SCC-AI Series Isolated Analog
Input Modules
The SCC-AI Series isolated analog input modules can extract a relatively
low-amplitude input signal from a high-common-mode voltage so the
E/M Series DAQ device can measure the input signal. They also can
amplify and filter the input signal, resulting in higher measurement
resolution and accuracy.
SCC-AI Series modules are available in a range of gains from 0.2 to 200.
They contain lowpass filters of either 10 kHz or 4 Hz bandwidth. Table 1
gives the gain and bandwidth for each module.
Table 1. SCC-AI Module Input/Output Range, Gain, and Bandwidth
ModelInput RangeOutput RangeGainBandwidth
SCC-AI01±42 Vpk/ VDC±8.4 V0.210 kHz
SCC-AI02±20 V±10 V0.510 kHz
SCC-AI03±10 V±10 V110 kHz
SCC-AI04±5 V±10 V210 kHz
SCC-AI05±1 V±10 V1010 kHz
SCC-AI06±100 mV±10 V10010 kHz
SCC-AI07±50 mV±10 V20010 kHz
SCC-AI13±10 V±10 V14 Hz
SCC-AI14±5 V±10 V24 Hz
Conventions
The following conventions are used in this guide:
<>Angle brackets that contain numbers separated by an ellipsis represent
a range of values associated with a bit or signal name—for example,
AI <0..7>.
»The » symbol leads you through nested menu items and dialog box options
to a final action. The sequence File»Page Setup»Options directs you to
pull down the File menu, select the Page Setup item, and select Options
from the last dialog box.
This icon denotes a note, which alerts you to important information.
This icon denotes a caution, which advises you of precautions to take to
avoid injury, data loss, or a system crash.When this symbol is marked on
the product, refer to the Read Me First: Safety and Radio-Frequency Interference document, shipped with the product, for precautions to take.
When symbol is marked on a product, it denotes a warning advising you to
take precautions to avoid electrical shock.
When symbol is marked on a product, it denotes a component that may be
hot. Touching this component may result in bodily injury.
boldBold text denotes items that you must select in the software, such as menu
items and dialog box options. Bold text also denotes parameter names.
italicItalic text denotes variables, emphasis, a cross-reference, or an introduction
to a key concept. Italic text also denotes text that is a placeholder for a word
or value that you must supply.
monospaceText in this font denotes text or characters that you should enter from the
keyboard, sections of code, programming examples, and syntax examples.
This font is also used for the proper names of disk drives, paths, directories,
programs, subprograms, subroutines, device names, functions, operations,
variables, filenames, and extensions.
SC-2345SC-2345 refers to both the SC-2345 connector block and the SC-2345
configurable connector.
SCCSCC refers to any SCC series signal conditioning module.
SCC-AISCC-AI refers to any isolated analog input module in the SCC-AI Series
unless otherwise noted.
SCC-AI Series Isolated Analog Input Modules User Guide2ni.com
What You Need to Get Started
To set up and use the SCC-AI, you need the following items:
❑ Hardware
–SCC-68
or
–SC-2345/2350 with one of the following:
•SCC-PWR01
•SCC-PWR02 and the PS01 power supply
•SCC-PWR03 (requires a 7 to 42 VDC power supply,
not included)
–One or more SCC-AI
–68-pin E/M Series DAQ device
–68-pin cable
–Quick Reference Label
❑ Software
–The latest version of NI-DAQmx
❑ Documentation
–SCC-AI Series Isolated Analog Input Modules User Guide
–SC-2345/2350 User Manual
–SCC-68 User Guide
or
–SCC Quick Start Guide
–Read Me First: Safety and Radio-Frequency Interference
–Documentation for your hardware
–Documentation for your software
❑ Tools
–1/8 in. flathead screwdriver
–Numbers 1 and 2 Phillips screwdrivers
–Wire insulation stripper
Note Software scaling of measurements is not supported on the Macintosh operating
system. Refer to the SCC-AI Module Pin Assignments section.
You can download NI documents from ni.com/manuals. To download
the latest version of NI-DAQmx, click Download Software at
Device Specific Information
Note For general SCC module installation and signal connection information, and
information about the SC-2345/2350 or SCC-68, refer to the SCC Quick Start Guide,
available for download at
Installing the Module
Caution Refer to the Read Me First: Safety and Radio-Frequency Interference document
before removing equipment covers or connecting/disconnecting any signal wires.
You can plug the SCC-AI into any analog input socket on the
SC-2345/2350 or SCC-68. The socket you choose determines which
E/M Series DAQ device channels receive the SCC-AI signals.
For single-stage input conditioning, plug the SCC-AI into any slot of the
SC-68, or any socket of the SC-2345/2350 J(X+1), where X is 0 to 7.
Connect the input signals to the module as described in the Connecting the
Input Signals section.
ni.com/manuals.
ni.com.
If you use the SCC-AI in a dual-stage configuration in an SC-2345, the
SCC-AI must be the first-stage module. Plug it into any socket J(X+9) and
plug the second-stage SCC into socket J(X+1), where X is 0 to 7. Connect
the input signals to the SCC-AI as described in the Connecting the Input
Signals section. The SC-2345 connects the output signals of the first-stage
SCC to the inputs of the second-stage SCC. An example of dual-stage
conditioning is an SCC-AI02 followed by an SCC-FV01 frequency input
module.
Sockets J9 to J16 of the SC-2345 are also available for digital input/output
(DIO) conditioning or control. Refer to the SC-2345/2350 User Manual
for more information about configuring, connecting, and installing SCC
modules.
SCC-AI Series Isolated Analog Input Modules User Guide4ni.com
Connecting the Input Signals
Note The signal names have changed. Refer to ni.com/info and enter rdtntg to
confirm the signal names.
Each screw terminal on the SCC-AI is labeled by pin number <1..4>. Pins 1
and 2 form a channel routed to E/M Series DAQ device channel X+8, and
pins 3 and 4 form a channel routed to the E/M Series DAQ device channel
X, where X is 0 to 7 depending on the socket where you plug in the module.
The SCC-AI provides channel-to-ground and module-to-module isolation
only. It does not provide isolation between the two channels of the SCC-AI.
Because both channels must have the same reference voltage, pins 1 and 3
are connected together internally.
Figure 1 shows the SCC-AI signal connections.
Signal
Source
+
–
+
–
SCC-AI
4
3
2
1
E/M Series DAQ Device
+
Lowpass
–
+
–
Filter
Lowpass
Filter
AI (X )
AI SENSE
AI GND
AI (X+8)
Figure 1. SCC-AI Signal Connections
The inputs are designed in a floating (nonreferenced) single-ended
configuration. If the measured signals are floating, connect the negative
input pins, 1 and 3, to AI SENSE on the SC-2345/2350 terminal block or
AI GND on the SC-68, through a 10 kΩ to 100 kΩ resistor. Figure 2 shows
a floating signal connection on one channel of the SCC-AI.