Net Safety Monitoring M2B Operating Manual

Reference Manual
Millennium II Basic Transmitter
Part Number: MAN-0082, rev. 08
Release: June 2016
Installing, operating or maintaining a Net Safety Product improperly could lead to serious injury or death from explosion or exposure to dangerous substances. Comply with all information on the product, in this manual, and in any local and national codes that apply to the product. Do not allow untrained per sonnel to work with this product. U se Net Safety part s and work procedur e s specified in this manual.
Net Safety Monitoring, Inc (Net Safety) designs, manufactures and test s pr o d ucts to function within specific conditio ns. Be c ause these products ar e sophisticated technical instrumen ts, i t is important that the owner and operation personnel must strictly adhere both to the information printed on the product nameplate and to all instructions provided in this manual prior to installation, operation, and maintenance.
Notice
The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure t heir accuracy, they are not to be construed as warranties or guarant e e s, expressed or implied, regarding the products or services described herein or their use or applicability.
All sales are governed by Net Safety’s terms and conditions, which are available upon request. We
reserve the right to modify or improve the designs or specifications of such products at any time . Net Safety does not assume responsibility for the selection, use or maintenance of any product.
Responsibility for proper selection, use and maintenance of any Net Safety products remains solely with the purchaser and end-user.
To the best of Net Safety’s knowledge the information herein is complete and accurate. Net Safety makes no warranties, expressed or implied, including implied warranties of merchantability and fitness for a particular purpo se wi th respect to this manu al an d, in no event, shall Net Safety be liable for any incidental, punitive, special or consequential damages including, but not limited to, loss of production, loss of profits, loss of revenue or use and costs incurred including without limitation for capital, fuel and power, and claims o f third parties.
Product names used herein are for manufacturer or supplier identification only and may be trademarks/registered trademarks of these companies.
Net Safety and the Net Saf ety logo are reg i ste r e d t r ade marks of Net Safety Monitoring, Inc. The Emerson logo is a trademark and service mar k o f the Emerson Electric Company.
Copyright © 2016 by R o se mount, Shakopee, M N .
All rights reserved. No part of this work may be reproduced or copied in any form or by any means - graphic, electronic, or mechanical without first re c e iving written pe rmission of Rosemount, Sha k opee, MN.
Warranty
Limited Warranty
Resale Products
Limitation of Remedy and Liability
1. and Liability) herei n, Se l l e r warrants that (a) the licensed firmware embodied in the Goods will execute the programming instructions provided by Seller; (b) that the Goods manufactured by Seller will be free from defects in materials or workmanship under normal us e and ca re; and (c) Services will be performed by trained personnel using proper equipment and instrumentation for the particular Service provided. The foregoing warranties will apply until the expiration of the applicable warranty period. Sensors and d et ectors are warrante d ag ainst defectiv e parts and workmanship for 24 m onths from the date of pur chase and other electr onic assemblies fo r 36 months from the date of purchase. Products purchased by Seller from a third party for resale to Buyer ( manufacturer. Buyer ag r e es that Seller has no liab ility for Resale Products b e y o n d making a reasonable commercial effort to arrange for procurement and shipping of the Resale Products. If Buyer discovers any warranty defects and no t i fies Seller thereof in writing during the applicable warranty period, Seller shall, at its option, (i) correct any errors that are found by Seller in the firmware or Services; (ii) repair or replace FOB point of manufacture that portion of the Goods found by Seller to be defective; or (iii) refund the purchase price of the defective portion of the Goods/Services. All replacements or repairs necessitated by inadequate maintenance; normal we ar and usage; unsuitable power sources or environmental c o nditions; accident; misuse; improper installation; modification; repair; use of unauthorized replacement parts; storage or handl i n g; or any other cause not the f ault of Seller, are not covered by this limited warranty and shall be replaced or repaired at Buyer’s sole expense and Seller s hal l not be obligated to pay any costs or charges incurred by Buyer or any other party except as may be agreed upon in writing in advance by Seller. All costs of dismantling, reinstallation, freight and the time and expenses of Seller’s per so nn el and representativ e s for site travel and dia g no sis under this limited warranty clause shall be borne by Buyer unless accepted in writing by Seller. Goods repaired and p ar ts r eplaced by Seller d ur i n g t he warranty period shal l be in warranty for the remainder of the original warranty period or 90 days, whichever is longer. This limited warranty is the only warranty made by Selle r and c an b e amended only in a wr i ting signed by an authorized representative of Seller. The li mited warranty herein ceases to be effective i f Buyer fails to operate and use the Goods sold hereunde r i n a safe and reasonable manner and in accordance with any wr i t ten instructions from t he m anufacturers. THE WARRANTIES AND REMEDIES SET FORTH ABOVE ARE EXCLUSIVE. THERE ARE NO REPRESENTATIONS OR WARRANTIES OF ANY KIND, EXP R ESS OR IMPLIED, AS TO MERCHAN T ABILITY, FITNESS FOR PARTICULAR PURPOSE OR ANY OTHER MATTER WITH RESPEC T TO ANY OF THE GOODS OR SERVICES.
. Subject to the limitations contained in Section 10 (Limitation of Remedy
) shall carry only the warr an ty e xtended by the original
2. DELAY IN PERFORMANCE. T HE REM EDIES OF BUYER SET FORTH IN T HE AGREEMENT ARE EXCLUSIVE. IN NO EVENT, REGARDLESS OF THE FORM OF T HE C LAI M OR C AUSE OF ACTION (WHETHER BASED IN CONTRACT, INFRINGEMENT, NEGLIGENC E, STRIC T L IABILITY, OTHER TORT OR OTHERWISE), SHALL SELLER’S LIABILITY TO BUYER AND/OR BUYER’S CUSTOMERS EXCEED THE PRICE TO BUYER OF THE SPECIFIC GOODS M AN UF AC TURED OR SERVICES PROVIDED BY SELLER GIVING RISE TO THE CLAIM OR CAUSE OF ACTION. BUYER AGREES THAT
IN NO EVENT SHALL SELLER’S LIABILITY TO BUYER AND/OR BUYER’S CUSTOMERS EXTEND TO
INCLUDE INCIDENTAL, CONSEQUENTIAL OR PUNITI VE DAMAGES. THE TERM
“CONSEQUENTIAL DAMAGES” SHALL INCLUDE, BUT NOT BE LIMITED TO, LOSS OF
ANTICIPATED PROFITS, R EVENUE OR USE AND COSTS INC UR R ED I N C L UDI NG WITHOUT LIMITATION FOR CAPITAL, FUEL AND POWER, AND CLAIMS OF BUYER’S CUSTOMERS.
. SELLER SHALL NOT BE LIABLE FOR DAMAGES CAUSED BY
Reference Manual Table of Contents
Table of Contents i
MAN-0082, Revisio n 08 June 2016
Contents
Section 1: Introduction ...................................................................... 1
1.1 Models covered ................................................................................................................... 1
1.2 Service support ................................................................................................................... 1
1.3 Return of material ............................................................................................................... 1
1.4 Product recycling/disposal .................................................................................................. 1
Section 2: Installation ........................................................................ 2
2.1 Unpacking and inspection ................................................................................................... 2
2.2 Dimensions ......................................................................................................................... 2
2.3 Mounting ............................................................................................................................ 2
2.4 Wiring ................................................................................................................................. 3
2.4.1 Gener al requi rements ........................................................................................... 3
2.4.2 Terminal connection ............................................................................................. 3
2.4.3 Cable choice and guidelines .................................................................................. 4
2.4.4 Important wiring guidelines .................................................................................. 4
2.4.5 Exter nal ground .................................................................................................... 5
2.4.6 Seals ..................................................................................................................... 5
2.4.7 Analog output, isolated supply, non-isolated supply and jumper configuration ..... 5
2.5 Wiring drawings .................................................................................................................. 7
2.6 Remote mounting of sensor ................................................................................................ 8
2.6.1 Wiring drawings for remote sensor wiring ............................................................. 9
2.7 Installation checklist .......................................................................................................... 10
Section 3: Operation ........................................................................ 11
3.1 Transmitter and faceplate description ............................................................................... 11
3.2 Intrusive access ................................................................................................................. 11
3.3 Non-intrusive access (magnetic Reed switch Access) ......................................................... 11
Section 4: Output configurations ..................................................... 13
4.1 Analog board assembly ..................................................................................................... 13
4.2 Analog/HART board assembly ........................................................................................... 14
4.3 Relay board assembly/configuration ................................................................................. 15
4.4 Digital board assembly/configuration................................................................................ 16
Section 5: Operation ........................................................................ 17
5.1 DIP switch settings ............................................................................................................ 17
5.1.1 Infr ar e d sensor (SC311) gas cur ve selection ........................................................ 17
5.1.2 Hydro gen sulfide sensor (ST320) range selection ................................................ 17
5.1.3 C ar b on monoxide sensor (ST360) range selection ............................................... 18
5.1.4 DIP switch settings for relay configuration .......................................................... 18
5.1.5 Digital Modbus DIP switch settings ..................................................................... 19
5.1.6 Anal o g and analog/HART DIP switch se tti ngs ...................................................... 20
Section 6: Calibration procedure ...................................................... 21
6.1 Calibration procedure ....................................................................................................... 21
6.1.1 Guidelines........................................................................................................... 21
6.1.2 Full calibration procedure ................................................................................... 21
6.2 Zeroing procedure ............................................................................................................ 22
6.3 Status conditions during calibration .................................................................................. 24
6.4 Calibration failures ............................................................................................................ 24
6.5 Manual reset ..................................................................................................................... 24
Table of Contents Reference Manual
ii Table of Contents
June 2016 MAN-0082, Re vision 08
Section 7: Monitoring and outputs .................................................. 25
7.1 Analog 4-20mA ................................................................................................................. 25
7.2 HART Communication (Optional) ...................................................................................... 25
7.2.1 HART Menu Structure ......................................................................................... 25
7.3 Relays (Optional) ............................................................................................................... 28
7.3.1 Al ar m r e l ay s ........................................................................................................ 28
7.3.2 F aul t r e l ay ........................................................................................................... 28
7.4 RS-485 Modbus RTU (Optio nal) ......................................................................................... 28
7.4.1 Mo dbus registers ................................................................................................ 29
7.5 Transmitter output operation............................................................................................ 30
7.6 Fault monitoring ............................................................................................................... 31
7.7 Fault conditions ................................................................................................................ 31
7.7.1 Transmitter fault conditions ................................................................................ 31
7.7.2 Sensor fault conditions ....................................................................................... 32
Section 8: Maintenance ................................................................... 33
8.1 Periodic response check .................................................................................................... 33
8.2 Troubleshooting ............................................................................................................... 33
8.3 Storage ............................................................................................................................. 33
8.4 Spare parts and accessories ............................................................................................... 34
Section 9: Electrostatic sensitive device ........................................... 35
Section 10: Wire resistance table ....................................................... 36
Section 11: Specifications .................................................................. 37
11.1 Electrical ........................................................................................................................... 37
11.1.1 Operating voltage range ..................................................................................... 37
11.1.2 Power consumption ............................................................................................ 37
11.1.3 EMC compliance ................................................................................................. 37
11.2 Environmental................................................................................................................... 37
11.2.1 Operating temperature ...................................................................................... 37
11.2.2 Relative humidity ................................................................................................ 37
11.2.3 Ingress protection ............................................................................................... 37
11.3 Mechanical ........................................................................................................................ 37
11.3.1 Enclosure material .............................................................................................. 37
11.3.2 Conduit opening ................................................................................................. 37
11.3.3 Weight ............................................................................................................... 37
11.4 Warranty ........................................................................................................................... 38
Section 12: Certifications ................................................................... 39
12.1 North American................................................................................................................. 39
12.2 IECEx ................................................................................................................................. 39
12.3 FC Models ......................................................................................................................... 39
12.3.1 North America .................................................................................................... 39
12.3.2 IECEx .................................................................................................................. 39
Section 13: Ordering information ...................................................... 40
Reference Manual Introduction
Introduction 1
Rosemount 6021 Innovation Boulevard Shakopee, MN 55379
RMA number
MAN-0082, Revisio n 08 June 2016

