Net Safety Monitoring ST3 XChems Operating Manual

Page 1
Reference Manual
XChem Electrochemical Sensors
Part Number: MAN-0132, rev. 10
Release: April 2016
Page 2
Page 3
Important Instructions
Installing, operating or maintaining a Net Safety Product improperly could lead to serious injury or death from explosion or exposure to dangerous substances. Comply with all information on the product, in this manual, and in any local and national codes that apply to the product. Do not allow untrained personnel to work with this product. Use Net Safety parts and work procedures specified in this manual.
Net Safety Monitoring, Inc (Net Safety) designs, manufactures and tests products to function within specific conditions. Because these products are sophisticated technical instruments, it is important that the owner and operation personnel must strictly adhere both to the information printed on the product nameplate and to all instructions provided in this manual prior to installation, operation, and maintenance.
Page 4
Notice
The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not to be construed as warranties or guarantees, expressed or implied, regarding the products or services described herein or their use or applicability. All sales are governed by Net Safety’s terms and conditions, which are available upon request. We reserve the right to modify or improve the designs or specifications of such products at any time.
Net Safety does not assume responsibility for the selection, use or maintenance of any product. Responsibility for proper selection, use and maintenance of any Net Safety products remains solely with the purchaser and end user.
To the best of Net Safety’s knowledge the information herein is complete and accurate. Net Safety makes no warranties, expressed or implied, including implied warranties of merchantability and fitness for a particular purpose with respect to this manual and, in no event, shall Net Safety be liable for any incidental, punitive, special or consequential damages including, but not limited to, loss of production, loss of profits, loss of revenue or use and costs incurred including without limitation for capital, fuel and power, and claims of third parties.
Product names used herein are for manufacturer or supplier identification only and may be trademarks/registered trademarks of these companies.
Net Safety and the Net Safety logo are registered trademarks of Net Safety Monitoring, Inc. The Emerson logo is a trademark and service mark of the Emerson Electric Company.
Copyright © 2016 by Rosemount, Shakopee, MN
All rights reserved. No part of this work may be reproduced or copied in any form or by any means - graphic, electronic, or mechanical without first receiving written permission of Rosemount, Shakopee, MN
Page 5
Warranty
Limited Warranty
Resale Products
Limitation of Remedy and Liability
1.
and Liability) herein, Seller warrants that (a) the licensed firmware embodied in the Goods will execute the programming instructions provided by Seller; (b) that the Goods manufactured by Seller will be free from defects in materials or workmanship under normal use and care; and (c) Services will be performed by trained personnel using proper equipment and instrumentation for the particular Service provided. The foregoing warranties will apply until the expiration of the applicable warranty period. Sensors and detectors are warranted against defective parts and workmanship as per Section to Buyer ( Buyer agrees that Seller has no liability for Resale Products beyond making a reasonable commercial effort to arrange for procurement and shipping of the Resale Products. If Buyer discovers any warranty defects and notifies Seller thereof in writing during the applicable warranty period, Seller shall, at its option, (i) correct any errors that are found by Seller in the firmware or Services; (ii) repair or replace FOB point of manufacture that portion of the Goods found by Seller to be defective; or (iii) refund the purchase price of the defective portion of the Goods/Services. All replacements or repairs necessitated by inadequate maintenance; normal wear and usage; unsuitable power sources or environmental conditions; accident; misuse; improper installation; modification; repair; use of unauthorized replacement parts; storage or handling; or any other cause not the fault of Seller, are not covered by this limited warranty and shall be replaced or repaired at Buyer’s sole expense and Seller shall not be obligated to pay any costs or charges incurred by Buyer or any other party except as may be agreed upon in writing in advance by Seller. All costs of dismantling, reinstallation, freight and the time and expenses of Seller’s personnel and representatives for site travel and diagnosis under this limited warranty clause shall be borne by Buyer unless accepted in writing by Seller. Goods repaired and parts replaced by Seller during the warranty period shall be in warranty for the remainder of the original warranty period or 90 days, whichever is longer. This limited warranty is the only warranty made by Seller and can be amended only in a writing signed by an authorized representative of Seller. The limited warranty herein ceases to be effective if Buyer fails to operate and use the Goods sold hereunder in a safe and reasonable manner and in accordance with any written instructions from the manufacturers. THE WARRANTIES AND REMEDIES SET FORTH ABOVE ARE EXCLUSIVE. THERE ARE NO REPRESENTATIONS OR WARRANTIES OF ANY KIND, EXPRESS OR IMPLIED, AS TO MERCHANTABILITY, FITNESS FOR PARTICULAR PURPOSE OR ANY OTHER MATTER WITH RESPECT TO ANY OF THE GOODS OR SERVICES.
. Subject to the limitations contained in Section 10 (Limitation of Remedy
7.4. Products purchased by Seller from a third party for resale
) shall carry only the warranty extended by the original manufacturer.
2.
DELAY IN PERFORMANCE. THE REMEDIES OF BUYER SET FORTH IN THE AGREEMENT ARE EXCLUSIVE. IN NO EVENT, REGARDLESS OF THE FORM OF THE CLAIM OR CAUSE OF ACTION (WHETHER BASED IN CONTRACT, INFRINGEMENT, NEGLIGENCE, STRICT LIABILITY, OTHER TORT OR OTHERWISE), SHALL SELLER’S LIABILITY TO BUYER AND/OR BUYER’S CUSTOMERS EXCEED THE PRICE TO BUYER OF THE SPECIFIC GOODS MANUFACTURED OR SERVICES PROVIDED BY SELLER GIVING RISE TO THE CLAIM OR CAUSE OF ACTION. BUYER AGREES THAT IN NO EVENT SHALL SELLER’S LIABILITY TO BUYER AND/OR BUYER’S CUSTOMERS EXTEND TO INCLUDE INCIDENTAL, CONSEQUENTIAL OR PUNITIVE DAMAGES. THE TERM “CONSEQUENTIAL DAMAGES” SHALL INCLUDE, BUT NOT BE LIMITED TO, LOSS OF ANTICIPATED PROFITS, REVENUE OR USE AND COSTS INCURRED INCLUDING WITHOUT LIMITATION FOR CAPITAL, FUEL AND POWER, AND CLAIMS OF BUYER’S CUSTOMERS.
. SELLER SHALL NOT BE LIABLE FOR DAMAGES CAUSED BY
Page 6
Page 7
Reference Manual Table of Contents
Table of Contents I
Section 1 : Introduction ............................................................................................... 1
Section 2 : Installation ................................................................................................. 2
Section 3 : Operation ................................................................................................. 10
Section 4 : Maintenance ............................................................................................ 13
Section 5 : Electrostatic sensitive device ..................................................................... 17
Section 6 : Wire resistance table ................................................................................ 18
Section 7 : Specifications ........................................................................................... 19
MAN-0132, Revision 10 April 2016
Contents
