Navien KDB-735GTD, KDB-535GTS, KDB-535GTG, KDB-535GPS, KDB-735GTS Installation Manual

...
Medium-sized gas boiler
29
1. Precautions for safety--------------------------------------30
2. Outside drawing of the boiler ----------------------------31
4. Electric wiring installation --------------------------------37
5. Gas piping installation-------------------------------------39
6. Heating and hot water piping installation --------------41
7. Exhaust / Intake vent installation ------------------------47
8. Temperature controller installation ---------------------- 52
9. Check points for test operation---------------------------53
10. Electric wiring diagram --------------------------------- 55
11. Specifications------------------------------------------------56
This installation manual is subject to change without notice for quality improvement.
Table of
contents
Medium-sized gas boiler
30
Precautions for safety
The instructions provided in this installation manual include important information for safe use of this product. Failure of complying with those instructions may result in death, severe injury, or tremendous loss of property.
The instructions for safe use are classified into Danger’, ‘Warning’,
Caution
by the degree of danger, which respectively contains the
following meaning.
Violation of instructions may cause a seriously dangerous situation such as death or a severe injury
Violation of instructions may cause a potentially dangerous situation such as death or severe injury.
Violation of instructions may cause a potentially dangerous situation such as a light or half-serious injury.
Violation of instructions may cause a situation such as a property loss, product malfunction, or deteriorated performance.
1) The symbols provided in the product and the installation manual contains the
following meaning.
This symbol implies that “precautions” shall be taken against a possibility of a personal injury under a specific condition.
This symbol implies that a “prohibition” shall be made against a possibility of a personal injury or a property loss under a specific condition.
This symbol implies that the instructions shall be complied with.
2) The warnings and cautions specified in the installation manual do not include all
the possible safety precautions to be taken for using the product. Consequently,
utmost care shall be taken for safety during use of the product.
1
Medium-sized gas boiler
31
Outside drawing of the boiler
Model no.:
KDB-535GTD, GTS, GTG
The sizes in the blank “( )” are applied to the model no..
A dedicated boiler (GTS, GTG) is not supplied with the hot water inlet and outlet on the rear of
the boiler.
Model no.:
KDB-535GPD, GPS
The sizes in the blank “( )” are applied to the model no.
A dedicated boiler (GPS) is not supplied with the hot water inlet and outlet on the rear of the
boiler.
2
Medium-sized gas boiler
32
Model no.:
KDB-735GTD, GTS, GTG
The sizes in the blank “( )” are applied to the model no..
A dedicated boiler (GTS, GTG) is not supplied with the hot water inlet and outlet on the rear of
the boiler.
Model no.:
KDB-735GPD, GPS
The sizes in the blank “( )” are applied to the model no.
A dedicated boiler (GPS) is not supplied with the hot water inlet and outlet on the rear of the
boiler.
Medium-sized gas boiler
33
Model no.:
KDB-1035GPD, GPS, GPG
1535GPD, GPS, GPG
2035GPD, GPS, GPG
The sizes in the blank “( )” are applied to the model no. 1535, and those in the bracket “[ ]” are to the
model no. 2035GPD, GPS, GPG.
A dedicated boiler (GPS, GPG) is not supplied with the hot water inlet and outlet on the rear of the
boiler.
Medium-sized gas boiler
34
Safe and correct installation method
After completion of installation, be sure to return the user’s (installation) manual to the user.
Be sure to check the gas to be used in the installation place, prior to installation.
Use of the gas, other than the one specified on the
name plate on the front of the boiler, may result in a fire or explosion.
Be sure to check the power supply gas to be used in the installation place, prior to installation.
 The power supply, if higher or lower than the one
specified on the front of the boiler, may cause a fire.
After reading the following instructions, install the product in a safe and correct way as
specified in the instructions.
Never install the boiler in a place with inflammable objects.
Highly inflammable materials, such as volatile
oil or alcohol, may cause a fire during ignition of the boiler.
Install the boiler in a boiler room free froml the impact of rain and wind.
Incomplete combustions, resulting from rain and
wind, may eventually lead to a carbon oxide poisoning.
3
Before installation
Selection of the installation place
Medium-sized gas boiler
35
Never install the boiler in a moist or enclosed
place such as a bathroom, a toilet.
Incomplete combustion, caused by oxygen
deficiency, may lead to a carbon oxide poisoning.
Installation in the above place may also cause
earlier product malfunctions.
Never install the product with corrosive gas such as ammonia, chlorine, sulfur, acids.
Corrosive gas may damage the boiler and cause
incomplete combustion, eventually leading to a carbon oxide poisoning.
Never install the boiler in the following areas.
