SELF-REGULATING HEATING CABLE FOR FIRE SPRINKLER SYSTEMS – Product Guide
Page 2
THE COMPLETE FREEZE PROTECTION SYSTEM
Nelson self-regulating electric heat trace cables are now listed and certied for freeze protection from main water lines to
sprinkler heads.
Recent NFPA 13 changes have approved self-regulating cables for use with branch sprinkler systems to ensure reliable re suppression
in unheated commercial and industrial facilities.
Nelson freeze protection is inexpensive to run, with virtually no maintenance needed. It also contributes to improved re safety, since
sprinkler systems can respond immediately without the need for antifreeze chemicals.
SELF-REGULATING CABLES
Nelson CLT and LT Series heating cables are available for both 120
and 208-277 Vac applications, with a choice of power densities
to provide freeze protection in ambient temperatures as low as
–40°C (–40°F). These cut-to-length cables can be used in wet or dry
environments. The LT Series is also approved for hazardous locations
when used with appropriate connection kits.
CONNECTION KITSSelf-Regulating Cables
A complete selection of connection kits and accessories are available
for spicing cables under pipe insulation or in a rugged NEMA 4X
enclosure for exceptional weather and corrosion resistance.
MONITORING AND CONTROL
Choose from a range of industrial thermostats, cable monitoring
systems and circuit management systems for simple, reliable
operation of any heating cable conguration. Nelson offers ordinary
and hazardous location controls with approvals and certications for
practically any application.
Connection KitsMonitoring and Control
A SIMPLER AND SAFER FREEZE PROTECTION SOLUTION
Nelson freeze protection overcomes the safety shortcomings of other methods.
Nelson’s re protection system is ideally suited for garages,
warehouses, porticos and other unheated commercial or industrial
locations where branch sprinkler systems are used for re protection.
Because the system is always charged with water, there is less risk of
corrosion due to trapped moisture and air.
Electricity costs are minimal because Nelson’s self-regulating cables
and temperature controls apply heat only where and when it is
needed.
APPROVALS
The NFPA 13, 2010 Edition, Standard for the Installation of Sprinkler
Systems allows listed electrical heat tracing to be utilized for freeze
protection of supply lines, standpipes, and branch lines containing
sprinklers.
Nelson CLT and LT Series self-regulating cable systems are approved
to the following standards:
• cCSAus Certied to the IEEE standard . 515.1-2012 in the United
States for supply lines, standpipes, branch lines and sprinkler
heads.
• CAN/CSA C22.2 No. 130-03 in Canada for supply lines,
standpipes, branch lines and sprinkler heads.
• UL Listed for supply lines, standpipes and branch lines not
containing sprinklers.
With dry systems, valves control water ow. As a result, water takes longer
to reach the sprinklers from the source. Nelson products ensure that water
is immediately available at each sprinkler head in the event of a re.
No antifreeze is needed, eliminating the possibility of chemicals leaking into
drains and ground water. If a re does occur, no chemicals are sprayed in
the facility or equipment.
Page 3
STEP 1: CALCULATING HEAT LOSS REQUIREMENTS
To determine the heat loss that must be replaced by the heating cable,
the following should be determined:
• Tf: Fluid Temperature to be maintained
• Ta: Minimum ambient temperature
• Size of pipe to be heated
• Thermal insulation – type and thickness
TABLE 1: PIPE HEAT LOSS ( WATTS/FT )
Insulation Thickness
mm (in)
25 (1.0)
38 (1.5)
50 (2.0)
63 (2.5)
75 (3.0)
Insulation Thickness
mm (in)
25 (1.0)
38 (1.5)
50 (2.0)
63 (2.5)
75 (3.0)
Note: Multiply heat loss values by 3.28 for Watts/m.
Determine the temperature differential to be maintained by subtracting
the ambient temperature from the uid temperature to be maintained.
(Tf – Ta )
HEAT LOSS
Use Table 1 to look up the heat loss for the proper pipe diameter and
thickness of insulation. If a rigid insulation such as calcium silicate is used,
the insulation should be oversized to the next available size. All insulations
should be sized to provide adequate space for the heating cable and allow
the joints to properly seal. The heat loss values in Table 1 include a 10%
safety factor.