1.1 Models covered .................................................................................................................. 1
1.2 Service support ................................................................................................................... 1
1.3 Return of material............................................................................................................... 1
1.4 Product recycling/disposal .................................................................................................. 1
2.1 Unpacking and inspection .................................................................................................. 2
2.2 Locate sensor ..................................................................................................................... 2
2.3 Sensor direct mount or sensor separation ........................................................................... 2
2.3.1 Sensor direct mount ............................................................................................. 2
2.3.2 Sensor separation ................................................................................................. 2
2.4 Dimensions ........................................................................................................................ 4
2.5 Mounting ........................................................................................................................... 5
2.6 Wiring ................................................................................................................................ 6
2.6.1 Field installation .................................................................................................... 6
2.6.2 Sensor separation distance ................................................................................... 7
2.6.3 Installation to transmitter or junction box ............................................................. 7
2.6.4 Sensor wiring ........................................................................................................ 7
2.6.5 External ground .................................................................................................... 8
2.7 Calibration .......................................................................................................................... 9
2.8 Installation checklist ........................................................................................................... 9
3.1 Sensor configuration settings ........................................................................................... 10
3.2 Sensor power up ............................................................................................................... 10
3.3 Sensor end of life diagnostic ............................................................................................. 10
3.4 Sensor communication ..................................................................................................... 11
3.5 Net Safety Millennium II Basic transmitter configuration ................................................... 11
3.5.1 Hydrogen sulfide sensor (ST320) ........................................................................ 12
3.5.2 Carbon monoxide sensor (ST360) ....................................................................... 12
3.6 Fault conditions ................................................................................................................ 12
4.1 Cross sensitivities ............................................................................................................. 13
4.1.1 Hydrogen sulfide sensor (ST320) ........................................................................ 13
4.1.2 Carbon monoxide sensor (ST360) ....................................................................... 14
4.2 Bump testing .................................................................................................................... 14
4.3 Sensor replacement procedure ......................................................................................... 14
4.4 Troubleshooting ............................................................................................................... 16
4.5 Storage ............................................................................................................................ 16
4.6 Spare parts and accessories .............................................................................................. 16
7.1 Performance ..................................................................................................................... 19
7.1.1 Response time .................................................................................................... 19
7.1.2 Accuracy ............................................................................................................. 19
7.1.3 Zero Drift ............................................................................................................ 19
Page 8
Reference Manual
II Table of Contents
Section 8 : Certifications ............................................................................................ 22
Section 9 : Ordering information ................................................................................ 23
April 2016 MAN-0132, Revision 10
7.1.4 Repeatability ...................................................................................................... 19
7.1.5 Detection Range ................................................................................................. 19
7.1.6 Calibration Frequency ......................................................................................... 20
7.1.7 Unpowered storage time .................................................................................... 20
7.2 Environmental .................................................................................................................. 20
7.2.1 Storage temperature .......................................................................................... 20
7.2.2 Operating temperature ...................................................................................... 20
7.2.3 Relative humidity ................................................................................................ 20
7.2.4 Metallurgy (housing) .......................................................................................... 20
7.2.5 Ingress protection ............................................................................................... 20
7.2.6 Weight ............................................................................................................... 20
7.3 Electrical ........................................................................................................................... 21
7.3.1 Voltage ............................................................................................................... 21
7.3.2 Power Consumption ........................................................................................... 21
7.4 Separation ........................................................................................................................ 21
7.5 Warranty .......................................................................................................................... 21
8.1 North America .................................................................................................................. 22
8.2 IECEx ................................................................................................................................ 22
8.3 EMI/EMC ........................................................................................................................... 22
Page 9
Reference Manual
1
MAN-0132, Revision 10 April 2016

