Net Safety Monitoring FlameWatch II Data sheet

FlameWatch II - Integrated Flame Detection/Video
PMS - Uncoated
PMS - Coated
PMS
BCR-0042-00-007
FlameWatch II
Integrated Flame Detection and Video
Bringing two technologies together...for enhanced protection. The FlameWatch II system is designed specifically for applications where a high performance flame detection solution and visual analysis/ record of an alarm event is required. These capabilities are ideally suited for remote locations in order to quickly evaluate the hazard from a controlled location and effectively mobilize response teams.
Product Data Sheet
July 2012
SMART” Gas Detector Series
Choose From Any Of Our Advanced Flame Detectors: UV, UV/IR, Phoenix Triple IR
Lowest Power Consumption of Any Flame Detector On the Market
Wide Voltage Range Allows For Greater Stability and System Compatibility
Wide Area Coverage, Extended Range with Fast Response Times
Manual and Automatic Testing of Optical Surfaces — Constantly Monitors Internal Electronics
Fast Response Times At All Sensitivity Settings With Wide Field of View
The FlameWatch II system is available with our entire line of advanced flame detection solutions - UV, UV/IR, Phoenix Triple IR flame sensors. The entire package includes Class 1, Division 1, Groups BCD classification; CSA/ATEX certification, FM approvals (flame detector only), NEMA 4X explosion proof rated housings; and is available in aluminum or stainless steel.
Field Adjustable Time Delay And Sensitivity Settings Significantly Reduces False Alarms, Simplifies Installation
Global Certifications and Approvals
Compatible With Industry Standard CCTV
Components
Video Jacks Included
 Wide Camera Viewing angle of 100°
 Full color, high resolution video
(NTSC & PAL formats available)
The FlameWatch II full colour, composite video signal easily integrates into a wide array of industry standard CCTV hardware and software security systems with both NTSC and PAL formats. The wide field of view provides large area coverage by a single camera and the high resolution video sensor captures accurate detail of the area being monitored.
With all the innovative design features from our entire flame line included, this package ensures a simplified installation, rock­solid performance, and lower maintenence costs.
The FlameWatch II provides the unique integration of an industrial flame detector with an explosion proof video camera — delivering the complete safety and security package for your application.
FlameWatch II - Integrated Flame Detection/Video
PMS - Uncoated
PMS - Coated
PMS
Field of View at Indicated Distance
in F eet for n-Heptane
15 °
15 °
30 °
45 °
30 °
45 °
Field of View at Indicated Distance
in F eet for n-Heptane
0 °
15 °
45 °
15 °
30 °
30 °
Vertical Field Of View With Detector At 45˚ From Horizontal
100
80
60
40
20
120
140
BCR-0042-00-007
Product Data Sheet
July 2012
FlameWatch II [Optional Phoenix Triple IR Flame Detector]
Specifications
“SMART” Gas Detector Series
ANALOG RE LAY DIGITAL HART
Operating Voltage Range
Power Consumption at 24 Vdc*
Temperature Range
Field of View
Spectral Range
Time Delay
Sensitivity Settings
Response Time
Enclosure Material
Humidity Range
Weight (with swivel)
Outputs
Certifications/Approvals
Warranty
De-Energized:
Nom 39 mA / 0.94 W
Nom 31 mA / 0.74 W
Max 65 mA / 1.56 W
Max 73 mA / 1.75 W
Energized:
Nom 53 mA / 1.22 W
Max 86 mA / 2.06 W
Certified -40°C to +75°C (-40°F to +167°F) — Operational -50°C to +85°C (-58°F to +185°F)
90 degrees vertical / 90 degrees horizontal
Wavelengths between 2.5 – 5.5 microns
Dip switch selectable to 0, 3, 5, 7 seconds
Two adjustable settings via DIP switch (High / Low)
<5 seconds [ depending on fuel source, fire size and distance ]
Red powdercoat with clear anodizing, copper-free aluminum (optional 316 Stainless Steel), factory sealed housing
2.1 Kg/4.5 lb (Stainless Steel option 3.4 Kg/7.5 lb)
Digitally stepped analog
output 0 to 20 mA - into a
maximum loop impedance of
800 Ohms at 32 Vdc
or 150 Ohms at 10.5 Vdc.
Isolated/Non-isolated
loop supply.
Normally open/normally
closed Form C contacts rated
5 Amps at 30 Vdc 125
Vac. Selectable energized /
de-energized Fire relay.
Fault relay fixed as energized.
Both Fire and Fault relays
fixed as non-latching.
