Nautel XR6, XR3-PREINST Preinstallation Manual

XR6/XR3 Transmitter
Pre-installation Manual
Document:XR6/XR3-PREINST
Issue: 3.0 2009-07-15
Status: Preliminary
blank
Nautel Limited
10089 Peggy’s Cove Road Hackett’s Cove, NS Canada B3Z 3J4 Phone: +1.902.823.3900 or Toll Free: +1.877.6NAUTEL (6628835) (Canada & USA only) Fax: +1.902.823.3183
Nautel Inc.
201 Target Industrial Circle Bangor, Maine USA 04401 Phone: +1.207.947.8200 Fax: +1.207.947.3693
Customer Service (24 hour support)
+1.877.628.8353 (Canada & USA only) +1.902.823.5100 (International)
Email: support@nautel.com Web: www.nautel.com
The comparisons and other information provided in this document have been prepared in good faith based on publicly available information. The reader is encouraged to consult the respective manufacturer's most recent published data for verification.
© Copyright 2009 NAUTEL. All rights reserved.
blank
XR6/XR3 Pre-installation Manual Table of contents
Contents
About this manual ix
About safety xiii
Safety precautions xv
Description 1-1
Capabilities 1-1
Options 1-2
Pre-installation tasks 2-1
Preparing for installation 2-1
Selecting a location for the transmitter 2-2
Installing an antenna feedline 2-3
Physical requirements 3-1
Clearances 3-1
Dimensions 3-2
Weights 3-5
Cooling requirements 4-1
Air flow in the transmitter 4-1
Cooling 4-2
Heating 4-3
Electrical requirements 5-1
Electrical power 5-1
Station reference ground 5-4
Page v
XR6/XR3 Pre-installation Manual
Control and monitoring 6-1
Controls 6-1
Alarm definitions 6-1
Remote control circuits and alarms 6-7
Remote performance monitoring 6-12
LAN interface (NxLink) 6-13
Other considerations 7-1
External RF drive source 7-1
External 10 MHz frequency reference 7-2
RF output requirements 8-1
Antenna feed cable 8-1
Antenna system 8-3
Parts and tools 9-1
Contacting Nautel 9-1
Parts supplied by Nautel 9-1
Parts not supplied by Nautel 9-2
Parts ordering 9-2
Module replacement program 9-2
Tools for installation 9-3
Accessories 10-1
Contacting Nautel 10-1
Ac line surge protection 10-2
Automatic antenna transfer control unit 10-2
RF contactor 10-3
Automatic switching system 10-4
Dynamic carrier control unit 10-4
Spares 10-4
Page vi Issue 3.0 2009-07-15
XR6/XR3 Pre-installation Manual
Pre-installation assistance 11-1
Pre-installation consulting 11-1
Installation and commissioning service 11-1
Online documentation 11-3
On-site support 11-3
Training 11-3
Standard warranty 11-4
Extended warranties 11-7
List of terms 12-1
Index IX-1
Issue 3.0 2009-07-15 Page vii
XR6/XR3 Pre-installation Manual
Page viii Issue 3.0 2009-07-15
XR6/XR3 Pre-installation Manual

About this manual

This manual provides information about preparing for the delivery and installation of an XR6/XR3 transmitter. This manual is intended for use by field technicians, site managers, and installation planners.
Using this manual
Read the task list provided in Section 2, “Pre-installation tasks” on page 2-1. The task list describes the preparations you must make prior to receiving and installing the XR6/XR3 transmitter.
Later sections of the manual provide reference information regarding physical, cooling, electrical, and antenna requirements.
Technical support
Nautel offers technical support to customers over the Internet and by telephone. Nautel’s customer support team will answer your questions and work with you to identify and resolve problems.
For technical support, call the Customer Support Team at 902-823-3900 or - in U.S.A. and Canada only - call toll free at 1-877-6NAUTEL (662-8835). Or find us on the Internet at http://
www.nautel.com.
For parts and tools information, see “Parts and tools” on page 9-1 of the XR6/XR3 Pre-Installation Manual.
For accessories or spares, see “Accessories” on page 10-1 of the XR6/XR3 Pre-Installation Manual.
For standard warranty information, see “Pre-installation assistance” on page 11-1 of the XR6/XR3 Pre-Installation Manual.
For extended warranty information, see “Pre-installation assistance” on page 11-1 of the XR6/XR3 Pre-Installation Manual.
XR6/XR3 transmitter manuals
The XR6/XR3 documentation suite includes the following documents:
Issue 3.0 2009-07-15 Page ix
XR6/XR3 Pre-installation Manual
XR6/XR3 Pre-installation Manual, XR6/XR3-PREINST. The Pre-installation Manual provides
instructions and reference information needed when planning and preparing for the installation of an XR6/XR3 transmitter.
Nautel Site Protection Manual. The Site Protection Manual provides detailed information
about protecting your site from lightning-related hazards.
XR6/XR3 Installation Manual, XR6/XR3-INST. The Installation Manual provides instructions
and reference information needed when installing an XR6/XR3 transmitter.
XR6/XR3 Operating and Maintenance Manual, XR6/XR3-OPS-MAINT. The Operating and
Maintenance Manual provides instructions for operating, maintaining and troubleshooting an XR6/XR3 transmitter. It also provides reference information needed when performing diagnostic procedures.
XR6/XR3 Troubleshooting Manual, XR6/XR3-TROUBLE. The Troubleshooting Manual
provides detailed technical information about the XR6/XR3 transmitter, including electrical schematics and mechanical drawings.
Nautel website / Online resources
The Nautel website provides useful resources to keep you up to date on your XR6/XR3.
Nautel User Group (NUG)
The website includes a special section that customers can log into in order to access the Nautel customer newsletter, product manuals, frequently asked questions (FAQ), information sheets, and information about field upgrades. Registration is available online and is required.
Documentation: online and printed
The website’s NUG section provides online access to all the documentation for your XR6/XR3. Documentation is provided in Acrobat (PDF) format. You can use the documentation online or print the sections that you need.
When using online documents:
Click on blue text (hyperlinks) to jump to a related section, or to get additional information (e.g., view a term’s definition).
To search a document to find keywords, use Find in Acrobat Reader’s Edit menu.
To quickly find a specific section, click the section in the PDF file’s
Bookmarks list.
Page x Issue 3.0 2009-07-15
XR6/XR3 Pre-installation Manual
When using printed documents:
To find keywords, go to the Index section at the end of the manual.
To find a specific term, go to the List of Terms section near the end of the manual.
Issue 3.0 2009-07-15 Page xi
XR6/XR3 Pre-installation Manual
Page xii Issue 3.0 2009-07-15
XR6/XR3 Pre-installation Manual

About safety

All Nautel transmitters are designed to meet the requirements of EN60215, Safety Requirements for Radio Transmitters.
The philosophy of EN60215 is that the removal of any cover or panel that can only be opened using a tool is a maintenance activity, and that any person performing a maintenance activity is expected to be trained for that activity. Under EN60215, it is assumed that trained personnel will be knowledgeable and will take precautions such as removing all power to the transmitter before accessing its components.
Electrical hazards
To remove power from the transmitter, switch off and lock out the ac power. There are three amber LEDs at the bottom rear of the cabinet that glow to remind anyone who has not turned off the power that the system is live and serious danger is present.
WARNING: It is not enough to remove RF power. The power line is still connected.
Mount the transmitter ac power disconnect switch/breaker close to the transmitter so that it can be reached quickly in an emergency. Clearly label the disconnect switch/breaker (e.g., EMERGENCY
SWITCH
After turning off the power, always perform a measurement to confirm that the power is off before touching anything within the transmitter. If the wrong breaker was opened, the equipment will be live.
Use only a non-contact voltage probe or a safety voltmeter (available from vendors such as Fluke, Ideal, and Teagam).
).
WARNING: Do not use an ordinary multimeter to check for voltage, since it may have been left inadvertently on the AMP (A) range, triggering a short and an arc blast that could result in severe burns and even death.
Use a proper lockout procedure to ensure that another worker cannot accidentally reapply power while you are performing maintenance on any part of the transmitter or site.
Issue 3.0 2009-07-15 Page xiii
XR6/XR3 Pre-installation Manual
Lightning hazards
Before opening the transmitter and touching internal parts, remove and solidly ground the antenna connection.
WARNING: It is not enough to ground the antenna terminal with the antenna still connected. Even a small impedance in the ground strap will result in lethal voltages during a lightning strike.
RF hazards
A serious RF hazard and very high voltages exist in the vicinity of the antenna and its networks during normal operations.
Toxic hazards
There are devices used in this equipment containing beryllium oxide ceramic, which is non-hazardous during normal device operation and under normal device failure conditions. These devices are specifically identified with “(BeO)” in the Description column of the Troubleshooting Manual’s parts list(s).
Do not cut, crush or grind devices because the resulting dust may be hazardous if inhaled. Unserviceable devices should be disposed of as harmful waste.
Other hazards
Ensure that appropriate fire alarms and fire extinguishers are available. Extinguishers must be suitable for use on electrical fires.
Many other site safety risks exist. It is beyond the scope of this manual to identify all the risks and procedures.
Page xiv Issue 3.0 2009-07-15
XR6/XR3 Pre-installation Manual

