Neets Switching Relay - 8 Installation Manuals

Neets Switching Relay - 8
Installation Manual
Neets Switching Relay - 8
Page 2 of 24
Foreword
The purpose of this document is to describe how to install and operate the Neets Switching Relay – 8
COPYRIGHT - All information contained in this manual is the intellectual property and copyrighted material of Neets. All rights are reserved. You may not allow any third party access to content, information or data in this manual without Neets’ express written consent.
CHANGES - Neets reserve the right to change the specification and functions of this product without any notice.
Questions, AFTER reading this manual, can be addressed to your local distributor or:
Neets A/S Langballe 4 8700 Horsens Denmark
by E-Mail: Support@Neets.dk or you may use our contact form at www.neets.dk
Revision list
This document (no: 230-028-306-0014) has the following revision changes:
Author: Date Description Pages Rev
MH: 11-08-2014 First release. All 1.00
MH: 05-03-2015 Single phase motor info added 4 2.00
MH: 31-07-2015 Firmware upgrade text changed 11 3.00
MH: 01-09-2015 New design according to Neets design guide All 4.00
What is in the box?
When you open the box it will contain the following items:
1 x Neets Switching Relay - 8 Power cable Cable relief brackets Cable relief covers Phoenix connectors Screws Cable binders Installation manual
Page 3 of 24
Important Safety Instructions
Caution:
Read these instructions: Read and understand all safety and operating instructions before using the equipment. Keep these Instructions: The safety instructions should be kept for future reference. Heed all Warnings: Follow all warnings and instructions marked on the equipment or in the user information. Avoid Attachments: Do not use tools or attachments that are not recommended, because they may be hazardous
Warning!:
• This equipment should be operated only from the included power supply.
• To remove power from the equipment safely, remove all power cords from the rear of the equipment, or the desktop power module (if detachable), or from the power source receptacle (wall plug).
• Power cords should be routed so that they are not likely to be stepped on or pinched by items placed upon or against them.
• Do not defeat the safety purpose of a polarized or grounding-type plug. A polarized plug has two blades with one wider than the other. A grounding-type plug has two blades and a third grounding prong. The wide blade or the
third prong is provided for your safety. If the provided plug does not t into your outlet, consult an electrician for
replacement of the obsolete outlet.
• Unplug this apparatus during lightning storms or when unused for long periods of time.
• Refer all servicing to qualied service personnel. There are no user-serviceable parts inside. To prevent the risk of
shock, do not attempt to service this equipment yourself because opening or removing covers may expose you to dangerous voltage or other hazards. Contact your local Neets reseller or distributor.
• If the equipment has slots or holes in the enclosure, these are provided to prevent overheating of sensitive components inside. These openings must never be blocked by other objects.
• Do not use this equipment near water.
• To reduce the risk of re or electric shock, do not expose this apparatus to rain or moisture and objects lled
with liquids.
• Unplug the product before cleaning. Clean only with a dry cloth and not cleaning uid or aerosols. Such products could enter the unit and cause damage, re, or electric shock. Some substances may also mar the nish of the
product.
FCC Class A Notice:
This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. Operation is subject to the following two conditions:
1. This device may not cause harmful interference.
2. This device must accept any interference received, including interference that may cause undesired operation.
The Class A limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference, in which case the user will be required to correct the interference at his own expense.
FCC regulations state that any unauthorized changes or modications to this equipment, not expressly approved by
the manufacturer, could void the user’s authority to operate this equipment.
The lightning bolt triangle is used to alert the user to the presence of uninsulated “dangerous
voltages” within the unit’s chassis that may be of sufcient magnitude to constitute a risk of electric
shock to humans.
The exclamation point triangle is used to alert the user to presence of important operating and service instructions in the literature accompanying the product.
!
Page 4 of 24
Contents
Foreword ..............................................................2
Revision list ............................................................2
Important Safety Instructions ...............................................3
Contents ..............................................................4
Description .............................................................5
What can it do? .......................................................5
Specications ...........................................................6
Front Panel...........................................................7
Rear Panel ...........................................................7
Hardware installation......................................................7
Mounting the unit in a 19” rack ............................................7
Mount cable relief bracket and covers ........................................9
Connections and Controls ..................................................9
AC Line .............................................................9
Relays ..............................................................9
RS-232/IR ports .......................................................10
Digital I/O ............................................................10
LAN ................................................................11
Front panel USB . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
How to connect… ........................................................12
How to control Switching Relay - 8 through USB ..................................13
How to upgrade the Firmware ...............................................14
How to connect several relay boxes to a RS-232 Line (daisy chaining) ...................14
Change the ID number of the relay box .........................................15
Reset the unit to Factory default .............................................16
Error indication ..........................................................16
RS-232 and LAN protocol ..................................................16
Communications parameter ...............................................17
Command ............................................................17
Global functions .......................................................18
LAN Settings .........................................................19
Relay control..........................................................20
Screen control settings..................................................20
Screen control ........................................................21
Input/output settings ...................................................22
Output control ........................................................23
RS-232 settings.......................................................23
RS-232 command ......................................................24
IR command (Advance users) ..............................................24
Page 5 of 24
Description
Neets Switching Relay – 8 (Relay – 8) provides total control in complex applications such as larger meeting / conference rooms, lecture halls, and auditoriums. Automatic, configurable control is provided for all devices requiring AC power on/off: projector lifts, screens, curtains and architec­tural lighting. Multiple relay activations can be immediate and simultaneous, or programmed for activation in a timed sequence.