Do not install the boiler near the electric equipment. Do not install the boiler in an uneven or unstable place. Do not install the boiler in a place with highly combustible materials. Do not install the boiler in a place inadequate for safe gas piping installation. Do not install the boiler in a place with special chemical agents
(generating combustible or corrosive gas).
Do not install the boiler in a place where it is difficult to get access to the
stairway or the exit for escaping.
Do not install the boiler in a place which is not well drained. Do not install the boiler below the shelf with unstable objects. Do not install the boiler in a place where it is difficult to conduct
maintenance of the boiler after installation.
Do not install the boiler in a place with noise and air pollution. Do not install the boiler in a place where the wind generated from a vent, a
range, and a hood have an impact on the air intake and exhaust.
Do not install the boiler in a place which is not well-ventilated. Do not install the boiler in a place with strong wind. Do not install the boiler in a place where it is difficult to install the
chimney pipe (chimney).
Be sure to install the boiler in a sufficient place for check up and repair of the boiler. A space of more than 1m shall be provided in front of the boiler, in order to perform maintenance and checks.
Other considerations
Medium-sized gas boiler
36
Install the boiler on the surface with a structure capable of enduring the load of the boiler (weight). (Refer to the
specifications presented in the user’s manual.)
Install the boiler in a horizontal, upright position so that the boiler does not lean toward one side.
Installation shall be made for the front side of the boiler to face forward.
Install the boiler to be fixed on the floor, in order to prevent vibration during operation.
Sufficient light shall be provided with the boiler room in order to help to observe the boiler equipment by sight
and offer the after-sales service for the equipment.
Be sure to install the boiler in the dedicated boiler room. (The boiler room shall be designed so that the gas
emitted from the boiler does not flow into the living room, and the wall between the boiler room and the living room shall be made of the fireproof materials, except for the entrance / exit door.)
The dedicated boiler room shall not be equipped with the ventilating fan which causes the negative pressure (the
pressure lower than the atmosphere pressure).
The dedicated boiler room shall not be equipped with the exhaust duct of the gas range (hood) which leads to air
flowing in and out of the living room and the kitchen.
Installation of the boiler shall not be made nearby the place for storage and treatment of the combustible or
inflammable objects. A sufficient space shall be provided for boiler installation as presented in the following figure, in order to perform the control, combustion, check-ups and repair of the boiler.
The top of the boiler body shall be kept at least 1.2m away from the structures such as the ceiling and the piping.
The boiler body shall be kept at least 450mm away from other structures such as the wall and the piping on the side of the
boiler.
The front of the boiler shall be kept more than 1m away from the structures in front of the wall.
The boiler shall be kept away from the nearby combustible objects, as illustrated in the following figure.
Appropriate facilities such as the casing shall be equipped with the boiler to prevent the rain from permeating into
the boiler.
The waterproof treatment shall be applied to the exposed insulation materials or lagging.
Proper measures shall be taken to protect the water pipe outside the boiler from getting frozen.
Proper measures shall be taken for boiler combustion to be protected against snow, rain and wind.
Precautions for boiler installation in a dedicated boiler room
Boiler installation method
Precautions for installation of the boiler in the outdoors
Medium-sized gas boiler
37
Electric wiring installation
The electric wiring installation shall be
performed to comply with the power supply of the product.
The power supply, if higher or lower than the one
specified on the name plate on the front of the boiler, may cause a fire.
Do not connect the power supply to the boiler until the
electric wiring installation is completed.
With the power supply on, the electricity flowing through the
boiler may cause an electric shock.
Install the power outlet in a place free from the impact of rain and moisture.
Electric leakage, possibly resulting from rain and
moisture, may cause a fire.
4
Medium-sized gas boiler
38
Never make a ground connection to the lightning
rods and the gas pipe.
Ground connection to the lightning rod may result in a boiler
malfunction.
Ground connection to the gas pipe may result in an explosive
accident.
Be sure to use the magnet switch for connection of the
circulation pump with more than 1.5kW.
The boiler may malfunction, without the magnet switch.
Install the electric wiring as presented in the electric wiring drawing in the installation manual.
Install the dedicated power outlet for the boiler, with a length of less than the effective length of
the power cord. Installation shall be made for the power outlet not to get in contact with the drain valve of the boiler.
Use the power outlet with a cover attached, and install the outlet at more than 300m above
ground level.
If the power outlet is not provided with a cover, install the outlet in a place free from the impact
of rain or moisture, or in the waterproof box or the indoor distribution box.
Never install a switch onto the power cord, nor use the power outlet with a switch attached. (The
boiler does not operate, when the switch is set at off.)