Safety precautions

This section provides very important information about protecting the safety of personnel and equipment:
Personal safety - see page xv
Site safety - see page xvi
Equipment safety - see page xviii
Personal safety
Training
The training of any personnel who will have physical access to the site or the transmitter is very important. Personnel must be familiar with the transmitter, so that they can avoid physical danger, and be aware of hazards to themselves and the equipment.
Nautel offers a number of training courses covering the basic fundamentals of RF systems and transmitters, and the operation and maintenance of the transmitter. For more information about available courses and schedules, go to the Nautel website at http://www.nautel.com/Training.aspx, or ask your Nautel sales representative.
Site orientation
When you give personnel access to the transmitter site (e.g., hiring new personnel, or giving access keys to personnel), perform a site orientation to ensure that they are familiar with the site, on-site procedures, and on-site hazards. Cover the following topics:
Securing the site (locking doors and fences) to prevent unauthorized access
How and when to call for technical support or emergency assistance
Areas of the site and pieces of equipment that are off limits
Issue 3.0 2009-07-15 Page xv
XR6/XR3 Pre-installation Manual
Voltage awareness
Ensure that all personnel that are able to access areas with high voltage circuits or high field strengths are aware of the hazards associated with high voltage. Cover the following topics:
High voltage or high field strength areas where caution is required
Physical risks of electric shock
Risks for personnel with pacemakers or other medical implants
Induced voltages in high field strength areas
On-site risks during thunderstorms and lightning strikes
Operation of safety interlocks (if installed)
First aid
Nautel does not offer first aid training, since the hazards associated with high voltage and RF energy are not specific to the transmitter. However, the customer should provide first aid training to all per­sonnel who have access to the transmitter site. First aid training should include CPR, care of burns, artificial respiration, and defibrillation if specific equipment is available on-site.
Site safety
Controlling access
Transmitters and antennas generate and carry dangerous voltages that can be harmful or fatal. It is very important that you control access to the site and its equipment. To secure your transmitter site, use:
Locking steel or security doors to prevent casual access
A perimeter fence to keep trespassers away from the antenna system and feedline
“No Trespassing” signs
An alarm system
Page xvi Issue 3.0 2009-07-15
XR6/XR3 Pre-installation Manual
Marking hazards
Place warning signs close to any hazardous areas or systems (e.g., the feedline or the antenna system). Make the signs large enough that they cannot be missed. Provide signage in all languages used in the region. These signs are intended not only for authorized personnel, but also for emergency responders or accidental trespassers.
Qualifying site personnel
Make sure that personnel who have access to the site are qualified to work around electronics and high voltage systems.
Ac power protection
You should take steps to protect equipment from surges (over-voltage spikes) on the ac power lines. Surges may occur during thunderstorms, or because of malfunctions in the electrical distribution grid. Surge suppressors and ac power conditioners can prevent serious damage to your on-site equipment, including the transmitter.
RF protection
Transmitters and their antenna systems create intense radio frequency fields at the transmitter site, particularly near the feedline, antenna and tower. At some sites, these fields may cause biological effects, including the heating of body tissues. Intense fields can also create dangerous high voltages on ungrounded, conductive surfaces and objects. At certain points where high voltage conductors come close to grounded conductors (e.g., at feedline junctions or on the tower), dangerous electrical arcing or flashovers can occur. It is very important that you take the following steps to prevent damage to equipment or personnel due to RF fields:
Use safety interlocks to de-energize transmitters if personnel open doors or panels accessing high field areas
Place warning signs in any locations where high fields can occur
Train personnel about the short-term and long-term hazards of RF radiation
Physically block access to the area around the antenna system, feedline and tower
Ground all exposed conductive surfaces or objects in high field areas
The RF connection to the transmitter output can be a serious safety hazard. Connect a 50 Ω test load during installation and commissioning. It is recommended that a switch be used to automatically connect the transmitter to the antenna system without human contact with the transmitting conductors.
Issue 3.0 2009-07-15 Page xvii
XR6/XR3 Pre-installation Manual
Safety interlocks
The transmitter contains an electrical interlock, which is an external circuit that turns off the RF output if any of its switches are opened.
Ac disconnect switch
Safe operation of the transmitter requires an ac disconnect switch. Lock the ac disconnect switch in the disconnected (open) position during the installation process.
Equipment safety
Electrostatic protection
The transmitter’s systems are very rugged and resistant to damage. However, it is possible for damage to occur because of high voltage electrostatic discharges during servicing. Train all service personnel to ground themselves to bleed off any static charge before opening the transmitter or touching any exposed components. Provide a grounding wand or known ground (e.g., a grounded metal table) that personnel can use to discharge themselves.
Surge protection
Surge protection is recommended for your entire site. However, even if you do not use a surge protector on the service entrance to the site, you should install a surge protector in the transmitter’s ac power feed to prevent over-voltage from entering the transmitter.
Lightning protection
The transmitter is designed to resist lightning strike damage. However, intense or repeated strikes could damage the transmitter. We recommend that you install lightning suppression on the antenna, tower and feedline to reduce the effect of lightning strikes on the transmitter itself (and to protect the rest of your site equipment and your personnel). For detailed information about lightning protection, see the Nautel Site Preparation Manual, available from your Nautel sales agent, or online from the Nautel website.
Physical protection
Consider physical hazards to equipment at your site, including the transmitter. Ensure that equipment is protected from weather (e.g., rain or flooding), even during extreme weather events. Place equipment so that it is not in the path of swinging doors or high-traffic areas. Do not allow wheeled items like office chairs or tables with wheels in the transmitter room, as these may damage equipment if accidentally pushed or knocked over. Do not place the transmitter under water pipes, drains, or sprinklers. Keep any equipment that generates heat, like the transmitter, away from flammable materials like ceiling panels, cubicle dividers, and curtains.
Page xviii Issue 3.0 2009-07-15
XR6/XR3 Pre-installation Manual
Earthquake protection
If the transmitter site is in a region that experiences any noticeable earthquake activity, take steps to prevent the transmitter from shifting or rocking during an earthquake. Even during minor earthquakes, rocking or movement of the transmitter is likely to damage the feedline connection, and could even cause a catastrophic failure of the ac power feed into the transmitter. During larger earthquakes, the weight of the transmitter chassis could be hazardous to nearby equipment or personnel.
Issue 3.0 2009-07-15 Page xix
XR6/XR3 Pre-installation Manual
Page xx Issue 3.0 2009-07-15
XR6/XR3 Pre-installation Manual Description

Section 1: Description

This section provides a basic description of the XR6/XR3 transmitter and includes the following topics:
Capabilities
Options - see page 1-2

Capabilities

Power

The XR6/XR3 is rated (with 140% positive peak modulation) for an RF output of 6 kW (XR6) or 3 kW (XR3) and capable (with 120% modulation) of RF outputs up to 7.5 kW (XR6) or 3.75 kW (XR3).
The operator can vary the power continuously or switch to preset power levels using the XR6/XR3 graphic user interface (GUI). Presets store the power level, active exciter, and power scheduler status on a time-of-day and date basis. The operator can configure exciters on a preset for a specific operating mode (e.g., exciter A for conventional AM, and exciter B for IBOC). The power output can also be scheduled to correspond with authorized daytime power levels.

Modulation

The XR6/XR3 is capable of double sideband (AM) modulation. With the addition of external signal generators, IBOC and DRM modulation can be provided to the exciter.

Duty Cycle

The XR6/XR3 will operate at nominal power with a 100% duty cycle – continuously – on an indefinite basis.

Antenna tolerance

The XR6/XR3 will operate at rated power even with a VSWR of 1.5:1. A higher VSWR results in a protective fallback of output power. The greater the VSWR, the greater the reduction in RF power. (To maintain the quality of digital broadcasts, a maximum VSWR of 1.4:1 is acceptable.)
The XR6/XR3 will not fail or completely shut down, regardless of antenna or feedline failure.
Issue 3.0 2009-07-15 Page 1-1
XR6/XR3 Pre-installation Manual Description

Remote control and monitoring

The XR6/XR3 remote control and monitoring options allow you to run a multiconductor signaling cable from the transmitter to a remote control board. This option lets you monitor all key parameters of transmitter operation, and control common functions, such as power output and exciter selection.

Redundancy

The XR6/XR3 features redundancy in all key systems:
RF power modules *
Exciters
Cooling fans
* The standard XR6/XR3 transmitter configuration contains one RF power module. A second RF power module is optional.

Ac power

The XR6/XR3 variable power transformer can be set to use a range of input voltages and power frequencies, as described in Section 2, “Installing the power transformer” on page 2-1of the XR6/ XR3 Installation Manual.

Options

DCC
The XR6/XR3 supports Dynamic Carrier Control (DCC) as an optional module. DCC reduces the power of the carrier when the sideband power drops below a threshold (that is, when there are periods of silence in the program content). This reduces overall power consumption.

IBOC

The XR6/XR3 supports IBOC digital radio as a modulation option. The external IBOC signal source provides a signal to the XR6/XR3 exciter.
DRM
The XR6/XR3 supports Digital Radio Mondiale (DRM) radio as a modulation option. The external DRM signal source provides a signal to the XR6/XR3 exciter.
Page 1-2 Issue 3.0 2009-07-15
XR6/XR3 Pre-installation Manual Description

NxLink

An optional NxLink module provides an Ethernet interface between the XR6/XR3 and a LAN (local area network). This interface allows remote control and monitoring of the XR6/XR3 from a computer .

Safety interlocks

Optional safety interlocks prevent unsafe access to the transmitter until the ac power is removed.
Issue 3.0 2009-07-15 Page 1-3
XR6/XR3 Pre-installation Manual Description
Page 1-4 Issue 3.0 2009-07-15
XR6/XR3 Pre-installation Manual Pre-installation tasks

Section 2: Pre-installation tasks

This section provides a list of tasks that you must perform prior to delivery and installation of the XR6/XR3 transmitter.
WARNING: FAILURE TO COMPLY WITH RECOMMENDATIONS MAY VOID YOUR MANUFACTURER’S WARRANTY. FOR MORE INFORMATION, REVIEW YOUR WARRANTY DOCUMENTS.

Preparing for installation

To prepare for installation of an XR6/XR3 transmitter, perform the following tasks:
1. Ensure that the correct transmitter configuration is ordered. Check the ac power requirements, preset frequency, IBOC option, and other options.
2. Select a location for the transmitter in the transmitter room. Determine whether additional heating, ventilating or cooling capacity is needed at the site. Identify any special requirements regarding air flow around the cabinet (for example, ducting hot air away from the cabinet, or bringing in external cooling air).
3. If this is an upgrade or replacement transmitter (that is, if the site is already set up for a transmitter), go to Step 7. (If you are upgrading a site, verify the feedline, the lightning protection systems, and the ac power service. Refer to the Nautel Site Protection Manual.)
4. Install ac power service into the planned location of the transmitter, and select a location for an ac power disconnect near the transmitter location. For detailed information, see
“Electrical power” on page 5-1.
Be aware of lightning protection issues when installing ac power. Lightning protection is essential to protect both personnel and equipment at your site. Refer to the Nautel Site
Protection Manual.
5. Install lightning protection on the antenna tower. Refer to the Nautel Site Protection Manual.
6. Place a work area with a clear table surface near the transmitter location. Provide electrostatic protection measures in the work area.
7. Order any accessories or optional equipment that you may need.
Issue 3.0 2009-07-15 Page 2-1
XR6/XR3 Pre-installation Manual Pre-installation tasks
8. Terminate the transmitter end of the RF feedline with the appropriate mating connector. Unless otherwise specified in contract documents, the transmitter will accept a 1-5/8 inch EIA flange connector.
9. If the transmitter will be used to broadcast IBOC, perform a full impedance sweep of the antenna system. See “Antenna system” on page 8-3.
10. Arrange manpower or lifting equipment to move and assemble the transmitter. You may want to use a forklift to move either the transmitter or its power transformer into place for installation.
11. Implement a safety interlock, if required.
12. If you are going to use an external RF drive, ensure that the drive meets required specifications.
13. If you are going to use an external frequency reference, ensure that the reference source meets required specifications.
14. Prepare to integrate the XR6/XR3 transmitter into your station control circuitry, if required.
15. Train your station technicians and operators on the use and maintenance of the XR6/XR3 transmitter.

Selecting a location for the transmitter

To ensure that the desired location for the XR6/XR3 transmitter is suitable, perform the following tasks:
1. Ensure that the floor area where the transmitter will be located is able to support the weight of the transmitter system.
The total weight of the assembled transmitter, once installed, is 213 kg (469 lbs).
2. Measure the space to ensure that the transmitter will fit. See Section 3, “Physical requirements” on page 3-1 for transmitter dimensions.
3. Ensure that transmitter room doors and the pathway of access from the receiving dock or building exterior to the installation location are large enough to accommodate the transmitter.
Page 2-2 Issue 3.0 2009-07-15
XR6/XR3 Pre-installation Manual Pre-installation tasks

Installing an antenna feedline

When installing an antenna feedline for the XR6/XR3 transmitter, perform the following tasks:
1. Ensure that the RF feedline that will connect the transmitter and the antenna system has a suitably rated coaxial cable.
2. Connect the shield of the antenna feedline coaxial cable directly to the station reference ground where it enters the building. For more information about the station reference ground, see “Station reference ground” on page 5-4.
3. Install lightning protection devices. For more information about lightning protection, refer to the Nautel Site Protection Manual.
4. Pass the center conductor and the shield of the feedline cable through a ferrite toroid that is positioned between the shield ground at the building entrance and the shield termination at the transmitter. Install the ferrite toroid prior to installing flanges on the feedline cable.
The ferrite toroid included in the ancillary kit, provided by Nautel with the transmitter,
can be used for coax cables with diameters up to 1 5/8 inches (1.625 in.). For larger diameters,contact Nautel support for recommendations (see page 11-3), or consult additional, outside suppliers.
Issue 3.0 2009-07-15 Page 2-3
XR6/XR3 Pre-installation Manual Pre-installation tasks
Page 2-4 Issue 3.0 2009-07-15
XR6/XR3 Pre-installation Manual Physical requirements

Section 3: Physical requirements

This section provides physical specifications for the XR6/XR3 transmitter and its components, and lists physical site requirements. This section includes the following topics:
Clearances
XR6/XR3 transmitter dimensions - see page 3-2
Weights - see page 3-5

