The Nelson Heat Trace CM-2201 is designed to monitor and
control one heating circuit in ordinary and Class I, Division
2, Class I, Zone 2, and Zone 2 hazardous locations. This
manual provides information pertaining to the installation,
operation, testing, communications and maintenance of
this device. See Appendix A for additional details.
1.1 Getting Started
The CM-2201 should be connected to external RTDs; power
and communication based on Appendix B and C. If any
problems occur, call Nelson technical support or follow the
Troubleshooting section.
The CM-2201 is designed to operate on input voltages
between 100 and 277 Vac and 50/60 Hz. Load switching is
handled by a 2-Pole solid-state relay and can control resistive loads of 30A continuous @ 40°C ambient.
The CM-2201 is designed to control one heating circuit by
monitoring one or two temperature inputs via industry
standard 3-wire, 100Ω, Platinum RTDs. Two separate RTDs
may be utilized to customize the temperature control inputs.
Several different modes are user selectable as well as the
sensor failure operational mode.
The CM-2201 assembly is rated UL Type 4X (IP66) and can
be operated in temperatures of -40°F to +104°F (-40°C to
+40°C).
The CM-2201 must be installed only in areas for which it
has been approved and in accordance with all applicable
electrical codes and ordinances. All conduit entry holes
must be appropriately installed and sealed to maintain
ingress protection rating.
Do not install this unit prior to functional testing if shipping
container or internal packaging shows signs of damage.
Notify the appropriate individuals immediately if damage is
suspected.
3.1 Selecting Installation Location
The CM-2201 should be installed in an area protected
from the elements as much as possible. It is possible to
install the unit in unprotected areas, but such often limits
maintenance/access. Further, installation in unprotected
areas must be carefully considered to ensure it is always
in operating conditions consistent with specifications. See
Appendix A for additional details.
3.2 Mounting
The CM-2201 should be mounted at a convenient height to
suit operator interaction. Conduit entries should be made
in the bottom of the enclosure to prevent damage to the
internal electronics from moisture intrusion. Conduit
entries should be drilled, and the use of suitable bushings
is required to maintain the environmental ratings.
3.3 Wiring
Electrical wiring diagrams and schematics are provided in
Appendix B and C of this manual. Ensure that all wiring and
connections are in accordance with applicable wiring codes.
Enclosure grounding must be in accordance with applicable
wiring codes for non-metallic devices.
4.0 Initial Set-Up
Upon initial power-up, the CM-2201 display will run selfcheck, display the software version, then the main program
will start.
4.1 Display Modes
This feature determines what messages and functions are
displayed during normal operations. If set to “normal user,”
only basic information is displayed. If set to “advanced
user,” all controller information is displayed. Each
parameter shown in this manual will list the Display
Mode required to view information and access each function
during programming.
4.2 Password Protection
The CM-2201 can have password protection enabled to
ensure that sensitive operating parameters are not
inadvertently adjusted. If password protection is enabled,
the user will be prompted to enter a valid value to access
any protected features. The user may also replace the default password value (1,2,3,4) with their own unique value
for greater protection of operational parameters. The password can be disabled indefinitely if no protection is desired.
4.3 Security Levels
CM-2201 has two levels of security; the high level (Advanced Display) uses password protection. Disabling the
password from the Password Enable / Disable menu will
keep the password disabled indefinitely – any parameter
can be changed without the use of a password. At this level,
all the functions and monitoring parameters are open. The
low level (Normal Display) does not give access to parameter settings, but is open for monitoring a few parameters,
such as temperature, current, GFI, etc.
If the password is “Enabled”, by going to the parameter to
be changed, after the ‘up’ or ‘down’ arrow is pressed, the
controller will ask to type the password, and after that, the
parameter can be changed and saved. The
password will stay disabled for 15 min, then be automatically re-enabled. During the 15 min period when the
password is disabled, other parameters can be changed
and saved.
The CM-2201 utilizes a 2 line x 16 character
alphanumeric display, viewable from the front keypad. The
top line is reserved for the function or operation and the
bottom line displays the value range.
5.2 Keypad
The keypad is touch sensitive. The operator must touch the
area on the main label and the controller will respond.
5.3 LED Functions
LED indicators will show the status of the respective
functions. The power LED will be illuminated when the
controller is connected to a source voltage. The heater LED
will be illuminated when voltage is applied to the heater.
The system LED will illuminate if there is an internal
hardware issue with the controller. The comm LED will
illuminate when the controller is sending data through
external communication. The alarm LED will flash when
there is a current active alarm condition; the alarm LED
will illuminate solid when an alarm was present, but is not
currently active.
