This manual is intended for users of the Regulated DC Power Supply and their instructors.
It is assumed that the reader has knowledge about electrical safety standards and the electrical
aspects of regulated DC power supplies.
Safety Guidelines
Indicates general danger, warning, or caution. When this symbol is marked on the
product, see the relevant section in the operation manual.
Indicates a location whose surface can become hot.
Protective conductor terminal.
Chassis (frame) terminal.
On (supply).
Off (supply).
Support
Worldwide Technical Support and Product Information
ni.com
Worldwide Offices
Visit ni.com/niglobal to access the branch office Web sites, which provide up-to-date
contact information, support phone numbers, email addresses, and current events.
National Instruments Corporate Headquarters
11500 North Mopac Expressway Austin, Texas 78759-3504 USA Tel: 512 683 0100
For further support information, refer to the NI Services appendix. To comment on National
Instruments documentation, refer to the National Instruments website at
enter the Info Code feedback.
This document is provided ‘as is’ and is subject to being changed, without notice, in future editions. For the latest version,
refer to
ni.com/manuals. NI reviews this document carefully for technical accuracy; however, NI MAKES NO EXPRESS
OR IMPLIED WARRANTIES AS TO THE ACCURACY OF THE INFORMATION CONTAINED HEREIN AND
SHALL NOT BE LIABLE FOR ANY ERRORS.
NI warrants that its hardware products will be free of defects in materials and workmanship that cause the product to fail to
substantially conform to the applicable NI published specifications for one (1) year from the date of invoice.
For a period of ninety (90) days from the date of invoice, NI warrants that (i) its software products will perform substantially
in accordance with the applicable documentation provided with the software and (ii) the software media will be free from
defects in materials and workmanship.
If NI receives notice of a defect or non-conformance during the applicable warranty period, NI will, in its discretion: (i) repair
or replace the affected product, or (ii) refund the fees paid for the affected product. Repaired or replaced Hardware will be
warranted for the remainder of the original warranty period or ninety (90) days, whichever is longer. If NI elects to repair or
replace the product, NI may use new or refurbished parts or products that are equivalent to new in performance and reliability
and are at least functionally equivalent to the original part or product.
You must obtain an RMA number from NI before returning any product to NI. NI reserves the right to charge a fee for
examining and testing Hardware not covered by the Limited Warranty.
This Limited Warranty does not apply if the defect of the product resulted from improper or inadequate maintenance,
installation, repair, or calibration (performed by a party other than NI); unauthorized modification; improper environment;
use of an improper hardware or software key; improper use or operation outside of the specification for the product; improper
voltages; accident, abuse, or neglect; or a hazard such as lightning, flood, or other act of nature.
THE REMEDIES SET FORTH ABOVE ARE EXCLUSIVE AND THE CUSTOMER’S SOLE REMEDIES, AND SHALL
APPLY EVEN IF SUCH REMEDIES FAIL OF THEIR ESSENTIAL PURPOSE.
EXCEPT AS EXPRESSLY SET FORTH HEREI N, PRODUCTS ARE PROVIDED "AS IS" WITHOUT WARRANTY OF
ANY KIND AND NI DISCLAIMS ALL WARRANTIES, EXPRESSED OR IMPLIED, WITH RESPECT TO THE
PRODUCTS, INCLUDING ANY IMPLIED WARRANTIES OF MERCHANTABILITY, FITNESS FOR A
PARTICULAR PURPOSE, TITLE OR NON-INFRINGEMENT, AND ANY WARRANTIES THAT MAY ARISE FROM
USAGE OF TRADE OR COURSE OF DEALING. NI DOES NOT WARRANT, GUARANTEE, OR MAKE ANY
REPRESENTATIONS REGARDING THE USE OF OR THE RESULTS OF THE USE OF THE PRODUCTS IN TERMS
OF CORRECTNESS, ACCURACY, RELIABILITY, OR OTHERWISE. NI DOES NOT WARRANT THAT THE
OPERATION OF THE PRODUCTS WILL BE UNINTERRUPTED OR ERROR FREE.
In the event that you and NI have a separate signed written agreement with warranty terms covering the products, then the
warranty terms in the separate agreement shall control.
Copyright
Under the copyright laws, this publication may not be reproduced or transmitted in any form, electronic or mechanical,
including photocopying, recording, storing in an information retrieval system, or translating, in whole or in part, without the
prior written consent of National Instruments Corporation.