Clearances

Required minimum clearances are 1.2 m (4.0 feet) at the front of the transmitter, and 1.8 m (6.0 feet) at the rear of the transmitter. (The clearance at the rear of the transmitter is required to allow installation of the power transformer. Less clearance may be acceptable if special arrangements are made to install the transformer.) No clearance is required on either side of the transmitter.
Check the clearance to ensure that you will be able to open all doors and access panels. The front control panel is hinged on the left (when looking at the front of the transmitter).
Also consider access to the rear of the transmitter during transformer installation and servicing, and access to the front of the transmitter during power module replacement. You must allow space to open the front panel and slide out any of the power modules. These modules slide straight in and out of the shelf unit in the front of the transmitter.
Internal fans pull cooling air through air filters in the upper rear panel. The cooling air exhausts as a low velocity stream through openings on top of the transmitter.
Issue 3.0 2009-07-15 Page 3-1
XR6/XR3 Pre-installation Manual Physical requirements

Dimensions

Figure 3.1: XR6/XR3 transmitter dimensions
184.0 cm (72.5 in)
)
n
i
5
9
.
0
c
m
(
2
3
.
1
i
n
)
0
.
4
8
.0
3
3
(
m
c
Page 3-2 Issue 3.0 2009-07-15
XR6/XR3 Pre-installation Manual Physical requirements
Figure 3.2: XR6/XR3 transmitter cabinet – top view
Minimum clearance to front of transmitter: 122 cm (48.0 in)
RF OUTPUT
33.0 cm (13.0 in)
Front
34.8 cm (13.7 in)
AUDIO & CONTROL WIRING
AC IN
7.1 cm (2.8 in)
Rear
6.6 cm (2.6 in)
Minimum clearance to rear of transmitter: 183 cm (72.0 in)
Issue 3.0 2009-07-15 Page 3-3
XR6/XR3 Pre-installation Manual Physical requirements
Figure 3.3: XR6/XR3 transmitter cabinet, seen from below (looking up)
Front
59.0 cm (23.1 in)
Transformer Anchor Points
AC IN
8.5 cm (3.35 in)
3.81 cm dia (1.5 in)
Rear
8.5 cm (3.35 in)
Page 3-4 Issue 3.0 2009-07-15
XR6/XR3 Pre-installation Manual Physical requirements

Weights

See Table 3.1 for the various weights of transmitter components, including crated and uncrated weights.
Table 3.1: XR6/XR3 Weight of components – Includes 1 RF Power Module
Crate contents Uncrated weight Crated weight
Main cabinet (no RF power modules or power transformer)
Main cabinet (with 1 RF power module, no power transformer)
XR6 Power transformer XR3 Power transformer Assembled transmitter, XR6
(total installed weight) Assembled transmitter, XR3
(total installed weight)
125 kg (275 lbs) N/A
145 kg (319 lbs) 237 kg (521 lbs)
68 kg (150 lbs) 110 kg (242 lbs)
47 kg (104 lbs) 89 kg (196 lbs)
213 kg (469 lbs) N/A
192 kg (423 lbs) N/A
Issue 3.0 2009-07-15 Page 3-5
XR6/XR3 Pre-installation Manual Physical requirements
Page 3-6 Issue 3.0 2009-07-15
XR6/XR3 Pre-installation Manual Cooling requirements

Section 4: Cooling requirements

This section provides information about heating and cooling requirements for the XR6/XR3 transmitter site. Topics in this section include:
Air flow in the transmitter
Cooling - see page 4-2
Heating - see page 4-3

Air flow in the transmitter

The XR6/XR3 uses redundant cooling fans and hot-air convection to ensure effective cooling. Cool air is drawn in through a filter in the lower portion of the back of the transmitter. Air circulates into
the base of the transmitter, and is then pushed up through the front rack of the transmitter by a set of fans. Warm air exits the transmitter through the grill or duct at the top of the transmitter.
Figure 4.1: Air flow in the XR6/XR3 transmitter cabinet with back panel filter installed
Exhaust air
Front of XR6/XR3
Fans
Back of XR6/XR3
Incoming air
Issue 3.0 2009-07-15 Page 4-1
XR6/XR3 Pre-installation Manual Cooling requirements

Cooling

Do not allow the transmitter room ambient air temperature to exceed 50°C (122°F) at sea level. Cooler temperatures are recommended in order to improve the reliability of the transmitter.
De-rate the ambient temperature 3ºC (5.4°F) per 500 m – or 2ºC (3.6°F) per 1,000 feet – above sea level.
Example: At 1600 m (1 mile) above sea level, maximum ambient temperature should not
exceed 40.4ºC (104.7°F).
Ensure that hot air from the transmitter is not drawn back into the transmitter’s cool air intake.

Cooling plant requirements

Table 4.1: Cooling plant requirements for the XR6
Transmitter
output (watts)
6,000 1,843 6.29 6,000 1,673 5.71 6,000 1,229 4.19
Table 4.2: Cooling plant requirements for the XR3
Transmitter
output (watts)
3,000 921 3.15 3,000 837 2.86 3,000 615 2.10
Waste heat
(watts)
Waste heat
(watts)
BTU/hour
(x1000 Btu)
BTU/hour
(x1000 Btu)
Modulation
Modulation
Air conditioning
required in a closed
system (tonnes)
100% 0.54
85% 0.47
0% 0.36
Air conditioning
required in a closed
system (tonnes)
100% 0.27
85% 0.24
0% 0.18
Page 4-2 Issue 3.0 2009-07-15
XR6/XR3 Pre-installation Manual Cooling requirements

Calculating BTU cooling requirements

To determine the number of British thermal units (Btu) being generated per hour as waste heat, multiply the average RF output power (in watts) by 0.19 (the heat factor at rated power) and then multiply the product by 3.413.

Closed loop or forced air cooling systems

Closed loop or forced air cooling systems can be used, so long as the air is well filtered to prevent dust and insects from entering the transmitter, and so long as a minimum of 200 cubic feet per minute (CFM) at 0.5 pounds per square inch (PSI) is supplied to the intake duct.

Heating

The transmitter room must contain a heating system that will ensure the ambient air temperature does not drop below 0°C (32°F).
Issue 3.0 2009-07-15 Page 4-3
XR6/XR3 Pre-installation Manual Cooling requirements
Page 4-4 Issue 3.0 2009-07-15
XR6/XR3 Pre-installation Manual Electrical requirements

Section 5: Electrical requirements

This section describes electrical power and electrical protection requirements associated with the XR6/XR3 transmitter. This section includes the following topics:
Electrical power
Station reference ground - see page 5-4
CAUTION: Technical pre-commissioning activities described in this section require technical decisions and the customization of electrical circuits. Do not attempt to perform these activities unless you are a certified electrician.
Refer to the Nautel Site Protection Manual for information about requirements associated with lightning protection.

Electrical power

The transmitter is preconfigured to operate from a 50/60 Hz, 3-phase (3-wire plus ground, Wye or closed delta)or 1-phase (2-wire plus ground) ac power source. You select the number of phases and specific voltage range when you order the transmitter.

Nominal voltage (minimum and maximum)

The primary winding of the main ac power transformer contains taps to accommodate voltages that differ from the ideal voltage of the power source. These taps provide increments and are selected during installation to provide the nominal voltage for the transmitter.
The high voltage transformer comes with the following standard taps:
Table 5.1: Nominal Voltages
Ac Power
Source
3-phase LV 198, 208, 218, 229, 239, 250
Transformer Standard Voltage Taps
HV 342, 361, 380, 399, 418, 437
1-phase - 200, 220, 240, 260
Issue 3.0 2009-07-15 Page 5-1
XR6/XR3 Pre-installation Manual Electrical requirements

Voltage stability

The ac power source nominal voltage must be stable to within plus or minus 10% under all loading conditions. The transmitter contains circuitry that maintains the RF output at the preset carrier level for voltage variations within the specified range, provided the correct transformer tap is chosen.
Table 5.2: Voltage Stability
Ac Power
Source
3-phase LV 188 263
1-phase - 180 286
Transformer Voltage Range
Minimum Maximum
HV 325 459

Power consumption

When operating at 6 kW (XR6) or 3 kW (XR3) with 100% modulation by a continuous sine wave, power consumption is approximately 10.8 kW (XR6) or 5.4 kW (XR3). When operating at 6 kW (XR6) or 3 kW (XR3) with no modulation, power consumption is 7.2 kW (XR6) or 3.6 kW (XR3).
Power consumption for a specific station will depend on the programming format and the level of audio processing. Nautel recommends the ac power source have a 25% over-capacity to ensure adequate regulation.

Ac power switch

Install an external ac power disconnect between the ac power source and the transmitter. (Nautel can provide a suitable ac power disconnect, if required.) For safety, place the ac disconnect close to the transmitter and label it
TRANSMITTER EMERGENCY ON/OFF SWITCH.

Ac transient power protection

Protect all conductors from the ac power source by connecting bi-directional surge protection devices between each conductor and the station reference ground. In addition, pass all the conductors, as a group, through a ferrite toroid. Install a ferrite toroid on the ac feed between the transmitter and the bi-directional surge protector.)
The ferrite toroid included in the ancillary kit, provided by Nautel with the transmitter, can be used for most ac supply cables. For larger diameters, contact Nautel support for recom­mendations (see page 11-3), or consult additional, outside suppliers.
Page 5-2 Issue 3.0 2009-07-15
XR6/XR3 Pre-installation Manual Electrical requirements
A surge protector panel containing suitably rated varistors is available from Nautel. Install the surge protector panel close to the station reference ground, and as close as possible to the ac service entrance.
The ac power source usually has the lowest impedance path to ground during a lightning strike and normally carries most of the lightning-induced current away from the transmitter site. When lightning hits the power source (for example, striking a transmission line near the transmitter site), a significant induced current may flow towards the transmitter. The goal of lightning protection is to route the current around the transmitter to the best available ground.
For detailed information about surge protectors and lightning protection, refer to the Nautel Site
Protection Manual.
Recommended configuration for three-phase ac power source. Use a 4-wire Wye (star) configuration, with the three phases balanced to ground.
CAUTION: For three-phase applications do NOT use open delta ac power sources that use two identical transformers. These systems are susceptible to third harmonic distortion and line transients, and may cause peak voltages to exceed the line voltage. This can cause increased power supply noise or even component failure (for example, rectifier failure).

Wiring

Table 5.3 on page 5-4 shows the wiring recommendations for each ac voltage, and identifies the wire
gauges that are specified for worst case conditions. Smaller gauges may be used when actual conditions related to transmitter power and wiring allow it. A certified electrician should be consulted to ensure that all wiring meets local electrical code requirements.
CAUTION:
Table 5.3 on page 5-4 is based on recommendations by the Canadian
Electrical Code. Local codes may vary.
Issue 3.0 2009-07-15 Page 5-3
XR6/XR3 Pre-installation Manual Electrical requirements
Table 5.3: Ac power wiring requirements
Power @ 100% modulation:
Cable
Temperature
Rating
Wire Size: AWG
o
C75oC90oC
60
6 6 6 208 V ac, 3-ph 32 (XR6), 16 (XR3) 6 8 8 240 V ac, 3-ph 27 (XR6), 13.5 (XR3)
10 10 10 380 V ac, 3-ph 17 (XR6), 8.5 A (XR3)
4 4 4 220 V ac, 1-ph 59 (XR6), 29.5 (XR3)
Voltage Amps/Phase

Station reference ground

Install a station reference ground that provides a continuous, low impedance path to the earth.
If a surge protector is not being used, connect the transmitter cabinet's designated safety ground point, the shield of the coaxial feedline, and the ground connection of the power source directly to the station reference ground using a copper strap that is at least 10 cm (4 in.) wide. Ensure that the site’s ac service entrance ground is directly connected to the station reference ground outside the transmitter building.
If a surge protector is being used, connect the transmitter cabinet's designated safety ground point, the shield of the coaxial feedline, and the ground connection of the power source directly to the surge protector, using a 10 cm (4 in.) copper strap. Connect the surge protector to the station reference ground using a copper strap that is at least 10 cm (4 inches) wide.
Ac power can enter the transmitter cabinet through the right rear side of the top panel (see Figure 3.2
on page 3-3)or the rear side of the bottom panel (see Figure 3.3 on page 3-4).
Ensure that the transmitter site’s grounding rods are adequate. For more information about electrical grounding protection, see the Nautel Site Protection Manual.
Page 5-4 Issue 3.0 2009-07-15
XR6/XR3 Pre-installation Manual Control and monitoring

Section 6: Control and monitoring

This section describes control and monitoring of the XR6/XR3 transmitter. This section includes the following topics:
Controls
Alarm definitions
Remote control circuits and alarms - see page 6-7
Remote performance monitoring - see page 6-12
LAN interface (NxLink) - see page 6-13

Controls

The XR6/XR3’s graphic user interface (GUI) lets you control a number of transmitter functions and set parameters and schedules. (For detailed information about the GUI, refer to the XR6/XR3 Operating and Maintenance Manual.) In addition, you can control the on/off status, the active (A/B) exciter, the preset RF power level, the power level adjustment, and system alarm reset remotely by means of a conventional remote control interface (see “Remote control circuits and alarms” on
page 6-7 or a LAN, using the optional NxLink module (see “LAN interface (NxLink)” on page 6-13).