Section 1: Introduction

1.1 Models covered

A Millennium II Basic gas detectio n system is composed of a field mounted transmitter and Millennium II series sensors whi c h m ay be integrally mounted to the transmitter or remotely mounted.
The transmitter is cer tified for use in hazardous locations and i s available as a single sensor system. Some operator controls including calibration can be accessed without opening the enclosure (housing) by using other commu nication devices and the attached magnet t o ac tuate the reed switch. Available outputs are: conventional 4 to 20 mA analog, Analog/HART, electromechanical relays, or Modbus RTU digital.

1.2 Service support

Technical support for this product can be provided by contacting your local Emerson Process Management representative or by contacting the Technical Support department at +1 866 347 342 7 (toll free) or Safety.CSC@Emerson.com

1.3 Return of material

To expedite the return of this product, prope r c o mmuni cation between the customer and the factor y i s important. Before returning a product, call +1 866 347 3427 (tol l f r ee ) o r e -mail
Safety.CSC@Emerson.com
On the return of the equipment, include the following information:
1. RMA number provided to you by Rosemount
2. Company name and contact information
3. Ship all equipment, prepaid to:
4. Mark all packages wit h the Pack items to protect them from damage and use anti-stati c b ag s o r aluminum-backed cardboard as
protection from electrostatic damage.
All equipment must be shipped prepaid. C o l lec t shipment s wil l not be accepted.
for a Return Material Authorization (RMA) number.
.
and type of return (e.g. return for evaluation)

1.4 Product recycling/disposal

Recycling of equipment and packaging should be taken into consideration and disposed of in accordance with local and national legislations/regulations.
Installation Reference Manual
2 Installation
Figure 2-1 Dimensions
A B C D E F G
in
mm
in
mm
in
mm
in
mm
in
mm
in
mm
in
mm
Transmitter (AL)
4.8
122
3.6
91
3.6
91
4.8
122
5.1
130
0.3
7.6
3.0
76
Transmitter (SS)
4.7
119
3.6
91
3.6
91
4.7
119
5.1
130
0.3
7.6
3.2
81
June 2016 MAN-0082, Re vision 08

Section 2: Installation

2.1 Unpacking and inspection

Carefully remove all of the components from the packaging and verify t hem against the enclo sed packing list. Inspect all components for any obvious damage such as broken or loose parts. If you find any components missing or damaged, notify your local Net Safet y r ep r e sentative or the factory immediately.

2.2 Dimensions

The Millennium II Basic transmitter enclosur e i s available in alumi num (6061) and stainle ss steel (SS316). Dimensions ar e p rovided in Figure 2-1 below.

2.3 Mounting

Ensure transmitter and sensor are securely mounted as per local regulations. The transmitter has mounting holes to allow mounting to a wall or pole as desired. Mounting kit hardware is required when mounting the transmitter a pole. Contact your local Net Safety representative for detailed information on the pole mounting kits. The transmitter should be mounted at eye-level and be easily accessible for monitoring and maintenance purposes.
Reference Manual Installation
Installation 3
Failure to follow these installation guidelines could result in death or serious injury. Ensure that only qualified personnel perform the installation.
Electrical shock could cause death or serious injury. Use extreme caution when making contact with the leads and terminals.
Do not open the transmitter, sensor, or junction box enclosure when in a classified area or when an explosive at mosphere may be present unless the p ower to the transmitter has been removed.
Wiring codes and regulations may vary. Wi r ing the installation of electrical equipment in a hazardous area and is the responsibility of the installer. If in doubt, consult a qualified official before wiring the system.
When separating the se nsor meet electromagnetic compatibility (EMC) requirements and to pro tect against interference caused by extraneous electrical or electromagnetic noise the conduit must not be used for wiring to other equipment.
MAN-0082, Revisio n 08 June 2016

2.4 Wiring

2.4.1 General requirements

must comply with all applicable regulations relating to
from the transmitter, the use of shielded cable is highly recommended to
If the 4-20 mA signal is not used, c o nnect a jumper between the 4 – 20 mA terminal and the common terminal to allow analog current levels to be monitored at the test jacks on the transmitter board.
In applications where wiring is installed in conduit, conduit must not be used for wiring to any other electrical equipment.
For effective comm uni c ation, Net Safety li m i t s sensor separation to 2000 f eet (600 meters) using 16 AWG wires.
Modbus RS-485 connection 2-wire mode, multipoint serial line available. Up to 16 addresses allowed. When developing a RS-485 chain of devices, the last devi c e i n t he c hai n r eq uires an end of line termination resisto r (120 Ohms).

