These operating instructions describe how to install and use the
FP-AI-110 and cFP-AI-110 analog input modules (referred to
inclusively as the [c]FP-AI-110). For information about
configuring and accessing the [c]FP-AI-110 over a network, refer
to the user manual for the FieldPoint network module you are
using.
Features
The [c]FP-AI-110 is a FieldPoint analog input module with the
following features:
•Eight analog voltage or current input channels
•Eight voltage input ranges: 0–1 V, 0–5 V, 0–10 V, ±60 mV, ±300 mV, ±1V, ±5V, and ±10 V
•Three current input ranges: 0–20, 4 –20, and ±20 mA
•16-bit resolution
•Three filter settings: 50, 60, and 500 Hz
•250 V
verified by 2,300 V
•–40 to 70 °C operation
•Hot swappable
CAT II continuous channel-to-ground isolation,
rms
dielectric withstand test
rms
Installing the FP-AI-110
The FP-AI-110 mounts on a FieldPoint terminal base (FP-TB-x),
which provides operating power to the module. Installing the
FP-AI-110 onto a powered terminal base does not disrupt the
operation of the FieldPoint bank.
To install the FP-AI-110, refer to Figure 1 and complete the
following steps:
1. Slide the terminal base key to either position X (used for any
module) or position 1 (used for the FP-AI-110).
2. Align the FP-AI-110 alignment slots with the guide rails on the
terminal base.
3. Press firmly to seat the FP-AI-110 on the terminal base. When
the FP-AI-110 is firmly seated, the latch on the terminal base
locks it into place.
4
5
3
6
1 I/O Module
2 Terminal Base
3 Alignment Slot
1
4Key
5Latch
6 Guide Rails
Figure 1. Installing the FP-AI-110
2
Installing the cFP-AI-110
The cFP-AI-110 mounts on a Compact FieldPoint backplane
(cFP-BP-x), which provides operating power to the module.
Installing the cFP-AI-110 onto a powered backplane does not
disrupt the operation of the FieldPoint bank.
To install the cFP-AI-110, refer to Figure 2 and complete the
following steps:
1. Align the captive screws on the cFP-AI-110 with the holes on
the backplane. The alignment keys on the cFP-AI-110 prevent
backward insertion.
2. Press firmly to seat the cFP-AI-110 on the backplane.
3. Using a number 2 Phillips screwdriver with a shank of at least
64 mm (2.5 in.) length, tighten the captive screws to 1.1 N ⋅ m
FP-AI-110 and cFP-AI-1102ni.com
(10 lb ⋅ in.) of torque. The nylon coating on the screws prevents
them from loosening.
The FP-TB-x terminal base has connections for each of the eight
input channels and for an external power supply to power field
devices. The cFP-CB-x connector block provides the same
connections. Each channel has separate input terminals for voltage
(V
) and current (IIN) input. Voltage and current inputs are
IN
referenced to the COM terminals, which are internally connected
to each other and to the C terminals. All eight V
terminals are
SUP
internally connected to each other and to the V terminals.
You can use a 10 –30 VDC external supply to power field devices.
Connect the external power supply to multiple V and V
SUP
terminals so that the maximum current through any V terminal
is 2 A or less and the maximum current through any V
terminal
SUP
is 1 A or less.
Install a 2 A maximum, fast-acting fuse between the external
power supply and the V terminal on each channel. The wiring
diagrams in this document show fuses where appropriate.
Table 1 lists the terminal assignments for the signals associated
with each channel. The terminal assignments are the same for the
FP-TB-x terminal bases and the cFP-CB-x connector blocks.
Table 1. Terminal Assignments
Terminal Numbers
1
Channel
V
IN
0121718
1341920
2562122
3782324
49102526
511122728
613142930
715163132
1
Install a 2 A, fast-acting fuse on each VIN terminal.
2
Install a 2 A, fast-acting fuse on each IIN terminal.
3
Install a 2 A maximum, fast-acting fuse on each V
2
I
IN
V
SUP
SUP
3
terminal.
COM
Caution Do not connect both current and voltage inputs
to the same channel.
Caution Cascading power between two modules defeats
isolation between those modules. Cascading power from
the network module defeats all isolation between
modules in the FieldPoint bank.
FP-AI-110 and cFP-AI-1104ni.com
Taking Measurements
with the [c]FP-AI-110
The [c]FP-AI-110 has eight single-ended input channels. All eight
channels share a common ground reference that is isolated from
other modules in the FieldPoint system. Figure 3 shows the analog
input circuitry on one channel.
V
SUP
V
COM
IN
I
IN
Filter
Filter
V
16-Bit
Isolated ADC
C
Figure 3. FP-AI-110 Analog Input Circuit
Measuring Voltage with the [c]FP-AI-110
The input ranges for voltage signals are 0–1 V, 0–5 V, 0–10 V,
±60 mV, ±300 mV, ±1V, ±5 V, and ±10 V.
Figure 4 shows how to connect a voltage source without an
external power supply to one channel of the [c]FP-AI-110.
VC
Voltage
Source
V
SUP
V
IN
I
IN
+
–
COM
To Analog
Input Circuitry
>100 MΩ
Input
Impedance
To Next Channel
[c]FP-AI-110
Figure 4. Voltage Source without External Power Supply
Figure 5 shows how to connect a voltage source with an external
power supply to one channel of the [c]FP-AI-110.
Powered
Voltage
Transducer
+
OUT
–
1 A
Max
V
SUP
V
COM
IN
I
IN
10–30 VDC
External
Power Supply
(Optional)
To Analog
Input Circuitry
[c]FP-AI-110
+
–
To Next Channel
2 A
Max
VC
Figure 5. Voltage Source with External Power Supply
Measuring Current with the [c]FP-AI-110
The input ranges for current sources are 0–20, 4–20, and ±20 mA.
The module reads current flowing into the I
and current flowing out of the terminal as negative. Current flows
into the I
terminal, goes through a 100 Ω resistor, and flows out
IN
from the COM or C terminal.
Figure 6 shows how to connect a current source without an external
power supply to one channel of the [c]FP-AI-110.
terminal as positive
IN
FP-AI-110 and cFP-AI-1106ni.com