Section 1: Introduction

1.1 Models covered

The Net Safety XChem electrochemical toxic gas sensors are designed specifically for use with the Net Safety Millennium II Transmitter (models M21, M22, or M2B). This sensor is both versatile and reliable for fast, accurate, and continuous monitoring of gases in extreme environments.
The sensor assembly consists of a factory sealed explosion proof enclosure (housing) rated for hazardous locations and a replaceable sensor module. This sensor must only be used with a Net Safety Millennium II series transmitter. If the sensor is connected to any other model of transmitter, it will not function and may result in the sensor or transmitter being damaged.

1.2 Service support

Technical support for this product can be provided by contacting your local Emerson Process Management/Net Safety representative or by contacting the Net Safety Technical Support department at +1 866 347 3427 or safety.csc@emerson.com
.

1.3 Return of material

To expedite the repair and return of this product, proper communication between the customer and the factory is important. Before returning a product for repair, call +1866 347 3427 or e-mail
safety.csc@emerson.com
On the return of the equipment, include the following information:
1. RMA number provided to you by Net Safety
2. Company name and contact information
3. Ship all equipment, prepaid to:
Rosemount 6021 Innovation Blvd. Shakopee, MN 55379
4. Mark all packages with the RMA number and type of return (e.g. return for evaluation).
Pack items to protect them from damage and use anti-static bags or aluminum-backed cardboard as protection from electrostatic damage.
All equipment must be shipped prepaid. Collect shipments will not be accepted.
for a Return Material Authorization (RMA) number.

1.4 Product recycling/disposal

Recycling of equipment and packaging should be taken into consideration and disposed of in accordance with local and national legislations/regulations.
Page 10
Reference Manual
2
April 2016 MAN-0132, Revision 10

Section 2: Installation

2.1 Unpacking and inspection

Carefully remove all of the components from the packaging and verify them against the enclosed packing list. Inspect all components for any obvious damage such as broken or loose parts. If you find any components missing or damaged, notify your local Net Safety representative or the factory immediately.
Recycling of packaging should be taken into consideration and disposed of in accordance with local and national legislations/regulations.

2.2 Locate sensor

Prior to installing the sensor, a plan should be developed for placement of the sensor. Although there are no absolute rules for determining the quantity of detectors or location of a sensor, the following points should be considered when planning the installation.
Carefully locate the sensor in an area where gases may potentially accumulate, considering that
light gases tend to rise and heavy gases tend to fall and accumulate in low areas.
Use redundant systems to enhance protection and reliability.
Consider air movement patterns in the facility.
Consider the construction of the facility such as trenches where heavy gases or peaks where light
gases may accumulate.
Seek advice from experts knowledgeable about the gas to be detected.
Refer to the regulatory publications that discuss guidelines for your industry.

2.3 Sensor direct mount or sensor separation

2.3.1 Sensor direct mount

The sensor can be directly attached to a Net Safety Millennium II transmitter and placed in an appropriate location for detecting the target gas, or the sensor can be separated and remotely mounted away from the Net Safety Millennium II transmitter. The sensor should be accessible for calibration and maintenance purposes. The transmitter should be located where it is accessible and visible.

2.3.2 Sensor separation

If the sensor is to be remotely mounted from the transmitter, the sensor must be connected to a certified junction box. In this case, the transmitter is typically located near eye-level for easy access and the sensor is mounted where the gas is likely to accumulate.
In order to ease the calibration process a calibration cup (CCS-1) can be attached to the bottom of the sensor housing and calibration tubing run from the calibration cup to a convenient place for applying the calibration gas, eliminating the need to access the sensor directly. In this case, to compensate for the effect of distance, consider decreasing the calibration tubing length to some length where the end of the tubing to the gas canister is still accessible or increase the calibration gas flow rate between the
Page 11
Reference Manual
3
Figure 2-1 Sensor separation example
MAN-0132, Revision 10 April 2016
calibration gas cylinder and sensor. Refer to Figure 2-1 for an example of the sensor separation. For tubing lengths less than 10 feet (3 meters), use a 0.5 LPM regulator and for lengths greater than 10 feet (3 meters) use a 1.0 LPM regulator. On initial install, always confirm readings directly at the transmitter by applying a known gas concentration to the sensor and compare the output from the transmitter. Readings should be accurate to the gas concentration applied taking into account the sensor accuracy specifications in Section 7.1.2.
Page 12
Reference Manual
4
Figure 2-2 Net Safety Millennium II (M21 or M22) enclosure and sensor dimensions
A B C D E F G H
April 2016 MAN-0132, Revision 10

2.4 Dimensions

The following tables outline the dimensions of the sensor when connected to either the Net Safety Millennium II Transmitter (Figure 2-2) or the Net Safety Millennium II Basic Transmitter/Junction Box (Figure 2-3). Both the transmitter and sensor enclosures are offered in stainless steel and aluminum.
in mm in mm in mm in mm in mm in mm in mm in mm
Stainless Steel 5.9 150 5.1 130 4.6 117 8.9 226 6.0 152 5.8 147 2.6 66 2.9 74
Aluminum 6.3 160 5.6 142 5.4 137 9.7 246 6.0 152 5.7 145 2.6 66 2.9 74
Page 13
Reference Manual
5
Figure 2-3 Net Safety Millennium II Basic (M2B) or junction box (JB) enclosure and sensor dimensions
A B C D E F G H I J
MAN-0132, Revision 10 April 2016
in mm in mm in mm in mm in mm in mm in mm In mm in mm in mm
Stainless Steel
Aluminum 4.8 122 3.6 91 3.6 91 4.8 122 5.1 130 0.3 7.6 2.6 66 2.9 74 3.0 76 9.0 229
4.7 119 3.6 91 3.6 91 4.7 119 5.1 130 0.3 7.6 2.6 66 2.9 74 2.8 71 8.9 226