Relay - 8 is designed to interact with AV control systems, to facilitate seamless integrated control of projectors, audio and video sources, and audio mixing along with relay switching functions. Relay - 8 incorporates a full range of options for real-time system control, including RS-232, IR or LAN. All functions are easily configurable through LAN using Neets configuration software or 3rd party systems, making the Relay - 8 a valuable tool for demanding applications.
What can it do?
• Easy control by RS232 or LAN
• Daisy Chain multiple Relay – 8 (Control multiple units by one RS232 port)
• Ready to use, as a standard relay box. (Control the relay by the I/O ports)
• RS232 Loop-through. Control any unit on RS232 port 2. (Can have different communication
parameter than RS232 port 1)
• When controlling the unit by LAN IR control is possible.
• LAN to RS232 gateway.
• Compatible with 3rd party control systems.
• Software screen mode for easy and safe control of electrical screen.
Page 6 of 24
Specications
Power Input
Voltage 100 VAC – 240 VAC Line Frequency 47 Hz – 63 Hz Power usage 12 W Connector type IEC plug
Relay Output
Voltage max 240 VAC Current max 8 A Load max AC1 1150 W @ 230 VAC Load max AC15 500 W @ 230 VAC Single-phase motor 370 W @ 230 VAC ¼ HP @ 125 VAC Connector 3 pin screw block
Input / Output
Input trigger low < 1 VDC Input trigger high > 4 VDC Output type Open drain Isolated output No Max voltage load 24 VDC Max current 0.5 A Connector 5 pin screw block
IR
Transmit frequency 400 Hz to 500 KHz
Approvals
IEC/EN 61000-6-1 IEC/EN 61000-6-2
Network (LAN)
Speed 10 / 100 Mbit Duplex modes Half or Full DHCP Default off Default IP 192.168.254.252 Default gateway 192.168.1.1 Default subnet mask 255.255.255.0
RS-232
Baud rate 1200 – 115200 bit/sec Data bits 7, 8 Parity Even, Odd, None Stop bits 1, 2
General
Width 437 mm / 483 mm Depth 141 mm Height 44 mm (1U) Weight 2.0 kg Shipping weight 2.9 kg Shipping dimensions 530 mm / 230 mm / (W/D/H) 80 mm Storage temperature -20 °C to 50 °C Storage moisture Non condensing Operation temperature 0 °C to 30 °C Operation moisture Non condensing
Page 7 of 24
Front Panel
Number Description
1 LED indication for transmitting or receiving RS-232 or transmitting IR
2 LED indication for IO status
3 LED relay status indication with corresponding relay test buttons
4 Mini USB for rmware update functionality
5 Power and status indication
Rear Panel
Number Description
1 100-240 VAC power in
2 8 x Potential-free relays
3 2 x bi-directional RS-232 or IR transmitter
4 8 x digital I/O connectors
5 1 x RJ-45 Network (LAN) connector
Hardware installation
The Relay – 8 is designed to be mounted in a rack or as a stand-alone unit on a desk, drawer or alike.
Make sure there is at least 40 mm of free space above the unit as air circulation around the unit is needed for reliable performance. If installed in a closed environment forced air circulation may be needed.
Mounting the unit in a 19” rack
The Relay – 8 can easily be installed in a 19” rack. Due to the standard 1U height, low weight and small mounting depth the Relay – 8 can be mounted from the rack front without the use of a rack shelf or supporting rails.
1
tx
rx
2
RS232 / IR
control
1 2 3 4 56 7 8
in
out
input / output
made in Denmark
Neets Control - DelTa
config IR on
Neets Switching Relay - 8
config on
made in Denmark
relay
1 2 3 4 56 7 8
test
on
LAN
PN: 306-0014
www.neets.dk
Control
Relay
100-240VAC
Power
Relay
47-63Hz, 12W
RS-232/IR
G
T2
R2
G
T1
R1
I/O 24V/500mA
G
586
7
G
142
3
NC
COM
NO
NC
COM
NO
NC
COM
NO
NC
COM
NO
NC
COMNONC
COM
NO
NC
COMNONC
COM
NO
Relay 1 Relay 8Relay 5Relay 4Relay 2
Relay 3
Relay 6 Relay 7
LAN
1
1
2
2
3
3
445
5
Page 8 of 24
1: Mount two clip nuts on each side of the rack as shown below:
2: Slide the Relay – 8 into the rack and secure with the M6x10 screws.