5.4 Monitoring
By touching the “Actual” button, followed by an arrow, the
controller will display all the active parameters, one at a time.
5.5 Alarm Management
All the alarm(s) will be saved in the alarm log. If the alarm
is not active (alarm LED solid red), the Alarm LED can be
turned off by touching “Reset”, one alarm at a time. If the
alarm is active (alarm LED flashing red), the user cannot
reset the alarm.
5.6 Soft-Start Feature
The Soft-Start feature enables self-regulating cables to be
energized at low temperatures without causing excessive
load on the electrical system, and extends cable life by
reducing cable internal heating due to inrush currents. The
resistance of self-regulating cables decreases as these
cables get colder, which results in higher current draw.
5.6 Soft-Start Feature Continued
This can result in breaker trips if temperatures are very cold
and the installed length of cable is high. The Soft-Start
feature operates by initially only energizing the cable for a
very short period of time – while the current draw may be
high during this period, the period is usually short enough
to reduce average load on the electrical system. This short
energization period is repeated and eventually increased;
after a few minutes, the cable is usually warm enough such
that the resistance has increased and the current decreased
to the point where it can be continuously energized.
5.7 Current-Limiting Feature
The Current-Limiting feature operates similarly to the
Soft-Start in that it restricts the amount of time the cable
is energized during any given period, thereby reducing the
average current draw of the cable during that period. For
example, if a cable normally draws 8 Amps, but current
limit is set to 6 Amps, then the cable would be energized
only 75% of the time.
5.8 Ground Faults
Ground faults typically are the result of damaged or
improperly installed cables which allow current-carrying
conductors/surfaces/parts to be in contact with grounded
objects. For example, if a heating cable has been secured
to a pipe with a clamp, and if the clamp has been
overtightened, then the ground braid and/or the pipe may
come in contact with current carrying parts within the
cable. This would result in current leakage to ground
through the ground braid of the cable and/or the pipe itself.
This type of fault can eventually become serious, resulting
in overheating/fire/shock hazards. Current leakage to
ground can be monitored by electronic circuitry, and the SPC
can be programmed to either alarm or trip when leakage
current exceeds the specified maximum allowable amount.
The CM-2201 allows the user to select different control
modes based on their individual process control
parameters.
6.1 On-Off Control
This control method simply energizes the cable until the
actual monitored temperature rises to the setpoint value
plus half the deadband value (upper limit). The cable is
then de-energized until the actual monitored temperature
drops to the setpoint value minus half the deadband value.
Note that this type of control can result in some temperature
“overshoot”; this is because the cable is de-energized
when the monitored temperature reaches the upper limit.
However, the residual heat in the cable continues to transfer
to the pipe, and this will cause the pipe temperature to
increase slightly above the upper limit. Similarly, there can
be some temperature “undershoot”.
6.2 Proportional Control
This control method uses the typical proportional control
algorithm, wherein the cable is cycled on and off at a rate
proportional to the difference between the setpoint value
and the actual monitored temperature. As the difference
between the setpoint value and the actual monitored
temperature increases, the amount of time the cable is
energized increases proportionately. This helps reduce the
“overshoot” and “undershoot” commonly associated with
On/Off control.
6.3 Forced Control Feature
This control method simply allows the user to force the
cable on or off as desired.
This message displays the name of the sub-menu when
entered.
1. Display Mode: All
2. Range: N/A
3. Default: N/A
7.1.2 Maintain Temp
This value sets the control setpoint temperature for
all operating modes. For On-Off control, the circuit is
energized if the control temperature is less than the
maintain temperature minus the deadband. The circuit is
de-energized if the control temperature is greater than the
maintain temperature plus the deadband. If maintain temp
is set to None then the heater circuit will have temperature
monitoring with no control temperature. If the maintain
temp is set to Off then the heater circuit will have no
temperature monitoring or control.
1. Display Mode: All
2. Range: -50°C to 500°C, none or -58°F to +932°F,
none, Off
3. Default: 10°F or 50°F
7.1.3 Low Temp Alarm
This value sets the Low Temperature Alarm setpoint. It
must be less than the maintain temperature minus the
Deadband. To disable this alarm set the value to “Off’.
When the measured temperature of either RTD A or RTD
B (if activated) is less than or equal to this setpoint, the
Low Temperature Alarm is activated and a “LOW TEMP
ALARM” message is added to the alarm stack. This alarm
deactivates when the temperature rises above the alarm
setpoint value.