A ground connection shall be installed, if not, on the side of the power outlet.
The wires of the room temperature controller shall be connected through the insulation pipe with
a thickness of more than 4mm. The insulation pipe shall be installed and concealed with an upper gradient toward the indoors.
The wires of the circulation pump, connected to the controller, shall not be
short-circuited.
Correct electric wiring installation
Medium-sized gas boiler
39
Gas piping installation
Be sure to perform the gas leak test after gas pipe installation, replacement of the burner, or the supply pressure or head pressure test.
Retention of the leaked gas, combined with static electricity or
spark, may cause a fire
In preparaion for the unexpected gas leak, be sure to install the gas leak alarm device and the gas breaker in the boiler room.
Retention of the leaked gas, combined with static electricity
or spark, may cause a fire
Be sure to check the gas to be used for the product prior to gas piping installation.
Use of the gas, other than the one specified on the name plate
on the front of the boiler, may cause incomplete combustion,
eventually leading to a fire or explosive ignition.
Install the gas holder, if used, in the well-ventilated outdoor without above ground high voltage power line. The gas holder shall be fixed not to fall down on the ground.
If the gas holder falls down or gets in contact with the high
voltage power line, an explosive accident may occur.
5
Medium-sized gas boiler
40
The gas piping installation shall be performed by the gas
company and the gas piping installation company.
1
Refer to the “Specifications” presented in this installation
manual, with regard to the connection size.
2
Use the metal pipe or the metal flexible pipe which passed a gas appliance test for gas piping. When LP gas is used, never install the fuse cock, and be sure to install the gas middle valve. (Installation of the fuse cock may cause a boiler malfunction.)
3
The following shall be kept in mind, when using LP gas.
The domestic low pressure regulator, appropriate for the
indicated gas consumption, shall be used as the LP gas regulator.
2 or more vessels with a weight of 50kg shall be installed
to be used for the LP gas vessel. (Connect the twin valve to simultaneously supply the gas from 2 vessels.)
The vessels with a small capacity may result in gas loss
for lack of vaporization volume, which may cause a boiler malfunction.
4
Be sure to connect the gas pipe directly to the main pipe. Never connect the gas pipe in common with other gas appliances.
5
A
separable union connection or a nut connection
shall be made on the connection points.
6
The gas pipe shall be installed with its surface exposed to the outside. However, the copper pipe, the stainless steel pipe, or other pipes made of heat- and corrosion-resistant materials without connection joints (except for welding joints) may be buried for installation.
7
Be sure to install the gas leak alarm device and the gas breaker in the boiler room.
LP gas: lower than the boiler
(300mm above the ground level)
LNG : higher than the boiler
Medium-sized gas boiler
41
The piping materials shall comply with the Korea Standard.
Gas pipe
Carbon steel pipe for fuel gas piping, Copper or copper alloy pipe,
Metal flexible pipe which passed the gas appliance test
Heating pipe Copper or copper alloy pipeInsulation, XLPE pipe+Insulation
Hot water
pipe
Copper or copper alloy pipeInsulation, XLPE pipe+Insulation
Items
Distance from the gas pipe
Flue pipe & chimney 300mm or more
Electric switch, Power outlet 300mm or more
Electricity meter, Safety cutout 600mm or more
Wire 150mm
Size of the pipe Interval
13mm or less To fix every 1m
13mm~33mm To fix every 2m
33mm or more To every 3m
Piping materials
Piping installation
Fixing the pipe
Medium-sized gas boiler
42
Heating and hot water piping installation
The exposed pipes shall be heat insulated with the insulation material.
The exposes pipes may get frozen in the winter.
If the water supply pipe is frozen, the hot water is not
supplied. When the heating pipe has run out of water, the water is not supplemented. Consequently, the boiler can not operate normally.
Fix the parts of the boiler pipes with appropriate tools, prior to piping installation.
Do not exert excessive force on the pipe during the
installation, Damages on the parts may cause a water leak.
Be sure to use the insulation flange on the heating inlet and outlet in case of installation of the copper pipe (the hot water inlet and outlet for a boiler dedicated for hot water supply).
Failure to use the insulation flange may cause rapid
corrosion (rusty water).
We do not take the responsibility of the problems arising from
failure to use the insulation flange.
Do not use water, other than the tap water, for the boiler.
Salt content in the sea water or spa water may accelerate
corrosion and shorten the life of the boiler.
We do not take the responsibility of the problems caused by
using water, other than the tap water.
Install the pipes as illustrated in the standard pipe drawing.
Failure to install the pipe as illustrated in the standard
piping drawing may deteriorate the efficiency of the boiler and the circulation of the heating water, which may result in a boiler malfunction.
