NetBotz® Smoke Sensor (NBES0307)
Installation Instructions
WARNING: The NetBotz Smoke Sensor is intended to provide supple mentary
protection for equipment in data center racks and enclosures only. It is not to be
used to protect s tru ctu res or personnel.
This Smoke Sensor includes a System Sensor® model 4W-B, I3 Series, Photoelectric
Smoke Detector. For complete safety, installation, operation, and maintenance
information, refer to the I3 Series Installation and Maintenance Instructions on the
System Sensor Web site, www.systemsensor.com.
Inventory
Smoke sensor with 3.05-m (10-ft)
cable (1)
Smoke sensor bracke t (1)
203-mm (8-in) tie wrap (10)
RJ-45 coupling (1)
M4 x 8 pan head screw (2)
M6 x 16 Phillips slot screw (2)
Adhesive cable tie hol der (5)
M6 black plastic cup
washer (2)
M3 knurled thumb nut (2)
M3 x 12 stud fastener (2)
Installation
Caution: Make sure you connect this sensor to a Sensor port on applicable NetBotz
products. See your NetBotz product documentation for details.
Caution: Make sure you remove the orange protective cover shown in step three.
Note: Smoke detection is best when you install the sensor near the top of the enclosure. The
sensor occupies one U-space.
Note: You can ext end the length of the sensor cable up to 30.5 m (100 ft) using the
RJ-45 coupling and standard CAT-5 cabling.
Note: Use adhesive cable tie holders and tie wraps to secure the sensor cable.
NetBotz Smoke Sensor (NBES0307) Installation Instructions2