CSA - Class I, Division 1, Groups A (Canada only), B, C and D - Temperature code T5 - CANADA: Class 1, Zone 1, Ex d IIB + H2 T5
ANSI-UL/ISA - Class I, Division 1, Groups B, C and D - Temperature code T5 - UNITED STATES: Class 1, Zone 1, AEx d IIB + H2 T5
ATEX/IECEx -
II 2 G Ex d II B+H2 T5 Gb GOST-R - 1Ex d II BT5/H2 INMETRO - BR-Ex d II B+H2 T5
Factory Mutual (FM) 3260 SIL2 ABS Marine NEMA Type 4X • IP66 - Enclosure ratings
10 to 32 Vdc
Nom 31 mA / 0.74 W
Max 65 mA / 1.56 W
0 to 95% RH, non-condensing
RS-485 RTU Modbus®
protocol
7 Years
Nom 57 mA /1.34 W
Max 123 mA / 2.96 W
HART Communication
Protocol
Summary of Distances
Fuel Fire Size Distance Typical Response
n-heptane 1’ x 1’ 210 feet max < 2sec @ 100 ft.
gasoline 1’ x 1’ 150 feet max < 5sec @ 150 ft.
methane 32” plume 140 feet max < 5sec @ 140 ft.
Example Field of View - Methane
32” plume - indicated in feet - consult factory for other gases
Immunity False Alarm Stimuli
Stimuli Immunity Range
arc welding/sparking/arcing 10 ft +
direct and/or indirect sunlight total
lightning total
halogen, fluorescent, incandescent light 10 ft +
250W Sodium Vapor, 250W Metal Halide Light 10 ft +
electric heater (1500W) 10 ft +
propane heater - mod./unmod. (27000w) 12 ft +
FlameWatch II - Integrated Flame Detection/Video
PMS - Uncoated
PMS - Coated
PMS
Field of View at Indicated D istance
in F eet for n-Heptane
15 °
15 °
30 °
45 °
30 °
45 °
Field of View at Indicated Distance
in F eet for n-Heptane
0 °
15 °
45 °
15 °
30 °
30 °
Vertical Field Of View With Detector At 45˚ From Horizontal
100
80
60
40
20
120
140
Product Data Sheet
BCR-0042-00-007
FlameWatch II [Optional UV/IR Flame Detector]
Specifications
“SMART” Gas Detector Series
ANALOG RE LAY HART
Operating Voltage Range
Power Consumption at 24 Vdc *with Heater
Temperature Range
Field of View
Spectral Range
Time Delay
Sensitivity Settings
Response Time
Enclosure Material
Humidity Range
Weight (with swivel)
Outputs
Certifications/Approvals
Warranty
Nom 45 mA / 1.1 W
Max 115 mA / 2.76 W
*Nom 90 mA / 2.16 W
Max 165 mA / 3.96 W
Certified -40°C to +75°C (-40°F to +167°F) / Operational -50°C to +75°C (-58°F to +167°F)
120 degrees horizontal / 95 degrees vertical
UV Radiation 185 to 260 nanometres (1850 to 2600 angstroms) | IR Radiation in the 4.4 micron range
Dip switch selectable to 0, 3, 5, 7 seconds
DIP switch selectable to 8, 16, 24 or 32 counts per second
<6 seconds [ depending on fuel source, fire size and distance ]
Red powdercoat with clear anodizing, copper-free aluminum (optional stainless steel), factory sealed housing
2.1 Kg/4.5 lb (Stainless Steel option 3.4 Kg/7.5 lb) - does not include junction boxes
Form C contacts rated 1 Amp at 30
0 to 20 mA - Into a maximum loop
Vdc, 0.5 Amp at 125 Vac. Selectable
impedance of 800 Ohms
at 32 V dc or 150 Ohms at 11.0 V dc.
Non-isolated loop supply
latching/non-latching Fire relay Fault
relay factory set as energized/non-
CSA - Class I, Division 1, Groups B, C and D - Temperature code T5 - CANADA: Class 1, Zone 1, Ex d IIB + H2 T5
ANSI/UL - Class I, Division 1, Groups B, C and D - Temperature code T5 - UNITED STATES: Class 1, Zone 1, AEx d IIB + H2 T5
ATEX/IECEx - II 2 G Ex d II B+H2 T5 Gb GOST-R - 1Ex d II BT5/H2 INMETRO - BR-Ex d II B+H2 T5
Factory Mutual (FM) 3260 SIL2 ABS Marine NEMA Type 4X • IP66 - Enclosure ratings
3 Years Electronics / 2 Years Sensors
10 to 32 Vdc
Nom 45 mA / 1.1 W
Max 115 mA / 2.76 W
*Nom 90 mA / 2.16 W
Max 165 mA / 3.96 W
0 to 95% RH, non-condensing
energized/de-energized,
latching, cannot be modified
Nom 71 mA / 1.7 W
Max 173 mA / 3.36 W
*Nom 106 mA / 2.22 W
Max 223 mA / 5.36 W
HART Communication Protocol
July 2012
Summary of Distances
Fuel Fire Size Typical Response
n-heptane 1’ x 1’
gasoline 1’ x 1’
methane 30” plume
Example Field of View - Methane
32” plume - indicated in feet - consult factory for other flame types
60˚
< 11sec @ 140 ft.
< 6sec @ 120 ft. (< 3sec @ 50 ft.)
< 6sec @ 100 ft.
60˚
60˚
Immunity False Alarm Stimuli
Stimuli Immunity Range
Direct/Indirect Sunlight total
1500W Heater 10 ft
Halogen, Incandescent Light 3 ft
Florescent Light 10 ft
Arc Welding 30 ft