Page 4
STEP 1: CALCULATING HEAT LOSS REQUIREMENTS
ADJUSTMENTS TO HEAT LOSS VALUES
The heat loss values in Table 1 are based on glass ber insulation. If
other insulations are used, multiply the heat loss value by the correction
factor shown in Table 2 for your specic insulation. Heat losses are based
on outdoor applications with 20 mph wind. If piping is located indoors,
multiply the heat loss value by 0.9.
Any thermally conductive item that protrudes through the thermal
insulation will require additional heat to be applied to the pipe. The
footage shown in Table 3 and Table 4 should be added to the required
heater cable length to compensate for these extra heat loss areas. When
multiple traces are required, increase the cable adders proportionally.
Based on K factor @ 50°F ( 10°C )
mean temperature ( BTU/hr-°F-ft²/inch )
Calculate Temperature DifferentialAdjustments to Heat Loss (QM)
ΔT = Tf – Ta
ΔT = +4 – (-23)°C
ΔT = +27°C
Heat Loss (Q)
Use Table 1 to nd heat loss. Where desired temperature falls
between two values, use interpolation. From Table 1:
@ +27°C ΔT
Q = 6.2 Watts/m
ΔT = Tf – Ta
ΔT = +40 – (-10)°F
ΔT = +50°F
@ +50°F ΔT
Q = 1.9 Watts/ft
Adjust the heat loss for exible elastomer. From Table 2, the correction
factor is 1.16.
QM = Q x 1.16
QM = 6.2 Watts/m x 1.16
QM = 7.2 Watts/m
Since the piping is indoors, an adjustment is necessary for the absence of
wind. If piping is located indoors, multiply the heat loss value by 0.9.
QM = 7.2 Watts/m x 0.9
QM = 6.5 Watts/m
QM = Q x 1.16
QM = 1.9 Watts/ft x 1.16
QM = 2.2 Watts/ft
QM = 2.2 Watts/ft x 0.9
QM = 2.0 Watts/ft
Page 5
STEP 2: SELECT THE PROPER HEATING CABLE
30
0
Nelson Type CLT self-regulating heater cable is a parallel circuit electric
heater strip. An irradiation cross-linked conductive polymer core material is
extruded over the multi-stranded, tin-plated, 18-gauge copper bus wires.
The conductive core material increases or decreases its heat output in
response to temperature changes. A thermoplastic elastomer dielectric
jacket is then extruded over the conductive core. A copper braid is
installed over this jacket providing a continuous ground path. A UV
stabilized thermoplastic elastomer overjacket is provided to cover the
braid for wet applications and exposure to the sun.
Nelson Type LT self-regulating heater cable is a parallel circuit electric
heater strip. An irradiation cross-linked conductive polymer core material is
extruded over the multi-stranded, tin plated, 16-gauge copper bus wires.
The conductive core material increases or decreases its heat output in
response to temperature changes. Two jackets provide extra dielectric
strength, moisture resistance, and protection from impact and abrasion
damage. The inner thermoplastic jacket is extruded over and bonded to
the core material. A thermoplastic elastomer outer jacket is then extruded
over the inner jacket. A stranded tinned copper metal braid is supplied on
all heaters. An optional overjacket (uoropolymer or modied polyolen)
can be specied when the heater cable is to be installed in wet or corrosive
environments.
FIGURE 1: POWER OUTPUT ON METAL PIPE
CLT SELF-REGULATING HEATER CABLE
33 (10)
30 (9)
26 (8)
23 (7)
20 (6)
16 (5)
13 (4)
10 (3)
7 (2)
3 (1)
WATTS PER METER (WATTS PER FOOT)
0
C
B
A
-1
(30)5 (40)
10
15
405060708090100110120130140150
(50)
(5)
(10)(15)
(60)
21
(70)
(21)
27
(80)
(27)
32
(90)
(32)(38)
Temperature °C (°F)
When selecting the proper heater cable, you should verify the following
conditions:
• Maintain Temperature
• Supply Voltage
• Piping Material
CABLE SELECTION
When selecting the heating cable with the desired power output, match a
cable from Figure 1 greater than or equal to the heat loss value in Step 1.
For designs requiring more than a single run of cable, use multiple runs of
the same wattage cable to meet the heat loss requirements.
VOLTAGE ADJUSTMENT
Use of products at other than nominal voltages requires minor
adjustments in power and maximum circuit lengths. Use Power
Adjustment Multiplier from Table 4 to verify that cable selected still meets
the desired power output conditions.
