NELSON™ HEAT TRACING SYSTEMS
INSTALLATION
LT-SE END SEAL KIT
DESCRIPTION
The LT-SE End Seal Kit is for use with all versions of
Nelson Heat Tracing Systems’ LT & CLT heater cables except
for J option. Minimum installation temperature –30°C (-22°F).
25mm (1")
102mm (4")
Cut heater cable off at required length. Strip
overjacket back 102mm (4”) from the end of heater
cable. Slide braid back over the overjacket portion
of the heater cable.
Cut off excess heater cable leaving 25mm (1”).
INSTRUCTIONS
KIT CONTENTS
5 Shrink Tubes, 13mm (0.5”) dia., 51mm (2”) length
5 Shrink Tubes, 16mm (0.63”) dia., 76mm (3”) length
excess shrink tube
While still warm, squeeze the entire width of shrink
tube closed. Cut off excess shrink tube.
Pull braid over the squeezed shrink tube, covering
the entire end seal and twist closed.
For Overjacket Products only:
At the end of the heater cable, snip a 10mm (0.4”)
slit between the bus wires. Slightly spread wires
apart.
!
Do not overlap braid
with shrink tube.
Slide a 16mm (0.63”) diameter, 76mm (3”) length
shrink tube over the braid leaving approximately
13mm (0.5”) of shrink tube past the braid. Shrink
with heat gun until completely shrunk.
While still warm, squeeze the entire width of shrink
tube closed.
Slide a 13mm (0.5”) diameter, 51mm (2”) length
shrink tube over the heater cable leaving
approximately 25mm (1”) of shrink tube past the
heater cable. Shrink with heat gun until completely
shrunk.
P.O. BOX 726 TULSA, OK 74101 TEL 918-627-5530 FAX 918-641-7336 www.nelsonheaters.com
Nelson Heat Tracing Systems products are supplied with a
limited warranty. Complete Terms and Conditions may be
found on Nelson's website at www.nelsonheaters.com
GA-1343 Rev 6
Sheet 1 of 1
January 2010
.