Troubleshooting
Symptoms/Cause Remedy
LEDs on the Remote Module or Local
Module are not lit.
Cause: The Fiber 500m Pod Extender is
not receiving power.
Ensure the power adapter is securely connected
to either the Local Module or Remote Module
as appropriate and to a proper local power
supply outlet.
Link LEDs on the Local Module and
Remote Module are not lit.
Cause: The connection between the
Local Module and Remote Module is not
correct.
Ensure that the proper fiber optioc cable is
connected between the Remote Module and
Local Module.
Host LED on the Local Module and the
USB LED on the Remote Module are not
lit.
Cause:
a. The link between the Local Module
and the NetBotz appliance is not
correct.
b. The NetBotz appliance is not
functioning.
c. The NetBotz appliance does not
recognize the Fiber 500m Pod Extender.
1. Ensure all cables are securely connected.
2. Remove and then reconnect the power
adapter to the Fiber 500m Pod Extender.
3. Restart the NetBotz appliance.
USB port LED on Remote Module is not
lit.
Cause:
a. Connection between the pod and the
Remote Module is not correct.
b. The pod is malfunctioning.
c. The Fiber 500m Pod Extender is
malfunctioning.
1.Ensure the pod is securely connected to the
USB port on the Remote Module. If the USB
port LED on the Remote Module is still not lit:
2.Disconnect the Fiber 500m Pod Extender
from the NetBotz appliance.
3.Connect the pod directly to the USB port on
the NetBotz appliance.
4.If the pod is functioning properly when
connected directly to the NetBotz appliance:
a.Connect another pod (of a different type) to
the Fiber 500m Pod Extender.
b.If the second pod does not work, the Fiber
500m Pod Extender may be malfunctioning.
Contact Technical support for assistance.