PIPING MATERIAL
The actual power output of the cable is affected by the installed piping
material. If the piping system is non-metallic, additional adjustments must
be made based on the specic piping material. Please consult a product
representative for technical assistance.
A CLT3-JT
CLT23-JT
B CLT5-JT
CLT25-JT
C CLT8-JT
CLT28-JT
65
60
54
49
43
38
(100)
(110)
(43)
(120)
(49)
(130)
(54)
(140)
(60)
(150)
(65)
LT SELF-REGULATING HEATER CABLE
39 (12)
36 (11)
33 (10)
30 (9)
26 (8)
23 (7)
20 (6)
16 (5)
13 (4)
WATTS PER METER (WATTS PER FOOT)
10 (3)
7 (2)
3 (1)
0
D
A LT3
(150)
LT23
B LT 5
LT25
C LT8
LT28
D LT10
LT210
65
C
B
A
-1
(30)
10
(50)
21
(70)
32
(90)
(110)
43
(130)
54
Page 6
STEP 2: SELECT THE PROPER HEATING CABLE
TABLE 3: PERFORMANCE AND RATING DATA
Maximum
Catalog NumberNominal Voltage
Segment Length
m (ft)
CLT SELF-REGULATING HEATER CABLE
CLT3-JT12067.4 (221)65 (150) 85 (185)
CLT23-JT240162.5 (533)65 (150) 85 (185)
CLT5-JT12054.3 (178)65 (150) 85 (185)
CLT25-JT240139.6 (458)65 (150) 85 (185)
CLT8-JT12043.3 (142)65 (150) 85 (185)
CLT28-JT240105.8 (347)65 (150) 85 (185)
Catalog NumberNominal Voltage
Maximum
Segment Length
m (ft)
Maximum Maintenance
Temperature
°C (°F)
LT SELF-REGULATING HEATER CABLE
LT312099.1 (325)65 (150) 85 (185) T6
LT23240198.1 (650)65 (150) 85 (185) T6
LT512082.3 (270)65 (150) 85 (185) T6
LT25240164.6 (540)65 (150) 85 (185) T6
LT812064.0 (210)65 (150) 85 (185) T5
LT28240128.0 (420)65 (150) 85 (185) T5
LT1012054.9 (180)65 (150) 85 (185) T5
LT210240109.7 (360)65 (150) 85 (185) T5
Electrical equipment T rating codes dene the maximum surface temperature that equipment will reach. It is used in hazardous (classied) area applications.
The total cable requirements are based on the pipe lengths plus adders.
PIPING REQUIREMENTS
Multiply the length of each pipe by the number of cable runs required.
PIPING ADDERS
Additional heating cable will be required for heat sinks which increase the
total heat loss of the piping system. Add the footages from Table 5 to the
calculated piping requirements.
SPRINKLER ADDERS
Additional heating cable will be required for sprinklers which increase the
total heat loss of the piping system. Add the footages from Table 6 to the
calculated piping requirements and piping adders.
TABLE 5: HEAT LOSS ADDERS FOR VALVES, PIPE SUPPORTS AND FLANGES
Additional Heater Length in Meters (Feet) for Various Heat Sinks
Adders are for various inline pipe ttings to compensate for greater areas of heat loss.
Note: For design conditions requiring more than a single run of heater cable, the values shown are required for each cable run.
Total cable length is determined from the sum of the previous calculations.
Total Length = Piping Requirements + Piping Adders + Sprinkler Adders
Refer to gures in the Installation and Maintenance Information section for
specic installation details for sprinkler heads with sprigs, sprinkler heads
without sprigs, and dry pendant sprinklers in freezer installations. This
information is to be used together with the Installation and Maintenance
Manual for Self-Regulating Heater Cable, document number GA-1765 and
Installation Instructions for Branch Sprinkler Systems, document number
GA-1935.
TABLE 6: HEAT LOSS ADDERS FOR SPRINKLERS
Sprinkler without sprigSprinkler with sprigDry sprinkler for freezer installations
(Refer to Figure 3)(Refer to Figure 4)(Refer to Figure 5)
4x pipe diameter2x sprig length2x drop length
Additional Heater Length in Feet for Sprinklers
Page 8
STEP 4: DETERMINE ELECTRICAL LOAD REQUIREMENTS
To determine the electrical requirements for your project, you must
determine the number of circuits and calculate the transformer loading.
