NATIONAL CONTROLS Z6T-00010-061 User Manual

Repeat Cycle
On Of
f
On Of
f
Input V
oltage
Relay Coi
l
Repeat Cycle Functio
n
Adj. "On" Delay
Adj. "Off" Delay
Z6T-180/5-001
N.C.
N.0.
COM
N.C.
N.0.
COM
L1L2
3.50
2.00
3.00
1.50
INPUT
VOLTAGE
CLEARANCE FOR #6 SCREW
(4 PL.)
.250
.250 X .031 MALE 'FAST-ON'
(8 PL.)
3310/12/92
"ON" DELAY
ADJUSTMENT
INCINC
R
Z6T-180/5-001
ADJUSTMENT
"OFF" DELAY
- +
Polarity shown for DC models
.27
1.875
Z6 Series
TIME DELAY RELAYS
1-31
FEATURES
100% functionally tested
Digital timing circuit
±1% repeatability
Individually adjustable ON and OFF
times Components protected by conformal
coating Low cost, open board construction
Superior transient protection
Fiberglass reinforced circuit board
Trimpot on-board with sealed cermet
element
Operating Logic: Upon application of volt age to the input terminals, the OFF delay is initiated. At the end of the OFF preset time, the relay coil is activated and the ON delay starts. At the end of the ON preset time, the relay coil is deactivated and a new cycle begins. The ON and OFF cycles will contin ue to alternate until voltage is removed.
LOGIC FUNCTION DIAGRAM
File #E59090
SPECIFICATIONS
TIME DELAY
Adjustment: Trimpot, factory fixed on special
order (min. order required)
Range: .1 to 10 sec. Repeatability: ±1% at constant temperature Accuracy:
Maximum time -0%, +10% Minimum time +0%, -50%
Reset Time: 500 ms max.
INPUT
Operating Voltage: 120 VAC ±10% Power Consumption: 3 VA max. Frequency: 50/60 Hz
OUTPUT
Type: Relay DPDT (2 form C) Rating: 10 A max. resistive at 240 VAC; 100 mA
at 5 VDC min. load current
-
Life: Mechanical: 10,000,000 operations Full Load: 500,000 operations
PROTECTION
Transient Voltage: Timers are protected by a 30
joule metal oxide varistor Dielectric Breakdown: 1500 V RMS min. at
-
60 Hz between input and outputs and between outputs
MECHANICAL
Termination: .25” x .032” male fast-on terminals Mounting: .25” standoffs, #6 screw
ENVIRONMENTAL
Storage Temperature: -23°C to 70°C Operating Temperature: -23°C to 55°C
ORDERING INFORMATION
AMETEK National Controls Corp. • 1725 Western Drive • West Chicago, Illinois 60185 • Tel: 800-323-2593 • 630-231-5900 • FAX: 630-231-1377 • www.nationalcontrols.com
TIME RANGE 120 VAC
.1 to 10 sec. Z6T-00010-061
Consult factory for any special requirements not listed in catalog (minimum order requirement may apply).