National Instruments respects the intellectual property of others, and we ask our users to do the same. NI software is protected
by copyright and other intellectual property laws. Where NI software may be used to reproduce software or other materials
belonging to others, you may use NI software only to reproduce materials that you may reproduce in accordance with the
terms of any applicable license or other legal restriction.
End-User License Agreements and Third-Party Legal Notices
You can find end-user license agreements (EULAs) and third-party legal notices in the following locations:
• Notices are located in the
directories.
• EULAs are located in the
•Review
<National Instruments>\_Legal Information.txt for information on including legal information in
installers built with NI products.
U.S. Government Restricted Rights
If you are an agency, department, or other entity of the United States Government (“Government”), the use, duplication,
reproduction, release, modification, disclosure or transfer of the technical data included in this manual is governed by the
Restricted Rights provisions under Federal Acquisition Regulation 52.227-14 for civilian agencies and Defense Federal
Acquisition Regulation Supplement Section 252.227-7014 and 252.227-7015 for military agencies.
Trademarks
Refer to the NI Trademarks and Logo Guidelines at ni.com/trademarks for more information on National Instruments
trademarks.
ARM, Keil, and µVision are trademarks or registered of ARM Ltd or its subsidiaries.
LEGO, the LEGO logo, WEDO, and MINDSTORMS are trademarks of the LEGO Group.
TETRIX by Pitsco is a trademark of Pitsco, Inc.
FIELDBUS FOUNDATION
<National Instruments>\_Legal Information and <National Instruments>
and FOUNDATION™ are trademarks of the Fieldbus Foundation.
EtherCAT® is a registered trademark of and licensed by Beckhoff Automation GmbH.
®
CANopen
DeviceNet
Go!, SensorDAQ, and Vernier are registered trademarks of Vernier Software & Technol ogy. Vernier Software & Technology
and
is a registered Community Trademark of CAN in Automation e.V.
™
and EtherNet/IP™ are trademarks of ODVA.
vernier.com are trademarks or trade dress.
Xilinx is the registered trademark of Xilinx, Inc.
Taptite and Trilobular are registered trademarks of Research Engineering & Manufacturing Inc.
®
is the registered trademark of Apple Inc.
FireWire
®
Linux
is the registered trademark of Linus Torvalds in the U.S. and other countries.
®
Handle Graphics
trademarks, and TargetBox
Tektronix
The Bluetooth
The ExpressCard
license.
The mark LabWindows is used under a license from Microsoft Corporation. Windows is a registered trademark of Microsoft
Corporation in the United States and other countries.
, MATLAB®, Real-Time Workshop®, Simulink®, Stateflow®, and xPC TargetBox® are registered
™
®
, Tek, and Tektronix, Enabling Technology are registered trademarks of Tektronix, Inc.
®
word mark is a registered trademark owned by the Bluetooth SIG, Inc.
™
and Target Language Compiler™ are trademarks of The MathWorks, Inc.
word mark and logos are owned by PCMCIA and any use of such marks by National Instruments is under
Other product and company names mentioned herein are trademarks or trade names of their respective companies.
Members of the National Instruments Alliance Partner Program are business entities independent from National Instruments
and have no agency, partnership, or joint-venture relationship with National Instruments.
Patents
For patents covering National Instruments products/technology, refer to the appropriate location: Help»Patents in your
software, the
patents.txt file on your media, or the National Instruments Patent Notice at ni.com/patents.
Export Compliance Information
Refer to the Export Compliance Information at ni.com/legal/export-compliance for the National Instruments global
trade compliance policy and how to obtain relevant HTS codes, ECCNs, and other import/export data.
WARNING REGARDING USE OF NATIONAL INSTRUMENTS PRODUCTS
YOU ARE ULTIMATELY RESPONSIBLE FOR VERIFYING AND VALIDATING THE SUITABILITY AND
RELIABILITY OF THE PRODUCTS WHENEVER THE PRODUCTS ARE INCORPORATED IN YOUR SYSTEM OR
APPLICATION, INCLUDING THE APPROPRIATE DESIGN, PROCESS, AND SAFETY LEVEL OF SUCH SYSTEM
OR APPLICATION.
