Ness D16x Installation Manual

NESS D16x C-Bus™ Enabled
ALARM CONTROL PANEL
INSTALLATION & PROGRAMMING MANUAL
FOR D16x C-BUS OPTIONS
REVISION 1
NESS D16x C-BUS ENABLED CONTROL PANEL – PROGRAMMING MANUAL
NESS D16x C-BUS ENABLED CONTROL PANEL – PROGRAMMING MANUAL
FEATURING
• Ness D16x is a Fully Approved C-Bus Product
• Full Compatibility with Clipsal C-Bus commands
• Featuring 16 easily programmable C-Bus Events
• Multiple D16x events can operate C-Bus devices Unsealed zones End of exit delay Alarm condition Armed or Disarmed state
• C-Bus devices can arm the D16x
NESS D16x C-Bus Enabled ALARM CONTROL PANEL
This manual covers the C-Bus programming options of the D16x panel. For full D16x programming information see the Ness X Series Installation Manual (Part No. 890-007).
CONTROL PANEL FEATURES
• 8 or 16 alarm zones.
• Supports up to 3 remote LCD or LED keypads.
• 56 user codes can be programmed to operate by keypad PIN, radio key or access card.
• Optional Ness Radio Interface for fully integrated wireless security.
• Programmable 2 Area partitioning can split the panel into two independent areas plus a common area.
• Monitor Mode allows partial arming, (eg, permieter security overnight).
• Day Mode feature allows daytime monitoring of fire doors, coolrooms etc.
• Temporary Day Zone feature allows easy enabling/disabling of Day Mode.
• Keypad Panic feature.
• Keypad Duress feature.
• Two button arming feature.
• Fire Alarm feature with different siren tones.
• Highly flexible zone to output mapping.
• Onboard Vibration Sensor Analyser with programmable sensitivity. Use with Nessensor vibration sensors.
• Siren chirp and strobe flash on arming with radio key.
• Quiet chirps option on arm/disarm by radio key.
• True Dynamic Battery Test actively tests the battery under load every hour.
• 4 programmable auxiliary outputs.
• Automatic reset fuses.
• Programmable siren/reset lockout.
• 30 event memory from keypad.
• Standard defaults to suit most applications.
• Easy programming by keypad or NessComms software.
• All programming data is permanently stored in a non-volatile memory.
• All inputs and outputs are heavily protected against lightning and high voltage supply transients.
• Optional output expander.
DIALLER
• Full remote upload/download by PC and modem using NessComms software.
• Remote control of outputs via telephone.
• Contact ID Format - Two 14 digit phone numbers plus one “follow me” number.
• Audible format feature.
• Phone line monitoring (activates output).
• Dialler ‘Listen in’ option for installers.
• Auto Test calls.
• Pulse or DTMF dialling.
• True dial tone detection.
• Hex programmable client codes.
It is recommended that the C-Bus connection and configuration is performed by an installer who has attended a C-Bus Training Course.
C-BUS TRAFFIC CONSIDERATIONS
It is possible to configure the panel to send C-Bus commands each time a zone is unsealed (triggered), even when the unit is disarmed.
Use this facility with caution - particula rly with passive infrared detectors (PIRs) since the normal operation of some security devices may flood the C-Bus network with excessive communication.
Every time a PIR is triggered the D16x will put out a command on the C-Bus network via the C-Bus Interface.
Excessive C-Bus traffic will affect the performance of the C-Bus network. This does not completely negate this type of set up, however it must be limited in its implementation.
For example a PIR in an entry foyer could be used if the event was limited to the panel being armed, being when it pulses on a courtesy light or triggers a “welcome home scene”. This would not give any consideration for it being night or day without a logical device eg. Colour Touch or Pascal Logic Unit, residing on the network.
NESS D16x C-BUS ENABLED CONTROL PANEL – PROGRAMMING MANUAL
C-BUS INTERFACE INSTALLATION
3 Pin plug from C-Bus Interface plugs into the SERIAL socket on the D16x board.
C-Bus Interface fits in this left hand slide rail position in the D16x housing.
RE D w i r e fro m t h e C-Bus Interface connects to any +12V terminal on the D16x board.
C-Bus Positive (Blue + Orange) C-Bus Negative (Blue & White + Orange & White)
NETWORK BURDEN JUMPER This jumper is supplied in the OFF position and can be enabled if the C-Bus Network Burden is required. (Further information is available from Clipsal).
NESS C-BUS INTERFACE
4 Wire Loom for connection to D16x board.
C-Bus Negative: blue & white + orange & white
C-Bus Positive: blue + orange
Remote OFF: brown + brown & white
Remote ON: green + green & white
Remote On/Off is not used by the Ness C-Bus Interface
C-BUS WIRING
Note that the Ness C-Bus interface does not require all the C-Bus wire pairs.