6
Medium-sized gas boiler
43
A separable union connection or a nut connection shall be performed on the connection points.
The piping materials shall comply with the Korea Standard.
 Do not use the metals with different electric potentials to install the piping in the
dedicated boiler for hot water supply, (For example, do not install the copper pipe in the iron boiler.) which may cause galvanic corrosion, eventually generating rusty water.
Do
not
use the rubber hose for the faucet, when installing the piping.
Be
sure
to remove foreign objects inside the pipe prior to the piping installation.
Install the piping correctly for the water supply, the hot water supply, the heating, and
the drain.
The
heating
pipe shall be equipped with the heating strainer.
If the
water
supply pressure exceeds the allowable working pressure specified on the
name plate, be sure to install the depressurizing valve.
Proper
measures
shall be taken against a water leak through a water leak test for the
entire piping after completion of installation.
The entire pipelines, except for the gas pipe, shall be provided with heat insulation to
protect against getting frost, after completion of installation. (Especially, care shall be taken for the water supply and the hot water pipes.)
Be sure to install the pressure release pipe for installation of the boiler. If it is
impossible to install the pressure release pipe, the safety valve, operating below the maximum allowable working pressure of the boiler, shall be installed. (The maximum allowable working pressure of the boiler is presented in the “Specifications”.)
Never install the valve and the check valve in the pipeline where the pressure release
pipe or the safety valve is installed.
Select the boiler expansion tank, if necessary, with a capacity suitable for the boiler
in use.
Do not use the water inlet for the purpose of the drain, and vice versa.
If the water is supplied to the boiler from the rooftop water tank, be sure to install the
water supply pipe in the auxiliary tank, separate from the rooftop water tank, for water supply to the boiler.
Install the pipes as illustrated in the standard pipe drawing.
Precautions for piping installation
Considerations in common
Medium-sized gas boiler
44
Model no. : KDB-535, 735 GTD, GTS
KDB-535, 735, 1035, 1535, 2035 GPD, GPS
Open piping system
- Be sure to comply with the instructions presented in the “Considerations in common”.
- Be sure to install the air vent valve in the distributor.
- The return water distributor shall be installed below the heating inlet on the boiler.
- The pressure release pipe shall be installed to exceed 25A.
- Never supply the water with a pressure higher than the maximum allowable working
pressure of the boiler specified on the name plate, nor connect the water pipe directly
for the piping.
- The reverse flow of the heating water into the expansion tank, while operating or
stopping the circulation pump, results from too much air in the pipe. (Open the valve in
the distributor one by one and remove the air from the pipe, while operating the
circulation pump.)
- The expansion tank shall be installed at least 1.5m above the heat dissipation surface in
case of the upward type, and at least 1.5m above the top of the boiler in case of the
downward type.
- The piping installation shall be performed not to mix the heating water and the hot
water.
Closed piping system
- Be sure to comply with the instructions presented in the “Considerations in common”.
- Be sure to install the strainer, the depressurizing valve, the check valve, and the closed
expansion tank, in order to directly connect the boiler to the water pipe.
- Be sure to install the depressurizing valve and the check valve in the water supply pipe.
- Install the air vent on top of the heat dissipation surface to facilitate air vent.
- Be sure to install the strainer in the water supply pipe, in order to prevent metal and
foreign objects from flowing into the water supply pipe.
- Be sure to install the safety valve.
- Be sure to install the closed expansion tank with an appropriate capacity.
Precautions for the piping installation for the combi boiler for
heating and hot water supply / the dedicated boiler for heating
Medium-sized gas boiler
45
Composition
1. Body
2. Cap
3. Cap gasket
4. Strainer screen
Features:
The device is to remove foreign objects in the boiler and the heating pipeline.
1. Prevention of corrosion in the pipe: The portion of accumulated foreign objects inside the pipe gets corroded first. Accordingly, the foreign objects shall be strained to prevent corrosion.
2. Extension of the boiler life: The accumulated foreign objects obstruct heat transfer, and the accumulated portion is overheated, which shortens the life of the boiler. Consequently, the foreign objects shall be strained to extend the boiler life.
3. Protection of main equipment: The heating circulation pump, the valve, and other equipment are protected from being damaged by foreign objects.
Installation method
1. Install the strainer in the direction of the heating water flow, as indicated in the body of the heating strainer.
2. You may install the strainer in a horizontal or vertical direction, as desired.
3. Install the valves on each end of the heating strainer, in order to prevent the heating water from draining during cleaning of the strainer.
4. The pocket shall be installed to face the ground surface, and a sufficient space shall be provided for cleaning the strainer.