PRODUCTS ARE NOT DESIGNED, MANUFACTURED, OR TESTED FOR USE IN LIFE OR SAFETY CRITICAL
SYSTEMS, HAZARDOUS ENVIRONMENTS OR ANY OTHER ENVIRONMENTS REQUIRING FAIL-SAFE
PERFORMANCE, INCLUDING IN THE OPERATION OF NUCLEAR FACILITIES; AIRCRAFT NAVIGATION; AIR
TRAFFIC CONTROL SYSTEMS; LIFE SAVING OR LIFE SUSTAINING SYSTEMS OR SUCH OTHER MEDICAL
DEVICES; OR ANY OTHER APPLICATION IN WHICH THE FAILURE OF THE PRODUCT OR SERVICE COULD
LEAD TO DEATH, PERSONAL INJURY, SEVERE PROPERTY DAMAGE OR ENVIRONMENTAL HARM
(COLLECTIVELY, “HIGH-RISK USES”). FURTHER, PRUDENT STEPS MUST BE TAKEN TO PROTECT AGAINST
FAILURES, INCLUDING PROVIDING BACK-UP AND SHUT-DOWN MECHANISMS. NI EXPRESSLY DISCLAIMS
ANY EXPRESS OR IMPLIED WARRANTY OF FITNESS OF THE PRODUCTS OR SERVICES FOR HIGH-RISK
USES.
Contents
Chapter 1
Installation and Preparation
Attaching the Connector Cover ........................................................................................ 1-1
Connecting the Power Cord.............................................................................................. 1-1
RMX-4120/4121/4122/4123 (750 W Models)......................................................... 1-2
This chapter describes how to turn on an RMX programmable power supply, what kind of load
cables to use, and how to connect cables to the output connectors.
Note Protection provided by this equipment may be impaired if it is used in a
manner not described in the manual.
Attaching the Connector Cover
RMX programmable power supplies are supplied with a connector cover that fits over the entire
sensing, J1, and J2 connectors. For safety reasons, be sure to attach the connector cover when
you use the RMX programmable power supply.
Figure 1-1. Connector Cover
Connecting the Power Cord
This product is a piece of equipment that conforms to IEC Overvoltage Category II (equipment
that consumes energy supplied from a fixed installation).
A power cord is not included with the RMX-4124/4125/4126/4127. Use a power cord that
conforms to this product’s rated AC input voltage, input current, and configured for the
plug type. Refer to your product specifications for details.
Caution Risk of electric shock. This product is a piece of equipment that conforms
to IEC Safety Class I (equipment that has a protective conductor terminal). Be sure
to earth ground the product to prevent electric shock. The product is grounded
through the power cord ground wire. Connect the protective conductor terminal to
earth ground.
•North America—Extra Hard Usage Cord, min. 300 V, 60 C, 14 AWG, 3 Conductor cord,
3 m or less, with a NEMA 5-15P to C14.
•Europe—HAR Marked, min. 300 V, 60 C, 2.5mm2, 3 Conductor cord, 3 m or less, with a
plug configured for the country of use to C14.
•International—Certified for country of use, min. 300 V, 60 C, 2.5mm
3 m or less, with a plug configured for the country of use to C14.
The power cord can be used to disconnect the RMX programmable power supply from the
AC power line in an emergency. Connect the plug to an easily accessible power outlet so that the
plug can be removed from the outlet at any time. Be sure to provide adequate clearance around
the power outlet.
1.Check that the AC power line meets the nominal input rating of the product. The product
can receive a nominal line voltage in the range of 100 VAC to 240 VAC at 50 Hz or 60 Hz.
2.Check that the POWER switch is turned off.
3.Connect the power cord to the AC inlet on the rear panel.
4.Insert the power plug into a grounded outlet.
2
, 3 Conductor cord,
RMX-4124/4125/4126/4127 (1500 W Models)
Caution Risk of electric shock. Before you connect the power cord, turn off the
switchboard breaker (a switch that cuts off the power supply from the switchboard).
Risk of fire. Connection to the switchboard must be performed by a person who has
knowledge about electrical safety standards and the electrical aspects of regulated
DC power supplies. The switchboard breaker must meet the requirements shown
below.
Caution Inside the product, protective circuits are connected to match the polarity
of the input terminal. Be sure to connect the L, N, and (GND) terminals of the product
to the matching terminals on the switchboard.
In an emergency, turn off the switchboard breaker to disconnect the product from the AC power line.
•Input terminal end: 14 mm of insulation stripped from conductor for the L and N wires.
Crimping terminal: (round, M4) that fixes the cable insulation in place
for the GND wire
•Length: 3 m or less
Switchboard Breaker Requirements
•Installation must be done in accordance with national wiring rules, such as NFPA 70 "NEC"
and CSA C22.1 "CEC".
•Rated current: 30 A (for safety, breakers whose rated current exceeds 30 A cannot be used)
•Do not power any other equipment from the switchboard breaker.
