National Instruments FP-RLY-420 User Manual

OPERATING INSTRUCTIONS
FP-RLY-420
8-Channel, SPST Relay Module
These operating instructions describe the installation, features, and characteristics of the FP-RLY-420. For details on configuring and accessing the FP-RL Y-420 o ver a network, refer to the user manual for the particular FieldPoint network module you are using with the FP-RLY-420.

Features

The FP-RLY-420 is a FieldPoint relay output module with the following features:
Eight Single-Pole Single-Throw (SPST) relay channels
Switching capacity 3 A at 35 VDC or 250 VAC
On/Off LED indicators
Hot plug and play operation
3,000 V input to output isolation
Double insulated for 250 V safe working voltage
–40 to +70 °C operation

Power Requirement

The FP-RLY-420 is powered via the local backplane bus from the FieldPoint network module. The FP-RLY-420 is a high-power consumption module and requires more than the nominal power allocated to an I/O module from the network module. In some applications, this could limit the number of I/O modules that you can connect to a single network module.
When defining a FieldPoint system that uses an FP-RLY-420 module, you must calculate the power consumption. First refer to the specifications section in the user manual for your network
FieldPoint is a trademark of National Instruments Corporation. Product and company names mentioned herein are trademarks or trade names of their respective companies.
321904B-01 © Copyright 1998, 1999 National Instruments Corp. All rights reserved. June 1999
module. The maximum number of terminal bases per bank multiplied by 1 watt is the total power the network module can supply. For example, an FP-1000 or FP-1001 can support nine terminal bases (9*1 W = 9 W).
Next, refer to the specifications section in the operating instructions for the I/O modules. Use the Power from Network Module specification. For example, a bank of modules consisting of four FP-RL Y-420 and fi ve FP-DI-301 modules requires a total of
8.4 W from the FieldPoint network module [4*(1.7 W) + 5*(0.325 W) = 8.4 W]. This power requirement is less than the 9 W maximum and is therefore acceptable.

Installation

The FP-RLY-420 mounts on a FieldPoint terminal base (FP-TB-xx) unit. The hot plug and play operation of the FP-RLY-420 allows you to install it onto a powered terminal base without disturbing the operation of other modules or terminal bases. The FP-RLY-420 receives operating power from the terminal base.
T o install the FP-RLY-420, refer to Figure 1 and follow these steps:
1. Slide the terminal base key to either position X (used for any module) or position 7 (used for the FP-RLY-420 module).
2. Align the FP-RLY-420 alignment slots with the guide rails on the terminal base.
3. Press firmly to seat the FP-RLY-420 on the terminal base. The terminal base latch locks the FP-RLY-420 into place when it is firmly seated.
Key
Latch
Alignment
Slot
Guide Rails
Terminal BaseI/O Module
Figure 1.
FP-RLY-420 2 www.natinst.com
Module Installation Diagram

Field Wiring

The terminal base has connections for each of the eight relay channels and an external supply to po wer f ield de vices. Each relay channel of the FP-RLY-420 has two terminals: N.O. (Normally Open) and I.C. (Isolated Common). The external supply is not needed for the internal operation of the FP-RLY-420; however, you may connect an external supply to power field devices by connecting to the V and C terminals of the terminal base. If you connect an external supply to the V and C terminals, the total current supplied cannot exceed 6 A.
Table 1 lists the terminal assignments for the signals of each channel.
Table 1.
Chan-
nel
0 1 2 17 18 1 3 4 19 20 2 5 6 21 22 3 7 8 23 24 4 9 10 25 26 5 11 12 27 28 6 13 14 29 30 7 15 16 31 32
N.O. I.C.
Terminal Assignments
Terminal Numbers
V
sup
COM
© National Instruments Corp. 3 FP-RLY-420
Figures 2a and 2b show examples of basic wiring connections.
+
VC
a. Total Current Less
Than 6 Amps
V
N.O. I.C. COM
V N.O. I.C.
COM
sup
sup
Load
Load
N.O.
Load
I.C.
N.O.
I.C.
Load
b. Total Current Greater
Than 6 Amps
+
+

Figure 2. Basic Field Connection (Two Channels Shown)