3: The unit is now ready to be connected with all peripherals as needed.
made in Denmark
control
input/output relay
1 2 3 4 5 6 7 8
in 0 0 0 0 0 0 0 0
out 0 0 0 0 0 0 0 0
1 2 3 4 5 6 7 8
test 0 0 0 0 0 0 0 0
on 0 0 0 0 0 0 0 0
RS232 / IR
1 2 rx 0 0 tx 0 0
Neets Switching Relay - 8
config on
Page 9 of 24
Mount cable relief bracket and covers
To secure heavy duty cables at the relay receptacles two sets of cable relief brackets and covers are supplied with the Relay - 8.
Secure the cable relief brackets with the supplied M4x6mm screws to the Relay - 8.
Insert your cable in the supplied screw terminal connector and insert this connector to the appropriate relay receptacle in the Relay – 8.
Secure the cables with supplied cable binders to the cable relief bracket.
Finally, mount the cable relief cover over the cable relief bracket and secure with supplied M4x45mm screw.
Connections and Controls
In this section, you will find information on how to connect and use the different ports.
AC Line
Connect the Relay - 8 to the AC line supply using the supplied power cable. The supplied cable will be equipped with a line socket connector for use in the country of sale.
The Relay - 8 incorporates a universal mains power supply, which accepts AC line input from 110 V to 240 V.
Relays
Relays allow the option of NO (Normal Open) and the NC (Normal Close) for greatest flexibility. On the front of the Relay – 8 you find a LED for each relay. When a relays led lights green it means that it’s COM are connected to NO.
Here you can connect cables directly to the Relay – 8 using the supplied terminal block connectors for each
LAN
Control
Relay
100-240VAC
Power
Relay
47-63Hz, 12W
RS-232/IR
G
T2
R2
G
T1
R1
I/O 24V/500mA
G
586
7
G
142
3
NC
COM
NO
NC
COM
NO
NC
COM
NO
NC
COM
NO
NC
COMNONC
COM
NO
NC
COMNONC
COM
NO
Relay 1 Relay 8Relay 5Relay 4Relay 2
Relay 3
Relay 6 Relay 7
LAN
LAN
PN: 306-0014
www.neets.dk
Control
Relay
Relay
RS-232/IR
G
T2
R2
G
T1
R1
I/O 24V/500mA
G
586
7
G
142
3
NC
COM
NO
NC
COM
NO
NC
COM
NO
NC
COM
NO
NC
COMNONC
COM
NO
NC
COMNONC
COM
NO
Relay 1
Relay 8Relay 5
Relay 4Relay 2
Relay 3
Relay 6 Relay 7
LAN
Page 10 of 24
individual relay. Use the supplied cable relief brackets to fix the cables with a cable tie to prevent accidental disconnection of the cables. See section Mount cable relief bracket and covers on page 6.
If you want to connect and switch AC power for your external equipment in an easy and convenient way use the Neets IEC Mains Adaptor (306-0015) (sold separately) instead of the terminal block and cable relief brackets.
RS-232/IR ports
The onboard RS-232 ports (T1, R1, T2, R2) can be used for one- or two-way communication. Both of the RS-232/IR ports can be used as either as RS-232 or as IR emitter. On the front of the Relay – 8 you will find 2 led for each RS232/IR port. When the Relay – 8 is sending data on a RS232/IR port it’s green tx led will light. When the Relay – 8 is receiving RS232 data the orange rx led will light.
Digital I/O
The Relay – 8 has 8 x I/O (Inputs/Outputs) available. They can be used for an external control keypad, PIR (movement) sensor, keyboard lock, extra relays, or other compatible uses. The ports are not potential free; you may need external relays if you need to prevent ground loops.
Neets IEC Mains Adaptor
When used as single IR port: Connect the IR emitter to T1 (white striped wire) and GND, as shown above.
When used as RS-232 transmit port: Connect the device to T1, R1 and GND, as shown here above.
When used as dual IR port: Connect the IR 1 emitter to T1 (white striped wire) and black wire on IR 1 emitter to IR 2 emitter (white striped wire), and black wire from IR 2 emitter to GND, as shown above.