•Keep the breaker readily accessible at all times.
•Indicate that the breaker is dedicated for use with this product and that it is used to
When crimping the core wire, use a
crimping terminal and tool that can
also grip the insulation.
Connection Procedure
1.Check that the AC power line meets the nominal input rating of the product. The product
can receive a nominal line voltage in the range of 100 VAC to 240 VAC at 50 Hz or 60 Hz.
2.Check that the POWER switch is turned off.
3.Attach a crimping terminal to the GND wire.
Figure 1-3. Attaching the Crimping Terminal
4.Connect the power cord and the included INPUT terminal cover to the AC INPUT terminal
on the rear panel. Be sure to connect the AC INPUT L, N, and (GND) terminals correctly.
Pass the power cord through the INPUT terminal cover, and fix the cord in place using the
cable gland.
1-4 | ni.com
RMX Programmable Power Supplies User Manual
STRIP-GAUGE
14 mm
Correct
Incorrect
Incorrect
The stripped wire is
touching the chassis.
The wire strands are
touching the chassis.
INPUT terminal cover
INPUT terminal cover
INPUT terminal cover
AC INPUT terminal
L: Black or brown
N: White or blue
(GND)
Screw
: Green or green and yellow
Power cord
Power cord
Power cord
Screw
Use this screw to fix the
wire in place.
Screw M4
Remove the first
14 mm of the wire’s
covering, and then
insert the wire here.
AC INPUT terminal
Cable gland:
Turn left to unlock
Cable gland:
Turn right to lock
Cable gland: Supports wires from 10.5 to 14.4 mm in diameter
Figure 1-4. Connecting the Power Cord
5.Attach an appropriate crimping terminal to the switchboard end of the power cord.
6.Turn off the switchboard breaker.
7.Connect the L, N, and (GND) wires of the power cord to the matching terminals on the
switchboard.
Caution Risk of electric shock. Regardless of whether load cables are connected to
the output terminals, be sure to attach the OUTPUT terminal cover before turning the
POWER switch on.
You can use the CONFIG settings to set how the RMX programmable power supplies
start when you turn the POWER switch on. Depending on the setting, the output may
be turned on automatically when the POWER switch is turned on. If you connect a
load without setting OVP and OCP to appropriate values, the load may be damaged
if the output is programmed to automatically turn on when the power is switched on.
When you turn the POWER switch on for the first time after purchase, the RMX programmable
power supply will be programmed with its factory default settings. Refer to Chapter 2, Factory
Default Settings (Initialization), for more information about these settings. Each subsequent
time you turn the power supply on, it starts with the panel settings (excluding the output on/off
setting) that were in use immediately before the POWER switch was turned off.
You can use the CONFIG setting CF02 to select how the RMX programmable power supply
starts when the POWER switch is turned on. Refer to Chapter 2, CF02 Power-on Status
Parameter, for more information about this setting.
1.Check that the power cord is connected correctly.
2.Check that the OUTPUT terminal cover is attached. Refer to the Attaching the Output
Terminal Cover section for more information about attaching the terminal cover. When the
product is shipped from the factory, the OUTPUT terminal cover is not attached.
3.Turn the POWER switch on. All the LEDs light, and then the voltmeter and the ammeter
display the following sequence of information: the rated voltage and rated current, the
firmware version number, the build number, and then the selected interface. Each item is
displayed for approximately 1 second. After a few seconds, the RMX programmable power
supply enters the operation standby state during which the output value is displayed.
1-6 | ni.com
RMX Programmable Power Supplies User Manual
Figure 1-5. Power On Information Display
Inrush Current
When the POWER switch is turned on, an inrush current of up to 70 A can momentarily flow
into the rear AC input of the programmable power supply. Check that sufficient current capacity
is available in the AC power line or the switchboard, particularly if you are using multiple RMX
programmable power supplies and turning on their POWER switches simultaneously.
Turning the POWER Switch Off
Flip the POWER switch to the side to turn RMX programmable power supplies off. The RMX
programmable power supplies save the panel settings (except the output on/off setting) that were
in use immediately before the POWER switch was turned off.
You can use CONFIG settings CF02 to select how the RMX programmable power supply starts
when the POWER switch is turned on. Refer to Chapter 2, CF02 Power-on Status Parameter,
for more information about this setting.
If the POWER switch is turned off immediately after the settings have been changed, the last
settings may not be stored.