Alarm definitions

This section describes the alarms that may occur, and what they indicate.
DC voltage supply faults
Fan P/S fault
The 48 V power supply used for the fans is monitored. A fault will be reported if the voltage varies by more than ± 10%.
RF drive P/S fault
The 62 V power supply used for the RF drive is monitored. A fault will be reported if the voltage varies by more than ± 10%.
Issue 3.0 2009-07-15 Page 6-1
XR6/XR3 Pre-installation Manual Control and monitoring
LVPS fault
The +24 V, +15 V, -15 V and +5 V power supplies are monitored. A fault will be reported if the voltage varies by more than ± 10%.
One or more of these faults will result in only one LVPS Fault message on the Status screen, though each one would be logged separately in the Event Log.
High B+ voltage
A fault is reported when the B+ voltage goes above 380 V. No other action will be performed automatically.
Low B+ voltage
For three-phase XR6 transmitters, there are three B+ voltage levels that will be automatically selected to provide optimum performance: 315 V, 190 V and 115 V. For three-phase XR3 transmitters, there are two B+ voltage levels: 220 V and 115 V. For single-phase XR6 transmitters, there are four B+ voltage levels: 315 V, 196 V, 115 V and 69 V. For single-phase XR3 transmitters, there are four B+voltage levels: 220 V, 196 V, 115 V and 69 V.
This alarm is triggered when the B+ voltage falls below the factory-set alarm threshold. The alarm threshold is factory calibrated to be approximately 250 V, 150 V or 91 V - for three-phase XR6 transmitters - to correspond to the B+ voltage level currently in use. For three-phase XR3 transmitters, the alarm threshold voltage is factory calibrated to be approximately 174 V or 91 V. For single-phase XR6 transmitters, the alarm threshold voltage is factory calibrated to be approximately 250 V, 155 V, 91 V or 55 V. For single-phase XR3 transmitters, the alarm threshold voltage is factory calibrated to be approximately 175 V, 155 V, 91 V or 55 V.
Besides being noted on the transmitter’s GUI Status screen, and by the alarms, this alarm also causes the following:
a shutback
the softstart relays to open
the fans to turn off
Recovery from this alarm is automatic when the B+ voltage rises above the factory-set alarm threshold, which is factory-calibrated to 265 V, 160 V and 97 V - for three-phase XR6 transmitters ­depending on which B+ voltage is selected (see “Low B+ voltage” on page 6-2). For three-phase XR3 transmitters, the factory-calibrated threshold is 185 V or 97 V. For single-phase XR6 transmitters, the factory calibrated threshold is 265 V, 165 V, 97 V or 59 V. For single-phase XR3 transmitters, the factory calibrated threshold is 185 V, 165 V, 97 V or 59 V. The recovery process is the same as the power on process.
Page 6-2 Issue 3.0 2009-07-15
XR6/XR3 Pre-installation Manual Control and monitoring
Output network faults
High DC current
This alarm is triggered when the dc current goes above approximately 41 A (XR6) or 21 A (XR3).
High RF current
This alarm is triggered when the RF current exceeds the factory-set alarm threshold.
High VSWR shutback
This alarm is triggered when the reflected power exceeds the factory-set alarm threshold ­approximately 480 W (XR3) or 960 W (XR6).
Total power limit
This fault is triggered when the product of the B+ (dc) voltage and the dc current is greater than approximately 15 kVA (XR6) or 7.5 kVA (XR3).
This fault causes an immediate cutback, but not a shutback.
Exciter faults
Mod driver fault A
This fault is reported to the microcontroller only if exciter A is selected. If the exciter transfer function is set to auto, then the microcontroller will attempt a changeover to exciter B. If it cannot, or if the exciter transfer function is set to manual, then this fault will cause a shutback.
Mod driver fault B
This fault is reported to the microcontroller only if exciter B is selected. If the exciter transfer function is set to auto, then the microcontroller will attempt a changeover to exciter A. If it cannot, or if the exciter transfer function is set to manual, then this fault will cause a shutback.
Auto changeover
This event is caused by a fault in the active exciter when the exciter transfer function is enabled (set to auto). These faults cause exciter changeovers: Mod Driver Fail A/B, RF Driver Fail, or PDM Drive Fail.
This fault causes the it is manually cleared. No further auto changeovers are possible until the alarm is cleared.
•The Auto changeover alarm can be cleared remotely by re-selecting the active exciter, or locally by using the transmitter’s GUI Preset screen.
Changeover LED on the transmitter’s front panel to light. It will remain lit until
Issue 3.0 2009-07-15 Page 6-3
XR6/XR3 Pre-installation Manual Control and monitoring
RF driver fault
This fault indicates a problem with the RF drive on the current exciter. If the exciter transfer function is set to auto, then the microcontroller will attempt a changeover to the other exciter. If it cannot, or if the exciter transfer function is set to manual, then this fault will cause a shutback.
PDM drive fault
This fault indicates that the PDM drive has stopped functioning. If the exciter transfer function is set to auto, then the microcontroller will attempt a changeover to the other exciter. If it cannot, or if the exciter transfer function is set to manual, then this fault will cause a shutback.
Cutbacks
Cutback level (1-8)
If three shutbacks occur within five seconds, the transmitter will enter a power reduction mode called a cutback.
There are eight levels of cutbacks, the last being a reduction to almost no forward power.
At any given cutback level, there is a predefined time limit that must expire before the cutback level returns to the previous level (e.g., level three back to level two). If there are no further cutbacks, this process continues until Level 0 (normal) is reached.
The cutback recovery process can be overridden by adjusting the power (up or down), or by initiating a reset - by pressing Reset on the transmitter’s GUI Status screen or by remote application.
Remote interface faults
Ext. interlock open
The external interlock input is wired to the remote interface PWB by the end user, and triggered by the conditions that they set (e.g., opening the door to the transmitter room). A triggered interlock may indicate a safety issue.
Ext. PDM inhibit
An EXTERNAL PDM INHIBIT alarm indicates that an external PDM inhibit command is present. The external PDM Inhibit is wired to the remote interface PWB.
Int. serial fault
This alarm indicates that there is no communication with the remote interface PWB.
The control/display PWB requests updates from the remote interface PWB every 200 ms. This alarm is triggered when a control/monitor PWB’s request for information is not acknowledged by the remote interface PWB within two seconds.
Page 6-4 Issue 3.0 2009-07-15
XR6/XR3 Pre-installation Manual Control and monitoring
Mod. protection
This fault is reported from the remote interface PWB. The fault indicates that excessive low frequency modulation has triggered the transmitter’s protection circuit.
Softstart faults
Softstart active
The softstart relays are initially open for 1.6 seconds when the transmitter is first powered on. The software should close the relays after 1.6 seconds and clear this alarm.
While active, this alarm causes a shutback and inhibits the RF drive and fan power supplies.
Softstart overtemp
The software keeps track of the calculated temperature of the softstart resistors and triggers this fault if that value is greater than 150°C (302°F).While this fault is on, RF power will not be available.
The temperature is assumed to rise 20°C (68°F) for each cold start, and 10°C (50°F) for each warm start. The calculated temperature falls exponentially between starts.
The transmitter’s GUI Status screen will show the current, calculated temperature, if it is above 150°C (302°F).
CAUTION: Performing a warm or cold start while this fault is active is strongly discouraged.
RF Power module faults
PM Fault A or B*
A fault is being reported by power module A or B.
Note: A second RF power module is optional with an XR6 or XR3 transmitter.
*
Other faults
Low backup battery
This fault indicates that the backup battery voltage has fallen below an acceptable level. The fault may be caused by weak batteries, or a fault in the detection or alarm circuitry on the control/monitor PWB.
Issue 3.0 2009-07-15 Page 6-5
XR6/XR3 Pre-installation Manual Control and monitoring
The backup battery should be replaced while ac power is ON. If the ac power faults, without adequate
backup battery power, then the log files will be lost.
CAUTION: Do not wait for an extended period to replace the batteries. The control/monitor PWB’s microcontroller may not retain its settings if ac power is turned off when the backup battery voltage is too low.
Page 6-6 Issue 3.0 2009-07-15
XR6/XR3 Pre-installation Manual Control and monitoring

Remote control circuits and alarms

You can control the active (A/B) exciter, the on/off status of the RF power stage, the preset RF power level, the power level adjustment, and system alarm reset remotely. The remote interface PWB
contains a selection circuit that lets you select internal (single ended input) or external (differential input) input for all controlled functions.
The external control circuits interface with the transmitter through opto couplers on the remote interface PWB. The opto couplers buffer and isolate the external circuits and prevent any unwanted transients from affecting transmitter operation while remote control is selected at the transmitter.
The switching circuits for the remotely controlled functions must be the equivalent of a normally open (momentary) switch. The switches must be configured to operate as a single-ended input using the transmitter's 24 V dc as the source, or as a differential input using an external dc power supply (24
- 30 V). Each control function has negative inputs on the remote interface PWB. The positive external
Option 1 - Single Ended Input (Internal V dc). When you use the transmitter's 24 V as the
current source for a control function's opto coupler, configure the circuit on the remote interface PWB for a single ended input. The SINGLE/DIFF 3-pin header (E19) must have its 2-socket shunt post connected between pins 2 and 3 to configure the circuit.
+24 V IN input (TB1-3) is used by all control functions.
Figure 6.1: Single-ended Input Selected
+24 V IN (TB1-3)
S1830900 V1
18
+24V
3
E19
1 2
SINGLE
REMOTE SELECTION CIRCUITRY
CONFIGURED FOR INTERNAL
REMOTE
INTERFACE
PWB
DC VOLTS
A negative logic (active state is a current-sink-to-ground) command must be applied to the control's negative (-) input. To avoid a ground loop, obtain the ground from TB1-18.
Issue 3.0 2009-07-15 Page 6-7
XR6/XR3 Pre-installation Manual Control and monitoring
Option 2 - Differential Input (External V dc). When you use an external dc voltage (24 V to
30 V) as the current source for a control function's opto coupler, configure the control function's external switching circuit and the remote interface PWB’s selection circuit for a differential input. The
SINGLE/DIFF 3-pin header (E19) must have its 2-socket shunt post connected between pins 1 and 2
to configure the circuit.
Figure 6.2: Differential Input Selected
EXTERNAL DC PWR SUPPLY (+24V TO +30V)
S1830901 V2
+24 V IN (TB1-3)
18
+24V
3
E19
1 2
DIFF
REMOTE SELECTION CIRCUITRY
CONFIGURED FOR EXTERNAL
REMOTE
INTERFACE
PWB
DC VOLTS
The normally open/momentarily closed switch should be located between the dc voltage's negative output and the remote control circuit’s negative (-) input.