LAN
PN: 306-0014
www.neets.dk
RS-232/IR
G
T2
R2
G
T1
R1
I/O 24V/500mA
G
586
7
G
142
3
LAN LAN
PN: 306-0014
www.neets.dk
RS-232/IR
G
T2
R2
G
T1
R1
I/O 24V/500mA
G
586
7
G
142
3
LAN LAN
PN: 306-0014
www.neets.dk
RS-232/IR
G
T2
R2
G
T1
R1
I/O 24V/500mA
G
586
7
G
142
3
LAN
IR-Emitter
IR 1 Emitter
IR 2 Emitter
LAN
PN: 306-0014
www.neets.dk
Control
RS-232/IR
G
T2
R2
G
T1
R1
I/O 24V/500mA
G
586
7
G
142
3
NC
COM
NO
Relay 8
LAN
Page 11 of 24
LAN
PN: 306-0014
www.neets.dk
Control
RS-232/IR
G
T2
R2
G
T1
R1
I/O 24V/500mA
G
586
7
G
142
3
NC
COM
NO
Relay 8
LAN
Neets Control - DelTa
config IR on
Neets Switching Relay - 8
config on
When used as outputs, the ports are active low. When indicated as active, the pins are tied to GND through a FET transistor (also called open drain/collector function). Each can draw up to 24VDC/500mA. For each output pin there is a led on the front of the Relay – 8. The led are on when the output pin is activated (The output pin is connected to GND)
When used as inputs the voltage has to be below 1 Volt DC to be accepted as LOW, and above 4 VDC (but below 24 VDC) to be accepted as HIGH. The inputs are de­fault HIGH and must be connected to ground in order to change state. For each input there is a led on the front of the Relay – 8. The led indicates the current state of the input. When the led lights orange it indicate that the input is high, when the light is off the input is low.
LAN
The network connector integrates the system into the local area network.
There are two LEDs on the connector with the following indication:
Color Off On Blink
Yellow No Link Link Activity
Green 10Mbit 100Mbit
Front panel USB
The USB port (labeled “config” on the front) can only be used to firmware upgrade the Relay – 8 through a Windows/MAC/Linux computer. See the section How to upgrade the Firmware on page 11 for details.
You are not able to configure or control the Relay – 8 through this port. Do not connect any other devices to this port. The USB connector for connecting to the Relay – 8 is type “mini USB B 5P”.
You can buy this cable on the web (buy a USB A to Mini USB B 5P).
Page 12 of 24
How to connect…
Connecting the Relay – 8 to the control system.
Using I/O pins
If you want to control one or more relays from a digital output, like any of the Neets Control system range provides, you can do this. By default the Relay – 8 is configured to link the I/O pins to the re­lays. This means that you can connect the I/O of the Neets Control system directly the Relay – 8.
Not using a Neets Control system to control the Relay – 8 ? Our I/O can interface with all system that can pull the Input low. To test this simply make a short circuit between the I/O pin and GND to active the relay.
If the Relay – 8 has been used before it is recommended to reset the Relay – 8 to make sure that no settings that prevents this operation are saved in the unit (See section page 13).
Using RS232
When controlling the Relay – 8 by RS232 you have to connect the RS232 port from the control system to the Relay – 8 RS232 port 1 (T1,R1 and G). The command that has to be sent can be found in the section on page 14.
Remember, controlling Relay – 8 by both RS232 and LAN is not possible at the same time.
Page 13 of 24
Using LAN
Controlling the Relay – 8 can also be done over LAN. This is done by creating a TCP connection from the control system to the control port (Default 5000). The protocol that is used to control the Relay – 8 over LAN is the same as used when controlling it by RS232. See the section on page 14. When connecting to the Relay – 8 control port, the RS232 control on RS232 port one is disabled.
Controlling an electrical screen or lift
The Relay – 8 offers you the possibility to control up to four electrical screen and lift directly by 240VAC. When controlling electrical screen and lift we always recom­mend that you use two relays. One relay for screen up and one relay for screen down (In a configuration called: mutual blocking). Here you can see how to connect your screen to the Relay – 8.
LAN
PN: 306-0014
www.neets.dk
Control
RS-232/IR
G
T2
R2
G
T1
R1
I/O 24V/500mA
G
586
7
G
142
3
NC
COM
NO
NC
COM
NO
NC
COM
NO
NC
COM
NO
NC
COMNONC
COM
NO
NC
COMNONC
COM
NO
Relay 1
Relay 8Relay 5
Relay 4Relay 2
Relay 3
Relay 6 Relay 7
LAN
Lift/ScreenAC Power outlet
When making the above configuration you add an extra safety level to your installation. The mutual blocking prevent that power can be connected to both up and down at the same time.
How you control this configuration depends on the way you connect it to you control system. In the previous three sections, you can find information on the three types of control you have.
How to control Switching Relay – 8 through USB
After Project Designer 1.6.4 it is possible to control and configure the Switching Relay - 8 through USB the same way you do today with RS232.
When connecting the Switching Relay - 8 to your computer it will be installed as a RS232 port on your system (The Windows driver is already included in the Project Designer software). Choose your favorite hyperterminal program or simply open the device driver in the Device Editor and use it to send the commands.
LAN
PN: 306-0014
www.neets.dk
Control
RS-232/IR
G
T2
R2
G
T1
R1
I/O 24V/500mA
G
586
7
G
142
3
NC
COM
NO
Relay 8
LAN
Screen down
Screen up
Neutral
Earth
Page 14 of 24
How to upgrade the Firmware
In case you need to update the firmware on Neets Switching Relay – 8. Please follow these four simple steps below.
