This document describes how to use the National Instruments 9481
and includes specifications and terminal assignments for the NI 9481.
Vis it ni.com/info and enter rdsoftwareversion to determine
which software you need for the modules you are using. For
information about installing, configuring, and programming the
system, refer to the system documentation. Visit
enter
cseriesdoc for information about C Series documentation.
Note The safety guidelines and specifications in this
ni.com/info and
document are specific to the NI 9481. The other
components in the system might not meet the same safety
ratings and specifications. Refer to the documentation for
each component in the system to determine the safety
ratings and specifications for the entire system. Visit
ni.com/info and enter cseriesdoc for information
about C Series documentation.
NI 9481 Operating Instructions and Specifications 2ni.com
Safety Guidelines
Operate the NI 9481 only as described in these operating
instructions.
Hot Surface This icon denotes that the component may be
hot. Touching this component may result in bodily injury.
Safety Guidelines for Hazardous Voltages
If hazardous voltages are connected to the module, take the
following precautions. A hazardous voltage is a voltage greater
than 42.4 V
performed only by qualified personnel adhering to local
electrical standards.
Caution Do not mix hazardous voltage circuits and
human-accessible circuits on the same module.
Caution Make sure that devices and circuits connected to
the module are properly insulated from human contact.
Caution When module terminals are hazardous voltage
LIVE (>42.4 V
/60 VDC), you must ensure that devices
pk
and circuits connected to the module are properly
insulated from human contact. You must use the NI 9932
connector backshell kit to ensure that the terminals are
not accessible.
Figure 1 shows the NI 9932 connector backshell.
Figure 1. NI 9932 Connector Backshell
NI 9481 Operating Instructions and Specifications 4ni.com
Safety Guidelines for Hazardous Locations
The NI 9481 is suitable for use in Class I, Division 2, Groups A, B,
C, D, T4 hazardous locations; Class I, Zone 2, AEx nC IIC T4
hazardous locations; and nonhazardous locations only. Follow
these guidelines if you are installing the NI 9481 in a potentially
explosive environment. Not following these guidelines may result
in serious injury or death.
Caution Do not disconnect I/O-side wires or connectors
unless power has been switched off or the area is known
to be nonhazardous.
Caution Do not remove modules unless power has been
switched off or the area is known to be nonhazardous.
Caution Substitution of components may impair
suitability for Class I, Division 2.
Caution For Zone 2 applications, install the system
in an enclosure rated to at least IP 54 as defined by
IEC 60529 and EN 60529.
Some modules are Lloyd’s Register (LR) Type Approved for
marine applications. To verify Lloyd’s Register certification, visit
ni.com/certification and search for the LR certificate, or
look for the Lloyd’s Register mark on the module.
Caution To meet radio frequency emission requirements
for marine applications, use shielded cables and install
the system in a metal enclosure. Suppression ferrites
must be installed on power supply inputs near power
entries to modules and controllers. Power supply and
module cables must be separated on opposite sides of the
enclosure and must enter and exit through opposing
enclosure walls.
NI 9481 Operating Instructions and Specifications 6ni.com
Connecting the NI 9481
The NI 9481 has a 10-terminal detachable screw-terminal connector
that provides connections for 4 electromechanical relay channels.
Each electromechanical relay channel has two interchangeable
terminals, CHa and CHb.
Each channel has an LED that indicates the state of the channel.
When a channel LED is lit, the channel is on. When the LED is
dark, the channel is off. The LEDs are disabled when the chassis
is in sleep mode. Refer to the Sleep Mode section for more
information about sleep mode.
When connecting a load to the NI 9481, connect the positive lead
of the load to either the CHa or the CHb terminal, and the ground
of the load to one of the leads of the power supply. Connect the
remaining CHa or CHb terminal to the other lead of the power
supply. Figure 3 shows a possible configuration.
CHa
+
or
Load
NI 9481
Figure 3. Connecting a Load to the NI 9481
NI 9481 Operating Instructions and Specifications 8ni.com
CHb
–
AC
Note Yo u must use 2-wire ferrules to create a secure
connection when connecting more than one wire to a
single terminal on the NI 9481.
When the channel is turned on, the terminal connected to the load
drives current or applies voltage to the load. When the channel is
off, the terminal does not drive current or apply voltage to the load.
Wiring for High-Vibration Applications
If an application is subject to high vibration, National Instruments
recommends that you either use ferrules to terminate wires to the
detachable screw-terminal connector or use the NI 9932 backshell
kit to protect the connections. Refer to Figure 4 for an illustration
of using ferrules. Refer to Figure 1 for an illustration of the
NI 9932 connector backshell.
Figure 4. 10-Terminal Detachable Screw-Terminal Connector with Ferrule
Sleep Mode
This module supports a low-power sleep mode. Support for sleep
mode at the system level depends on the chassis that the module is
plugged into. Refer to the chassis manual for information about
support for sleep mode. If the chassis supports sleep mode, refer to
the software help for information about enabling sleep mode. Visit
ni.com/info and enter cseriesdoc for information about
C Series documentation.
NI 9481 Operating Instructions and Specifications 10ni.com
Typically, when a system is in sleep mode, you cannot
communicate with the modules. In sleep mode, the system
consumes minimal power and may dissipate less heat than it does
in normal mode. Refer to the Specifications section for more
information about power consumption and thermal dissipation.