The method of cleaning (Removal of foreign objects)
1. Close the valves on each side of the strainer, to completely shut off the heating water.
2. Open the cap to remove the foreign objects on the strainer screen.(! Caution: Care shall be taken against a burn, possibly caused by the heating water.)
3. After cleaning, check if there is a leak of the heating water. Then, open the valve to use the strainer.
4. The heating strainer shall be cleaned periodically. At the beginning of use, foreign objects usually remain in the pipe, which shall be cleaned out.
STRAINER
Medium-sized gas boiler
46
Model no.: KDB-535, 735 GTG KDB-1035, 1535, 2035 GPG
Open piping system
- Be sure to comply with the instructions presented in the “Considerations in common”.
- Never supply the water with a pressure higher than the maximum allowable working pressure of the boiler specified on the name plate, nor connect the water pipe directly for the piping.
- Be sure to use the coated piping material and the stainless piping material for the dedicated boiler for hot water supply.
- The pressure release pipe shall be installed to exceed 25A.
- The expansion tank shall be installed at least 1.5m above the maximum height of the hot water pipe in case of the upward type, and at least 1.5m above the top of the boiler in case of the downward type.
- When installing the hot water storage tank, connect the hot water outlet to lower part (inlet) of the hot water tank, and the hot water inlet to the upper part (outlet) of the hot water tank.
- Use the connection wire to the circulation pump of the boiler to install the hot water storage tank separately.
- If the water pressure is too low, attach an additional pump to the hot water outlet.
- When attaching an additional pump, be sure to install the pressure switch (S/W) and the check valve. (Do not connect them to the wire of the circulation pump of the boiler.)
Closed piping system
-Be sure to comply with the instructions presented in the “Considerations in common”.
- Be sure to install the strainer, the depressurizing valve, the check valve, the safety valve, and the closed expansion tank, in order to directly connect the boiler to the water pipe.
- Be sure to use the coated piping material and the stainless piping material for the dedicated boiler for hot water supply.
- Be sure to install the depressurizing valve and the check valve in the water supply pipe.
- Install the air vent on top of the hot water supply pipe to facilitate air vent.
- Be sure to install the safety valve.
- Be sure to install the closed expansion tank with an appropriate capacity.
- When installing the hot water storage tank, connect the hot water outlet to lower part (inlet) of the hot water tank, and the hot water inlet to the upper part (outlet) of the hot water tank.
-
Use the connection wire to the circulation pump of the boiler, in order to install the hot
water storage tank separately.
- If the water pressure is too low, attach an additional pump to the hot water outlet.
-
When attaching an additional pump, be sure to install the pressure switch (S/W) and the
check valve. (Do not connect them to the wire of the circulation pump of the boiler.)
Precautions for the piping installation for the
dedicated boiler for hot water supply
Medium-sized gas boiler
47
Exhaust / Intake vent installation
Installation of the exhaust and intake chimney pipe (chimney) shall be performed in a specified method.
Incorrect installation of the exhaust and intake
chimney pipe (chimney) may lead to an exhaust gas poisoning.
The connection points of the exhaust and intake pipes shall be free from any leakage.
The exhaust gas, if flowing into the indoors, may
cause carbon oxide poisoning.
The air intake or the exhaust vent shall be installed in the outdoors or a well-ventilated place where the exhaust gas emitted from the vent does not flow into the indoors.
The exhaust gas, if flowing into the indoors, may
cause carbon oxide poisoning.
Be sure to install the air intake and the exhaust vent.
Failure of ventilation may lead to incomplete
combustion due to oxygen deficiency, which may eventually result in carbon oxide poisoning.
The boiler of the forced exhaust type (FE) can not employ the multiple exhaust ducts.
The reverse flow of the exhaust gas may cause
carbon oxide poisoning.
7
Medium-sized gas boiler
48
The horizontal section of the chimney pipe shall be installed to be inclined downward at an angle of 5°, to prevent the condensed water or rain from flowing in reverse into the boiler.
Flow of the condensed water or rain into the
boiler may deteriorate the performance of the boiler and shorten the life of the boiler.
r
The exhaust duct type of the forced exhaust type (FE) boiler: the single exhaust type, the
chamber type, the shared exhaust type
The total length of the exhaust duct shall be kept to 10m or less, and the curved parts to 3
segments or less. (except for the curve on the edge point of the exhaust duct)
■ The connection size of the exhaust duct shall comply with the specifications. (Refer to the
specifications.)
Care shall be taken to prevent the middle part of the exhaust duct from getting narrower. The
exhaust duct shall be installed to keep the radius of the curved part at maximum as possible.