2.4.2 Terminal co n nection

When connecting cable wir es, use a small screwdri v e r to gently press down and ho l d the spring connector open. Insert the appropriate wire into the open connector hole, releasing the screwdriver to secure the wire as shown in Figure 2-2.
. In applications where the wiring is installed in conduit,
The connector will ac c o m modate wire sizes be tween 14 and 20 AWG.
Installation Reference Manual
4 Installation
Figure 2-2 Terminal connection
June 2016 MAN-0082, Re vision 08

2.4.3 Cable choice and guidelines

Radio frequency interference (RFI) can be caused by near by el ectri cal dev i ces (e.g. transformers or high voltage equipment) as well as handheld co m m unication devic e s/rad i os, which when activated, may impede the proper functioning of the transmitter and sensor. Selecting the right instrumentation cable and making proper grounding connections within the junction box will reduce or eliminate interference. Visible symptoms of RFI include inconsistent, incorrect, and erratic LEL and ppm readings.

2.4.4 Important wiring guidelines

Gas detection instruments are an impor tan t p art of a safety alarm and shutdown system. T he sy ste m is composed of:
Detection instruments
Customer connected equipment
Wiring
Net Safety designs and manufactures its detection equipment under rigid q ual i ty c o ntr o l m anagement systems and makes every effort to design fo r the har shest of industrial environments. T he other components of the system – the customer-connected equipment and wiring – are also important contributors to the overall quality and performance of the safety system.
It is important to implement wiring that ensures the reliability and integrity of the safety system. Field wiring practices and the choice of cable type specified vary from project to project. Poor practices and choices are often fou nd to be the source of unwante d system disruptions. RFI and electromagnetic interference (EMI) are usually very powerful disruptive fo rces in i ndustrial facil iti es a nd these forces act upon the system thro ug h the wiring.
The cable used should be a very high quality instrument grade, certified for the application conditions, consisting of a rugged protective outer jacket, an overall electrical shield of fine braided copper or metallic foil, and internal pairs or triads of foil shielded copper wire of suitable gauge for the power conducted over the specified length.
The shields must be electrically continuous from the instrument junction box through other junction boxes and finally to the connected equipment. The shield must be connected to a suitable g r o u nd si nk as specified in the instrument manual in order to protect the system from electrical disturbances.
In general, communication cables and power cables should not run in parallel for any significant length, and should not be carr ied i n the same cable tray. Through inductance, high currents i n power cables can induce significant ‘noise’ in communication cables running parallel alongside power cables.
Reference Manual Installation
Installation 5
MAN-0082, Revisio n 08 June 2016

2.4.5 External ground

In order to ensure proper operation of the sensor, an external earth grou nd is recommended. Net Safety recommends that the external gro und b e co nnected to the grounding point on the enclosure.

2.4.6 Seals

The use of seals is recommended to further pr o te ct the system against water ingression , and equipment should be installed according to applicable local electrical codes. Seals are especi ally recommended for installations that use hi gh-pressure or steam cleaning devices in proximity to the transmitter.
Waterproof and explosionproof conduit seals are recommended to prevent water accumulation
within the enclosure
Seals should be locat ed as c lose to the device as possible and not more than18 inches (46 cm) a way
Explosionproof installations may require an additional seal where conduit enters a non-hazardous
area; ensure conformity with local wiring codes
When pouring a seal, u se a fiber dam to ensure proper formation of the seal. Seals should never be
poured at temperatures below freezing
The jacket and shielding of the cable should be stripped back to permit the seal to form around the
individual wires. This will prevent air particles and water leakage through the inside of the shield and into the enclosure
It is recommended that explosionproof drains and conduit breathers be used. In some applications,
changes in temperatur e and barometric pressure can cause breat hing which allows mo i st ai r to enter and circulate inside the conduit. Joints in the conduit system are seldom tight enough to prevent this breathin g

2.4.7 Analog output, isolated supply, non-isolated supply and jumper configuration

The analog output may be powered from the main instrument power supply or a separate, independent power supply in which case an isolated wiring configuration is necessary. These configurations only apply to Analog and Analog/HART model transmitters.
To set a non-isolated or isolated current output, simply move the jumper/shorting jack located at JP1 near the power and output terminals, to either the non-isolated or isolated current position. For non­isolated current out p ut, e nsure pins 3 and 2 at JP1 l o cation on the terminal board are jumpered (shorted). See Figure 2-3 for reference. F ac tory standard models ship with jumper in t he n o n -isolated current output position.
For isolated current output, pins 1 and 2 at JP1 should be jumpered (shorted). See Figure 2-3 for reference.
Installation Reference Manual
6 Installation
Figure 2-3 Non-isolated and isolated current jumpers
Always ensure that JP configuration chosen
Non-isolated current output
Isolated current output configuration.
June 2016 MAN-0082, Re vision 08
configuration (default).
1 jumpers are in the correct po si ti on depending on the current outp ut
Pin 1 and Pin 2 jumpered at JP1
Reference Manual Installation
Installation 7
Figure 2-4 Non-isolated terminal connection (for Analog and Analog/HART models)
Figure 2-5 Isolated terminal connection (for Analog and Analog/HART models)
MAN-0082, Revisio n 08 June 2016

2.5 Wiring drawings

The drawings below are general ways in wiring the system showing analog signal output. Consult qualified personnel on specific wiring requirements.
Installation Reference Manual
8 Installation
Figure 2-6 Remote mounting of sensor
June 2016 MAN-0082, Re vision 08

2.6 Remote mounting of sensor

When necessary to mo unt sensor remotely ( sep arated from transmitter) by way of junction box and conduit, it is important that the installer follow the necessary requirements and guidelines relating to sensor separation a nd c able selection. See Figure 2-6 for typical remote mounting of the sensor.
When sensors are bein g m ounted remotely, co nsult the multi-purp o se junction box manual (MAN-0081) for wiring instructions. Alway s e nsure that the transmitter is supplying 10.5 - 32 VDC across the sensor po we r te rminals of Net Safety junction box (JB-MPD-A/S).
The maximum distan ce b etween the sensor and tr ansmitter is limi ted b y the r e si stance of the connecting wiring, which is a function of the gauge of the wire being used. For effective communication, Net Safety limits the separation distance between senso r and tr ansmitter to 2000 feet (600 meters) using 16 AWG wire. See Section 10 for information on wire gauge and resistance.
Reference Manual Installation
Installation 9
Figure 2-7 Non-isolated terminal wiring with remote sensor wiring (for Analog and Analog/HART models)
Figure 2-8 Isolated terminal wiring with remote sensor wiring (for Analog and Analog/HART models)
MAN-0082, Revisio n 08 June 2016

2.6.1 Wiring drawings for remote sens o r wiring

The drawings below are an analog output drawing showing wiring of sensor to transmitter remotely via a junction box. Consult qual i fi e d p er so nnel on specific wiring requirements.
Installation Reference Manual
10 Installation
June 2016 MAN-0082, Re vision 08

2.7 Installation checklist

Review the following checklist prior to turning the power on to the transmitter after install ation has been completed:
Ensure that the transmitter and se nsor are properly and firmly mounted. Ensure that stopping plugs are securely ti g htened on any unused conduit entr i e s . Ensure that the transmitter and sensor are not obstruc ted; transmitter and s e n so r are accessible
and target gas is not inhib ited from reaching the sensor.
Ensure adherence to applicable local guidelines and requirements on wiring and sealing of
equipment in hazardous and non-hazardous area s.
Ensure that proper shielding and grounding practices are adhered to and local codes are being
followed.
Check system operational voltage and conditions; ensuring that they ar e wi thin the applicable
specifications of the transmitter and sensor.
Verify wiring at all termination and junction points (transmitter, junction box, and power supply). Ensure that the transmitter housing co ver and sensor cap are secured tightly.
Reference Manual Operation
Operation 11
Figure 3-1 Faceplate description
Do not open the transmitter, sensor, or junction box enclosure when in a classified area or when an explosive at mosphere may be present unless the power to the transmi tter has been removed.
MAN-0082, Revisio n 08 June 2016

Section 3: Operation

3.1 Transmitter and faceplate description

After wiring is completed and power is applied, indicated by the green power LED, a warm-up routine will begin, where the sensor is automatically tested to ensure proper operation. The Status LED will slowly flash red and the current output will be 3.0 mA (indicated by Analog models). Once the war m ­up routine has been completed, the LED will flash green, indicating normal operation. The time taken for the transmitter to complete its warm-up cy cl e i s dependent on t he type o f sensor b eing used.
The transmitter faceplate shows the posi ti o n of the magnetic switch, the status LED, and the status L ED states. See Section 7 for more information on the Status LED.