Inputs

This section describes the remote inputs to the system. These inputs are only accepted by the system if the remote/local status is set to remote, unless otherwise noted. That setting can only be made by a local user.
Inputs are toggled between states by an active pulse unless otherwise noted. To ensure proper operation, the duration of the active pulse should be a minimum of 250 ms.
Note: The external PDM inhibit input is intended to be used in conjunction with
antenna switching circuitry, to ensure minimal RF output current is flowing during the opening/closing of contacts in the transmitter's RF feed cable. An active
inhibit
condition must be applied, to inhibit the RF output, prior to contact
PDM
opening. The active condition must be maintained until contact closure has occurred, and an appropriate impedance has been connected to the transmitter's RF output. The RF output will instantly be restored to its original level when the active condition is removed.
Page 6-8 Issue 3.0 2009-07-15
XR6/XR3 Pre-installation Manual Control and monitoring
TB2-6 (-): PDM INHB terminal. Continuous active signal inhibits the PDM by causing a shut­back. This also works when the remote/local status is set to local.
TB1-1 and TB1-2: EXT INTLK terminals. A short circuit between the pins for normal operat­ing status, an open between these pins causes a shutback. This also works when the remote/ local status is set to local.
TB1-4 (-): RF OFF terminal. Same as pressing the RF Off button on the front panel. Provide an active pulse to activate.
TB1-6 (-): RF ON terminal. Same as pressing the RF On button on the front panel. Tells the system to provide RF power if possible. Provide an active pulse to activate.
TB1-8 (-):
J3-23 (-): IBOC Input Select A input. Sets IBOC/Analog for Exciter A. Continuous active sig­nal selects IBOC input, otherwise analog input is selected.
J3-25 (-): IBOC Input Select B input. Sets IBOC/Analog for Exciter B. Continuous active sig­nal selects IBOC input, otherwise analog input is selected.
J2-10 (-): Preset Scheduler (Auto/Man) input. Enables or disables the Automatic Preset (for­merly power level) changes. Provide an active pulse to toggle between Auto or Manual modes.
The following inputs will only take effect when the Preset Scheduler Mode is set to Manual.
J2-12 (-): Preset 1 input. Selects RF power preset 1 of 6. Provide an active pulse to activate.
J2-14 (-): Preset 2 input. Selects RF power preset 2 of 6. Provide an active pulse to activate.
J2-16 (-): Preset 3 input. Selects RF power preset 3 of 6. Provide an active pulse to activate.
J2-18 (-): Preset 4 input. Selects RF power preset 4 of 6. Provide an active pulse to activate.
RESET terminal. Causes a system reset. Provide an active pulse to activate.
J2-20 (-): Preset 5 input. Selects RF power preset 5 of 6. Provide an active pulse to activate.
J2-22 (-): Preset 6 input. Selects RF power preset 5 of 6. Provide an active pulse to activate.
Note: A minimum one second interval between commands is required for the
following two exciter selection commands.
Issue 3.0 2009-07-15 Page 6-9
XR6/XR3 Pre-installation Manual Control and monitoring
TB1-14 (-): EXCITER A terminal. Causes a changeover to select exciter A as the main exciter. Setting is saved in current preset. Provide an active pulse to select this exciter.
TB1-16 (-): EXCITER B terminal. Causes a changeover to select exciter B as the main exciter. Setting is saved in current preset. Provide an active pulse to select this exciter.
TB1-10 (-): POWER INCREASE terminal. Increases the power level of the current preset. Send an active pulse to increase the power slightly, or send a signal of greater duration to continue increasing the power.
TB1-12 (-): POWER DECREASE terminal. Decreases the power level of the current preset. Send an active pulse to decrease the power slightly, or send a signal of greater duration to continue decreasing the power.

Remote status and alarm indications

Outputs that indicate the status of operator controlled circuits are available on connectors J2 and J3 on the remote interface PWB. A switching device for each alarm output provides current-sink-to­ground when a logic true condition exists.
The switching circuit provides an open collector for a logic false condition and has no influence on the external monitoring circuit.
The following outputs are available:
Note: All outputs are active low.
•J3-18: Exciter Changeover. See “Auto changeover” on page 6-3.
•J2-24: Preset Scheduler On Status.
•J3-21: Auto Exciter Status. Indicates if the current preset allows auto exciter changeover in the event of failures. (Set from the GUI only.)
•J3-20: Memory Battery Alarm. See “Low backup battery” on page 6-5.
•J3-19: RF Overcurrent Alarm. See “High RF current” on page 6-3.
•J2-23: Exciter B Status. Indicates which exciter is presently active.
•J3-15: LV P S Fail. See “LVPS fault” on page 6-2.
•J3-14: Exciter Fail.
Page 6-10 Issue 3.0 2009-07-15
XR6/XR3 Pre-installation Manual Control and monitoring
•J3-13: Pwr Mod Fail. One or more power modules has a fault.
•J3-12: Low B+. See “Low B+ voltage” on page 6-2.
•J3-11: High VSWR. See “High VSWR shutback” on page 6-3.
•J3-17: Cutback. See “Cutback level (1-8)” on page 6-4.
•J3-16: Shutback. Indicates that a shutback is currently active.
•J3-3: RF On Status. Indicates that the RF On LED is active, showing the operator’s request for RF power.
J3-(5,6,7,8,9,10): Preset (1-6) Status. Indicates which preset is currently active.
•J3-4: Remote Status. Indicates whether or not the system is in Remote or Local control mode. Changes can only be made remotely if the transmitter is set to Remote mode. The local user’s control of transmitter operation is limited, unless the transmitter is set to Local mode.
Issue 3.0 2009-07-15 Page 6-11
XR6/XR3 Pre-installation Manual Control and monitoring

Remote performance monitoring

The transmitter provides outputs that let you monitor RF performance. They include dc voltages that represent the forward power level, the reflected power level, the B+ voltage and the dc current. In addition, a true RF sample of the RF output voltage waveform is available for external monitoring. These outputs are provided on the remote interface PWB.

Analog samples

Sample voltages, in the range of 0 to 4 V are provided for the following system parameters:
•J2-1: Fwd Power
•J2-3: Refld Power
•J2-5: B+ Voltage
•J2-7: Dc Current
•J8: RF Monitor
Forward power level. A buffered dc voltage that reports the forward power level on J2-1. This
voltage is a pure square law function and will be 3.9 ± 0.5 V when the forward power is 6.5 kW (XR6) or 2.8 ± 0.5 V when the forward power is 3.3 kW (XR3). The monitoring circuit’s impedance must be greater than 1,000 ohms.
Reflected power level. A buffered dc voltage that reports the reflected power level on J2-3. This
voltage is a pure square law function and will be 3.9 ± 0.5 V when the reflected power is 960 W (XR6) or 2.8 ± 0.5 V when the reflected power is 480 W (XR3). The monitoring circuit’s impedance must be greater than 1,000 ohms.
B+ volts. A buffered dc voltage on J2-5 that is directly proportional to the dc voltage from the main
dc power supply. This voltage will be 3.0 V when the dc voltage being applied to the RF stage is 312 V. The monitoring circuit impedance must be greater than 1,000 ohms.
Dc Current. A buffered dc voltage on J2-7 that reports the dc current level of the main B+ power
supply. The output is 3.0 ± 0.5 V with a dc current of 40 A.
Page 6-12 Issue 3.0 2009-07-15
XR6/XR3 Pre-installation Manual Control and monitoring
RF monitor sample. A true sample of the RF output voltage waveform is available through the J8
BNC connector (RF MONITOR) on the remote interface PWB. The RF monitor output is intended to be applied to a station modulation monitor with a 50 Ω input impedance. It may also be monitored by an oscilloscope during maintenance procedures. The RF monitor output can be set to provide
1.0 V rms or 5.0 V rms for each preset power level, provided they are preset to a level that is between 600 W and 6 kW (XR6) or between 300 W and 3 kW (XR3).
Note: Some older modulation monitors may not accept a 1 V input.
Note: The output level range is determined by the setting of the BYPASS/GAIN
switch. When the switch is set BYPASS, the RF monitor sample voltage is a nominal 1 V rms. When the switch is set to GAIN, the RF monitor sample voltage increases to a nominal 5 V rms. The rms output level is adjusted from the GUI. Setting the level higher than the limit determined by the BYPASS/GAIN switch [1 V rms or 5 V rms (carrier)] will cause distortion in the waveform, and may prevent accurate measurement of the modulation depth.

LAN interface (NxLink)

A serial port is available on 9-pin D-sub connector J12 of the XR6/XR3’s remote interface PWB. This port allows you to remotely control and interrogate the XR6/XR3’s operational status. If the NxLink Ethernet interface module option is installed and you wish to use it as the remote interface, connector J12 is linked to Port 1 of the NxLink module. Refer to the NxLink Technical Instructions Manual for further details on the NxLink module.
Issue 3.0 2009-07-15 Page 6-13
XR6/XR3 Pre-installation Manual Control and monitoring
Page 6-14 Issue 3.0 2009-07-15
XR6/XR3 Pre-installation Manual Other considerations

Section 7: Other considerations

This section describes other considerations regarding the XR6/XR3 transmitter.
External RF drive source
External 10 MHz frequency reference - see page 7-2

External RF drive source

You can apply an externally generated RF drive (carrier frequency only) to the remote interface board’s digital EXT RF IN BNC connector (J6). This replaces the internal carrier frequency oscillator for one or both exciters (A/B).
Note: There is only one external RF drive input. If you use it for both exciters,
duplicate the RF drive source (main/standby), and incorporate an automatic changeover circuit to select the standby source if the main source fails.
The external RF drive must:
be the carrier frequency (ƒc), within ± 5 Hz or 5 parts per million (ppm), whichever is greater, when it is not being modulated.
have a peak-to-peak amplitude of between 5.0 V and 12 V (sine wave or square wave).
be spectrally pure when it is not being modulated.
Note: Any signal connected to the EXT RF IN input may affect the transmitter’s RF
output. To comply with regulatory limits on emissions, ensure that the RF drive source is acceptable.
Issue 3.0 2009-07-15 Page 7-1
XR6/XR3 Pre-installation Manual Other considerations

Installing an external RF drive source

1. If the RF drive for one or both exciters is to be applied from an external source, connect its wiring as follows:
– Route RF drive coaxial cable through a cable entry hole in the cabinet and through the
ferrite toroid, to the vicinity of the remote interface PWB.
– Cut the RF drive coaxial cable to length, terminate it with a coaxial BNC connector and
connect it to the remote interface PWB’s EXT RF connector (J6).
2. Configure either (or both) exciter RF synthesizer(s) to operate on Ext RF drive by setting the E4 jumper(s) to 1-2.

External 10 MHz frequency reference

You can apply an externally generated 10 MHz signal (such as a GPS clock signal) for use as the reference frequency for the RF drive (carrier frequency) to the 10 MHz REFERENCE INPUT BNC connector J2 on each RF synthesizer PWB.
1. The external 10 MHz frequency reference (one for each RF synthesizer PWB) must:
– remain stable at 10 MHz within ± 20 Hz – have a peak-to-peak amplitude of between 2.2 V and 8.0 V (sine wave or square wave) – be spectrally pure, since spurs may pass through to the transmitter output.
2. Configure each RF synthesizer PWB by setting E2 to 1-2 and E1 to 1-2.
Page 7-2 Issue 3.0 2009-07-15
XR6/XR3 Pre-installation Manual RF output requirements

Section 8: RF output requirements

This section describes requirements associated with the antenna and RF cabling to be used with the XR6/XR3 transmitter.
Antenna considerations include the following:
Antenna feed cable
Antenna system - see page 8-3
For detailed information about protecting the transmitter system from antenna lightning strikes, see the Nautel Site Protection Manual.

Antenna feed cable

Maximum voltage

The maximum voltage at the transmitter’s connection to a 50 Ω load is 2,617 V peak, when operating at 6 kW (1,851 V peak at 3 kW), with 125% modulation.