1. Display Mode: All
2. Range: -50C to Maintain Temperature, Off, -58°F to
Maintain Temperature, Off
3. Default: 5°C or 41°F
4. Restrictions: Message does not exist if Maintain
Temperature is set to Off.
7.1.4 High Temp Alarm
This value sets the High Temperature Alarm setpoint.
It must be greater than the maintain temperature plus
deadband. To disable this alarm set the value to “Off”.
When the measured temperature of either RTD A or RTD B
(if activated) is greater than or equal to this setpoint, the
High Temperature Alarm is activated and a “HIGH TEMP
ALARM” message is added to the alarm stack. The alarm
deactivates when the temperature falls below this alarm
setpoint.
1. Display Mode: All
2. Range: Maintain Temperature to +500°C, Off,
Maintain Temperature to +932°F, Off
3. Default: Off
4. Restrictions: Message does not exist if Maintain
Temperature is set to Off.
7.1.5 Low Current Alarm
This value sets the Low Current Alarm setpoint. It must be
less than the high current alarm setpoint. To disable this
alarm set the value to “Off’. When the heater current is
less than or equal to this setpoint, the Low Current Alarm
is activated and a “LOW CURRENT ALARM” message is
added to the alarm stack. The alarm deactivates when
the Heater Current rises above this alarm setpoint. Note:
This setpoint is based on the heater at 100% power. If
Proportional Control or Current Limiting is enabled, all
current measurements will be scaled to 100% power, based
on a constant resistive load, before being compared to the
alarm setpoint.
1. Display Mode: All
2. Range: 0.1A to High Current Alarm, Off
3. Default: Off
7.1.6 High Current Alarm
This value sets the High Current Alarm setpoint. It must
be greater than the low current alarm setpoint. To disable
this alarm set the value to “Off’. When the heater current
is greater than or equal to this setpoint, the High Current
Alarm is activated and a “HIGH CURRENT ALARM” message
is added to the alarm stack. The alarm deactivates when
the heater current falls below this alarm setpoint. This
setpoint is based on the heater at 100% power.
If Proportional Control or Current Limiting is enabled, all
current measurements will be scaled to 100% power, based
on a constant resistive load, before being compared to the
alarm setpoint.
1. Display Mode: All
2. Range: Low Current Alarm to 30.0A, Off
3. Default: Off
7.1.7 Ground Fault Alarm
This value sets the Ground Fault Alarm setpoint. It must
be less than the ground fault trip setpoint. To disable this
alarm set the value to "Off'. When the Ground Fault Current
is greater than or equal to this setpoint, the Ground Fault
Alarm is activated and a "GROUND FAULT ALARM" message
is added to the alarm stack. The alarm deactivates when
the Ground Fault Current falls below this alarm setpoint.
1. Display Mode: All
2. Range: 10 to Ground Fault Trip, Off
3. Default: 30mA
7.1.9 Low Voltage Alarm Continued
1. Display Mode: All
2. Range: 85VAC to High Voltage Alarm, Off
3. Default: Off
7.1.10 High Voltage Alarm
This value sets the High Voltage Alarm setpoint. It must
be greater than the Low Voltage Alarm setpoint. To
disable this alarm set the value to “Off’. When the Heater
Voltage is greater than or equal to this setpoint, the High
Voltage Alarm is activated and a “HIGH VOLTAGE ALARM”
message is added to the alarm stack messages. The alarm
deactivates when the Heater Voltage drops below this alarm
setpoint.
1. Display Mode: All
2. Range: Low Voltage Alarm to 280VAC, Off
3. Default: Off
7.2 Program - Heater Setup
7.1.8 Ground Fault Trip
This value sets the Ground Fault Trip setpoint. It must be
greater than the ground fault alarm setpoint. To disable
this trip alarm set the value to “Off’. When the Ground
Fault Current is greater than or equal to this setpoint, the
heater circuit is de-energized, the Ground Fault Trip Alarm
is activated and a “GROUND FAULT TRIP” message is added
to the alarm stack. This is a latching alarm and trip. When
the cause of the alarm has been corrected, the circuit may
be energized by the manual reset function.
1. Display Mode: All
2. Range: Ground Fault Alarm to 500mA, Off
3. Default: 50mA
7.1.9 Low Voltage Alarm
This value sets the Low Voltage Alarm setpoint. It must be
less than the high voltage alarm setpoint. To disable this
alarm set the value to “Off’. When the Line Voltage is less
than or equal to this setpoint, the Low Voltage Alarm is
activated and a “LOW VOLTAGE ALARM” message is added
to the alarm stack. The alarm deactivates when the Line
Voltage rises above this alarm setpoint.
