass for minimal vapor
bubbles. Properly charged unit will have head pressure 30°F above the ambient conditions
12. If environment is subject to cold weather, use a Head Master valve. Recommend LAC-4-210
13. Check compressor superheat at compressor suction line 15-25°F, Subcooling 4-6°F
Remote condenser liquid line 3/8”, fitting: 3/8“Flare.
2. Maximum refrigerant line length: 45 ft. (13.7 m) including fittings.
3. Maximum vertical rise without oil trap in discharge line: 15 ft. (4.6 m)
4. Minimum condenser height: Remote condenser must not be installed more than 6 ft. below the
refrigerant line connections at rear of showcase unit.
5. Insulate 3/8” liquid line, to limit heat exchange between lines.
6. Add 0.7oz of refrigerant per feet of refrigerant line added. View sight glass for minimal vapor bubbles.
Properly charged unit will have head pressure 30°F above the ambient conditions.
7. If environment is subject to cold weather, use a Head Master valve. Recommend LAC-4-210.
8. Minimum allowable voltage is 210V. For lower voltages use buck and boost model number SQUARE
D 500SV43B.
Condenser above the unit
IMPORTANT: Inverted 1/2
x 1/2 copper P-Trap to
prevent liquid draining from
condenser to compressor.
IMPORTANT: In cold
weather conditions, use
Headmaster valve LAC-4-
210. See manual for
additional instructions.
Correctly installed roof top
discharge line P-Trap and insulated
liquid line.
Max. two 20”
s
loo
12
Do not install more than two 20”
loops.
p
p
p
When installing the condenser above the machine. When installing the condenser below the machine.
DO Slope refrigerant lines downward toward compressor. DO Slope refrigerant lines downward toward condenser.
Slope discharge
line towards
condenser.
Max. two 20”
s
loo
Slope liquid line
towards
ressor.
com
Max. two 20”
s
loo
DO NOT Install any part of the refrigerant lines below the DO NOT Install the condenser lower than 6 ft. (1.83m) below
connection fittings at rear of machine. the connection fittings at rear of machine.
DO NOT Create oil trap in refrigerant lines by sloping lines
down ward than rising upward.
Condenser sizing and placement
The condenser should be designed for proper capacity for RD-8 or RD-3. (9850BTU per side)
The location of the remote condenser should be such that the ambient air temperature does not exceed 110°F
(43°C). If ambient temperature exceeds 110°F (43°C) cabinet performance might suffer.
13
The condenser coil and fan blades must be kept clean. The condenser can be cleaned with compressed air or by
using a brush. If a brush is used, brush in the direction of the fins taking care not to be bend the fins.
If condenser fins are bent this will also restrict air flow through the condenser and the fins will need to be
straightened with a fin comb.
If the air flow is restricted or the condenser is dirty the head pressure will be excessively high, no heat exchange
will result and the compressor will overheat and eventually become damaged. Problems related to dirty
condenser or poor air flow will not be covered under warranty.
Head Pressure Control Valve
When the temperature at the condenser is above 70°F (21°C), the refrigerant flow from the compressor is
directed by the head pressure control valve through the condenser and into the receiver. When the temperature
at the condenser drops below 70°F (21°C), the pressure in the bellows of the head pressure control valve
becomes greater than the pressure of the liquid refrigerant coming from the condenser. This change allows the
valve to partially restrict the flow of liquid refrigerant leaving the condenser. This allows discharge gas to bypass the condenser and flow directly into the receiver, mixing with the liquid refrigerant from the condenser.
The amount of discharge gas that by-passes the condenser increases asthe ambient temperature at the
condenser decreases. This action of head pressure valve allows the head pressure to be maintained at
approximately 240 p.s.i. (16.5 bar) on RD-8 unit during low ambient conditions. The remote system depends on
an adequate refrigerant charge in order for the system to remain balanced during ambient temperature changes.
If the refrigeration system is undercharged and the ambient temperature is below 70°F (21°C) the head pressure
control valve will not work properly. The head pressure control valve will allow too much refrigerant to bypass
the condenser.