3.2 Intrusive access

This involves the r emo v al of the top cover and faceplate to access the pushbutton switch when calibrating and rese tting the transmitter . Pressing and hold i ng the pushbutton down for up to three (3) seconds resets the transmitter; latched alar ms are cleared and sensor performed self-tests. Holding down the pushbutton for up to fi ftee n ( 15) seconds sends the transmitter into full calibration mode. See Section 6 for more information on calibration and manual reset.

3.3 Non-intrusive access (magnetic Reed switch Access)

This involves pl ac i ng and holding the attached mag net next to the base of the l ab el mount as indicated in Figure 3-2. When the magnet is held for up to three (3) seconds, a manual reset will be initiated. If
Operation Reference Manual
12 Operation
Figure 3-2 Positioning of magnet
June 2016 MAN-0082, Re vision 08
the magnet is held for up to fi ftee n ( 15) seco nds a full calibration procedure will begin. See Section 6 for more information on calibration and manual reset.
Reference Manual Output configurations
Output configurations 13
Sensor Terminals
Sensor Wire
White
Red
Blue
Black
Green
Marked
+VDC
Sig A
Sig B
COM
Function
10.5 - 32 VDC
A B Comm
Earth Ground
Output Terminals
Marked
+VDC
COM
4 – 20
ISO
Function
Power (+) (10.5-32 VDC)
Power (-)
Current loop output
Isolate the power for current loop
Figure 4-1 Analog circuit boa r d assembly
MAN-0082, Revisio n 08 June 2016

Section 4: Output configurations

4.1 Analog board assembly

The Analog model Millennium II Basic Transmitter provides a 4-20 mA signal output, allowing the user/operator wit h a signal represent i ng various conditions and states of the transmitter. See the following table for current output and meaning.
Output configurations Reference Manual
14 Output configurations
Sensor Terminals
Sensor Wire
White
Red
Blue
Black
Green
Marked
+Vdc
Sig A
Sig B
COM
Function
10.5 - 32Vdc
A B Comm
Earth Ground
Output Terminals
Marked
+VDC
COM
4 – 20
ISO
Function
Power (+) (10.5-32 VDC)
Power (-)
Current loop output
Isolate the power for current loop
Figure 4-2 Analog/HART circuit board assembly
For Hart Communicator connection in isolated or non must be a minimum of 250 Ohms to a maximum of 600 Ohms. Do not install r esistor within Millennium II Basic Transmitter.
June 2016 MAN-0082, Re vision 08

4.2 Analog/HART board assembly

The Analog/HART Millennium II Basic Transmitter provides the user/operator with the option of using a HART Communicator to gain access to the transmitter settings and output. This allows reviewing, logging, and monitoring of data which is ideally suited for maintenance. See 7.2 for more information.
-isolated configuration, the total loop resistance the
Reference Manual Output configurations
Output configurations 15
Sensor Terminals
Sensor Wire
White
Red
Blue
Black
Green
Marked
+VDC
Sig A
Sig B
COM
Function
10.5 - 32 VDC
A B Comm
Earth Ground
Output Terminals
Marked
RST
+VDC
COM
FNO
FCOM
FNC
A1NO
A1COM
A1NC
A2NO
A2COM
A2NC
Function
Remote
Power
VDC)
Power
Fault
Alarm 1
Alarm 2
Relay definitions:
Figure 4-3 Relay circuit bo ard a ss embly
MAN-0082, Revisio n 08 June 2016

4.3 Relay board assembly/configuration

This assembly has thr e e (3) relays; a fault alar m r e l ay , a low alarm relay and a high alarm relay. The fault alarm relay is fixed as energi zed and non-latching and ca nnot be changed. The low alarm relay and the high alarm relay may be configured as energized or de-energized and latching or non-latching. By default the low and high alarm relay cont act s are de-energized and non-latching. For more information on adjusting the relay settings refer to 7.3.
Reset
(+) (10.5-32
(-)
(Low Alarm)
(High Alarm)
Fault Alarm contacts: Fault Normally Open (FNO), Fault Common (FCOM), and Fault Normally Closed (FNC).
Low Alarm contacts : Al ar m 1 Normally Open (A1NO), Alarm 1 Common (A1C OM ) and Alarm 1 Normally Closed (A1NC).
High Alarm contact s: Al arm 2 Normally Open (A2NO), Alarm 2 Commo n ( A2COM) and Alarm 2 Normally Closed (A2NC).
Output configurations Reference Manual
16 Output configurations
Sensor Terminals
Sensor Wire
White
Red
Blue
Black
Green
Marked
+VDC
Sig A
Sig B
COM
Function
10.5 - 32 VDC
A B Common
Earth Ground
Output Terminals
Marked
+VDC
COM
A(positive )
B(negative)
COM
Shld
Function
Power (+)
Power (-)
Modbus RTU
Modbus RTU
Modbus RTU
Shield
Figure 4-4 Digital circuit board assembly
June 2016 MAN-0082, Re vision 08

4.4 Digital board assembly/configuration

This assembly allows digital output utilizing Modbus Digital RS-485 protocols. See 7.4 for more information.
(10.5-32 VDC)
Terminal A
Terminal B
Terminal Common
Reference Manual Operation
Operation 17
The gas curve or range sho uld only be changed wh e n the sensor and transmitte r ar e i n After powering up, the transmitter state. The system sho ul d b e recalibrated wit h 50% of changed.
Position 1
Position 2
Position 3
Position 4
Gas Curve
OFF
OFF
OFF
OFF
Methane (0)
ON
OFF
OFF
OFF
Propane (1)*
OFF
ON
OFF
OFF
n-Butane (2)*
ON
ON
OFF
OFF
Iso-Pentane (3)*
OFF
OFF
ON
OFF
n-Pentane (4)*
ON
OFF
ON
OFF
Ethane (5)
OFF
ON
ON
OFF
Iso-Butane (6)*
ON
ON
ON
OFF
Ethylene (7)
OFF
OFF
OFF
ON
Hexane (8)*
ON
OFF
OFF
ON
Propylene (9)*
Position 1
Position 2
Position 3
Position 4
Range(Setting)
ON
OFF
OFF
OFF
Range 1 (20ppm)
OFF
ON
OFF
OFF
Range 2 (50ppm)
OFF
OFF
ON
OFF
Range 3 (100ppm)
MAN-0082, Revisio n 08 June 2016

Section 5: Operation

5.1 DIP switch settings

5.1.1 Infrared sensor (SC311) gas curve selection

When using the SC311 sensor with the Millennium II Basic transmitter, DIP switch 2 on the transmitter should be set up as follows:
normal state.
, the status LED will slowly flash green to indicate normal operating
the specific target gas if the sensor’s range is
*Indicates gases are no t third party perform anc e verified

5.1.2 Hydrogen sulfide sensor (ST320) range selection

Operation Reference Manual
18 Operation
Position 1
Position 2
Position 3
Position 4
Range(Setting)
ON
OFF
OFF
OFF
Range 1 (500ppm)
OFF
ON
OFF
OFF
Range 2 (1000ppm)
DIP Switch 1 Settings
Position
Status
Value
Function
Position 1 On
16%
DIP Switch 1 positions are used in conjunction with DIP
Off
0%
Position 2 On
8%
Off
0%
Position 3 On
4%
Off
0%
Position 4 On
2%
Off
0%
June 2016 MAN-0082, Re vision 08