The exhaust duct shall be heat insulated with the non-flammable insulation material.
Installation of the chimney pipe for the forced exhaust type (FE) boiler
Medium-sized gas boiler
49
The exhaust duct shall be made of the stainless steel (pipe) or the heat- and corrosion-
resistant metal.
The exhaust duct shall be connected, if necessary, to the boiler tightly not to be pulled
out or shaken.
If the exhaust duct passes through the combustible wall or the ceiling made of
combustible material, the exhaust duct shall be heat insulated with a non-flammable material with a thickness of more than 20mm, and kept at least 50mm away from the wall or the ceiling. In addition, the exhaust duct, if passing through the ceiling, shall be equipped with the inspection hole.
The exhaust duct shall be installed as a single unit, if possible. Never use the exhaust
duct in common with the heaters of the natural exhaust type or those using other fuel (briquette, petroleum).
The air intake shall be provided in a well-ventilated place such as the outdoors, into
which the exhaust gas emitted from the exhaust duct does not flow. (
Make sure that failure of air intake and ventilation causes oxygen deficiency,
eventually leading to incomplete combustion.)
Bore holes in the wall to install the vent on the upper side of the wall and the air intake
on the lower side, to facilitate ventilation.
The effective cross-sectional area of the air intake or the vent shall be larger than that of
the exhaust duct.
The bird protection net shall be installed on top of the exhaust duct so that birds, mice or
objects with a diameter of more 16mm can not go into the exhaust duct.
A space of more than 300mm shall be provided between the top of the exhaust duct and
the outer wall surface, if non-flammable.
If the exhaust duct is to be installed and concealed into the ceiling, the connection points
shall be securely connected to prevent exhaust gas leakage. Then, wind a non-flammable material, other than the metal, around the connection points.
Finish the connection points using the heat resistant silicon (except for the plaster bandage).
Install the inspection hole to check and repair the exhaust pipe in a dark side.
In order to extend the exhaust pipe, install one hanger at least every 900mm and tighten the
installed hangers securely. (in case of the pipe extension with a length of more than 1m)
Incorrect installation of the exhaust pipe may cause deteriorated performance of the
product as well as a disaster. Consequently, the installation shall be performed in accordance with this manual.
Installation of the chimney pipe
Medium-sized gas boiler
50
Combi boiler for heating and hot water supply-
Open expansion tank”
Standard piping drawing
Combi boiler for heating and hot water supply-
Closed expansion tank”
Medium-sized gas boiler
51
Dedicated boiler for hot water supply
Closed expansion tank”
Medium-sized gas boiler
52
Installation of the temperature controller
Install the temperature controller on the wall of the room to be provided with
frequent indoor heating.
The temperature controller shall be installed 1.2m to 1.5m above the floor, with
sufficient air circulation.
Do not install the controller in a place nearby the frequently opened door, or
where cold wind blows, or under direct sunlight, or easily accessible by children.
(The example of the installation place, : Temperature controller
1. Connect 2 temperature controller wires from the boiler to 2 wires on the rear side of the temperature controller securely.
2. Fix the bracket of the temperature controller onto the desired position on the wall, or into the holes of the wall outlet using a bolt.
3. Install the temperature controller by hanging the connection wire onto the bracket carefully in the desired direction.
Note : Do not exert excessive force while connecting the wire, and secure the bolt tightly. Pushing the
temperature controller upward will separate the temperature controller and the bracket. If the cover of the wire peels off or the terminal connection is inferior, the temperature controller may not function normally. Consequently, care shall be taken for the insulation treatment of the temperature controller.
8
Installation place
Installation method
Medium-sized gas boiler
53
Check points for test operation
1) Check if the boiler is installed correctly.
Check if the floor surface is made of strong and flat non-flammable materials
such as concrete and if the surrounding area is also made of non-flammable
materials.
Check the air intake and vent in the boiler room.
Check if the boiler room is provided with a drain, and if the boiler is equipped
with the drain valve.
Check if the boiler and the pipeline are heat insulated to prevent frost damage.
Check if the flue pipe is correctly installed.
Check if rain does not permeate through the penetration portion of the exhaust
pipe.
Check if the boiler is evenly installed.
Check if there is water leakage near the piping connection joint.
Check if there is any leakage near the gas pipe connection joint.
Check if the boiler room is equipped with the gas leak alarm device and the gas
breaker.
The location of installation of the gas leak alarm device
LNG : 300mm from the ceiling
LPG : 300mm from the floor
Check if the fuel is the same as the gas specified on the name plate of the boiler.
Check if the pressure release pipe or the safety valve are installed in the boiler.
Check if the ground wire is connected. (If the ground connection is made on the
fuel pipe or the lightning rod, change the position.)
