National Instruments 9403 Getting Started Manual

GETTING STARTED GUIDE
NI 9403
32 DIO, 5 V/TTL, Bidirectional, 7 μs
This document explains how to connect to the NI 9403.
Note Before you begin, complete the software and
hardware installation procedures in your chassis documentation.
Note The guidelines in this document are specific to

Safety Guidelines

Operate the NI 9403 only as described in this document.
Caution Do not operate the NI 9403 in a manner not
specified in this document. Product misuse can result in a hazard. You can compromise the safety protection built into the product if the product is damaged in any way. If the product is damaged, return it to NI for repair.
2 | ni.com | NI 9403 Getting Started Guide

Safety Voltages

Connect only voltages that are within the following limits:
Channel-to-COM ±30 V maximum on up to
8 channels at a time, Measurement Category I
Isolation
Channel-to-channel None
Channel-to-earth ground
Continuous 60 VDC, Measurement
Category I
Withstand
up to 3,000 m altitude 1,000 Vrms, verified by a 5 s
dielectric withstand test
up to 5,000 m altitude 860 Vrms, verified by a 5 s
dielectric withstand test
Measurement Category I is for measurements performed on circuits not directly connected to the electrical distribution system referred to as MAINS voltage. MAINS is a hazardous live
NI 9403 Getting Started Guide | © National Instruments | 3
electrical supply system that powers equipment. This category is for measurements of voltages from specially protected secondary circuits. Such voltage measurements include signal levels, special equipment, limited-energy parts of equipment, circuits powered by regulated low-voltage sources, and electronics.
Caution Do not connect the NI 9403 to signals or use
for measurements within Measurement Categories II, III, or IV.

Safety Guidelines for Hazardous Locations

The NI 9403 is suitable for use in Class I, Division 2, Groups A, B, C, D, T4 hazardous locations; Class I, Zone 2, AEx nA IIC T4 and Ex nA IIC T4 hazardous locations; and nonhazardous locations only. Follow these guidelines if you are installing the NI 9403 in a potentially explosive environment. Not following these guidelines may result in serious injury or death.
Caution Do not disconnect I/O-side wires or
connectors unless power has been switched off or the area is known to be nonhazardous.
4 | ni.com | NI 9403 Getting Started Guide
Caution Do not remove modules unless power has
been switched off or the area is known to be nonhazardous.
Caution Substitution of components may impair
suitability for Class I, Division 2.
Caution For Division 2 and Zone 2 applications,
install the system in an enclosure rated to at least IP54 as defined by IEC/EN 60079-15.
Caution For Division 2 and Zone 2 applications,
connected signals must be within the following limits.
Capacitance 0.02 μF max

Special Conditions for Hazardous Locations Use in Europe and Internationally

The NI 9403 has been evaluated as Ex nA IIC T4 Gc equipment under DEMKO Certificate No. 07 ATEX 0626664X and is IECEx UL 14.0089X certified. Each NI 9403 is marked II 3G and is suitable for use in Zone 2 hazardous locations, in ambient temperatures of -40 °C ≤ Ta ≤ 70 °C. If you are using the NI 9403 in Gas Group IIC hazardous locations, you must use the device in