5.1.3 Carbon monoxide sensor (ST360) range selection

5.1.4 DIP switch settings for relay configu ration

DIP switch 1 and DIP swi tch 3, as se en in the tables below, show the settings for relay al ar m l e v e l s an d status. DIP switch 3 position 4, is used in conjunction with DIP switch 1, if needed to set up the alarm level. The user is allowed to fully utilize, if necessary, all the percentages offered. To arrive at the desired low alarm level, add different percentages, while taking note of the sensor’s range/scale. The high alarm level (A2) is automatically set to twice the low alarm level (A1).
Example: For a sensor wi th range/scale of 50 ppm, and DIP switch 1 set with positions 2 and 4 ‘On’ (8 % +2 %) the low level alarm point would be (10 % of 50 ppm) whic h i s 5 ppm automatically making the high level alarm point 10 ppm.
Switch 3, *position 4*, if needs be, to set the Alarm point (% of full scale or range)
Reference Manual Operation
Operation 19
DIP Switch 3 Settings
Position
Status
Value
Function
Position 1
ON
RFU
Not used now
OFF
RFU
Position 2 ON
Energized
Defines Relay Coil Status OFF(default)
De-energized
Position 3 ON
Latching
Defines Relay Latch Status OFF(default)
Non-Latching
Position 4 ON
32%
*Used with DIP Switch 1 to set the Alarm Point, (% of full OFF
0%
DIP Switch 1
Position 1
Position 2
Position 3
Position 4
MODBUS Address
OFF
OFF
OFF
OFF
16
ON
OFF
OFF
OFF
15
OFF
ON
OFF
OFF
14
ON
ON
OFF
OFF
13
OFF
OFF
ON
OFF
12
ON
OFF
ON
OFF
11
OFF
ON
ON
OFF
10
ON
ON
ON
OFF
9
OFF
OFF
OFF
ON 8 ON
OFF
OFF
ON 7 OFF
ON
OFF
ON
6
ON
ON
OFF
ON
5
OFF
OFF
ON
ON 4 ON
OFF
ON
ON 3 OFF
ON
ON
ON 2 ON
ON
ON
ON
1
MAN-0082, Revisio n 08 June 2016
scale/range) if needs be*.

5.1.5 Digital Modbus DIP sw itch setting s

DIP switch 1 selects the Modbus address. DIP switch 2 defines the Modbus settings. Positions 1 and 2 of DIP switch 2 select the baud rate of the Modbus system. Positions 3 and 4 of DIP switch 2 select the data format of the Modbus data link. T he se DIP switches must be set before the Millenni um I I Basic is powered up. Once the device is powered up the setting will be locked until another power down and up cycle. Refer to the following tables for DIP switch positions.
Operation Reference Manual
20 Operation
DIP Switch 2 settings for b aud rate
Position 1
Position 2
BAUD Rate
OFF
OFF
19200
OFF
ON
9600
ON
OFF
4800
ON
ON
2400
DIP Switch 2 for fo r mat bits
Position 3
Position 4
Date Format
OFF
OFF
8 bits data, no parity bit, 2 stop bits (also compatible to 1 stop bit)
OFF
ON
8 bits data, no parity bit, 2 stop bits
ON
OFF
8 bits data, odd parity bit, 1 stop bits
ON
ON
8 bits data, even parity bit, 1 stop bits
June 2016 MAN-0082, Re vision 08

5.1.6 Analog and analog/HART DIP switch settings

DIP switch 1 is not utilized when using the Millennium II Basic analog and analog/HART models. DIP switch 2 settings/positions, are utilized for different gas curves when using IR sensors (SC311) and for changing toxic sensor r anges (ST3XX). Refer to specific sensor manuals to see the combinations of DIP switch 2 positions and when it is utilized.
Reference Manual Calibration procedure
Calibration procedure 21
All systems should be bypassed during calibratio n a nd bu mp te stin g to avo i d un wanted alarms.
MAN-0082, Revisio n 08 June 2016

Section 6: Calibration procedure

6.1 Calibration procedure

Prior to attempting calibration read and understand the calibration procedure below. Also see Figure
6-1 for additional reference.
The following calibration procedure should be followed to ensure an accurate correlation between the output signals and the gas concentration. For accurate performance, the Millennium II Basic Transmitter is calibrated using 50% span gas.

6.1.1 Guidelines

Calibration is recommended after the Millennium II Basic and sensor are installed. Calibration should be performed after the sensor has been powered for at l east 24 hours. Refer to specific sensor manuals for details on calibrating.

6.1.2 Full calibration procedure

1. Confirm successful power-up of transmitter, (green or red flashing of status LED).
2. For analog model connect a standard ammeter to the transmitter Tes t J acks (not required but gives visual confirmation). See figures in Section 4 for Test Jacks location.
3. Press and hold the pushb utton, or activ ate the Reed switch using the mag net, for at least fifteen (15) seconds; the status LED flashes green fast, and then goes solid green (first soli d g reen), keep holding the pushbutton or magnet, after which, the status LED goes solid red. Release the pushbutton or remove mag net.
4. When the current output i s 3 mA (indicated by anal og models) and the stat us L ED is once again solid green (second solid green). Apply zero gas (clean air). Recommendation: Flow clean air at a rate of 0.5 liter per minute or more to the sensor for best results.
5. When the current output i s 3.3 mA (indicated by analog models) and the status LED is flashing red, apply the calibration ga s ( 50% o f f ul l span) to the sensor . R ecommenda tion: Flow span gas at a rate of 0.5 liter per minute to the sensor for direct sensor calibration. If the sensor is separated with long tubing runs, increase the gas flow rate to ensure tubing does not affect calibration results.
6. When the current output is 3.6 mA (indicated by analog models) and the status LED is solid green, remove the calibration gas.
7. Apply zero gas (clean air) again to purge the system if calibrati o n tu bing is used.
8. After the sensor is purge d o f gas, the transmitter will return to normal operation.
Calibration procedure Reference Manual
22 Calibration procedure
Zeroing does not require the application of a calibration gas. It does, however, contaminated gas i s pr e se nt in the ambient air, i f the sur rounding air is bei ng used .
Zeroing is not a substitute for performing a full calibration. Zeroing can be completed on an interim basis; however, It is highly recommended t hat a full
June 2016 MAN-0082, Re vision 08

6.2 Zeroing procedure

This option is useful if the sensor’s zero point has drifted as a result of a change in the ambient
conditions.
require that no
calibration be completed whenever possible.
1. Confirm successful power-up of transmitter, (green flash i ng o f statu s L ED ev er y sec ond: no fault indicated).
2. For analog model connect a standard ammeter to the transmitter Tes t J acks (not required but gives visual confirmation). See figures in Section 4 for Test Jacks location.
3. Press and hold the pushb utton, or activ ate the Reed switch using the magnet, until the status LED flashes green fast, and then goes solid g r e en. Release the pushbutton or deactivate the Reed switch.
4. When the status LED is solid green, the current output will be 3 mA (indicated by analog models). Apply zero gas (clean air). Recommendation: Flow clean air at a rate of 0.5 liter per m i nu te or more to the sensor.
5. Zeroing is complete when the current output is 3.6 mA (indicated by analog models) after which, the Status LED flashes green every second (current output of 4 mA). Remove the zero g as, or allow the transmitter to return to normal operation if ambient (clean surrounding) air was used.
6. Normal operation is confirmed by a current output of 4 mA (indicated by analog models) and the status LED flashing green every second.
Reference Manual Calibration procedure
Calibration procedure 23
Figure 6-1 Calibration procedure
LED and analog
Zero Calibration
MAN-0082, Revisio n 08 June 2016
Activate/hold calibrati on
switch for six to t en seconds
Full Calibration
Activate/hold calibrati on sw it c h f or
ten to fifteen seconds until status
LED turns red
Status LED flashes
fast green
Status LED goes
solid green
3.0 mA output
Apply air from canister or use
clean ambient air to perform
zero
output
indication
Status LED solid
red
Status LED goes
solid green
3.0 mA output
Apply air from canister or use
clean ambient air to perform
zero
Status LED flashed
Red
3.3 mA output
Status LED alternating red
and green
3.0/3.3 mA output
Status LED solid green
3.6 mA output
Apply 50% span target gas to
perform span
Calibration Failed
Perform manual reset and
complete calibration
procedure again
Calibration Successful
Remove calibration gas and
purge calibration lines if used
Calibration procedure Reference Manual
24 Calibration procedure
Condition
Current output
LED indication
Relay outputs
Fault
Alarm
Zero calibration initiated
4.0 mA
Fast flash green
Normal state
Normal state
Full calibration initiated
4.0 mA
Solid red
Normal state
Normal state
Zero calibration being completed
3.0 mA
Solid green
Normal state
Normal state
Apply span calibration gas
3.3 mA
Flashing red
Normal state
Normal state
Successful calibration
3.6 mA
Solid green
Normal state
Normal state
Calibration failed
3.0/3.3
Alternating red and green
Fault state
Normal state
June 2016 MAN-0082, Re vision 08

6.3 Status conditions during calibration

6.4 Calibration failures

If the calibration pro c ed ur e fails, the Status LED will alternate red and g r ee n wi th the analog output changing back and fo r th fr om 3.0 mA to 3.3 mA. The unit will remain in a failed state until it is manually reset.

