
Installation And Maintenance Instructions
HEAT TRACING TEMPERATURE SWITCH
FOR HAZARDOUS LOCATIONS
Model TH7325
Line sensing bulb and capillary type
Model
TH7325-2
DPST Relay - Line sensing bulb and
cappilary type
Model
TA7140
Ambient sensing probe type
Description
The remote bulb and capillary types are used to
sense the fluid media temperature.
The local mount types are used to sense ambient
temperatures for freeze protection applications.
Caution: Sensing bulb and probe must not
exceed specified proof temperatures.
Installation
Caution: This switch should be installed by a
trained service person.
Switch
Mounting: Switch may be mounted in any position.
Wiring (continued)
Electrical Connection:
Clamping screw terminals on insulated terminal block
via 3/4 NPT (female) conduit connection. Use only
copper conductors, 75°C rated for standard SPDT snap
switch models, & 125°C rated for relay model (TH7325-2).
Standard SPDT snap-switch models TH7325 &
TA7140, may be wired normally open or normally closed,
per Figures 1 - 4. Contact positions (C, NO, NC) are
clearly identified next to terminal block.
Wire code for built-in jumper wire to terminal block:
Purple = Common, Blue = NC, Red = NO
DPST Relay model TH4X325-2, may be wired per
Fig. 5. Circuit 1 (2 positions) are for first conductor of
heating cable & first phase of power supply.
Circuit 2 (2 positions) are for second conductor of
heating cable & second phase of power supply. Contact
positions for both circuits are clearly identified next to the
terminal block. Note that the other 2 positions of the
terminal block are not used.
Relay contacts for both circuits are wired to close
on falling (decreasing) temperature.
The braid of heating cable must be connected to the
ground screw provided on every switch.
Testing of the Switch
Sensors: Install bulb toward the bottom of pipe or
vessel, away from heat sinks and appro-
ximately 90° from the heat tracing cable.
Always secure both bulb and capillary
and wrap with proper insulating tape.
Orient the local mount probe for optimal
ambient temperature sensing, away from
heat sources or heat sinks.
Enclosure: Type NEMA 4.
Enclosure temperature limits:
-40 °F to 140 °F (-40 °C to 60 °C)
Wiring
All electrical wiring must comply with local and
national electrical codes.
Caution: Electrical rating must be within range
stated on switch nameplate. Failure to
stay within rating may result in damage
to, or failure of electrical contacts.
Electrical
Rating: Standard Switch 22A @ 125,250,480 VAC.
DPST Relay: Coil - 240VAC, 4VA
Contacts - 22A @ 208/240VAC.
Testing of the switch may be done before or after final
installat ion. If bench tested, the switch should be retested when installed in the final application. Be sure
switch can be tested without affecting other equipment.
Check nameplates for elec trical rating and circuitry
(normally closed or normally open) of switch. Cycle
switch a few times to check operation.
Set-Point Adjustment
Turn adjustment knob counter-clockwise to increase set-point.
Agency Approvals
Hazardous Locations (Division I)
Class I, Groups B,C & D
Class II, Groups E, F & G
Class III
File No. E58658 File No. LR34556
Job Identification 1Z1A0.AE
APPROVED
0081
LCIE 07 ATEX 6093 X
II 2 G D
Ex d IIC T6 *
Ex tD A21 IP6X T80°C*
-40°C < Tamb < +60°C
* Relay Model - T4, T130°C
NELSON HEAT TRACING SYSTEMS, Tulsa, OK 74146 Bulletin No. 27278-AD 3-10-08 1 of 3

Troubleshooting
Warning: Disconnect electrical power supply to
switch before removal or inspection.
Failure to observe this warning could
result in serious injury or switch damage.
Important: The switch is
not field-repairable. In
case of damage, replace entire switch.
Causes of improper operation:
1. Incorrect electrical connection: check leads to
swi tch. Be sure they are properly connected.
See “Wiring” section for circuitry color code.
2. Faulty control circuit: check electrical power
supply to switch. Check for loose or blown fuses,
open-circuited or grounded wires, loose connections
at switch.
3. Incorrect temperature: check temperature in
system. Temperature must be within range
specified on nameplate.
4. Excessive vibration: check for temperature
fluctuations in system. Check switch mounting
and be sure there is no excessive vibration.
If the operation of the swi tch cannot be corrected
by the above means, consult factory or authorized
factory representative.
For service or ordering information
Consult factory or authorized factory representative.
Specify full catalog number (with any optional modifications or factory set-point) as shown on part
number code.
Warranty
All products of the company are sold and all services
are offered subject to the company's standard conditions of sale.
TEMPERATURE RANGE
SWITCH
NUMBER
TA7140
TH7325
TH7325-2
ADJUSTABLE RANGE
15 TO 140 °F (-9 TO 60 °C)
25 TO 325 °F (-4 TO 163 °C) -40 TO 420 °F (-40 TO 215 °C)
25 TO 325 °F (-4 TO 163 °C) -40 TO 420 °F (-40 TO 215 °C)
BULB SENSOR EXPOSURE
LIMITS (PROOF)
-40 TO 160 °F (-40 TO 71 °C)
REMOTE BULB AND
CAPILLARY MODEL
TIGHTEN 4mm SET SCREW
TO LOCK COVER IN PLACE
AFTER FIELD WIRING
Ø 5/16
8
8
203
MAX
Ø 1/16
2
6 9/16
167
4 1/2
114
ADJUSTING K NOB
REMOV E COVER
TO ADJU ST
FM
APPROV E D
THERMOSTAT FOR
HAZARDOUS LOCATIONS.
