National Instruments FieldPoint FP-DI-330, FieldPoint cFP-DI-330 Operating Instructions Manual

FieldPoint™ Operating Instructions
FP-DI-330 and cFP-DI-330
Eight-Channel Universal Digital Input Module
These operating instructions describe how to install and use the National Instruments FP-DI-330 and cFP-DI-330 digital input modules (referred to inclusively as the [c]FP-DI-330). For information about configuring and accessing the [c]FP-DI-330 over a network, refer to the user manual for the FieldPoint network module you are using.

Features

The [c]FP-DI-330 is a FieldPoint digital input module with the following features:
Eight digital input channels
Universal inputs that work with any voltage from 5 V TTL level up to 250 VDC/VAC
Compatibility with sourcing, sinking, or power-sensing applications
On/Off LED indicators
250 V verified by 2,300 V
–40 to 70 °C operation
Hot swappable
CAT II continuous channel-to-ground isolation,
rms
, 1 minute dielectric withstand test
rms

Installing the FP-DI-330

The FP-DI-330 mounts on a FieldPoint terminal base (FP-TB-x), which provides operating power to the module. Installing the FP-DI-330 onto a powered terminal base does not disrupt the operation of the bank.
To install the FP-DI-330, refer to Figure 1 and complete the following steps:
1. Slide the terminal base key to position X.
2. Align the FP-DI-330 alignment slots with the guide rails on the terminal base.
3. Press firmly to seat the FP-DI-330 on the terminal base. When the module is firmly seated, the terminal base latch locks it into place.
4
5
3
6
1
1 I/O Module 2 Terminal Base 3 Alignment Slot
4Key 5 Latch 6 Guide Rails

Figure 1. Installing the FP-DI-330

2

Installing the cFP-DI-330

The cFP-DI-330 mounts on a Compact FieldPoint backplane (cFP-BP-x), which provides operating power to the module. Installing the cFP-DI-330 onto a powered backplane does not disrupt the operation of the bank.
To install the cFP-DI-330, refer to Figure 2 and complete the following steps:
1. Align the captive screws on the cFP-DI-330 with the holes on the backplane. The alignment keys on the cFP-DI-330 prevent backward insertion.
2. Press firmly to seat the cFP-DI-330 on the backplane.
3. Using a number 2 Phillips screwdriver with a shank of at least 64 mm (2.5 in.) length, tighten the captive screws to 1.1 N ⋅ m
FP-DI-330 and cFP-DI-330 2 ni.com
(10 lb in.) of torque. The nylon coating on the screws prevents them from loosening.
3 5
2
2
1
1 cFP I/O Module 2 Captive Screws 3 cFP Controller Module

Figure 2. Installing the cFP-DI-330

4
4
4 Screw Holes 5 cFP Backplane

Wiring the [c]FP-DI-330

The FP-TB-x terminal base has connections for each FP-DI-330 input channel and for an external supply to power field devices. The cFP-CB-x connector block provides the same connections for the cFP-DI-330. You can wire each channel to a switch, a sourcing-output device, a sinking-output device, or a load.
Each channel has two input terminals, IN terminal, V
; and a common terminal, COM. All eight COM
SUP
terminals are internally connected to each other and to the C terminals. All eight V
terminals are internally connected to
SUP
each other and to the V terminals.
and INb; a supply
a
© National Instruments Corp. 3 FP-DI-330 and cFP-DI-330
You can use a 5–250 VDC external power supply to power field devices. Connect the positive lead of the external power supply to both V terminals and the negative lead to both C terminals. Ensure that the current through both V terminals can never exceed 2 A.
Install 2 A maximum, fast-acting fuses between the external power supply and the V terminals. The wiring diagrams in this document show fuses where appropriate.
Table 1 lists the terminal assignments for the signals associated with each channel. The terminal assignments are the same for the FP-TB-x terminal bases and the cFP-CB-x connector blocks.

Table 1. Terminal Assignments

Terminal Numbers
Channel
0 1 2 17 18
1 3 4 19 20
2 5 6 21 22
3 7 8 23 24
4 9 10 25 26
5 11 12 27 28
6 13 14 29 30
7 15 16 31 32
IN
a
IN
b
V
SUP
COM
If you are using the cFP-DI-330 in a hazardous voltage application, you must use the cFP-CB-1 connector block or a suitable hazardous voltage cable. A hazardous voltage is a voltage greater than 42.4 V
Caution Ensure that hazardous voltage wiring is
or 60 VDC.
peak
performed only by qualified personnel adhering to local electrical standards.
Caution Do not mix circuits with hazardous voltages and
human-accessible circuits on the same module.
Caution Cascading power between two modules defeats
isolation between those modules. Cascading power from the network module defeats all isolation between modules in the FieldPoint bank.
FP-DI-330 and cFP-DI-330 4 ni.com

Connecting Devices to the [c]FP-DI-330

Figure 3 shows how to connect several types of devices to channels of the [c]FP-DI-330. Devices connected to V common potential.
2 A
Max
V
SUP
IN
(Ch 1)
IN
IN
IN
IN
IN
IN
IN
a
(Ch 1)
b
COM
V
(Ch 2)
a
(Ch 2)
b
COM
V
(Ch 3)
a
(Ch 3)
b
COM
V
(Ch 4)
a
(Ch 4)
b
COM
SUP
SUP
SUP
Input
Circuitry
Input
Circuitry
Input
Circuitry
Input
Circuitry
Sinking-
+
Output
Device
(NPN)
Sourcing-
Output
+
Device
(PNP)
Sinking-
Output Device (NPN)
Sourcing-
Output Device (PNP)
and COM share a
SUP
+
VC
Power Supply
5–250 V
External
V
SUP
(Ch n)
IN
Switch
IN
a
(Ch n)
b
COM
Input
Circuitry
To Next Channel
[c]FP-DI-330

Figure 3. Connecting Devices to the [c]FP-DI-330

© National Instruments Corp. 5 FP-DI-330 and cFP-DI-330