Caution After you turn the POWER switch off, wait at least 10 seconds after the
panel display turns off before you turn the POWER switch back on. Repeatedly
turning the POWER switch on and off at short intervals can cause damage to the
inrush current limiter. Furthermore, this will shorten the service life of the POWER
switch and the internal input fuse.
You can use brackets or slide rails to mount the RMX programmable power supply to a rack.
When you mount an RMX programmable power supply to a rack, install the optional support
angles (NI P/N) to support the device.
NI recommends that you keep all pieces that you remove from a RMX programmable power
supply during installation. You will need these pieces if you remove the device from a rack.
When using several RMX programmable power supplies together for master-slave parallel or
series operation, mount them to a rack before use.
Load Considerations
Note The output can become unstable if the following types of loads are connected.
Loads with Peak Current or Pulse-Shaped Current
The front panel of the RMX power supply only displays averaged voltage and current values.
If the supply is connected to a load that draws current in spikes or pulses it is possible that the
front panel will display a current reading lower than the programmed current setpoint. In reality,
the spikes or pulses in the load current are exceeding the programmed current setpoint causing
the supply to switch instantaneously into constant-current mode and causing the output voltage
to drop.
For these types of loads, you must increase the set constant current or increase the current
capacity.
Figure 1-6. Loads with Peak Current or Pulse-Shaped Current
1-8 | ni.com
RMX Programmable Power Supplies User Manual
IO
RD
EO
Equivalent circuit of the RMX-4122
Regenerative load
+
0
Reverse current
-IO
+IO
Irp
RD (in Ω) ≤
RD: Reverse current bypass dummy load
E
O: Output voltage
Irp: Maximum reverse current
EO (in V)
Irp (in A)
Load
Output current
Loads that Generate Reverse Current to the Power Supply
RMX programmable power supplies cannot sink reverse current from the load. Therefore, if a
regenerative load (such as an inverter, converter, or transformer) is connected and tries to sink
power into the terminals of the power supply, the output voltage will increase and can become
unstable. This can cause a malfunction.
For these types of loads, connect a resistor (R
) as shown in the following figure to bypass the
D
reverse current. However, the amount of current to the load decreases by Irp.
Figure 1-7. Loads with Accumulated Energy
Caution Use a resistor with sufficient rated power for R
. If a resistor with
D
insufficient rated power for the circuit is used, the resistor will burn out.
Loads with Accumulated Energy
Connecting a load with accumulated energy, such as a battery, to an RMX programmable power
supply may cause current to flow from the load to the internal circuit. This current may cause
damage or reduce the life of the load.
For this type of load, connect a reverse-current-prevention diode (D
programmable power supply and the load in series as shown in the following figure.
) between the RMX
RP
This cannot be used in conjunction with remote sensing.
Caution To protect the load and the RMX programmable power supplies, use a D
RP
that conforms to the following specifications.
•Reverse voltage withstand capacity–At least twice the rated output voltage of the RMX
programmable power supply.
•Forward current capacity–Three to ten times the rated output current of the RMX
programmable power supply.
•A diode with small loss.
•Be sure to take into account the heat generated by D
. DRP will burn out with inadequate
RP
heat dissipation.
Load Cables
Caution Risk of fire. Use load cables whose capacity is adequate for the
RMX programmable power supply’s rated output current. The output connector and
its surrounding area become hot. Use cables whose covers have heat resistance at
85 °C and higher.
Caution Risk of electric shock. Use the cable which has higher withstanding
voltage than the specified insulation voltage of the product to secure the double
insulation or reinforced insulation.
The current capacity of a load cable is dependent on the maximum allowable temperature of the
cable's insulation.
A cable’s temperature is determined by the resistive loss based on the current, the ambient
temperature, and the cable’s external thermal resistance. The following table shows the current
capacity of heat-resistant vinyl wires that have a maximum allowable temperature of 60 °C,
assuming that a wire is stretched out horizontally in air in an ambient temperature of 30 °C.
The current capacity must be reduced under certain conditions, such as when vinyl cables that
have a low heat resistance are used, when the ambient temperature is 30 °C or greater, or when
cables are bundled together and little heat is radiated.