High voltage feed throughs

Be very careful whenever a high voltage RF conductor passes through a wall or bulkhead. Gas insulation flashovers can occur in poor installations. Ensure that this part of your installation is installed by professionals experienced with high-power radio frequency circuits.
Insulator flashover. Surface flashovers along an insulator occur when there is an electrical
breakdown in the gas (normally air) at its surface. The mechanism that triggers a flashover depends on the insulation surface conditions. Gas breakdown flashover occurs when one or more of the following conditions are met:
The voltage field at the insulator surface or at an adjacent electrode reaches the critical break­down level for the gas.
The electrode or insulator interface is poor or dirty, resulting in a three material junction. This creates excessive high voltage stress on the air insulator, causing a gas breakdown flash­over.
Moisture damage on the insulator surface creates regions of high voltage that can cause a gas breakdown flashover.
Issue 3.0 2009-07-15 Page 8-1
XR6/XR3 Pre-installation Manual RF output requirements
Three-material junctions: A frequent cause of breakdowns at an insulator surface is the junction
of three materials: a metal conductor, a solid insulator, and a gas insulator. The insulators form a capacitive RF divider between the metal conductor and the grounded periphery. Since the dielectric constant of the solid is higher than the gas (air), the high voltage stress is concentrated on the air.
It is very important to minimize the junction's stress gradient and to avoid triple junctions wherever possible.
WARNING: FAILURE TO PROVIDE CORRECT STRESS CONTROL AT HIGH RF VOLTAGE CONDUCTOR/INSULATOR JUNCTIONS CAN CAUSE INSULATOR BREAKDOWNS OR EVEN FIRES.
Bowl type bushings. Use bowl type bushing insulators to increase the surface tracking distance
from the central conductor to the grounded periphery or wall.
Insulator Breakdown/Damage. An insulator can be damaged during gas breakdown flashovers.
When current flows across the surface of an insulator, especially when it is coated with a conductive contaminant that is slightly damp, carbon tracks can form. Once this occurs, the track provides a conductive path and reduces the effectiveness of the insulator.
Pitting and erosion of the insulator may also occur. To reduce the possibility of tracking damage, clean all insulator surfaces periodically, and use stress control techniques at the conductor/insulator junction.
Other causes. Other causes of breakdowns may include improperly adjusted spark balls or the
disruption of air gaps by rain, snow, insects, birds, grass, or an accumulation of pollution (soot) on insulator surfaces.

Small radius conductors

Be careful when using small radius conductors to carry high RF voltages and currents. If the radius is too small it may cause a local corona, which can lead to a breakdown.

Feedline testing

Test the RF transmission system from the transmitter flange to the antenna before putting the transmitter into service. This is very important, especially if you are re-using an existing site with a previously installed feedline. Ensure that the entire system can tolerate the expected peak voltages of normal operation, especially those occurring during modulation peaks, without breaking down.
Page 8-2 Issue 3.0 2009-07-15
XR6/XR3 Pre-installation Manual RF output requirements

Antenna system

Ensure that the antenna system meets or exceeds the standards specified in EIA Standard TR-101-A, paragraph 8(b), with a normal impedance of 50 ohms at the carrier frequency. The transmitter will operate with a maximum VSWR of 1.5:1, or with sideband VSWRs of up to 2:1 when the carrier frequency impedance is 50 ohms. However, overall system performance degrades as the VSWR increases.
Advances in digital modulation schemes like IBOC and DRM systems require better performance from antenna systems. To ensure the proper operation during digital broadcasting, ensure that the VSWR does not exceed 1.4:1 at the carrier frequency ±15 kHz.
In order to achieve the proper sideband symmetry (Hermitian symmetry) needed for IBOC operation, you may need to adjust the tuning of the antenna system to balance the impedances at the sidebands. You must perform a full impedance sweep of the antenna system before broadcasting IBOC. This requires information about phase versus frequency for Hermitian symmetry at the power amplifier. The information will be provided with the transmitter at time of shipment. For information about your transmitter’s RF phase, contact Nautel Customer Support.
Issue 3.0 2009-07-15 Page 8-3
XR6/XR3 Pre-installation Manual RF output requirements
Page 8-4 Issue 3.0 2009-07-15
XR6/XR3 Pre-installation Manual Parts and tools

Section 9: Parts and tools

This section describes parts associated with the XR6/XR3 transmitter, and tools needed during installation and routine operation. Topics include:
Parts supplied by Nautel
Parts not supplied by Nautel - see page 9-2
Parts ordering - see page 9-2
Module replacement program - see page 9-2
Tools for installation - see page 9-3

Contacting Nautel

You can reach Nautel to order parts or for technical assistance at:
Nautel Limited
10089 Peggy’s Cove Road Hackett’s Cove, NS Canada B3Z 3J4 Phone: +1.902.823.3900 877 6NAUTEL Fax: +1.902.823.3183
Email: support@nautel.com
Web: www.nautel.com

Parts supplied by Nautel

Ancillary parts kit

An ancillary parts kit is shipped with the XR6/XR3. This kit contains hardware needed during the installation process. The kit includes toroids, spare fuses, screws and other miscellaneous hardware.
Issue 3.0 2009-07-15 Page 9-1
XR6/XR3 Pre-installation Manual Parts and tools

Documentation

See “XR6/XR3 transmitter manuals” on page ix.

Parts not supplied by Nautel

Some parts and materials required to complete installation are not supplied by Nautel. The parts you need vary with the installation requirements. The list of parts you normally provide yourself during installation include:
A suitable 50 Ω RF output coaxial cable, terminated by the proper connector, complete with center male connector at the transmitter end.
All external control and monitor wiring, including the associated terminating devices, con­duit and conduit clamps.
All electrical power cables, including conduit, terminating devices, and conduit clamps.

Parts ordering

You can order replacement parts from your Nautel sales agent, or directly from Nautel through the Nautel website.

Module replacement program

Nautel offers a module replacement program for customers who require expedited servicing and replacement of faulty modules. The module replacement program provides immediate replacement of failed modules with refurbished modules.
The replacement module is shipped to the customer as soon as the customer reports the failure. The customer then returns the failed module to Nautel within 30 days using the same shipping package.
Page 9-2 Issue 3.0 2009-07-15
XR6/XR3 Pre-installation Manual Parts and tools

Tools for installation

The tools you need during transmitter installation include the following:
Digital voltmeter
Philips screwdrivers, sizes #1 and #2
Pliers
Wire cutters
Slot screwdriver, 5 mm (3/16 inch)
Metric and Imperial socket set up to 24 mm (15/16 inch)
Metric and Imperial wrench set up to 25 mm (1 inch)
Feeler gauge (to measure spark gap)
Issue 3.0 2009-07-15 Page 9-3
XR6/XR3 Pre-installation Manual Parts and tools
Page 9-4 Issue 3.0 2009-07-15
XR6/XR3 Pre-installation Manual Accessories

Section 10: Accessories

This section describes accessories and optional equipment for the XR6/XR3 transmitter. Accessories include the following:
Ac line surge protection
Automatic antenna transfer control unit - see page 10-2
Automatic switching system - see page 10-4
Dynamic carrier control unit - see page 10-4
Spares - see page 10-4
Documentation - see page ix

Contacting Nautel

You can reach Nautel to order parts or for technical assistance at:
Nautel Limited
10089 Peggy’s Cove Road Hackett’s Cove, NS Canada B3Z 3J4 Phone: +1.902.823.3900 877 6NAUTEL Fax: +1.902.823.3183
Email: support@nautel.com
Web: www.nautel.com
Issue 3.0 2009-07-15 Page 10-1
XR6/XR3 Pre-installation Manual Accessories

Ac line surge protection

A surge protector panel is recommended for all equipment at the transmitter site. The surge protection panel helps to protect the site from lightning induced voltage transients on the ac power
source or the antenna or ground system. Nautel offers an ac line surge protection panel, which is suitable for use with the XR6/XR3 transmitter. (Various versions are available, depending on your ac configuration and supply voltage.) However, you can use any surge protector with at least a 1,500 Joule per phase rating.
Connect the surge protector’s ground terminal directly to the station reference ground using a 10 cm (4 in.) wide copper strap. Also connect the surge protector’s ground directly to the ac power supply ground, the transmitter’s grounding point, and the common ground for the site. Ensure that the common ground is isolated from any other sources of ground (for example, grounding rods not connected to the station reference ground), to prevent lightning charges from bypassing the surge protector and passing through the ground and into the site.
Place the surge protector as close as possible to the ac service entrance, minimizing both the physical and electrical distance between the service entrance and the surge protector. For detailed information about surge protection, refer to the Nautel Site Protection Manual.

Automatic antenna transfer control unit

The automatic antenna transfer control unit is a 19-inch, rack-mountable assembly that is used in conjunction with two Nautel AM or FM broadcast series transmitters that are to be connected in a main/standby configuration. The control unit controls the on/off status of the transmitters by controlling the status of their safety interlock circuits. It also controls the ac voltage applied to relays or contactors, to determine the routing of the RF output of the on-air transmitter to the antenna. See
“Automatic switching system” on page 10-4. The control unit allows manual or automatic switching
of the main and standby transmitters. In automatic mode, the forward power levels of both transmitters are monitored. If the main (on-air) transmitter's RF output falls below a preset threshold (typically 3 dB), an automatic changeover to the standby transmitter takes place. An interlock override feature allows the operator to enable the RF output of the standby (off-air) transmitter into a dummy load for maintenance or troubleshooting.
Page 10-2 Issue 3.0 2009-07-15
XR6/XR3 Pre-installation Manual Accessories
Figure 10.1: Automatic antenna transfer control unit

RF contactor

The RF contactor is an RF output switching device for a main/standby control cabinet that interfaces main and standby transmitters (less than 15 kW RF output power) between an antenna and a dummy load. Typically, an automatic antenna transfer control unit controls the RF contactor's position by applying ac voltage to the 'set' or 'reset' solenoid of the RF contactor. The RF contactor's position determines the routing of the transmitter outputs to the antenna and dummy load. Micro-switches on the RF contactor provide interlock control for both transmitters and prevent 'live' switching.
Figure 10.2: RF contactor assembly
Issue 3.0 2009-07-15 Page 10-3
XR6/XR3 Pre-installation Manual Accessories

Automatic switching system

The automatic switching system is a changeover rack for the XR6/XR3 that includes an automatic antenna transfer control unit and an RF contactor. The main component of the automatic switching system is a double-pole, double-throw latching switch.

Dynamic carrier control unit

The Dynamic Carrier Control (DCC) option is an add-on, DSP-based module for the XR6/XR3 exciter. This system reduces ac power consumption by reducing the carrier power when the instantaneous modulation level of the transmitter drops below a threshold. The DCC unit supports Amplitude Modulation Companding (AMC), Dynamic Amplitude Modulation (DAM) and Dynamic Carrier Control (DCC) algorithms with various selectable carrier compression levels. Enhanced AMC may also be available.

Spares

spares kit

The spares kit includes fans, fuses, and semiconductors. Contact Nautel Customer Support for details about the contents of the spares kit for your transmitter.

XR series RF power module

The XR RF power module integrates four modulators and eight amplifier units, with a combined power output rating of 9.4 kW, including carrier and modulation. It is compatible with all XR series transmitters.
Figure 10.3: XR RF power module
Page 10-4 Issue 3.0 2009-07-15
XR6/XR3 Pre-installation Manual Accessories

RF Module testing cable and test load

The RF module testing cable allows bench testing and troubleshooting of RF power modules using a direct connection to the transmitter.
The test cable provides a temporary connection from the transmitter to an RF power module that has been removed from the transmitter and placed on a workbench. The test cable provides low-level, safe voltages, that allow the diagnosis of RF power module problems — this is a unique feature of Nautel transmitters.
The RF power module test load provides a low power load suitable for operating an RF power module on the test cable only.