Relay Output Circuit

The outputs of the FP-RLY-420 consist of Form A electromechanical relays. The power-up state is of f (open) to ensure safe installation. In the ON state, the N.O. and I.C. contacts connect together to form a short circuit. Choose the impedance of the loads so that the current switched b y any one channel in t he ON state is no more than 3 A.
In the ON state, there is an effectiv e resistance of 100 m between the N.O. and I.C. terminals, which causes a voltage drop. For example, if the current is 3 A, the voltage drop across the N.O. and I.C. terminals is 0.3 V.
FP-RLY-420 4 www.natinst.com
Figure 3 shows the diagram of one channel’s relay output circuit.
V
V
sup
N.O.
I.C. COM
C
Figure 3.
Relay Output Circuit
The maximum switching capacity of each relay is 3 A up to 250 VAC or 35 VDC. To switch greater DC voltages, refer to Figure 4.
3
2.5
Current (Amps)
2
1.5 1
.5
Safe Operating
Region
2004060
Figure 4.
Maximum Current vs. DC Volts
DC Volts
80 100 120

Contact Protection for Inductive Loads

When inductive loads are connected to the relays, a large counter-electromotive force may occur at relay switching time because of the energy stored in the inductive load. These flyback voltages can severely damage the relay contacts and greatly shorten the life of the relay.
It is best to limit these flyback voltages at your inductive load by installing, across your inductive load, a flyback diode for DC loads or a metal oxide varistor (MOV) for AC loads. Refer to the next section, Guidelines for Selecting Contact Protection Circuits, for more information.
© National Instruments Corp. 5 FP-RLY-420
In addition, the FP-RLY-420 contains its own internal protection MOV to prevent excessively high voltage from being applied across the contacts. The MOV is located between the N.O. and I.C. contacts of each relay, but National Instruments still recommends the use of a protection circuit across your inductive load.

Guidelines for Selecting Contact Protection Circuits

Proper selection is critical as the use of a contact-protection device can extend contact life. When mounting the protection device, always locate it near the immediate area of the load or contact. T ypically you should mount a protectiv e device within 18 in. of the load or contact.
T ypically , contact-protection circuits are provided for an ov erview, but you should thoroughly examine the circuit you are plann ing to use. For more specific information on any of these circuits, contact the Technical Services Department at American Zettler, Inc.

Diode and Zener Diode Circuit

Diagram Notes
1
Use in DC applications only. Use when diode circuit causes too long
release time.
Load
Use zener diode with zener voltage about equal to power supply voltage.
1
This section has been reprinted with permission from American Zettler, Inc.
FP-RLY-420 6 www.natinst.com

Diode Circuit

Diagram Notes
Use in DC applications only. Compared to RC type, circuit delays release
time (2 to 5 times values stated in catalog). For larger voltages, use diode with reverse
breakdown 10 times circuit voltage and forward load circuit.
Load
For smaller voltages, use reverse breakdown voltage of 2 to 3 times power supply voltage.

CR Circuits

Diagram Notes
Load
Load
Circuit A is suitable for AC or DC applications, but if used with AC voltage, impedance of the load should be smaller than the CR circuit’s. Do not utilize for timer loads, as leakage current can cause faulty operations.
Circuit B is suitable for AC or DC. If the load is a relay or solenoid, release times lengthen. Effective when connected to both contacts, power supply voltage across the load is 100 to 200 V.

Varistor Circuit

Diagram Notes
Effective for A C and DC applications.
Circuit slightly delays release time.
Load
Effective when connected to both contacts, power supply voltage across the load is 100 to 200 V.
© National Instruments Corp. 7 FP-RLY-420

In-Rush Current

The type of load and its in-rush current characteristics, together with switching frequency, can cause contact welding. For loads with in-rush current, measure the steady state current and in-rush current to determine the proper relay. Some typical types of loads and the in-rush current they create are summarized in the follo wing chart.
Type of Load In-Rush Current
Resistive load Steady-state current Solenoid load 10 to 20 times the steady-state current Motor load 5 to 10 times the steady-state current Incandescent lamp load 10 to 15 times the steady-state current Mercury lamp load Approximately 3 times the steady-state
Sodium vapor lamp load 1 to 3 times the steady-state current Capacitive load 20 to 40 times the steady-state current Transformer load 5 to 15 times the steady-state current
current

Status Indicators

Figure 5 shows the module label and status indicators. You can remove the insertable label to see wiring diagrams for the input channels.
Figure 5.
FP-RLY-420 8 www.natinst.com
Status Indicators and Module Label
After the module has been inserted into a terminal base (and power is applied), the green POWER indicator lights and the FP-RLY-420 informs the network module of its presence. When the network module recognizes the FP-RLY-420, the network module sends initial configuration information to the FP-RLY -42 0. After receiving this initial information, the green READY indicator lights and the FP-RLY-420 is in its normal operating mode. In addition to the green POWER and READY indicators, each channel has a numbered, green, output state indicator that lights when the channel is in the ON state.