To calculate your electrical requirements, you will need the following:
• Total cable length
• Supply voltage
• Minimum ambient/start-up temperature
NUMBER OF CIRCUITS
Use Table 4 and Table 7, if necessary, to determine your maximum circuit
length allowed. Divide your total cable length by the maximum length
to determine the number of electrical circuits required. To reduce
distribution costs, select the smallest branch circuit breaker rating as
possible.
CALCULATE TRANSFORMER LOADING
Using your selected supply voltage, use Table 8 to calculate your Amp/
VOLTAGE ADJUSTMENT
Use of products at other than nominal voltages requires minor
adjustments in power and maximum circuit lengths. Use Length
Adjustment Multiplier from Table 4 or Table 6 to verify adjusted maximum
circuit lengths.
Ft value at your selected minimum ambient/start-up temperature. To
calculate your transformer load, use the following formula:
Amps/Ft x total cable length x supply voltage / 1000 =
Transformer Load (kVA or kW)
TABLE 7: CIRCUIT BREAKER SELECTION
Max. Length in Meters (Feet) Vs. Circuit Breaker Size
1. Circuit breakers are sized per national electrical codes.
2. When using 240 volt product at 208, 220 or 277 volts, use the circuit adjustment factors shown in the Voltage Adjustment Table.
3. When using 2 or more heater cables of different wattage ratings in parallel on a single circuit breaker, use the 15A column amperage of 15 amps, divide it by
the maximum footage to arrive at an amps/foot gure for each cable. You can then calculate circuit breaker sizes for these combination loads. These amps/
foot factors include the 125% sizing factor.
4. National electrical codes require ground-fault equipment protection for each branch circuit supplying electric heating equipment. Exceptions to this
requirement can be found in the 2002 N.E.C.
5. Heater cables with D1 optional construction require the use of ground fault interrupter/ground leakage device with a trip setting no greater than 30mA.
Multiply transformer sizing by 3.28 for Amps/m.
Note: For start-up temperatures other than those shown above, interpolation may be used for sizing accuracy.
Nelson’s PLT Series non-metallic connection kits are UL (Underwriter's
Laboratory) and CSA (Canadian Standards Association) approved for use
in freeze protection application for wet sprinkler piping systems when
used with approved Nelson heating cables. PLT Series connection kits are
approved for use with all Nelson CLT and LT Series eld-fabricated heating
cables.
FIGURE 3: TYPICAL FREEZE PROTECTION SYSTEM FOR SPRINKLER LINES
LT-ST Tee Splice
Connecon Kit
PLT-BC Power
Connecon Kit
CM-2201 Electronic
Controller
Enclosures supplied in PLT Series connection kits are rated NEMA 4X. In
addition to power connection kits and end seals, Nelson also provides
splice connections, tee splice connections and associated accessories as
required to complete your entire heat tracing installation.
Thermal
Insulaon
LT-ME End Seal or PLT-L
Heang Cable
Oponal Lighted End Seal
Sprinkler Head
on Sprig Piping
TABLE 9: CONNECTION KITS AND GENERAL ACCESSORIES
Catalog NumberUnits EachDescription
PLT-BC-J-31Power Connection Kit for 1/2" to 3” diameter pipe
PLT-BC-J-121Power Connection Kit for 3 1/2" to 12” diameter pipe
PLT-BC-J-201Power Connection Kit for 12 1/2" to 20” diameter pipe
PLT-BS-U-31Splice Connection Kit for 1/2" to 3” diameter pipe
PLT-BS-U-121Splice Connection Kit for 3 1/2" to 12” diameter pipe
PLT-BS-U-201Splice Connection Kit for 12 1/2" to 20” diameter pipe
PLT-L(X)-J-31Lighted End Seal for 1/2" to 3” diameter pipe, replace (X) with voltage
PLT-L(X)-J-121Lighted End Seal for 3 1/2" to 12” diameter pipe, replace (X) with voltage
PLT-L(X)-J-201Lighted End Seal for 12 1/2" to 20” diameter pipe, replace (X) with voltage
LT-SS5Splice Connection Kit, heat shrink version
LT-ST5Tee Splice Connection Kit, heat shrink version
GT-61Fiberglass Tape, 18 meters (60 feet)
GT-601Fiberglass Tape, 55 meters (180 feet)
AT-501Aluminum Foil Tape, 46 meters (150 feet)
WS-1001Warning Signs
LT-ME5End Seals, molded silicone
LT-MP5Power End Terminations, molded silicone
LT-SE5End Seals, heat shrink version
LT-SP5Power End Terminations, heat shrink version
Note: PLT Series Connection Kits include both the end seal and/or power end terminations for a single heat tracing segment. Additional components may be
required based on the specic piping system conguration.