Table 1-1. Current Capacity of Heat-resistant Vinyl Wires
Nominal
Cross-sectional
Area
2 mm
3.5 mm
5.5 mm
1-10 | ni.com
2
2
2
AWG (Reference
Cross-sectional
Area)
Allowable
Current
(Ta = 30 °C)
Recommended
Current
14 (2.08 mm2)27 A10 A
12 (3.31 mm2)37 A—
10 (5.26 mm2)49 A20 A
RMX Programmable Power Supplies User Manual
Table 1-1. Current Capacity of Heat-resistant Vinyl Wires (Continued)
Nominal
Cross-sectional
Area
2
8 mm
2
14 mm
2
22 mm
2
30 mm
2
38 mm
2
50 mm
2
60 mm
2
80 mm
2
100 mm
2
125 mm
2
150 mm
2
200 mm
AWG (Reference
Cross-sectional
Area)
Allowable
Current
(Ta = 30 °C)
Recommended
Current
8 (8.37mm2)61 A30 A
6 (13.3 mm2)88 A50 A
4 (21.15 mm2)115 A80 A
2 (33.62 mm2)139 A—
1 (42.41 mm2)162 A100 A
1/0 (53.49 mm2)190 A—
2/0 (67.43 mm2)217 A—
3/0 (85.01 mm2)257 A200 A
4/0 (107.2 mm2)298 A—
—344 A—
—395 A300 A
—469 A—
Protecting Against Noise
When connecting wires that have the same heat resistance, separating the wires as much as
possible to increase heat radiation enables a greater amount of current to flow. However, wiring
the + (positive) and - (negative) output wires of the load cable side by side or bundling them
together will minimize unwanted noise on the output. The currents shown in Table 1-1 are
allowable currents that have been reduced in consideration of the potential bundling of load
cables. Use these values as a guideline when connecting load cables.
Cabling Considerations When Using Remote Sensing
As you increase the current setpoint or increase the resistance of your load cabling, the voltage
drop between the RMX power supply and your load will increase. This results in the voltage at
your load being smaller than the programmed voltage setpoint. Refer to Appendix A,
Specifications, to see the maximum voltage drop each RMX power supply's remote sense
terminals can compensate for. If the voltage drop exceeds this level, use shorter load cables or
cables with a greater cross-sectional area.
Caution Risk of electric shock. Turn the POWER switch off before you touch the
OUTPUT terminals. Even if you turn the output off or turn the POWER switch off,
if the bleeder on/off setting (CF11) is set to “OFF,” the voltage that was present when
the output was on will remain at the output terminals. Turn the bleeder circuit on
before you touch the output terminals. Regardless of whether load cables are
connected to the output terminals, be sure to attach the OUTPUT terminal cover
before turning the POWER switch on. Confirm that the voltage between any output
terminal and ground is lower than the isolation voltage of the RMX programmable
power supply.
Figure 1-9. RMX-4125 Output Terminal
1.Turn the POWER switch off. Check that there is no voltage across the output terminals.
2.Connect one end of the included chassis connection wire to the chassis terminal, and then
connect the other end of the wire to the negative or positive output terminal.
Note For safety reasons, connect one of the output terminals to the chassis terminal
unless your application requires the output terminals to be floating.
Use the screw on the RMX to connect the wire to the chassis terminal. Use the screw on the
output terminal to connect the wire to the output terminal.
1-12 | ni.com
RMX Programmable Power Supplies User Manual
Chassis
connection wire
Screw (M3)
Screw (M4)
Chassis
connection wire
Screw (M3)
Screw (M4)
Figure 1-10. RMX-4120/4121/4124/4125
Figure 1-11. RMX-4122/4123/4126/4127
3.Attach crimping terminals to the load cables.
The output terminals have holes for connecting the load cables. Use crimping terminals that
are appropriate for the bolts that you are using.
4.Use the included bolt set to connect the load cables to the output terminals.
Connect the positive cable to the positive output terminal and the negative cable to the
negative output terminal. The orientation of the crimping terminals will vary depending on
the wire diameter of the load cables used.
Attach the cable to the outer side
of the crimping terminal.
Spring washer
Washer
Nut
Bolt (M5)
Screw (M4)
Figure 1-12. Connection Using M8 Bolt Set for RMX-4120/4121/4124/4125
Figure 1-13. Connection Using M5 Bolt Set for RMX-4122/4123/4126/4127
Crimping terminal
Note If you do not connect load cables in the correct orientation, you will not be
able to attach the OUTPUT terminal cover.
1-14 | ni.com
RMX Programmable Power Supplies User Manual
R
line up the half of the cover.
Attaching the Output Terminal Cover
You can adjust the diameter of the holes that the load cables pass through by changing the
positions in which the top and bottom halves of the OUTPUT terminal cover are put together.
There are two available positions. Use the appropriate position for the load cables that you are using.