9
Medium-sized gas boiler
54
1) Open the water supply valve to supplement water in the boiler.
The water supply pressure shall be kept to less than the allowable working pressure,
specified on the name plate of the boiler.
Upon completion of water supplement, the makeup water lamp on the controller
goes out.
2) Connect the boiler to the power supply.
Do not touch the power cord with wet hands.
3) Push the power switch of the boiler controller to on.
4) Open the valve on the fuel line.
5) Set the room temperature controller S/W at the operation mode.
6) After ignition of the boiler, check the combustion mode and the heating
circulation mode.
Set the temperature on the temperature controller Set the room temperature
controller button (High speed, Temperature, Time) at ON Operation of the burner fan Check the gas pressure Check the wind pressure Operation of the ignition transformer Open the 1
st
and 2nd gas valve
Ignition Flame detection Combustion ON/OFF in accordance with
the temperature setting (operation of the circulation pump)
Check if the boiler stops operation and the circulation pump is operating, by
adjusting the temperature controller from the boiler controller.
7) Press the “Hot water” button on the room temperature controller (DR-1), in
order to check if the circulation pump stops operation and hot water is supplied.
8) Press the “Outside” button on the room temperature controller to check if the
boiler stops operation.
Test operation
Medium-sized gas boiler
55
Electric Wiring Diagram
10
Medium-sized gas boiler
56
Specifications
1) Stainless boiler
Model no.
Classification
535GTD 535GTS 535GTG 735GTD 735GTS 735GTG
Heating output
kcal/h
(kW)
50,000
(58.1)
50,000
(58.1)
-
70,000
(81.3)
70,000
(81.3)
-
Hot water output
kcal/h
(kW)
50,000
(58.1)
-
50,000
(58.1)
70,000
(81.3)
-
70,000
(81.3)
Hot water supply capacity (△ 40℃)
/min
21 - 21 29 - 29
Purpose
Combi
Heating
only
Hot water
only
Combi
Heating
only
Hot water
only
LNG
%
92.3 92.2 92.2 92.6 92.8 92.8
Efficieny (Total)
LPG
%
92.3 92.2 92.2 92.6 92.8 92.8
Fuel
City gas (13A), LP gas
Maximim allowable working pressure
kgf/cm
2
(MPa)
3.5 (0.343)
Heat transfer area
m2
1.96 2.78
Heating area
m2
100 100 - 140 140 -
Volume of pipe water
40 46 46 60 68 68
Weight
kg
100 93 93 110 102 102
Power supply
1φ, 220V, 50Hz
Burner Model no.
KPG-50A KPG-70A
Power consumption
W
143 208
Gas pressure
mmH2O
LN gas : 200
50
100
, LP gas : 280±50
Fuel consumption
LNG : 61,000kcal/h(70.9kW) LPG : 5.1kg/h(70.9kW)
LNG : 84,000kcal/h(97.6kW) LPG : 7kg/h(97.6kW)
Width
Ng mm
547 547
Depth + Burner
mm
848 837
size
Height
mm
1,032 1,240
Heating inlet
·
Outlet
A
40 40 - 40 40 -
Drain
A
40 40 40 40 40 40
Discharge outlet
A
40 40 40 40 40 40
Hot water inout·Outlet
A
20
40 20 - 40
Piping size
Gas inlet
A
15
Chimney size
φ
148
Exhaust gas
250 or less
The specifications presented in this manual is subject to change without notice for quality improvement.
11
Medium-sized gas boiler
57
2) Steel boiler
Model
Classification
535GPD 535GPS 735GPD 735GPS
Heating output
kcal/h
(kW)
50,000
(58.1)
50,000
(58.1)
70,000
(81.3)
70,000
(81.3)
Hot water output
kcal/h
(kW)
50,000
(58.1)
-
70,000
(81.3)
-
Hot water supply capacity (△
40℃)
/min
21
-
29 -
Purpose
Combi Heating only Combi Heating only
LNG
%
92.6 92.7 92.8 92.8
Efficiency (Total)
LPG
%
92.6 92.7 92.8 92.8
Fuel
City gas (13A), LP gas
Maximum allowable working pressure
kgf/cm
2
(MPa)
3.5 (0.343)
Heat transfer area
m2
2.34 3.10
Heating area
m2
100 100 140 140
Volume of pipe water
56 63 72 85
Weight
kg
151 146 180 173
Power supply
1φ, 220V, 50Hz
Burner Model no.