Page 11
Addional heang cable, see TABLE 6 for specific requirements
Thermal Insulaon, install per NFPA13
recommendaonsfor sprayshadowing
INSTALLATION AND MAINTENANCE INFORMATION
For proper installation of Nelson CLT and LT Series heating cables on sprinkler piping, refer to the details below. These details are
supplemental to the Installation and Maintenance Manual for Self-Regulating Heater Cable, document number GA-1765 and Installation
Instructions for Branch Sprinkler Systems, document number GA-1935.
FIGURE 3: SPRINKLER HEAD WITHOUT SPRIG
Thermal Insulaon, install per NFPA 13
recommendaons for spray shadowing
Addional heang cable, see TABLE 6
for specific requirements
FIGURE 4: SPRINKLER HEAD WITH SPRIG
Thermal Insulaon, install per NFPA 13
recommendaons for spray shadowing
Addional heang cable, see TABLE 6
for specific requirements
FIGURE 5: DRY PENDANT SPRINKLER IN FREEZERS
Freezer wall thermal insulaon
1. The illustrations in Figures 3 – 6 are basic examples of various sprinkler installations and are for reference only. For sprinkler and/or sprinkler piping not
reected in these details, please consult your local representative for optional recommendations.
2. Use on insulated appropriately Listed or Certied steel schedules 5, 10, 20 and 40 standpipe, supply lines, and branch lines containing sprinklers up to and
including 6 inch size. Includes use on elbows, tees, anges, hangers and valves. Appropriately Listed or Certied berglass insulation with a k-factor of 130140 W/m-K @ 24°C (0.25-0.27 BTU-in / hr-°F-ft
3. For systems having piping which connects between buildings, in unheated areas, coolers or freezers where the temperature is -40°C (-40°F) or greater.
4. For use in Ordinary Hazard Occupancies only as specied in NFPA 13 the Standard for the Installation of Sprinkler System. The system must comply with the
obstruction requirements of NFPA 13 so that the thermal insulation over the trace heating does not unacceptably obstruct the sprinkler or cover the
wrench boss.
5. For use with sprinkler heads with a temperature rating of 68°C (155°F) or higher.
2
@ 75°F) with weatherproof cladding must be used.
Addional heang cable, see TABLE 6
for specific requirements
Page 12
Emerson brings integrated manufacturing
solutions to diverse industries worldwide.
Our comprehensive product line, extensive
experience, world-class engineering and
global presence enable us to implement
solutions that give our customers the
competitive edge. Nelson Heat Trace is our
industrial line of heating cables solution.
They provide a full line of products and
expertise for the powering, controlling and
monitoring of pipeline temperatures.
For over 150 years, our electrical product
brands have been providing a rich tradition
of long-term, practical, high quality
solutions with applications ranging from
the construction and safe operation of
petrochemical and process plants to
providing quality power that precisely
controls automotive robotic production.
Engineers, distributors, contractors,
electricians and site maintenance
professionals around the world trust
Emerson brands to make electrical
installations safer, more productive and
more reliable.
The Appleton Group business unit of Emerson
is organized into three focused groups that
provide distributors and end users expert
knowledge and excellent service.
Electrical Construction Materials
This group is made up of the Appleton and
O-Z/Gedney brands. They manufacture
a broad range of electrical products
including conduit and cable ttings, plugs
and receptacles, enclosures and controls,
conduit bodies and industrial and hazardous
lighting. Whether the application is hazardous
location, industrial or commercial, the
electrical construction materials group has
the products to meet your needs.
Power Quality Solutions
The SolaHD brand offers the broadest
power quality line, including uninterruptible
power supplies, power conditioners, voltage
regulators, shielded transformers, surge
protection devices and power supplies.
Heating Cable Systems
This group is made up of the EasyHeat
and Nelson brands. They offer a broad
range of electrical heating cable products
for residential, commercial and industrial
applications.