CLASS I
GROUPS: B, C & D
CLASS II
GROUPS: E, F & G
CLASS III
SWITCH NUMBER MEDIA TE
4 1/2
114
TEMPERATURE SWITCH
TYPE 4
LISTED
R
366S
ADJUSTABLE RA NGE
ELECTRICAL RATINGS
ELECTRICAL RATINGS
F
50 100
C
LOCAL MOUNT MODEL
4
102
008 1
II 2 G D
EEx d IIC T6
LCIE 02 ATEX 6206
Tamb -40 %%dC
F
500
C
DIMENSIONS IN BOXES
ARE IN MILLIMETERS
Ø 9/32 MOUNTING HOLE 4 PLACES
7
4
102
1/2
13
(INTERNAL)
HEX
1 HEX
25
INTERNAL
GROUND SCR EW
WITH CLAMP
TERMINAL BLOCK
ACCEPTS #16-#10 AWG
LEAD WIRES
102
4
3/4 NPT
FEMALE
CONDUIT
6 FOR RELAY MODEL ONLY
152
1 7/32
30
3/8
10
2
51
EXT ERNAL
GROUND
SCREW
WIT H
CLAMP
NELSON HEAT TRACING SYSTEMS, Tulsa, OK 74146 Bulletin No. 27278-AD 3-10-08 2 of 3

Installation Instructions
Installing the Thermostat
1. Verify that the thermostat is suitable for the area where it is to be
installed.
2. Check the line voltage and the heat-tracing load to ensure that the
Conduit
drain
thermostat ratings are not exceeded.
3. Mount the unit in a position that prevents condensation from draining
into the enclosure from the connecting conduit, (see diagram at left).
Positioning the Sensor Bulb (Line Sensing)
Single traced
90°
Heating cable
Control thermostat bulb
Tap e
4. Position the bulb in the lower quadrant of the pipe as shown in the
diagrams to the left. Place the bulb at least three feet from pipe
supports, valves, or other heat sinks; protect the capillary from kinks
or bends less than 1/2 inch in radius.
5. Tape the bulb firmly to the pipe with aluminum tape, making sure
Double traced
Heating cable
Control thermostat bulb
Tap e
Setting the Thermostat
there is no air space between the bulb and pipe. Do not overlap the
bulb and heating cable with the same piece of tape.
6. Set the thermostat dial to the desired temperature, then finish wiring.
7. Complete insulating. Do not turn the system on until the bulb is
covered with thermal insulation.
8. Fill the piping or tank. Once the thermostat has begun to cycle, check
the fluid temperature with an immersed thermostat (best for plastic
systems) or an accurate temperature indicator. Adjust the dial
setting, if necessary.
Wiring
GFEPD
Ø
208-V or 240-V supply … 240-V heater
Ø
or
G
120-V supply … 120-V heater
Ø
N
277-V supply … 240-V heater
C
NO NC
Power
G
connection
Thermostat bulb
(see "Positioning”
Braid
instructions above
for mounti ng de tails)
Heating
Cable
Figure 1. Pipe-sensing
Power supply
GFEPD
G
208-V or 240-V supply … 240-V heater
Ø Ø
Power
G
Ø Ø
connection
Braid
Heating
cable
Circuit1
Circuit2
Control
thermostat
Control
thermostat
Thermostat bulb
(see "Positioning”
instructions above
for mounti ng de tails)
GFEPD
Ø
Ø
208-V or 240-V supply
or
ØGN
120-V supply … 120-V heater
277-V supply … 240-V heater
C
NO N C
Alarm
Thermostat bulb
(see "Positioning”
instructions above
for mounti ng de tails)
Figure 2. Low-temperature alarm
Rela y
Figure 5
. Heat-tracing control
Control
thermostat
GFEPD
Ø
Ø
208-V or 240-V supply
or
ØGN
120-V supply … 120-V heater
277-V supply … 240-V heater
C
NO NC
Alarm
Thermostat bulb
(see "Positioning”
instructions above
for mountin g de tails)
Control
thermostat
Figure 3. High -tempera ture alarm
GCNANBNCØBØ
Braid
Heating
cable A
GFEPD
Heating
cable B
120- V supply … 120-V heater or
Ø
C
277-V supply … 240-V heater
120-V or
277-V
coil
Heating
cable C
NONC
NC
NO
C
Figure 4. Contactor control
For switching heat-tracing loads greater than 22 A
or switching multiple heat-tracing circuits.
C
Control
thermostat
Thermostat bulb
(see "Positioning”
instructions above
for mounti ng de tails)
Important: All information, including illustrations, is believed to be reliable. Users, however, should independently evaluate the suitability of each
product for their particular application.
NELSON HEAT TRACING SYSTEMS, Tulsa, OK 74146 Bulletin No. 27278-AD 3-10-07 3 of 3