6.5 Manual reset

A manual reset is requir e d after a calibration failure or to clear a latched alarm. Simply press an d hold down the pushbutton for up to three (3) seconds, cycle power, or place and hold the flat surface of the magnet near the Reed switch for up to three (3) sec o nds. The status LED will fast flash gree n, then slowly flash red, indi c ati ng reset, after whic h, the status LED will flash green slowly, to indicate normal operation.
Reference Manual Monitoring and outputs
Monitoring and outputs 25
When remote HART Communication is being pins at J3. See
MAN-0082, Revisio n 08 June 2016

Section 7: Monitoring and outputs

7.1 Analog 4-20mA

The Millennium II Basic transmitters (with the exception of the M2B-R) offer a variable 4-20 mA analog output. This output will provide gas concentration through the 4-20 mA range, where 4 mA equals zero gas concentrati o n and 20 mA equals the hig h r ang e of the sensor (e.g. 10 0% LEL or 100 ppm). Other conditions such as faults and calibration notifications (e.g. apply gas) are indicated in the 0-3.9 mA range. Faults are ind i c ated at either 0 mA or 2.5 mA.

7.2 HART Communication (Optional)

The HART protocol is a powerful communication technology enabling users to exploit the full functionality of the Millenni u m I I Basic Transmitter.
The HART Communicator may be connected to the Analog/HART model Millennium II Basic Transmitter via the HART Port connector (HPT -001) which prov i d e s the nec e ssary interface for communication on the analog output wires. The HART Port connector is fitted to one of the ¾” NPT conduit entries and its communication wires fitted to the HART Pins located at J3 on the Analog/HART PCB. The HART Communicator probe wires (leads) are then connected to HART Port connector contact points.
Figure 4-2 for the location of J3. By default the jumper is connected across the pins.
When the system is power ed-up, the communicator will search for the Millennium II Basic Transmitter and when a connection is established, the communicator will show the device information. If the Millennium II Basic Transmitter Device Description (DD) is loaded into the communicator, the communicator can access all the information and features of the Millennium II Basic Transmitter. If the communicator is not programmed with the specific DD, the Millennium II Basic Transmitter can still work with the communicator as a generic device.

7.2.1 HART Menu Structure

The Hart Menu structur e e xists when using the HAR T Communicator and allows the user to see al l existing options, Device status, Calibration information and History. Refer to Figure 7-1 and Figure 7-2 for the HART menu structur e and tre e.
completed, ensure the HART Jumper is connected across
Monitoring and outputs Reference Manual
26 Monitoring and outputs
Figure 7-1 HART menu tree - page 1
Loop test
Zero only
Z&Span Calibration
See next page “History”
See next page
Num resp preams
Zero calibration
June 2016 MAN-0082, Re vision 08
This section displays a g eneral menu tree for M i llennium II series sensors. Additional menus may exist when using communicator but should be ignored if they are not available in this menu tree.
Process variables
Diag/Service
Device setup.
Device status PV Value xx % LEL/PPM PV Current xxmA PV LRV 0% LEL/PPM PV URV 100% LEL/PPM
Basic setup
Detailed setup
Review
PV Value xx % LEL/PPM
PV % rnge xx% Loop current xx mA
Test device
Calibration
Device status History
Tag xxxx
Long Tag xxxxxxxx PV unit % LEL/PPM PV Xfer fnctn Linear Range values Device information
Sensor
Signal condition Output condition
Device information
See next page
“Review”
Device reset
Zero & Span
PV mA
Manufacturer Net Safety
Model Millennium II Basic Dev ID xxxxx Cfg Chng count xxxxx Tag xxxxxxxxxxxx Long Tag xxxxxxxxxxxxx Date xx/xx/xx Descriptor xxxxxxxx xxxxx Message xxxxxxxxxxxx Final asmbly num xxxxx
Revision #’s
PV LRV 0% LEL/PPM
PV URV xx % LEL/PPM PV % rnge xx % Xfer fnctn, linear
Analog Output
HART Output
PV Value xx % LEL/PPM
Loop current xx mA Current gas type
PV
PV Range value
Loop current xx mA
Loop test
Loop current mode
Poll Addr xx Num reg preams xx
Reference Manual Monitoring and outputs
Monitoring and outputs 27
Figure 7-2 HART menu tree - page 2
“History”
“Sensor”
“Review”
Sensor
Reset Max Min Temperature
MAN-0082, Revisio n 08 June 2016
Max Temperature xxx Deg C
Max Temperature
Min Temperature
Calibration Log
Catalytic Bead Sensor, IR combustible, H2S toxic
Max Temperatur e S ince Reset xx Deg C Reset Date xx/xx/xxxx Reset Time xxxx Reset Max Min Temperature
Min Temperature xxx Deg C
Min Temperature Sin ce Reset xx Deg C Reset Date xx/xx/xxxx Reset Time xxxx
Calibration Date xx/xx/xxxx
Calibration Time xxxx Cal Event Type xxxxxxxxx Next Log Previous Log Most Recent Log
Sensor Class Cat Bead Combustible, Infrared Combustible,
PV xx % LEL
PV Unit % LEL
H2S toxic, CO toxic
Sensor Temperat u r e xxx Deg C Sensor Remain Time xxxx Days Current gas type PV LSL 0% LEL/PPM PV USL 100% LEL/PPM PV Min span 1% LE L/PPM Gas type and range
Current gas type
Custom K factor PV U SL Support gas type
Support USL(range)
Manufacturer Net Safety
Model Millennium II Basic Dev ID xxxxxx Tag xxxxxxxxxxx Long Tag xxxxxxxxxxxxxx Descriptor xxxxxxxx xxxxxx Message xxxxxxxxxxxxxx Date xx/xx/xx Final asmbly num xxxxxxx Universal rev 7 Fld dev rev xx Software rev xx Poll addr xx Loop current mode Disabled/Enabled Num reg preams xx Num resp preams xx
Sensor gas 1 Sensor gas 2
Sensor gas 3……….16
Sensor range 1 Sensor range 2
Sensor range 3…….5
Monitoring and outputs Reference Manual
28 Monitoring and outputs
The fault relay output is not commonly used to imitate an indicates a potential problem with the transmitter not an alarm condition.
June 2016 MAN-0082, Re vision 08

7.3 Relays (Optional)

7.3.1 Alarm relays

The Millennium II Basic transmitters com e compl ete with two (2) programmable al arm relays. These relays will change the i r st ate from their non-alar m state to an alarm state when gas concentrati o ns, as read by the sensor, go ab o ve the programmed alar m points set in the transmit ter .
The alarm relays can be programmed to be energized or de-energized under normal conditi o ns, and then either latching or non-latching.

7.3.2 Fault relay

Millennium II Basic transmitters and sensors complete conti nu al c hecks for situations that may prevent the transmitter and sensor from providing an expected response to ambient conditions and records these as a fault condition in the message log and the output(s) of the tr ansmitter. When a syste m fault is detected, the Red Status LED will flash fa st (250 millisecond s o n, 250 milliseconds off), the analog output will output a 2.5 mA signal, and the fault relay will change st ates (de-energize to provide a fault condition).
The fault relay is normally energized when no fault conditions are present and is set up for non-latching. The operation of the fault relay is not configurable.
The Millennium II Basic transmitter provides various fault conditions to indicate that the transmitter or connected sensor(s) are not operating as expected. These fault conditions will override any alarm conditions because the sensor may be unable to detect a gas exposure reliably. Examples of fault conditions can range from no detection due to memory or communication errors and sensor failure. Other faults can provide unreliable detection due to sensor drift or sensor nearing the end of its life. When a Millennium II Basic transmitter is in fault mode, immediate action should be taken to determine the source and correct the fault condition.
automatic shutdown. The fault output