1. Install Neets Project designer 1.6.4 or higher
2. Connect the unit to your computer
3. Say “Yes” to upgrade the unit
4. The firmware is now completed
How to connect several relay boxes to a RS-232 Line (daisy chaining)
By default, a RS232 line only allows you to be connected to a single receiver. But with the Relay – 8 you can control multiple units with just a single RS232. So how do we do this?: Each Relay – 8 can be assigned a id number (Default 1) that allows you to define what unit a command should be handled by.
If the Relay – 8 device a command on Tx1 that has a id number different from itself, it will re-transmit the command on Tx2.(This function is called RS232 loop-through) So adding a second Relay – 8 on the first Relay – 8 Tx 2 will allow you to control this. This is called daisy chaining the units.
Remember to assign different ID number to each of the Relay – 8 you are using in this constella­tion. See page 12 for details on how to change the id. Using the same ID number on multiple units will result in only one Relay – 8 will react to the command and not all with same id number.
Neets Switching Relay 8
After a rmware upgrade all saved settings will be lost
and have to be saved again.
ii
Page 15 of 24
Change the ID number of the relay box
When controlling the Relay – 8 by the External protocol by ether RS232 or LAN the unit has a ID number that must be used in the command that are send to it. By default the Relay – 8 has address 1.The address can either be changed by RS232, LAN or the test button on the front of the unit.
To change address of the Relay – 8, see the command UNITID in the protocol list. Changing the address of the Relay – 8 on the front of the unit is done like this:
• Connect power to the unit.
• Within 5 sec, press one of the test button and hold it until its LED lights up.
When the Relay – 8 is powered up, it shows it’s current address on the relay status LED. LED 1 = address 1, LED 2 = address 2 …. (While the unit address is displayed the power on LED is blue.) If no LED is on, that indicates that the unit has an address that is not in the range 1-8. The address can be given any address using the UNITID command on ether RS232 or LAN.
Relay box
ID
LED status when power on Test button to press when
changing to this ID
1
Relay 1
2 Relay 2
3
Relay 3
4 Relay 4
5 Relay 5
6 Relay 6
7 Relay 7
8 Relay 8
Other
ID has been set by the RS232
command.
Neets Control - DelTa
config IR on
Neets Switching Relay - 8
config on
relay
1 2 3 4 5 6 7 8
test
on
1 2 3 4 5 6 7 8
test 0 0 0 0 0 0 0 0
on 0 0 0 0 0 0 0 0
1 2 3 4 5 6 7 8
test 0 0 0 0 0 0 0 0
on 0 0 0 0 0 0 0 0
1 2 3 4 5 6 7 8
test 0 0 0 0 0 0 0 0
on 0 0 0 0 0 0 0 0
1 2 3 4 5 6 7 8
test 0 0 0 0 0 0 0 0
on 0 0 0 0 0 0 0 0
1 2 3 4 5 6 7 8
test 0 0 0 0 0 0 0 0
on 0 0 0 0 0 0 0 0
1 2 3 4 5 6 7 8
test 0 0 0 0 0 0 0 0
on 0 0 0 0 0 0 0 0
1 2 3 4 5 6 7 8
test 0 0 0 0 0 0 0 0
on 0 0 0 0 0 0 0 0
1 2 3 4 5 6 7 8
test 0 0 0 0 0 0 0 0
on 0 0 0 0 0 0 0 0
1 2 3 4 5 6 7 8
test 0 0 0 0 0 0 0 0
on 0 0 0 0 0 0 0 0
Page 16 of 24
Reset the unit to Factory default
You can at any time press and hold the relay 1 and 8 test button in for 5 sec. The unit will reboot and assume the factory settings.
It is also possible to reset the Relay – 8 using the command RESET. See the protocol list for details.
After resetting the system, it has these settings:
• I/O is set to inputs and controls the relays (I/O 1 ->relay 1, I/O 2 ->relay 2).
• RS232 port 1: 19200 8N1, ready for loop-through.
• RS232 port 2: 19200 8N1.
• IP Address: 192.168.254.252.
• LAN control port: TCP, port 5000.
• LAN to RS232 port 1: TCP, port 5011.
• LAN to RS232 port 2: TCP, port 5012.
• Neets LanBus: Multicast address: 224.10.10.25, port 7979.
Error indication
If there is an error in the system, it will be displayed on the front of the Relay – 8. On error the power led will flash red.
The above led is ashing.
Unexpected Error Turn off the power to the
control system for 20 sec before turning the power on again.
If the error is not resolved, contact Neets or your local distributor.