7.2.1 Heater Setup
This message displays the name of the sub-menu when
entered.
1. Display Mode: Advanced
2. Range: N/A
3. Default: N/A
7.2.2 Enable Heater
This selection enables control and monitoring of the heater
circuit. Setpoints and measured value messages cannot be
accessed unless the heater is enabled. Select “No” if the
circuit is not used.
This selection allows for user defined Heater Identification.
It provides a unique, identifiable tag or label for each heater
circuit. The Heater Name allows up to 20 alphanumeric
characters which are entered one at a time from left
to right. The cursor indicates which character is being
selected. Press the [SELECT UP/DOWN] arrow keys to change
the character. Move to the next character by pressing [NEXT]
arrow. Press [ENTER] in the last character position to save
the Heater ID.
1. Display Mode: Advanced
2. Range: 20 Characters
3. Default: Blank
7.2.4 Manual Override
This selection sets the response of the heater circuit to the
Override inputs. The Override inputs respond to contact
closure. If the Override is set to “Off”, the override inputs
are ignored and control of the heater circuit operates
normally based on the measured temperature and maintain
temperature setpoint. If the Override is set to “On”, an open
contact on the override inputs forces the heater Off.
When the contact on the override input is closed, the heater
control resumes in normal manner.
1. Display Mode: Advanced
2. Range: On, Off
3. Default: Off
7.2.5 Deadband
The Deadband is defined as the difference between the
setpoint temperature and the actual maximum temperature
that is ideally allowed in excess of the setpoint temperature.
Decreasing the deadband increases the temperature control
accuracy but also increases the heater switching frequency.
1. Display Mode: Advanced
2. Range: 1 °C to 5 °C, 1 °F to 10 °F
3. Default: 2 °C or 5 °F
4. Note: Deadband is disabled for Proportional Control
mode.
7.2.6 Control Type
This selection determines the type of control method used
by the controller: either On-Off (Deadband), or Proportional
Control. The On-Off control mode is available for all heating
devices. Proportional Control mode is only available for
series type heating devices.
Warning: Proportional Control should never be selected
for use with self-regulating heating cable types due to
the constantly changing characteristics of self-regulating
cables – this will cause the control to be unstable. Further,
the continual cycling associated with Proportional Control
can result in internal heating of the cable and lead to
reduced life expectancy.
1. Display Mode: Advanced
2. Range: On-Off, Proportional
3. Default: On-Off
4. Selection does not exist if Maintain Temperature is
set to Off.
7.2.7 Current Limiting
This selection sets the maximum average current limit
allowed for the heater circuit. It is useful for reducing the
power output of constant wattage heaters. The load will be
turned on for a period of time, then turned off for a period of
time to maintain the average current draw to the value set.
1. Display Mode: Advanced
2. Range: 0.5 to 30.0 A, Off
3. Default: Off
4. Note: The value range is in 0.5A increments.
7.2.8 Soft Start Mode
This function ramps the heater output from Off to nominal
current of the heater over the set softstart cycle time. It
is useful for reducing inrush currents of self-regulating
heaters. At the end of the soft start cycle time, the load will
no longer be controlled by the soft start function.
This value sets the frequency at which the Auto Test Cycle is
activated. Auto Test is a feature that exercises the system
by automatically applying power to the heater at specified
time intervals. If an alarm condition is detected during this
period, the Auto Test Alarm is activated and an “ALARM
DURING AUTO TEST” message is added to the System Status
messages. This is a latching alarm. To clear the alarm,
locate the alarm message in the Alarm Menu and press
[ENTER]. To disable this feature, set the value to “Off”. The
Auto Test Cycle does not operate if heater is forced off for
any reason, including ground fault trip. Auto Test decreases
maintenance by providing an early warning of problems that
would otherwise go undetected until the heater was needed.
1. Display Mode: Advanced
2. Range: 1 to 720 hours, Off
3. Default: 24 hours
7.2.10 RTD Operation
This selection determines how the control temperature is
utilized by the RTD inputs.
In One RTD Mode, the temperature is based on the
measured temperature from RTD-A.
In Backup Mode, control temperature is based on RTD-A. If
for any reason RTD-A fails, then RTD-B takes over.
7.2.10 RTD Operation Continued
Functions requiring two RTDs to operate, such as Average,
Lowest, Highest and High Temperature Cutoff, will operate
in One RTD mode if one of the two RTDs fail.