Plug-in power amplifier unit

The XR series power amplifier is a broadband, 1,000 watt plug-in unit compatible with all XR series transmitters.
Figure 10.4: XR power amplifier unit
Issue 3.0 2009-07-15 Page 10-5
XR6/XR3 Pre-installation Manual Accessories
Plug-in power modulator unit
The power modulator unit is a 2,000 watt plug-in unit compatible with all XR series transmitters.
Figure 10.5: Power modulator unit
Page 10-6 Issue 3.0 2009-07-15
XR6/XR3 Pre-installation Manual Pre-installation assistance

Section 11: Pre-installation assistance

Nautel provides a number of support options to help you during pre-installation planning and preparation:
Pre-installation consulting
Installation and commissioning service
Online documentation - see page 11-3
On-site support - see page 11-3
Training - see page 11-3
Standard warranty - see page 11-4
Extended warranties - see page 11-7

Pre-installation consulting

Nautel field support specialists are available to answer questions and work with you to ensure that your site will be ready for the installation of your XR6/XR3 transmitter. For support, contact Nautel Cus­tomer Service and request assistance (see “On-site support” on page 11-3).

Installation and commissioning service

Nautel offers an installation and commissioning service to customers who want assistance with configuring and commissioning a new Nautel transmitter. After the customer completes the transmitter assembly and installation, Nautel technical personnel will spend up to three days on-site to help make the ac power, RF and remote connections, and to assist with the configuration and testing of Nautel equipment.
The customer is responsible for ensuring that the following stages of installation have been completed, prior to the arrival of Nautel personnel:
Ac power wiring for the transmitter has been installed and connected at the breaker panel or the building’s service entrance. If local electrical codes allow Nautel personnel to connect the transmitter to the ac supply, using the customer's cable, that task is included in this service. Otherwise, the customer must ensure that an approved electrician is present for this task.
Issue 3.0 2009-07-15 Page 11-1
XR6/XR3 Pre-installation Manual Pre-installation assistance
The customer has prepared the RF coaxial cable – used to connect the transmitter to the antenna – and installed the required connector. The customer has also installed the RF coax­ial cable in place and connected it to the antenna, while leaving the transmitter end of the cable unconnected.
Where required, all remote control and monitoring cables have been installed and connected to the station equipment (e.g., modulation monitor, frequency monitor, and power meter).
The site has been made ready for the equipment, and adequate protection against lightning and lightning-induced transients has been provided.
The transmitter has been unpacked, closely checked for any damage caused by shipping, and then assembled.
The following test equipment has been made available at the site:
– Two-channel oscilloscope (with probes)
– Audio signal generator
– Distortion analyzer
– Spectrum analyzer
– Modulation monitor
– Frequency counter
– 50 Ω test load (rated for 150% of carrier power, VSWR less than 1.1:1)
Nautel’s service representative takes full responsibility for commissioning the transmitter, validating all external interfaces (i.e., the ac supply, RF output, remote control and monitoring equipment) and checking out the equipment prior to activation. The service representative turns on the transmitter, performs all adjustments and set-up procedures, and carries out proof of performance tests at the site. These tests ensure that the transmitter is operating normally in compliance with its specifications. The service representative also provides a demonstration and a short explanation of the operation of the transmitter. Finally, the customer signs an Acceptance of Installation Certificate that provides feedback to Nautel regarding the commissioning service.
Page 11-2 Issue 3.0 2009-07-15
XR6/XR3 Pre-installation Manual Pre-installation assistance

Online documentation

Nautel provides documentation online to customers, letting you familiarize yourself with specifications, operation, maintenance and troubleshooting prior to the delivery of your equipment.

On-site support

If you require on-site assistance, Nautel’s field support specialists can help you prepare your site, and ensure that your XR6/XR3 transmitter installation can proceed as quickly as possible. For more information about onsite support, including scheduling and pricing, contact Nautel Customer Service:
Telephone: +1.902.823.3900
Fax: +1.902.823.3183
Email: support@nautel.com
After business hours (Atlantic time or Eastern time in North America), requests sent by fax or email will be acknowledged within one working day.

Training

Nautel's SBE-certified broadcast training programs satisfy your day-to-day knowledge requirements. Students participating in Nautel's broadcast transmitter or RF basics training programs earn one SBE credit for each completed day of training. Nautel’s comprehensive selection of training programs will help a customer’s staff develop valuable skill sets, reduce downtime, and make the most of the customer’s technology investment.
Nautel training programs are made up of individual modules that can be mixed and matched to meet the customer’s specific training needs. All Nautel training courses are available at the Nautel Training Center. Training can also be provided at the customer’s facility, for training the customer’s technical staff on the customer’s transmitter.
All training courses at the Nautel Training Centre combine classroom and hands-on laboratory work to ensure a balanced learning experience. Many of our classes also include diagnostic lab exercises.
Nautel training courses feature:
Limited class sizes to ensure maximum student participation and access to equipment
Issue 3.0 2009-07-15 Page 11-3
XR6/XR3 Pre-installation Manual Pre-installation assistance
Emphasis on need-to-know, day-to-day knowledge
Labs that focus on the tasks most often performed at the transmitter site.

XR series on-site or factory training

This includes product overview, site and pre-installation, theory of operation, testing and adjustments, operating instructions, system-level troubleshooting, component-level troubleshooting, component parts lists, and wiring route sheets.

Standard warranty

Nautel Limited/Nautel Incorporated, hereinafter referred to as Nautel, guarantees all mechanical and electrical parts of the equipment for a period of 13 months from date of shipment.
1. A "Part Failure" shall be deemed to have occurred when the part has become defective, or does not have the characteristics required for the specified equipment performance:
(a) When the equipment is operated within the design parameters, and
(b) When the equipment is installed and adjusted according to Nautel's prescribed procedures as stated in the instruction manual.
2. Nautel shall provide replacements for all "Parts" at no cost to the Customer when they become defective during the warranty period, and upon the return of the defective part.
3. In the event that a "Part" fails during the warranty period and causes damage to a sub­assembly that cannot be readily repaired in the field, the entire sub-assembly so damaged may be returned to Nautel for repair. The repairs will be made without charge to the Customer.
4. Where warranty replacements or repair are provided under items 2 or 3, Nautel will pay that part of the shipping costs incurred in returning the part/assembly to the Customer.
5. Warranty replacement parts and repair, which are provided under items 2 or 3, shall be guaranteed for a period of ninety days from date of shipment or until the end of the original warranty period, whichever occurs later.
6. Nautel will not assume responsibility for any charges incurred by other than Nautel employees.
Page 11-4 Issue 3.0 2009-07-15
XR6/XR3 Pre-installation Manual Pre-installation assistance
7. Nautel shall have the privilege of investigating whether failures have been caused by factors beyond its control.
8. Nautel shall in no event be liable for any consequential damages arising from the use of this equipment.
9. When requesting a warranty repair/replacement, please provide complete and accurate information. Observe the instructions regarding “Equipment being returned to Nautel” on
page 11-6 and provide the information requested.
10. When ordering spare/replacement parts, please provide complete and accurate information. Refer to the parts list of the Repair manual for ordering information. Provide as much of the information requested for 'Equipment Being Returned to Nautel' on page two of this warranty as is practical. The information identified by an asterisk is the minimum required.

Technical assistance

Nautel's field service department provides telephone technical assistance on a 24 hour, seven days a week basis. Requests by other media (facsimile or e-mail) will be responded to the next working day if received after Nautel's normal working hours. Contact the appropriate field service centre from the following:
Nautel Limited
10089 Peggy’s Cove Road Hackett’s Cove, NS Canada B3Z 3J4 Phone: +1.902.823.3900 or Toll Free: +1.877.6NAUTEL (6628835) (Canada & USA only) Fax: +1.902.823.3183
Nautel Inc.
201 Target Industrial Circle Bangor, Maine USA 04401 Phone: +1.207.947.8200 Fax: +1.207.947.3693
Customer Service (24 hour support)
+1.877.628.8353 (Canada & USA only) +1.902.823.5100 (International)
Email: support@nautel.com Web: www.nautel.com
Issue 3.0 2009-07-15 Page 11-5
XR6/XR3 Pre-installation Manual Pre-installation assistance

Module exchange service

In order to provide Nautel customers with a fast and efficient service in the event of a problem, Nautel operates a factory rebuilt, module exchange service which takes full advantage of the high degree of module redundancy in Nautel equipment. This module exchange service is operated from Nautel's factory in Bangor, Maine and Hackett's Cove, Nova Scotia. These two locations allow us to provide a quick turn around service to keep our customers on the air. During the transmitter's warranty period, up to thirteen months from shipment, repair and exchange of modules is at no charge to the customer. When the warranty has expired, a charge of 80% of the list price for all exchanged modules is made. If the faulty module is returned to Nautel within 30 days, a credit is issued reducing this charge by one half to 40% of the list price. USA customers are required to contact our Bangor, Maine facility. Canadian and overseas customers should contact our Nova Scotia, Canada facility.

Equipment being returned to Nautel

For all equipment being returned to Nautel and all requests for repairs or replacements:
Obtain an RMA number from Nautel (you must have an RMA number to return equipment)
Mark the item as 'field return'
Mark the item with the RMA number assigned by Nautel
Address the item to the appropriate Nautel facility
Complete and accurate information regarding the equipment being returned will ensure prompt attention and will expedite the dispatch of replacements. Refer to the nameplate on the transmitter and/or the appropriate module/assembly to obtain name, type, part and serial number information. Refer to the parts list of this manual or the appropriate service instruction manual for additional ordering information.
The following information should accompany each request (* denotes minimum required information):
*Model and serial number of equipment
*Name of part/assembly
Serial number of part/assembly
*Complete reference designation of part/assembly
Page 11-6 Issue 3.0 2009-07-15
XR6/XR3 Pre-installation Manual Pre-installation assistance
*Nautel's part number of part/assembly
*OEM's part number of part/assembly
Number of hours in use
Nature of defect
*Return shipping address

Extended warranties

Nautel's standard 13-month warranty provides excellent coverage and satisfies most customers’ needs. However, if you want extended coverage, Nautel offers one- and two-year Extended Warranty Plans to cover electrical and mechanical repairs or replacements for all Nautel equipment.

Coverage

The Extended Warranty Plan includes:
A module exchange program for many common modules and circuit boards (North America only)
Toll-free hotline (North America only)
Necessary labor performed by Nautel authorized personnel to repair the product to meet factory specifications
Necessary components
Modifications to correct performance problems
Return shipping.
Issue 3.0 2009-07-15 Page 11-7
XR6/XR3 Pre-installation Manual Pre-installation assistance
Details
Extended Warranty Plans must be purchased prior to the expiration of original 13-month warranty.
One-year Extended Warranty Plans add an additional year (12 months) of coverage after the end of the customer’s standard 13-month warranty. The two-year plan adds an additional two years (24 months).
Only repairs done at Nautel's facilities or by Nautel authorized personnel will be covered by the Extended Warranty Plans.
You must ship faulty products back to Nautel, prepaid, and in the original package or in a package that provides equivalent protection.
Nautel can choose to repair or replace equipment.

Purchasing a one- or two-year Extended Warranty Plan

If the transmitter is still covered by its original 13-month warranty period, you can contact Nautel by telephone, fax, mail, or email with the model number, serial number and date of purchase.
Once you purchase a Nautel Extended Warranty Plan, you receive an extended warranty plan certificate, plan number, and a toll-free number (North America only) to call for any service-related issues.