RS-232 and LAN protocol
Controlling the Relay – 8 over RS232 or LAN is done with the same protocol. If you are using a Neets Control system there is a Device Driver available which provides you with all the commands below. Open the Device driver in the Neets Device Editor and use the “play” function on each command gives you an easy way of setting up and configuring the Relay – 8 from your computer.
input/output
relay
1 2 3 4 5 6 7 8
in 0 0 0 0 0 0 0 0
out 0 0 0 0 0 0 0 0
1 2 3 4 5 6 7 8
test 0 0 0 0 0 0 0 0
on 0 0 0 0 0 0 0 0
Page 17 of 24
Communications parameter
Default RS232 settings: Baudrate: 19.200 Databit: 8 Stopbit: 1 Parity: None
Default LAN settings: Network Protocol: TCP Control port: 5000 (Only one active connection at a time) LAN to RS232 port 1 gateway port: 5010 (Only one active connection at a time) LAN to RS232 port 2 gateway port: 5011 (Only one active connection at a time)
Control from the RS232 port is enabled by default. When connecting to a LAN control port the RS232 ports converts to LAN-RS232 gateways and they can not be used to control the Relay -
8. The only way to get back to RS232 control is by cycling power.
Command
When entering all the commands in the Neets Device Editor software, select “Chr/ASCII” as input format. To understand the commands below please keep this in mind:
Symbol: Description:
<A> When constructing the command, this part must be replaced with a
sting or number.
<B> When constructing the command, this part must be replaced with a
sting or number.
\CR Every command line must end with a carriage return.
Carriage return is commonly referred to as “CR” or if you need to enter it in hex, the value is 0D and in decimal, it is 13.
“,” or , When making a command it consist of several parts.
Each part is separated with a comma.
E.g. NEUNIT=1,RELAY=1,ACTION=SET,TIME=10.5
Please be aware that all the RS232 commands are case sensitive. If the Relay – 8 detects an error in the command line, the entire command will be ignored.
Sending multiple commands is possible without time delay between commands. Just remember that each command must end with \CR.
If you are looking for a complete list of commands already made, look at the premade device driver found in the Neets device driver library.
Saving the settings. When adjusting the settings of the Relay – 8, it is important to save the settings that you want the Relay – 8 to use after the next power cycling. This is done with the save command. You can nd more information regarding the save on page 15.
i
Page 18 of 24
Example
Below you will find a few command that can control the Relay – 8. The below command are just a few examples to show you how the interface are working. For more details on the command go the next sections.
Examples of command than can be send on ether RS232 or LAN. e.g: NEUNIT=1,RELAY=1,ACTION=SET\CR Reply: NEUNIT=1,OK\CR
e.g: NEUNIT=1,RELAY=1,ACTION=? \CR Reply: NEUNIT=1,RELAY=1,ACTION=RELEASE\CR
Global functions
In the global functions you find all the functions that allows you to adjust the basic functions of the Relay – 8. Normally the functions are used while setting up the system. If you wish to use these settings after a power cycle of the Relay – 8 please remember to use the save command.
Below is the settings for the global functions, for all commands it is mandatory that the start of the sequence look like this: NEUNIT=<A>,
Where <A> as default is 1. All commands must be started with a “,” and all lines must end with a \CR
Description: Syntax <A> Default <A> R/W
Save the current settings as the default startup values.
SAVE=TRUE W
Restore factory defaults values for the entire system.
FACTORYDEFAULT=TRUE W
Set all the values to their default (last saved). This is done by re-booting the unit.
RESET=TRUE W
Get/set unit ID You can set the unit id number either at the front of the unit using its relay test buttons. See general manual for the unit for more details. The ID that can be assigned on the front are: 1, 2, 3 ….8 By RS232 or LAN you can define any id that you want as long as they are no longer that 9 ascii charaters. e.g.: NEUNIT=1, UNITID=Neets1\CR NEUNIT=1, UNITID=RoomA\CR
UNITID=<A> Up to 9
character long.
1 R/W
Unit, SN UNITSN=<A> xxyyzzzzz R
Unit software version SWVERSION=? x.y.z R
Example of use: NEUNIT=1,UNITID=23\CR <- Set the ID number of the unit to 23.
Page 19 of 24
LAN Settings
In the LAN Settings you find the settings to set the LAN parameter for the unit. Remember that if you want the unit to use the current settings at next power up, you have to send the save command.
Below are the settings for the LAN port. For all commands the mandatory start sequence look like this: NEUNIT=<A>,SETTINGS=LAN.
Where <A> as default is 1. All commands must be started with a “,” and all lines must end with a \CR
Description: Syntax <A> Default <A> R/W
Set unit IP address IPADDRESS=<A> xxx.xxx.xxx.xxx 192.168.254.252 R/W
Set unit sub net SUBNET=<A> xxx.xxx.xxx.xxx 255.255.255.0 R/W
Set gateway GATEWAY=<A> xxx.xxx.xxx.xxx 192.168.254.252 R/W
Select if DHCP is used or not.
DHCP=<A> ON, OFF OFF R/W
LAN speed (F = Full duplex­,H = Half duplex)
SPEED=<A> 10F, 10H,
100F, 100H, AUTO
100F R/W
Set control TCP Port IPPORT=<A> 0-65555 5000 R/W
Get the MAC address of the unit.