Problem Possible Cause Remedy
1. Head pressure low / liquid line
between valve and receiver cold.
Ambient condenser temp. below 70°F
(21°C)
2. Head pressure low / liquid line
between valve and receiver hot.
3. Head pressure high/ liquid line
returning from condenser is cool.
Ambient condenser temp. above 70°F
(21°C).
a. Valve defective, not allowing
discharge gas into receiver
a. System low charged.
b. Valve defective, not allowing enough
sub-cooled liquid into receiver.
a. Valve defective, not allowing
refrigerant to circulate through
condenser.
14
a. Replace valve.
a. Find and repair leak if present.
Recover refrigerant and weigh in proper
charge.
b. Replace valve.
a. Replace valve.
Pump Down System
A pump-down system consists of a normally closed solenoid valve installed in the liquid line and a lowpressure control that senses suction pressure.
The system operation is as follows: A thermostat is wired to the liquid line solenoid valve. On a call for cooling,
the thermostat contacts close. This causes the solenoid coil to be energized, opening the valve. Liquid
refrigerant flows into the evaporator and the suction pressure rises above the low-pressure control setpoint. The
contacts on the low-pressure control close and the compressor begins to run.
When the thermostat is satisfied, its contacts open, causing the solenoid valve to close. This stops refrigerant
flow into the evaporator. As the compressor continues to run, refrigerant is pumped out of the evaporator coil
and suction pressure falls. When the suction pressure reaches the cut-out setting on the low-pressure control, its
contacts open, stopping the compressor. This removes most of the refrigerant from the low side of the system
and prevents liquid migrating to the compressor crankcase during the off-cycle and the ensuing possibility of
liquid slugging at compressor startup
.
15
CABINET ELECTRICAL WIRING
Step 1: Ensure proper voltage input, minimum 210VAC 60Hz maximum 253VAC 60Hz.
If voltage is below the 210VAC or above 253VAC, a BUCK and BOOST transformer is required.
Step 2: Remove the lower-rear and left-side compressor access panel.
Step 3: Remove the left-side junction-box panel and locate the electrical wiring diagram on
the inside of the panel.
Step 4: Install permanently connected field wiring to the 230V/ 60Hz/ 1 Phase (4-wire) compressor circuit.
The pigtail wires are provided. See the circuit amperage ratings located on the unit nameplate.
SHELF & ACCESSORY INSTALLATION
16
START-UP & OPERATING INFORMATION
START-UP INFORMATION AND PERFORMANCE EVALUATION
Step 1: Open the front panel and flip the toggle switch to the “ON” position for both left and right side unit.
Both the condensing unit, and the evaporator fans should operate, and the fluorescent lighting should
turn on.
Step 2: While the condensing unit and evaporator fans are running, verify that there is a flow of cold air from
the honeycomb, at the top of the cabinet for each left and right side unit.
Step 3: Observing the controller in the upper-left corner, monitor the cabinet temperature, and verify that both
left and right side unit cools to 40°F within 20-30 minutes.
Step 4: Continue to monitor temperature performance through the complete run cycle, until the system enters
the defrost cycle. The defrost cycle (condensing unit shutdown) is programmed to run for 10 ~ 30
minutes every two hours.
Step 5: Verify that all unit access-cover panels have been replaced, and the cabinet is ready to be loaded by
store personnel.
OPERATING GUIDELINES
1. For best results, pre-cool all products before stocking the display case.
2. Stock products only after the cabinet has cooled.
3. When loading the cabinet, do not place merchandise outside of the shaded area.
4. Allow at least 1” between the upper surface of the displayed product and the shelf directly above it.
5. Do not overload product. Improper loading of merchandise may result in refrigeration inefficiency.
6. Do not remove the glass side panels during operation.
7. Do not stock the shelves with all bottles or cans. Heavy merchandise should not be loaded on the glass
shelves.
