Nelson GA-1935, Branch Sprinklers, Nelson Heat Trace Type CLT and LT Self-Regulating Heaters Installation Instructions

NELSON
INSTALLATION
HEAT TRACING FOR BRANCH SPRINKLER SYSTEMS
INSTRUCTIONS
DESCRIPTION
These are supplementary instructions specific to the installation of heating cable on branch sprinkler systems and are to be used together with the installation and maintenance instructions for self-regulating heater ca ble (GA-1765).
HEAT TRACING SYSTEMS RELATED TO FIRE PROTECTION SERVICE
For use with all wattages of CLT, LT heater cables at 120, 208, 240 and 277V.
For use in Fire Protection Service:
1. Use on insulated appropriately listed or certified steel schedules 5, 10, 20 and 40 standpipe and sprinkler system pipe up to and including 6 inch size. Includes use on elbows. tees, flanges, hangers and valves a s shown (see Nelson instruction booklet #GA-1765). Appropriately listed or certified fiberglass insulation with a k-factor of 0.25-0.27 BTU-in / hr-°F-ft
2
@ 75oF (130-140 W/m-K @ 24oC) must be used. In locations that
may be exposed to moisture weatherproof cladding must be used.
2. For systems having piping which connects between buildings, in unheated areas, coolers or freezers where the temperature is at or above -40
o
F (-40oC).
3. For use in Ordinary Hazard Occupancies only as specified in NFPA 13 the Standard for the Installation of Sprinkler System. The system must comply with the obstruction requirements of NFPA 13 so that the thermal insulation over the trace heating does not unacceptably obstruct the sprinkler or cover the wrench boss.
4. Fire Suppression system heater circuits must be connected to monitoring equipment. A listed Power Supervisory Relay with the appropriate voltage coil shall be connected in parallel prior to the heat tracing. The output contacts of the Listed Fire Control Panel must have provisions for supervisory circuits.
5. For use with sprinkler heads with a minimum temperature rating of 155oF (68oC).
6. For proper selection of heating cable and connection kits refer to the Nelson Sprinkler Design Guide #GA-
2499.
Note: For Nelson Heat Trace Cable Installation see our Installation & Maintenance Manual #GA-1765.
Branch – Short Sprig Up In Line Sprinkler
P.O. BOX 726 TULSA, OK 74101 TEL 918-627-5530 FAX 918-641-7336 www.nelsonheaters.com
GA-1935 Rev. 1
Sheet 1 of 3
NELSON
INSTALLATION
HEAT TRACING FOR BRANCH SPRINKLER SYSTEMS
Tee-Splice Kit
INSTRUCTIONS
Branch – Long Length Insulation – Short Sprig Branch
Insulation – In Line Sprinkler
Insulation – Vertical Pendant Mounted Sprinkler Head
P.O. BOX 726 TULSA, OK 74101 TEL 918-627-5530 FAX 918-641-7336 www.nelsonheaters.com
GA-1935 Rev. 1
Sheet 2 of 3 May 2015