7.4 RS-485 Modbus RTU (Optional)

Modbus digital RS-485 Modbus RTU protocol is used. The Millennium II Basic transmitter utilizes 2- wire Modbus RS-485 multi serial mode. This Modbus
solution implements a 2-wire electrical interface in accordance with the EIA/TIA-485 standards. F or this Modbus configuration, it is important that a third wire be used for connecting all the commons (COM) in the chain. Also a 120 Ohm line termination is required for the last device in the line. See Figure 7-3. The Instrument Engineer is responsible for calculating line length and adhering to Modbus protocols.
Reference Manual Monitoring and outputs
Monitoring and outputs 29
Figure 7-3 Two-wire Modbus configuration
Reg#
Meaning
Readable
Writeable
40001
Concentration value as calculated by sensor (RTUsensor_out), Channel 1
X
40002
Sensor status (RTUsensor_stat)
X
40003
Temperature of sensor element housing in Kelvin (RTU temperature)
X
40011
Calibration gas value
X
40021
Sensor class
X 40022
Low alarm value
X X 40023
High alarm value
X X 40027
Current sensor range
X
X
40101
Reset sensor
X
40102
Full calibration
X
40104
Zero calibration
X
MAN-0082, Revisio n 08 June 2016

7.4.1 Modbus registers

Monitoring and outputs Reference Manual
30 Monitoring and outputs
Condition
Current output
LED indication
Relay outputs
Fault
Alarm
No gas present
4 mA
Slow green
Normal state
Normal state
Gas present, concentration below alarm points
4-20 mA depending on gas concentration
Slow red
Normal state
Normal state
Gas present, concentration above alarm points
4-20 mA depending on gas concentration
Slow red
Normal state
Alarm state Fault condition present, no gas present
2.5 mA
Very fast red
Fault state
Normal state
Fault condition present, gas present
2.5 mA
Very fast red
Fault state
Normal state
Fault condition present, gas above alarm points
2.5 mA
Very fast red
Fault state
Normal state
Electrochemical XChem sensors only:
Very fast red
Fault state for 5
55 seconds
Normal state
Fault relay:
LED indications:
Flash description
On
Off
Slow
50 milliseconds
1 second
Fast
250 milliseconds
250 milliseconds
Very fast
50 milliseconds
50 milliseconds
Alarm relay(s):
June 2016 MAN-0082, Re vision 08

7.5 Transmitter output operation

The following table outlines the operation of the outputs of the Millennium II Basic transmitter under different conditions. These outputs include the analog output, LED indications, and the relay outputs. For the outputs’ status, refer to the descriptions below the table.
Sensor end of life condition present, gas above or below alarm points
Fault state means that t he r elay is in the de-energized state. Normal state means that the
relay is in the energized state.
Flash rates are outlined in the following table:
Alarm state means that if the r elay is programmed for normally de-energized, the relay will energize to alarm; if the relay is programmed for normally energized, the relay will de-energize to alarm. Normal state is what state that the relay i s p r ogrammed for (e.g. normally energized o r normally de-energized).
2.5 mA for 10 seconds, 4-20 mA for 50 seconds
seconds, normal state for
Reference Manual Monitoring and outputs
Monitoring and outputs 31
The fault detection circuitry does not monitor the operation of external response equipment or external wiring to the transmitter. It is important that extern al equi pment and wiring be checked periodically to ensure they are operational.
Fault conditions will override any alarm conditions because the sensor may be unable to detect a gas exposure reliably, as such, the alarm relay will not provide an output.
Fault conditions provided by an instrumentation device are critical indicators that the device is not operating as expected; therefore, when a fault condi ti o n is present, immediate a ttention to that fault condition is required.
Net Safety strongly recommends that the 2.5 mA analog fault condition and fault relay (if used) be monitored in conjunction with alarm levels on the analog output and the alarm relay, if used.
Fault condition
M2B
Input voltage less than 8 VDC
Critical memory fault
Onboard power supply fault
MAN-0082, Revisio n 08 June 2016

7.6 Fault monitoring

Self-testing circuitry continuously checks for problems that could prevent proper response. When power is applied to the Millennium II Basic Transmitter, a microcontroller automatically tests the system to ensure that it is functioning properly. During normal operation, it continuously monitors the signal from the internal sensor source. In addition, a watchdog timer is maintained to ensure the program is running cor r e c tl y. When a system faul t i s d e tected, the Status LED will have a red fast flash and the fault signal will output a 2.5 mA signal. The transmitter’s event log may be viewed in order to distinguish the fault condition.

7.7 Fault conditions

7.7.1 Transmitter fault condit ions

Fault conditions that t he tr ansmitter detects ar e as follows:
P
Input voltage more than 33 VDC
P P P
Monitoring and outputs Reference Manual
32 Monitoring and outputs
Fault condition
SC310
SC311
ST322
ST332
ST340
ST320
ST330
ST341
ST360
Zero calibration failure
Span calibration failure
Low temperature
High temperature
Low power
P P P P P
High power
P P P P P
Replace sensor
P P P P P P P P P
Zero drift
P P P P P
Signal invalid
P
Over-range
P P P P P
Memory fault
Power supply fault
Sensor end of life
Sensor weak signal
Sensor thermistor fault
June 2016 MAN-0082, Re vision 08

7.7.2 Sensor fault conditions

Fault conditions that the various Millennium II sensors detect are as follows:
P P P P P P P P P P P P P P P P P P P P P P
P P P P P P P P P P P P P P P P P P P P P P P P
P
Reference Manual Maintenance
Maintenance 33
MAN-0082, Revisio n 08 June 2016

Section 8: Maintenance

8.1 Periodic response check

Net Safety Monitoring recommends that a bump test be performed every ninety (90) days to ens ur e continued functionality and accuracy of the detection system. Full calibration is recommended when the sensor fails to meet acc eptable accuracy standards. This involves the application of calibration gas to the sensor, then the o b servation of the response LEDs, analog output, and external monitoring equipment. Be sure to prevent unwanted response of external monitoring dev i ces an d eq uipment during this procedure. If the Millennium II Basic’s response to calibration gas is within the specified accuracy then it is not ne c essary to perform a calibration.
Example: When 50% of full scale is applied, the response is expected to be between 1 1.5 mA (4 7% of full scale) and 12.5 mA (53% o f full scale). An additional consideration i s the ac cu racy tolerance of the calibration gas whic h m ay be plus or minus a few percent. If the calibrati o n g as i s ±10% of full scale then the reading may be fro m 10.7 mA (42% of full scale) to 13.3 mA (58% of full sc ale).

8.2 Troubleshooting

Response to the input should be checked and, if necessary, calibration should be performed whenever the accuracy of this check is not satisfactory . The system should also be checked when sen so r o r transmitter is added or removed. If problems should develop, first check for faulty wiring, confirm proper voltage to transmitter and attempt a cal i br atio n. If pr o bl e ms per sist, pl ease contact Net Safety’s support department first by phone to t r y and r esolve any issues. If i ssues cannot be resolv e d, please follow the procedure on how to return equipment.

8.3 Storage

The transmitter and its electronic components/parts should be stored in locations free from dust and moisture. The storage temperature should be well within the limits of the certified temperatures of the equipment. See Section 11 for storage temperatures.
Maintenance Reference Manual
34 Maintenance
Description
Part Number
3/4 NPT ATEX certified plug - Aluminum
CP-AL-002
3/4 NPT ATEX certified plug - Stainless Steel
CP-SS-001
Conduit reducer - 3/4” to M20 - Aluminum
M20R
Conduit reducer - 3/4” to M20 - Stainless Steel
M20R-SS
Aluminum separation kit
JB-MPD-A
Stainless Steel separation kit
JB-MPD-S
Magnet assembly
MAGNET-1
Sun shade kit - Requires UN-MK-1
SSK-2
1" Pipe Mounted Sun shade kit/rain guard - Includes UN-MK-31
SSK-51
2" Pipe Mounted Sun shade kit/rain guard - includes UN-MK-32
SSK-52
3" Pipe Mounted Sun shade kit/rain guard - Includes UN-MK-33
SSK-53
Millennium II Basic transmitter board - Analog output
TX-M2B-A
Millennium II Basic transmitter board - Analog/HART output
TX-M2B-AH
Millennium II Basic transmitter board - Analog/HART output for wireless
TX-M2B-AH-FC Millennium II Basic transmitter board - Modbus output
TX-M2B-D
Millennium II Basic transmitter board - Relay output
TX-M2B-R
2" Pipe Mounting kit (stainless steel)
UN-MK-1
1" Pipe Mounting kit - All Millennium II & ECO-SENSE Gas Detectors (stainless steel)
UN-MK-31
2" Pipe Mounting kit - All Millennium II & ECO-SENSE Gas Detectors (stainless steel)
UN-MK-32
3" Pipe Mounting kit - All Millennium II & ECO-SENSE Gas Detectors (stainless steel)
UN-MK-33
June 2016 MAN-0082, Re vision 08

