Bridge the earth OUT terminal to earth RETURN terminal.
SANS 10222-3 or local
specifications
or local specifications
coupled to the fence
earth at any other point
Connection/Configuration Diagram
7
*JP4 – Bypass Safety Switch. Not to be installed during normal use.
JUMPER OPERATION:
Function
JP1
JP2
JP3
Energizer Operation
Gate Alarm
out
in
out
Switched Input delayed for 4 minutes with
energizer On only
Gate Alarm
in
out
out
Switched Input delayed for 1 minute with
energizer On only
Panic Alarm
out
out
out
Switched Input instantaneous (panic alarm)
with energizer On or Off
High/Low
Voltage Mode
in
in
out
Switched Input toggles the energizer between
High Voltage and Low Voltage mode
Remote On/Off
out
out
in
Switched Input acts as remote On\Off switch
Remote On/Off
indication and
Gate alarm
in
out
in
Strobe indicates fence is On or Off, Switched
Input delayed for 4 minutes with energizer On
only
Not yet available
out
in
in
Service Alarm disabled, Switch Input delayed
for 4 minutes with energizer On only
in
in
in
Reserved for factory use
All other Jumpers are reserved for factory use only
PC Board Replacement Procedures
8
REMOVAL
STEP 1: Disconnect mains power and the
battery terminals if connected.
STEP 2: Remove screws.
STEP 3: Remove all connectors
from PC Board.
STEP 4: Gently pullPCBoard
vertically upwardstoremove(connections
are on the back sideofthePCBoard).
REPLACEMENT
STEP 5: Gently push PC Board back into
place. Take care that the spade connectors
are correctly positioned before pushing the
PC Board into place. Also ensure that the
opto-coupler (looks like LED) is correctly
positioned before pushing the PC Board
into place.
STEP 6: Reconnect all connectors to thePC
Board.
STEP 8: Reconnect the battery terminals
and apply mains power.
Service Conditions
9
HOW TO CHECK: (ALL FUSES ARE 2 AMPERE FAST BLOW)
FUSE DESCRIPTION & FAULT SYMPTOMS
SUPPLY
BATTERY
SUPPLY: The power LED does not illuminate when the mains power is present
AUX: The siren and strobe does not function
BATTERY: The energizer switches off in the absence of mains power
AUX
Basic definitions
A fence used for security purposes which comprises an electric fence and a physical
General requirements for electric security fences
Appendix
10
• Electric Fence:
A barrier which includes one or more electric conductors, insulated from earth, to
which electric pulses are applied by an energizer
• Connecting Lead:
An electric conductor, used to connect the energizer to the electric fence or the
earth electrode
• Electric Security Fence:
barrier electrically isolated from the electric fence
• Public Access Area:
Any area where persons are protected from inadvertent contact with pulsed
conductors by a physical barrier
• Pulsed Conductors:
Conductors which are subjected to high voltage pulses by the energizer
• Secure Area:
An area where a person is not separated from pulse conductors below 1,5m by a
physical barrier
Electric fences shall be installed and operated so that they cause no electrical hazard to
persons, animals or their surroundings.
Electric fence constructions which are likely to lead to the entanglement of animals or
persons shall be avoided, as entrapment can be lethal.
An electric fence shall not be supplied from two different energizers or from independent
fence circuits of the same energizer.
For any two different electric fences, each supplied from a different energizer with
independent timing, the distance between the wires of the two electric fences shall be at
least 2.5m. If this gap is to be closed, this shall be affected by means of electrically nonconductive material or an isolated metal barrier.
Barbed wire or razor wire shall not be electrified by an energizer.
Any part of an electric fence which is installed along a public road or pathway shall be
the fence posts or firmly clamped to the fence wires. The size of the warning signs shall be
shall be indelible, inscribed on both sides of the warning plate and have a height of at least
cannot be avoided, it shall be made underneath the power line and as nearly as possible at
Appendix (continued)
11
identified at frequent intervals by prominently placed warning signs securely fastened to
at least 100mm x 200mm. The background colour of both sides of the warning plate shall
be yellow. The inscription on the plate shall be in black.
The warning sign shall typically appear as depicted in the figure below. The inscription
25mm.
Warning signs shall be placed at;
• each gate
• each access point
• intervals not exceeding 10m
• adjacent to each sign relating to chemical
hazards for the information of emergency services.
Gates in electric security fences shall be capable of being opened without the person
receiving an electric shock.
The energizer earth electrode shall penetrate the ground to a depth of at least 1m. The
distance between any electric security fence earth electrode and other earth systems shall
not be less than 2m.
Connecting leads that are run inside buildings shall be effectively insulated from the
earthed structural parts of the building. This may be achieved by using insulated high
voltage cable.
Connecting leads that are run underground shall be run in a conduit of insulating material
or else insulated high voltage cable shall be used. Care shall be taken to avoid damage to
the connecting leads due to external factors.