Using the Extended Warranty Plan

Contact Nautel's Canadian or U.S. service facility by phone, fax, or email as soon as a problem occurs. The following will be required when contacting Nautel:
Extended warranty plan number
Product model number
Serial number
Brief description of the problem
If Nautel’s service technicians are unable to solve the problem over the telephone, Nautel will give you an RMA number. You then return the module or circuit board to a Nautel service facility, so that Nautel can provide a replacement. Do not ship a component back to Nautel until you have an RMA number.
Page 11-8 Issue 3.0 2009-07-15
XR6/XR3 Pre-installation Manual List of terms

Section 12: List of terms

This section defines some of the terms that are used in Nautel documentation.
AES-EBU. Audio Engineering Society/European Broadcasting Union (AES/EBU) is the name of a
digital audio transfer standard. The AES/EBU digital interface is usually implemented using 3-pin XLR connectors (the same type connector used in professional microphones). One cable carries both left- and right-channel audio data to the receiving device.
AMC. Amplitude Modulation Companding
Antenna Tuning Unit (ATU). A device that matches the transmitter to the impedance of the
antenna.
B+. The high voltage dc generated by the transmitter’s ac power supply for use within the transmitter.
The B+ voltage is used to supply the transmitter’s modulators and other transmitter circuitry.
Cutback. A reduction in RF output power, caused by a total power limit fault or the occurrence of
three shutbacks within a five second period.
DAM. Dynamic Amplitude Modulation.
DCC. Dynamic Carrier Control.
DSP. Digital Signal Processing.
HD Radio. High Definition (HD) Radio is another term for In Band On Channel (IBOC)
technology. HD Radio is a trademark of iBiquity Digital Corporation.
IBOC. Nautel In-Band-On-Channel technology provides high quality digital audio over existing AM
radio channels.
IPM. Incidental Phase Modulation
NE IBOC. Nautel’s In-Band-On-Channel signal generator. See IBOC. Required for XR series IBOC
installations.
PDM. Pulse Duration Modulation.
Issue 3.0 2009-07-15 Page 12-1
XR6/XR3 Pre-installation Manual List of terms
Preset. A setting that controls power level, active exciter, and power scheduler status on a time-of-
day and date basis. Exciters can be configured on a preset for a specific operating mode (for example, Exciter A - conventional AM, and Exciter B - IBOC). The XR6/XR3 allows you to pre-program up to six presets.
Shutback. A complete loss of RF output power, caused by any one of a variety of faults, including
high VSWR, low B+ voltage, high RF current, RF drive failure, external interlock or spark gap.
Surge protection board. An electrical panel that protects equipment from electrical surges in the
ac power supply, antenna or site ground caused by lightning strikes.
VSWR. Voltage standing wave ratio. This is an expression of the ratio of forward voltage to reverse
voltage on the feedline and antenna system. An ideal VSWR of 1:1 provides maximum transmitter­antenna efficiency.
Page 12-2 Issue 3.0 2009-07-15
XR6/XR3 Pre-installation Manual
Index
Numerics
10 MHz Reference Input BNC connector,
7-2
4-wire Wye (star) configuration, 5-3
A
AC line surge protection 10-2
AC power
surge protection, 10-2
Ac power
emergency on/off switch, 5-2 over capacity, 5-2 stability, 5-2 surge protection, 5-2 switch assembly, 5-2 transformer, 5-1
Wye configuration, 5-3 Ac power, 5-2 access panels, 3-1 active exciter 6-7 active exciter, 6-1 adjustment, RF power, 6-1, 6-7 air conditioning 4-2 air exhaust, 3-1 air filters, 3-1 air flow, 2-1 air insulator, 8-1 air temperature, 4-3 air temperature, transmitter room, 4-2 ancillary kit, 9-1 antenna considerations 8-1 antenna feedline, 2-3 antenna tower, 2-1
antenna transfer control unit (NX1) 10-2 antenna tuning 8-3 assistance, onsite, 11-3 assistance, technical, 11-1
audio
processing, 5-2
automatic antenna transfer control unit
(NX1) 10-2
B
bi-directional surge protection, 5-2 bowl type bushing insulators, 8-2 breakdown flashover, 8-1 breakdown level, 8-1 British thermal units (Btu), 4-3 building entrance, 2-3 bushing insulators, 8-2
C
cable, coaxial, 2-3 capacitive RF divider, on insulators, 8-2
carbon tracks, causing insulator break-
down, 8-2 carrier control unit (NAX154) 10-4 carrier frequency impedance, 8-3 carrier frequency oscillator, 7-1 carrier frequency, 7-1, 7-2 carrier level, 5-2 changeover rack 10-4 clearances, 3-1 closed loop cooling systems, 4-3 closed system 4-2 coaxial cable, 2-3, 9-2 coaxial RF feedline, 5-4
Issue 3.0 2009-07-15 Page IX-1
XR6/XR3 Pre-installation Manual
conduit, 9-2 connector, RF, 2-2 consulting assistance 11-1 control and monitor wiring, 9-2 control panel, 2-2 cooling exhaust, 3-1 cooling systems, 4-3 cooling, 2-1 copper strap, for grounding, 5-4, 10-2 corona, around small radius RF conductors,
8-2
D
designated reference ground point, 5-4 digital broadcasting, 8-3 digital modulation schemes, 8-3
digital PHASE COMPONENT BNC connec-
tor, 7-1 documentation, online, 11-3 DRM, 8-3
external control and monitor wiring, 9-2 external DC power supply, 6-7 external frequency reference, 2-2 external monitoring circuit, 6-10 external monitoring, 6-12 external RF driver, 2-2
F
feed throughs, 8-1 feedline termination, 2-2 ferrite toroid, 5-2 filters, 3-1 flange connector, 2-2 flange, RF feedline, 8-2 flashover, 8-1 forward power level, 6-12 frequency impedance, 8-3 frequency oscillator, 7-1 frequency reference, 2-2
ducting, 2-1 dynamic carrier control unit (NAX154) 10-4
E
EIA flange connector, 2-2 EIA Standard, 8-3 electrical ground, 5-3 electrical power cables, 9-2 electrodes, 8-1 electrostatic protection, 2-1 emergency on/off switch, 5-2 engineering support, 11-1 erosion of an insulator, 8-2 exciter, active, 6-1, 6-7
G
gas breakdown flashover, 8-1 gas insulator, 8-2 GPS clock signal, 7-2 ground point, 5-4 ground system, 10-2 ground terminal, 10-2 ground, electrical, 5-3
H
hardware needed during installation, 9-1 heating system, 4-3 Hermitian symmetry 8-3 high voltage feed throughs, 8-1
Page IX-2 Issue 3.0 2009-07-15
XR6/XR3 Pre-installation Manual
high voltage RF conductor, 8-1
I
IBOC
sideband symmetry 8-3 IBOC, 8-3 impedance path to ground, 5-3 impedance sweep 8-3 impedance, 8-3 induced current, lightning, 5-3 installed RF feedline, 8-2 insulation flashovers, 8-1 Insulator flashover, 8-1 insulators, 8-1
J
J2, 7-2
modulation 5-2, 8-2 modulation monitor, 6-13 modulation, 8-3 module testing cable (XR PMTK), 10-5 moisture damage to insulators, 8-1 monitor wiring, 9-2 monitoring, 6-12
N
NAX154, dynamic carrier control unit 10-4 NAX188 AC line surge protection 10-2 nominal voltage, 5-1
NX1, automatic antenna transfer control
unit 10-2
O
on/off switch, 5-2 J8 BNC connector, 6-13 junction stress gradient, RF feedline, 8-2 junction, three material, 8-1
L
lightning
induced current, 5-3
protection, 2-1 lightning protection, 2-3 line surge protection 10-2 loading conditions, power, 5-2 local corona, RF conductor, 8-2 location for transmitter, 2-1 logic true condition, 6-10
M
mating connector, RF, 2-2 minimum clearances, 3-1
onsite assistance, 11-3 opto couplers, 6-7 oscilloscope, 6-13 output voltage waveform, 6-12 over-capacity, Ac power, 5-2
P
panel, rear, 3-1 parts ordering 9-2 parts, 9-1 peak voltages, RF feedline, 8-2 phases balanced to ground, Ac power, 5-3 planning assistance 11-1 plug-in power amplifier unit (XR PA), 10-5 plug-in power modulator unit (XR MOD),
10-6
pollution, as a trigger of insulator break-
down, 8-2
Issue 3.0 2009-07-15 Page IX-3
XR6/XR3 Pre-installation Manual
power amplifier unit (XR PA), 10-5 power consumption 5-2 power consumption, 5-2 power modulator unit (XR MOD), 10-6 power service, 2-1 power source 5-1 power switch assembly, 2-1, 5-2 power transformer, 5-1 preset carrier level, 5-2 preset power level 6-13 preset RF power level, 6-1, 6-7 previously installed RF feedline, 8-2 pricing, support, 11-3 primary winding, power transformer, 5-1 programming format, 5-2
R
rain, as a trigger of insulator breakdown,
8-2
rear panel, 3-1 reference frequency, 7-2 reference ground, 5-4 reference source, 2-2 reflected power level, 6-12 refurbished modules 9-2 replacement parts 9-2 requirements, site, 2-1 reset, system alarm, 6-1, 6-7, 6-13 RF contactor 10-4 RF divider, on insulators, 8-2 RF feedline, 2-2, 2-3 RF output coaxial cable, 9-2 RF output voltage waveform, 6-12
RF power, preset, 6-1, 6-7 room, transmitter, 4-2
S
safety interlocks, 2-2 scheduling onsite support, 11-3 shield ground, 2-3 shield termination, 2-3 shield, feedline, 2-3 sideband symmetry 8-3 sideband VSWRs, 8-3 site requirements, 2-1 small radius conductors, RF, 8-2 snow, as a trigger of insulator breakdown,
8-2
solid insulator, 8-2 spares kit, 10-4 square law function 6-12 standards, 8-3 star configuration, Ac power, 5-3 station modulation monitor, 6-13 station reference ground, 5-2, 5-4, 10-2 stress control techniques, voltage, 8-2 stress gradient, RF feedline, 8-2 surge protection 10-2 surge protection, 5-2, 10-2 surge protector panel, 5-3 switching system, automatic 10-4 symmetry, sideband 8-3 synthesizer board, 7-2 system alarm reset 6-7 system alarm reset, 6-1, 6-13 system performance, 8-3
Page IX-4 Issue 3.0 2009-07-15
XR6/XR3 Pre-installation Manual
T
taps, transformer, 5-1 technical support, 11-1 temperature, transmitter room, 4-2 terminating devices, 9-2 three material junction, 8-1 tools, 9-1 toroid, 2-3, 5-2 total weight, 2-2 tower, 2-1 training, 2-2 transformer, Ac power, 3-5 transients, from lightning, 10-2 transients, in remote control wiring, 6-7 transmitter flange, RF feedline, 8-2 transmitter location, 2-1 transmitter room, 4-2 triple junctions, RF feedline, 8-2
W
waste heat 4-2 waste heat, 4-3 waveform, RF input voltage, 6-12 website 9-2 weight, 2-2 weight, components, 3-5 work area, 2-1 workbench, 2-1 Wye (star) configuration, Ac power, 5-3
X
XR MOD, plug-in power modulator unit,
10-6
XR PA, plug-in power amplifier unit, 10-5 XR PM, XR series power module, 10-4 XR PMTK, module testing cable, 10-5 XR series power module, 10-4
tuning, antenna 8-3 typical program content, 6-8, 6-9
U
uncrated weight, 3-5 upgrading a site, 2-1 upper rear panel, 3-1
V
varistor, 5-3 voltage feed throughs, 8-1 voltage transients, 10-2 voltage, AC 5-1 VSWR, 8-3
Issue 3.0 2009-07-15 Page IX-5
XR6/XR3 Pre-installation Manual
Page IX-6 Issue 3.0 2009-07-15
XR6/XR3
Pre-installation Manual
Document: XR6/XR3-PREINST
Issue: 3.0 2009-07-15
Nautel Limited
10089 Peggy’s Cove Road Hackett’s Cove, NS Canada B3Z 3J4 Phone: +1.902.823.3900 or Toll Free: +1.877.6NAUTEL (6628835) (Canada & USA only) Fax: +1.902.823.3183
Nautel Inc.
201 Target Industrial Circle Bangor, Maine USA 04401 Phone: +1.207.947.8200 Fax: +1.207.947.3693
Customer Service (24 hour support)
+1.877.628.8353 (Canada & USA only) +1.902.823.5100 (International)
Email: support@nautel.com Web: www.nautel.com © Copyright 2009 NAUTEL. All rights reserved.
Loading...