8.4 Spare parts and accessories

capable transmitters
Reference Manual Electrostatic sensitive device
Electrostatic sensitive device 35
MAN-0082, Revisio n 08 June 2016

Section 9: Electrostatic sensi ti ve d evi ce

Definition: Electrostatic discharge (ESD) is the transfer, between bodies, of an electrostatic charge caused by direct contact or induced by an electrostatic field.
The most common cause o f E SD i s p hysical contact. Tou ching an object can cause a discharge of electrostatic energy. If the charge is sufficient and occurs near electronic components, it can damage or destroy those comp o ne nts. In some cases, damage is instantaneo us and an immediate m al function occurs. However, symptoms are not always im mediateperformance may be marginal or seemingly normal for an indefinite period of time, followed by a sudden failure.
To eliminate potential ESD damage, review the following guidelines:
Handle boards by the sid es taking care not to touch electronic components.
Wear grounded wrist o r foot straps, ESD shoes or heel gro unders to dissipate unwant ed static
energy.
Prior to handling boards, dispel any charge in your body or equipment by touching a grounded
metal surface.
Ensure all compone nts are transported and sto r ed i n ESD safe packaging.
When returning boards, carefully package in the original carton and static protective wrapping.
Ensure ALL personnel are ed uc ated and trained in ESD Control Pr o ce dur e s .
In general, exercise accepted and proven precautions normally observed when handling electrostatic sensitive devices.
Wire resistance table Reference Manual
36 Wire re s istance table
Distance Feet (Meters)
AWG #20
0.5 mm2
AWG #18
0.8 mm2
AWG #16
1.0 mm2
AWG #14
2.0 mm2
100 (30.5)
1.02
0.64
0.40
0.25
200 (61)
2.03
1.28
0.80
0.51
300 (91.4)
3.05
1.92
1.20
0.76
400 (121.9)
4.06
2.55
1.61
1.01
500 (152.4)
5.08
3.20
2.01
1.26
600 (182.9)
6.09
3.83
2.41
1.52
700 (213.4)
7.11
4.47
2.81
1.77
800 (243.8)
8.12
5.11
3.21
2.02
900 (274.3)
9.14
5.75
3.61
2.27
1000 (304.8)
10.20
6.39
4.02
2.53
1250 (381)
12.70
7.99
5.03
3.16
1500 (457.2)
15.20
9.58
6.02
3.79
1750 (533.4)
17.80
11.20
7.03
4.42
2000 (609.6)
20.30
12.80
8.03
5.05
2250 (685.8)
22.80
14.40
9.03
5.68
2500 (762)
25.40
16.00
10.00
6.31
3000 (914.4)
30.50
19.20
12.00
7.58
3500 (1066.8)
35.50
22.40
14.10
8.84
4000 (1219.2)
40.60
25.50
16.10
10.00
4500 (1371.6)
45.70
28.70
18.10
11.40
5000 (1524)
50.10
32.00
20.10
12.60
5500 (1676.4)
55.80
35.10
22.10
13.91
6000 (1828.8)
61.00
38.30
24.10
15.20
6500 (1981.2)
66.00
41.50
26.10
16.40
7000 (2133.6)
71.10
44.70
28.10
17.70
7500 (2286)
76.10
47.90
30.10
19.00
8000 (2438.4)
81.20
51.10
23.10
20.20
9000 (2743.2)
91.40
57.50
36.10
22.70
10000 (3048)
102.00
63.90
40.20
25.30
June 2016 MAN-0082, Re vision 08

Section 10: Wire resistance table

Resistance shown is one way. This figure must be doubled when determining closed loop resistance.
Reference Manual Specifications
Specifications 37
MAN-0082, Revisio n 08 June 2016

Section 11: Specifications

11.1 Electrical

11.1.1 Operating voltage range

10.5 to 32 VDC 18 to 32 VDC (HART versions only)

11.1.2 Power consumption

1.5 W @ 24 VDC (average - varies by sensor types/quantities)

11.1.3 EMC complian ce

EN 50270:2006 per EMC d irective 2004/108/EC

11.2 Environmental

11.2.1 Operating temperature

-67 °F to +185 °F (-55 °C to +85 °C )
-58 °F to +185 °F (-50 °C to +85 ° C) – North American explosion-proof certification

11.2.2 Relative humidity

0 - 95% RH non-condensing

11.2.3 Ingress protection

IP67 Type 4X

11.3 Mechanical

11.3.1 Enclosure material

Cast Aluminum (6061) Stainless steel (SS316)

11.3.2 Conduit opening

3/4” NPT (3X)

11.3.3 Weight

Aluminum: 2.0 lbs (0.8 kg) Stainless Steel: 3.5 lbs (1.6 kg)
Specifications Reference Manual
38 Specifications
June 2016 MAN-0082, Re vision 08

11.4 Warranty

3 years
Reference Manual Certifications
Certifications 39
MAN-0082, Revisio n 08 June 2016

Section 12: Certifications

12.1 North American

Class I, Division 1, Groups BCD T5 Class I, Zone 1, AEx/Ex d IIB+ H
-50°C ≤ Ta ≤ + 85°C NEMA Type 4X/IP 67 FM6320, ANSI/ISA 12.13.01, CSA C22.2 No. 152:2006

12.2 IECEx

Ex d IIB+H2 T5 Gb
-55°C ≤ Ta ≤ + 85°C IP67 IEC 60079-0:2011/IEC60079-1:2007 IECEx FMG 14.0010X
T5
2

12.3 FC Models

12.3.1 North America

Class I, Division 1, Groups BCD T5 Class I, Zone 1, AEx/Ex d IIB+ H
-50 °C ≤ Ta ≤ +85 °C NEMA Type 4X/IP67 CSA C22.2 No. 152:2006

12.3.2 IECEx

Ex d IIB+H2 T5 Gb
-55°C ≤ Ta + 85°C IP67 IEC 60079-0:2011/IEC60079-1:2007 IECEx FMG 14.0010X
Special conditions for safe use:
Consult the manufacturer if dimensional information on the flameproof joints is necessary.
Follow the manufacturer’s instructions to reduce the potential of an electrostatic charging hazard.
T5
2
Ordering information Reference Manual
40 Ordering information
Model
Description
M2B
Millennium Basic II Single Channel Transmitter
Output
Description
A
Analog Output
AH
Analog and HART Protocol Output
D Digital RS485 Modbus RTU Protocol Output
R Relay Output
Enclosure
Description
A
Aluminum
S
Stainless Steel
Wireless
Description
_ Not Required
FC
Wireless Ready - THUM C ap able (Used Only With AH o r AHR
June 2016 MAN-0082, Re vision 08

Section 13: Ordering information

Outputs)
Notes
Notes
Notes
EmersonProcess.com/FlameGasDetection
Americas
Emerson Process Management
Europe
Emerson Process Management AG
Middle East and Africa
Emerson Process Management
SAFETY.CSC@Emerson.com
Asia Pacific
Emerson Process Management
SAFETY.CSC@Emerson.com
©2016 Emerson Process Management. All rights reserved.
The Emerson logo is a trademark and service mark of Emerson Electric Co. Rosemount is a mark of one of the Emerson Process Management family of companies. All other marks are property of their respective owners.
The contents of this publication are presented for information purposes only, and, while effort has been made to ensure their accuracy, they are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. All sales are governed by our terms and conditions, which are available on request. We reserve the right to modify or improve the designs or specifications of our products at any time without notice.
MAN-0082
Revision 08
June 2016
AnalyticExpert.com
youtube.com/user/RosemountMeasurement
6021 Innovation Blvd. Shakopee, MN 55379 USA T +952 906 8888 F +952 949 7001 SAFETY.CSC@Emerson.com
Neuhofstrasse 19a P.O. Box 1046 CH-6340 Baar Switzerland T + 41 (0) 41 768 6111 F +41 (0) 41 768 6300 SAFETY.CSC@Emerson.com
Emerson FZE Jebel Ali Free Zone Dubai, UAE P.O. Box 17033 T +971 4 811 8100 F + 971 4 886 5465
twitter.com/Rosemount_News
facebook.com/Rosemount
Asia Pacific Private Limited 1 Pandan Crescent Singapore 128461 Republic of Singapore T + 65 6 777 8211 F + 65 6 777 0947
Loading...