Net Safety Monitoring SC311 Specifications

SC311 Infrared Combustible Gas Sensor
FGD-PDS-SC311-Infrared-Combustible-Gas-Sensor
Product Data Sheet
SC311 Infrared Combustible Gas Sensors
Millennium II Series Sensors
The SC311 delivers the latest technology advancements in infrared sensing of flammable gases in a rugged package designed for the most extreme industrial environments. Hydrocarbon gas LEL detection is fast, reliable and highly accurate with only periodic bump testing recommended and a simple annual calibration sequence. A full 5 year warranty is included with a typical sensor life of 8–10 years.
July 2016
 Lowest power consumption available  Long range (+2,000 ft.) sensor separation  Industry leading 5 year sensor warranty  Field selectable gas curves available  Immune to poisoning - standard gases detected
include methane, propane, butane, and ethylene
Single or Dual Channel Transmitter Available
There’s no longer the need to purchase multiple gas speci c
detectors. You have the option to utilize 1 or 2 toxic and/or combustible gas sensors on a single Millennium II transmitter and easily mix and match any of our sensor technologies.
Sensor Designed for Durability & Performance
High resolution, dual-beam optics are employed in the sensor
design which eliminates refl ective surfaces preventing fouling,
fogging or misalignment. Not only does this provide enhanced overall performance but it also means low power consumption which equals cost savings and more reliable coverage.
ST3 Sensors shown with JB-MPD-A/S.
 Very fast response and highly accurate  Designed to perform in the most extreme
industrial environments
Failsafe Operation & Advanced Diagnostics
Continuous self-check for several performance parameters as well as environmental compensation for temperature, pressure and humidity maintains a high level of sensor performance and reliability.
SC311 Infrared Combustible Gas Sensor
Specifications
Table 1 - SC311 Infrared Combustible Gas Sensor
Hydrocarbon Combustible Gases [% LEL] Infrared
P/N: SC311(A/S)-100-ASSY
Performance
Response Time T50 ≤ 4.3 s
T60 ≤ 7 s T90 ≤ 11 s
Accuracy ±5 % LEL
0—100 % LEL
Detection Range
Zero Drift < 5 % full scale per year
Repeatability ±2 % LEL full scale
Electromagnetic Compatibility (EMC) IEC 61000-4-3
Environmental
Temperature -40 °F to +167 °F (-40 °C to +75 °C)
Relative Humidity 0–95 % RH non condensing
Ingress Protection (IP) Rating IP64
Enclosure
Enclosure Material Aluminum (AL6061) or stainless steel (SS316)
Certifications North American
Gases Detected*: Methane, Propane, n-Butane, Iso-Pentane, n-Pentane, Ethane, Iso-Butane, Ethylene, Hexane (Field Selectable Curves) *other gases available - contact factory
Class I, Division 1, Groups BCD T5 Class I, Zone 1, AEx/Ex d IIB +H2 T5
-40 °C ≤Ta ≤+75 °C
IECEx Ex d IIB+H2 T5 Gb
IECEx FMG 12.0007X
INMETRO
Ex d IIB+H2 T4 Gb IP66/67
July 2016
Sensor Separation Up to 2,000 feet/600 meters (18 AWG cabling)
Transmitter Required Millennium II Series (M21, M22, M2B)
Warranty Five years
2 EmersonProcess.com/FlameGasDetection
July 2016
Aluminum Housings 6.3 160 5.6 142 5.4 137 9.7 246 6.0 152
Stainless Steel Housings 5.9 150 5.1 130 4.6 117 8.9 226 6.0 152
Aluminum Housings 5.7 145 2.6 66 2.9 74 4.1 103
Stainless Steel Housings 5.8 147 2.6 66 2.9 74 3.9 100
SC311 Infrared Combustible Gas Sensor
Accessories and Ordering Information
Table 2 - SC311 Infrared Combustible Gas Sensor
JB-MPD-A Termination Box - Digital Output - Stainless Steel
JB-MPD-S Termination Box - Digital Output - Stainless Steel
CCS-1 Calibration Cup/Rain Shield/Splash Guard/Dust Filter with DF-1
CC-INLINE Inline Calibration Adaptor, allows slip stream of gas to be brought to sensor and vented back into main stream
Table 3 - Ordering Information
SC311A-100-ASSY (Aluminum Housing) Hydrocarbon based Combustible Gases, 0–100 % LEL
SC311S-100-ASSY (Stainless Steel Housing) Hydrocarbon based Combustible Gases, 0–100% LEL
Drawings and Dimensions
* Aluminum Shown
A B C D E
Aluminum Housings 6.3 160 5.6 142 5.4 137 9.7 246 6.0 152
Stainless Steel Housings 5.9 150 5.1 130 4.6 117 8.9 226 6.0 152
F G H I
Aluminum Housings 5.7 145 2.6 66 2.9 74 4.1 103
Stainless Steel Housings 5.8 147 2.6 66 2.9 74 3.9 100
3EmersonProcess.com/FlameGasDetection
SC311 Infrared Combustible Gas Sensor
FGD-PDS-SC311-Infrared-Combustible-Gas-Sensor
EmersonProcess.com/FlameGasDetection
Product Data Sheet
July 2016
YouTube.com/user/RosemountAnalytical
Twitter.com/Rosemount_News
Americas Emerson Process Management
6021 Innovation Blvd.
Shakopee, MN 55379
USA
T + 1 866 347 3427 F + 1 952 949 7001
Safety.CSC@Emerson.com
Europe Emerson Process Management AG
Neuhofstrasse 19a P.O. Box 1046 CH-6340 Baar
Switzerland
T + 41 (0) 41 768 6111 F + 41 (0) 41 768 6300
Safety.CSC@Emerson.com
©2016 Emerson Process Management. All rights reserved.
The Emerson logo is a trademark and service mark of Emerson Electric Co. Rosemount and the Rosemount logotype are registered trademarks of Rosemount Inc. All other marks are the property of their respective owners.
The contents of this publication are presented for information purposes only, and while effort has been made to ensure their accuracy, they are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. All sales are governed by our terms and conditions, which are available on
request. We reserve the right to modify or improve the designs or specications of our products
at any time without notice.
Analyticexpert.com
Facebook.com/Rosemount
Middle East & Asia Emerson Process Management
Emerson FZE Jebel Ali Free Zone Dubai, UAE
P.O. Box 17033 T + 971 4 811 8100 F + 971 4 886 5465
Safety.CSC@Emerson.com
Asia Pacific Emerson Process Management
1 Pandan Crescent
Singapore 128461
Singapore
T + 65 777 8211 F + 65 777 0947
Safety.CSC@Emerson.com
Loading...