Connecting leads shall not be installed in the same conduit as the mains supply wiring,
communication cables or data cables.
Connecting leads and electric fence wires shall not cross above overhead power or
communication lines.
Mains supply wiring shall not be installed in the same conduit as signaling leads associated
with the electric security fence installation.
Crossings with overhead power lines shall be avoided wherever possible. If such a crossing
right angles to it.
If connecting leads and electric fence wires are installed near an overhead power line, the
clearances shall not be less than those shown in the table below.
If connecting leads and electric fence wires are installed near an overhead power line, their
receiving an electric shock unless they attempt to penetrate the physical barrier, or are in a
provided by the energizer. Protection from the weather shall be provided from the ancillary
Appendix (continued)
12
Power Line Voltage (V) Clearance (m)
Equal to or less than 1 000 3
Greater than 1 000 and equal or less than 33 000 4
Greater than 33 000 8
height above the ground shall not exceed 3m.
Where an electric security fence passes below bare power line conductors, the highest
metallic element shall be effectively earthed for a distance of not less than 5m on either
side of the crossing point.
This height applies either side of the orthogonal projection of the outermost conductors of
the power line on the ground surface, for a distance of:
• 2m for power lines operating at a nominal voltage not exceeding 1 000 Volts
• 15m for power lines operating at a nominal voltage exceeding 1 000 Volts
Electric security fences and their ancillary equipment shall be installed, operated and
maintained in a manner that minimizes danger to persons, and reduces the risk of persons
secure area without authority. Exposed conductive parts of the physical barrier shall be
effectively earthed.
A spacing of 2.5 m shall be maintained between uninsulated electric fence conductors or
uninsulated connecting leads supplied from different energizers. This spacing may be less
where conductors or connecting leads are covered by insulating sleeving, or consist of
insulated cables, rated to at least 10kV.
This requirement need not apply where the separately energized conductors are separated
by a physical barrier, which does not have any openings greater than 50mm.
A vertical separation of not less than 2m shall be maintained between pulsed conductors
fed from different energizers.
Ensure that all ancillary equipment connected to the electric security fence circuit provides
a degree of isolation between the fence circuit and the supply mains equivalent to that
equipment unless this equipment is certified by the manufacturer as being suitable for use
outdoors, and is of a type with a minimum degree of protection IPX4.
• Keep the wires to the fence separate from the keypad, gate, siren, strobe and
mains wiring.
• Never use the energizer battery to power a radio alarm transmitter or alarm panel.
• Always test the fence after installation for correct short and open-circuit alarming at
Installation Notes
13 14
• Do not try and modify the energizer. Any unauthorized modifications will null and
void the warranty and possibly render the unit illegal.
• If the external On/Off facility is used, the wire between the remote switch and the
• A remote receiver can obtain 12VDC from the keypad bus. Current consumption
• The siren and strobe lights together must not draw more than 1.8Amps.
• The wire between the magnetic gate switch and the energizer can be up to a 100m
• Use HT (high voltage) wire between the fence and energizer, including the earth
• Always use ferrules or line clamps to connect two high voltage wires together.
• The fence must be earthed properly with three earth electrodes close to the
• When replacing the front of the energizer, hook the top in first while holding it an
energizer can be up to a 100m in length. The switch contact must be open for the
fence to be energized.
must not exceed 0.1 Amps. This is not sufficient to supply power for an armed
response transmitter.
in length, but must not run parallel with any fence wires. The gate switch must be
open circuit if the gate is open.
wire. Never run these wires in the same conduit or through the same hole as the
low voltage wiring.
Avoid using dissimilar materials for connections like copper on steel.
energizer. The distance between the fence earth electrode and any other earth
systems shall be not less than 2m for a security fence installation (typically a
suburban property installation) and 10m for an agricultural fence installation
(typically a rural property installation).
angle and then push it closed at the bottom. Fasten the lid down with the two cap
screws.
various points along the fence.
• Do not use the energizer with non-rechargeable batteries.
• The energizer contains a sealed lead-acid battery that will vent to the atmosphere
under certain conditions. For this reason it is imperative that the energizer be
• Refer to the applicable laws and regulations concerning the installation of electric
installed in a well ventilated area.
fences in your country and area.
IEC Safety Information
• There are no user serviceable parts inside the energizer.
• If the supply cord is damaged, it must be replaced by the manufacturer, its
service agent, or similar qualified persons in order to avoid a hazard.
• This appliance is not intended for use by persons (including children) with
• Electric fencing can be lethal. Avoid head contact with the fence.
reduced physical, sensory or mental capabilities, or lack of experience and
knowledge, unless they have been given supervision or instruction concerning
use of the appliance by a person responsible for their safety.
Ask the installer to explain the options of current limiting resistors.
Rev 1.2, 20 June 2016
Updated for Wizord 2i
Print Code: MO 024
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.