Nelson GA-2335, TE760 Thermostat Instruction Sheet

NELSON™ HEAT TRACING SYSTEMS
TE760 THERMOSTAT
SPECIFICATION / APPLICATION
INSTALLATION
These thermostats are used for high temperature piping on freeze protection and process maintenance applications in hazardous locations.

OUTLINE

Approvals:
FM - Class I; Div. 1; Groups B, C, D
- Class II; Div. 1; Groups E, F, G
- Class l; Zone 1; AEx d IIB+H CSA - Class I; Div. 1; Groups B, C, D
- Class II; Div. 1; Groups E, F, G
- Class I; Zone 1; Ex d IIB+H
2
2
ENCLOSURE
Cast Aluminum
CLASSIFICATIONS
NEMA Type 4, 7, 9 IP66
TEMPERATURE RANGE
0 to 538°C (32 to 1000°F)
SENSING PROBE

Length Material Max. Bulb Temperature

3m (10ft.) Incoloy 825 593°C (1100°F)
ELECTRICAL DATA
Load Switching: 8 amp resistive @ 240VAC Control Voltage: 120VAC
CALIBRATION ACCURACY
±1% of span
SWITCH TYPE
Single Pole Double Throw
P.O. BOX 726 TULSA, OK 74101 TEL 918-627-5530 FAX 918-641-7336 www.nelsonheaters.com
GA-2335 Rev. 2
December 2005
NELSON™ HEAT TRACING SYSTEMS
f
5
r
TE760 THERMOSTAT
SPECIFICATION / APPLICATION
INSTALLATION
INSTALLATION
Drain / Seal Fitting
(Appleton part #EYDEF7
or equal)
Power Supply
Conduit Drain
Sensing Probe
MI Cold Section
Junction Box
Conduit to Thermostat
Stand-of
Pipe Clamps
Method for installing LT, HLT
and NC heater cable types.
Pipe
INSTALLATION NOTES:
Securely mount thermostat enclosure and connect to power wiring.
Verify thermostat set point is at the desired maintenance temperature.
Close enclosure cover to prevent damage from inclement weather.
Insure all fittings associated with the power wiring are installed per applicable codes.
When conduit type systems are used, low point drains / conduit drains are highly recommended.
ANNUAL MAINTENANCE:
Spray a coat of lubricant and rust preventative such as CRC Stor & Lube on the electrical wire connections.
Fiberglass Tape
WIRING DIAGRAM
Nelson Heat Tracing Systems products are supplied with a limited warranty. Complete Terms and Conditions may be found on Nelson's website at
www.nelsonheaters.com.
to Heate
Red White
T/C Probe
Cable
GND
+ -
Terminal Block
C NO
120 VAC
N
NC L2
H
L1
P.O. BOX 726 TULSA, OK 74101 TEL 918-627-5530 FAX 918-641-7336 www.nelsonheaters.com GA-2335 Rev. 2 December 2005