2.5 Mounting

Prior to mounting the sensor to the transmitter or junction box enclosure apply suitable grease (jet lube, etc.) to the threading of the 3/4” FNPT (female NPT) conduit entry of the enclosure as well as the threading on the sensor 3/4” MNPT (male NPT) fitting. This aids in protecting the enclosures from water ingress. After the grease has been applied properly, fit and tighten the sensor to the transmitter or junction box enclosure by using appropriate tools.
The transmitter and junction box have mounting holes to allow mounting to a flat surface or pole as desired. Mounting kit accessories are available to aid in mounting the detector to a flat surface or a pole. Contact your local Net Safety representative for detailed information.
The sensor must always be mounted vertically such that its mouth is pointed in the downward position as shown in Figure 2-4.
Page 14
Reference Manual
6
Figure 2-4 Net Safety XChem Sensor mounted to Net Safety Millennium II series transmitters
Failure to follow these installation guidelines could result in death or serious injury. Ensure that only qualified personnel perform the installation.
Electrical shock could cause death or serious injury. Use extreme caution when making contact with the leads and terminals.
Do not open the transmitter, sensor, or junction box enclosure when in a classified area or when an explosive atmosphere may be present unless the power to the transmitter and sensor has been removed.
April 2016 MAN-0132, Revision 10
Net Safety Millennium II
Sensor mouth

2.6 Wiring

Transmitter
3/4” NPT
3/4” NPT
ATEX locking collar
Sensor pointing downwards
Net Safety Millennium II Basic
Transmitter &
Junction Box
Sensor pointing downwards
3/4” NPT
3/4” NPT
ATEX locking collar
Sensor mouth

2.6.1 Field installation

Wiring codes and regulations may vary. Wiring must comply with all applicable regulations relating to the installation of electrical equipment in a hazardous area and is the responsibility of the installer. If in doubt, consult a qualified official before wiring the system.
When separating the sensor from the transmitter, the use of shielded cable is highly recommended to protect against interference caused by extraneous electrical or electromagnetic noise. To meet EN50270:2006 requirements follow the recommendations on cable choice and guidelines as outlined in the Net Safety Millennium II Transmitter manual (MAN-0076) or Net Safety Millennium II Basic transmitter manual (MAN-0082). In applications where the wiring is installed in conduit, the conduit must not be used for wiring to other equipment.
Page 15
Reference Manual
7
Do not open the transmitter, sensor, or junction box enclosure when in a classified area or when an explosive atmosphere may be present unless the power to the sensor has been removed.
Figure 2-5 Terminal connection
Table 2-1 Sensor wire colors and terminal definition
Wire color
Marking
Function
MAN-0132, Revision 10 April 2016

2.6.2 Sensor separation distance

The maximum separation distance between the sensor and the transmitter is limited by the resistance of the connecting wiring, which is a function of the gauge of the wire being used. Net Safety recommends that sensor separation must not exceed 2000 feet (610 meters) while using 16AWG (1.31mm
2
) wire. Refer to Section 6 for wire gauges and resistance values.

2.6.3 Installation to transmitter or junction box

The Net Safety XChem sensor is supplied with a 3/4” NPT male conduit connection and is intended to be mounted directly to an available 3/4” NPT conduit entry on a Net Safety Millennium II Transmitter or remotely using a certified junction box. Net Safety has an available offering of certified junction boxes designed specifically to work with this sensor. Please contact your local Net Safety representative for further information.

2.6.4 Sensor wiring

When connecting cable wires, use a small flathead screwdriver to gently press down and hold the spring connector open. Insert the appropriate wire into the open connector hole, releasing the screwdriver to secure the wire. Refer to Figure 2-5 below.
Connect the sensor wires to the Net Safety Millennium II Transmitter or junction box as per the appropriate transmitter or junction box manual. Figure 2-6 outlines the connections to a M21 Net Safety Millennium II transmitter. Table 2-1 outlines the wire colors and their purpose.
White Red Blue Black Green
+Vdc Sig A Sig B COM
10.5-32Vdc Connection
Communication
signal A
Communication
signal B
Common / supply
ground
Earth ground
Page 16
Reference Manual
8
Figure 2-6 Net Safety Millennium II M21 sensor wiring
Figure 2-7 External grounding point
April 2016 MAN-0132, Revision 10

2.6.5 External ground

In order to ensure proper operation of the sensor, an external ground is required. Net Safety recommends that the external ground be connected to the grounding point on the enclosure according to IECEx requirements. Refer to Figure 2-7 for grounding connection location.
External Earth Ground point
Page 17
Reference Manual
9
MAN-0132, Revision 10 April 2016

2.7 Calibration

The Net Safety XChem sensor should be powered up for at least twenty-four (24) hours prior to completing the first calibration.
Although the sensor has been factory calibrated, this calibration may have been disrupted after shipment and calibration after installation is necessary to ensure performance.
Calibration cycles are recommended to be completed every three (3) months to ensure the proper operation of the sensor.
Refer to the respective Net Safety Millennium II transmitter manual (MAN-0076 or MAN-0082) for the calibration procedure.