KPG-50A KPG-70A
Power consumption
W
143 208
Gas pressure
mmH2O
LP gas: 280±50, LNG : 200
50100
Fuel consumption
LNG : 61,000kcal/h(70.9kW), LPG : 5.1kg/h(70.9kW)
LNG : 84,000kcal/h(97.6kW), LPG : 7kg/h(97.6kW)
Width
mm
547 547
Depth + Burner
mm
850 838
Prod uct size
Height
mm
1,148 1,410
Heating inlet
·
outlet
A
40 40 40 40
Drain
A
40 40 40 40
Discharge outlet
A
40 40 40 40
Hot water inlet·outlet
A
20
20 -
Pipi ng
size
Gas inlet
A
15
Flue size
φ
148
Exhaust gas
250 or less
The specifications presented in this manual is subject to change without notice for quality improvement.
Medium-sized gas boiler
58
3) Steel boiler
Model
Classifications
1035GPD 1035GPS 1035GPG 1535GPD 1535GPS 1535GPG
Heating Output
kcal/h
(kW)
100,000
(116.2)
100,000
(116.2)
-
150,000
(174.4)
150,000
(174.4)
-
Hot water Output
kcal/h
(kW)
100,000
(116.2)
-
100,000
(116.2)
130,000
(151.1)
-
150,000
(174.4)
Capacity of hot water supply (△
40℃)
/min
42 - 42 54 - 63
Purpose
Combi
Heating
only
Hot water
only
Combi
Heating
only
Hot water
only
LNG
%
91.2 91.2 91.2 91.5 91.5 91.5
Efficiency (Total)
LPG
%
91.2 91.2 91.2 91.5 91.5 91.5
Fuel
Citygas (13A), LP gas
Maximum allowable working pressure
kgf/cm
2
(MPa)
3.5 (0.343)
Heat transfer area
m2
3.32 4.77
Heating area
m2
662 662 - 992 992 -
Volume of pipe water
135 148 148 173 188 188
Weight
kg
267 248 248 390 370 370
Power supply
1φ, 220V, 50Hz
Burner Model no.
KPG-100A KPG-150A
Power consumption
W
224 232
Gas pressure
mmH2O
LP gas: 280±50, LNG : 200
50100
Fuel consumption
LNG : 124,000kcal/h(144.1kW)
LPG : 10.3kg/h
(144.1kW)
LNG : 178,000kcal/h(206.9kW)
LPG : 14.8kg/h(206.9kW)
Width
mm
687 796
Depth
Burner
mm
994 1,094
Product Size
Height
mm
1,403 1,411
Heating inlet
·
outlet
A
65 65 - 80 80 -
Drain
A
65 65 65 80 80 80
Discharge outlet
A
65 65 65 80 80 80
Hot water inlet·outlet
A
20
65 20 - 80
Piping size
Gas inlet
A
20 25
Flue size
φ
200
Exhaust gas
250 or less
The specifications presented in this manual is subject to change without notice for quality improvement.
Medium-sized gas boiler
59
4) Iron boiler
Model Classification
2035GPD 2035GPS 2035GPG
HeatingOutput
kcal/h (kW)
200,000
(232.5)
200,000
(232.5)
-
Hot waterOutput
kcal/h (kW)
130,000
(151.1)
-
200,000
(232.5)
Hot water supply capacity (△
40℃)
/min
63 - 83
Purpose
Combi Heating only Hot water only
LNG
%
92.0 92.0 92.0
Effici ency (Total)
LPG
%
92.0 92.0 92.0
City gas (13A), LP Gas
Maximum allowable working pressure
kgf/cm
2
(MPa)
3.5 (0.343)
Heat transfer area
m2
6.46
Heating area
m2
1323 1323 -
Volume of pipe water
237 255 255
Weight
kg
475 450 450
Power supply
1φ, 220V, 50Hz
Burner
Model no.
KPG-200A
Power consumption
W
366
Gas pressure
mmH2O
LP gas: 280±50, LNG : 200
50100
Fuel consumption
LNG : 24Nm3/h, 252,000kcal/h(293.0kW), LPG : 21kg/h
Width
mm
796
Depth + Burner
mm
1,165
Product size
Height
mm
1,716
Hot water inlet·outlet
A
80 80 -
Drain
A
80 80 80
Discharge outlet
A
80 80 80
Hot water inlet·outlet
A
20
80
Piping size
Gas inlet
A
32
Flue size
φ
200
Exhaust gas
250 or less
The specifications presented in this manual is subject to change without notice for quality improvement.
Medium-sized gas boiler
60
MEMO
Medium-sized gas boiler
61
MEMO
Medium-sized gas boiler
62
MEMO
Medium-sized gas boiler
63
MEMO
Medium-sized gas boiler
64
MEMO
Loading...