17
COOLING AIRFLOW PATTERN
18
GENERAL MAINTENANCE
CLEANING THE HONEYCOMB
In order to maintain peak operating performance, remove the honeycomb (as shown below) and rinse it with
clean water to remove dust. Under normal conditions, inspect and clean every 30 days.
CLEANING THE BOTTOM OF THE INNER BOX & DRAIN
Lift the fan duct, as shown below, and clean the bottom of the inner box with a mild detergent and a soft, damp
cloth. Check the drain hole for proper water flow and remove any blockage. Rinse with clean water.
CLEANING THE CABINET
To clean the cabinet and shelves, use a mild detergent and a soft, damp cloth. Rinse with clean water. Do not
use paint thinner, laundry detergent, or harsh chemicals.
LIGHTING
Power must be turned OFF prior to servicing fluorescent bulbs. Failure to switch power OFF will
damage the ballast.
Replace inoperable fluorescent lights.
19
PRECAUTIONS
CAUTION: Do not operate the unit with the access panels removed.
STORING THE CABINET
Step 1: Disconnect the unit from its power source.
Step 1: Wipe the interior of the cabinet with a damp cloth.
Step 1: Polish the interior of the cabinet with a dry cloth.
Step 1: Store the unit in a clean, dry place. Do not choose a location where the unit will be exposed to direct
sunlight, high temperature, or high humidity.
TROUBLE SHOOTING
Before calling your serviceman, please make these simple checks:
If the unit is not operating:
1. Is the cabinet plugged in?
2. Is there a main-power failure?
3. Is there a blown fuse?
4. Has the refrigeration unit cycled off, because it is at the designated operating temperature?
If the fluorescent light is off:
1. Is the fluorescent-light tube properly connected to the socket?
2. Does the fluorescent light need to be changed?
If the cabinet temperature is too warm:
1. Is the thermostat set correctly?
2. Is the cabinet located in direct sunlight?
3. Is the cabinet located in a strong air-flow path?
4. Is the distance between the upper surface of the displayed merchandise and the shelf directly above it at
least 1”?
5. Is the air temperature around the cabinet above 75°F?
Reasons for high pressure trips:
1. Overcharge or Non-condensable.
2. Dirty condenser.
3. TXV sensor bulb loose or power head defective.
4. TXV sensor bulb poorly insulated.
REFER TO THE ENVIRONMENTAL CONSIDERATIONS, ON PAGES 5 THROUGH 9,
THAT WILL AFFECT COOLING PERFORMANCE.
20
Wiring Diagram RD Remote
IMPORTANT: When using a Heatcraft Flexpack, connect the condenser fan motor wires shown above
to the relay dedicated for the RD refrigerated showcase.
21
Wiring Diagram (buck and boost model number Square D 500SV43B)
Measure line voltage; if line voltage is less than 210V, use buck and boost per instructions below.
1. Connect line voltage supply (LV) side to H1 and H4/X1 terminal.
2. Measure output voltage between terminals H1 and X4. Do not connect to unit if voltage exceeds
253V.
3. Connect load side or unit side to H1 and X4 terminals.
22
Warranty Activation
Form No.: QF-PE-0047-C
Date Issued: 4/20/2010
PART NUMBER: 1189633A
Document Name:
To activate the warranty for this machine the following information must be returned to
SandenVendo's Customer Service Department within 5 days of Installation
<Contact Information> FAX : 1-800-561-5684 or e-mail : customerservice@vendoco.com
CustomerStore Addres s :
Store No. & Store Name
Date of Installation :Installer's Name
RD8 Warranty Activation and Checklist
Model Name :
Serial No. :Cabinet :Remote Condenser :
Asset Management No. : Cabinet :Remote Condenser :
ShockWatch State (Color)at Rear :
RD2 RD-8 (Self Contain) RD3 RD-8 REMOTE
at Front :
Installation: Manuals can be obtained at www.vendoco.com (http://www.vendoco.com/Documents.aspx?ID=8)
Check Items
Inspect for damages on cabinet.
1
When you joined the two halves together, did you follow the