1. Display Mode: Advanced
2. Range: One RTD, Backup, Average, Lowest, Highest,
High Temperature Cutoff
3. Default: One RTD
4. Restrictions: Message does not exist if Maintain
Temperature is set to Off.
7.2.11 RTD Failure Mode
This selection sets the controller’s fail-safe mode. The
controller detects if RTD-A has failed and will use RTD-B if
available. If RTD-B is not installed or has also failed, the
heater will be set to its fail-safe state as selected in this
mode. For freeze protection where there is no hazard from
overheating, you may select “On” to operate the heater
continuously and prevent freeze up.
For processes where there is a potential hazard from
overheating, you may select “Off”, to de-energize the circuit
until one of the RTDs becomes available.
1. Display Mode: Advanced
2. Range: On, Off
3. Default: Off
4. Restrictions: Message does not exist if Maintain
Temperature is set to Off.
In Average Mode, the control temperature is based on the
average of RTD-A and RTD-B measured temperatures.
In Lowest Mode, control temperature is based on the lowest
of the two temperature measurements.
In Highest Mode, control temperature is based on the
highest of the two temperature measurements.
In High Temperature Cutoff Mode, control temperature is
based on RTD-A, but if the temperature from RTD-B exceeds
the high temperature alarm, the heater is turned Off and a
high temperature alarm is activated. The High Temperature
cutoff mode will operate in One RTD mode if the high
temperature alarm is turned Off.
This message displays the name of the sub-menu when
entered.
1. Display Mode: Advanced
2. Range: N/A
3. Default: N/A
7.3.2 Password
This selection determines if password protection is required
for programming changes. The display will show “Disabled”
if program access is currently enabled, and show “Enabled”
if program access is currently disabled.
1. Display Mode: All
2. Range: Enabled or Disabled
3. Default: Enabled
12
CM-2201 Programming
7.3.3 Change Password
This selection allows the user to change the default password. The user is prompted to enter the old password, press
[ENTER]. If verified, the user is then able to enter the new
password, press [ENTER]. The user is prompted to re-enter
the new password. By not entering a password and pressing
[ENTER], the controller assumes no password.
1. Display Mode: Advanced
2. Range: Any combination of 2 to 16 characters 0 – 9,
A – Z.
3. Default: 1234
7.3.4 Units
This selection determines the unit of measure for
temperature values. All temperatures are displayed in the
selected units of either Celsius degrees (°C) or Fahrenheit
degrees (°F).
1. Display Mode: Advanced
2. Range: Celsius, Fahrenheit
3. Default: Celsius
7.3.5 Operational Costs
This value sets the cost per kWh of electrical power. This
is used to calculate energy costs for operating this control
circuit.
1. Display Mode: Advanced
2. Range: $0.01 to 1.00
3. Default: $0.05
7.3.6 Display Mode
This selection determines what messages are displayed by
the controller for operations personnel. If set to “advanced
user”, all messages are displayed. If set to “normal user,”
only the basic messages are displayed. Each message listed
throughout this manual shows the Display Mode required
to see the message. “Advanced only” indicates that the
display mode must be set to “advanced user” to view the
message.
1. Display Mode: All
2. Range: Normal, Advanced
3. Default: Advanced
7.3.7 Default Display
This function specifies the information that will be
displayed when no key has been pressed for the Display
Timeout interval as described below.
VALUEINFORMATION
DISPLAYED
System statusAlarm status of all the
heaters
Heater statusAlarm status of the
heater
Heater tempTemperature of the
heater
1. Display Mode: Advanced
2. Range: System Status, Heater Status, Heater Temp
3. Default: system status
4. Restrictions: Temperature messages are not
displayed if Maintain Temperature is set to Off.
7.3.8 Display Timeout
This function sets the length of time from the last key press
to automatically return to the Default Display information.
Selecting “Off’ disables this function.
1. Display Mode: Advanced
2. Range: 5 to 600 seconds, Off
3. Default: 120 seconds
7.3.9 Modbus Address
This selection sets a unique address to ensure only one
CM-2201 attempts communications with the master unit
at any time. See Section 8.0 for complete information on
Modbus communications.
1. Display Mode: Advanced
2. Range: 1 to 255 to accommodate multiple devices on
same network.
3. Default: 1
7.3.10 Baud Rate
Sets the communication baud rate for the RS485 serial port.
All controllers connected to the same data highway must
operate on the same baud rate.