National Instruments RMX-10051, RMX-10050 User Manual

USER GUIDE
RMX-10050/10051
Power Distribution Units
Overview
The RMX-10050/10051 are a series of Power Distribution Units (PDUs) installed in integrated test equipment platforms. Each PDU receives mains power through an inlet, and distributes that power to various outlets. Some models may include an output sequencing feature, additional DC power outputs, or a remote EPO feature. All models are constructed of a steel chassis and designed for fixed mounting within an EIA-310 compliant rack enclosure.
There are two single-phase and two three-phase PDUs. The following tables provide environmental ratings and feature information.
Table 1. RMX-10050/10051 Environmental Ratings (All Models)
Category Rating
Operational Maximum Altitude 3000 m
Operational Temperature Range 0 °C to 50 °C
Operational Humidity Range 5% to 85% relative humidity, noncondensing
Table 2. RMX PDU Family and Features
Product Model Part Number Included Features
Single Phase PDU with DC Output
Single Phase PDU RMX-10050 (785342-01) Remote EPO
Three Phase PDU (Wye) RMX-10051 (785344-01) DC Output, Remote EPO,
Three Phase PDU (Delta) RMX-10051 (785343-01) DC Output, Remote EPO,
RMX-10050 (785341-01) DC Output, Remote EPO,
Sequencing
Sequencing
Sequencing
The AC output voltages provided by each PDU are based on the mains voltage and the specific configuration. AC output ratings are also affected by the specific configuration.
Table 3. RMX-10050/10051 Input and AC Output Ratings
Product
RMX-10050 (785341-01) Single Phase with DC Output
RMX-10050 (785342-01) Single Phase
RMX-10051 (785344-01) Three Phase Wye 4P5W
RMX-10051 (785343-01) Three Phase Delta 3P4W
Mains Inlet
Connector
IEC 60320 C20 100-240 V~
IEC 60320 C20 100-240 V~
IEC 60309 ABL Sursum S51S30
IEC 60309 ABL Sursum S51S30
Mains Inlet
Rating
2P3W 16A 50/60 Hz
2P3W 16A 50/60 Hz
220/380­240/415 V~ L-L 4P5W 16A 50/60 Hz
200-208 V~ L-L 3P4W 16A 50/60 Hz
AC Output Ratings
C13: 100-240V~, 10 A max per receptacle Total AC output:
8.7 A max with DC fully loaded, 16 A max with DC disabled
C13: 100-240V~, 10 A max per receptacle Total AC output: 16 A max
C13: 220-240 V~, 10 A max per receptacle C19: 220-240 V~, 16 A max per receptacle Total AC output Group J3: 16 A max Group J2: 16 A max Group J1: 12.7 A max with DC fully loaded, 16 A max with DC disabled
C13: 200-208 V~, 10 A max per receptacle C19: 200-208 V~, 12.8 A max per receptacle Total AC output with balanced load Group J3: 9.2 A max Group J2: 9.2 A max Group J1: 5.6 A max with DC fully loaded,
9.2 A max with DC disabled
Note For the RMX-10051 (785344-01), the neutral pin in the inlet connector is not used.
2 | ni.com | RMX-10050/10051 User Guide
When the DC output feature is included, it draws power from the AC mains, and affects the available AC Output power. DC output ratings are shown in the following table.
Table 4. RMX-10050/10051 Family DC Output Ratings
DC
Channel
Power
Capacity
Voltage
RMX-10050 (785341-01)
Output
Rating
RMX-10051 (785344-01)
Output
Rating
RMX-10051 (785343-01)
Output
Rating
DC1 125 W 12 VDC 10.4 A max 12.5 A max 12.5 A max
DC2 125 W 24 VDC 5.2 A max 6.25 A max 6.25 A max
DC3 125 W 24 VDC 5.2 A max 6.25 A max 6.25 A max
DC4 125 W 48 VDC 2.6 A max 3.13 A max 3.13 A max
Note All models, except the RMX-10050 (785342-01), include a DC output
feature. The total DC Output is always limited to 500 W. This is divided evenly as 125 W per each of the four output channels.
Safety
This product is intended for indoor use only and should not be exposed to excess moisture.
This product is intended for installation in a restricted access location by a skilled person.
This product is intended for use by an instructed person.
This product is classified as pluggable equipment. The mains inlet plug serves as the disconnect device. The mains inlet plug shall be installed so that it is easily accessible.
This product is equipped with a safety ground connection through the mains inlet plug, as well as a redundant chassis ground screw on the rear panel. Ensure that the product is properly grounded before applying power.
Disconnect all power to the product prior to servicing.
Do no open this product as it contains no user serviceable parts inside. All service concerns should be directed to National Instruments.
The ratings for all output receptacles are marked on the top cover of the chassis. Be sure to observe the ratings for all connected load equipment.
If this product is used in a manner which does not comply with this instruction manual, the protection provided by the equipment may be impaired.
Hot Surface Contact with the top cover of chassis may cause burns. Ensure the
unit has cooled prior to handling.
RMX-10050/10051 User Guide | © National Instruments | 3