2.8 Installation checklist

Review the following checklist prior to turning the power on to the sensor after installation has been completed:
Ensure that the transmitter and sensor are properly and firmly mounted Ensure that stopping plugs are securely tightened on any unused conduit entries Ensure that the transmitter and sensor are not obstructed such that they are accessible and the
target gas is not inhibited from reaching the sensor
Remove the red protective plastic cap/cover from the sensor mouth If IP filters are fitted to the sensor, check for any damage or debris If calibration cups or splash guards are fitted to the sensor, ensure that they are properly fitted Ensure adherence to applicable local guidelines and requirements on wiring and sealing of
equipment in hazardous and non-hazardous areas
Ensure that proper shielding and grounding practices are adhered to and local codes are being
followed
Check system operational voltage and conditions and ensure that they are within the applicable
specifications of the sensor
Verify wiring at all termination and junction points (transmitter, junction box, and power supply) If the sensor housing has been opened, ensure that the sensor module is properly seated and
making a good connection. Refer to Section 4.3 for more details.
Perform initial calibration as per Section 2.7.
Page 18
Reference Manual
10
Tip
Refer to the relevant transmitter manual prior to attempting a
Figure 3-1 Net Safety Millennium II display examples
April 2016 MAN-0132, Revision 10

Section 3: Operation

3.1 Sensor configuration settings

All configuration settings for the Net Safety XChem sensor are accessed through the Net Safety Millennium II series of transmitters. When using the Net Safety Millennium II Transmitter, configuration settings are accessed by selecting menu options through the main display.
calibration.

3.2 Sensor power up

When power is applied to the sensor by the transmitter, a warm-up routine will begin where the sensor will automatically be tested to ensure its proper operation. The warm-up time for the Net Safety XChem sensor is typically between thirty (30) and ninety (90) seconds depending on the sensor type; the ST341 oxygen sensor could take up to an hour to warm-up. During the warm-up period, the Net Safety XChem sensor may not provide accurate results and gas concentration levels may fluctuate during the warm-up period. Refer to the Net Safety Millennium II transmitter manual (MAN-0076) or the Net Safety Millennium II Basic transmitter manual (MAN-0082) for status indicators during this period. Confirm that the Net Safety Millennium II transmitter display properly shows ppm on the display as shown in Figure 3-1. If the display reads xxx, then the sensor cell is not seated properly in the sensor housing. Refer to Section 4.3 for more information.

3.3 Sensor end of life diagnostic

An automatic test of the sensor will be performed daily to ensure the sensor’s integrity. This test will be completed one (1) hour after initial power-up and then every twenty four (24) hours following that.
Note that sensor end of life indication is not available on the Oxygen (ST340 or ST341) sensors.
During the test cycle, a period of ten (10) seconds, it is expected that the sensor response time will increase to less than sixty (60) seconds.
If a sensor end of life indication fault is generated, the analog output of the associated transmitter will be 2.5mA (fault condition) for a period of ten (10) seconds. The analog output will then return to its
Page 19
Reference Manual
11
MAN-0132, Revision 10 April 2016
operational state (4mA with no gas present) for a period of fifty (50) seconds. This cycle will continue until the sensor has been replaced. When using the M21 or M22 transmitter, the display will read “Sensor Reached Life End” on the respective channel and the gas concentration will not be shown.
If used with a Net Safety Millennium II transmitter with relay capabilities, the sensor end of life diagnostic will be indicated through the fault relay. The fault relay will change states (de-energize, indicating a fault condition, upon the detection of the end of life condition. The fault relay will stay de­energized as long as the fault condition is present. When the sensor has detected an end of life condition, the alarm relay will not provide an alarm condition if gas is present, therefore, it is recommended that the sensor be replaced as quickly as possible. For further information on the operation of the relays, please refer to the associated transmitter manual (MAN-0076 or MAN-0082).
Net Safety Monitoring recommends that if a fire and gas system or other control system is used, that the fault signal (2.5mA) and fault relay (if available) are monitored to indicate sensor faults.
Due to the electrochemical sensor technology used in the Net Safety XChem sensors, the sensor end of life diagnostic may indicate a sensor with decaying response or a non-responding sensor. It is recommended that the sensor be replaced when this fault message is indicated.
Please contact Net Safety Monitoring for replacement sensor modules.

3.4 Sensor communication

The Net Safety XChem sensor uses a proprietary protocol to communicate with the Net Safety Millennium II series of transmitters. This sensor should never be connected to any device other than the Net Safety Millennium II series of transmitters. Selected DIP switches and menu options allow communication between the transmitter and sensor. Configuration settings are stored in the memory of the sensor. Incorrect settings will cause the sensor to not communicate properly with the transmitter. If any problems develop, please refer to the troubleshooting section (4.4) of this manual.
3.5 Net Safety Millennium II Basic transmitter
configuration
When using the Net Safety XChem electrochemical toxic sensor with the Net Safety Millennium II Basic Digital transmitter model (M2B-D), the sensor’s range can be changed by accessing a specific Modbus register. The user should write to register 40027 using the preset single register command 0x06. The desired range can then be entered in the register. Refer to 7.1.5 for the available ranges.
When using the Net Safety XChem electrochemical toxic sensor with the Net Safety Millennium II Basic Analog (M2B-A), Analog/HART (M2B-AH), and Relay (M2B-R) transmitter models the sensor’s range can be changed to facilitate the need to accurately detect different gas concentrations. This is done by making use of the transmitter’s DIP Switch 2 positions as seen in the tables below. Select the transmitter’s DIP Switch 2 position that gives the range of gas to be detected.
Page 20
Reference Manual
12
Table 3-1 Net Safety Millennium II Basic transmitter DIP switch 2 positions for the ST320 sensor
Position 1
Position 2
Position 3
Position 4
Range(Setting)
ON
OFF
OFF
OFF
Range 1 (20ppm)
OFF
ON
OFF
OFF
Range 2 (50ppm)
OFF
OFF
ON
OFF
Range 3 (100ppm)
Table 3-2 Net Safety Millennium II Basic transmitter DIP switch 2 positions for the ST360 sensor
Position 1
Position 2
Position 3
Position 4
Range(Setting)
ON
OFF
OFF
OFF
Range 1 (500ppm)
OFF
ON
OFF
OFF
Range 2 (1000ppm)
Fault condition
Analog output
Fault relay output
April 2016 MAN-0132, Revision 10

