FieldPoint™ Operating Instructions
FP-AI-110 and cFP-AI-110
Eight-Channel, 16-Bit Analog Input Modules
These operating instructions describe how to install and use the FP-AI-110 and cFP-AI-110 analog input modules (referred to inclusively as the [c]FP-AI-110). For information about configuring and accessing the [c]FP-AI-110 over a network, refer to the user manual for the FieldPoint network module you are using.
Features
The [c]FP-AI-110 is a FieldPoint analog input module with the following features:
Eight analog voltage or current input channels
Eight voltage input ranges: 0–1 V, 0–5 V, 0–10 V, ±60 mV, ±300 mV, ±1V, ±5V, and ±10 V
Three current input ranges: 0–20, 4–20, and ±20 mA
16-bit resolution
Three filter settings: 50, 60, and 500 Hz
250 V verified by 2,300 V
–40 to 70 °C operation
Hot swappable
CAT II continuous channel-to-ground isolation,
rms
dielectric withstand test
rms
Installing the FP-AI-110
The FP-AI-110 mounts on a FieldPoint terminal base (FP-TB-x), which provides operating power to the module. Installing the FP-AI-110 onto a powered terminal base does not disrupt the operation of the FieldPoint bank.
To install the FP-AI-110, refer to Figure 1 and complete the following steps:
1. Slide the terminal base key to either position X (used for any module) or position 1 (used for the FP-AI-110).
2. Align the FP-AI-110 alignment slots with the guide rails on the terminal base.
3. Press firmly to seat the FP-AI-110 on the terminal base. When the FP-AI-110 is firmly seated, the latch on the terminal base locks it into place.
4
5
3
6
1
1 I/O Module 2 Terminal Base 3 Alignment Slot
4Key 5Latch 6 Guide Rails
Figure 1. Installing the FP-AI-110
2
Installing the cFP-AI-110
The cFP-AI-110 mounts on a Compact FieldPoint backplane (cFP-BP-x), which provides operating power to the module. Installing the cFP-AI-110 onto a powered backplane does not disrupt the operation of the FieldPoint bank.
To install the cFP-AI-110, refer to Figure 2 and complete the following steps:
1. Align the captive screws on the cFP-AI-110 with the holes on the backplane. The alignment keys on the cFP-AI-110 prevent backward insertion.
2. Press firmly to seat the cFP-AI-110 on the backplane.
3. Using a number 2 Phillips screwdriver with a shank of at least 64 mm (2.5 in.) length, tighten the captive screws to 1.1 N ⋅ m
FP-AI-110 and cFP-AI-110 2 ni.com
(10 lb in.) of torque. The nylon coating on the screws prevents them from loosening.
3 5
2
2
4
4
1
1cFP-DI-300 2Captive Screws 3 cFP Controller Module
Figure 2. Installing the cFP-AI-110
4 Screw Holes 5cFP Backplane
Wiring the [c]FP-AI-110
The FP-TB-x terminal base has connections for each of the eight input channels and for an external power supply to power field devices. The cFP-CB-x connector block provides the same connections. Each channel has separate input terminals for voltage (V
) and current (IIN) input. Voltage and current inputs are
IN
referenced to the COM terminals, which are internally connected to each other and to the C terminals. All eight V internally connected to each other and to the V terminals.
terminals are
SUP
You can use a 10–30 VDC external supply to power field devices. Connect the external power supply to multiple V and V terminals so that the maximum current through any V terminal
© National Instruments Corp. 3 FP-AI-110 and cFP-AI-110
SUP
is 2 A or less and the maximum current through any V
terminal
SUP
is 1 A or less.
Install a 2 A maximum, fast-acting fuse between the external power supply and the V terminal on each channel. The wiring diagrams in this document show fuses where appropriate.
Table 1 lists the terminal assignments for the signals associated with each channel. The terminal assignments are the same for the FP-TB-x terminal bases and the cFP-CB-x connector blocks.
Table 1. Terminal Assignments
Terminal Numbers
Channel
V
IN
1
2
I
IN
V
0 1 2 17 18
1 3 4 19 20
2 5 6 21 22
3 7 8 23 24
4 9 10 25 26
5 11 12 27 28
6 13 14 29 30
7 15 16 31 32
1
Install a 2 A, fast-acting fuse on each VIN terminal.
2
Install a 2 A, fast-acting fuse on each IIN terminal.
3
Install a 2 A maximum, fast-acting fuse on each V
Caution Do not connect both current and voltage inputs
to the same channel.
SUP
SUP
3
terminal.
COM
Caution Cascading power between two modules defeats
isolation between those modules. Cascading power from the network module defeats all isolation between modules in the FieldPoint bank.
FP-AI-110 and cFP-AI-110 4 ni.com
Taking Measurements with the [c]FP-AI-110
The [c]FP-AI-110 has eight single-ended input channels. All eight channels share a common ground reference that is isolated from other modules in the FieldPoint system. Figure 3 shows the analog input circuitry on one channel.
V
V
SUP
V
I
COM
IN
IN
Filter
16-Bit
Isolated ADC
Filter
C
Figure 3. FP-AI-110 Analog Input Circuit
Measuring Voltage with the [c]FP-AI-110
The input ranges for voltage signals are 0–1 V, 0–5 V, 0–10 V, ±60 mV, ±300 mV, ±1V, ±5 V, and ±10 V.
Figure 4 shows how to connect a voltage source without an external power supply to one channel of the [c]FP-AI-110.
VC
V
SUP
To Analog
Input Circuitry
>100 M Input Impedance
Voltage
Source
V
IN
I
+
IN
COM
Figure 4. Voltage Source without External Power Supply
© National Instruments Corp. 5 FP-AI-110 and cFP-AI-110
To Next Channel
[c]FP-AI-110
Figure 5 shows how to connect a voltage source with an external power supply to one channel of the [c]FP-AI-110.
Powered
Voltage
Transducer
+
OUT
1 A
Max
V
SUP
V
I
COM
IN
IN
10–30 VDC
External
Power Supply
(Optional)
To Analog
Input Circuitry
To Next Channel
[c]FP-AI-110
+
Figure 5. Voltage Source with External Power Supply
Measuring Current with the [c]FP-AI-110
2 A
Max
VC
The input ranges for current sources are 0–20, 4 –20, and ±20 mA. The module reads current flowing into the I
terminal as positive
IN
and current flowing out of the terminal as negative. Current flows into the I
terminal, goes through a 100 resistor, and flows out
IN
from the COM or C terminal.
Figure 6 shows how to connect a current source without an external power supply to one channel of the [c]FP-AI-110.
FP-AI-110 and cFP-AI-110 6 ni.com