Specifications
The following specifications are typical for the range –40 to 70 °C
unless otherwise noted.
Output Characteristics
Number of channels.......................... 4 electromechanical relay
channels
Relay type ......................................... Single pole single throw
Power-on output state ....................... Channels off
If you need to clean the module, wipe it with a dry towel.
Screw-terminal wiring ...................... 12 to 24 AWG copper
conductor wire with 10 mm
(0.39 in.) of insulation
stripped from the end
Tor que for screw terminals ...............0.5 to 0.6 N · m
(4.4 to 5.3 lb · in.)
Ferrules ............................................. 0.25 mm
2
to 2.5 mm
2
Weight............................................... 150 g (5.3 oz)
Safety
Safety Voltages
Connect only voltages that are within the following limits.
CHa-to-CHb...................................... 250 V
Measurement Category II
Measurement Category II is for measurements performed on
circuits directly connected to the electrical distribution system.
This category refers to local-level electrical distribution, such as
NI 9481 Operating Instructions and Specifications 14ni.com
rms
max,
that provided by a standard wall outlet, for example, 115 V for U.S.
or 230 V for Europe.
Caution Do not connect the NI 9481 to signals or use
for measurements within Measurement Categories III
or IV.
Isolation
Channel-to-channel
Continuous ........................... 250 V
Withstand ............................. 1,400 V
rms
, verified by a 5 s
rms
dielectric withstand test
Channel-to-earth ground
Continuous ........................... 250 V
Withstand ............................. 2,300 V
rms
, verified by a 5 s
rms
dielectric withstand test
Hazardous Locations
U.S. (UL) .......................................... Class I, Division 2,
Refer to the product Declaration of Conformity (DoC) for
additional regulatory compliance information. To obtain product
certifications and the DoC for this product, visit ni.com/
certification
click the appropriate link in the Certification column.
To meet these specifications, you must panel mount the system and
either affix ferrules to the ends of the terminal wires or use the
NI 9932 backshell kit to protect the connections.
Operating vibration,
sinusoidal (IEC 60068-2-6) ..............5 g, 40 to 500 Hz; 0.062 in.
double amplitude,
10 to 40 Hz
Environmental
National Instruments C Series modules are intended for indoor use
only but may be used outdoors if installed in a suitable enclosure.
Refer to the manual for the chassis you are using for more
information about meeting these specifications.
Operating temperature
(IEC 60068-2-1, IEC 60068-2-2) .....–40 to 70 °C
Storage temperature
(IEC 60068-2-1, IEC 60068-2-2) .....–40 to 85 °C
Ingress protection.............................. IP 40
NI 9481 Operating Instructions and Specifications 18ni.com
Operating humidity
(IEC 60068-2-56).............................. 10 to 90% RH,
noncondensing
Storage humidity
(IEC 60068-2-56).............................. 5 to 95% RH,
noncondensing
Maximum altitude............................. 2,000 m
Pollution Degree (IEC 60664).......... 2
Environmental Management
NI is committed to designing and manufacturing products
in an environmentally responsible manner. NI recognizes that
eliminating certain hazardous substances from our products is
beneficial to the environment and to NI customers.
For additional environmental information, refer to the NI and the Environment Web page at ni.com/environment. This page
contains the environmental regulations and directives with which
NI complies, as well as other environmental information not
included in this document.
EU Customers At the end of the life cycle, all products
must be sent to a WEEE recycling center. For more
information about WEEE recycling centers and National
Instruments WEEE initiatives, visit
environment/weee
.
ni.com/
RoHS
ѻકЁ䰤ࠊՓ⫼ᶤѯ᳝ᆇ⠽䋼ᣛҸ
National Instruments
National InstrumentsЁRoHS
ni.com/environment/rohs_china
about China RoHS compliance, go to
environment/rohs_china
ヺড়Ё⬉ᄤֵᙃ
DŽ݇Ѣ
(RoHS)
ড়㾘ᗻֵᙃˈ䇋ⱏᔩ
DŽ
(For information
ni.com/
.)
NI 9481 Operating Instructions and Specifications 20ni.com
Where to Go for Support
The National Instruments Web site is your complete resource for
technical support. At
everything from troubleshooting and application development
self-help resources to email and phone assistance from
NI Application Engineers.
National Instruments corporate headquarters is located at
11500 North Mopac Expressway, Austin, Texas, 78759-3504.
National Instruments also has offices located around the world to
help address your support needs. For telephone support in the
United States, create your service request at
and follow the calling instructions or dial 512 795 8248. For
telephone support outside the United States, contact your local
branch office:
Australia 1800 300 800, Austria 43 662 457990-0,
Belgium 32 (0) 2 757 0020, Brazil 55 11 3262 3599,
Canada 800 433 3488, China 86 21 5050 9800,
Czech Republic 420 224 235 774, Denmark 45 45 76 26 00,
Finland 358 (0) 9 725 72511, France 01 57 66 24 24,
Germany 49 89 7413130, India 91 80 41190000,
Israel 972 3 6393737, Italy 39 02 41309277, Japan 0120-527196,
NI 9481 Operating Instructions and Specifications 22ni.com
National Instruments, NI, ni.com, and LabVIEW are trademarks of National Instruments Corporation. Refer to the
Terms of Use section on
product and company names mentioned herein are trademarks or trade names of their respective companies.
For patents covering National Instruments products/technology, refer to the appropriate location: Help»Patents
in your software, the