3.5.1 Hydrogen sulfide sensor (ST320)

3.5.2 Carbon monoxide sensor (ST360)

3.6 Fault conditions

The Net Safety XChem sensor will provide a number of fault conditions that the Net Safety Millennium II transmitter will translate into an analog or fault relay output. These fault conditions are outlined in the following table.
Sensor zero drift 2.5mA Fault
Memory fault 2.5mA Fault
Sensor nearing end of life Alternating 2.5mA for ten (10)
Calibrate Sensor 2.5mA Fault
seconds and normal level fifty (50) seconds
Alternating 2.5mA for ten (10) seconds and normal level fifty (50) seconds
Page 21
Reference Manual
13
noted that some cross interference break through will occur if gas is applied for a longer period of time.
Table 4-1 List of cross sensitive gases/compounds
Cross sensitive gas
Cross sensitive gas concentration
Reading
MAN-0132, Revision 10 April 2016

Section 4: Maintenance

4.1 Cross sensitivities

This relates to the fact that certain compounds and or gases can cause a reaction and hence some effects or response from the sensor. See the tables below for a list of these cross sensitive gases/compounds. For more information, please contact Net Safety.
The values listed below are typical values and should not be used as a basis for cross calibration. Cross sensitivities may not be linear and should not be scaled either. The data provided is based on gassing for a minimum of five (5) minutes using the gas sensor manufacturers test equipment. It should be

4.1.1 Hydrogen sulfide sensor (ST320)

Carbon monoxide 300 ppm <3 ppm
Sulfur dioxide 5 ppm <1 ppm
Nitrogen dioxide 5 ppm <± 0.5ppm
Nitric oxide 50 ppm <1 ppm
Hydrogen 100 ppm <1 ppm
Chlorine 1 ppm 0 ppm
Ethylene 100 ppm 0 ppm
Carbon dioxide 5000 ppm 0 ppm
Page 22
Reference Manual
14
Table 4-2 List of cross sensitive gases/compounds
Cross sensitive gas
Cross sensitive gas concentration
Reading
Do not open the transmitter, sensor, or junction box enclosure when in a classified area or when an explosive atmosphere may be present unless the power to the sensor has been removed.
Avoid touching any electronic components, as they may be susceptible to electrostatic discharge (ESD). Refer to Section 5 for further information and proper handling instructions of electronic components.
April 2016 MAN-0132, Revision 10

4.1.2 Carbon monoxide sensor (ST360)

Hydrogen sulfide 15 ppm < 0.1 ppm
Sulfur dioxide 5 ppm 0 ppm
Nitrogen dioxide 5 ppm -0.5ppm
Nitric oxide 35 ppm <7 ppm
Hydrogen 100 ppm <60 ppm
Chlorine 1 ppm 0 ppm
Ethylene 100 ppm <90 ppm

4.2 Bump testing

As part of the site preventative maintenance program Net Safety recommends that a bump test of the sensor is completed every three (3) months. Bump testing consists of a visual inspection of the sensor, applying a known gas concentration to the sensor verifying the accuracy of the response to the specifications of the sensor, and alarm system simulation. If the response is outside of the specifications of the sensor a calibration should be completed. Refer to Section 2.7 for more information. After a calibration has been completed, it is recommended that a bump test be completed to verify accuracy and response of the sensor.

4.3 Sensor replacement procedure

Sensors are pre-calibrated at the factory; however, field calibration must be performed as a part of commissioning. When the sensor end of life diagnostic is indicating a fault condition, a calibration can no longer be performed, or the sensor is not operating properly, the sensor module may need to be replaced. Refer to steps below for replacing the sensor module.
1. Remove power from the sensor.
2. Remove the locking ring by loosening the set screws with 1.5 mm Allen Key tool.
3. Remove the bottom part of the sensor enclosure by turning it in a counter clockwise rotation to
expose the sensor module.
Page 23
Reference Manual
15
MAN-0132, Revision 10 April 2016
4. Carefully remove the sensor module from the sensor housing by pulling the module straight out of
the housing. NOTE: DO NOT TWIST THE SENSOR MODULE.
5. Properly dispose of the old sensor module as per local guidelines and regulations.
6. Remove the replacement sensor module from its packaging ensuring not to touch any electronic
components as this may cause problems due to an unwanted electrostatic discharge (ESD).
7. Rotate replacement sensor module until it aligns with the guide posts. Once aligned, press firmly
into place.
8. Install and hand-tighten the bottom part of the sensor enclosure by turning it in a clockwise
direction.
9. Install the locking ring by tightening the set screws with 1.5 mm Allen Key tool.
10. Restore power to sensor via the transmitter.
11. Verify that the display shows ppm and not xxx as shown in Figure 3-1. If the display is showing xxx,
then the sensor module is not seated properly. In this case, repeat all steps within this procedure.
Page 24
Reference Manual
16
Description
Part Number
April 2016 MAN-0132, Revision 10

4.4 Troubleshooting

Sensors and transmitters are not designed to be repaired in the field. If problems should develop, first check for faulty wiring, confirm proper voltage to sensor, and attempt a calibration. If problems persist, please contact Net Safety’s technical support department first by phone to try and resolve any issues. If issues cannot be resolved, please follow the procedure in Section 1.3 Return of material.

4.5 Storage

The sensor and its electronic components/parts should be stored in locations free from dust, liquid spills, contaminants, and moisture. The storage temperature should be well within the limits of the certified temperatures of the equipment. See Section 7 for certified temperatures.

