NELSON™ HEAT TRACING SYSTEMS
TE460 T H E R M O S T A T
SPECIFICATION / APPLICATION
INSTALLATION
DESCRIPTION
These thermostats are used for high temperature piping
on freeze protection and process maintenance applications
in ordinary locations.
ENCLOSURE
Powder Coated Steel
CLASSIFICATIONS
NEMA Type 4 IP66
TEMPERATURE RANGE
0 to 538°C (32 to 1000°F)
SENSING PROBE
Length Material Max. Bulb Temperature
3m (10ft.) Incoloy 825 593°C (1100°F)
ELECTRICAL DATA
Load Switch: 8 amp resistive @ 240VAC
Control Voltage: 120VAC
CALIBRATION ACCURACY
±1% of span
SWITCH TYPE
Single Pole Double Throw
OUTLINE
Approvals:
UL - Ordinary Locations
FM - Ordinary Locations
CSA - Ordinary Locations
P.O. BOX 726 TULSA, OK 74101 TEL 918-627-5530 FAX 918-641-7336 www.nelsonheaters.com
GA-2332 Rev. 2
December 2005

NELSON™ HEAT TRACING SYSTEMS
TE460 T H E R M O S T A T
SPECIFICATION / APPLICATION
INSTALLATION
INSTALLATION
Thermostat
Condulet & Drain
(not included in kit)
Junction Box
Condulet to
Thermostat
Pipe Clamps
Method for installing LT,
HLT and NC heater cables.
Sensing Probe
MI Cold Section
Pipe
Stand-of
INSTALLATION NOTES:
• Securely mount thermostat enclosure and
connect to power wiring.
• Verify thermostat set point is at the desired
maintenance temperature.
• Close enclosure cover to prevent damage from
inclement weather.
• Insure all fittings associated with the power
wiring are installed per applicable codes.
• When conduit type systems are used, low point
drains / conduit drains are highly recommended.
ANNUAL MAINTENANCE:
Spray a coat of lubricant and rust preventative such
as CRC Stor & Lube on the electrical wire
connections.
Fiberglass Tape
WIRING DIAGRAM
Nelson Heat Tracing Systems products are supplied with a limited warranty. Complete Terms and Conditions may be found on Nelson's website
at
www.nelsonheaters.com.
to Heate
Red
White
T/C Probe
Cable
GND
+ -
Terminal Block
C NO
120 VAC
N
NC L2
H
L1
P.O. BOX 726 TULSA, OK 74101 TEL 918-627-5530 FAX 918-641-7336 www.nelsonheaters.com
GA-2332 Rev. 2
December 2005