These operating instructions describe how to install and use the
FP-AI-110 and cFP-AI-110 analog input modules (referred to
inclusively as the [c]FP-AI-110). For information about
configuring and accessing the [c]FP-AI-110 over a network, refer
to the user manual for the FieldPoint network module you are
using.
Features
The [c]FP-AI-110 is a FieldPoint analog input module with the
following features:
•Eight analog voltage or current input channels
•Eight voltage input ranges: 0–1 V, 0–5 V, 0–10 V, ±60 mV, ±300 mV, ±1V, ±5V, and ±10 V
•Three current input ranges: 0–20, 4–20, and ±20 mA
•16-bit resolution
•Three filter settings: 50, 60, and 500 Hz
•250 V
verified by 2,300 V
•–40 to 70 °C operation
•Hot swappable
CAT II continuous channel-to-ground isolation,
rms
dielectric withstand test
rms
Installing the FP-AI-110
The FP-AI-110 mounts on a FieldPoint terminal base (FP-TB-x),
which provides operating power to the module. Installing the
FP-AI-110 onto a powered terminal base does not disrupt the
operation of the FieldPoint bank.
To install the FP-AI-110, refer to Figure 1 and complete the
following steps:
1.Slide the terminal base key to either position X (used for any
module) or position 1 (used for the FP-AI-110).
2.Align the FP-AI-110 alignment slots with the guide rails on the
terminal base.
3.Press firmly to seat the FP-AI-110 on the terminal base. When
the FP-AI-110 is firmly seated, the latch on the terminal base
locks it into place.
4
5
3
6
1
1I/O Module
2Terminal Base
3Alignment Slot
4Key
5Latch
6Guide Rails
Figure 1. Installing the FP-AI-110
2
Installing the cFP-AI-110
The cFP-AI-110 mounts on a Compact FieldPoint backplane
(cFP-BP-x), which provides operating power to the module.
Installing the cFP-AI-110 onto a powered backplane does not
disrupt the operation of the FieldPoint bank.
To install the cFP-AI-110, refer to Figure 2 and complete the
following steps:
1.Align the captive screws on the cFP-AI-110 with the holes on
the backplane. The alignment keys on the cFP-AI-110 prevent
backward insertion.
2.Press firmly to seat the cFP-AI-110 on the backplane.
3.Using a number 2 Phillips screwdriver with a shank of at least
64 mm (2.5 in.) length, tighten the captive screws to 1.1 N ⋅ m
FP-AI-110 and cFP-AI-1102ni.com
(10 lb ⋅ in.) of torque. The nylon coating on the screws prevents
them from loosening.
The FP-TB-x terminal base has connections for each of the eight
input channels and for an external power supply to power field
devices. The cFP-CB-x connector block provides the same
connections. Each channel has separate input terminals for voltage
(V
) and current (IIN) input. Voltage and current inputs are
IN
referenced to the COM terminals, which are internally connected
to each other and to the C terminals. All eight V
internally connected to each other and to the V terminals.
terminals are
SUP
You can use a 10–30 VDC external supply to power field devices.
Connect the external power supply to multiple V and V
terminals so that the maximum current through any V terminal
is 2 A or less and the maximum current through any V
terminal
SUP
is 1 A or less.
Install a 2 A maximum, fast-acting fuse between the external
power supply and the V terminal on each channel. The wiring
diagrams in this document show fuses where appropriate.
Table 1 lists the terminal assignments for the signals associated
with each channel. The terminal assignments are the same for the
FP-TB-x terminal bases and the cFP-CB-x connector blocks.
Table 1. Terminal Assignments
Terminal Numbers
Channel
V
IN
1
2
I
IN
V
0121718
1341920
2562122
3782324
49102526
511122728
613142930
715163132
1
Install a 2 A, fast-acting fuse on each VIN terminal.
2
Install a 2 A, fast-acting fuse on each IIN terminal.
3
Install a 2 A maximum, fast-acting fuse on each V
CautionDo not connect both current and voltage inputs
to the same channel.
SUP
SUP
3
terminal.
COM
CautionCascading power between two modules defeats
isolation between those modules. Cascading power from
the network module defeats all isolation between
modules in the FieldPoint bank.
FP-AI-110 and cFP-AI-1104ni.com
Taking Measurements
with the [c]FP-AI-110
The [c]FP-AI-110 has eight single-ended input channels. All eight
channels share a common ground reference that is isolated from
other modules in the FieldPoint system. Figure 3 shows the analog
input circuitry on one channel.
V
V
SUP
V
I
COM
IN
IN
Filter
16-Bit
Isolated ADC
Filter
C
Figure 3. FP-AI-110 Analog Input Circuit
Measuring Voltage with the [c]FP-AI-110
The input ranges for voltage signals are 0–1 V, 0–5 V, 0–10 V,
±60 mV, ±300 mV, ±1V, ±5 V, and ±10 V.
Figure 4 shows how to connect a voltage source without an
external power supply to one channel of the [c]FP-AI-110.
VC
V
SUP
To Analog
Input Circuitry
>100 MΩ
Input
Impedance
Voltage
Source
V
IN
I
+
–
IN
COM
Figure 4. Voltage Source without External Power Supply