4.6 Spare parts and accessories

Calibration cup/splash guard CCS-1
Calibration Kit CAL-KIT-1
Calibration Gas CAL-CYL-AIR (103L Air)
CAL-CYL-H2S-10 (58L, 10ppm, H CAL-CYL-H2S-25 (76L, 25ppm, H CAL-CYL-H2S-50 (76L, 50ppm, H CAL-CYL-H2S-A-10 (58L, 10ppm, H CAL-CYL-H2S-A-25 (58L, 25ppm, H CAL-CYL-H2S-A-50 (58L, 50ppm, H
CAL-CYL-CO-250 (103L, 250ppm, CO)
Calibration cup CCS-1
Separation kit JB-MPD-A - aluminum
JB-MPD-S - stainless steel
Replacement sensor module ST320-100 (H2S)
ST341-25 (O
)
2
ST360-1000 (CO)
Ingress protection filter IPF-001
2” Pole mounting kit UN-MK-32
Duct mounting kit UDM-001 (1m sampling pipe)
UDM-002 (1.5m sampling pipe) UDM-003 (direct mount to duct)
S, nitrogen balanced)
2
S, nitrogen balanced)
2
S, nitrogen balanced)
2
S, oxygen balanced)
2
S, oxygen balanced)
2
S, oxygen balanced)
2
Page 25
Reference Manual
17
MAN-0132, Revision 10 April 2016

Section 5: Electrostatic sensitive device

Definition: Electrostatic discharge (ESD) is the transfer, between bodies, of an electrostatic charge caused by direct contact or induced by an electrostatic field.
The most common cause of ESD is physical contact. Touching an object can cause a discharge of electrostatic energy (ESD). If the charge is sufficient and occurs near electronic components, it can damage or destroy those components. In some cases, damage is instantaneous and an immediate malfunction occurs. However, symptoms are not always immediate—performance may be marginal or seemingly normal for an indefinite period of time, followed by a sudden failure.
To eliminate potential ESD damage, review the following guidelines:
Handle boards by metal shields—taking care not to touch electronic components.
Wear grounded wrist or foot straps, ESD shoes or heel grounders to dissipate unwanted static
energy.
Prior to handling boards, dispel any charge in your body or equipment.
Ensure all components are transported and stored in static safe packaging
When returning boards, carefully package in the original carton and static protective wrapping
Ensure ALL personnel are educated and trained in ESD Control Procedures
In general, exercise accepted and proven precautions normally observed when handling electrostatic sensitive devices. A warning label is placed on the packaging, identifying product using electrostatic sensitive semiconductor devices.
Page 26
Reference Manual
18
Distance Feet (Meters)
AWG #20
0.5mm
2
AWG #18
0.8mm
2
AWG #16
1.0mm
2
AWG #14
2.0mm
2
April 2016 MAN-0132, Revision 10

Section 6: Wire resistance table

100 (30.5) 1.02 0.64 0.40 0.25
200 (61) 2.03 1.28 0.80 0.51
300 (91.4) 3.05 1.92 1.20 0.76
400 (121.9) 4.06 2.55 1.61 1.01
500 (152.4) 5.08 3.20 2.01 1.26
600 (182.9) 6.09 3.83 2.41 1.52
700 (213.4) 7.11 4.47 2.81 1.77
800 (243.8) 8.12 5.11 3.21 2.02
900 (274.3) 9.14 5.75 3.61 2.27
1000 (304.8) 10.20 6.39 4.02 2.53
1250 (381) 12.70 7.99 5.03 3.16
1500 (457.2) 15.20 9.58 6.02 3.79
1750 (533.4) 17.80 11.20 7.03 4.42
2000 (609.6) 20.30 12.80 8.03 5.05
2250 (685.8) 22.80 14.40 9.03 5.68
2500 (762) 25.40 16.00 10.00 6.31
3000 (914.4) 30.50 19.20 12.00 7.58
3500 (1066.8) 35.50 22.40 14.10 8.84
4000 (1219.2) 40.60 25.50 16.10 10.00
4500 (1371.6) 45.70 28.70 18.10 11.40
5000 (1524) 50.10 32.00 20.10 12.60
5500 (1676.4) 55.80 35.10 22.10 13.91
6000 (1828.8) 61.00 38.30 24.10 15.20
6500 (1981.2) 66.00 41.50 26.10 16.40
7000 (2133.6) 71.10 44.70 28.10 17.70
7500 (2286) 76.10 47.90 30.10 19.00
8000 (2438.4) 81.20 51.10 23.10 20.20
9000 (2743.2) 91.40 57.50 36.10 22.70
10000 (3048) 102.00 63.90 40.20 25.30 Resistance shown is one way. This figure must be doubled when determining closed loop resistance.
Page 27
Reference Manual
19
Hydrogen Sulfide (ST320)
Carbon Monoxide (ST360)
Oxygen (ST341)
T20
T50
T90
Hydrogen Sulfide (ST320)
Carbon Monoxide (ST360)
Oxygen (ST341)
Hydrogen Sulfide (ST320)
Carbon Monoxide (ST360)
Oxygen (ST341)
Hydrogen Sulfide (ST320)
Carbon Monoxide (ST360)
Oxygen (ST341)
Hydrogen Sulfide (ST320)
Carbon Monoxide (ST360)
Oxygen (ST341)
MAN-0132, Revision 10 April 2016