•For cables that are up to 10 mm in diameter: Put the top and bottom halves of the OUTPUT
terminal cover together so that the hole diameter is small.
•For cables that are between 10 mm and 18 mm in diameter: Put the top and bottom halves
of the OUTPUT terminal cover together so that the hole diameter is large.
1.Remove the screw that is attached next to the output terminals on the RMX. Use this screw
to attach the OUTPUT terminal cover.
2.Place the bottom half of the OUTPUT terminal cover underneath the load cables connected
to the output terminals.
Figure 1-14. Attaching Bottom Half of the OUTPUT Terminal Cover
emove the screws, and then
Note The top and bottom halves of the OUTPUT terminal cover have different
shapes.
3.Align the tabs of the top half of the OUTPUT terminal cover with those of the bottom half.
Align the tabs of the OUTPUT terminal cover according to the load cable diameter.
Align the protrusion of
the top half of the cover
with the top section
of the protrusion of the
bottom half.
Bottom half of the cover
For thick load cables
Cover hole diameter:
10 mm to 18 mm
Cover hole diameter:
Up to 10 mm
For thin load cables
Top half of the cover
Align the protrusion of
the top half of the cover
with the middle section
of the protrusion of the
bottom half of the cover.
Bottom half of the cover
Middle
section
Top section
After you have lined up the top and bottom halves
of the cover, use the screws to fix the cover in place.
Screws (M3)
Figure 1-15. Aligning Both Halves of the OUTPUT Terminal Cover
4.Push the OUTPUT terminal cover against the rear panel, and then use the RMX screws to
fix the cover in place. Ensure that the screws are securely fastened.
Figure 1-16. Attaching the OUTPUT Terminal Cover
1-16 | ni.com
RMX Programmable Power Supplies User Manual
Sensing
When RMX programmable power supplies are shipped from the factory, the connector is
attached to the sensing terminals. RMX programmable power supplies are supplied with a
connector cover that fits over the entire sensing, J1, and J2 connectors. For safety reasons,
be sure to attach the connector cover when you use the RMX programmable power supply.
If they are damaged or lost, contact National Instruments.
Figure 1-17. Connector Cover
Figure 1-18. Terminal Connector
Caution Risk of electric shock and damage to internal circuits.
Never wire the sensing terminals while the POWER switch is turned on.
Use sensing cables that provide reinforced or double insulation with a capacity
greater than or equal to the isolation voltage of the RMX programmable power
supply. For uncovered sections of the shielded cables, use insulation tubes to secure
reinforced or double insulation with a capacity greater than or equal to the isolation
voltage of the RMX programmable power supply.
The sensing terminals are at approximately the same electric potential as the negative
output terminal. Insert the cables so that the wire strands do not touch the chassis
when they stick out of the sensing terminal. Also, insert the cables so that the stripped
wires do not stick out of the terminal.
Strip 7 mm (0.28 inches) of the
cable covering, and then insert
the cable here.
Incorrect
Incorrect
Correct
The wire itself is
in contact with
the chassis.
Wire scraps are
in contact with
the chassis.
Strip gauge
7 mm (0.28 inches)
Use this screw to fix the cables
cables in place so that they do
not come loose.
Local sensing jumpers
Even if you turn the output off or turn the POWER switch off, if the bleeder on/off
setting (CF11) is set to oFF, the voltage that was present when the output was on will
remain at the output terminals. Set the bleeder on/off setting to on before you touch
the sensing terminals.
Regardless of whether local sensing or remote sensing is used, be sure to attach the
sensing terminal cover before turning the POWER switch on.
If the sensing cables come loose, the output voltage across the load may become unstable, and
an excessive voltage may be applied to the load. If an appropriate OVP trip point is set, the OVP
will trip before an excessive voltage is generated.
When you are finished with remote sensing, return to local sensing mode.
Figure 1-19. Sensing Cable Connections
TerminalFunction
-SNegative remote sensing terminal.
-LSNegative local sensing terminal connected to the negative output terminal
—Not connected.
+LSPositive local sensing terminal connected to the positive output terminal.
+SPositive remote sensing terminal.
Sensing cable: AWG28 to AWG16
1-18 | ni.com
Table 1-2. Sensing Terminals and Functions
RMX Programmable Power Supplies User Manual
+
–
+LS
+S
-LS
-S
Output terminal
Chassis terminal
Sensing terminal
RMX
Load
Use twisted-pair wires for the load cables.
Make the cables as short as possible.