MACADDRESS=<A> xx:xx:xx:xx:xx R
Set the multicast address the unit must use when communicating with other Neets units by LAN. (Remember when changing this value, it must also be done on all other system this unit must communicate with.) After changing the multicast address remember to send the save command in order to make sure that the system uses this address at next reboot.
MULTICASTADDRESS=<A> xxx.xxx.xxx.xxx 224.10.10.25 R/W
Set the multicast port the unit must use when communicating with other Neets units by LAN. (Remember when changing this, it must also be done in all other systems this unit must communicate with.) After changing the multi­cast port, remember to send the save command in order to make sure that the system uses this port
MULTICASTPORT=<A> 0-65555 7979 R/W
Page 20 of 24
Example of use: NEUNIT=1,SETTINGS=LAN,IPADDRESS=192.168.10.2,SUBNET=255.255.255.0,GATE­WAY=192.168.10.1\CR
Relay control
When controlling the relays you can do simple things like “Set”, “Release” and “Toggle” the relays. You can also do more advanced things, like delaying the execution of the command and setting the time that the “Set” function should apply.
Below is the possible settings of relays. For all commands, the mandatory start sequence look like this: NEUNIT=<A>,RELAY=<B>
Where <A> as default is 1, and <B> is the relay you want to control. All commands must be started with a “,” and all lines must end with a \CR
Description: Syntax <A> Default <A> R/W
Control the relay ACTION=<A> SET, RELAESE
or TOGGLE
RELEASE R/W
Delay before execution of action (Start delay)
DELAY=<A> 0-6500.0 0 W
Time (chances the action from latch to momentary in this time)
TIME=<A> 0-6500.0 0 W
Example of use: NEUNIT=1,RELAY=1,ACTION=SET,TIME=10.5\CR <- This command sets relay 1 in 10.5 seconds. To get the current status of a relay use this command: NEUNIT=1,RELAY=1,ACTION=?\CR Reply: NEUNIT=1,RELAY=1,ACTION=RELEASE\CR
Screen control settings
The screen control offers you an easy and safe way to control electrical screens and lifts using 2 relays or I/O. When combining 2 relays in screen mode, you define the screen up and down time once. After this you simply send command indicating the direction the screen should move. The Screen mode ensures that the 2 relays or I/O in no way can be activated at the same time.
Below are the settings for the screen control, for all commands the mandatory start sequence look like this: NEUNIT=<A>,SETTINGS=SCREEN,SCREEN=<B>.
Where <A> as default is 1 and <B> is the number of the screen you want to configured. All com­mands must be started with a “,” and all lines must end with a \CR.
Page 21 of 24
Description: Syntax <A> Default <A> R/W
Select the screen that
should be congured
SCREEN=<A>
<A> R/W
1 IO 1 and 2
2 IO 3 and 4
3 IO 5 and 6
4 IO 7 and 8
5 Relay 1 and 2
6 Relay 3 and 4
7 Relay 5 and 6
8 Relay 7 and 8
W
Enable or disable the screen mode
ENABLED=<A> TRUE or FLASE FALSE R/W
Delay time, pause time between the two outputs can be activated
BLOCKTIME=<A> 0-6500.0 second 0 R/W
Up time, The time it takes the screen to move from bottom to top of the screen.
UPTIME=<A> 0-6500.0 second 0 R/W
Down time, The time it takes the screen to move from top to bottom of the screen.
DOWNTIME=<A> 0-6500.0 second 0 R/W
Example: NEUNIT=1,SETTINGS=SCREEN,SCREEN=2,ENABLED=TRUE\CR <-Combine IO 3 and 4 on screen mode.
Example: NEUNIT=1,SETTINGS=SCREEN,SCREEN=2,UPTIME=35,DOWNTIME=30,BLOCKTIME=1.5\CR <-Set screen 2 to a uptime of 35 sec, a down time to 30 sec and a block time to 1,5 sec.
Screen control
Below are the possible settings of screen control, For all commands the mandatory start se­quence look like this: NEUNIT=<A>,SCREEN=<B>
Where <A> as default 1, and <B> is the screen you want to control. All commands must be started with a “,” and all lines must end with a \CR
Description: Syntax <A> R/W
Control the Screen ACTION=<A> UP, DOWN, STOP R/W
Example of use: NEUNIT=1,SCREEN=2,ACTION=UP\CR <- This command makes screen 2 go up in the time defined by the command “UPTIME” found in the “Screen control settings” section.
Page 22 of 24
Input/output settings
Below is the settings for the I/O, for all commands are the mandatory start sequence look like this: NEUNIT=<A>,SETTINGS=IO,IO=<B>
Where <A> as default is 1 and <B> is the number of the I/O you want to configured. All com­mands must be started with a “,” and all lines must end with a \CR
Description: Syntax <A> Default <A> R/W
Set the I/O to input or output FUNCTION=<A> INPUT or OUTPUT INPUT R/W
Set to use PUSH or PULL mode for status change on input. This is a global setting that applies for all IO.