Section 7: Specifications

7.1 Performance

7.1.1 Response time

10 sec 10 sec 7 sec
15 sec 15 sec 10 sec
36 sec 30 sec 20 sec

7.1.2 Accuracy

0°C to +50°C (+32°F to +122°F)
±6 ppm or 17% of reading, whichever is greater
-40°C to 0°C (-40°F to +32°F) ±7 ppm or 27% of reading, whichever is greater
0°C to +50°C (+32°F to +122°F)
±13 ppm or 5% of reading, whichever is greater
-20°C to 0°C (-4°F to +32°F) ±32 ppm or 17% of reading, whichever is greater

7.1.3 Zero Drift

<5% full scale per year <5% full scale per year <5% full scale per year

7.1.4 Repeatability

<3% full scale <3% full scale <3% full scale

7.1.5 Detection Range

0°C to +50°C (+32°F to +122°F)
± 0.5% Vol.
-20°C to 0°C (-4°F to +32°F) ± 1.5% Vol.
20 ppm 50 ppm 100 ppm
500 ppm 1000 ppm
25% Vol.
Page 28
Reference Manual
20
Hydrogen Sulfide (ST320)
Carbon Monoxide (ST360)
Oxygen (ST341)
Hydrogen Sulfide (ST320)
Carbon Monoxide (ST360)
Oxygen (ST341)
Hydrogen Sulfide (ST320)
Carbon Monoxide (ST360)
Oxygen (ST341)
April 2016 MAN-0132, Revision 10

7.1.6 Calibration Frequency

Three (3) months

7.1.7 Unpowered storage time

Six (6) months

7.2 Environmental

7.2.1 Storage temperature

+3°C to +20°C (+37°F to +68°F)
+3°C to +20°C (+37°F to +68°F)

7.2.2 Operating temperature

-40°C to +50°C (-40°F to +122°F)
-20°C to +50°C (-4°F to +122°F)

7.2.3 Relative humidity

15-90% relative humidity, non­condensing
15-90% relative humidity, non­condensing

7.2.4 Metallurgy (housing)

316 Stainless steel and 6061 anodized aluminum.
0°C to +20°C (+32°F to +68°F)
-20°C to +50°C (-4°F to +122°F)
15-99% relative humidity, non­condensing

7.2.5 Ingress protection

7.2.6 Weight

IP64
Stainless steel: 3.5 lbs, 1.4 kg Aluminum: 1 lb, 0.4 kg
Page 29
Reference Manual
21
Hydrogen Sulfide (ST320)
Carbon Monoxide (ST360)
Oxygen (ST341)
MAN-0132, Revision 10 April 2016

7.3 Electrical

7.3.1 Voltage

10.5 to 32 Vdc

7.3.2 Power Consumption

Peak inrush 667 mA (16.0 W) at 24 Vdc 655 mA (15.7 W) at 24 Vdc 685 mA (16.4 W) at 24 Vdc
Operational 13 mA (0.3 W) at 24 Vdc 13 mA (0.3 W) at 24 Vdc 13 mA (0.3 W) at 24 Vdc

7.4 Separation

Up to 2000 feet (610 meters) with 16AWG (1.31mm2) wire.

7.5 Warranty

2 years
Page 30
Reference Manual
22
April 2016 MAN-0132, Revision 10

Section 8: Certifications

8.1 North America

Class I Division 1 Groups B,C D T5 Ex d IIB+ H Class I Zone 1 AEx d IIB +H
-40°C ≤ Ta + 75°C (sensor dependent) IP 64

8.2 IECEx

II 2G Ex d IIB+H2 T5 Gb
-40°C ≤ Ta + 75°C (sensor dependent) IP64 IECEx CSA 11.0006
T5
2
2
T5

8.3 EMI/EMC

EN 50270:2006
Page 31
Reference Manual
23
MAN-0132, Revision 10 April 2016

Section 9: Ordering information

Model Description
ST Electrochemical toxic gas sensor compatible with all Net Safety Millennium II Transmitters
Type Performance
320 Hydrogen Sulfide (H2S), 0-20/50/100ppm, Field Selectable
341 Oxygen (O2), 0-25%
360 Carbon Monoxide (CO), 0-500/1000ppm, Field Selectable
Housing Enclosure Material
A Aluminum
S Stainless Steel
Range Sensor Range (Type Specific)
-100-ASSY ST320 and ST330 Only
-1000-ASSY ST360 Only
-25-ASSY ST341 Only
Page 32
Americas
Europe
EmersonProcess.com/FlameGasDetection
Emerson Process Management
6021 Innovation Blvd. Shakopee, MN 55379 T +1 866 347 3427 F +1 952 949 7001
Safety.CSC@Emerson.com
AnalyticExpert.com
MAN-0132
Revision 10
April 2016
Emerson Process Management AG
Neuhofstrasse 19a P.O. Box 1046 CH-6340 Baar Switzerland T + 41 (0) 41 768 6111 F + 41 (0) 41 768 6300
Safety.CSC@Emerson.com
Middle East & Africa Emerson Process Management
Emerson FZE Jebel Ali Free Zone Dubai, UAE P.O. Box 17033 T + 971 4 811 8100 F + 971 4 886 5465
Safety.CSC@Emerson.com
Twitter.com/Rosemount_News
Facebook.com/Rosemount
Youtube.com/user/RosemountAnalytical
©2016 Emerson Process Management. All rights reserved.
Emerson Process Management, Rosemount Analytical, and Net Safety are marks of Emerson Process Management group of companies. All other marks are the property of their respective owners.
The contents of this publication are presented for information purposes only, and while effort has been made to ensure their accuracy, they are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. All sales are governed by our terms and conditions, which are available on request. We reserve the right to modify or improve the designs or specifications of our products at any time without notice.
Loading...