Local Sensing
By factory default, RMX programmable power supplies are set to local sensing (the rear panel
sensing connector is hard wired). The sensing point during local sensing is the output terminal.
This method does not compensate for the voltage drop across the load cable, so use this method
when the load current is small or when you do not need to consider the load effect voltage.
Figure 1-20. Local Sensing
Remote Sensing
Remote sensing is a feature that reduces the effect of voltage drops across load cabling
resulting in a more accurate voltage being applied at the terminals of the load.
Refer to Appendix A, Specifications for the maximum voltage drop each RMX power supply's
remote sense terminals can compensate for. Select a load cable that has sufficient current
capacity to prevent the voltage drop in the load cable from exceeding the compensation voltage.
Refer to the Load Cables section for more information about the cables.
When using remote sensing, the output terminals compensate for the voltage drop across the load
cabling by increasing the output voltage above the programmed setpoint until the sense leads
detect the programmed setpoint at the load itself. This requires the output terminals to generate
a voltage that is greater than the programmed voltage level. If you are performing remote sensing
with the voltage close to the maximum output voltage of the power supply, the total output is
still limited by the maximum output voltage at the terminals of the power supply (105% of the
rated output voltage). If the signal doesn’t seem to be stable, an electrolytic capacitor may be
required at the sensing point (across the load).
To minimize noise on the output signal, use twisted-pair wires or 2-core shielded wires. Connect
the ground of your shielded wire to the ground of the RMX programmable power supply or the
load.
Use twisted-pair wires for the load cables.
Make the cables as short as possible.
+
+
Load
–
For the sensing cables, use twisted-pair
wires or shielded wires.
C
–
Connect an
electrolytic
capacitor
across the load
as necessary.
1.Turn the POWER switch off.
2.Remove the sensing connector from the rear panel sensing terminals.
3.Remove the local sensing jumpers from the sensing connector.
4.Remove 7 mm of the wire covering. Connect the negative sensing cable to -S and the
positive sensing cable to +S.
Use cable screws to securely fix the cables in place so that they do not come loose.
5.Pinch the tip of the band, and remove the band from the connector cover.
Figure 1-22. Bottom Cover with Band
6.As shown in the figure, create a ring 40 mm away from the connector, and fasten with the band.
Make the ring as small as possible, and fasten the band as tight as possible. The band can
be reused. Do not cut the extraneous portion of the band.
1-20 | ni.com
RMX Programmable Power Supplies User Manual
through the hole by holding this area with
a pair of tweezers.
Figure 1-23. Sensing Wire Assembly
40 mm
You can pull out the band that you passed
7.Firmly attach the sensing connector to the sensing terminals.
8.Fasten the lower side of the connector cover to the panel with the included screws, and then
insert the tip of the band into the hole of the cover. Finally, bring the top and bottom sides
of the connector cover together, and fasten with the included screws.
Connecting an Electrolytic Capacitor Across the Load
If the cabling is largely inductive, it may be necessary to connect an electrolytic capacitor across
the load. If you run into this problem, the following symptoms may appear:
•The output of the power supply is oscillating. If very long wires are used to connect the
load, the inductive and capacitive components of the cable can cause phase shifting that
results in oscillation at the output. You can reduce this effect by shortening the load cables.
However, if this does not rectify the problem, connect and electrolytic capacitor across the
load.
•If the load current is changing rapidly in a pulse-shaped pattern, the output voltage may
fluctuate due to inductance in the cabling. You can reduce the inductance component by
twisting the load cables, which stabilizes the voltage. However, if this does not rectify the
problem, connect an electrolytic capacitor across the load.
Table 1-3. Electrolytic Capacitor with RMX Programmable Power Supplies
RMX-4120
RMX-4124
RMX-4121/
RMX-4125
RMX-4122/
RMX-4126
RMX-4123/
RMX-4127
36 V or more96 V or more276 V or more780 V or more
Capacitance: 0.1 μF to a few hundred μF.
Withstand voltage: At least 120% of the rated output voltage of the RMX programmable
power supply.
Inserting a Mechanical Switch Between the RMX Programmable
Power Supply and the Load
If you want to connect and disconnect the load using a mechanical switch that is inserted
between the RMX programmable power supply and the load, be sure to include switches in the
sensing cables as shown in the following figure. Also make sure to turn on and off the load cable
and sensing cables simultaneously. Before you turn the mechanical switch on or off, be sure to
turn the output or the POWER switch off.
Figure 1-25. Mechanical Switch in a Sensing Cable
1-22 | ni.com
Loading...
+ 118 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.