In PULL mode you have to request the status of all input you want to know the state of like this; NEUNIT=1,SET­TINGS=IO,MESSAGE=PUSH\ CR
In PUSH mode the Relay – 8 will send a message to you when there is a change on one of the inputs.
E.g. NEUNIT=1,IO=1,STA­TUS=HIGH\CR
MESSAGE=<A> PUSH or PULL PULL R/W
Link input to relay activation
Input 1 is linked to relay 1
Input 2 is linked to relay 2
Input 8 is linked to relay 8
When a relay is linked to an input this will apply until they are either unlinked or a command that control either the relay or the input are received.
LINK=<A> TRUE or FALSE TRUE R/W
Example: NEUNIT=1,SETTINGS=IO,IO=2,FUNCTION=INPUT\CR <- This set output 2 to input
Page 23 of 24
Output control
Below is the possible control of I/O, for all commands the mandatory start sequence look like this: NEUNIT=<A>,IO=<B>
Where <A> as default is 1, and <B> is the I/O you want to control. All commands must be start­ed with a “,” and all lines must end with a \CR
Description: Syntax <A> R/W
Control the output ACTION=<A> SET, RELEASE or TOGGLE R/W
Delay before executed of action (Start delay)
DELAY=<A> 0-6500.0 second W
Time (chances the action from latch to momentary in this time)
TIME=<A> 0-6500.0 second W
Read the input
reply example:
NEUNIT=1,IO=1,STATUS=HIGH\CR
STATUS=? HIGH, LOW R
Example of use: NEUNIT=1,IO=2,ACTION=SET,TIME=10.5\CR <- This command sets IO 2 in 10.5 seconds
RS-232 settings
Below are the settings for the RS232. For all commands the mandatory start sequence look like this: NEUNIT=<A>,SETTINGS=RS232, RS232=<B>
Where <A> as default is 1, and <B> is the RS232 port number to make settings for. All com­mands must be started with a “,” and all lines must end with a \CR
Description: Syntax <A> Default <A> R/W
Set the comport baud rate BAUDRATE=<A> 1200, 2400,
4800, 9600, 14400, 19200, 38400, 57600, 115200
19200 R/W
Set the comport data bit DATABIT=<A> 7, 8 8 R/W
Set the comport parity PARITY=<A> NONE, ODD or
EVEN
NONE R/W
Set the comport stop bit STOPBIT=<A> 1 or 2 1 R/W
Set the comport TCP Portnumber (if used as LAN gateway)
IPPORT=<A> 0-65555 1:5011
2:5012
R/W
Example of use: NEUNIT=1,SETTINGS=RS232,RS232=1,BAUDRATE=19200,DATABIT=7\CR
Page 24 of 24
RS-232 command
Below are the settings for the COM port. For all commands the mandatory start sequence look like this: NEUNIT=<A>,RS232=<B>
Where <A> as default is 1, and <B> is the COM port number to use. All commands must be started with a “,” and all lines must end with a \CR
Description: Syntax <A> Default <A> R/W
Data container. Each byte must be converted to a 2 byte ASCII value.
Fx: “Neets” becomes “4E65657473”
DATA=<A> Up to 500 byte of
date
R/W
Example of use: NEUNIT=1,RS232=2,DATA=4E65657473\CR send “Neets” on RS232 port 2
IR command (Advanced users)
On the Tx 1 and 2 it is also possible to send IR codes. Sending IR codes is only possible when con­trolling the unit over LAN.
Before you start working with sending IR commands it is important to understand that this part of the system are intended for advance users and requires a high level of IR code knowledge. The format of the IR code that are used are a common used format. This allows you to easily find IR codes from other sources than Neets, e.g. www.remotecentral.com
If you want to control things like volume on a device you should remember to retransmit the IR command as long as you want the volume to change. (Remember to wait for the acknowledgement of sending IR command before sending the next)
Below are the settings for the IR. For all commands the mandatory start sequence look like this: NEUNIT=<A>,IR=<B>
Where <A> as default is 1, and <B> is the IR port number to use. All commands must be start­ed with a “,” and all lines must end with a \CR
Description: Syntax <A> Format R/W
Data container. The data are in RAW IR code format. Can be copied directly from Neets Device Editor.
DATA=<A> Up to 500 byte of
date
xxxx yyyy …. zzzz R/W
Example of use: NEUNIT=1,IR=2,DATA=0000 006D 0022 0002 0155 00AB 0015 0040 0016 0015 0015 0015 0016 0040 0015 0040 0016 003F 0016 0040 0015 0015 0016 0015 0016 003F 0016 0040 0015 0015 0016 0015 0016 0015 0015 0015 0016 0040 0015 0040 0016 0015 0015 0015 0016 0015 0016 0015 0015 0015 0016 0015 0016 0015 0015 0015 0016 0040 0015 0040 0016 003F 0016 0040 0015 0040 0016 003F 0016 0040 0015 05E9 0156 0055 0016 0E3F\CR <-Sending a IR command on the Tx 2 port.