Isolation and Safety Guidelines

Caution
attempting to connect ANY circuits that may contain hazardous voltages to the FP-RLY-420.
This section describes the isolation of the FP-RLY-420 and its compliance with international safety standards. The outputs are isolated from the backplane of the terminal base with an isolation barrier designed and tested to protect against fault voltages of up to 3000 Vrms. In addition, the FP-RLY-420 provides double insulation (compliant to UL and IEC safety standards) for working common-mode voltages of 250 Vrms. Safety standards (such as those published by UL and IEC) require the use of double insulation between hazardous voltages and any human-accessible parts or circuits. You should never attempt to use any isolation product between human-accessible parts (such as DIN rails or monitoring stations) and circuits that may be at hazardous potentials under normal conditions, unless the product is specifically designed (as the FP-RLY-420 is) for such an application.
Even when a product like the FP-RLY-420 is used in applications with hazardous potentials, follow these guidelines to ensure a safe total system:
The safe ty isolation of the FP-RLY-420 is from input to output, not between channels on the same module. If any of the channels on a module are wired at a hazardous potential, ensure that all other devices or circuits connected to that module are properly insulated from human contact.
Read the following information before
© National Instruments Corp. 9 FP-RLY-420
•Do not share the external supply voltages (V and C on the terminal base) with other devices (including other FieldPoint devices) unless those devices are also isolated from human contact.
As with any hazardous voltage wiring, ensure that all wiring and connections meet with applicable electrical codes or common sense practices. Mount terminal bases in an area, position, or cabinet that prevents accidental or unauthorized access to wiring with hazardous voltages.
The isolation of the FP-RLY-420 is certified as double insulated for normal operating voltages of 250 Vrms. Do not use the FP-RLY-420 as the sole isolating barrier between human contact and working voltages of more than 250 Vrms.

Specifications

The following specifications are typical for the range –40 to +70 °C, unless otherwise noted.
Input Characteristics
Number of channels..........................8
Relay type.........................................1 Form A (SPST)
Nonlatching
Maximum Switching Capacity (Resistive Load)
AC ..............................................3 A at 250 VAC
DC ..............................................3 A at 35 VDC
2 A at 40 VDC 1 A at 55 VDC
0.4 A at 120 VDC
Note
Above 55 °C ambient, max. 1.5 A per channel.
Minimum switching voltage.............10 mA at 5 VDC
On resistance.....................................100 m
Off state leakage ...............................0.3 µA at 250 VAC
Expected Life
Mechanical .................................20 × 106 operations min.
Electrical (at 30 cpm)................. 300,000 operations at 3 A,
35 VDC 100,000 operations at 3 A, 250 VAC
FP-RLY-420 10 www.natinst.com
Maximum switching frequency
Mechanical .................................20 operations per second
Electrical.....................................1 operation per second at
maximum load
Relays operate time...........................6 ms typical, 8 ms max.
Relays release time ...........................3 ms typical, 4 ms max.
Relay bounce time ............................3 ms max.
Contact material................................ Gold-plated silver cadmium
oxide
Isolation (CH–GND and CH–CH)....3,000 Vrms
Safety isolation, working voltage
(CH–GND only) ...............................250 Vrms, designed per IEC
1010 as double insulated
Physical
Indicators ..........................................Green POWER and
Weight...............................................160 g (5.6 oz.)
READY indicators, 8 green
output state indicators
Power Requirements
Power from network module............1700 mW
Environment
Operating temperature......................–40 to +70 °C
Storage temperature..........................–55 to +100 °C
Relative humidity..............................5% to 90% noncondensing
CE Mark Compliance
This product meets applicable EU directive(s) as follows:
Safety isolation .................................EN 61010 (double insulation
EMC Directive
Immunity.................................... EN 50082-1:1994
Emissions ...................................EN 55011:1991 Group I
© National Instruments Corp. 11 FP-RLY-420
for 250 Vrms working
isolation, installation
category II)
Class A at 10 m
Mechanical Dimensions
Figure 6 shows the mechanical dimensions of the FP-RLY-420 installed onto a terminal base. Dimensions are given in inches [millimeters].
4.22 [107.19]
4.31
[109.5]
3.60 [91.44]
Figure 6.
Mechanical Dimensions
Loading...